NJTA Design Manual Section 2 Structures Design
NJTA Design Manual Section 2 Structures Design
NJTA Design Manual Section 2 Structures Design
SECTION 2
STRUCTURES DESIGN
Table of Contents
Page No
2.1 GENERAL...................................................................................................................1
2.2 BRIDGES ....................................................................................................................1
2.2.1 DESIGN SPECIFICATIONS ...................................................................................1
2.2.2 MODIFICATIONS TO CURRENT CODES ................................................................3
2.2.3 MATERIALS .......................................................................................................7
2.2.3.1 Structural Steel............................................................................................. 7
2.2.3.2 Concrete....................................................................................................... 8
2.2.3.3 Reinforcement Steel..................................................................................... 8
2.2.4 SUPERSTRUCTURE DESIGN ...............................................................................8
2.2.4.1 Stringers and Beams.................................................................................... 8
2.2.4.2 Deck Slabs ................................................................................................. 11
2.2.4.3 Bearings ..................................................................................................... 19
2.2.5 SUBSTRUCTURE DESIGN .................................................................................22
2.2.5.1 Piers ........................................................................................................... 22
2.2.5.2 Abutments .................................................................................................. 23
2.2.5.3 Scour Design.............................................................................................. 24
2.2.6 DESIGN FOR SEISMIC EVENTS .........................................................................25
2.2.6.1 Design Specifications................................................................................. 25
2.2.6.2 General Considerations ............................................................................. 25
2.2.6.3 Design Requirements................................................................................. 26
2.2.6.4 Retrofit Requirements ................................................................................ 27
2.2.6.5 References ................................................................................................. 28
2.2.7 COMPUTER SOFTWARE ...................................................................................28
2.2.7.1 Guidelines on Use ...................................................................................... 28
2.2.7.2 Commercial Structural Programs ............................................................... 29
2.2.8 PERMITS .........................................................................................................31
2.3 RETAINING WALLS.................................................................................................31
2.3.1 EARTH RETAINING STRUCTURES......................................................................31
2.3.2 ALTERNATE / PROPRIETARY RETAINING WALLS ................................................33
2.4 CULVERTS ...............................................................................................................34
2.5 SIGN SUPPORTS.....................................................................................................34
2.5.1 GENERAL DESIGN CRITERIA ............................................................................35
2.5.2 OVERHEAD SIGN STRUCTURE DESIGN .............................................................40
MAY 2007
NJTA Design Manual Structures Design
MAY 2007
NJTA Design Manual Structures Design
List of Exhibits
Page No
Exhibit 2 - 1 One Course Bridge Deck Slabs .......................................................................12
Exhibit 2 - 2 Two Course Bridge Deck Slabs .......................................................................13
Exhibit 2 - 3 Reconstruction of Surfaced Decks (Surfacing 2 inches thick or less).............14
Exhibit 2 - 4 Reconstruction of Surfaced Decks (Surfacing up to 4 inches thick) ...............15
Exhibit 2 - 5 Reconstruction of Surfaced Decks (Surfacing up to 6 inches thick) ...............16
Exhibit 2 - 6 Reconstruction of Bare Concrete Decks ..........................................................17
SERIES 100 – BRIDGE DECK GEOMETRY........................................................................67
Exhibit 2 - 100 Turnpike Bridge Deck Geometry Mainline – 1 .............................................67
Exhibit 2 - 101 Turnpike Bridge Deck Geometry Mainline – 2 .............................................68
Exhibit 2 - 102 Turnpike Bridge Deck Geometry Mainline – 3 .............................................69
Exhibit 2 - 103 Turnpike Bridge Deck Geometry Ramps – 1 ...............................................70
Exhibit 2 - 104 Turnpike Bridge Deck Geometry Ramps – 2 ...............................................71
Exhibit 2 - 105 Turnpike Bridge Deck Geometry Ramps – 3 ...............................................72
Exhibit 2 - 106 Turnpike Bridge Deck Geometry Ramps – 4 ...............................................73
Exhibit 2 - 107 Turnpike Bridge Deck Geometry Ramps – 5 ...............................................74
Exhibit 2 - 108 Parkway Bridge Deck Geometry Mainline – 1..............................................75
Exhibit 2 - 109 Parkway Bridge Deck Geometry Mainline – 2..............................................76
Exhibit 2 - 110 Parkway Bridge Deck Geometry Mainline – 3 .............................................77
Exhibit 2 - 111 Parkway Bridge Deck Geometry Ramps – 1................................................78
SERIES 200 – SUBSTRUCTURE DETAILS ........................................................................79
Exhibit 2 - 200 Substructure Details – 1...............................................................................79
Exhibit 2 - 201 Substructure Details – 2...............................................................................80
Exhibit 2 - 202 Substructure Details – 3...............................................................................81
Exhibit 2 - 203 Substructure Details – 4...............................................................................82
Exhibit 2 - 204 Substructure Details – 5...............................................................................83
Exhibit 2 - 205 Substructure Details – 6...............................................................................84
Exhibit 2 - 206 Substructure Details – 7...............................................................................85
Exhibit 2 - 207 Substructure Details – 8...............................................................................86
Exhibit 2 - 208 Substructure Details – 9...............................................................................87
Exhibit 2 - 209 Substructure Details – 10.............................................................................88
Exhibit 2 - 210 Substructure Details – 11.............................................................................89
Exhibit 2 - 211 Substructure Details – 12.............................................................................90
Exhibit 2 - 212 Substructure Details – 13.............................................................................91
MAY 2007
NJTA Design Manual Structures Design
MAY 2007
NJTA Design Manual Structures Design
SECTION 2
STRUCTURES DESIGN
2.1 GENERAL
This Section of the Authorities Design Manual provides guidance, policies, standard
practice and procedures for the development of bridge and/or structure projects.
One of the primary goals of this Section is to provide assistance to Engineers to
ensure that bridges constructed for the Authority are highly durable and economical.
Although this Section provides guidance on design procedure, it does not preclude
the need for a complete analysis and design to produce a safe, economical and
maintainable structure.
2.2 BRIDGES
2.2.1 Design Specifications
Except as modified below, the design of all highway bridges shall be
governed by the latest edition of the American Association of State Highway
and Transportation Officials (AASHTO) LRFD Bridge Design Specifications
and all current Interim Specifications issued by the Association (referred to as
the AASHTO LRFD Specification).
The AASHTO LRFD bridge design philosophy dictates that bridges are
designed for specified limit states to achieve constructability, safety and
serviceability goals, while still achieving desired economy, aesthetics and
inspectability. The four main limit states are as follows:
The Service Limit State limits stresses, deformations and crack widths
under normal service conditions.
The Fatigue and Fracture Limit State limits the allowable fatigue stress
range for anticipated stress cycles to control crack initiation and propagation
and to prevent fracture during the design life of the bridge.
The Strength Limit State ensures the bridge has the appropriate strength
and stability required to maintain its structural integrity under the load
combinations that it is expected to experience during its design life.
The Extreme Event Limit States ensure that the bridge is proportioned to
resist collapse due to unique occurrences such as earthquake, vessel
collision, flood etc.
The following basic equation is the basis of LRFD methodology and must be
satisfied for each Limit State:
Bridges constructed to carry railways shall conform to the latest edition of the
Manual for Railway Engineering published by the American Railway
For local roads and State highways over Authority facilities, the jurisdiction for
structural maintenance shall be confirmed during Phase A. For local roads
and State highways that fall under the Authority’s maintenance jurisdiction,
the Authority’s Design Manual shall be followed for the bridges structural
integrity. The geometric requirements for these local and State Highways
shall conform to the requirements of the applicable agencies. For local roads
and State highways that fall under the maintenance jurisdiction of other
agencies, the current design standards of the applicable agencies shall be
followed.
12’ 4’ 4’ 21’ 4’ 4’ 4’
16k 16 28 28 28 28 28 28
The permit vehicle shall occupy one design lane with all remaining design
lanes occupied by the HL-93 design vehicle.
Low relaxation strands shall be used and accounted for in the design of
prestressed concrete beams.
For service load combinations that involve traffic loading, tension stresses in
members with bonded or unbonded prestressing tendons should be
investigated using Load Combination Service III and the tension in the
precompressed tensile zone shall be zero. Stress Limit limitations stated in
AASHTO LRFD Specification Table 5.9.4.2.2-1 shall be accounted for in the
permit vehicle check.
The minimum clear cover for all reinforcement shall be two inches except as
given below:
These instructions shall apply unless it is known that the construction method
will be such as to make them inappropriate.
2.2.3 Materials
2.2.3.1 Structural Steel
Structural steel shall comply with AASHTO M270, Grade 50W (ASTM
A709, Grade 50W) unless otherwise approved by the Authority’s
Engineering Department. Hybrid designs incorporating Grade
HPS70W, in bottom flanges and negative moment top flanges with
conventional Grade 50W Steel in positive moment top flanges and all
webs, should be evaluated on a case by case basis to economize
structural steel designs.
2.2.3.2 Concrete
Concrete for use in deck slabs for new bridges, widenings and major
deck reconstruction shall be High Performance Concrete (HPC) with a
minimum compressive strength (f’c) of 4,400 psi unless otherwise
directed by the Authority’s Engineering Department. The concrete
strength used for deck slab design using HPC shall be 4,000 psi.
Concrete for use in precast prestressed slabs, box beams and girders
shall have a minimum compressive strength at 28 days of 5,000 psi.
Higher strengths may be used, if required by the design, where this
can be justified on grounds of economy. The required minimum
concrete compressive strength at the time of application of the
prestress force (f’ci) shall be computed and shown on the plans to the
nearest 100 psi and shall not normally be less than 0.8 (f’c).
The value of the concrete strength (f’c) to be used for the design of
reinforced concrete using Class A, B or C concrete shall be 500 psi
less than the specified minimum compressive strength except for deck
slabs using high performance concrete.
2. Composite Construction
Steel or precast prestressed concrete beams with a concrete deck
slab shall normally be designed as composite structures,
assuming that no temporary supports will be provided for the
beams or girder during the placement of the permanent dead load.
3. Curved Stringers
In general, outer stringers shall be curved in plan to match the
curvature of the bridge fascia unless the mid-ordinate of the curve
is so small that the curvature can be accommodated within the
normal slab overhang and the resulting appearance of the fascia
is not aesthetically objectionable.
5. Welded Details
Certain miscellaneous details - supports for screed rails and
reinforcement, steel deck forms, connection plates, gussets, etc. -
shall normally not be welded to members or parts subject to
tensile stress. At locations where welding cannot be avoided, the
maximum live load stress range at the point of attachment shall be
checked in accordance with AASHTO LRFD Specification Section
6.6. The plans shall show clearly the flange areas where no
welding is permitted.
6. Splices
For span lengths between 120 ft and 150 ft, an optional field splice
shall be permitted, preferably located between the 1/3 and outer ¼
points of the span (near dead load contraflexure points for
continuous spans). For spans in excess of 150 ft, optional field
splices shall be located between each of the 1/3 and outer ¼
points.
7. End Diaphragms
End diaphragms and their connections shall be designed for the
effect of wheel loads which they may be required to support, for
the effect of transverse movement due to thermal, wind or seismic
forces and for jacking loads required for future bearing
replacement. The diaphragms and their connections shall be
designed to resist the forces listed above in appropriate
combinations.
8. Depth of Stringers
Stringers, beams and girders shall generally be of uniform depth
for the full length of the structure, except where changes in depth
are absolutely necessary to meet underclearance requirements or
where a change in depth is desirable to enhance the appearance
of the structure. Changes in depth shall not normally be made in
MAY 2007 2 - 10
NJTA Design Manual Structures Design
The following deck designs shall be used for all bridges that are
owned and/or maintained by the Authority, as noted in Subsection
2.2.1:
MAY 2007 2 - 11
NJTA Design Manual Structures Design
EXHIBIT 2 - 1
ONE COURSE BRIDGE DECK SLABS
(NO NOISEWALL)
NEW BRIDGES AND MAJOR RECONSTRUCTION
1st COURSE
MAXIMUM TRANSVERSE
SLAB ADDITIONAL LONGITUDINAL
EFFECTIVE REINFORCEMENT
SLAB SPAN (S) THICKNESS REINFORCEMENT REINFORCEMENT
OVERHANG (TOP AND
(without an IN OVERHANG IN BOTTOM
LENGTH BOTTOM)
overlay)
Slab Span (S) is defined as the distance from beam centerline to beam centerline.
MAY 2007 2 - 12
NJTA Design Manual Structures Design
EXHIBIT 2 - 2
TWO COURSE BRIDGE DECK SLABS
(NO NOISEWALL)
NEW BRIDGES AND MAJOR RECONSTRUCTION
1st COURSE
MAXIMUM TRANSVERSE
SLAB ADDITIONAL LONGITUDINAL
EFFECTIVE REINFORCEMENT
SLAB SPAN (S) THICKNESS REINFORCEMENT REINFORCEMENT
OVERHAN (TOP AND
(without IN OVERHANG IN BOTTOM
G LENGTH BOTTOM)
overlay)
4'-0" to 6'-6" 2.50 ft. 7 ¼” #5 @ 7” #6 @ 7” #5 @ 10”
>6'-6" to 7'-6" 3.00 ft 7 ¼” #5 @ 6 #5 @ 6” #5 @ 8”
>7'-6" to 8'-3" 3.33 ft 7 ½” #5 @ 5 ½” #5 @ 5 ½” #5 @ 8”
>8'-3" to 8'-9" 3.75 ft 7 ¾” #5 @ 5 ½” #6 @ 5 ½” #5 @ 8”
>8'-9" to 9'-3" 4.00 ft 8” #5 @ 5 ½” #6 @ 5 ½” #5 @ 8”
>9'-3" to 9'-9" 4.00 ft 8 ¼” #5 @ 5 ½” #6 @ 5 ½” #5 @ 8”
>9'-9" to 10'-6" 4.00 ft 8 ½” #6 @ 7” #5 @ 7” #5 @ 7”
>10'-6" to 11'-3" 4.00 ft 8 ¾” #6 @ 6” #5 @ 6” #5 @ 6”
>11'-3" to 12'-0" 4.00 ft 9” #6 @ 5 ½” #4 @ 5 ½” #5 @ 6”
Slab Span (S) is defined as the distance from beam centerline to beam centerline.
MAY 2007 2 - 13
NJTA Design Manual Structures Design
EXHIBIT 2 - 3
RECONSTRUCTION OF SURFACED DECKS
(SURFACING 2 INCHES THICK OR LESS)
REINFORCING STEEL MAXIMUM ALLOWABLE EFFECTIVE SLAB SPAN - FEET
TRANSVERSE LONGITUDINAL 8.00" 8.50" 9.00" 9.50" 10.00" 10.50" 11.00"
TOP & BOT BOTTOM SLAB SLAB SLAB SLAB SLAB SLAB SLAB
Effective Slab Span as established in accordance with Section 8.1.1 of AASHTO Standard Specifications
MAY 2007 2 - 14
NJTA Design Manual Structures Design
EXHIBIT 2 - 4
RECONSTRUCTION OF SURFACED DECKS
(SURFACING UP TO 4 INCHES THICK)
REINFORCING STEEL MAXIMUM ALLOWABLE EFFECTIVE SLAB SPAN - FEET
TRANSVERSE LONGITUDINAL 8.00" 8.50" 9.00" 9.50" 10.00" 10.50" 11.00"
TOP & BOT BOTTOM SLAB SLAB SLAB SLAB SLAB SLAB SLAB
Effective Slab Span as established in accordance with Section 8.1.1 of AASHTO Standard Specifications
MAY 2007 2 - 15
NJTA Design Manual Structures Design
EXHIBIT 2 - 5
RECONSTRUCTION OF SURFACED DECKS
(SURFACING UP TO 6 INCHES THICK)
REINFORCING STEEL MAXIMUM ALLOWABLE EFFECTIVE SLAB SPAN - FEET
TRANSVERSE LONGITUDINAL 8.00" 8.50" 9.00" 9.50" 10.00" 10.50" 11.00"
TOP & BOT BOTTOM SLAB SLAB SLAB SLAB SLAB SLAB SLAB
Effective Slab Span as established in accordance with Section 8.1.1 of AASHTO Standard Specifications
MAY 2007 2 - 16
NJTA Design Manual Structures Design
EXHIBIT 2 - 6
RECONSTRUCTION OF BARE CONCRETE DECKS
REINFORCING STEEL MAXIMUM ALLOWABLE EFFECTIVE SLAB SPAN - FEET
TRANSVERSE LONGITUDINAL 8.00" 8.50" 9.00" 9.50" 10.00" 10.50" 11.00"
TOP & BOT BOTTOM SLAB SLAB SLAB SLAB SLAB SLAB SLAB
Effective Slab Span as established in accordance with Section 8.1.1 of AASHTO Standard Specifications
2. Reinforcement
For deck slab designs, the Authority’s standard shall be epoxy
coated reinforcing steel. On a case-by-case basis, however, the
Authority may consider other corrosion resistant reinforcing steel
to replace epoxy coated reinforcement or to use as an alternative
bid item.
MAY 2007 2 - 17
NJTA Design Manual Structures Design
The quantity of 7/8” diameter plain bars, weld metal, angles and
any other supports for reinforcement steel - such as chairs,
bolsters, etc. used to support the deck reinforcement on the
stringers/beams will not be measured for payment.
3. Concrete Haunch
Where concrete slabs are supported on steel or precast concrete
stringers, girders or other beams, the bottom of the concrete slab
shall be positioned above the top of the supporting beam so as to
provide a concrete haunch. The haunch shall be made deep
enough to ensure that the concrete slab can be constructed to the
nominal depth shown on the plans and with its top surface at the
required profile, without any decrease in slab depth over the beam
due to construction tolerances, variation in beam depth, variation
in camber, deflection of the beams or other causes. The
dimension from the top surface of the slab to the top of the beam
shall not be less than the nominal slab plus one-inch. The top of
the beam shall normally be set so as to provide the minimum
haunch depth over the thickest flange plate, except that for
continuous girders, the haunch may be reduced over the interior
support where the variability of the elevation of the top of the
beam may be expected to be less. Where field splices in the
stringers are shown on the plans, or permitted by the
Specifications, the haunch shall be a minimum depth of one-inch
over the splice plate. Bolt heads may project into the haunch, but
one-inch minimum of clear cover shall be maintained between the
main steel reinforcement and the bolts.
5. Slab Corners
The reinforcing of the acute corners of skewed slabs shall be
given special consideration. In these areas, it may be necessary
to place the main reinforcement in a fanned arrangement
extending into the corner and dropping the permanent steel bridge
MAY 2007 2 - 18
NJTA Design Manual Structures Design
2.2.4.3 Bearings
1. Standard Drawing Types:
Standard bearing designs have been made for Elastomeric Bearings
and Pot Bearings and are detailed on Standard Drawing Nos. BR-10
to BR-12.
Section 14.7.5.2
Replace the first sentence of the first paragraph with the following:
“The elastomer shall have a specified shear modulus between 0.095
and 0.150 ksi.
MAY 2007 2 - 19
NJTA Design Manual Structures Design
Pertinent References:
a. AASHTO LRFD Bridge Design Specification, 3rd Edition
b. AASHTO Standard Specifications for Highway Bridges, 17th
Edition
c. Guide Specifications for Seismic Isolation Design, 1999 including
2000 interims
d. Stanton, J.F., et al. Stability of Laminated Elastomeric Bearings,
ASCE Journal of Engineering Mechanics, Vol. 116, No. 6, June
1990.
MAY 2007 2 - 20
NJTA Design Manual Structures Design
Bearing Properties:
t = 0.25 in δ
T = 2.5 in δ δ
L = 10 in
W = 17 in
δ = 0.5 in
L–2δ = 9 in δ
W–2δ = 16 in
Shear Modulus, G = 100 psi
Bearing Force, P = 175 kips
I = 972 in4
Ar = 144 in2
Ar
Net shape factor: S=
2((L − 2δ ) + (W − 2δ ))t
S = 11.5
Consider average compressive stress due to the total dead load and
live load.
G
σ TL ≤ .
h
3.84 rt
L 2.67
−
⎛ L ⎞
S (S + 2 )⎜1 +
L
S 1+ 2 ⎟
W ⎝ 4W ⎠
MAY 2007 2 - 21
NJTA Design Manual Structures Design
G
σ TL ≤ ,
kh
1.92 rt
L − 1.33
⎛ L ⎞
S (S + 2 )⎜1 +
L
S 1+ 2 ⎟
W ⎝ 4W ⎠
2 G
σ TL ≤
3 hrt
3.84
L − 2δ − 2.67
L − 2δ ⎛ L − 2δ ⎞
S 1+ 2 S (S + 2 )⎜⎜1 + ⎟⎟
W − 2δ ⎝ 4(W − 2δ ) ⎠
G
or σ TL ≤ .
hrt
5.76
L − 2δ − 4.00
L − 2δ ⎛ L − 2δ ⎞
S 1+ 2 S (S + 2 )⎜⎜1 + ⎟⎟
W − 2δ ⎝ 4(W − 2δ ) ⎠
P
σ TL =
Ar
MAY 2007 2 - 22
NJTA Design Manual Structures Design
3. Footings
Frame piers shall generally be designed with a continuous footing
supporting all the shafts, except that piers founded on rock or piles
may have individual footings for each shaft. The footing width of
piers founded on soil shall be at least one-third of the height (from
bottom of footing to top of cap beam) and for piers founded on
rock or unyielding soil shall be at least one-fourth the height. Soils
with a bearing capacity of at least three tons per square foot may
be considered unyielding. If piles are used, the distance between
the outer rows shall be not less than one-fourth the height of the
pier.
2.2.5.2 Abutments
1. Design Criteria
The AASHTO LRFD Specification as modified herein shall govern
the design of the abutment’s structural concrete and foundation.
2. Approach Slabs
Approach slabs shall be provided for all abutments and shall be
constructed for the full width of the roadway including shoulders.
Two conditions of support for the approach slab shall be
considered in the design of the abutment.
a. The “as-constructed” condition where the approach slab is
supported by the fill as a surcharge load.
b. The condition where the soil does not provide any support for
the approach slab immediately adjacent to the abutment and
the slab spans as a beam from the backwall to the soil. The
span of the slab shall be assumed to be 25 feet.
MAY 2007 2 - 23
NJTA Design Manual Structures Design
3. Construction Condition
Abutments shall be designed for a construction condition where
the earth fill is fully placed before the superstructure is erected.
The design for this condition shall include a surcharge load for
construction equipment. For this condition, the resistance factors
may be increased by 25%.
MAY 2007 2 - 24
NJTA Design Manual Structures Design
http://earthquake.usgs.gov/research/hazmaps/interactive/index.php.
MAY 2007 2 - 25
NJTA Design Manual Structures Design
For the design of local road bridges over the Turnpike, including State
and Federal highways, the design shall be based on the lesser of the
two events, unless the owner has a published policy which requires
otherwise.
For the design of certain special bridges which the Authority deems to
be “critical”, the design shall be based on a performance objective of
MAY 2007 2 - 26
NJTA Design Manual Structures Design
Bridges that are single span, bridges with less than 50,000 square ft
in deck area, or bridges with an overall length less than 1,000 linear
feet shall be designed using the NEHRP response spectra. Bridges
with a deck area exceeding 50,000 square ft or an overall length
exceeding 1,000 linear feet shall require a site-specific evaluation.
For both the FEE and SEE objectives, the Seismic Zone at the site
shall be defined according to Table 3.10.4-1 in the AASHTO LRFD
Bridge Design Specifications except the value of “A” shall be taken as
the peak ground acceleration (PGA) from the 2002 USGS maps for
the 2,500-year event at the site.
http://isddc.dot.gov/olpfiles/FHWA/010433.pdf
MAY 2007 2 - 27
NJTA Design Manual Structures Design
Bridges that are single span, bridges with less than 50,000 square ft
in deck area, or bridges with an overall length less than 1,000 linear
feet shall be retrofitted to resist the 10% in 50 year probability event
(return period of approximately 500 years) using the formulation of the
NEHRP response spectra described above for the FEE performance
level in Design Requirements above.
For both the FEE and SEE performance levels, the Seismic
Performance Category (SPC) at the site shall be defined according to
Table 1 in the FHWA Seismic Retrofitting Manual except the value of
“A” shall be taken as the PGA from the 2002 USGS maps for the
2,500-year event at the site.
2.2.6.5 References
Building Seismic Safety Council, 2003a, NEHRP Recommended
Provisions for Seismic Regulations for New Buildings and Other
Structures, Part 1: Provisions, 2003 Edition, FEMA 450, Washington,
D.C.
MAY 2007 2 - 28
NJTA Design Manual Structures Design
PENNDOT Programs:
MAY 2007 2 - 29
NJTA Design Manual Structures Design
MAY 2007 2 - 30
NJTA Design Manual Structures Design
2.2.8 Permits
For permit requirements to be considered during design, reference is made to
the Authority’s Procedure Manual. The following information is provided for
general guidance.
MAY 2007 2 - 31
NJTA Design Manual Structures Design
c. For structures founded on soil, the resultant of all the forces acting on
the structure above its base shall intersect the base within the middle
half. For structures founded on rock, the resultant shall intersect the
base within the middle three-fourths. No uplift shall be permitted on
piles except under seismic loadings.
d. The loads on the rear piles of abutments and retaining walls shall be
computed with the horizontal forces from the soil reduced to 75
percent of the maximum values. The pile resistance load shall not be
exceeded for this condition.
f. The passive resistance of the soil in front of the structure shall not be
considered as resisting either the horizontal forces caused by the
earth pressure or the bending moments in the stem due to those
factors.
2. Wall Thickness
The minimum thickness of any cast-in-place concrete wall shall be 12
inches for walls up to 10 feet high, 15 inches for walls up to 14 feet high,
and 18 inches thick for walls higher than 14 feet. Low walls should be
designed with a vertical rear face and higher walls should be battered,
with a rear face batter of not less than 1 in 12. Battered faces shall
(where possible) be plane, and changes in batter shall be avoided.
MAY 2007 2 - 32
NJTA Design Manual Structures Design
3. Backfill
The backfill behind abutments and walls shall consist of a layer of Porous
Fill which shall be a minimum of five feet wide, and shall be adequately
drained at its base to prevent the build up of water pressure at the back of
the structure.
4. The Sample Plans and Exhibits 2-500 Series of this Manual may be
referred to for guidance in providing for proprietary wall presentations.
The following guidance shall also be followed:
For MSE wall systems that are located adjacent to roadways that may
be chemically deiced, a high density polyethylene geo-membrane
shall be placed below the pavement and just above the first row of
reinforcements to intercept any flows that may contain the deicing
chemicals. The membrane shall be sloped to drain away from the
MAY 2007 2 - 33
NJTA Design Manual Structures Design
2.4 CULVERTS
Culverts shall be constructed as box culverts or 3-sided rigid frames with reinforced
concrete Class “B”. As a minimum, culverts shall be of sufficient length so that the
full roadway section, including shoulders and berms, can be maintained. Footings
for culvert wingwalls shall either be placed at the same time as the culvert floor slab
or shall be adequately keyed and doweled into it. Toe walls shall be provided along
the edge of culvert floor slabs or apron slabs.
Precast culverts shall be permitted and the design shall conform to either the
AASHTO LRFD Specification or the AASHTO Standard Specification for Highway
Bridges. Engineers shall contact precast manufacturers during the design to discuss
project specific design requirements and details to ensure there will be no conflicts
during the construction phase. Precast culverts shall not be used when the top slab
is to be used as a riding surface.
1. Ground Mounted
Small Highway Signs (<50 square feet)
Large Highway Signs (≥50 square feet)
MAY 2007 2 - 34
NJTA Design Manual Structures Design
1. Ground Mounted
a. Small Highway Signs (<50 square feet)
Should the Engineer feel that if any of the standard signs or any other
small signs which are to be erected on a 4” aluminum tubular post are
considered to be in an area subject to frequent impact from vehicles, it
should be proposed to the Authority’s Engineering Department that
these signs be erected on multiple galvanized steel wing channel
posts or another type of support.
MAY 2007 2 - 35
NJTA Design Manual Structures Design
the horizontal stringers, which hold the sheet sections together, within
allowable limits, limiting panel sizes are shown on Standard Drawing
SI-25 for either 2, 3 or 4 post mounting systems. To assist the
Engineer in determining the proper size and number of posts to use
on any particular ground mounted installation, the chart on Standard
Drawing SI-25 has been provided. The intersection of a sign panel’s
height and width will fall within an area which will indicate whether 2,
3, or 4 supports are required. On this drawing there is a series of
diagrams which show the proper spacing of the posts along the width
of the panel expressed as decimal fractions of the panel width.
Once the number of posts required to support the panel has been
determined, the Engineer shall calculate “h”. This dimension “h” is the
height of the longest post used on that installation. It is measured
from the middle of the sign panel to ground level, and is rounded off to
the next 2-foot increment. In determining “h”, the Engineer shall
assume that the ground outside of the berm area slopes 1 foot
vertically for every 2 feet horizontally, unless there is information
available to substantiate using a flatter or a steeper side slope. It is
desirable to provide posts of sufficient length to insure flush ground
mounting.
Having the values of “h” and the area of the sign panel, the Engineer
can then use the charts on Standard Drawing SI-25 for determining
the post diameter to be used on that installation. The post size to be
used will be indicated by the curve (properly selected as to required
numbers of posts) which lies just above the intersection of “A” and “h”.
The post size indicated on that curve shall be the outside diameter
and wall thickness of all tubular supports for that installation. In some
instances, especially where large diameter and or heavy wall
thicknesses are indicated for a particular installation, consideration
should be given to the use of an additional post, whereby a tube of
smaller diameter and thickness of wall may be utilized.
On any ground mounted sign installation which will have two sign
panels, one mounted above the other, the length of “h” shall be
computed to the centerline of the combination, including the space
separating the two panels. The area to be used when determining the
post size shall be the total area of the two panels.
MAY 2007 2 - 36
NJTA Design Manual Structures Design
For sign areas greater than 50 sq. ft. and less than 100 sq. ft. timber
posts shall be used in accordance with Exhibit 2-402. Having the
values of “H” and “W” of the sign panel, the Engineer can than use the
tables for determining the number of posts, size of the posts, as well
as the depth of post embedment.
For sign areas greater than 100 sq. ft., timber poles shall be used in
accordance with Exhibit 2-403. Once the number of poles required to
support the panel has been determined, the Engineer shall calculate
“A”. This dimension “A” is the height of the longest pole used on that
installation. It is measured from the underside of sign panel to ground
level. In determining “A”, the Engineer shall assume that the ground
outside of the berm area slopes 1 foot vertically for every 2 feet
horizontally, unless there is information available to substantiate using
a flatter or a steeper side slope.
Having the values of “H” and “W” of the sign panel, the Engineer can
then use the Tables on Exhibits 2-403 for determining the number of
poles, Class of timber pole as well as the depth and size of foundation
embedments to be used on that installation.
On any ground mounted sign installation which will have two sign
panels, one mounted above the other, the height of “H” shall be taken
as combination of both sign heights, including the space separating
the two panels. The area to be used when determining the post size
shall be the total area of the two panels.
MAY 2007 2 - 37
NJTA Design Manual Structures Design
The Standard Drawings for the span-type sign structures provide two
(2) standard heights of end frames and five (5) standard lengths for
box truss sections. Span lengths from 45 ft. to 135 ft., in increments
of 5 ft., may be obtained by using the standard box truss sections in
appropriate combinations, as indicated on the Standard Drawings.
Sign structure spans shall be set in increments of 5 ft. wherever
possible. Where this is not possible, the standard truss sections shall
be combined with a minimum number of special sections to obtain the
necessary length.
MAY 2007 2 - 38
NJTA Design Manual Structures Design
The length of the trussed cantilever arm is not standardized but shall
be detailed to suit the width of the sign proposed to be mounted on
the arm. The arm shall extend to 6 in. beyond the outer edge of the
sign panel.
MAY 2007 2 - 39
NJTA Design Manual Structures Design
below the bottom edge of the sign. Standard Drawings for Parkway
sign structures are under development. Until the Standard Drawings
are available, the Authority shall provide Engineers with applicable
sign structure details on a project by project basis.
The length of the trussed and simple cantilever arms shall be detailed
to suit the width of the sign proposed to be mounted on the arm. The
arm shall extend to 6 in. beyond the outer edge of the sign panel.
d. Bridge-Mounted Signs
Bridge mounted sign structures are not preferable where a proposed
location for a sign structure falls upon a bridge or viaduct, the
Engineer shall first attempt to move the planned location of the
structure off the bridge. Where this cannot be accomplished, the sign
structure shall either be mounted on one of the bridge substructure
units or on separate foundations carried down to the ground alongside
the bridge. Only as a last resort and only with written approval of the
Authority’s Engineering Department shall the sign structure be
mounted on the bridge superstructure, in which case it shall be
located as close as possible to a bearing. Under no circumstances
may a bridge mounted sign or associated appurtenances extend
below the bottom flange of the fascia beam of the structure to which it
is attached.
MAY 2007 2 - 40
NJTA Design Manual Structures Design
Drawings are available for span-type, cantilever and butterfly sign structures
for the Turnpike roadways, and these designs shall be used wherever
possible within the limits of span and loading noted on the drawings. Where
special designs are necessary, the Engineer shall use components and
details of the standard sign structures to the fullest extent possible.
Structures to be located on the Parkway Roadways shall be designed in
entirety using the criteria contained herein this section. Standard Drawings
for the Parkway sign structures are under development. Until the Standard
Drawings are available, the Authority shall provide Engineers with applicable
sign structure details on a project by project basis.
All foundations for Turnpike and Parkway sign structures shall have the top of
the concrete pedestal, shown as “Elevation A” on Exhibit 2-405 to 2-412 and
Standard Drawings SI-14, SI-,16A&B, SI-17 A&B, SI-18A&B and SI-22 , set
at 4 ft. 0 in. higher than the highest point of the roadway cross section at the
transverse centerline of the structure. The top elevation shall be the same for
both pedestals. Sign structures pedestals may be constructed on three types
of foundations; spread footing, driven pile supported footing, or drilled shafts.
Where spread footings or driven pile supported footings are to be used, the
elevation of sign structure foundations shall be set so that the soil cover over
the top of the footing at the centerline of the stem shall be at least 4 ft.
Where these footings are located in embankment slopes, the minimum cover
at the outside of the footings shall be 2 ft. Where it is deemed appropriate to
found sign structure pedestals on drilled shafts, the bottom of the pedestal
shall be min. 2 ft. below grade.
Foundations for sign structures shall be designed by the Engineer and shall
conform to the details shown on Standard Drawings SI-22 for spread footing
and pile foundations. The dead loads and wind loads defined below may be
used for foundation design of overhead sign structures. The loading
combinations given in the AASHTO Specification, Table 3-1, shall be used for
the design of sign structure foundations. Where foundations are to be
constructed adjacent to existing Turnpike or Parkway pavement, including
shoulders, the width of the foundation shall preferably be that which will not
require the removal of paved shoulders for its construction. When excavation
for a spread footing or pile bearing footing is required adjacent to Turnpike or
Parkway pavement, these excavations shall be protected by steel sheet piling
which shall be left in place. When determining the most cost effective
foundation type, the cost of the sheet piling to remain, if required, shall be
considered by the Engineer.
The maximum allowable soil bearing pressure under sign structure footings
founded in fill shall be 3 ksf under the effects of combinations of gravity and
wind loads, unless soils investigations indicate that a higher bearing pressure
can be safely sustained by the soil. The 3 ksf bearing pressure allowed
under these circumstances shall not be increased as provided for by in Table
3-1 of the AASHTO Specification. In accordance with Sections 5 of both the
Authority’s Procedures Manual and the Design Manual, a soils investigation
shall be conducted for all foundations in existing ground and a Geotechnical
Engineering Report shall be submitted. In areas where the maximum
allowable soils pressure is less than 3 ksf, the footing shall be founded on a
MAY 2007 2 - 41
NJTA Design Manual Structures Design
The stability of the foundation against overturning shall be checked. The ratio
of the overturning moment divided by the righting moment shall be computed
for each principal axis of the foundation. Usually, the directions of the
principal axes of the foundation will be normal to the face of the signs and
parallel to the face of the signs. The sum of the computed ratios in these two
directions shall not exceed two-thirds.
Where footings carry eccentric gravity loads, as will be the case for cantilever
signs, the net vertical force and overturning moment at the centerline of the
footing shall be computed. This computed overturning moment of the gravity
loads shall be added to the overturning moment of the wind loads. The
righting moment of the gravity loads shall be taken about the outer edge of
the footing or the outer row of piles, whichever is applicable. Drilled shaft
foundations, where deemed appropriate, shall consider the above noted
eccentric loads at the top of pedestal elevation where it meets the vertical
centerline of the drilled shaft. The effects of torsion shall be considered in the
foundation design of all butterfly and cantilever structures.
MAY 2007 2 - 42
NJTA Design Manual Structures Design
** Note: These dimensions are the distance from the centroid of the
walkway to the outside face of the truss chord. Where
MAY 2007 2 - 43
NJTA Design Manual Structures Design
** Note: These dimensions are the distance from the centroid of the
walkway to the outside face of the truss chord. Where
walkways are provided with luminaires, 11 lbs. per ft.
should be added from the load given.
The Engineer shall determine the individual loads for all members of
Parkway sign structures. Luminaires, catwalks, and, associated
appurtenances shall not be provided on Parkway sign structures unless
directed otherwise by the Authority.
All Parkway signs structures shall provide adequate under clearance and
design strength to allow for a provisional sign panel height of 18-0”.
For span type structures, the length of this provisional sign panel shall be
no less than 40% of the sign structure span and need not be greater than
80% of the sign structure span, unless required by original design. The
span of the sign structure shall be measured from centerline of end post
to centerline of end post. Under no circumstances shall any span type
sign structure be designed for less than 800 square feet of sign area.
For cantilever and butterfly type sign structures, the provisional sign panel
area shall extend from the outmost point on the cantilevered arm to 2’-0”
from the centerline of the mounting post. Under no circumstances shall
any cantilever type sign structure be designed for less than 300 square
feet of sign area, or any butterfly type of sign structure be designed for
less than 500 square feet of sign area.
All Contract Drawings prepared for Parkway Signs shall have the design
sign area clearly published on the General Plan and Elevation plan sheet.
MAY 2007 2 - 44
NJTA Design Manual Structures Design
The following Loading shall be used for all Turnpike and Parkway Sign
Structure Designs.
Wind Drag Coefficients, Cd, shall be determined in accordance with Table 3.6
of the AASHTO Specification. Where the exact dimensions of a sign panel or
sign structure element cannot be determined, the Engineer shall select the
most conservative Drag Coefficient available for the most appropriate
element type denoted in Table 3-6 of the AASHTO Specification. When
determining the Wind Drag Coefficient for square shaped tubular truss
members, the radius (r) denoted in Table 3-6 of the AASHTO Specification
may be assumed as twice the thickness of the square shaped tubular
member.
The Height and Exposure Factor, KZ, shall be no less than 0.94 for all parts of
the sign structure under normal exposure. Higher values of KZ shall be
considered, in accordance with Table 3-5 of the AASHTO Specification, when
structures are situated in abnormally exposed conditions on high
embankments or on bridge piers or superstructures. The standard designs
have been prepared using a value of KZ of 1.0. The Engineer shall check the
design of the standard sign structures for the particular use intended
wherever it is determined that a higher value of the KZ is appropriate.
MAY 2007 2 - 45
NJTA Design Manual Structures Design
Ice Load
Ice load shall be considered as 3.0 PSF and shall be applied as directed in
Section 3.7 of the AASHTO Specification. For the purposes of placing ice
loading on walkway grating, the horizontal area of the walkway grating shall
be considered as solid with uniform ice loading on the top and bottom
surfaces, only. Given the conservative nature of this loading, additional ice
loading need not be considered on walkway hangers or walkway
appurtenances such as hand railing and luminaires. Where luminaires are
present on structures without walkway grating, ice loading on hangers and
walkway appurtenances shall be considered.
Fatigue Loading
Fatigue loading shall be considered for all span type and cantilever sign
structures. For the purposes of design, the fatigue stress shall be defined as
the stress experienced by the member, or connection detail, when loaded
only with the specific event fatigue load. Dead loads and Ice loads shall not
be considered to act in addition to the specific event fatigue loading. The
Importance Factor for all fatigue wind loads shall be taken as 1.0
Vortex Shedding
Fatigue loading induced by vortex shedding need not be considered for
the design of span type or cantilever/butterfly structures.
MAY 2007 2 - 46
NJTA Design Manual Structures Design
2.6 LIGHTING
All lighting associated with the illumination of sign panels will be discussed in Section
7 of this Manual.
All light poles shall be designed in accordance with the 2001 AASHTO Standard
Specifications for Structural Supports for Highway Signs, Luminaires, and Traffic
Signals. It is noted that this code does not mandate that “common light poles” meet
the fatigue design criteria. The fatigue design criteria, however, will be required for
any “high-level lighting structures” that have a luminaire mounting height greater than
50 feet. Pole and equipment suppliers for roadside “common light pole” shall note
that the Authority will require these structures to meet the fatigue design criteria in
the event that the AASHTO specifications require it. Suppliers shall be responsible
for staying informed of any AASHTO updates that require fatigue design on these
structures.
MAY 2007 2 - 47
NJTA Design Manual Structures Design
The Engineer shall notify the State’s One Call System, identify and verify all
existing utility and fiber-optic conduits in the vicinity of the proposed noise
barrier wall alignment. If any existing facility interferes with the noise barrier,
the Authority’s Engineering Department shall be contacted for possible
relocation of the existing elements or realignment of the noise barrier as
appropriate.
Design criteria for the noise barrier structural components, not specifically
herein addressed, shall conform to applicable Sections of the AASHTO
Standard Specifications for Highway Bridges, with current interims. For new
bridge superstructure components supporting noise barrier, design criteria
shall conform to applicable Sections of the AASHTO LRFD Specifications,
with current interims, as modified by Subsection 2.2. For evaluating existing
bridge superstructure components supporting noise barrier, design criteria
shall conform to applicable Sections of the AASHTO LFD Specifications, with
current interims, as modified by Subsection 2.2.
The Tables listed in the AASHTO Guide Specifications shall be referred to for
determining the design category and the design wind pressure, P, for the
design of noise barriers.
MAY 2007 2 - 48
NJTA Design Manual Structures Design
Notes:
1. Adjoining ground surface shall be defined as the ground elevation (or
water elevation) immediately adjacent to the structure. In situations
where noise barriers are mounted on bridges and retaining walls, the
height to be utilized in determining the design wind pressure, P, shall be
taken from the lowest average ground or water elevation adjacent to the
noise barrier, to the centroid of the loaded area.
2. Cc refers to the combined height, exposure and location coefficient.
Dead Loads
Wind Loads
Seismic Loads
Earth Loads
Traffic Loads
Ice and Snow Loads
Bridge Loads
Seismic Loads
The seismic dead load, EQD, in the following formula shall be computed as
follows:
EQD = A x f x D
f
0.75 Dead load, except on bridges
2.50 Dead load, on bridges
MAY 2007 2 - 49
NJTA Design Manual Structures Design
8.0 Dead load for connections of walls, not cast in place, to bridges
5.0 Dead loads for connections of walls, not cast in place, to retaining
walls
The dead load shall consist of the weight of all the component materials
making up the noise barrier, excluding the foundation. The point of
application of the Seismic Dead Load, EQD, of the individual components
shall be at their respective centers of gravity.
5. When the tops of noise walls have to be stepped, the maximum height of
step should not exceed 2 feet.
MAY 2007 2 - 50
NJTA Design Manual Structures Design
10. Noise barriers shall be designed to retain all anticipated differential fills
plus an additional 2 feet of soil as a minimum.
11. The Phase A Submission for noise barriers shall include a report to
address the possibility of icing, the storage of snow, utilities impact,
drainage, mounting on culverts or bridges and the issues discussed in
Items 4, 5, 6, 7 and 8 above.
3. Access to the back side of the noise barrier should be provided for
inspection, litter control, soil erosion monitoring, grass mowing and
maintenance. In subdivision areas, access may be via local streets,
when available. If access is not available via local streets, access gates
or openings are essential at intervals along the noise barrier. Offset
barriers concealing the access opening must be overlapped a minimum of
4 times the offset distance in order to maintain the integrity of the noise
attenuation of the main barrier. Location of the access openings should
be coordinated with the appropriate agency or landowner.
MAY 2007 2 - 51
NJTA Design Manual Structures Design
3. For noise barrier retrofit onto existing bridges, the noise barrier wall adds
a significant amount of stress on the bridge superstructure caused by the
additional weight and rotational loading for which the existing structure
may not have been originally designed. The Engineer must perform a
complete 3-dimensional analysis of the bridge superstructure, and verify
that the dead, live load and wind load from the wall do not overstress any
component of the bridge including the existing parapets, slab overhang,
girders and superstructure or substructure members. The analysis may
result in need to strengthen the existing superstructure (i.e. installation of
additional full depth diaphragms, girder/stringer cover plates, etc.).
Both the dead load of noise barriers and the wind load on the noise
barriers can affect the overload capacity and deflection of some existing
bridges. The effects of the torsional moments and twist shall be included.
The Engineer must check the change in the load capacity of the bridge
and verify whether the change is acceptable.
MAY 2007 2 - 52
NJTA Design Manual Structures Design
2.7.8 Materials
1. Concrete for cast in place foundations and precast / prestressed posts
and panels shall conform to the Standard Specifications. Class C
concrete shall be used for foundations and Class P concrete shall be
used for precast elements.
2. Reinforcing steel shall conform to ASTM A615, Grade 60, fs =24 ksi.
Welded wire fabric fabricated from deformed wire may be substituted for
reinforcing bars in noise barrier panels only. Refer to the Standard
Specifications for additional criteria concerning the use of welded wire
fabric reinforcement.
If the location of the noise barrier panels may subject the panels to
splashing from the roadway surface, provision of corrosion protected
reinforcement, should be recommended. In such cases, the panels
anticipated to be affected by this splashing should be scheduled for
placement of corrosion protected reinforcement.
MAY 2007 2 - 53
NJTA Design Manual Structures Design
the Controlling Group Load Case and from Section 20, Subsection I.C
shall be applied to the noise barrier and shall be multiplied by a factor of 2
to obtain F, the applied lateral load. The intent of this procedure is to
maintain a factor of safety of 2 against overturning. The allowable
overstresses referenced in the Section 20, Subsection I.B publications
should not be applied to the allowable soil strength.
Sloped soil conditions shall be taken into account when computing the
required embedment length for drilled shaft foundations.
MAY 2007 2 - 54
NJTA Design Manual Structures Design
Due to the unique nature of repair contracts, the Standard Legend Sheet is
not usually applicable; a legend with the special symbols and general notes
pertaining to the specific contract at hand shall be included.
3. North Arrow
6. Drainage facilities
7. Utilities
8. Railroads tracks and right of way lines; each track shall be identified by
the railroad line and branch number and structure number where
applicable.
MAY 2007 2 - 55
NJTA Design Manual Structures Design
When the longitudinal limit of the replacement does not occur over an
existing diaphragm, the Plans shall provide for new intermediate
diaphragms of steel or reinforced concrete to provide edge support for
the replacement slab where it abuts the existing slab.
MAY 2007 2 - 56
NJTA Design Manual Structures Design
1. For each site, a bridge deck plan upon which the anticipated limits
of each replacement are outlined with respect to the lane lines of
the traveled roadways and substructure elements. Each deck
replacement location shall be identified by the lane to be closed in
order to conduct the construction. If the replacement requires a
concrete and debris catch and/or steel protection plates, it shall be
indicated.
3. Diaphragm details
The design of the permanent metal bridge deck forms shall be the
Contractor’s responsibility. Requirements governing the selection,
design and fastening of the forms shall be set forth in the contract
specification. Shop drawings shall be furnished by the Contractor
showing design, details and connections.
The Plans shall show the required staging of construction and traffic
by sectional views which illustrate the available traffic lanes and slab
replacements in each stage. In general, replacement shall be
sequenced such that on bridges carrying mainline roadways of the
Turnpike or Parkway, one lane may be closed for construction but a
minimum of two traffic lanes must be available in every stage in each
direction. For example, the Turnpike’s Hudson County Extension is a
two-lane roadway in each direction. Two traffic lanes must be
MAY 2007 2 - 57
NJTA Design Manual Structures Design
On Turnpike roadways and ramps, lane and shoulder closings for slab
replacement work will be done in accordance with standard
procedures as outlined in the “TP” series of Standard Drawings. Lane
and shoulder closings in interchange areas, ramps and mixing bowl
areas may require special details and arrangements of traffic
protection devices which must be given on the Plans. On Parkway
roadways and ramps, lane and shoulder closings for slab replacement
work will be done in accordance with standard procedures as outlined
in the Garden State Parkway Traffic Manual and MUTCD and details
and arrangements of traffic protection devices must be given on the
Plans.
MAY 2007 2 - 58
NJTA Design Manual Structures Design
MAY 2007 2 - 59
NJTA Design Manual Structures Design
MAY 2007 2 - 60
NJTA Design Manual Structures Design
The original Turnpike bridges were designed and built with bare
concrete decks. In subsequent years, the decks received an overlay
of a waterproofing material and asphalt. In order to maintain the
height of the overlay at deck joints, a thin steel bar was welded to the
top of the joint armoring. The item Pavement Riser Repair consist of
removing and replacing these damaged steel bars atop the joint
armoring. The work is done in conjunction with the reconstruction of
the joint headers.
MAY 2007 2 - 61
NJTA Design Manual Structures Design
Individual items for furnishing all MPT devices will be required when it
has been determined in advance that such devices are not available
from the Authority.
MAY 2007 2 - 62
NJTA Design Manual Structures Design
to east or south to north; for example, Stringer S-4 would be the fourth
stringer, including the fascia stringer, from either the west or south. A few
bridges, Structure Nos. E107.87, E109.83, W107.88 and N2.01, violate this
numbering convention, but on the whole, most bridges have their various
structural elements numbered in this fashion.
In general, the Contractor will install the lane closings and certain
shoulder closings on Turnpike and Parkway roadways and ramps for
miscellaneous repair contracts.
MAY 2007 2 - 63
NJTA Design Manual Structures Design
MAY 2007 2 - 64
NJTA Design Manual Structures Design
QUANTITY
ITEM
ITEM
NO. AS-
PLAN KEY LOCATION DESCRIPTION
BUILT
4 Repair Spalled Concrete- 2 SF A S. Abutment under S-4 on
Abutment Brstw
4 Repair Spalled Concrete- 4 SF B S. Abutment near S-7 on Bkw
Abutment
4 Repair Spalled Concrete- 4 SF E S. Abut top East WW
Abutment
5 Repair Spalled Concrete- 6 SF H P4 E. End Cantilever Faced &
Pier Seat
5 Repair Spalled Concrete- 2 SF AA P14 N Face under S-4 at Top
Pier
8 Epoxy Resin Injection-Pier 10 LF J P4 N Face under S-5 at
Bottom
8 Epoxy Resin Injection-Pier 15 LF BB P15 N Face under S-2 at Top
11 Clean and Resent Rockers- 5 Ea. BB P15 Face under S-2 of Top
Pier
12 Substructure Waterproofing 400 SF DDD N. Abut under S-1 thru S-7
The original design philosophy for drainage on structure was to place inlets in
the gutters uphill of a joint. If the joint can be sealed to prevent runoff from
going through the joint, then some inlets can be eliminated. A gutter flow
analysis should be run in accordance with Section 4 of this Manual to
determine the necessity of the inlets. Inlets that can be eliminated are then
plugged with concrete and the discharge piping removed.
Since the original construction of Turnpike and Parkway structures, the area
underlying the bridge has been developed. Thus, inlets that are air drop may
require piping of the runoff to the ground below and open joints without;
troughs may need to have troughs installed to collect the runoff and funnel it
to an acceptable discharge point.
MAY 2007 2 - 65
NJTA Design Manual Structures Design
prevent snagging and is flexible enough, that under the vibration of the bridge
due to traffic, it provides a constant flushing action to remove debris.
REFERENCES
1. AASHTO LRFD Bridge Design Specifications, 3rd Ed, with 2006 Interims.
2. AASHTO LRFD Bridge Construction Specifications, 2nd Ed, with 2006 Interims
3. AASHTO Guide Manual for Condition Evaluation and Load and Resistance Factor
Rating of Highway Bridges, 1st Ed., with 2005 Interim Revisions.
4. AASHTO Manual for Condition Evaluation of Bridges, 2nd Edition, with 2003 Interims
5. AASHTO Standard Specifications for Highway Bridges, 17th Edition
6. AASHTO Standard Specifications for Structural Supports for Highway Signs,
Luminaires and Traffic Signals, 4th Edition with 2003 Interims
7. AASHTO Guide Specifications for the Structural Design of Sound Barriers, 1st Edition
with 2002 Interims
8. AASHTO/AWS D1.5 Bridge Welding Code
9. Guide Specifications for Seismic Isolation Design, 2nd Edition including 2000 interims
10. Stanton, J.F., et al. Stability of Laminated Elastomeric Bearings, ASCE Journal of
Engineering Mechanics, Vol. 116, No. 6, June 1990.
11. Applied Technology Council, 1997a, NEHRP Guidelines for the Seismic
Rehabilitation of Buildings, FEMA 273, Washington, D.C.
12. Applied Technology Council, 1997b, NEHRP Commentary for the Seismic
Rehabilitation of Buildings, FEMA 274, Washington, D.C.
13. Building Seismic Safety Council, 2003a, NEHRP Recommended Provisions for
Seismic Regulations for New Buildings and Other Structures, Part 1 - Provisions,
2003 Edition, FEMA 450, Washington, D.C.
14. Building Seismic Safety Council, 2003b, NEHRP Recommended Provisions for
Seismic Regulations for New Buildings and Other Structures, Part 2 - Commentary,
2003 Edition, FEMA 450, Washington, D.C.
15. Federal Highway Administration, Seismic Retrofitting Manual for Highway Bridges,
1995 Edition, FHWA-RD-94-052, MacLean, VA.
MAY 2007 2 - 66
NJTA Design Manual Structures Design
EXHIBIT 2 - 100
TURNPIKE BRIDGE DECK GEOMETRY MAINLINE – 1
MAY 2007 2 - 67
NJTA Design Manual Structures Design
EXHIBIT 2 - 101
TURNPIKE BRIDGE DECK GEOMETRY MAINLINE – 2
MAY 2007 2 - 68
NJTA Design Manual Structures Design
EXHIBIT 2 - 102
TURNPIKE BRIDGE DECK GEOMETRY MAINLINE – 3
MAY 2007 2 - 69
NJTA Design Manual Structures Design
EXHIBIT 2 - 103
TURNPIKE BRIDGE DECK GEOMETRY RAMPS – 1
MAY 2007 2 - 70
NJTA Design Manual Structures Design
EXHIBIT 2 - 104
TURNPIKE BRIDGE DECK GEOMETRY RAMPS – 2
MAY 2007 2 - 71
NJTA Design Manual Structures Design
EXHIBIT 2 - 105
TURNPIKE BRIDGE DECK GEOMETRY RAMPS – 3
MAY 2007 2 - 72
NJTA Design Manual Structures Design
EXHIBIT 2 - 106
TURNPIKE BRIDGE DECK GEOMETRY RAMPS – 4
MAY 2007 2 - 73
NJTA Design Manual Structures Design
EXHIBIT 2 - 107
TURNPIKE BRIDGE DECK GEOMETRY RAMPS – 5
MAY 2007 2 - 74
NJTA Design Manual Structures Design
EXHIBIT 2 - 108
PARKWAY BRIDGE DECK GEOMETRY MAINLINE – 1
MAY 2007 2 - 75
NJTA Design Manual Structures Design
EXHIBIT 2 - 109
PARKWAY BRIDGE DECK GEOMETRY MAINLINE – 2
MAY 2007 2 - 76
NJTA Design Manual Structures Design
EXHIBIT 2 - 110
PARKWAY BRIDGE DECK GEOMETRY MAINLINE – 3
MAY 2007 2 - 77
NJTA Design Manual Structures Design
EXHIBIT 2 - 111
PARKWAY BRIDGE DECK GEOMETRY RAMPS – 1
MAY 2007 2 - 78
NJTA Design Manual Structures Design
EXHIBIT 2 - 200
SUBSTRUCTURE DETAILS – 1
MAY 2007 2 - 79
NJTA Design Manual Structures Design
EXHIBIT 2 - 201
SUBSTRUCTURE DETAILS – 2
MAY 2007 2 - 80
NJTA Design Manual Structures Design
EXHIBIT 2 - 202
SUBSTRUCTURE DETAILS – 3
MAY 2007 2 - 81
NJTA Design Manual Structures Design
EXHIBIT 2 - 203
SUBSTRUCTURE DETAILS – 4
MAY 2007 2 - 82
NJTA Design Manual Structures Design
EXHIBIT 2 - 204
SUBSTRUCTURE DETAILS – 5
MAY 2007 2 - 83
NJTA Design Manual Structures Design
EXHIBIT 2 - 205
SUBSTRUCTURE DETAILS – 6
MAY 2007 2 - 84
NJTA Design Manual Structures Design
EXHIBIT 2 - 206
SUBSTRUCTURE DETAILS – 7
MAY 2007 2 - 85
NJTA Design Manual Structures Design
EXHIBIT 2 - 207
SUBSTRUCTURE DETAILS – 8
MAY 2007 2 - 86
NJTA Design Manual Structures Design
EXHIBIT 2 - 208
SUBSTRUCTURE DETAILS – 9
MAY 2007 2 - 87
NJTA Design Manual Structures Design
EXHIBIT 2 - 209
SUBSTRUCTURE DETAILS – 10
MAY 2007 2 - 88
NJTA Design Manual Structures Design
EXHIBIT 2 - 210
SUBSTRUCTURE DETAILS – 11
MAY 2007 2 - 89
NJTA Design Manual Structures Design
EXHIBIT 2 - 211
SUBSTRUCTURE DETAILS – 12
MAY 2007 2 - 90
NJTA Design Manual Structures Design
EXHIBIT 2 - 212
SUBSTRUCTURE DETAILS – 13
MAY 2007 2 - 91
NJTA Design Manual Structures Design
EXHIBIT 2 - 213
SUBSTRUCTURE DETAILS – 14
MAY 2007 2 - 92
NJTA Design Manual Structures Design
EXHIBIT 2 - 214
SUBSTRUCTURE DETAILS – 15
MAY 2007 2 - 93
NJTA Design Manual Structures Design
EXHIBIT 2 - 300
SUPERSTRUCTURE DETAILS – 1
MAY 2007 2 - 94
NJTA Design Manual Structures Design
EXHIBIT 2 - 301
SUPERSTRUCTURE DETAILS – 2
MAY 2007 2 - 95
NJTA Design Manual Structures Design
EXHIBIT 2 - 302
SUPERSTRUCTURE DETAILS – 3
MAY 2007 2 - 96
NJTA Design Manual Structures Design
EXHIBIT 2 - 303
SUPERSTRUCTURE DETAILS – 4
MAY 2007 2 - 97
NJTA Design Manual Structures Design
EXHIBIT 2 - 400
PARKWAY GROUND MOUNTED SIGNS – 1
MAY 2007 2 - 98
NJTA Design Manual Structures Design
EXHIBIT 2 - 401
PARKWAY GROUND MOUNTED SIGNS – 2
MAY 2007 2 - 99
NJTA Design Manual Structures Design
EXHIBIT 2 - 402
PARKWAY GROUND MOUNTED SIGNS – 3
EXHIBIT 2 - 403
PARKWAY GROUND MOUNTED SIGNS – 4
EXHIBIT 2 - 404
OVERHEAD SIGN STRUCTURES NOTES
EXHIBIT 2 - 405
TURNPIKE OVERHEAD SIGN STRUCTURES – 1
EXHIBIT 2 - 406
TURNPIKE OVERHEAD SIGN STRUCTURES – 2
EXHIBIT 2 – 407
TURNPIKE OVERHEAD SIGN STRUCTURES – 3
EXHIBIT 2 - 408
TURNPIKE OVERHEAD SIGN STRUCTURES – 4
EXHIBIT 2 - 409
PARKWAY OVERHEAD SIGN STRUCTURES – 1
EXHIBIT 2 - 410
PARKWAY OVERHEAD SIGN STRUCTURES – 2
EXHIBIT 2 - 411
PARKWAY OVERHEAD SIGN STRUCTURES – 3
EXHIBIT 2 - 412
PARKWAY OVERHEAD SIGN STRUCTURES – 4
EXHIBIT 2 – 413
ANTI-SNAG NOSING DETAILS – 1
EXHIBIT 2 - 414
ANTI-SNAG NOSING DETAILS – 2
EXHIBIT 2 - 500
PROPRIETARY RETAINING WALL DETAILS – 1
EXHIBIT 2 - 501
PROPRIETARY RETAINING WALL DETAILS – 2
EXHIBIT 2 - 502
PROPRIETARY RETAINING WALL DETAILS – 3
EXHIBIT 2 - 503
PROPRIETARY RETAINING WALL DETAILS – 4