MD Yeast TR 13.8kv Oc DT Tr05 Rev0.00

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SAUDI JOOD

Project Substation
CONTRACT NO. 4400005831 YEAST
REPLACEMENT OF PROTECTION IN MADINAH

Transformer Feeder Incomer TR05

Over Current Protection LV SIDE

MLFB IN = 1 A

7 S J 8 0 fN = 60 Hz Tconst. = 80 ms

Current transformer 2400 / 1 A System voltage 13.8 kv

RELAY SETTING

Primary Winding Power = 63.00 MVA


Secondary Winding Power = 63.00 MVA
Tertiary Winding Power = MVA
Transformer Regulation = + 12% to - 12%
Primary Winding Rated Voltage = 116 KV
Primary Winding Voltage at Max Tap = 129.92 KV
Primary Winding at Min Tap = 102.08 KV
Secondary Winding Rated Voltage = 13.8 KV
Secondary operating voltage = 13.8 KV

% Impedance = 13.50%

No of Taps = 25
Nominal Tap No = 13

NOTE: This was a GT Transformer with 110kv Y- 13.8 - Connection.

Each Delat with 31.50 MVA and One Delat wil be used.

MV Side Full Load Current = 31.50 MVA = 1317.90 A


3 x 13.8 kv
MV SIDE IS DELTA CONNECTION => Iload = 1863.8

MV Side Through Fault Current = 31.50 MVA = 9762.25 A


3 x 13.8 x 13.5%
Isc(sec.) = 4.0676 A

Low Set O/C Setting ( I > )


I> = 180% of rated current
= 2372.23 = 0.98843 A
Select I> = = 0.98843 x IN
X-tic = = DT
t> = = 1.4 sec

MD-YEAST-TR-13.8KV-OC-DT-TR05-REV0.00 1/2
SAUDI JOOD

High Set O/C Setting ( I >> )


BLOCKED

Low Set Earth Fault Setting ( Io > )

Io > > = 300 A Prim. ;


= 0.125 A Sec.
X-tic = = DT
to = = 1.4 sec

High Set E/F Setting ( Io >> )

Io >> = BLOCKED
to >> = BLOCKED

Protection Parameter Recommended Setting


I> 0.99 x IN
X-tic DT
Phase Over Current t> 1.400
I >> BLOCKED
t >> BLOCKED

Io > 0.125
X-tic DT
Earth Fault
K 1.4
Io >> BLOCKED
to >> BLOCKED

MD-YEAST-TR-13.8KV-OC-DT-TR05-REV0.00 2/2