Application Note Protection Class
Application Note Protection Class
Satisfactory operation of protective relays can depend on accurate representation of currents ranging from small leakage
currents to very high overcurrent's, requiring the protective current transformer to be linear, and therefore below magnetic
saturation at values up to perhaps 30 times full load current .
This wide operating range means that protective current transformers require to be constructed with larger cross-sections
resulting in heavier cores than equivalent current transformers used for measuring duties. For space and economy reasons,
equipment designers should however avoid over-specifying protective current transformers ITL technical staff are always
prepared to assist in specifying protective CT's but require some or all of the following information;
IEC Specification
According to IEC 60044-1 protective current transformers are specified as follows:
Rated Output:
The burden including relay and pilot wires (standard burdens are 2.5,5,75,10, 15 and 30VA)
Accuracy Class:
Accuracy Class Current error @ rated Phase displacement @ rated primary current Composite error @ rated accuracy limit
primary current primary current
% mins Centiradians %
5P 1 60 1.8 5
10P 3 10
Standard Accuracy Limit Factors are 5, 10, 15, 20 and 30. The electrical requirements of a protection current transformer can
therefore be defined as :
Three Phase Unrestricted Earth fault Protection Combines 3 Phase & Unrestricted
Overcurrent Protection (Detects earth faults on load side of Earth Fault Protection
the CTs)
If however, the transformers are badly matched, a spill current will arise which will trip the relay. Similarly, current transformers
must operate below the saturation region, since, in a 3 phase system, third harmonics in the secondary are additive through
the relay thereby creating instability and erroneously tripping the earth fault relay.
Time Grading
Time lags on relays are set in such a way that a fault in a sub-section will isolate that section of the distribution only. Accurate
time grading can be adversely affected by inaccuracy or saturation in the associated current transformer. The following table is
intended to show typical examples of CT applications However, in all cases manufacturers recommendations must be
followed.
High impedance differential impedance 1A or 5A Class PX, use relay manufacturers formulae
High speed feeder protection 1A or 5A Class PX, use relay manufacturers formulae
Sensitivity
Sensitivity is defined as the lowest value of primary fault current, within the protected zone, which will cause the relay to oper-
ate. To provide fast operation on an in-zone fault, the current transformer should have a 'Knee-Point Voltage' at least twice the
setting voltage of the relay.
The 'Knee Point Voltage' (Vkp) is defined as the secondary voltage at which an increase of 10% produces an increase in
magnetising current of 50%. It is the secondary voltage above which the CT is near magnetic saturation.
Differential relays may be set to a required sensitivity but will operate at some higher value depending on the magnetising
currents of the CTs, for example:
Primary Operating Current (P.O.C) = K (lr + nle) where:
K = CT Ratio
Ir = Relay set current
Ie = CT magnetising current
n = Number of CTs in parallel
The diagram shows a restricted earth fault system with the relay fed from 400/5 CTs. The relay may be set at 10%, but it
requires more than 40A to operate the relay since the CT in the faulty phase has to deliver its own magnetising current and that
of the other CTs in addition to the relay operating current.
Stability
That quality whereby a protective system remains inoperative under all conditions other than those for which it is designed to
operate, i.e. an in-zone fault Stability is defined as the ratio of the maximum through fault current at which the system is stable
to nominal full load current. Good quality current transformers will produce linear output to the defined knee-point voltage
(Vkp).
Typically,
Vkp = 2lf (Rs + Rp) for stability, where
If = max through fault secondary current at stability limit
Rs = CT secondary winding resistance
Rp = loop lead resistance from CT to relay
Transient Effects
Balanced protective systems may use time lag or high speed armature relays. Where high speed relays are used, operation of
the relay occurs in the transient region of fault current, which includes the d.c. asymmetrical component. The build up of
magnetic flux may therefore be high enough to preclude the possibility of avoiding the saturation region.
The resulting transient instability can fortunately be overcome using some of the following techniques:
c) Stabilising resistors in series with current operated relays, or in parallel with voltage operated relays.
These limit the spill current (or voltage) to a maximum value below the setting value. For series resistors in current operated
armature relays.
Rs = Vkp - VA
2Ir Ir
Ir
Where:
Rs = value of stabilising resistor in ohms
Vkp = CT knee-point voltage
VA = relay burden (typically 3VA)
Ir = relay setting current
Special Note:
The value of Rs varies with each fault setting. An adjustable resistor is therefore required for optimum results. Often a fixed
resistor suitable for mid-setting will suffice.
25 1
LEAD BURDEN VA ON 5A CT
LEAD BURDEN VA ON 1A CT
20 0.8
2
2
m
m
0m
15 5m 0.6
1.
1.
2
mm
10 2.5 0.4
5 0.2
2
6mm
2
10mm
10 20 30 40 50 60 METRES