Electrak Underfloor To Workstation PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56
At a glance
Powered by AI
The key takeaways are that Legrand is a global leader in electrical and digital building infrastructures. They focus on innovation through R&D investment and new product launches. Their power distribution business unit provides solutions for today's building demands.

Legrand's main business units are their power distribution business unit, which provides solutions like transformers, busbars, and desk modules. Their key areas of focus are innovation, research and development, and maintaining a high rate of new product launches.

Some of Legrand's sustainability initiatives include efficient and environmentally aware product design, product functions that help avoid energy waste, managing manufacturing/logistics sites sustainably, and integrating environmental concerns into their global sites.

POWERING THE

WORKSTATION

UNDERFLOOR
TO WORKSTATION
POWER AND DATA
DISTRIBUTION
SYSTEMS

THE GLOBAL SPECIALIST


IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
Global
strength
built on local
knowledge
Legrand is the global specialist in electrical and digital
building infrastructures. Innovation is the driving force
behind its development. With an increasing investment
in research and development (circa 5% of sales) and
more than 4,000 active patents, the Legrand Group
is focused on maintaining a high rate of new product
launches that present innovative solutions to the market.

LEGRANDS POWER DISTRIBUTION SUSTAINABLE DEVELOPMENT


BUSINESS UNIT From design through to manufacturing,
From Zucchini transformers, through high power the Legrand Group selects materials and
distribution and rising main busbar to Electrak processes that respect people and the
powertrack, desk modules and lighting control, environment.
Legrands power distribution business unit provides Eficient and environmentally aware product design
market leading solutions to the increasing demands
Product functions that help to avoid energy waste
of todays buildings.
Management of manufacturing and logistics sites
Integration of environmental concerns and
ISO 14001 procedures at the Groups global sites*

* 84% of sites are ISO 14001:2004 accredited including all UK sites.

XX
CONTENTS
POWERTRACK
Overview 6
Ordering information 8
Technical information 17
FLOOR BOXES
Overview 22
Ordering information 24
Technical information 29
GROMMETS
Overview 30
Ordering information 32
Technical information 33
INTERSOC-R
Overview 34
Ordering information 38
Technical information 42
INTERSOC ON-DESK
Overview 46
Ordering information 50
Technical information 52

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 1


WWW.LEGRAND.CO.UK/ELECTRAK

Electrak ...
the specialist in power distribution
throughout the workplace
Electrak, a brand of the Legrand Group in the UK, is a leading name
in power distribution and lighting control solutions. Electrak busbar
systems, loor boxes, grommets, desk modules and lighting control
ranges are installed in high speciication ofices around the world.

2
POWERING THE WORKSTATION
UNDERFLOOR POWER
Electraks power track system is perfect for supplying underfloor power in cavity
floor installations. With minimal parts, push-fit assembly and a complementary
range of floor boxes, this flexible, easy to install system can be reconfigured as
office layouts evolve.

POWER TRACK CAVITY FLOOR BOXES


See page 6 See page 22

WORKSTATION POWER
Electraks access grommets provide the gateway for power to feed from the
underfloor power track network to the workstation, where all desk power
requirements are met with our new range of desk modules, Intersoc-R and
Intersoc on-desk.

GROMMETS INTERSOC-R INTERSOC ON-DESK


See page 30 See page 34 See page 46

FULLY ADDRESSABLE LIGHTING CONTROL


Designed to work in harmony with Electraks buscom trunking, Lightraks
lighting control system offers high end sophistication with unbeatable
flexibility and speed of installation.
Find out more at www.legrand.co.uk/electrak

BUSCOM LIGHTRAK
power and data backbone lighting control system

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 3


WWW.LEGRAND.CO.UK/ELECTRAK

Electrak ...
UK manufacturing. Global recognition

OVER 30 YEARS OF EXPERIENCE QUALITY ASSURED UK MANUFACTURING


Legrands cost-effective Electrak systems have With its Electrak ranges manufactured from its
been designed and manufactured to distribute UK manufacturing base situated in the North
power and data reliably and safely throughout East of England, Legrand adapts to the changing
the workplace. The original underloor busbar demands of projects by providing a rapid production
system, invented by Electrak in the 1980s, sets the process whilst ensuring quality meets the highest
benchmark for lexible power distribution. standards.

INDUSTRY EXPERTS
As part of its ongoing commitment to research
and development, Legrand continually evolves its
product ranges to ensure it develops the best and
most innovative solutions available on the market.
Legrand takes pride in its enviable reputation for
market leading customer service, industry
knowledge and product expertise.

4
Trusted throughout the UK and across the world

UNITED KINGDOM MIDDLE EAST & INDIA ASIA PACIFIC


Morgan Stanley, Canary Wharf ADMA-OPCO HQ, Dubai Credit Suisse, ICC I, Hong Kong
Media City, Manchester Internet City, Dubai Deutsche Bank, ICC I, Hong Kong
JP Morgan, Canary Wharf Burjuman Centre, Dubai Barclays Capital, Cheung
RBS, Edinburgh ADIC/Al Bahr Towers, Abu Dhabi Kong Centre
Bridgewater Place, Leeds Al Dar HQ, Abu Dhabi Customs Headquarters,
Network Rail, Nationwide Central Bank of Kuwait North Point, Hong Kong
Swiss Re, City of London Ministry of Education, Kuwait Standard Chartered Bank,
Amazon, Swansea PIFFS Aridya, Kuwait IFC II, Hong Kong
Heathrow Airport, London PAAET, Kuwait Citi Bank Tower, Hong Kong
Fort Dunlop, Birmingham Qatar News Agency Macquarie Bank, IFC I, Hong Kong
Royal Bank of Canada, Barclays, Chennai, India UBS Bank, IFC II, Hong Kong
City of London Barclays, Pune, India JP Morgan, Hong Kong
Snow Hill, Birmingham Barclays, Andheri, India Standard Chartered Bank, Marina
Barclays Capital, Canary Wharf Barclays, Mumbai, India Bay, Singapore
Temple Back, Bristol RBS, Delhi, India Barclays Capital, Marina Bay, Singapore
Standard Chartered Bank, Fidelity, Delhi, India Nomura Bank, Marina Bay, Singapore
City of London Credit Suisse, Serangoon Road,
London Underground Singapore
BBC, White City ABN Amro, One Rafles Quay, Singapore
Mann Island, Liverpool RBS, One George Street, Singapore
Barclays Capital, Shanghai
Standard Chartered Bank, Shanghai
UBS Bank, Shanghai

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 5


WWW.LEGRAND.CO.UK/ELECTRAK
6
Powertrack...
adaptable, reliable
underfloor power

Integral track connector plugs into feed unit Lengths simply push-fit together

Integral fixing brackets for rapid installation Tap-offs plug in to shuttered socket outlets
and lock on to track body

THE INDUSTRY STANDARD IN UNDERFLOOR POWER


Electrak powertrack / underloor busbar is perfect for cavity
loor installations. With minimal parts, push-it assembly and a
complementary range of loor boxes and grommets, this lexible,
easy to install system can be reconigured as ofice layouts evolve.
The system consists of continuous lengths of track which are fed via
a feed unit and can be installed in loor voids as low as 48mm.
63 A rated, IP 40 protection
Available in ive versions: single phase, clean earth, dual circuit,
three phase and auxiliary earth
Tinned busbar version available for use within Abu Dhabi
(see page 15)
Available in 1.2m, 1.8m, 2.4m and 3.6m lengths
Tap-off outlets are located at every 300 or 600mm pitch
Floor mountable (stand-off brackets also available)

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 7


WWW.LEGRAND.CO.UK/ELECTRAK
Electrak powertrack / underfloor busbar
selection chart

Description Length (m)

Track lengths with 300 mm socket centres

4 outlets 12

6 outlets 18

8 outlets 24

12 outlets 36

Track feeds

Excluding cables and conduit

Fexible metal conduit

Fexible metal conduit

Standard tap-off / auxillary earth tap-off


3
32 A unfused 16 mm L, N, PE
5
3
13 A fused 16 mm L, N, PE
5
3
13 A 5437 fused 16 mm L, N, PE
5
Low noise / clean earth tap-off
3
32 A unfused 16 mm CE, L, N, PE
5
3
13 A fused 16 mm CE, L, N, PE
5
3
13 A 5437 fused 16 mm CE, L, N, PE
5
Dual circuit tap-off

3
32 A unfused 20 mm CE, L1, N1 L2, N2, PE
5

3 phase tap-off
3
32 A 415 V 3 phase 20 mm L1, L2, L3, N, PE
5
3
32 A L1 unfused reconfigurable live pin 16 mm L1, N, PE
5
3
32 A L2 unfused reconfigurable live pin 16 mm L2, N, PE
5
3
32 A L3 unfused reconfigurable live pin 16 mm L3, N, PE
5

Key code / Busbar arrangement

008_009_Electrak 2014 v3.indd 8 27/08/2014 13:07


ELECTRAK 24 ELECTRAK 25 ELECTRAK 26 ELECTRAK 27 ELECTRAK 28
Standard system Low noise / clean Dual circuit 3 phase Auxillary earth
(white) earth system (green) system (dark green) system (grey) system (red)

DA1123 JA2123 KA3123 NA4123 YA5123

DA1183 JA2183 KA3183 NA4183 YA5183

DA1243 JA2243 KA3243 NA4243 YA5243

DA1363 JA2363 KA3363 NA4363 YA5363

DF1010 JF2010 KF3010 NF4010 YF5010

DW1000 JW2000 KW3000 NW4000 YW5000

DW1010 JW2010 KW3010 NW4010 YW5010

DW1020 JW2020 KW3020 NW4020 YW5020

DP1332 DP1332 YP5332


DP1532 DP1532 YP5532
DP1313 DP1313 YP5313
DP1513 DP1513 YP5513
DP1327 DP1327 YP5327
DP1527 DP1527 YP5527

JP2332 JP2332
JP2532 JP2532
JP2313 JP2313
JP2513 JP2513
JP2327 JP2327
JP2527 JP2527

KP3328

KP3528

NZ4331
NZ4531
NP43321
NP45321
NP43021
NP45021
NP43031
NP45031

PE N2 L2 PE CE N1 L1 PE CE N1 L1 N2 L2 PE N L1 L2 L3 PE N1 L1

1 : All NP tap-offs are reconfigurable between L1, L2 or L3 for 3 phase track


9

008_009_Electrak 2014 v3.indd 9 27/08/2014 13:05


Electrak 24 powertrack / underfloor busbar system
standard system (white)

DF1010

DW1010

---
- - -/
DA1123 DP1332

Selection charts p. 8-9


Dimensions and technical information p. 17-21
Approved to ASTA Standard 138 and ISO 9001 : 2008
Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations
A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos. Track system components Pack Cat. Nos. Tap-off units
Electrak 24 standard track lengths Tap-off length is determined by the cable and not
the conduit length, e.g. a 3 m tap-off has 3 m of
Track lengths fit together using the integral cable and 26 m of flexible metal conduit1
connectors on each length Tap-off units in excess of 3 m should only be used if
Track lengths should always be secured using the they contain a fuse or if the power track is protected
integral floor fixing brackets by a protective device not exceeding 32 A
300 mm socket centres
1 DA1123 12 m, 4 outlets, 2 floor fixing brackets 32 A unfused
1 DA1183 18 m, 6 outlets, 2 floor fixing brackets 16 mm L, N, PE
1 DA1243 24 m, 8 outlets, 2 floor fixing brackets
1 DA1363 36 m, 12 outlets, 3 floor fixing brackets 1 DP1332 3 m
1 DP1532 5 m
Track feed unit
13 A fused
1 DF1010 With one 25 mm diameter hole suitable for MICC,
armoured cables or single core cables in conduit 16 mm L, N, PE
1 DP1313 3 m
Flexible interlinks 1 DP1513 5 m
Can be used to overcome obstructions or
as corners where required 13 A 5437 fused - high integrity
1 DW1000 Excluding cables and conduit 16 mm L, N, PE
1 DW1010 12 m flexible metal conduit 1 DP1327 3 m
1 DW1020 24 m flexible metal conduit 1 DP1527 5 m
Special fixing brackets
Required when track is raised off surface level
Brackets raise track by 21 mm and should be
spaced 600 mm apart
1 DZ1210 For fitting under track body and track feed
1 DZ1230 For fitting under integral track connectors

1 : Tap-offs are supplied as standard with flexible metal conduit


For alternative wiring solutions, contact us on +44 (0) 845 600 6266

10

010_011_Electrak 2014 v2.indd 10 27/08/2014 12:44


Electrak 25 powertrack / underfloor busbar system
low noise / clean earth system (green)

JF2010

JW2010

---
- - -/
JA2123
JP2332

Selection charts p. 8-9


Dimensions and technical information p. 17-21
Approved to ASTA Standard 138 and ISO 9001 : 2008
Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations
A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos. Track system components Pack Cat. Nos. Tap-off units
Electrak 25 low noise / clean earth track lengths Tap-off length is determined by the cable and not
the conduit length, e.g. a 3 m tap-off has 3 m of
Track lengths fit together using the integral cable and 26 m of flexible metal conduit1
connectors on each length Tap-off units in excess of 3 m should only be used if
Track lengths should always be secured using the they contain a fuse or if the power track is protected
integral floor fixing brackets by a protective device not exceeding 32 A
300 mm socket centres
1 JA2123 12 m, 4 outlets, 2 floor fixing brackets 32 A unfused
1 JA2183 18 m, 6 outlets, 2 floor fixing brackets 16 mm CE, L, N, PE
1 JA2243 24 m, 8 outlets, 2 floor fixing brackets
1 JA2363 36 m, 12 outlets, 3 floor fixing brackets 1 JP2332 3 m
1 JP2532 5 m
Track feed unit
13 A fused
1 JF2010 With one 25 mm diameter hole suitable for MICC,
armoured cables or single core cables in conduit 16 mm CE, L, N, PE
1 JP2313 3 m
Flexible interlinks 1 JP2513 5 m
Can be used to overcome obstructions or
as corners where required 13 A 5437 fused - high integrity
1 JW2000 Excluding cables and conduit 16 mm CE, L, N, PE
1 JW2010 12 m flexible metal conduit 1 JP2327 3 m
1 JW2020 24 m flexible metal conduit 1 JP2527 5 m
Special fixing brackets
Required when track is raised off surface level
Brackets raise track by 21 mm and should be
spaced 600 mm apart
1 DZ1210 For fitting under track body and track feed
1 DZ1230 For fitting under integral track connectors

1 : Tap-offs are supplied as standard with flexible metal conduit


For alternative wiring solutions, contact us on +44 (0) 845 600 6266

11

010_011_Electrak 2014 v2.indd 11 27/08/2014 12:44


Electrak 26 powertrack / underfloor busbar system
dual circuit system (dark green)

KF3010

KW3010

---
- - -/
KA3123
KP3328

Selection charts p. 8-9


Dimensions and technical information p. 17-21
Approved to ASTA Standard 138 and ISO 9001 : 2008
Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations
A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos. Track system components Pack Cat. Nos. Tap-off units
The dual power track system has both standard and Tap-off length is determined by the cable and not
low noise / clean earth systems incorporated the conduit length, e.g. a 3 m tap-off has 3 m of
cable and 26 m of flexible metal conduit1
Electrak 26 dual circuit track lengths Tap-off units in excess of 3 m should only be used if
Track lengths fit together using the integral they contain a fuse or if the power track is protected
connectors on each length by a protective device not exceeding 32 A
Track lengths should always be secured using the Standard 32 A unfused
integral floor fixing brackets
300 mm socket centres 16 mm L, N, PE
1 KA3123 12 m, 4 outlets, 2 floor fixing brackets 1 DP1332 3 m
1 KA3183 18 m, 6 outlets, 2 floor fixing brackets 1 DP1532 5 m
1 KA3243 24 m, 8 outlets, 2 floor fixing brackets
1 KA3363 36 m, 12 outlets, 3 floor fixing brackets Standard 13 A fused

Track feed unit 16 mm L, N, PE


1 DP1313 3 m
1 KF3010 With two 25 mm diameter holes suitable for MICC, 1 DP1513 5 m
armoured cables or single core cables in conduit
Standard 13 A 5437 fused
Flexible interlinks
16 mm L, N, PE
Can be used to overcome obstructions or
as corners where required 1 DP1327 3 m
1 DP1527 5 m
1 KW3000 Excluding cables and conduit
1 KW3010 12 m flexible metal conduit Low noise / clean earth 32 A unfused
1 KW3020 24 m flexible metal conduit
16 mm CE, L, N, PE
Special fixing brackets 1 JP2332 3 m
Required when track is raised off surface level 1 JP2532 5 m
Brackets raise track by 21 mm and should be Low noise / clean earth 13 A fused
spaced 600 mm apart
1 DZ1210 For fitting under track body and track feed 16 mm CE, L, N, PE
1 DZ1230 For fitting under integral track connectors 1 JP2313 3 m
1 JP2513 5 m
Low noise / clean earth 13 A 5437 fused
16 mm CE, L, N, PE
1 JP2327 3 m
1 JP2527 5 m
Dual circuit 32 A unfused
20 mm CE, L1, N1, L2, N2,PE
1 KP3328 3 m
1 KP3528 5 m

1 : Tap-offs are supplied as standard with flexible metal conduit


For alternative wiring solutions, contact us on +44 (0) 845 600 6266

12

012_013_Electrak 2014 v2.indd 12 27/08/2014 12:45


Electrak 27 powertrack / underfloor busbar system
3 phase system (grey)

NF4010

NW4010

---
- - -/
NA4123 NZ4331

Selection charts p. 8-9


Dimensions and technical information p. 17-21
Approved to ASTA Standard 138 and ISO 9001 : 2008
Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations
A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos. Track system components Pack Cat. Nos. Tap-off units
Electrak 27 3 phase track lengths Tap-off length is determined by the cable and not
the conduit length, e.g. a 3 m tap-off has 3 m of
Track lengths fit together using the integral cable and 26 m of flexible metal conduit1
connectors on each length Tap-off units in excess of 3 m should only be used if
Track lengths should always be secured using the they contain a fuse or if the power track is protected
integral floor fixing brackets by a protective device not exceeding 32 A
300 mm socket centres
1 NA4123 12 m, 4 outlets, 2 floor fixing brackets 32 A 415 V 3 phase
1 NA4183 18 m, 6 outlets, 2 floor fixing brackets 20 mm L1, L2, L3, N, PE
1 NA4243 24 m, 8 outlets, 2 floor fixing brackets
1 NA4363 36 m, 12 outlets, 3 floor fixing brackets 1 NZ4331 3 m
1 NZ4531 5 m
Track feed unit
32 A L12 unfused
1 NF4010 With one 25 mm diameter hole suitable for MICC,
armoured cables or single core cables in conduit Unfused
Reconfigurable live pin
Flexible interlinks 16 mm L, N, PE
Can be used to overcome obstructions or 1 NP4332 3 m
as corners where required 1 NP4532 5 m
1 NW4000 Excluding cables and conduit 32 A L22 unfused
1 NW4010 12 m flexible metal conduit
1 NW4020 24 m flexible metal conduit Unfused
Reconfigurable live pin
Special fixing brackets 16 mm L, N, PE
Required when track is raised off surface level 1 NP4302 3 m
Brackets raise track by 21 mm and should be 1 NP4502 5 m
spaced 600 mm apart
32 A L32 unfused
1 DZ1210 For fitting under track body and track feed
1 DZ1230 For fitting under integral track connectors Unfused
Reconfigurable live pin
16 mm L, N, PE
1 NP4303 3 m
1 NP4503 5 m

1 : Tap-offs are supplied as standard with flexible metal conduit


For alternative wiring solutions, contact us on +44 (0) 845 600 6266
2 : All NP tap-offs are reconfigurable between L1, L2, or L3 for
3 phase track

13

012_013_Electrak 2014 v2.indd 13 27/08/2014 12:45


Electrak 28 powertrack / underfloor busbar system
auxiliary earth system (red)

YF5010

YW5010

---
- - -/
YA5123 YP5332

Selection charts p. 8-9


Dimensions and technical information p. 17-21
Approved to ASTA Standard 138 and ISO 9001 : 2008
Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations
A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos. Track system components Pack Cat. Nos. Tap-off units
Electrak 28 auxiliary earth track lengths Tap-off length is determined by the cable and not
the conduit length, e.g. a 3 m tap-off has 3 m of
Track lengths fit together using the integral cable and 26 m of flexible metal conduit1
connectors on each length Tap-off units in excess of 3 m should only be used if
Track lengths should always be secured using the they contain a fuse or if the power track is protected
integral floor fixing brackets by a protective device not exceeding 32 A
300 mm socket centres
1 YA5123 12 m, 4 outlets, 2 floor fixing brackets 32 A unfused
1 YA5183 18 m, 6 outlets, 2 floor fixing brackets 16 mm L, N, PE
1 YA5243 24 m, 8 outlets, 2 floor fixing brackets
1 YA5363 36 m, 12 outlets, 3 floor fixing brackets 1 YP5332 3 m
1 YP5532 5 m
Track feed unit
13 A fused
1 YF5010 With one 25 mm diameter hole suitable for MICC,
armoured cables or single core cables in conduit 16 mm L, N, PE
1 YP5313 3 m
Flexible interlinks 1 YP5513 5 m
Can be used to overcome obstructions or
as corners where required 13 A 5437 fused - high integrity
1 YW5000 Excluding cables and conduit 16 mm L, N, PE
1 YW5010 12 m flexible metal conduit 1 YP5327 3 m
1 YW5020 24 m flexible metal conduit 1 YP5527 5 m
Special fixing brackets
Required when track is raised off surface level
Brackets raise track by 21 mm and should be
spaced 600 mm apart
1 DZ1210 For fitting under track body and track feed
1 DZ1230 For fitting under integral track connectors

1 : Tap-offs are supplied as standard with flexible metal conduit


For alternative wiring solutions, contact us on +44 (0) 845 600 6266

14

014_Electrak 2014 v2.indd 14 27/08/2014 12:46


Electrak 28R As a specific requirement for use within
Abu Dhabi, Legrand has developed a
tinned busbar which has been designed
tinned powertrack... in line with the guidance for busways
outlined by the Abu Dhabi Distribution
Designed to meet local standards Company (ADDC), as detailed below.

Guideline For Design, Testing and Installation Of Appendix 8. Colour identification for cables
Busways GL.GN.01. Issued by: Abu Dhabi Distribution Co. Conductor Colour
Low Voltage Switchgear Committee Non-lexible ixed wiring and all 3 phase cables:
Issue: 2, Revision: 1, effective 01/02/2012 Phase 1 Red
16. Lighting & Small Power Busways & Modular Wiring Phase 2 Yellow
Lighting & Power Socket bus duct and modular wiring are considered Phase 3 Blue
part of building wiring and regulated by the Electricity Wiring Regulation Neutral Black
issued by RSB. It shall comply with respective specifications under the Earth conductors Green / yellow
Wiring regulation. ADDC LVSGC approves these methods in principle
provided that the RSB set aspects are incorporated (like tinning of copper, The Electrak 28R powertrack range is a single
colour coding etc.). phase system and therefore adopts red (L), black
Guideline For Design, Testing and Installation Of Busways GL.GN.01 (N), and green/yellow (E) cables to meet with the
Copyright Abu Dhabi Distribution Co. requirments of The Regulation and Supervision
Developed to meet the ADDC requirements for busways, this specially Bureau of the Water, Wastewater and Electricity
designed range sees all busbars tinned along their entire length, and Sector in the Emirate of Abu Dhabi.
all busbar connectors and tap-off blades plated.
Appendix 9. Capacity of conduits and trunking
Approved to ASTA standard 138 and designed to be in accordance with
Diameter of Conduit (mm ) 2

the requirements of BS EN 60439-2: 2000 and BS EN 61534-22: 2009 Conduit


(IEC 61534: 2009). 20 25 32
(mm ) 2

Maximum number of conductors


1.5 7 12 -
2.5 5 9 12
4.0 3 6 9

The tap-offs contain a maximum of 3 x 4mm 2

conductors housed in as 20mm metal lexible


conduit to meet the requirements of The
Regulation and Supervision Bureau of the Water,
Wastewater and Electricity Sector in the Emirate
Electrak 28R tinned tap-offs Electrak 28R tinned busbar connectors of Abu Dhabi.

The Electrical Wiring Regulations 2007 NOTE: When designing installations in regions
Issued by: The Regulation and Supervision Bureau for the with higher ambient temperatures than 35C,
Water, Wastewater and Electricity Sector in the Emirate of de-rating factors may need to be applied. Please
refer to the table on page 21 for details.
Abu Dhabi. Revision 1, January 2009
7.7 Busways, bus ducts ad busbar risers
7.7.6 Busways, bus ducts and busbar risers shall have neutral conductors
of equal size to the phase conductors and shall have a dedicated Earth
Conductor. The use of the metal casing as an earth conductor permitted
only for Earth Leakage Protected Installations, and with the prior approval
of the Distribution Company.
The Electrical Wiring Regulations 2007 - Copyright The Regulation and Supervision Bureau (RSB)

The Electrak powertrack system uses equal size tinned copper


busbars for live, neutral and earth conductors to meet with the
requirements of The Regulation and Supervision Bureau of the Water,
Wastewater and Electricity Sector in the Emirate of Abu Dhabi.

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 15


WWW.LEGRAND.CO.UK/ELECTRAK
Electrak 28R tinned powertrack / underfloor busbar system
auxiliary earth system (red)

YF5010R

YW5010R

---
- - -/
YA5123R YP5332R

Selection charts p. 8-9


Dimensions and technical information p. 17-21
Approved to ASTA Standard 138 and ISO 9001 : 2008
Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations
A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos. Busbar system components Pack Cat. Nos. Tap-off units
63A auxiliary earth busbar lengths Tap-off length is determined by the cable and not the
conduit length, e.g. a 3 m tap-off has 3 m of cable
Busbar lengths fit together using the integral and 26 m of flexible metal conduit1
connectors on each length Tap-off units in excess of 3 m should only be used if
Lengths should always be secured using the integral they contain a fuse or if the busbar run is protected
floor fixing brackets by a protective device not exceeding 32 A
300 mm socket centres
1 YA5123R 12 m, 4 outlets, 2 floor fixing brackets 32 A unfused
1 YA5183R 18 m, 6 outlets, 2 floor fixing brackets 20 mm L, N, PE (4 mm2)
1 YA5243R 24 m, 8 outlets, 2 floor fixing brackets
1 YA5363R 36 m, 12 outlets, 3 floor fixing brackets 1 YP5332R 3 m
1 YP5532R 5 m
Feed unit
13 A 5437 fused - high integrity
1 YF5010R With one 25 mm diameter hole suitable for MICC,
armoured cables or single core cables in conduit 20 mm L, N (25 mm2), PE (4 mm2)
1 YP5327R 3 m
Flexible interlinks 1 YP5527R 5 m
Can be used to overcome obstructions or
as corners where required
1 YW5000R Excluding cables and conduit
1 YW5010R 12 m flexible metal conduit
1 YW5020R 24 m flexible metal conduit
Special fixing brackets
Required when busbar is raised off surface level
Brackets raise the system by 21 mm and should be
spaced 600 mm apart
1 DZ1210 For fitting under lengths and feed units
1 DZ1230 For fitting under integral connectors

1 : Tap-offs are supplied as standard with flexible metal conduit


For alternative wiring solutions, contact us on +44 (0) 845 600 6266

16

016_Electrak 2014 v2.indd 16 27/08/2014 14:33


Electrak powertrack / underfloor busbar
design and installation

n General installation notes n Special fixing brackets


Electrak power track is a compact system that can be installed in floor Electrak special fixing brackets are available to raise the system by
voids as low as 48 mm 21 mm. Ensure brackets are spaced 600 mm apart and always have
support under the integral connectors and feed units. Failure to do so
Feed units are provided with one or two 25 mm diameter holes suitable may undermine the integrity of the system
for MICC, armoured cables or single core cables in conduit
Track lengths connect together and to feed units using the integral Cat. No. DZ1210 raised off-floor fixing brackets are spaced at 600 mm
connectors on each length centres along the busbar run. Also use bottom half of bracket under
feed unit and flexible interlink
Lengths should always be secured using the integral floor fixing Cat. No. DZ1230 raised off-floor fixing brackets are always used under
brackets ; three on the 36 m length and two on 24 m, 18 m or 12 m integral connectors. Busbar is secured to raised brackets using the
lengths integral fixing bracket

Access to power is provided along the busbar length by simply


plugging tap-off units into shuttered socket outlets. These tap-off
units feed all types of conventional floor service outlet boxes or
feed workstations directly through the floor via insulated conductors
contained in flexible metal or VO rated nylon conduit. When connecting
tap-offs directly through the floor via grommet outlets to workstations
care must be taken to ensure that the tap-off length is adequate

The dual system has both standard and low noise / clean earth Integral fixing bracket
screws to special bracket
systems incorporated. As well as dual tap-offs, both standard and low Integral connector
noise / clean earth tap-offs can be plugged into any socket outlet along 50 mm 185 mm
the busbar length. The dual tap-off incorporates both standard and low
noise cables 7 mm 7 mm

Optimum layout flexibility is achieved by positioning busbar lengths a 99 mm


maximum of 52 m apart and 25 m from the wall, and by connecting
the 3 m tap-off units to floor outlet boxes. This means every part of the
floor area can be served. Flexible interlinks can be used to overcome
obstructions or used as corners if required 21 mm to underside and
Cat. No. DZ1210 36 mm to top of busbar length Cat. No. DZ1230

n Dimensions

93 75 250 109
118 68

46 46 47 32
15
2 x 25 25 65

End view A End view B

92

Integral fixing
bracket fixing
centres

Example floor layout


25 m

socket outlet points every


52 m

300 or 600 mm along


busbar run
52 m

3 m flexible floor service


tap-off unit outlet box
52 m

feed unit integral


connectors

All dimensions (mm) are nominal

17

017_019_Electrak 2014 v3.indd 17 27/08/2014 12:48


Electrak powertrack / underfloor busbar system
design and installation (continued)

n Product configuration

Flexible interlink Tap-off connection


Flexible interlink boxes Depress tap-off side clips and push down
must be securely fixed Tap-off
inline to surface so no
movement can take place
after fixing

Side clip
Push down

Interlink feed
entry socket.
Remove dust
cover label Make sure both tap-
Remove dust cover off side clips are fully
from end entry pushed home on both
socket before use sides of tthe bar

Screw fix to surface

Feed unit (Cat. No. DF1010) Sub-cabling Tap-off connection

Tap-off metal
flexible conduit
Feed unit protective earth
terminal and earth bond

Protective earth must


always be connected via
the earth terminal block Lift lid
20 mm conduit fitting.
Tighten back nut securely
Connector terminals

Lift terminal tab to access


terminal screws and close
after use

25 mm cable
conduit fixing hole

Close lid and secure with lid


fixing screw before power up

Feed unit (Cat. No. JF2010) Sub-cabling Tap-off connection

Tap-off metal
flexible conduit
Feed unit protective earth
terminal and earth bond

Protective earth must


always be connected via
the earth terminal block Lift lid
20 mm conduit fitting
Tighten back nut securely
Connector terminals

Lift terminal tab to access


terminal screws and close
after use

Clean earth
25 mm cable
conduit fixing hole

Close lid and secure with lid


fixing screw before power up

All dimensions (mm) are nominal

18

017_019_Electrak 2014 v3.indd 18 27/08/2014 12:48


Feed unit (Cat. No. KF3010) Sub-cabling Dual tap-off connection (dark green)
Tap-off metal
flexible conduit
Lift terminal tab to access
terminal screws and close
after use

Feed unit protective


earth terminal and
Protective earth earth bond 20 mm conduit fitting Connections
must always be Lift lid
Tighten back nut securely L1, N1, CE = low noise
connected via the L2, N2, PE = standard
earth terminal block

Connections
L1, N1, CE = low noise
L2, N2, PE = standard Connector terminals

Clean earth

2 x 25 mm
cable conduit
fixing hole
Close lid and secure with lid
fixing screw before power up

Feed unit (Cat. No. NF4010) Sub-cabling 3 phase tap-off connection

Tap-off metal
flexible conduit
Feed unit protective earth
terminal and earth bond

Protective earth must


always be connected via
the earth terminal block Lift lid 20 mm conduit fitting
Tighten back nut securely
Connector terminals

Lift terminal tab to access


terminal screws and close
after use

25 mm cable
conduit fixing hole

Close lid and secure with lid


fixing screw before power up

Feed unit (Cat. No. YF5010 and YF5010R) Sub-cabling Tap-off connection
Tap-off metal
flexible conduit
Feed unit protective earth
terminal and earth bond

Protective earth must


always be connected via
the earth terminal block Lift lid
20 mm conduit fitting
Tighten back nut securely
Connector terminals

Lift terminal tab to access


terminal screws and close
after use

25 mm cable
conduit fixing hole

Close lid and secure with lid


fixing screw before power up

All dimensions (mm) are nominal

19

017_019_Electrak 2014 v3.indd 19 27/08/2014 12:49


Electrak powertrack / underfloor busbar system
installation (continued)

1 Fix feed unit to surface

Feed unit
Make chalk line to
align busbar lengths
Direction of
busbar run

2 Connect busbar length to feed unit


Integral
Remove connector
dust cover
Busbar length

Push down

Make sure connector


clips are fully pushed Push down
home on both sides
Feed unit

Additional
length

3 Connect additional busbar lengths

Remove dust cover


before connecting
additional lengths

First fixing
bracket

Tap-off outlets
reusable plastic
dust covers

Pull out fixing bracket


4 Secure busbar lengths to surface lugs and screw fix on
both sides

All integral fixing brackets must


be fixed to surface at 12 m fixing
centres from first bracket on each
busbar length

All dimensions (mm) are nominal

20

020_021_Electrack 2014 v2.indd 20 27/08/2014 12:50


Electrak powertrack / underfloor busbar system
technical data

n Standards Volt drops (live and neutral)


Busbars 30 mV/A/m
Approved to ASTA Standard 138 Cable connector 04 mV/A
BS EN 60439-2 : 2000, BS EN 61534-22 : 2009 Integral connector 04 mV/A
and IEC 61534-22 : 2009
Manufactured within an approved ISO 9001 : 2008 and ISO 14001 : 2004 facility 32 A tap-off 04 mV/A
Assessed Quality Assurance Certificate No. 2029 + 4 mm2 cable 11 mV/A/m
Electrak powertrack / underfloor busbar fully complies with the requirements of Flexible corner assembly 15 mV/A
BS 7671 : 2008 + A1 : 2011 (IET Wiring Regulations)
+ 10 mm2 cable 40 mV/A/m
n Ambient temperature rating factors
The current carrying capacity for a powertrack / underfloor busbar (In) is affected Mechanical data E24 E28 E28R
by the ambient temperature
For Electrak powertrack / underfloor busbar the ambient rating factor Ka is equal Number of conductors 3-6 3
to 1 for ambient temperatures up to and including 35 C Busbar conductor cross sectional area 13 mm2 13 mm2
Iz = Ka In Housing cross sectional area (copper equivalent) 13 mm2 13 mm2
Where : Cable terminal capacity 16 mm2 16 mm2
Iz = effective current carrying capacity for continuous service under particular Tap-off cable 32 A 4 mm2 4 mm2
installation conditions
Tap-off cable 13 A fused 15 mm2 25 mm2
Ka = ambient temperature factor
In = nominal current carrying capacity Tap-off conduit, up to 4 conductors 16 mm 20 mm
For ambient temperatures exceeding 35 C the values of Ka and Iz are given in Tap-off conduit, 5 and 6 conductors 20 mm2 N/A
the following tables
Flexible corner cable (tri-rated, high temperature) 10 mm2 10 mm2
Powertrack / underfloor busbar system Flexible corner conduit 25 mm 25 mm
Ambient 20C 25C 30C 35C 40C 45C 50C IP rating 40 40
Ka 1 095 085 080
Iz 63 A 59 A 53 A 50 A
Material specifications
32 A unfused tap-off (using thermosetting 90C cables) Housing - busbar lengths Galvanised steel, natural finish
Ambient 20C 25C 30C 35C 40C 45C 50C High conductivity copper
Busbars (Tinned version is electro-tin plated)
Ka 1 095 085 080
Iz 32 A 30 A 27 A 25 A Busbar insulator PTFE
Integral connectors / Tap-off outlets Flame retardant polycarbonate
13 A fused tap-off (using 25 mm2 thermosetting 90C cables)
Tap-off outlet entry shutter Acetal
Ambient 20C 25C 30C 35C 40C 45C 50C
Tap-off housing Flame retardant polycarbonate
Ka 1
Integral connector blades Copper (Tinned version is plated)
Iz 13 A
Tap-off blades Copper (Tinned version is plated)
References : Tap-off/flexible corner conduit, metal Electro-galvanised steel
BS 7671 : 2008 incorporating amendment No. 1 : 2011 Tap-off cable LSOH to BS 7211
Appendix 8 Current carrying capacity for powertrack systems
Flexible interlink cable Tri-rated to BS 6231
Appendix 4 Table 4B1 Rating factors for thermosetting cables
Feed box/flexible interlink boxes Galvanised steel
Appendix 4 Table 4E1A Single core 90C thermosetting insulated cables
(non-armoured) Feed connector terminals/earth block Brass (Tinned version is plated)

n Earth fault loop impedance


Fixing brackets Galvanised steel
13 A tap-off, fuse To BS 1362, ASTA approved
BS 7671 : 2008 + A1 : 2011 IET Wiring Regulations require accurate
determination of the total earth loop impedance, which must be sufficiently low to
allow the protective device to operate within the specified time, which for socket
outlets is 04 seconds. The values relevant to Electrak for calculating the earth Earth fault loop impedance
fault loop impedance are shown in the electrical test data table, see opposite Phase busbar 15 m/m

n Durability
Earth busbar 15 m/m
Earth housing 11 m/m
Electrak systems are superbly designed and extremely robust. They can
be expected to stand up to all normal site conditions. Electrak powertrack / Earth busbar and housing 08 m/m
underfloor busbar has been short circuit strength tested by ASTA Cable connector 04 m

n Installations with high protective conductor currents


Integral connector 06 m
32 A tap-off 06 m
All unfused tap-offs comply with Regulation 5437 without the need for additional
earth conductors. Regulation 54371103 (ii) states a single copper protective + 4 mm2 cable 11 m/m
conductor having a cross-sectional area of not less than 4 mm2, complying Flexible corner assembly 15 m
with the requirements of Regulations 5432 and 5433, the protective conductor + 10 mm2 cable 40 m/m
being enclosed to provide additional protection against mechanical damage, for
example, within a flexible conduit Rated conditional short-circuit current 16 KA
For installations with high protective conductor currents requiring Ambient temperature 25C
fused tap-offs, a 5437 compliant tap-off must be used. Normally fused tap-offs
incorporate 15 m2 (25 m2 for tinned system) conductors, however in the fused
5437 tap-offs, the 15 m2 (25 m2 for tinned system) earth conductor is replaced Electrical test data
with a 4 mm2 conductor and therefore complies with Section 54371103 (ii)
Rated current 63 A
n 32 A tap-off unit Rated voltage 230/400 V~
The 3 m 32 A tap-off unit comprises an unfused tap-off with 26 m of flexible Frequency 50/60 Hz
metal conduit with integral 4 mm2 LSOH conductors Conductor resistance - live and neutral 30 m/m
These units are designed to comply with regulation 43421 of the Conductor impedance 15 m/m
IET Wiring Regulations by virtue of the following :
maximum length of cable is 3 m
it is factory assembled and fully tested item with cable installed in high quality
flexible conduit
Fault condition protection for the tap-off assembly and the floor box socket outlets
is delivered by the circuit protection device
Disconnection time for socket outlets is 04 seconds (Regulation 411322). The
Electrak system meets this requirement
Tap-off units in excess of 3 m should only be used if they contain a fuse
or the busbar run is protected by a protective device not exceeding 32 A All dimensions (mm) are nominal

21

020_021_Electrack 2014 v2.indd 21 27/08/2014 12:50


Floor boxes...
choice, flexibility and
easy installation

2, 3 and 4 compartment raised access


loor boxes and slab boxes offer complete
versatility. Floor boxes are available pre-wired
with power track tap-off, or supplied empty
(unassembled), with a choice of single or
separate compartment bases and three depth
options. With a vast selection of power and
data plates available, boxes can be tailored
to the speciic requirements of each ofice
installation.

22
Rapid fit /remove mechanism Quick-fit, reversible lid for
adjusts for flooring thickness rapid installation

Durable ABS trim and


lid surround

Various RCD protection Rapid fit push lock secures


options available base in floor aperture

Available pre-wired with Three depth options: Single or separate


tap-off 75mm, 85mm, 110mm compartment bases

Available in 2, 3 and 4 compartments and with a choice of


three depths, Electrak loor boxes have been developed
with a host of special features:
Available pre-wired with tap-off or supplied unassembled
A vast selection of power and data plates,
including RCD options
Single or separate compartment bases for ease of data
cabling
Rapid installation and fast ratchet mechanism which
adjusts to loor inish thickness

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 23


WWW.LEGRAND.CO.UK/ELECTRAK
access floor service outlet and slab mounted floor boxes
empty boxes and accessory plates

2 compartment 3 compartment 4 compartment

To configure boxes as required, select :


1. Box depth

230

230

230
2. Number of compartments required

mm

mm

mm
3. Desired accessory plates
mm mm mm
290 366 366
100 mm 100 mm 75 mm
Empty boxes Example width plates width plates
width plates

Single base 75 mm depth CR2001 CR011 CR4001

Single base 85 mm depth (standard box) CR2002 CR012 CR4002

Single base 110 mm depth CR2003 CR013 CR4003

Separate compartment base 75 mm depth CR2004 CR014 CR4004

Separate compartment base 85 mm depth CR2005 CR015 CR4005

Separate compartment base 110 mm depth CR2006 CR016 CR4006

Slab boxes 1 compartment 2 compartment 3 compartment 4 compartment

Fix directly onto floor slab (supplied empty) CR5102 CR5202 CR5302 CR5402

Accessory plates For 1, 2 and 3 compartment boxes For 4 compartment boxes

Blank plate CR020 CR4100

2 gang switched socket outlet CR022 CR4101

2 gang switched socket outlet,


CR023 CR4102
low noise / clean earth

2 gang non-standard switched socket outlet CR027 CR4103

2 gang unswitched socket outlet CR029 CR4104

3 gang unswitched socket outlet CR030 CR4105

3 gang unswitched socket outlet, CR044 CR4118


low noise / clean earth

2 gang RCD socket outlet CR036 CR4111

2 gang RCD socket outlet, CR043 CR4117


low noise / clean earth
Punched plate for 2 x 1 gang accessories CR026
(603 mm fixing centres)
Punched plate for 2 gang accessories CR028
(1206 mm fixing centres)

Angled punched plate for 4 x RJ45 sockets CR042 CR4115


(37 mm x 22 mm cut-outs)

2 x LJ2 accessory plate (50 mm fixing centres) CR031 CR4106

4 x BNC connector plate CR033 CR4108

4 x Data / telecoms plate CR024 CR4112


(37 mm x 22 mm cut-outs)
6 x Data / telecoms plate CR025 CR4113
(37 mm x 22 mm cut-outs)

24

024_Electrak 2014 v1.indd 24 27/08/2014 12:51


access floor pre-wired service outlet boxes
and accessory plates

Pre-wired service outlet boxes with Electrak tap-offs


1. Select power track tap-off and desired configuration
2. Select additional accessory plates (if required)

Includes 1 x twin Includes 2 x twin Includes 1 x 2 gang Includes 2 x 2 gang


3 compartment switched socket outlet switched socket outlet RCD socket outlet RCD socket outlet

Electrak 24 - standard tap-off

DP1332 - 3 m CR100 CR102 CR100R CR102R

DP1532 - 5 m CR101 CR103 CR101R CR103R


Electrak 25 - low noise /
clean earth tap-off
230

JP2332 - 3 m CR110 CR112 CR110R CR112R


mm

mm
366 JP2532 - 5 m CR111 CR113 CR111R CR113R

Electrak 28 - auxiliary earth tap-off

YP5332 - 3 m CR104 CR106 CR104R CR106R

YP5532 - 5 m CR105 CR107 CR105R CR107R

Additional plates for 3 compartment boxes

2 x LJ2 accessory plate


Blank plate CR020 CR031
(50 mm fixing centres)

Punched plate for 2 x 1 gang accessories


CR026 4 x BNC connector plate CR033
(603 mm fixing centres)

Punched plate for 2 gang accessories 4 x Data / telecoms plate


CR028 CR024
(1206 mm fixing centres) (37 mm x 22 mm cut-outs)

Angled punched plate for 4 x 6 x Data / telecoms plate


CR042 (37 mm x 22 mm cut-outs) CR025
RJ45 sockets (37 mm x 22 mm cut-outs)

Modular RCD
Includes 1 x twin Includes 2 x twin protecting 2 x twin
Includes 1 x 2 gang Includes 2 x 2 gang switched socket
4 compartment switched socket switched socket
RCD socket outlet RCD socket outlet
outlet outlet outlets and 1 spare
compartment

Electrak 24 - standard tap-off

DP1332 - 3 m CR120 CR122 CR120R CR122R CR4402

DP1532 - 5 m CR121 CR123 CR121R CR123R CR4403


Electrak 25 - low noise /
clean earth tap-off

JP2332 - 3 m CR130 CR132 CR130R CR132R CR4412


230
mm

JP2532 - 5 m CR131 CR133 CR131R CR133R CR4413


mm
366
Electrak 28 - auxiliary earth tap-off

YP5332 - 3 m CR124 CR126 CR124R CR126R CR4406

YP5532 - 5 m CR125 CR127 CR125R CR127R CR4407

Additional plates for 4 compartment boxes

Blank plate CR4100 4 x BNC connector plate CR4108

Angled punched plate for 4 x 4 x Data / telecoms plate


RJ45 sockets (37 mm x 22 mm cut-outs) CR4115 (37 mm x 22 mm cut-outs) CR4112

2 x LJ2 accessory plate 6 x Data / telecoms plate


(50 mm fixing centres) CR4106 (37 mm x 22 mm cut-outs) CR4113

25

025_Electrak 2014 v1.indd 25 27/08/2014 12:51


access floor service outlet boxes slab mounted floor boxes
empty boxes empty boxes

CR5302

CR4002

3 compartment slab floor box shown with two twin


switched socket outlets, punched data plate and a
power track tap-off
CR5102
CR012

Selection charts p. 24 Selection charts p. 24


Dimensions and technical information p. 29 Dimensions and technical information p. 29
Lid and trim mouldings are precision engineered from hard wearing Electrak slab floor boxes are an ideal solution for underfloor power and
durable ABS. The lid is reinforced with a galvanised mild steel plate data requirements
Mounting frame and box base - 09 mm thick galvanised steel Used in conjunction with Electrak floor grommets, slab boxes prevent
Each compartment has 2 entries for 20 mm and 2 entries for 25 mm unwanted access to power and data connections
flexible conduits
Grey mouldings. Alternative colours available to special order. Goosewing
grey plates
2, 3 and 4 compartment boxes are also available with separate individual
compartment base units for convenient offsite pre-wiring
Supplied in parts or fully assembled and configured to customer
specification
Conform to IEC-61534-22

Pack Cat. Nos. 2 compartment floor boxes Pack Cat. Nos. Slab floor boxes
Empty boxes Fixes directly onto floor slab
100 mm compartment widths Fast and efficient installation with integrated fixing
plates
1 CR2001 Single base - 75 mm depth Wide range of power and data accessory plates
1 CR2002 Single base - 85 mm depth (standard box) Manufactured from 09 mm thick galvanised steel
1 CR2003 Single base - 110 mm depth Each compartment has 2 entries for 20 mm and
1 CR2004 Separate compartment base - 75 mm depth 2 entries for 25 mm flexible conduits
1 CR2005 Separate compartment base - 85 mm depth 100 mm compartment widths
1 CR2006 Separate compartment base - 110 mm depth Use plates from the 1, 2 and 3 compartment floor box
section p. 24
3 compartment floor boxes 1 CR5102 1 compartment slab floor box
Empty boxes
1 CR5202 2 compartment slab floor box
100 mm compartment widths 1 CR5302 3 compartment slab floor box
1 CR011 Single base - 75 mm depth 75 mm compartment widths
1 CR012 Single base - 85 mm depth (standard box)
1 CR013 Single base - 110 mm depth Use plates from the 4 compartment floor box section
p. 24
1 CR014 Separate compartment base - 75 mm depth
1 CR015 Separate compartment base - 85 mm depth 1 CR5402 4 compartment slab floor box
1 CR016 Separate compartment base - 110 mm depth

4 compartment floor boxes


Empty boxes
75 mm compartment widths
1 CR4001 Single base - 75 mm depth
1 CR4002 Single base - 85 mm depth (standard box)
1 CR4003 Single base - 110 mm depth
1 CR4004 Separate compartment base - 75 mm depth
1 CR4005 Separate compartment base - 85 mm depth
1 CR4006 Separate compartment base - 110 mm depth

Screed / edge trim boxes, and metal


or lockable lids are available to order
contact us on +44 (0) 845 600 6266

26

026_027_Electrak v1.indd 26 27/08/2014 13:59


access floor service outlet boxes
accessory plates and ancillary items

Selection charts p. 24-25


Dimensions and technical information p. 29
Lid and trim mouldings are precision engineered from hard wearing durable ABS. Lid is reinforced with a galvanised mild steel plate
Mounting frame and box base - 09 mm thick galvanised steel
Each compartment has 2 entries for 20 mm and 2 entries for 25 mm flexible conduits
Grey mouldings. Alternative colours available to special order. Goosewing grey plates
2, 3 and 4 compartment boxes are also available with separate individual compartment base units for convenient offsite pre-wiring
Supplied in parts or fully assembled and configured to customer specification
Conform to IEC-61534-22

Pack Cat. Nos. 1, 2 and 3 compartment accessory plates Pack Cat. Nos. 4 compartment accessory plates
100 mm width 75 mm compartment widths
1 CR020 Blank plate 1 CR4100 Blank plate
1 CR022 2 gang switched socket outlet 1 CR4101 2 gang switched socket outlet
1 CR023 2 gang switched socket outlet, low noise / clean earth 1 CR4102 2 gang switched socket outlet, low noise / clean earth
1 CR027 2 gang non-standard switched socket outlet 1 CR4103 2 gang non-standard switched socket outlet
1 CR029 2 gang unswitched socket outlet 1 CR4104 2 gang unswitched socket outlet
1 CR030 3 gang unswitched socket outlet 1 CR4105 3 gang unswitched socket outlet
CR044 3 gang unswitched socket outlet, CR4118 3 gang unswitched socket outlet,
low noise / clean earth low noise / clean earth
1 CR036 2 gang RCD socket outlet 1 CR4111 2 gang RCD socket outlet
1 CR043 2 gang RCD socket outlet, low noise / clean earth 1 CR4117 2 gang RCD socket outlet, low noise / clean earth
1 CR026 Punched plate for 2 x 1 gang accessories 1 CR4115 Angled punched plate for 4 x RJ45
(603 mm fixing centres) (37 mm x 22 mm cut-outs)
1 CR028 Punched plate for 2 gang accessories 1 CR4106 2 x LJ2 accessory plate (50 mm fixing centres)
(1206 mm fixing centres) 1 CR4108 4 x BNC connector plate
1 CR042 Angled punched plate for 4 x RJ45 1 CR4112 4 x Data / telecoms plate (37 mm x 22 mm cut-outs)
(37 mm x 22 mm cut-outs) 1 CR4113 6 x Data / telecoms plate (37 mm x 22 mm cut-outs)
1 CR031 2 x LJ2 accessory plate (50 mm fixing centres)
1 CR033 4 x BNC connector plate
Ancillary items for service outlet boxes
1 CR024 4 x Data / telecoms plate (37 mm x 22 mm cut-outs)
1 CR025 6 x Data / telecoms plate (37 mm x 22 mm cut-outs) 1 CR0001 Floor tile cut-out template 2 compartment
1 CR0003 Floor tile cut-out template 3/4 compartment
10 CR0000 Cable outlet flap
10 CR0010 Cable routers
50 CR0011 Screws for accessory plates
1 CR0012 Pack of 5 keys for use with lockable floor boxes
1 CR0002 Lid 2 compartment box
1 CR0004 Lid 3/4 compartment box
1 CR0005 Mounting frame for vinyl floor. For 2 compartment box
Replaces mounting frame attached to base
1 CR0006 Mounting frame for vinyl floor. For 3/4 compartment
box. Replaces mounting frame attached to base
10 CR0007 Floor box lid handle
1 CR0020 Metal lid and trim - replacement for 3 and 4
compartment boxes - powder coated grey

Electrak tap-offs p. 10-14, 16

27

026_027_Electrak v1.indd 27 27/08/2014 12:52


access floor pre-wired service outlet boxes
3 and 4 compartment

CR100
CR122

Dimensions and technical information p. 29

Electrak floor boxes can be supplied pre-wired to power track tap-offs with any variation of sockets, tap-offs, depth or other configuration

Pack Cat. Nos. 3 compartment pre-wired boxes with 1 x TSSO Pack Cat. Nos. 4 compartment pre-wired boxes with 1 x TSSO
100 mm compartment widths 75 mm compartment widths
Single base 85 mm depth, pre-wired with : Single base 85 mm depth, pre-wired with :
1 CR100 3 m Electrak 24 standard tap-off Cat. No. DP1332 1 CR120 3 m Electrak 24 standard tap-off Cat. No. DP1332
1 CR101 5 m Electrak 24 standard tap-off Cat. No. DP1532 1 CR121 5 m Electrak 24 standard tap-off Cat. No. DP1532
1 CR110 3 m Electrak 25 low noise / clean earth tap-off 1 CR130 3 m Electrak 25 low noise / clean earth tap-off
Cat. No. JP2332 Cat. No. JP2332
1 CR111 5 m Electrak 25 low noise / clean earth tap-off 1 CR131 5 m Electrak 25 low noise / clean earth tap-off
Cat. No. JP2532 Cat. No. JP2532
1 CR104 3 m Electrak 28 auxiliary earth tap-off 1 CR124 3 m Electrak 28 auxiliary earth tap-off Cat. No. YP5332
Cat. No. YP5332 1 CR125 5 m Electrak 28 auxiliary earth tap-off Cat. No. YP5532
1 CR105 5 m Electrak 28 auxiliary earth tap-off
Cat. No. YP5532
4 compartment pre-wired boxes with 2 x TSSO
3 compartment pre-wired boxes with 2 x TSSO 75 mm compartment widths
100 mm compartment widths Single base 85 mm depth, pre-wired with :
1 CR122 3 m Electrak 24 standard tap-off Cat. No. DP1332
Single base 85 mm depth, pre-wired with :
1 CR123 5 m Electrak 24 standard tap-off Cat. No. DP1532
1 CR102 3 m Electrak 24 standard tap-off Cat. No. DP1332
1 CR132 3 m Electrak 25 low noise / clean earth tap-off
1 CR103 5 m Electrak 24 standard tap-off Cat. No. DP1532 Cat. No. JP2332
1 CR112 3 m Electrak 25 low noise / clean earth tap-off 1 CR133 5 m Electrak 25 low noise / clean earth tap-off
Cat. No. JP2332 Cat. No. JP2532
1 CR113 5 m Electrak 25 low noise / clean earth tap-off 1 CR126 3 m Electrak 28 auxiliary earth tap-off Cat. No. YP5332
Cat. No. JP2532
1 CR127 5 m Electrak 28 auxiliary earth tap-off Cat. No. YP5532
1 CR106 3 m Electrak 28 auxiliary earth tap-off
Cat. No. YP5332
1 CR107 5 m Electrak 28 auxiliary earth tap-off Pre-wired floor boxes can be supplied with RCD rather than standard
Cat. No. YP5532 sockets. Add an R to the end of the part numbers for an RCD version.
For example CR100R is a 3 compartment floor box with a twin RCD
socket and a DP1332 tap-off

Also available :
- pre-wired boxes with fused tap-offs
- shallow or deep versions
- separate compartment bases
contact us on +44 (0) 845 600 6266

28

028_Electrak 2014 v1.indd 28 27/08/2014 12:53


access floor service outlet boxes access floor service outlet boxes
with RCD protection technical information

n Floor boxes
Dimensions
Lid can accommodate carpets up to 6 mm depth
Accessory plates are 172 mm long, with 162 mm fixing centres
Materials
Lid and trim mouldings are precision engineered from hard wearing
durable ABS. Lid is reinforced with a galvanised mild steel plate
Mounting frame and box base 09 mm thick galvanised steel
Floor service unit conforms to IEC-61534-22
Wiring
Each compartment has 2 entries for 20 mm and 2 entries for 25 mm
flexible conduits
Colour
CR4401
Grey mouldings. Alternative colours available to special order
Goosewing grey plates
Selection charts p. 24-25
Dimensions and technical information (opposite)
Dimensions from top of floor tile into floor void
Electrak floor boxes are available with various RCD protection options
and can be supplied pre-wired to power track tap-offs
C
Pack Cat. Nos. Floor boxes with RCD protection and A
2 x TSSO
B
Boxes contain 1 spare 75 mm width compartment
1 CR4400 Includes standard sockets
1 CR4401 Includes low noise sockets A B C
Accessory Underside lid to top of
box depth accessory (plug clearance)
Pre-wired RCD protected floor boxes (mm) (mm) (mm)

Boxes contain RCD and 2 x TSSO with 75 35 35


1 spare 75 mm compartment 85 45 35
1 CR4402 Pre-wired with Cat. No. DP1332 tap-off 110 45 60
CR4403 Pre-wired with Cat. No. DP1532 tap-off
n To install box
1
1 CR4412 Pre-wired with Cat. No. JP2332 tap-off
1 CR4413 Pre-wired with Cat. No. JP2532 tap-off
Cut hole in raised floor tile, lower
complete box into aperture and push
firmly down

Floor tile cut-out dimensions


2 compartment : 263 mm x 203 mm1
3 and 4 compartment : 340 mm x 203 mm1
Floor cut-out aperture is the same for single base or separate
compartment base

To fit carpet :
Detach lid and trim assembly by lifting
the blue locking handles and lifting out.
Cut and fit carpet. Push lid and trim
assembly back into place

1 : The aperture dimension 203 mm has a fixing tolerance between 203 to 205 mm

29

029_Electrak 2014 v1.indd 29 27/08/2014 12:54


Floor
grommets...
perfectly balancing
capacity and size
ACCESS GROMMETS
The Electrak range of simple to install access grommets
allow cables and conduit to link between underloor
power and desk power systems
Ranging from 144mm to 232mm in diameter
169mm diameter grommet can accommodate up to 3 x
32mm conduits - perfectly balancing capacity and size
Push-it lid with optional screw ixing to prevent
unauthorised access

30
Cable flap allows
Removable inlay for optional permanent connection
carpet fitting of services

NEW 169mm diameter


provides the perfect balance
Flat mounted RCD socket between size and capacity

Spring loaded screws for rapid Available pre-wired to power


installation track tap-offs

POWER AND DATA GROMMETS


The Electrak range of cleaners grommets are the latest
addition to its power and data grommets range. Within
their 169mm diameter, the grommet can house a lat
RCD socket and provide ample space for the user to plug
in or unplug equipment.
Cleaners grommet with lat mounted RCD socket
or standard socket options
Push-it lid with cable lap feature
Spring loaded screws for rapid installation
Available pre-wired to power track tap-offs

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 31


WWW.LEGRAND.CO.UK/ELECTRAK
floor grommets
access / power and data

EG0010 EG0030

EG0040 EG0045

Dimensions and technical information p. 33

Pack Cat. Nos. Plastic access grommets Pack Cat. Nos. Plastic power and data grommets
Quick fit installation 169 mm cut-out size 152 mm
Precision engineered from hard wearing durable ABS
Grey mouldings. Other colours available to special Quick fit installation
order Precision engineered from hard wearing durable ABS
Grommets conform to IEC-61534-22 Grey mouldings. Other colours available to special
Simply secured by pushing down the spring-loaded order. Conform to IEC-61534-22
screws and rotating a quarter turn Removable carpet recess
Cable flap feature so grommet lid can be closed
1 EG0010 144 mm cut-out size 127 mm while in use
Can accomodate all cable types or three metal Simply secured by pushing down the spring loaded
conduits up to a 20 mm or 25 mm without foam screws and rotating a quarter turn
1 EG0040 13 A power grommet
1 EG0030 169 mm cut-out size 152 mm Supplied complete with
Allows power, data and flexible conduit up to 32 mm 13 A unswitched socket
to pass through raised access floor 1 EG0045 RCD power grommet
Lid can be locked with screw (included) Supplied complete with 13 A RCD socket
Maximum number of conduits :
9 x 20 mm 1 EG0051 13 A power/data grommet
5 x 25 mm Supplied complete with 13 A socket and
3 x 32 mm 1 x 37 x 22 mm cut-out
1 EG0052 Data grommet
1 EG0055 232 mm cut-out size 215 mm Supplied complete with data plate
High capacity grommet 2 x 37 x 22 mm cut-out
Recommended for installation in light traffic areas
Pre-wired power grommets
Aluminium access grommet
169 mm cut-out size 152 mm
Body cast aluminium
Lid injection moulded plastic Nylon 66 with Cleaners socket version
neoprene cable gasket 1 EG0041 DP1332 - 3 m unfused
Secured by quarter-turn fasteners 1 EG0042 DP1532 - 5 m unfused
Floor depth 25 to 55 mm 1 EG0043 DP1313 - 3 m 13 A fused
Access grommet depth 60 mm
(95 mm when back box included) 1 EG0044 DP1513 - 5 m 13 A fused
1 EG0015 144 mm cut-out size 127 mm RCD socket version
Allows power, data and flexible 1 EG0046 DP1332 - 3 m unfused
conduit up to 25 mm to pass 1 EG0047 DP1532 - 5 m unfused
through raised access floor 1 EG0048 DP1313 - 3 m 13 A fused
1 EG0049 DP1513 - 5 m 13 A fused
Aluminium power grommet
1 EG0025 13 A power grommet
Supplied complete with 13 A
unswitched socket

32

032_Electrak 2014 v2.indd 32 27/08/2014 12:55


floor grommets
technical information

n 144 mm plastic floor grommet n To install plastic floor grommet


Dimensions A B
144 mm grommet 144 mm
EG0010
55 mm

125 mm min Recommended hole


127 mm min cutter is a 5"/127 mm
hole saw blade
Floor panel cut-out diameter Wing

n 169 mm plastic floor grommets


Lift handle and pull to Push grommet into raised floor tile aperture
remove lid Push down spring loaded screws and rotate quarter turn
to secure
Access grommet Ensure wings are located under floor panel
Cat. No. EG0030 For honeycombed floor panels one wing should face
downwards and one wing should face upwards
55

C D E 1
2
148
169

Power grommet

Cable access
insert (1) Push down lid to close
Slide lid into lug holes
Drop cable access insert into (2) If grommet is not in use,
102

housing opening replace cable access insert

n 144 mm aluminium grommets


148
169

Recommended hole cutter is a 6/152 mm hole saw blade


Access grommet

n 232 mm plastic floor grommet Cat. No. EG0015


60
Dimensions

Large quick fit grommet 232 mm


Cat. No. EG0055
90

58 mm
13 A power grommet

Cat. No. EG0025


213 mm min 60
40
215 mm max 95
Floor panel cut-out diameter
Recommended hole cutter is a
adjustable hole saw blade with 144
range of 40 mm - 300 mm
Recommended hole cutter is a 5/127 mm hole saw blade

All dimensions (mm) are nominal

33

033_Electrak 2014 v4.indd 33 27/08/2014 12:56


34
Intersoc-R ... fast, TM

reliable, adaptable
modular desk power

COMPLETE SOLUTIONS FOR DEMANDING ENVIRONMENTS


Intersoc-R is a modular desk power system designed to
meet the demands of modern workplaces for faster and more
adaptable solutions.
Designed with speed of installation and lexibility in mind,
Intersoc-Rs modular coniguration enables thousands of
different combinations to be made - providing solutions for every
installation requirement.
Modular system - rapid coniguration and easy workstation
relocation
Push-it connection - modules can simply be disconnected
and additional modules inserted
Busbar interconnection - no need for wiring
Easily adapted to meet the changing demands of the workplace

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 35


WWW.LEGRAND.CO.UK/ELECTRAK
The next generation
of power distribution

Available in standard and clean earth versions, with ixed


or rotatable socket options and a safe shuttered electrical
connection, Intersoc-R is the next generation of power
distribution...
Simple push-it, module connection with auto-lock mechanism
creates robust joints and makes installation quicker and easier
32 A system with safe shuttered electrical connections for
additional safety, meets the requirements of BS 7671 : 2008
(including section 543.7)
MCB, RCD and RCBO modules, with reversible hinged covers,
provide a full range of circuit protection options
2, 3 or 4 gang British standard socket modules with ixed or
rotatable, fused or unfused (BS 6396) sockets options - all the
options you need to meet the requirements of any installation
8 international socket options make Intersoc-R ideal for
installations across the globe
Outgoing connections: lexible interlink or end cap with ST
or GST options

NEW Intersoc On-desk


Personal power and data system
Find out more on page 46

36
UNDERFLOOR TO WORKSTATION SYSTEM GUIDE
WWW.LEGRAND.CO.UK/ELECTRAK
Intersoc-RTM desk modules
electrical supply

IAB301A

IAB002A

IAB660B
IAB312A

IAB610BB

Dimensions and technical information p. 42-45

Intersoc-R features fast modular connection with push-fit auto lock mechanism, safe shuttered electrical connections and a robustly designed rigid
joint between modules. Available in standard and clean earth versions
Independently approved by Intertek. Complies with BS 5733 and the relevant parts of BS 1363 part 2. Manufactured in an approved
ISO 9001 : 2008 facility. Meets the requirements of BS 7671 : 2008 for high integrity earthing (section 5437)

Pack Cat. Nos. 32 A pre-wired feed modules Pack Cat. Nos. 16 A feed modules pre-wired to 13 A fused
plug
Standard earth tap-offs (E24 - White tap-off)
1 IAB002A With 2 m 15 mm2 cable
1 IAB311A 3 m unfused metal tap-off Cat. No. DP1332
1 IAB003A With 3 m 15 mm2 cable
1 IAB312A 5 m unfused metal tap-off Cat. No. DP1532
1 IAB005A With 5 m 15 mm2 cable
1 IAB315A 3 m 13 A fused 5437 metal tap-off Cat. No. DP1327
1 IAB316A 5 m 13 A fused 5437 metal tap-off Cat. No. DP1527
16 A rewirable feed modules
Low noise / clean earth tap-offs
(E25 - Green tap-off) 1 IAB201A Rewirable feed module (for cable)
1 IAC311A 3 m unfused metal tap-off Cat. No. JP2332
1 IAC312A 5 m unfused metal tap-off Cat. No. JP2532 16 A feed units with in-built GST
1 IAC315A 3 m 13 A fused 5437 metal tap-off Cat. No. JP2327 connector
1 IAC316A 5 m 13 A fused 5437 metal tap-off Cat. No. JP2527
1 IAB660B Compact feed module with male GST connector
Auxiliary earth tap-offs (E28 - Red tap-off) 1 IAB201B Feed module with male GST and earth bond lead
1 IAF311A 3 m unfused metal tap-off Cat. No. YP5332
1 IAF312A 5 m unfused metal tap-off Cat. No. YP5532 16 A pre-wired connection leads
1 IAF315A 3 m 13 A fused 5437 metal tap-off Cat. No. YP5327 13 A fused plug pre-wired to GST connector
1 IAF316A 5 m 13 A fused 5437 metal tap-off Cat. No. YP5527
1 IAB002B With 2 m 15 mm2 cable
32 A re-wirable feed modules 1 IAB003B With 3 m 15 mm2 cable
1 IAB005B With 5 m 15 mm2 cable
1 IAB301A Standard earth (for flexible conduit) GST to GST connection leads
1 IAC301A Low noise (for flexible conduit)
1 IAB610BB 1 m length
32 A feed units with in-built Neutrik 1 IAB620BB 2 m length
connectors 1 IAB630BB 3 m length

1 IAB301E Standard earth


1 IAC301E Low noise

32 A tap-offs pre-wired to Neutrik connectors


Standard earth tap-offs (E24)
1 IAB311E 3 m unfused metal tap-off Cat. No. DP1332
1 IAB312E 5 m unfused metal tap-off Cat. No. DP1532
1 IAB315E 3 m 13 A fused 5437 metal tap-off Cat. No. DP1327
1 IAB316E 5 m 13 A fused 5437 metal tap-off Cat. No. DP1527
Low noise / clean earth tap-offs (E25)
1 IAC311E 3 m unfused metal tap-off Cat. No. JP2332
1 IAC312E 5 m unfused metal tap-off Cat. No. JP2532
1 IAC315E 3 m 13 A fused 5437 metal tap-off Cat. No. JP2327
1 IAC316E 5 m 13 A fused 5437 metal tap-off Cat. No. JP2527

38

038_039_Electrak 2014 v2.indd 38 27/08/2014 12:56


Intersoc-RTM desk modules
protection, BS sockets, end caps and interlinks

IAC502R IAB402A IAZ001A IAB703A

IAB533F IAB450A

IAB600B

IAB504R IAB610B

Dimensions and technical information p. 42-45

The BS version is available with fixed or rotatable sockets. Individually fused sockets are available to meet the requirements of BS 6396 : 2008
(5 x 20 mm anti-surge ceramic fuses)
A wide range of interconnection solutions are available. When 16 A cabling interconnection is used with 32 A under desk solutions, suitable de-rating
protection devices must be incorporated to protect the cables
All protection and switching modules, end caps and interlinks are universally compatible with standard and clean earth / low noise systems

Pack Cat. Nos. Protection and switching modules Pack Cat. Nos. Socket modules low noise / clean earth
(green sockets) (continued)
1 IAB401A With 13 A fuse
1 IAB402A With 13 A fuse and sw/neon 3 gang unfused
1 IAB403A With 13 A fuse and neon
1 IAB404A 32 A max. single isolation module 1 IAC503F Fixed sockets
1 IAB405A With 30 mA RCD 1 IAC503R Rotatable sockets
1 IAB408A With neon indicator 3 gang individually fused
1 IAB420A With 16 A MCB
1 IAB430A With 20 A MCB 1 IAC533F 315 A fixed sockets
1 IAB440A With 32 A MCB 1 IAC533R 315 A rotatable sockets
1 IAB450A With 16 A RCBO 4 gang unfused
1 IAB460A With 20 A RCBO
1 IAB470A With 32 A RCBO 1 IAC504F Fixed sockets
1 IAC504R Rotatable sockets
Socket modules standard (grey sockets) 4 gang individually fused
2 gang unfused 1 IAC534F 315 A fixed sockets
1 IAC534R 315 A rotatable
1 IAB502F Fixed sockets
1 IAB502R Rotatable sockets
End cap
2 gang individually fused
1 IAZ001A Blank end cap
1 IAB532F 315 A fixed sockets
1 IAB532R 315 A rotatable sockets
Intersoc to intersoc pre-wired interconnection
3 gang unfused
16 A
1 IAB503F Fixed sockets
1 IAB503R Rotatable sockets 1 IAB603A 03 m length
1 IAB605A 05 m length
3 gang individually fused 1 IAB610A 1 m length
1 IAB533F 315 A fixed sockets 1 IAB620A 2 m length
1 IAB533R 315 A rotatable sockets 1 IAB630A 3 m length
1 IAB650A 5 m length
4 gang unfused
32 A
1 IAB504F Fixed sockets
1 IAB504R Rotatable sockets 1 IAB703A 03 m length
1 IAB705A 05 m length
4 gang individually fused 1 IAB710A 1 m length
1 IAB534F 315 A fixed sockets 1 IAB720A 2 m length
1 IAB534R 315 A rotatable sockets 1 IAB730A 3 m length
1 IAB750A 5 m length
Socket modules low noise / clean earth Power out end caps 16 A
(green sockets)
2 gang unfused Without flex

1 IAC502F Fixed sockets 1 IAB600B End cap with female GST connector
1 IAC502R Rotatable sockets 1 IAB600C End cap with female ST connector

2 gang individually fused With flex to female GST connector

1 IAC532F 315 A fixed sockets 1 IAB610B 1 m length


1 IAC532R 315 A rotatable sockets 1 IAB620B 2 m length
1 IAB630B 3 m length

39

038_039_Electrak 2014 v2.indd 39 27/08/2014 12:57


Intersoc international range
international socket options

IAB5N4A IAB5P4A

IAF5N2A IAC5P2A

Dimensions and technical information p. 42-45

The Intersoc 32 A under-desk range is a complete modular power system. Intersoc offers a wide range of international socket options.
The Intersoc modular system features safe shuttered electrical connections and a robustly designed rigid joint between modules. All modules
connect with single push-fit action and auto lock

Pack Cat. Nos. Schuko socket modules Pack Cat. Nos. 5 A Indian socket modules
2 gang grey socket outlets 2 gang grey socket outlets
1 IAB5N2A 90 angled sockets 1 IAB5P2A 90 angled sockets
1 IAB5N2B 45 angled sockets 1 IAB5P2B 45 angled sockets
4 gang grey socket outlets 4 gang grey socket outlets
1 IAB5N4A 90 angled sockets 1 IAB5P4A 90 angled sockets
1 IAB5N4B 45 angled sockets 1 IAB5P4B 45 angled sockets
2 gang red socket outlets 2 gang green socket outlets
1 IAF5N2A 90 angled sockets 1 IAC5P2A 90 angled sockets
1 IAF5N2B 45 angled sockets 1 IAC5P2B 45 angled sockets
4 gang red socket outlets 4 gang green socket outlets
1 IAF5N4A 90 angled sockets 1 IAC5P4A 90 angled sockets
1 IAF5N4B 45 angled sockets 1 IAC5P4B 45 angled sockets

French/Belgium socket modules 15 A South African socket modules


2 gang grey socket outlets 2 gang grey socket outlets
1 IAB5U2A 90 angled sockets 1 IAB5Q2A 90 angled sockets
1 IAB5U2B 45 angled sockets 1 IAB5Q2B 45 angled sockets
4 gang grey socket outlets 4 gang grey socket outlets
1 IAB5U4A 90 angled sockets 1 IAB5Q4A 90 angled sockets
1 IAB5U4B 45 angled sockets 1 IAB5Q4B 45 angled sockets
2 gang red socket outlets 2 gang green socket outlets
1 IAF5U2A 90 angled sockets 1 IAC5Q2A 90 angled sockets
1 IAF5U2B 45 angled sockets 1 IAC5Q2B 45 angled sockets
4 gang red socket outlets 4 gang green socket outlets
1 IAF5U4A 90 angled sockets 1 IAC5Q4A 90 angled sockets
1 IAF5U4B 45 angled sockets 1 IAC5Q4B 45 angled sockets

40

040_Electrak 2014 v1.indd 40 27/08/2014 12:57


Intersoc international range
international socket options (continued)

IAB5R4A IAB5S4A

IAC5R2A IAC5S2A

Dimensions and technical information p. 42-45

The Intersoc 32 A under-desk range is a complete modular power system. Intersoc offers a wide range of international socket options.
The Intersoc modular system features safe shuttered electrical connections and a robustly designed rigid joint between modules. All modules
connect with single push-fit action and auto lock

Pack Cat. Nos. Australian/Chinese socket modules Pack Cat. Nos. 15 A USA socket modules
2 gang grey socket outlets 2 gang grey socket outlets
1 IAB5R2A 90 angled sockets 1 IAB5S2A 90 angled sockets
1 IAB5R2B 45 angled sockets 1 IAB5S2B 45 angled sockets
4 gang grey socket outlets 4 gang grey socket outlets
1 IAB5R4A 90 angled sockets 1 IAB5S4A 90 angled sockets
1 IAB5R4B 45 angled sockets 1 IAB5S4B 45 angled sockets
2 gang green socket outlets 2 gang green socket outlets
1 IAC5R2A 90 angled sockets 1 IAC5S2A 90 angled sockets
1 IAC5R2B 45 angled sockets 1 IAC5S2B 45 angled sockets
4 gang green socket outlets 4 gang green socket outlets
1 IAC5R4A 90 angled sockets 1 IAC5S4A 90 angled sockets
1 IAC5R4B 45 angled sockets 1 IAC5S4B 45 angled sockets

20 A USA socket modules


2 gang grey socket outlets
1 IAB5T2A 90 angled sockets
1 IAB5T2B 45 angled sockets
4 gang grey socket outlets
1 IAB5T4A 90 angled sockets
1 IAB5T4B 45 angled sockets
2 gang green socket outlets
1 IAC5T2A 90 angled sockets
1 IAC5T2B 45 angled sockets
4 gang green socket outlets
1 IAC5T4A 90 angled sockets
1 IAC5T4B 45 angled sockets

41

041_Electrak 2014 v1.indd 41 27/08/2014 12:58


Intersoc-RTM desk modules
technical information

n Under-desk dimensions (mm)

GST
Compact and Blank interconnect
GST feed unit Feed unit end cap male

75 1105 12 50

1 1
2 socket module 3 socket module

60

1565 2145

1
4 socket module

2725

Fixed Rotatable
end view end view

32 379

60 60

1 : Dimensions only apply to BS sockets and not the international range

MCB, RCD protection module 1 Protection module Interconnection

60 60

1745 1155 50 775

1 : 845 mm depth

All dimensions (mm) are nominal

42

042_045_Electrak 2014 v3.indd 42 27/08/2014 12:59


n Testing and accreditation n British Standards
BS 6396 : 2008 Electrical Systems in Office Furniture and Educational
Furniture Specification

BS 7671 : 2008 incorporating amendment No. 1 : 2011. Requirements


for Electrical Installation (IET Wiring Regulations 17th Edition)

Electricity at Work Regulations 1989


Independently approved by Intertek
Complies with BS 5733 and relevant parts of BS 1363-2 Health & Safety Legislation
Manufactured within an approved ISO 9001 : 2008 and
ISO 14001 : 2004 facility
Assessed quality assurance certificate No. 2029 Below is a brief outline of the main criteria within the standards :

BS 6396 : 2008 was published with regard to the use of electrical


equipment within general office and educational furniture. This
Electrical test data
standard sets out in its scope the use and testing of electrical socket
outlets and associated wiring when used together with a 13 A BS 1363
Rated current up to 32 A fused plug for mains supply and makes provision for the routing of
Rated voltage 250 V ~ cables through furniture
Frequency 50/60 Hz
For compliance with this standard, socket outlet configurations of up
to 4 outlets should be individually fused at 5 A and up to 6 outlets
individually fused at 315 A
Conductor resistance at 20C
Fixed Rotatable A note on individual socket fusing BS 6396 Compliance :
2 socket module 08 m 09 m
The standard requires individual socket fusing (as per the table below)
4 socket module 16 m 17 m
Total number of Individually fused
Volt drop sockets at
Live and neutral 2, 3 or 4 sockets 5A
5 or 6 sockets 315 A
2 socket module 15 m V/A
4 socket module 30 m V/A Meets the requirements of BS 7671 : 2008 (2011) (17th Edition)
Protection module 40 m V/A The Health and Safety Executive states that installations which
(depending on device)
conform to the standards laid down in BS 7671 : 2008 (2011) are
regarded by the HSE as likely to achieve conformity with the relevant
In-feeds : parts of the Electricity at Work Regulations 1989
16 A 40 m V/A
Special note should be taken of regulation 5437 within
+15 mm2 29 m V/A/m BS 7671 : 2008 - Earthing requirements for the installation of
32 A 20 m V/A equipment having high protective conductor currents
+4 mm2 11 m V/A/m
Regulation 5437 has particular importance when there is a
Interconnections : requirement for a quantity of information technology equipment
16 A/32 A 20 m V/A being supplied from a final circuit in a location where the sum of their
protective currents exceeds 10 mA in normal use. Due to current in
+15 mm2 29 m V/A/m the protective conductor arising from the use of IT equipment, there
+4 mm2 11 m V/A/m is a requirement to provide mechanically protected 4 mm2 conductor
(54371103 (ii)). Intersoc achieves this when wired in accordance
with the installation sheets by providing mechanically protected 5 mm2
protective conductors within the product
Earth fault loop impedance

2 socket module 15 m
Material specification
4 socket module 30 m
Protection module 40 m Module housing Heat resistant ABS
(depending on device) Socket outlets polycarbonate
In-feeds : Busbars high conductivity copper CW004A (C101)
16 A 20 m Other metalwork phosphor bronze CW451K (PB102), CW452K (PB103)
+15 mm2 29 m/m brass CW507L (CZ107), CW508L (CZ108)
32 A 20 m high conductivity copper CW004A (C101)1
+4 mm2 11 m/m
1 : European grades with nearest British Standard shown in brackets
Interconnections :
16 A/32 A 40 m V/A
+15 mm2 29 m/m
+4 mm2 11 m/m

Mechanical data

Number of conductors 3
Busbar conductor cross-sectional area 5 mm2
16 A rewirable in-feed terminal capacity 10 mm2
32 A rewirable in-feed terminal capacity 10 mm2

43

042_045_Electrak 2014 v3.indd 43 27/08/2014 13:00


Intersoc-RTM desk modules
installation and configuration

n Installation
To connect and disconnect Intersoc modules
1. Connection / disconnection to be made by a competent person
2. Before connecting modules ensure they are the correct way up and in line
3. Push modules together one at a time
4. Modules self-lock when fully pushed together
5. To disconnect modules slide green latch to unlock module and pull apart
6. Always end module run with blank end cap or interconnect

Module self-locking latch

Underside of
modules shown

To fix modules to surface


Slide green latch Blank end cap
1. Insert through all fixing holes no. 8 pozi-pan screw or
M4 bolt to required length
2. Tighten screw / bolt down to mounting surface

2 socket module

All dimensions (mm) are nominal

44

042_045_Electrak 2014 v3.indd 44 27/08/2014 13:00


n Product configuration
1. Select the type of distribution system - standard, or low noise / clean earth
2. Select the means of powering the system - cable or power track tap-off
3. Select the type of in-feed module to match the cable capacity - 16 A or 32 A
4. Select the means of protection
5. Select the number of socket modules from the 2, 3 or 4 gang range (individually fused or unfused)
6. Select fixed or rotatable sockets
7. Select the interconnection units if required
8. Finish system with the end cap
(All modules push fit and lock together on-site or can be factory assembled to customer requirement)

Raised floor Floor grommet iiiiiil

lllllll
lllllllllllllllll
In-feed and power module push

llll l
Tap-off together and self-lock when fully

l l ll
1 2 l pushed home
l l ll
ll l l l l ll
llllllll
llllllllllllllllllllllllll
lllllllllllllll l l ll ll ll l l l l
lllll

Underfloor power track 32 A in-feed connected to tap-off and Tap-off and in-feed pulled through floor
left underfloor until required grommet after testing and when required

All dimensions (mm) are nominal

45

042_045_Electrak 2014 v3.indd 45 27/08/2014 13:00


XX
Intersoc on-desk...

power and data for


modern workspaces
The new Electrak Intersoc on-desk range brings power, data
and rapid USB charging capability to the modern workstation.
With its contoured edges, clean lines and stylish aluminium and
mirror white inish, Intersoc on-desk blends in perfectly
with contemporary ofice design schemes and enhances the
functionality of the desk space.

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 47


WWW.LEGRAND.CO.UK/ELECTRAK
Intersoc on-desk... del

rapid USB char


The fast pace of modern work practices, combined with the need for instant connectivity
is placing an ever greater reliance on the use of multiple devices, whether it be at our
workstation or whilst were on the move. The new range of Intersoc on-desk modules offers
a convenient answer to the growing demand for user-specific desk power and data access,
no matter what the technology requirements.
RAPID USB CHARGING
With an impressive 3.1 Amp dual charging facility, Intersoc on-desks twin USB modules
offer a high speciication, rapid charge facility that keeps your mobile devices ready should
you need to work on the move. Up to two devices (e.g. tablet and smart phone) can be
simultaneously charged at a faster rate than common, lower output chargers.

SUPERCHARGED
CHARGING
Twin USB charging modules
offer a high specification, rapid
charge facility

48
ivering power, data and
ging to the workstation
HIGH PERFORMANCE DATA
CAT 6A keystone jack modules offer high performance data and are supplied via
cables which neatly feed through the rear of the unit. CAT 6 modules are also
available with simple RJ45 connection at both the front and rear of the unit. Putting personal back
into desk power and data...
TAILORED TO YOUR REQUIREMENTS
Intersoc on-desk can be
Coniguring Intersoc on-desk modules to your exact requirements couldnt be
tailored to the demands of
simpler. Choose from: lat (horizontal) or angled (vertical) mounted units; select
any workstation.
any combination of power and data, and further enhance functionality with single
or double Euro modules or any device from within Legrands Arteor modular
wiring accessories range.

Left: Power is fed to the Intersoc on-desk unit via a choice of


13 A pre-wired plug, GST connector, or Intersoc-R under-desk
connector
Above left: On-desk units are available in flat mounted (pictured)
and angle mounted versions (data options are not available with
horizontal units)
Above: High specification CAT 6A keystone jacks can be supplied
with performance certificates. Easy to fix brackets are supplied
with protective pads that wont damage the desk
Left hand page: Convenient personal power and data ports for
laptops, with CAT 5 / CAT 6 RJ45 feed neatly nestling to the rear
of the unit, plus dual USB charging facility

UNDERFLOOR TO WORKSTATION SYSTEM GUIDE 49


WWW.LEGRAND.CO.UK/ELECTRAK
Intersoc on-desk modules

Pre-wired with Pre-wired with Pre-wired with


3 m ex and 15 m ex and 15 m ex and
BS 1363 plug GST connector Intersoc-R connector

Description Cat. No. Cat. No. Cat. No.

Horizontal unit with 2 x sockets individually fused


HA3320AA HB1320AA HD1320AA
at 315 A

Horizontal unit with 3 x sockets individually fused


HA3330AA HB1330AA HD1330AA
at 315A

Horizontal unit with 4 x sockets individually fused


HA3340AA HB1340AA HD1340AA
at 315 A

Vertical unit with 2 x sockets individually fused at


VA3320AA VB1320AA VD1320AA
315 A

Vertical unit with 3 x sockets individually fused at


VA3330AA VB1330AA VD1330AA
315 A

Vertical unit with 4 x sockets individually fused at


VA3340AA VB1340AA VD1340AA
315 A

Vertical unit with 2 x sockets individually fused at


315 A plus 1 x rear pluggable CAT 5 / CAT 6 VA3320AB VB1320AB VD1320AB
RJ45 outlet
Vertical unit with 2 x sockets individually fused at
315 A plus 2 x rear pluggable CAT 5 / CAT 6 VA3320AC VB1320AC VD1320AC
RJ45 outlets

Vertical unit with 2 x sockets individually fused at


VA3320AD VB1320AD VD1320AD
315 A plus 1 x rear pluggable data USB outlet

Vertical unit with 2 x sockets individually fused at


VA3320AE VB1320AE VD1320AE
315 A plus 2 x rear pluggable data USB outlets

Vertical unit with 2 x sockets individually fused at


315 A plus 1 x CAT 6A RJ45 outlet with 3 m data VA3320AF VB1320AF VD1320AF
lead
Vertical unit with 2 x sockets individually fused at
315 A plus 2 x CAT 6A RJ45 outlets with 3 m VA3320AG VB1320AG VD1320AG
data leads
Vertical unit with 2 x sockets individually fused at
315 A plus carrier to accept 1 x Euro Module VA3320AK VB1320AK VD1320AK
(25 x 50 mm)
Vertical unit with 2 x sockets individually fused at
315 A plus carrier to accept 2 x Euro Modules VA3320AL VB1320AL VD1320AL
(50 x 50 mm)
Vertical unit with 3 x sockets individually fused at
315 A plus 1 x rear pluggable CAT 5 / CAT 6 VA3330AB VB1330AB VD1330AB
RJ45 outlet
Vertical unit with 3 x sockets individually fused at
315 A plus 2 x rear pluggable CAT 5 / CAT 6 VA3330AC VB1330AC VD1330AC
RJ45 outlets

Vertical unit with 3 x sockets individually fused at


VA3330AD VB1330AD VD1330AD
315 A plus 1 x rear pluggable data USB outlet

Vertical unit with 3 x sockets individually fused at


VA3330AE VB1330AE VD1330AE
315 A plus 2 x rear pluggable data USB outlets

Fixings
Description Cat. No.
Long desk clamp for mounting horizontal units at on the desk H010
Adhesive xing strips for mounting horizontal units H002
Long desk clamp for mounting vertical units at an angle on desk V010

50

050_051 Electrak 2014 v2.indd 50 27/08/2014 14:51


Intersoc on-desk modules
with twin outlet USB charger (31 A)

Pre-wired with Pre-wired with Pre-wired with


3 m ex and 15 m ex and 15 m ex and
BS 1363 plug GST connector Intersoc-R connector

Description Cat. No. Cat. No. Cat. No.

Horizontal unit with 1 x unfused socket plus twin


HA3012AA HB1012AA HD1012AA
outlet USB charger

Horizontal unit with 2 x sockets individually fused


HA3322AA HB1322AA HD1322AA
at 315 A plus twin outlet USB charger

Horizontal unit with 3 x sockets individually fused


HA3332AA HB1332AA HD1332AA
at 315 A plus twin outlet USB charger

Vertical unit with 1 x unfused socket plus twin


VA3012AA VB1012AA VD1012AA
outlet USB charger

Vertical unit with 2 x sockets individually fused at


VA3322AA VB1322AA VD1322AA
315 A plus twin outlet USB charger

Vertical unit with 3 x sockets individually fused at


VA3332AA VB1332AA VD1332AA
315 A plus twin outlet USB charger

Vertical unit with 1 x unfused socket, twin outlet


USB charger plus 1 x rear pluggable CAT 5 / VA3012AB VB1012AB VD1012AB
CAT 6 RJ45 outlet
Vertical unit with 1 x unfused socket, twin outlet
USB charger plus 2 x rear pluggable CAT 5 / VA3012AC VB1012AC VD1012AC
CAT 6 RJ45 outlets
Vertical unit with 1 x unfused socket, twin outlet
USB charger plus 1 x rear pluggable data VA3012AD VB1012AD VD1012AD
USB outlet
Vertical unit with 1 x unfused socket, twin outlet
USB charger plus 2 x rear pluggable data VA3012AE VB1012AE VD1012AE
USB outlets
Vertical unit with 2 x sockets individually fused at
315 A, twin outlet USB charger plus 1 x rear VA3322AB VB1322AB VD1322AB
pluggable CAT 5 / CAT 6 RJ45 outlet
Vertical unit with 2 x sockets individually fused at
315 A, twin outlet USB charger plus 2 x rear VA3322AC VB1322AC VD1322AC
pluggable CAT 5 / CAT 6 RJ45 outlets
Vertical unit with 2 x sockets individually fused at
315 A, twin outlet USB charger plus 1 x rear VA3322AD VB1322AD VD1322AD
pluggable data USB outlet
Vertical unit with 2 x sockets individually fused at
315 A, twin outlet USB charger plus 2 x rear VA3322AE VB1322AE VD1322AE
pluggable data USB outlets
Vertical unit with 2 x sockets individually fused at
315 A, twin outlet USB charger plus 1 x CAT 6A VA3322AF VB1322AF VD1322AF
RJ45 outlet with 3 m data lead
Vertical unit with 2 x sockets individually fused at
315 A, twin outlet USB charger plus 2 x CAT 6A VA3322AG VB1322AG VD1322AG
RJ45 outlets with 3 m data leads
Vertical unit with 2 x sockets individually fused at
315 A, twin outlet USB charger plus carrier to VA3322AK VB1322AK VD1322AK
accept 1 x Euro Module (25 x 50 mm)
Vertical unit with 2 x sockets individually fused at
315 A, twin outlet USB charger plus double VA3322AL VB1322AL VD1322AL
carrier to accept 2 x Euro Modules (50 x 50 mm)

Note:
All sockets are individually fused at 315 A and mounted at 45 (except units with a single socket outlet which will be unfused and mounted at 90).
Other options are available to special order. Contact us on +44(0) 845 600 6266
CAT 5 / CAT 6 outlets have a rear facing RJ45 that will accept either CAT 5 or CAT 6 data cabling (no data cabling is included with the product)
CAT 6A outlets are supplied with 3 m pre-wired lead and performance certicate
The twin outlet charging USB can supply 31 A shared between the 2 outlets
The data USB outlets have a short ying lead and type-A receptacle at the rear for USB connection to the PC (no USB cabling is included with the product)
Units supplied with carriers to accept Euro modules will be supplied with apertures at the rear for the passing of data or AV cables

51

050_051 Electrak 2014 v2.indd 51 27/08/2014 14:52


Intersoc on-desk modules
technical information

n On-desk dimensions (mm)


Horizontal units Unit with 2 x sockets

40

100

130
Vertical units 178

30

Unit with 2 x sockets plus twin


outlet USB charger
10
0

50

Unit with 3 x sockets


185
178

Unit with 2 x sockets plus 1 x CAT 5 /


CAT 6 RJ45 outlet
195
243

Unit with 4 x sockets


1825
2305

Unit with 2 x sockets plus 2 x CAT 5 /


CAT 6 RJ45 outlets
260
308

205
253

All dimensions (mm) are nominal

52

052_053 Electrak 2014 v2.indd 52 27/08/2014 13:01


n On-desk dimensions (mm) (continued) n Testing and accreditation
Unit with 2 x sockets plus 1 x CAT 6A
RJ45 outlet

Complies with BS 5733 and relevant parts of BS 1363-2


Manufactured within an approved ISO 9001 : 2008 and
ISO 14001 : 2004 facility
205

n BS 6396 : 2008
253

Electrical Systems in Office Furniture and Educational Furniture


Specification
Unit with 2 x sockets plus 2 x CAT 6A
RJ45 outlets Below is a brief outline of the main criteria within the standard :

BS 6396 : 2008 was published with regard to the use of electrical


equipment within general office and educational furniture. This
standard sets out in its scope the use and testing of electrical socket
outlets and associated wiring when used together with a 13 A BS 1363
fused plug for mains supply and makes provision for the routing of
cables through furniture
260
308 For compliance with this standard, socket outlet configurations of up
to 4 outlets should be individually fused at 5 A and up to 6 outlets
individually fused at 315 A
Unit with 2 x sockets plus carrier for A note on individual socket fusing BS 6396 Compliance :
Euro Module (25 x 50 mm)
The standard requires individual socket fusing (as per the table below)

Total number of Individually fused


sockets at
2, 3 or 4 sockets 5A
5 or 6 sockets 315 A
190
238

Material specification

Unit with 2 x sockets plus carrier for Module housing aluminium


Euro Modules (50 x 50 mm) Module fascia polycarbonate
Socket outlets polycarbonate
End caps flame retardant ABS

USB charger module specification


215
263 Supply voltage (nominal) 230 V (AC)
Supply current 13 mA
Power consumption (max.) 03 W
Frequency 50 Hz
Output voltage +50 V 025 (DC)
Output current : 3A
Output power : 15 W (max.)
Over current protection : 38 A (max.)
Output connector : 2 x USB Type A sockets
Current per socket : 2 A (max.)

All dimensions (mm) are nominal

53

052_053 Electrak 2014 v2.indd 53 27/08/2014 13:02


Contact details
Quotations and Technical Support:
Legrand Electric Ltd.
Great King Street North,
Birmingham, B19 2LF
Tel: +44 (0) 845 600 6266
Fax: +44 (0) 845 600 6760
E-mail: [email protected]
Customer Services:
Legrand Electric Ltd.
No. 1 Industrial Estate,
Medomsley Road, Consett,
County Durham, DH8 6SR
Tel: +44 (0) 845 600 6266
Fax: +44 (0) 845 600 6366
E-mail: [email protected]
Accounts:
Legrand Electric Ltd.
Great King Street North,
Birmingham, B19 2LF
Tel: +44 (0) 870 608 9000
Fax: +44 (0) 870 608 9004

FOLLOW
US AT
www.legrand.co.uk
www.legrand.ie

www.youtube.com/legrandtvuk
www.twitter.com/legranduk

www.voltimum.co.uk
www.voltimum.ie

Electrak workstation power system guide 08/2014.5K

Head office (UK and Ireland):


Legrand Electric Limited
Great King Street North, Birmingham, B19 2LF
Tel: 0870 608 9000 Fax: 0870 608 9004
Website: www.legrand.co.uk

The Legrand logo is a registered trademark


This document is printed on sustainably sourced paper. Please recycle. of the Legrand group of companies.

You might also like