Pcs7 Compendium Part D en-US en-US
Pcs7 Compendium Part D en-US en-US
Pcs7 Compendium Part D en-US en-US
___________________
Operation and Maintenance (V8.1) 2
___________________
What's new?
___________________
Replacing hardware 4
Process Control System PCS 7
Compendium Part D Firmware update of
___________________
hardware 5
Operation and Maintenance (V8.1)
___________________
Service and maintenance of
SIMATIC PDM 6
Operating Manual
___________________
AS and OS expansions 7
___________________
Backing up and restoring
data 8
01/2015
A5E35031848-AA
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
1 Preface ................................................................................................................................................... 7
2 What's new? ......................................................................................................................................... 10
3 Installing updates and service packs ..................................................................................................... 11
3.1 Introduction ............................................................................................................................ 11
3.1.1 General .................................................................................................................................. 11
3.1.2 What must necessarily be taken into account? ..................................................................... 12
3.1.3 Differences between maintenance and a software update with the redundant OS
server ..................................................................................................................................... 14
3.2 Checking plant configuration.................................................................................................. 15
3.3 Checking plant status ............................................................................................................. 17
3.3.1 General .................................................................................................................................. 17
3.3.2 Status of PC stations using SIMATIC Shell ........................................................................... 17
3.3.3 Time synchronization ............................................................................................................. 19
3.3.4 Status of OS connections ...................................................................................................... 19
3.3.5 Standard server settings ........................................................................................................ 22
3.3.6 Preferred server settings ........................................................................................................ 24
3.3.7 Redundancy status on the OS server .................................................................................... 26
3.3.8 Client-server connections ...................................................................................................... 29
3.3.9 Archive synchronization of the redundant OS server after a hot restart of the standby
server ..................................................................................................................................... 30
3.3.10 Process control messages ..................................................................................................... 32
3.4 Checking the WinCC channel diagnostics ............................................................................. 32
3.5 Checking the OS functionality after restarting an OS server ................................................. 35
3.6 Deactivating and activating non-redundant OS servers ........................................................ 36
3.7 Deactivating and activating redundant OS servers................................................................ 37
3.8 Additional Information ............................................................................................................ 38
4 Replacing hardware .............................................................................................................................. 39
4.1 Use of new hardware ............................................................................................................. 41
4.2 Deploying new hardware as replacement .............................................................................. 44
4.3 Procedure for replacing hardware.......................................................................................... 45
Checklists
You can download the checklist for the SIMATIC PCS 7 compendium part D (V8.1) as a zip
file via the "Info" button on the entries page.
Validity
This documentation is valid for the software packages:
SIMATIC PCS 7 V8.1
Additional support
If this manual does not contain the answers to any questions you may have about how to
use the products described, please contact your local Siemens representative.
You can locate your contact at http://www.siemens.com/automation/partner.
You can find a guide to the technical documentation available for individual SIMATIC
products and systems at http://www.siemens.de/simatic-tech-doku-portal.
The online catalog and online ordering system are available at
www.siemens.com/industrymall.
Training center
Siemens offers a number of training courses to familiarize you with the SIMATIC PCS 7
process control system. Contact your regional training center or the main training center in
Nuremberg, 90327, Germany (http://www.sitrain.com).
Technical support
You can contact technical support for all Industry Automation and Drive Technology products
using the Support Request web form http://www.siemens.de/automation/support-request.
More information about our technical support services is available on the Internet at
http://support.automation.siemens.com/WW/view/en/16604318.
3.1.1 General
One scenario which may arise within a PCS 7 plant is the need to install updates or service
packs safely and effectively.
Updates may be:
PCS 7 updates
PCS 7 service packs
Microsoft updates
Antivirus software updates
Other software updates
Compendium Part D focuses on the preparations and checks which you need to make
before you start to install PCS 7 updates and service packs or maintain PCS 7 plant
sections. The information applies in particular to redundant plant sections which are to be
maintained or upgraded during operation.
Note
You can find practical information and brief instructions for the PCS 7 software update in the
document "Information and brief instructions for updating/upgrading PCS 7 software"
(http://support.automation.siemens.com/WW/view/en/39980937).
The procedure for updating software in the context of a PCS 7 project is described in detail
in the following documents:
"SIMATIC Process Control System PCS 7 Software update without utilization of new
functions" (http://support.automation.siemens.com/WW/view/en/90682681)
"SIMATIC Process Control System PCS 7 Software update with utilization of new
functions" (http://support.automation.siemens.com/WW/view/en/90683053)
"SIMATIC Process Control System PCS 7 Fault-tolerant Process Control Systems"
(http://support.automation.siemens.com/WW/view/en/90682535)
You can find information about Microsoft updates and antivirus software in the following
sources:
FAQ "With what are SIMATIC PCS 7 V8.x, V7.x, V 6.x, V5.x and V4.x compatible?"
(http://support.automation.siemens.com/WW/view/en/64847781)
FAQ "Which Microsoft Security Patches have been tested for compatibility with SIMATIC
PCS 7?" (http://support.automation.siemens.com/WW/view/en/18490004)
SIMATIC Process Control System PCS 7 Security concept PCS 7 & WinCC (Basic)
(http://support.automation.siemens.com/WW/view/en/60119725)
SIMATIC Process Control System PCS 7 Trend Micro OfficeScan 11 Configuration
(http://support.automation.siemens.com/WW/view/en/103630611)
Symantec Endpoint Protection V12.1.4 configuration
(http://support.automation.siemens.com/WW/view/en/71874887)
Use of Whitelisting with McAfee Application Control in the PCS 7- / WinCC environment
(http://support.automation.siemens.com/WW/view/en/88653385)
SIMATIC Process Control System PCS 7 Configuration McAfee VirusScan Enterprise 8.8
White Paper (http://support.automation.siemens.com/WW/view/en/66475606)
Whitepaper: "Security Concept PCS 7 and WinCC (Basic)"
(http://support.automation.siemens.com/WW/view/en/60119725)
Process availability
Operator control and monitoring functions often must continue to run, thus ensuring that the
PCS 7 plant operates safely, while such actions are being performed. The following sections
describe checks, which we recommend you carry out before, during, and after an update or
maintenance work.
If it is necessary to restore the plant to the same state it had before the update or service
pack was installed, we strongly recommend that you back up all computers (including the
ES) and the PCS 7 multi-project or keep the backup available. You can find details on this in
the section titled "Backing up and restoring data" (Page 101).
Make sure that all software products and information required to carry out the update, such
as additional software, libraries, add-ons, information about non-standard functions within
the project, modified system pictures, or other data specific to the plant, etc. are available. All
project-specific settings, such as PC, network, web server and archiving system, should also
be known. You need to verify this information with the plant operator in advance, because
there may have been changes to the PCS 7 plant since its initial installation/most recent
update.
Plant status
You should always evaluate the plant status before you start starting work on OS stations in
Runtime.
Is the OS server system in a redundant status?
Do all clients have a connection to the OS servers?
Only if you can answer "yes" to these two questions can you start the scheduled update.
You should carry out specific intermediate checks while the relevant work is being
performed. You should carry out these checks while updating the PCS 7 project on the ES,
but they should also be performed on the updated OS stations in the plant.
For example, you first install a new PCS 7 service pack on a redundant partner and the
associated OS clients. Then you check whether the plant can be operator-controlled on the
updated stations. If this test is successful, you can continue with the work and update the
remaining OS stations.
After the work has been completed successfully, you must perform a full check of the plant
redundancy status and its operator control and monitoring functionality.
Note
A guide to checking the redundancy status is available in the section titled "Checking the OS
functionality after restarting an OS server" (Page 35).
Coordination of timings
You must make sure that matters are organized such that maintenance work is not carried
out on redundant components simultaneously. Actions of this type must be coordinated so
that they are performed one after the other and they must not overlap.
Also note the following regarding the update sequence of the PCS 7 stations:
Before you start to update the OS stations (Runtime), you must have already updated the ES
itself with a new PCS 7 service pack, for example, as well as the PCS 7 project. As part of
this process, it is essential that you have compiled all AS and OS stations with the new PCS
7 service pack for the entire PCS 7 project. We always recommend that you carry out an OS
simulation or a brief test (for example, download the target system for AS and OS in a testing
environment) before starting work on a running plant.
Note
You can find a summary of the individual check points in the "PCS 7 delta configuration"
checklist that is part of the PCS 7 Compendium Part D.
3.1.3 Differences between maintenance and a software update with the redundant
OS server
Maintenance
In this context, maintenance is considered a task performed when the OS server is
deactivated and in which the OS software version is not changed. This may involve cleaning
the OS server hardware, for example.
When deactivating a redundant OS server, you must not allow all OS clients to switch from
the master server to the standby server at the same time, because this would render the
plant inoperable for the duration of the switchover.
Configuring a preferred server for the OS clients enables you to achieve even distribution
across the master and standby servers. If one of the OS servers is deactivated, only half of
the OS clients will switch to the partner server.
Software update
You must install the same software version on the OS servers and the OS clients connected
to them.
The standby OS server is usually deactivated first and its software updated. Before you
deactivate the standby OS server you must check that the master OS server is fully
functional and a sufficient number of functional OS clients must be connected to that master
OS server.
First update only the OS clients which are interconnected with the standby OS server that
has already been updated or which have defined it as their preferred server. Then update
the OS clients which are interconnected with the master OS server or which have defined it
as their preferred server.
This method is not practical if the maximum number of OS clients must be available for
operator control and monitoring purposes during the software update. In this case, all OS
clients must first be connected to the master server by configuring the preferred server. The
standby server is then deactivated, the OS software updated, and the server started again.
The next step involves deactivating each OS client one after the other, updating the
software, and then connecting each OS client to the standby server by configuring the
preferred server. Once each OS client has been updated, check that its operator control and
monitoring functions are working correctly.
Once all OS clients with their new software version have been connected to the standby
server, the master server will be deactivated and its software updated.
Once the software has the same version on the redundant OS server and all OS clients, the
OS clients can be distributed between the master and standby servers by configuring the
preferred server.
Note
In order to guarantee the continuous operator control and monitoring capabilities, the
following conditions must be fulfilled:
Before downloading the AS: Operate and monitor the processes through the operator
stations, whose software has not yet been updated.
After downloading the AS: Operate and monitor the processes through the operator
stations, whose software has been updated.
Note
Depending on the plant configuration, the additional measures for activating and
deactivating an OS server may vary.
You should consult with the system administrator responsible for SIMATIC BATCH,
SIMATIC Route Control, PH (Process Historian), MES and other systems to define the
measures that need to be introduced. Also refer to the respective product manuals in this
regard.
Note
The system configuration can be checked by the SIMATIC Management Console
(inventory function). You will find further information in the "SIMATIC Process Control
System PCS 7 SIMATIC Management Console (V8.1)"
(http://support.automation.siemens.com/WW/view/en/90683240) operating manual.
3.3.1 General
To check the current plant status, we recommend carrying out these tests on the OS server
and the OS client directly, as settings may also have been changed directly on the Runtime
computers.
Certain checks must be performed in the WinCC Explorer, which means it will have to be
accessed. If access to the WinCC Explorer is blocked by OS Runtime, you will have to
terminate OS Runtime mode. In this case, we recommend first carrying out all plant status
checks which can be performed during OS server/OS client Runtime, before terminating that
mode.
If settings need to be changed on the OS server or the OS client directly, you must also
incorporate the changes on the ES. This means there will be no difference between the PCS
7 project on the ES and the data on the Runtime system, plus the changes will not be lost
when the Runtime system is loaded again.
Note
The state monitoring (check for installation readiness) can also be performed with the aid of
SIMATIC Management Console. You will find additional information on this in the "SIMATIC
Process Control System PCS 7 SIMATIC Management Console (V8.1)"
(http://support.automation.siemens.com/WW/view/en/90683240) manual.
Procedure
1. Open the Windows Explorer on the ES.
2. Select the folder "My Computer > Simatic Shell" in the tree view.
Note
You can use the shortcut menu, for example, to check the redundant connection to the
partner server on an OS server via the menu command "Redundancy Settings".
Note
You can find more detailed information in the manual titled "SIMATIC Process Control
System PCS 7 - Service Support and Diagnostics"
(http://support.automation.siemens.com/WW/view/en/90682682) and in the WinCC online
help.
Note
The manual titled "SIMATIC Process Control System PCS 7 - Time Synchronization"
(http://support.automation.siemens.com/WW/view/en/90682531) contains more detailed
information on the topic of "time synchronization".
Procedure
1. Open the WinCC Explorer on the OS server. The OS project must be in Runtime on the
server.
2. Select the menu command "Options > Status - Connections".
3. Check the entries in the "Status" column. The "Cleared" entry may indicate an error in the
configuration or hardware.
General information
As a general rule, only a standard server for alarms, the SSM (Split Screen Manager) and
optionally also for user archives is configured for PCS 7.
Standard servers are configured in the "Server Data > Standard Server" menu of the WinCC
Explorer. Such configurations are usually set on the ES and then loaded to the OS client.
Configured standard servers must be checked on the OS client directly, as settings may also
have been changed directly on the OS client. The WinCC Explorer needs to be accessed on
the OS client for this purpose.
The standard server must be checked on every OS client. If deviating settings do arise, the
ES project must be adjusted.
Alarms
If you want to generate operator messages for operations on an OS client, you will have to
specify a standard server for alarms. You cannot configure alarm logging on the OS client
itself. The messages must be archived on an OS server.
Example
Scenario
A PCS 7 plant contains three non-redundant OS servers. The server data from three OS
servers is assigned to an OS client. If a non-redundant OS server has been configured on
the OS client as the standard server for alarms and SSM and this OS server needs to be
deactivated, then:
The OS areas of an OS server not in process mode cannot be operator-controlled.
No operator messages will be generated for the OS areas that can still be operator-
controlled while the server is shut down.
The configured compilations of trends are not available. The same applies to OS servers
still in process mode.
The configured screen compositions are not available. The same applies to OS servers
still in process mode.
You should therefore check if a server is a standard server before deactivating runtime on it.
Deactivation of process mode on the OS server must be timed in such a way that the
functionality it provides will not be missed.
Note
When a redundant OS server is used, the functionality of the standard server will be
maintained only if one computer of the OS server pair is deactivated.
If no standard server is configured for alarms of an OS client, then the OS client will not
generate any operator messages.
Procedure
1. Open the WinCC Explorer on the OS client.
2. Open the "Server Data" shortcut menu.
When attempting to deactivate runtime on one of the two redundant servers, a check is
made in the system to see whether there is a redundancy problem and this will be indicated
in the event of an error.
The following system variables can be checked on the OS server to determine the
redundancy status of the OS server.
On the clients, the status of all the redundant OS server pairs and non-redundant OS servers
downloaded from the packages are displayed in the right-hand part of the area overview:
Green button:
The monitored OS servers are available and are in runtime with the status "OK".
Yellow button:
One server or multiple servers have a problem. The servers are still available for the
clients.
If a server partner is switched off or has an error state and the second server partner also
develops an error state, the second server partner initially remains available for the
connected clients. The second server partner only disconnects the clients if the first server
partner is in an operational state again and has synchronized with the second server partner.
This therefore ensures that the clients can at least connect to this server pair, even if both
server partners have a problem.
Red button:
Not all of the monitored OS servers are in runtime.
Not all of the monitored OS servers have the status "OK".
Not all of the monitored OS servers have a fault-free network connection.
No button:
The process "CCEmergencyWatchRTServer.exe" is missing from the startup list on the OS
client.
No packages are loaded on the OS client.
Note
You can find further information in the FAQ "On the WinCC client, how do you establish
which server this is connected to?"
(http://support.automation.siemens.com/WW/view/en/26412141).
3.3.9 Archive synchronization of the redundant OS server after a hot restart of the
standby server
Scenario
Server A is the master server and server B is the standby server. Maintenance work needs
to be performed on the redundant OS server. No preferred server is configured for OS
clients; the OS clients are therefore connected to the master server.
To avoid an unnecessary redundancy switchover of the OS clients, the standby server will
be deactivated first in this case. Once the maintenance work is complete, server B will be
restarted.
A time window of two hours is required for the maintenance work. Within this time window,
the TagLogging and AlarmLogging values have only been archived by server A.
Before you deactivate server A for the required maintenance work, you need to ensure that
archive synchronization has been completed in full.
Note
If server A is deactivated before the archive synchronization is complete, data loss can occur
as a consequence.
The redundancy option of the PCS 7 OS provides a series of system messages. You need to
evaluate the following system messages to determine whether or not archive
synchronization has been successfully completed.
Example
In process mode, open the process control message list with the OS client button shown
below:
The process control messages generated by OS redundancy all start with the string
"REDRT" in the event text. If you configure a user filter with this string, it will facilitate the
search for the relevant messages.
Create a filter with the string "REDRT":
Result
Filtered process control list with messages generated by OS redundancy.
The archive synchronization procedure starts automatically ten minutes after the standby
server has undergone a hot restart.
Note
You can find a list of system messages and a general definition of the measures that need to
be taken in the FAQ "What are the causes of PCS 7 control technology and system
messages and what measures are to be taken to clear them?"
(http://support.automation.siemens.com/WW/view/en/37696303).
Scenario
A redundant OS server needs to be serviced. The standby server has lost the connection to
the AS. If the master server is deactivated in this situation, the plant can no longer be
operator-controlled because the standby server has not established process communication.
To avoid this situation, you need to check the process control message list before
deactivating an OS server and resolve the causes of critical messages that are still relevant.
It helps here to filter the process control list for the name of the computer you want to
service.
Icon Description
Channel / connection operational with no restriction
Procedure
1. Start the "Channel Diagnosis" WinCC channel diagnostics on the activated OS server
with the Start menu command "SIMATIC > WinCC > Tools > Channel Diagnosis".
Operation of the Start menu via the OS must not be blocked for this procedure to work.
2. The application window for "Channel Diagnosis" opens.
The left section of the "Channels/Connections" tab shows the status information for all
installed channels and their connections.
3. Check the icons next to the "SIMATIC S7 Protocol Suite" channel name and the
connection.
The status of the channel or the connection is correct when a green check mark is
displayed in front of the respective entry. The meaning of the icons are available in the
table "Overview of status displays."
4. If there is no green check mark in front of the name of channel and connection, select the
connection in the left window. Check the entries of the counters "First Error Code" and
"Last Error Code" in the right window. The entries provide information about errors
detected.
The shortcut menu of the value display provides you with direct help.
5. On the "Configuration" tab, select the status and error displays that you want to output to
the log file. To do this, select the "SIMATIC S7 Protocol Suite" channel and configure the
error displays.
You can find a description of this process under the topic "How to configure the trace
function of a channel" in the WinCC online help.
6. Check the channel-specific log file. To do this, open the file at "<Installation
directory>\WinCC\Diagnostics" in a text editor. Check the latest entries with the "ERROR"
flag. You can find a description of this step under the topic "Description of the entries in
the log file" in the WinCC online help.
7. If the error cannot be located even after checking the log file, contact the Customer
Support Team.
Note
You can find more information on the topic of "Channel Diagnosis" in the WinCC online
help.
Deactivating
If a non-redundant OS server is deactivated, process operation cannot continue with the
corresponding OS clients.
1. Check to determine when the OS server function will not be necessary.
2. Check the configuration of the PCS 7 plant.
3. Check the plant status of the PCS 7 plant.
4. Check that the OS server is functioning correctly with the help of an OS client.
5. Deactivate the runtime of the OS server.
Note
In the case of a server shutdown you can, for example, operate an OS single station
system in parallel to the OS server for emergency operation. The PCS 7 engineering
system does not support synchronization of the OS server and the OS single station
system in the PCS 7 project.
The OS single station system must be fully installed, configured, and licensed for
emergency operation.
Activating
The functionality of the client-server system needs to be checked once the OS server has
been activated. Read the section titled "Checking the OS functionality after restarting an OS
server (Page 35)" for more information.
Procedure
1. Open the OS project on the OS server.
2. Activate Runtime on the OS server.
3. Check that the OS server is operating correctly.
Deactivating
To safeguard process operation on a permanent basis, you should never deactivate both
computers of a redundant OS server pair at the same time. You must always deactivate the
standby server first.
1. Check the configuration of the PCS 7 plant.
2. Check that the OS clients are configured correctly.
3. Check the plant status of the PCS 7 plant.
4. Check that the redundant OS server is operating correctly.
5. Deactivate Runtime on the standby OS server.
6. Check that the plant is operating correctly without an available standby OS server.
Activating
When activating redundant servers, it is important to ensure that the first server has been
fully activated before activating the redundancy partner.
No client should be running before the servers are activated for the first time. The OS clients
can then be activated.
The functionality of the client-server system needs to be checked once the OS server has
been activated.
Read the section titled "Checking the OS functionality after restarting an OS server
(Page 35)" for more information.
1. Check that the OS server is configured correctly.
2. Check that the OS clients are configured correctly.
3. Check the plant status of the PCS 7 plant.
4. Open the WinCC project on the standby OS server.
5. Activate Runtime of the OS server, if an automatic start has not been configured.
6. Check that the OS server and connected OS clients are operating correctly.
7. Check the archive synchronization of the redundant OS server.
Note
If you have a defective module, please contact your regional Siemens representative so that
the module can be replaced as soon as possible. You can find further information on support
with spare parts under (http://support.automation.siemens.com/DE/view/en/16611927).
The replacement modules must be approved for use with the respective PCS 7 version. The
manual "SIMATIC Process Control System PCS 7 Released Modules"
(http://support.automation.siemens.com/WW/view/en/103151431) and the PCS 7 V8.1
readme file (online) (http://support.automation.siemens.com/WW/view/en/101094704) for
each PCS 7 version provide information about the approval status. Components must
always be replaced with identical models (identical MLFB).
If listed modules are no longer available, successor modules should be installed; these need
to be explicitly compatible as replacements. Information about whether or not a new module
is compatible as a replacement is available on the delivery release, as shown in the figure
below, which uses HART analog modules as an example.
Redundancy
If a redundant component fails and a successor module or a new hardware or firmware
version is used, the partner component will also need to be upgraded to the same type. See
the section titled "Procedure for replacing hardware (Page 45)" for more information.
Procedure
You need to determine if scenario 1 is applicable for the PCS 7 version you are using. If this
is not the case, scenario 2 applies automatically. Use the checklist to perform the check for
each type of module according to the section titled "Replacing hardware".
Note
The replacement part scenario (case 2) is always possible, even if new functions (case 1)
could be used but you do not wish to change the configuration.
Definition
HSP Hardware Support Package
Software package installed in HW Config; facilitates the configuration of new hardware.
Note
New HSPs are released together with new STEP 7 versions. Never install a STEP 7 version
which is more recent than the one officially released for the PCS 7 version to use these
HSPs.
Note
These module drivers and their proper integration into the S7 program form the basis of
hardware component diagnostics and status information.
Product Modules
CPU 41X-? H V4.5 6ES7 412-3HJ14-0AB0, 6ES7 414-4HJ14-0AB0,
6ES7 417-4HT14-0AB0,
CPU 41X-???04 V4.0 / V4.1 6ES7 414-3XJ04-0AB0, 6ES7 416-2XK04-0AB0,
6ES7 416-3XL04-0AB0, 6ES7 417-4XL04-0AB0,
6ES7 414-4HJ04-0AB0, 6ES7 417-4HL04-0AB0,
The "Readme.txt" file contains concrete information about the additional release of H-CPU
V4.5. The HSP and the required meta information will be supplied as software as of PCS 7
V6.1 SP2.
The following overview of the release schedule should clarify this point:
The order of the delivery releases shows that H-CPU V4.5 can only be used with its full
range of functions starting with PCS 7 V6.1 SP2 or V7.0 SP1. The HSP of H-CPU V4.5 was
officially released only for PCS 7 V7.0 SP1. The H-CPU must be operated as a replacement
for PCS 7 V6.1 SP1. We recommend an upgrade to PCS 7 V6.1 SP2.
New functions such as "firmware update in RUN" can only be used because you can now
configure the H-CPU V4.5 in PCS 7.
None of this is possible in PCS 7 V6.1 SP1 or V7.0. The H-CPU V4.5 is used as a
replacement component here (see section (Page 44)).
Redundancy
If an HUP/HSP is used in a PCS 7 project for redundant components, such as H-CPU or IM
153-2, you will have to replace both redundant components during a maintenance interval.
Note
The following always applies when replacing hardware: The old hardware component has
been configured and the new hardware component which is compatible as a replacement is
then deployed.
When a new hardware component is deployed as a replacement, it will not be possible to
use its advanced functions.
Product Modules
ET 200M IM 153-2BAx1 * 6GK7 153-2BA01-0XB0;
6GK7 153-2BA81-0XB0
ET 200M IM 153-2BAx2 * 6GK7 153-2BA02-0XB0,
6GK7 153-2BA82-0XB0
Redundancy
If new hardware is used to replace redundant components such as H-CPU or IM 153-2, you
will have to replace both redundant components during a maintenance interval.
Note
If a redundant module is defective, the same module type and firmware version must be
used to ensure that process mode will not be disrupted.
NOTICE
Only make changes to a plant during operation if no redundancy faults are present, i.e. the
REDF LED is not lit, and you have ensured that both IMs for all stations connected
redundantly (e.g. ET 200M) are in fault-free mode. Otherwise, process mode may be
disrupted.
Procedure
The exact procedure for a specific component is provided in its accompanying manual. The
table below provides information about the relevant components and associated manuals.
Note
Plan your firmware update in such a way that the plant operator control and monitoring
functions remain uninterrupted.
For example, when updating the firmware of a redundant CPU and its CP it is not advisable
to deactivate the connected redundant OS servers at the same time to perform maintenance
on them. Coordinate such actions so they are carried out one after the other.
NOTICE
System change
Only make a system change during operation if no redundancy errors are present; i.e. the
REDF LED is not lit, and you have ensured that both IMs for all stations connected
redundantly (e.g. ET 200M) are in error-free operation. Otherwise, process mode may be
disrupted.
NOTICE
Only update firmware during operation if no redundancy faults are present, i.e. the REDF
LED is not lit, and you have ensured that both IMs for all stations connected redundantly
(e.g. ET 200M) are in fault-free mode. Otherwise, process mode may be disrupted.
Requirements
The requirements and steps needed for updating an interface module are described in the
manual titled "SIMATIC Process Control System PCS 7 Service Support and Diagnostics"
for the respective PCS 7 version.
You can find more information in the following manuals:
ET 200M (http://support.automation.siemens.com/WW/view/en/1142798)
ET 200S (http://support.automation.siemens.com/WW/view/en/19728475)
ET 200SP (http://support.automation.siemens.com/WW/view/en/58649293)
ET 200iSP (http://support.automation.siemens.com/en/view/en/98821323)
ET 200pro (http://support.automation.siemens.com/WW/view/en/21210852)
DP/PA Link and Y Link (http://support.automation.siemens.com/WW/view/en/1142696)
NOTICE
If the "Update firmware after downloading" box is checked, the IM will restart once the
firmware has been downloaded, which will cause the ET 200 station to fail temporarily.
NOTICE
Before you begin the update, make sure that both IMs are in redundant mode.
The PROFIBUS DP cable is plugged in at both ends.
Both IMs are plugged in.
The IMs and modules do not indicate any faults.
Otherwise, the station will briefly fail after the restart instead of switching over.
Example: SM 331 AI 6 x TC
The firmware can be updated via HW Config for electrically isolated analog input module
60331; AI 6 x TC (6ES7331-7PE10-0AB0). See the manual titled "SIMATIC S7-300 S7-300
Automation System Module Data"
(http://support.automation.siemens.com/WW/view/en/8859629) for more details.
Note
HCF DDs are part of the HCF DD library and can be used in PDM and in handheld
communicators. These device descriptions may only be imported into PDM from the
device catalog supplied.
Every PDM software version is delivered together with a device catalog. Each combination
has been tested and released. The version of the device catalog is listed in the "Readme" of
the PDM version under "Scope of delivery".
Note
The device catalog CD (device library) that ships with the product varies according to the
SIMATIC PDM delivery version; e.g. SIMATIC PDM V8.0 and SIMATIC PDM V8.2.
New device descriptions may have been added or existing ones removed or updated. For
this reason, you should retain the device catalogs used.
The following device descriptions are supplied with the device catalog:
Device descriptions for Siemens field devices
Device descriptions for released HCF (HART Communication Foundation) field devices
Device descriptions for released field devices of the FF (Fieldbus Foundation)
Device descriptions for field devices from third-party manufacturers
Universal device description for HART
Profile device description for PROFIBUS DP/PA field devices
Profile device description for PROFINET field devices
If your project contains device types for which no device descriptions are provided in the
device catalog supplied, you can import the necessary device descriptions from older
delivery versions of the device catalog.
Note
Only import individual device descriptions from previous delivery versions of the device
catalog and never the entire catalog.
The import of device descriptions of a newer device catalog is only permitted if this device
catalog is released for your SIMATIC PDM version. You can find this information in the
"pdmdevices-Readme" document.
Additional device descriptions can be obtained from other sources and imported in the same
way as the device catalog. Other sources are:
Downloads from manufacturer website
Data carrier supplied with the field device
Save these device descriptions (data) as well. We recommend that you keep a collection of
all device descriptions. Note that you will have to extract devices from external sources prior
to import and that you may have to import them individually.
Use the same PDM software version and uniform device descriptions in every PCS 7 ES.
Follow the steps given above to import device descriptions.
Note
In the device integration manager, you can create a printout of the integrated device
descriptions via the menu command "File > Print Device List".
You will find further functions of the Device Integration Manager in the
"SIMATIC Process Control System PCS 7 SIMATIC PDM 8.2"
(http://support.automation.siemens.com/WW/view/en/90682678) operating manual.
Example for the FDC 157-0 device (PROFIBUS PA) in PDM V8.2
Once the device has been opened with PDM, you will find the DD version and the software
and hardware revision of the device in the parameter view.
Note
Note that the first time you open a device with SIMATIC PDM, its initial values will be
displayed. These values may differ from the actual values in the device. The "Upload to
PC/PG..." function is used to transfer the device parameters to SIMATIC PDM.
In certain cases, values can be changed by means of local operation on the keypad, for
example. These changes will not be shown in SIMATIC PDM until after "Upload to PC/PG"
has been performed.
Detailed information
To obtain detailed information on the EDD in PDM V8.2, open the object properties via the
"Device" menu in the PDM. In the "Device" tab you will find the following information:
Device-type designation
Device DDL
Order number
Manufacturer
DD_Version (DD_Revision)
Device_Type
Device_Revision
Device GSD name EDD name DD version DD_Revision SW/FW Com type
revision of
the device
FDC 157-0 SI028131.GSE SIDP_DPPAK.DDL 1.1.14 14 V 1.0.2 PA
SITRANS T3K PA SIEM8090.GSD SIPA__TTK101.DDL 01.768.06- 6 1.32 PA
04
SIPART PS2 SI028079.GSD SIPA_ACP_PS2A_M.DDL 21.768.6- 6 4.00.00 PA
004
You can use the information gathered, for example, to later search through the detailed
summary of the device catalog "ListOfIntegratedDevices" to find the right EDD version for
your device. You can find this list on the device catalog CD in the "Manuals" folder.
Collecting the data has two advantages:
You can compare the EDD versions specified in the "ListOfIntegratedDevices" catalog
with those used in your project.
Then you only have to import the EDD files required to operate your devices.
Please be aware that your project may contain a device type which has different SW/FW
revisions. The EDD version must always match an SW/FW revision of the device. If an
incorrect EDD is assigned, PDM will detect the deviation and communication with the device
will not be established. As a user you will receive a message from PDM stating which device
it expects and which one it has detected during device identification.
The SIPART PS2 has been configured with the EDD for SW revision 5.00.00. The PDM
device identification function detects that the connected device has a deviating SW revision
of 4.00.00. A project-specific device overview makes clear how the EDD versions and the
SW/FW revisions of the device relate to one another.
Applications
For an update of the PCS 7 ES, the SIMATIC PDM version released for this PCS 7 ES and
the associated device catalog should be installed. You will find further information in the
"PCS 7 Readme" (http://support.automation.siemens.com/WW/view/en/101094704).
Note
Please note the installation requirements when using a more recent PDM version. You can
find more detailed information in the "PDM Readme" ("pdmbase-readme") on your SIMATIC
PDM CD.
1. case:
The project is upgraded to a later PCS 7 version. You need to reinstall the master ES.
2. case:
The project needs to be edited on a different ES. You need to update the installation to
implement the same software version.
Requirement
If the required device descriptions are missing from the PCS 7 ES, it may not be possible to
edit the devices using PDM in the PCS 7 project. If this is the case, check the PDM
installation and verify that all necessary device descriptions have been imported; if they have
not, the error message shown below will appear when the project or HW Config is opened.
HW Config will be opened as read-only in this case. Individual device descriptions will be
missing in most cases.
Procedure
1. Install the PDM version released for the PCS 7 ES and import the device catalog
associated with it (import all devices).
2. Import additional device descriptions which were not imported in the previous step as part
of the PDM device catalog in the same or an updated version.
3. Optional: import individual devices from older PDM device catalogs.
Caution: Selectively import only the missing device descriptions and not the entire
catalog.
4. Open the process device plant view in SIMATIC Manager. Sort the devices to list those
with no description file. You can display the "Devices" column in SIMATIC Manager under
"Options > Settings > Columns > Process Device Plant View".
If no device description has been assigned to a configured device, its symbol will be
displayed in gray. The device description (EDD) file is not installed in this example. You
receive the following message when you double-click on this device:
You can use the Device Integration Manager to display the available and missing device
descriptions in your projects.
Note
A PCS 7 project can contain information about device descriptions which are no longer
used in the project. In this case, you need to carry out a "Save with reorganization" for the
project.
Note
You can find information about the the device description library "SIMATIC PDM Device
Library 1#2014" in the entry http://support.automation.siemens.com/WW/view/en/92561933.
The entry http://support.automation.siemens.com/WW/view/en/92561357 provides the library
for download.
To check the device descriptions, open the "Device Integration Manager" (Start > Device
Integration Manager).
Select the menu command "File > List of integrated device descriptions" to display an
overview of all integrated device descriptions.
Select the menu command "File > List of used device descriptions" and the integrated and
non-integrated (black circle) device descriptions are displayed once you have selected a
project.
Note
In certain cases, it may be that new device descriptions of older software versions of PDM
may not be supported.
The device manufacturer will inform you if a new device description is only supported as of a
particular PDM software version.
Example
Using the example of the SIPART PS2PA positioner 5.00.00, you can see which additional
features a new EDD version provides.
Note
The additional features are available once the SIPART PS2 EDD version 1/21/2008 (not
included in device catalog 01/2009) has been imported.
6.6.1 Scenario 1 - Replacing a device of the same type and with a later version
Note
Please note that replacing the SIPART PS2 HART positioner FW C1 with the FW 4.00.00
version necessitates a parameter check and an initialization.
The "Download to devices..." function transfers the parameters from SIMATIC PDM to the
device.
Note
Please note that the reassignment requires a parameter check.
The "Download to devices..." function transfers the parameters from SIMATIC PDM to the
device.
7. Make the assignment of the new device type. The procedure is described in the section
titled "Scenario 1 - Replacing a device of the same type and with a later version
(Page 67)".
Note
Please note that replacing the device type requires a reassignment of parameters and an
initialization.
The "Download to devices..." function transfers the parameters from SIMATIC PDM to the
device.
The export dialog is opened. Using the export dialog, you can back up the device
parameters and diagnostics and document manager information.
6. Delete the SITRANS LR250 in HW Config. This deletion of the device type is required
because the LR250 and LR260 have different GSD files. The associated PDM object is
automatically deleted with it.
7. Configure the new device type (here an LR260) in HW Config using the backed up
property information (e.g. settings, addresses).
8. Perform the assignment of parameters of the LR260 in the PDM. In so doing, take note of
the procedure for the configuration and parameter assignment of field devices described
in "PCS 7 Compendium Part A" (www.siemens.com/pcs7-documentation). You can also
find further information in the section titled "Changing the AS configuration" (Page 78).
Note
As long as a PDM object is in the PDM database, one PDM tag of the associated license is
used. Devices which are no longer used and which have been backed up must be deleted to
release these PDM tags.
General information
Some plants need to be expanded or modified during operation. This step may be due to the
complexity of the automated process or the high cost associated with restarting.
In PCS 7, changes can be made on a standard AS and on an H system during operation.
The differences between the more flexible H system and a standard AS will be explained in
the following subsections.
The abbreviation CiR (Configuration in RUN) is also used to refer to changes to the
hardware configuration during operation in PCS 7.
Principle
Any changes made to the configuration of a standard AS only relate to the distributed
PROFIBUS I/Os and are implemented via the configuration of "CiR objects" and "CiR
modules", which function as placeholders for future I/O expansions in HW Config.
These placeholders can only be activated for the first time in HW Config and subsequent
changes to properties can only be loaded by stopping the AS.
Therefore, the size of the placeholders should be set prior to commissioning the plant to
ensure there is sufficient space for the planned expansions until the next scheduled AS
STOP.
Every PROFIBUS I/O expansion made during operation reduces the set size incrementally.
At the next scheduled AS STOP the placeholder size can be set according to new targets, as
long as it will not violate the system limits for the CPU and PROFIBUS.
Note
The changes to the configuration for a standard AS are only available after the "Enable CiR"
option is set in HW Config for a respective DP master system and after the configuration has
been loaded in STOP operating mode.
Application field
Typical cases of configuration changes on a standard AS include:
Adding a DP slave or PA slave with the next highest bus address.
Adding a module to the first free slot at the end of a modular station, e.g. ET 200M.
Reassigning parameters for modules within a modular station, e.g. ET 200M (based on
the functions of the module in use).
Removing a DP slave or PA slave with the next highest bus address.
Removing the last configured module in a modular station, e.g. the ET 200M.
You can find an overview of all supported configuration changes in the manual titled
"SIMATIC Process Control System PCS 7 Engineering System"
(http://support.automation.siemens.com/WW/view/en/90663380).
Use the "Save and Compile" function only after successfully downloading the
configuration changes. If you cannot perform the download for some reason, you can
reverse your configuration changes by closing HW Config.
Note
The CiR function only supports addition or deletion for F I/Os. You can find further
information in the section titled "Configuration in Run (CiR)" in the "SIMATIC Industrial
Software S7 F/FH Systems Configuring and Programming"
(http://support.automation.siemens.com/DE/view/en/2201072) manual.
Note
You can find special considerations for using an ET 200iSP on a standard AS described
in the section titled "Configuration changes in RUN" in the "SIMATIC Distributed I/O
ET 200iSP" (http://support.automation.siemens.com/en/view/en/98821323) manual.
Principle
In contrast to a standard AS, the configuration of an H system is changed not via CiR
objects, but by means of a master/standby switchover with the modified configuration. This
means that many of the restrictions described in the previous section do not apply here. This
means changes in HW Config can be downloaded during operation without previously
activating a function.
Application field
Typical cases of configuration changes on an H system:
Adding distributed stations on the PROFIBUS DP or PROFIBUS PA with any bus
address.
Adding more modules within ET 200M at any free slots.
Reassigning parameters for modules within the ET 200M or ET 200isP (based on the
capabilities of the module in use).
Assigning a different process image partition to a module.
Note
You can either add or remove modules during a hardware change. If you want to rebuild
your H system by removing a module type and inserting a new type in its place, you need
to perform two hardware changes one after the other.
Requirements
ET 200M, DP/PA link, and Y link should always be mounted with an active backplane bus
and fully equipped with bus modules, because the bus modules cannot be plugged in or
pulled out during operation.
ET 200iSP is to be equipped with additional terminal modules and fitted with reserve
modules on the free slots, because the terminal modules cannot be plugged in or pulled
out during operation.
Bus cables for PROFIBUS DP and PROFIBUS PA should be provided with active bus
terminating elements at both ends so that the cables are properly terminated even during
the rebuilding period.
PROFIBUS PA bus systems should be built with components from the SplitConnect
product series (see interactive catalog CA01) and active field distributors (AFD, AFDiS
and AFS) so that the lines do not have to be split.
Restrictions
Which parameters cannot be changed during operation of an H system (selection for typical
PCS 7 projects)?
CPU: Activation of process image partition
CPU: Size of maximum local data requirements
Setting for time synchronization
Transmission rate to the DP master systems
Settings on the Ethernet CP and PROFIBUS CP
Changes to the I/O addresses
Note
If a fault is pending on an interface module, the master/standby switchover will cause the
system to indicate a station failure of the DP slave concerned when the configuration is
downloaded in RUN.
As of PCS 7 V7.0 SP2, related problems with the signal modules concerned are resolved
automatically as soon as the configuration change is active.
With older PCS 7 versions, the ACC input must first be set on the MOD_D1 driver blocks
concerned to ensure that these problems will be resolved.
All changes must be downloaded via HW Config using "Download station configuration in
RUN mode". The "Compile and download objects" function in SIMATIC Manager cannot
be used for this purpose.
Procedure
As of PCS 7 V6.1 SP1, the required tasks are performed automatically for the most part via
the dialog that appears after you have selected the "Download station configuration in RUN
mode" function in HW Config.
Use the "Save and Compile" function only after successfully downloading the configuration
changes. If you cannot perform the download for some reason or if the H system no longer
goes into the "RUN Redundant" state, you can reverse your configuration changes by
closing HW Config.
Deleting a connection
Once a connection has been deleted, you need to highlight the corresponding station and
run the "Download Connections and Gateways" function. This downloads the entire
connection configuration to the AS.
This function can also be performed when the CPU is in the RUN(P) operating mode. Check
the effects on the process in advance and change the charts associated with the connection
prior to the deletion.
Note
Downloading the network configuration using the "Selected Station", "Selected Station and
Partner Station", and " Stations on the Subnet" menu commands can only be performed
when the AS is in STOP.
The basics for program changes, especially the rules regarding maintaining delta download
capability, are described in the section titled "Download" in the "SIMATIC Process Control
System PCS 7 CFC for SIMATIC S7" (http://support.automation.siemens.com/WW/view/en/)
manual.
Requirements
You can download program changes when the CPU is in RUN-P mode. It is generally
possible to download changes if the following conditions are met:
At least one complete download has been performed successfully.
The download is performed with the program structure used most recently.
As soon as delta download capability is lost, the "Delta Download" selection is grayed out
and only a complete download can be performed.
7.2.2 Checking the delta download capability with time stamp comparison
Select the menu command "CPU > Compare" in the CFC editor to check the project status
before each download procedure.
PCS 7 provides the following three time stamps:
As can be seen in the screenshot, the online program that you have downloaded to the CPU
is only identical to the offline program, in other words, the chart folder and the compiled
blocks in the block folder, if the last two time stamps match exactly and are more recent than
the "Last download-relevant change" time stamp.
In all other cases, care needs to be given to the running process:
If the last download-relevant change is more recent than the last compilation, changes
made in the project have not been compiled.
If the last compilation is more recent than the compilation of the loaded program, the
compiled changes in the project have not been download to the CPU.
Note
The SIMATIC Manager menu command "Options > Reference Data > Generate" cannot be
used in PCS 7, because it would require a complete download with the CPU in STOP.
The "Options > Chart Reference Data" function is provided in the CFC editor for PCS 7 to
display reference information about the chart folder.
Note
You will find additional information on the subject of "Type updating in Run" in the "SIMATIC
Process Control System PCS 7 CFC for SIMATIC S7"
(http://support.automation.siemens.com/WW/view/en/) manual in the section titled "Type
updating with a CPU 410-5H PA" and in the Industry Online support portal in the entry
"Process optimization with the controller SIMATIC PCS 7 CPU 410-H"
(http://support.automation.siemens.com/WW/view/en/96839331).
Archiving
Make sure you archive the latest project version after every download. Otherwise, in some
circumstance it may not be possible to perform a delta download with a retrieved project due
to time stamps that have changed over time.
Note
The "Archive project after successful download" option requires that the Version Trail options
package is installed on the ES.
Selective download
The "Selective download" function can be used to download one or more modified CFCs or
SFCs. You can use selective downloading of individual charts to specifically select which
configured changes should be transferred to the target system and enabled. This makes it
possible, for example, to configure multiple units on a CPU at one time, because the
changes to a specific unit can be compiled, downloaded, and tested. Selective download is
not possible under the following conditions:
A complete download is required
A complete compilation is required
Status message for TCiR is displayed (a type adjustment has been initiated)
Note
Dependent charts arise due to one of the following conditions:
Change to an SFC type: All charts that contain an instance of this SFC type are
dependent and are also downloaded when the SFC type is downloaded.
A dependent chart is a chart that contains at least one block which is in the same runtime
group as a block of the chart to be downloaded.
CAUTION
Before downloading
Make sure that no dangerous system states can arise before downloading. If you have
changed multiple charts with cross-chart interconnections and do not then transfer all
charts to the AS together using "Selective downloading", damage could occur due to
inconsistent states.
Note
You will find further information on the subject of "Selective Downloading" in the in the
section "How to download modified charts to the CPU individually" of the"Process Control
System PCS 7 Engineering System (V8.1)"
(http://support.automation.siemens.com/WW/view/de/90663380) manual and in the
"Downloading individual charts selectively" section of the "Process Control System PCS 7
CFC for SIMATIC S7 (V8.1)" (http://support.automation.siemens.com/WW/view/en/) function
manual.
Inserting the new blocks of a chart in the runtime group of this chart reduces the number of
dependent charts, which would also need to be included in the selective download.
Note
As of PCS 7 V8.0, there is the option of reading back charts cyclically and automatically.
7.3.1 General
There are other regulations and procedural guidelines for F/FH systems in safety mode in
addition to those described in the section titled "Program changes" (Page 87).
Requirements
Qualified personnel who hold the necessary authorizations and qualifications to
commission and/or maintain the SIMATIC F system, as well as devices and systems
associated with PIC protection functions, in accordance with the safety engineering
requirements of the manufacturer and the TV (German Technical Inspectorate).
Modifications to the safety-instrumented system must be carefully planned, tested, and
approved prior to implementation.
You must ensure that the safety integrity level required of the system is maintained during
and after the modifications.
Note
You can find more information in IEC 61511-1.
Note
You can find more information in the following manuals:
Making and downloading changes in safety mode:
Manual "Industrial Software S7 F/FH Systems Configuring and Programming"
(http://support.automation.siemens.com/WW/view/en/2201072) in section
"Changing the safety program".
Safety mode, changes, change tracking and acceptance:
Manual "PCS 7 Compendium - Part B - Process Safety", section "Changes, tracking
changes, and acceptance"
You can find FAQs relating to S7 F/FH systems under
(http://support.automation.siemens.com/WW/view/en/13711209/133000).
The following sections contain a range of use cases which require a particular procedure.
General information
The creation of F block types is described in section "Creating F block types" in the
manual "Industrial Software S7 F/FH Systems Configuring and Programming"
(http://support.automation.siemens.com/WW/view/en/2201072).
You should always copy F block types from the master data library or your F block type
project. The PAR_IDs of the inputs/outputs of your original F block type must be in their
original state.
Use F process tag types with F block types for your project and enter them in your master
data library. Copy CFCs with F block types from the master data library.
To copy a CFC with F block types, all PAR_IDs need to be reset in the copy. Use the
program provided in the FAQ below to do this. Alternatively, copy the CFC to your F block
type project, reset the PAR_ID information there, and copy the chart from the F block type
project at a later time.
Note
You can find further information in the FAQ "What do you need to take into account when
working with F block types?" (http://support.automation.siemens.com/DE/view/en/24931461).
Deleting F_CH_DO F channel drivers (applies to F library fail-safe blocks smaller than V1.3)
If you only delete individual F_CH_DO F channel drivers for an F I/O with outputs, which
have multiple F_CH_DO F channel drivers placed on them, the safety program may trigger
an F STOP immediately after safety mode is activated once the delta download has been
performed.
You can restart the safety program straightaway following the F STOP, for example, by using
the "RESTART" input on the F_SHUTDN block.
Note
You can find further information in the FAQ "What do you need to take into account when
deleting F_CH_DO F channel drivers and using the F library "Fail-safe blocks (V1_2)" or
"Fail-safe blocks (V1_1)?" (http://support.automation.siemens.com/WW/view/en/26623656).
Note
You can find further information in the "Data backup" section of the "SIMATIC Process
Control System PCS 7 Service Support and Diagnostics"
(http://support.automation.siemens.com/WW/view/en/90682682) manual.
Note
In the query dialog of Ax DVD, you have the option of selecting an operating system without
installing PCS 7 or with PCS 7 installation (e.g. OS server). The installation of the operating
system is adapted for use with PCS 7.
Note
These DVDs were specifically assigned to an individual computer by the operating system
license and cannot be used anywhere else.
The DVDs cannot be ordered separately, nor can they be replaced if lost.
Note
Backup strategy
Make a backup of the PCS 7 station before installing any update.
To keep the system backup up-to-date with the most recent version, a new backup
should be made each time the software changes. In general, it is a good idea to create
backups on a regular basis.
Backups can also be made at specified intervals when there are frequent changes. The
system administrator needs to decide which method is appropriate.
Requirements
To restore the system from a backup, you need to use hardware identical to that in use at
the time of the backup. The hardware in use and its installation position should always be
recorded for this purpose.
If the computer is no longer physically present, because it has been destroyed in a fire,
for example, and you do not have another identical model, you should expect to
experience problems when restoring the system from a backup. In the worst case
scenario, a new installation will be required.
License keys cannot and may not be included in the backup.
Important: Record the following settings of the hard disk(s):
Hard disk type (ATA vs. SATA)
Hard disk size / partition size, quantity and sequence of the partitions
Formatting of the hard disk or partition
Record the settings in the PC BIOS setup, e.g.:
SATA configuration (AHCI, RAID or IDE modes)
Settings of "onboard" devices (e.g. LAN)
The last point should be a matter of course in creating full documentation for a plant.
Namely, information such as the computer name, IP addresses, number of network
adapters, operating system, installed service packs, installed software, etc.
CAUTION
In principle, you can use any type of backup software. Despite extensive testing, however,
there is no way to fully exclude the possibility that the functioning of a SIMATIC PCS 7
system may be disrupted or hindered by additional third-party software not explicitly
approved for SIMATIC PCS 7.
You must check whether the "SIMATIC Image Creator" used is compatible with the existing
device.
Microsoft also offers a backup utility (ntbackup.exe) in its operating systems. The system
administrator can use it as an additional backup tool. You can find it under "System Tools" of
the operating system.
Note
You should create and regularly test a recovery plan in your own interest.