Interview Questions
Interview Questions
Interview Questions
Zone 2 an explosive gas-air mixture is not present under normal operation and
if it occurs it exist only for short time.
Ex e - Increased safety
Ex N or n - Non sparking
Ex I Intrinsic Safety
Ex p - Pressurization
Ex O - Oil immersion
Ex s - Special protection.
Ex d II B T5
Cold Work, Hot Work, Vehicle Entry & Vessel Entry permit. Interinsic Safe meters
only should be used such megger, vibration meter, temperature meter and other
ordinary meters shall not used unless the Hot Work Permit is obtained.
IP55: - The second 5 (indicate) Protected against jets of water from all directions
and IP65: - The first 6 (indicate) completely protected against dust.
06. Explain different Insulation classes and the corresponding temperature rise
allowed?
C 1800C
07. What are IR, WR, KWH, OLR, MCC, MCB, MCCB, VCB, BOCB and
SF6?
IR Insulation Resistance
WR - Winding Resistance
A meter is used to measuring the electrical circuit and the value of current,
voltage and resistance is called AVO meter.
10. What is Bridge Megger? Where it is used?
Bridge Megger is used to measure the lowest value of resistances accurately and
it is used to measure the motor winding resistance and transformer winding
resistance during preventive maintenance. The winding resistance of the three
windings should be equal.
Voltage - Volt
Current - Ampere
Frequency - Hertz
0.75, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400,
600(Dimensions are in Square mm)
LC - Lead covered
14. What is MICC? Where it is used? What mineral used for this cable?
Mineral Insulated Copper Conductor and it is used for fire alarm systems
and
Lead Covered Cables are used in Oil Fields due to avoid damages of
Cable glands are used to protect from mechanical damage, to give earth
continuity and for entering in junction box, MCC etc.
Trace the cable fault through cable fault locator and cable route through cable
route locator
In explosion proof areas double compression glands are used to avoid the
gasses entering in the electrical apparatus.
Cold Compound joint kits, Hot Compound joint kits and Heat
Shrinkable joint kits
Nickel Cadmium Batteries: - It is used in Refineries for its reliability, long life and
less maintenance. No need to deal with H2So4 dangerous.
Lead Acid Batteries: - It is also used but life is limited, maintenance costs are high
and handling H2So4 is too dangerous for its chemical concentration.
Nickel Cadmium Cell - 1.2 Volts, Sp. Gravity is 1200 in all conditions and Lead
Acid Cell - 2.1 Volts, Sp. Gravity is in Full charge 1280, Half charge 1240 and
Discharge - 1180
21. What will effect if you are connecting the batteries in Series and Parallel?
If the Batteries are connected in Series the voltage will be increase and the
Batteries are connected in Parallel the Current will be increase.
22. What is the maintenance procedure of Batteries?
Charging method in which current does not appreciably change against battery
demand. Suitable for applications where a battery needs to be fully recharged in
the short time
24. How do you decide the boost charge current rate for given 100Ampere
UPS have Converter, Inverter, A V R, Battery Bank, Static switch and Bypass
Switch
The static switch have supply on both end i.e. Converter supply and
The inverter is always taking the load, the converter fails to feed supply to the
inverter, it will work with the help of battery bank
If the inverter is fails to take the load, the A V R supply will take the load without
power interruption through the static switch
classification?
Parts of motor are Stator, Rotor, Winding, Shaft, End shields, Fan, Fan Cover,
Terminal Box, Bearings, Bearing housings, Lifting hook and Pulley key
250 V 500 V
Over load, Short circuit on motor winding, Single phasing, Loose connection of
power cables, Bearing problem and Vibration on a running motor
Over Load Relay, Single phasing preventer, Stalling Relay, Thermal Over Load
Relay and Earth Fault (Short-circuit) Relay
Over Current Relay (Instantaneous), Thermal Over Current Relay, Stalling Relay,
Earth Fault Relay, Negative Sequence Relay and Temperature Relay
Primary winding
Secondary winding
Conservator tank
Buccholz relay
Buccholz relay
Differential relay
Restricted earth fault relay
Temperature sensor
Transfer the load to other transformer (if provided) or isolate the load
Check the insulation resistance of primary and secondary winding and check
the winding resistance
Check the Earth connections of Transformer and measure the earth value
Collect the sample of Transformer Oil and carry out B.D.V. test
39. What are the light fittings used in Gathering Centers & Booster Stations?
Incandescent lamp, Mercury high discharge lamp, Fluorescent lamp and Halogen
lamp fittings are used in Gathering Centers & Booster Stations and it certified by
BASEEFA
In twin tube light set while glowing the lamp, ring will move one by one inside the
florescent tube this is called stroboscopic effect due to two chokes are
connected nearby. To eliminate this effect connect one capacitor in series with
one light circuit
The automatic voltage regulators are usually provided to maintain the generator
voltage reasonably constant in spite of the fluctuating load i.e. to increase the
voltage when the load is high and reduce the voltage when the load comes down
Open circuit or loose connection in the exciter circuit also short circuited turns
in field windings
The Tong Tester is called in other words as clip on meter. In this we can measure
the current flowing in the circuit in each phase for any unbalance if is noticed.
Can be used without breaking the circuit.
Primary and Secondary Voltage must be same as check tap changer position
All these relay will have instantaneous tripping as well as IDMT (Inverse Definite Minimum Time)
delay tripping or only IDMT or instantaneous.
OVERCURRENT RELAY:
This relay operates when a over current of short circuit noticed in the load.
Normally these relays will be having plug setting for current selection.
IDMT is normally used for over current. Instantaneous will be actuated only during short circuit
and for this normally the setting will be 10 times the normal current.
Whatever the current fall in the secondary of C. T. will flow through over current relays 50 / 51.
When any fault occurs between phases & earth, this relay will operate.
This relay connected to the zero balanced (residually connected) C. T. connection as shown in the
diagram. Normal over current will not pass through this relay, at point 0 the current will be zero.
When a fault occurs between phase and earth, there will be unbalance and that unbalance current
will pass through relay (50 N / 51 N).
This relay protects only the zone connected in between the neutral C. T. and residually
connected C. T. in the phase side i.e., it is protecting star winding of the transformer. When any
unbalance or earth fault occurs after the phase C. T. there will be unbalance currents neutral C. T.
as well as residually connected phase CT and both currents nullified at point O. So there wont
be any current flow in the relay and the relay wont operate.
When fault occurs in the winding there will be a current flow in the neutral CT only. The current
will operate the 87TG relay.
DIFFERENTIAL RELAY
This relay protects the Zone connected between the CTs i.e. it is protecting only the transformer.
The CT connection is in winding side and in winding side, this is because to compensate vector
difference. The CT ration is also to be selected according to the transformation ratio.
When there is fault after the transformer secondary (i.e. after the secondary CT) there wont be
any difference of primary and secondary currents, are balanced in the Restraining coil.
When a fault occurs in the transformer, that current will be transformed to primary side only. So
that there will be different in the currents of primary and secondary. That unbalanced current will
pass through the operating coil and the relay will operate.
COORDINATION OF RELAY
If any fault occurs in motor, the neares relay has to trip D breaker itself, so that it wont affect the
other system. Similarly if any fault occurs after A breaker, the nearest is A breakers relay. So A
should trip and other system not affected.
Normally the operating and tripping of breaker time will be around 350 msec.
If after A breaker fault occurs A will trip at 350msec if it fails B will trip at 700msec, I B also
fails C will trip 1 sec. This is called the co-ordination of Relays.
UNDER VLTAGE RELAY:
This relay operates when under voltage occurs in a connected system, normally this relay setting
be 80% of the applied voltage. This relay is used to trip the equipments connected, during under
voltage condition. These relay having two types, instantaneous and IDMT (Inverse Definite
Minimum Time)
IDMT relay are all dis type and the setting can be done through plug setting arrangement.
AC Alternating current where the voltage is alternating from peak voltage (on both +ve ve side)
to ZERO voltage periodically.
V1/V2=N1/N2=I1/I2=K or NS/NP=VS/VP=IP/IS=K
It is the gas and oil operated relay. It has two circuits, on is trip and second is alarm. Any minor
fault develops that time the evaporated gas will actuate the alarm circuit; otherwise any major
fault rush of oil will actuate the Trip Circuit.
a) Buchholzs relay
b) Overheated relay
c) Earth fault relay
d) Temperature sensor
The oil should withstand 30KV for 1 minute gap with a gap of 2.5mm
It is a small container, contains silica gel and oil. It absorbs the moisture from the atmospheric air
and allow the fresh air to the conservator.
C.T. is Current Transformer which step down the current. It is used for current measurement and
protection.P.T. is Transformer Tap changing on HT side. Transformer is working at mutual
induction action.
1. YPM of Transformer
Procedure to lay 11 KV cable ?How to make joints for 11 KV cable?procedure to test joints and
laid 11 KV cable?
http://electrical-engineering-portal.com/commissioning-of-hv-panel-operational-and-functional-
checkup