Question
Whatwillcausean F13OpenBypassA,F14OpenBypassB,F15OpenBypassC faultcodeonan150F
SMCFlexsoftstarter?
Whattestingandtroubleshootingstepscanbetakentodeterminethecauseofthesefaults?
Isitpossibletodisable,overrideormaskoutthesefaults?
Answer
Seestepsbelowfortroubleshooting F13OpenBypassA,F14OpenBypassB,F15OpenBypassC faultson
aSMCFlexcontroller.SomestepswillrequiredisassemblyoftheSMCFlexsoftstarter.Refertothe
followinglinks:
SMCFlex(585A)SeriesBPowerPoleandControlModuleReplacement
(http://literature.rockwellautomation.com/idc/groups/literature/documents/in/150in042_ene.pdf)publication
150IN042.
SMCFlex(108135A)SeriesBPowerPoleandControlModuleReplacement
(http://literature.rockwellautomation.com/idc/groups/literature/documents/in/150in046_ene.pdf)publication
150IN046.
SMC3/SMCFlex/SMC50(201,251,317,361,480A)RenewalPartInstructions
(http://literature.rockwellautomation.com/idc/groups/literature/documents/in/150in037_ene.pdf)publication
150IN036
Bulletin150SMCFlex(625A1250A)RenewalPartInstructions
(http://literature.rockwellautomation.com/idc/groups/literature/documents/in/150in064_ene.pdf)publication
150IN064.
1.Checkthecontrolvoltagepowersupplytoensurethecorrectvoltageisbeingsuppliedtothesoft
starteronterminals11and12.
2.Makesurethatallthecontrolterminalconnectionsandwiringaresecure.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/47638/page/1 1/3
30/08/2016 47638Causes/TroubleshootingOpenBypassFaultF13,F14,F15onSMCFlexSoftStarter
3.CheckcontrolmoduleconnectionsfromterminalsTB2,TB3,TB4,TB5,TB6,TB7tothepowerpolesto
ensureconnectionsaretight,secureandnowiresarelooseorbroken.
4.Checksettingsforparameters107Aux1,108Aux2,109Aux3,110Aux4andensurethe
configurationisNOTsettoExternalBypass,unlesstheSMCFlexcontrollerhasbeenconfiguredtobe
usedwithanExternalBypasscontactor.
5.ForSMCFlexsoftstarters5through85amps,upgradethefirmwaretoRevision6.008.Firmware
6.008fixesanissuewiththeSMCFlexsoftstarters,from5through85amps,whereinrarecases
somecustomersmayexperienceintermittentornuisance F13OpenBypassA,F14OpenBypassB,or
F15OpenBypassCFaults .
6.For625,780,970,1250Ampcontrollersaminimumcontrolpowersourceof800VAisrequired.
7.For625,780,970,1250Ampcontrollersverifytheorangejumperoneachoftheinternalbypass
contactorsissettotheEImode.
Note:Step8onlyappliestoSMCFlexcontrollerssizes108Ampsandlarger.Thereisnoadditional
testingforthe85AmpandsmallerunitstodetermineiftheissueiswiththeSMCFlexControlModule
ortheinternalbypasscontactors.
8.ToverifyiftheproblemiswiththeSMCFlexControlModuleorwithaPhaseA,BorCPowerPole
bypasscontactor(forthe108A1250Aunits)followtheinstructionsinthefileattachmentsareaatthe
bottomofthistechnote.
9.Thesefaultsaresometimescausedbyhighvoltagessurgesonthecontrolpowerportionofthe
system.Thissurgegetsintothecontrolmodule'spowersupplywhichpowerstheintegralbypassrelay
coils,resultinginanOpenBypassandresultingfaultcode.RemovetheSMCFlexControlModule
fromthepowerstructureandvisuallyinspectcircuitboardcomponentsmarkedQ2,Q10,Q13andQ15
fordiscolorationordamage.
Refertotechnote26055ReplacementPartsfor150FSMCFlexControllers
(//rockwellautomation.custhelp.com/app/answers/detail/a_id/26055)ortheSMCFlexUserManualFor
SeriesBControllers(http://literature.rockwellautomation.com/idc/groups/literature/documents/um/150
um008_enp.pdf)Publication150UM008foradditionalinformation.
Note:Itisnotpossiblethroughaparameterchangetodisableormaskoutthese
faults.
Attachments
OpenBypassRev2.pdf(/ci/fattach/get/833266/0/filename/Open+Bypass+Rev+2.pdf) (16.99
KB)
DISCLAIMER
Thisknowledgebasewebsiteisintendedtoprovidegeneraltechnicalinformationonaparticularsubjector
subjectsandisnotanexhaustivetreatmentofsuchsubjects.Accordingly,theinformationinthiswebsiteis
notintendedtoconstituteapplication,design,softwareorotherprofessionalengineeringadviceorservices.
Beforemakinganydecisionortakinganyaction,whichmightaffectyourequipment,youshouldconsulta
qualifiedprofessionaladvisor.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/47638/page/1 2/3
30/08/2016 47638Causes/TroubleshootingOpenBypassFaultF13,F14,F15onSMCFlexSoftStarter
ROCKWELLAUTOMATIONDOESNOTWARRANTTHECOMPLETENESS,TIMELINESSORACCURACY
OFANYOFTHEDATACONTAINEDINTHISWEBSITEANDMAYMAKECHANGESTHERETOATANY
TIMEINITSSOLEDISCRETIONWITHOUTNOTICE.FURTHER,ALLINFORMATIONCONVEYEDHEREBY
ISPROVIDEDTOUSERS"ASIS."INNOEVENTSHALLROCKWELLBELIABLEFORANYDAMAGESOF
ANYKINDINCLUDINGDIRECT,INDIRECT,INCIDENTAL,CONSEQUENTIAL,LOSSPROFITORDAMAGE,
EVENIFROCKWELLAUTOMATIONHAVEBEENADVISEDONTHEPOSSIBILITYOFSUCHDAMAGES.
ROCKWELLAUTOMATIONDISCLAIMSALLWARRANTIESWHETHEREXPRESSEDORIMPLIEDIN
Top (/app/answers/detail/a_id/47638/page/1#top)
RESPECTOFTHEINFORMATION(INCLUDINGSOFTWARE)PROVIDEDHEREBY,INCLUDINGTHE
IMPLIEDWARRANTIESOFFITNESSFORAPARTICULARPURPOSE,MERCHANTABILITY,ANDNON
INFRINGEMENT.Notethatcertainjurisdictionsdonotcountenancetheexclusionofimpliedwarrantiesthus,
thisdisclaimermaynotapplytoyou.
ThispageisbestviewedinInternetExplorer10,Firefox31,Chrome37,Safari6ornewer.
(http://www.rockwellautomation.com/global/blog/overview.page)
(https://www.facebook.com/ROKAutomation)
(https://plus.google.com/+RockwellautomationInc)
(https://www.linkedin.com/company/rockwell
(http://www.slideshare.net/RockwellAutomation)
(http://twitter.com/ROKAutomation)
(http://www.youtube.com/rokautomation)
automation)
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/47638/page/1 3/3