1.1 Control Philosophy CAS-1 NMDC
1.1 Control Philosophy CAS-1 NMDC
1.1 Control Philosophy CAS-1 NMDC
Suction Air Filter With Silencer and Manometer : Each compressor unit is
provided with dry air intake filter and silencer unit (SF-1 /SF-2/SF-3).The
inlet air source should be as cool as possible. Filter should not be placed in
any area where the maximum ambient temperature exceeds the specified
maximum design compressor inlet air temperature that is listed on the
compressor data plate. Air temperature in excess of the specified maximum
will have negative effect on compressor aerodynamics performance.
The inlet air filter assembly and blown of silencer will be mounted outside
and away from the walls to prevent the reflection of the noise . The exhaust
from the silencer should be directed upward and equipped with a rain cap
for protection from weather. U Tube Manometer ( MM-1001 ) is fitted with
filter. The manometer is positioned where filter cleanliness can be easily
monitored. In built silencer is used to attenuate the traveling sound
waves to compressor suction.Differential pressure(DPT-A01/DPT-A02/DPT-
A03 ) across suction filter produces high alarm if the pressure crosses the
set point . It indicates that the filter has been choked and goes to the
maintenance mode to prevent back pressure and filter element needs to be
cleaned manually.
Compressor :
1. Principle of operation :
Filtered air ( controlled by electric actuated inlet guide vane ,IGV-1001-
01/IGV-1001-02/IGV-1001-03 valve operated by 110V AC ,1phase which is
provided to it from control panel ) enters the the compressor's first stage and is
compressed. After inlet compression, the air travels through an intercooler
where heat and moisture are removed from the compressor air .
After the air is cooled and dried , it enters the compressor's second stage
and is further compressed. The air is then directed through a second
intercooler to once again remove heat and moisture .
Finally ,the air enters the compressor's third stage ,where it is compressed to
the design discharge pressure and supplied to the plant air system . Moisture
is condensed as the compressed air is cooled between compression stages .The
amount condensed depends upon humidity condition existing at site. The
condensate must be drained from the compressor.
The PLC control panel is responsible for positioning the inlet control valve
(IGVs ) , positioning the unloading control valve (UCVs ),
sequencing start - up and shut down events , governing different modes of
operation ,monitoring operation parameters , and providing alarm & trip
indications. The control panel utilizes PLC to perform these functions .
Communication takes place via the PLC operator interface located on front
of the control panel.
2. Safety Precautions
1) Ensure all piping and electrical connections are secure before operating
the compressor .
2) Ensure that all valves controls , and the trip and safety are functioning
correctly.
3) Review the operating precautions outlined in the Motor's instruction
manual before the Motor is operated
4) Verify that the compressor drive shaft can be rotated by hand before
starting the compressor.
5) If unusual noises , vibration are detected during operation , stop the
compressor immediately to determine and correct the cause
Note : Gear type coupling must have the coupling sleeve secured to the coupling
hub with an adapter during uncoupled operation
b) Start the driver and verify that the rotational direction of driver shaft is
Correct.
c) connect the coupling between the compressor and driver ( lubricate
coupling as necessary.)
d ) Inspect sight glass (1LG001/2LG001/3LG001 )on oil reservoir for proper
level If oil level drop below the bottom of the oil level sight gauge before
operating the pump , oil should be added until the level reaches the mid
point of the sight gauge.
4) Current Date and Time
The current date and time are maintained by 'the real time hardware clock'.
the date & time can be adjusted using following procedure .
a) Push the Main Menu function key to access Main Menu screen. Status
Screen is shown.
b) Under the Main menu, push the Set points function key to access Setpoint
Screen1.
d)Push the STATUS key on the PLC touch pad screen to access the status
Screen.
e) Push the Main Menu key on the touch screen to access the Main menu
Screen.
f ) Push MODE key to access the 'mode of operation ' screen.The 'mode of
operation' screen contain four individual mode selection menus.
i. Control Mode
ii. Start/ Stop Mode
iii. Inlet control device Mode
iv. Unloading valve Mode
h ) After the appropriate control mode selection has been made, push the
STATUS key on the touch screen to return to the Status screen
i) Open the cooling water supply valve ( 1BFV-001,2BFV -001) to the
intercooler tube bundles
j) Pull out the Emergency Stop key on the front of the control panel to enable
the start sequence.
l) The auxiliary oil pump (AOP) will start when the start-up procedure is
confirmed..Fifteen seconds after the AOP started , the low oil pressure alarm
and trip are enabled ( by 1PT001/ 2PT001/3PT001) and the oil temperature
( by 1TE001/2TE001/3TE001) is checked. If the oil temperature is 74 deg
F( 23deg C ) or greater, you are permitted to start. If the oil temperature does
not exceed the permissive setpoint , the following message will appear in the
upper left corner of status screen : AOP ON - wait ,Cold oil . If the oil
temperature does not exceed 74 deg F ( 23 deg C) within 15 minutes, the start-
up sequence will be aborted.
CAUTION : Operating personnel should stay clear of the coupling and rotating
shafts while the control system is waiting for the oil temperature to reach 74
deg F ( 23deg C). You will start automatically once the oil temperature reaches
23 deg C ( 74deg F)
m) Twenty- five seconds after the motor is energized, the oil pressure is checked,
the motor starter status is checked ( ie breaker of respective compressor
spring charged , switch gear selected remote, control supply healthy, trip coil
supervision healthy,protection relay not disturbed ) and the motor current
alarm is enabled. If the oil pressure is sufficient , the AOP automatically shuts
off.
If the oil pressure does not exceed the acceptable level within 60 seconds after
the motor starter status is checked, the PLC assumes a main oil pump (MOP)
failure and trips the compressor.
If the motor starter status indicates that the motor has not been started ,the
PLC assumes a motor overload condition ( etc ) exists, and the start sequence is
aborted
n) Five seconds later, the following events occur :
i) The inlet & unloading valves are placed under control of the PLC. The inlet
control valve (1IGV / 2IGV /3IGV) modulates from its closed position. The
unloading valve (1UCV/ 2UCV/3UCV) waits an additional 8 seconds to begin
modulation to prevent a possible surge
ii) The interstage air temperature alarm and trip are enabled.
OPERATIONAL CHECKS
Although the Compressor is designed to operate autonomously , occasional
monitoring and minor adjustment is necessary for safe and efficient operation :
a) Adjust intercooler water valves ( 1BFV001/ 2BFV001/3BFV003) to maintain
the design interstage air temperature 15 deg F ( 8 deg C) higher than the
design cooling water inlet temperature is located on the compressor name
plate b) Check the oil reservoir oil level(1LG001/2LG001/3LG001) . Monitor the
oil temperature and pressure ( by 1TE001/2TE001 /3TE001,
1PT001/2PT001/3PT003 ).
If necessary, adjust water flow through the oil cooler to maintain an oil
temperature to the bearings of 115 - 125 deg F ( 46 - 52 deg C )
c) The moisture elimination section drain valve discs are notched to allow
constant moisture drainage. In some cases , it may be necessary to open the
valves to ensure adequate drainage .
Caution : Ensure that there is no moisture accumulation in the intercoolers
during the operation. Plugged or restricted drainage from the intercoolers
will result in a rising water level and eventual water carry - over into the
next stage of compression . Water in the air stream will damage impellers
resulting in a loss of performance and vibration
d) The operating personnel should record data approximately every 4 hours.
The operating data should be reviewed periodically. The data will alert the
operating personnel of a maintenance problem , such as dirty oil cooler, etc.
This will aid the operating personnel in scheduling maintenance shutdowns
and reduce unexpected shutdowns that may be detrimental to the plant.
Manual Start
CC
Auxiliary oil pump start
Next Page
Oil Temperature Oil Pressure
No Yes
Alarm
? No low oil Pr
PAP Starting, Oil in XX PSIG
Oil in XX deg F
Wait : Cold Oil
PAP starting Auxiliary oil
oil is XX PSIG pump stops
No Oil is xx deg F
? PAP Starting oil in xx PSIG
Has 20 min Oil in XX deg F
Timer started ABORT
? START
UP
Yes
Is oil Temp. & pressure
Satisfied
Yes Is seal air pr. Yes
? Satisfied ?
Compressor Drive
Motor Status
Alarm on
Low oil temp
Wait 25 seconds
ABORT No
Start - Up
Trip motor
?
starter status
Is Motor Starter
Yes Coil Energized
No
Yes No
Shut off auxiliary ?
oil pump ?
Has 35 second
Is oil pressure timer elapsed
> 37 PSIG Yes
PAP running
Oil in xx deg F
Air out xx PSIG
RS Vib xx micro m
AUTOMATICALLY INITIATED START - UP
Note : Temperature, pressure and vibration transmitters are monitored for failure
at all times. A fault with any of these transmitters will be annunciated on the PLC
operator interface and prevent start - up until the fault is corrected.
1) Check the oil reservoir level and temperature . If necessary , add oil until the Full
mark is reached on the oil level sight gauge. Heat the oil if the temperature is less
than 74degF (24deg C). The optional oil heater should be configured to maintain the
oil temperature at 100 deg F (38 deg C)
2) Prime the main main oil pump if the compressor is being started for the first time,
or the main oil pump has currently been repaired or replaced
a) Remove pipe plug from suction side of the pump.
b) Fill pump and suction line with oil .
c) Replace and tighten pipe-plug.
3)Turn on the air supply to the pneumatic control components and the seal air
piping harness ( if required)
4)Push the STATUS key on the PLC touch pad screen to access the status screen.
5)Push the MAIN MENU key on the touch screen to access the Main Menu Screen.
6)Push the MODE key to access the 'mode of operation' screen.
7)Access the drop-down menu titled START/STOP MODE. Select the desired operating
mode ( AUTO /MANUAL or AUTO/ AUTO) by pressing the appropriate selection in the
START/STOP drop down menu. Also, select the control mode ( Base,Suction
Throttle, Intermittent or Auto /dual ).
Note :
The ( AUTO/MAN) start/stop mode can be selected with any of the control
modes ( Suction Throttle, Base Mode, Intermittent Mode , or Auto/Dual). The
( AUTO/AUTO ) start/stop mode can only be utilized when the intermittent or
Auto/dual control modes are selected
8) After the appropriate control mode selections have been made, push the STATUS
Key on the PLC touch pad screen to return to the Status screen.
9) Open the cooling water supply valves to the intercooler tube bundles.
10) Open the manual block valve ( 1NRV001/2NRV )to the plant air system.
11) Pull out the EMERGENCY Stop key on front of the control panel to enable the
start seq unce.
13) If the system pressure is above the low system pressure setpoint , the unit will
be placed in stand -by mode and the following message will be displayed in the
upper left corner of the Status screen: WAITING TO AUTO-START .
CAUTION
Operating personnel should stay clear of the coupling and rotating shafts while
the control system is waiting for the plant air pressure to decrease. Motor will
start automatically once the plant air pressure decreases to the low system
Pressure setpoint.
14) When the system pressure falls below the automatic start setpoint , the
Auxiliary oil pump ( AOP) will start.
15) Fifteen seconds after the AOP is started ,the low oil pressure alarm and trip
are enabled and the oil temperature is checked. If the oil temperature is
74 deg F (23 deg C) or greater , the driver is permitted to start. If the
Oil temperature does not exceed the permissive set point ,the following
message will appear in the left corner of the Status screen : AOP ON - Wait ,
Cold oil . If the oil temperature does not exceed 74deg F ( 23 deg C) within
15 minutes ,the start up sequence will be aborted.
Note : The compressor will not auto start if the start- up sequence has been
aborted due to the cold oil condition . The operator will have to manually launch
the start-up sequence , at which time , the auto start feature will re- initiate.
16) Twenty -five seconds after the motor starter is energized, the oil pressure is
checked , and the motor current alarm is enabled. If the oil pressure is
sufficient , the AOP automatically shuts off..
If the oil pressure does not exceed the acceptable level within 60 seconds
after the motor starter energized ,PLC assumes a main oil pump ( MOP )
failure and trips the compressor.
If the motor starter status indicates that the driver has not started , the
PLC assumes a motor overload condition (etc.) exists, and the start sequence
is aborted.
17) Five seconds later , the following events occur :
a) The inlet and unloading valves are placed under control of the PLC. The
inlet control valve (1IGV/ 2IGV) modulates from its closed position .The
unloading valve (1UCV/2UCV) waits an additional 8 seconds to begin
modulation to prevent a possible surge
b) The interstage air temperature alarm and trip are enabled
Automatic Start
The seal air system provides pressurized air to the pinion seals. The
pressurized air provides a barrier so that oil cannot leak into the compressed
air system. The seal air system consists of a seal air blow -off regulator and an
optional seal air supply regulator.
During normal operation of the air compressor unit.the last stage of compress -
ion provides a small amount of pressurized air into the seal air system. This air
is provided to the pinion seals. The seal air blow-off regulator vents any excess
air. The seal air blow-off regulator should be adjusted to 6-7 psig ( 0.41 to 0.48
bars).
EMERGENCY SHUTDOWN
3. Push the ACK key on the lower right corner of the trips & alarm screen.
Then hide the alarm screen followed by the RESET key located on the upper
left corner of the status screen. These actions will clear the trip status.
Note : The compressor coast down timer is set for 120 seconds to prevent
attempted start - up while the driver is coasting down. A
(COASTDOWN) message will appear on the upper left corner of the
Status screen during the coast down period.
CAUTION
In cold weather climates it may be necessary to continue running the cooling
water to prevent freeze-up of the oil cooler.
MANUAL SHUTDOWN
1.Slowly close the manual shut-off valve to isolate the compressor from plant
air system
CAUTION
Failure to close the manual shut -off valve may lead to reverse rotation of the
Compressor ( if the check valve were to fail )
2. Push the STATUS key on the PLC touch pad screen to access the Status
screen .
3. Push the STOP key located on the Status screen. A screen will appear
prompting the operator to CONFIRM or IGNORE the stop command .Press
the CONFIRM key to continue .
Note
If the operator encounters an emergency, pushing the EMERGENCY STOP
push key on the front of the control panel will immediately unload the
compressor and shut down the driver.
Manual Stop
PAP running
Oil in xx deg F
Air out xx PSIG
RS Vib xx micro m
Yes
Re start is permitted
No
Has 15 Minute Timer Elapsed ?
Yes
4) The compressor will now receive an automatic stop command once the plant air
system demand is satisfied.
5) Once the automatic stop command is received, the compressor ' s inlet control
valve will close and the unloading valve will open.
6) The compressor will continue running in this manner until the system pressure
drops below the low system pressure setpoint at which time the compressor will
reload. If the system pressure does not drop below the low system pressure setpoint
within 30 minutes of the compressor unloading , the compressor receives a shutdown
command.
7) When the shutdown command is received the following steps are automatically
taken
a) The motor starter is de-energized to stop the motor
b) The auxiliary oil pump will start
c) The compressor coast down timer initiates. The timer is set for 120 sec to prevent
an attempted start -up while the driver is coasting down
d) If the shutdown sequence is successful, the following message will appear in the
Upper left corner of the status screen during the shutdown-screen.
Stopping
Coast down
Cool down
Compressor shutdown
8) Two minutes after the shutdown command is received , the message 'Cooldown'
appears in the upper left corner of the Status screen.,at which time a compressor
restart is permitted. If the system pressure has fallen below the low system
pressure setpoint , the compressor will automatically restart.
9) If a restart is not attempted, the AOP will remain on for an additional thirteen
minutes for cooling and then shut down automatically.
10) After coast down the unit will await an auto start command.
11) When the system pressure drops below the low system pressure setpoint,the
compressor will automatically start.
Automatic Stop
PAP running
Oil is xx deg F
Air out xx PSIG
RS Vib xx micro m
Yes
Yes
? Start 30 min
Unl. Valves
Has Timer open ln valve Timer
Elapsed closes
No
No
Ln valve opens Yes
?
Unl Valve closes ?
Is system Pr. No
Below set pt
Has
30 min Timer
elapsed
Aux. Oil
pump start
EE
EE
Start timer
No
? Yes
Re start is permitted
Has 2 min timer elapsed
Is system Pr.
Below pr, set
point
Has 15 min timer elapsed ?
No ?
Yes Yes
CAUTION
Operating the unit in a surge condition can cause extensive damage to the
compressor . It is recommended that the unit not be operated in a continuous
surge condition.
If surge occurs while the unit is operated in the suction throttling or control
modes ,the control system will automatically change the compressor's operating set
point in an attempt to prevent future surge occurrences . The control system will
also automatically reload the compressor into the plant air system after making a
change to the operating set point.If compressor surge occurs again, the control
system will continue to change the operating setpoint away from surge until a max
operating set point is achieved . At this point , the unloading valve will remain
fully open until an operator investigates the problem and pushes the
ACKNOWLEDGE and RESET function keys.
After the unit is operating , check to see that the surge detection circuitry is
functional. The following procedure may be used :
1. If the block valve to the plant air system is not closed, slowly close it.
2. Push the STATUS key on the PLC touch pad screen to access the status screen.
3. Push MODE key to access the mode of operation screen .
4. Access the "CONTROL MODE " drop- down menu.
5. Push BASE to configure the compressor to operate in base mode.
6. Access the "UNLOADING VALVE" drop-down menu.
7. Push MANUAL to place the unloading valve under manual control.
8. Slowly close the unloading control valve by pushing the key. The % open valve
on the screen will decrease and the compressor discharge pressure will increase. As
the discharge pressure increases, the compressor approaches surge.When surge
occurs, the PLC should recognize it and open the unloading control valve ,flash the
Common alarm light, sound the horn, and display the surge condition on the
operator interface screen.
CAUTION : If the control panel does not recognize surge , push the key on the
operator interface until the surge condition is eliminated . Contact an Eliott service
office.
9. To clear the surge recognition circuit , push the ACK and RESET keys.
Following are the details of each compressor in brief :
Oil filter (OF-101 /102/ 103 ) : Cartridge type duplex filter is used for oil
filtration purpose.
Thermostatic Control valve (1TCV 1001/ 2TCV1001/3TCV1001) is furnished to
regulate the oil temperature to the compressor .When the oil temperature to
the compressor is below 110degF ( 43 deg C), the control valve causes the oil
by pass the cooler . When the oil temperature exceeds the 120degF (49 deg C),
the valve routes all the oil through the cooler. At oil temperatures between 110
deg F and 120degF (43degC & 49 deg C) , the valve regulates the oil flow
between the oil cooler and the bypass to maintain this temperature range.
Oil heater (1OHR/ 2OHR /3OHR) : An oil heater is installed in the side of the oil
reservoir . An integral thermostat can be adjusted to obtain the desired oil
Temperature.
Safety , Control & monitoring device of the lubrication system : The system is
equipped with an oil pressure transmitter (1PT001 / 2PT001/3PT001)
and oil temperature element (1TE001/ 2TE001/3TE001 ,connected with PLC)
on the oil feed line to the compressor. The oil pressor transmitter trips the
compressor if a low oil pressor condition should occur. The oil temperature
alarms and trips the compressor if a hot oil condition should occur.
During normal compressor operation ,the main oil pump supplies oil to fulfill
the unit's oil requirements ( bearings , gears). The auxiliary oil pump remains
on stand by until the performance of the main oil pump deteriorates. The relief
valve is to be adjusted to maintain a system oil press within the range (1.7 bar
to 2.0 bar )
When the unit shuts down (manually or due to or safety trip device ) the
auxiliary oil pump automatically starts. The auxiliary oil pump continues to
operate and cool the compressor bearings. After 15 minutes ,the auxiliary oil
pump automatically shuts off.
Lubrication system operating data :
1) Low oil temperature alarm - 21 deg C
2) Minimum oil temperature for permissive start - 23deg C
3) System oil pressure - 1.7 bar to 2.1 bar differential
4) Max.Pressure drop across oil filter - 0.7 bar
5) Low oil pressure trip - 1.0 bar
6) Low oil pressure permissive - 1.4 bar
7) Auxiliary oil pump start pressure - 1.4 bar
8) Auxiliary oil pump stop pressure - 2.2 bar
9) Oil temperature from oil cooler - 46deg C to 52 deg C
10) High temperature alarm oil from cooler - 57deg C
11) High temperature trip oil from cooler - 60 deg C
12) Reservoir Capacity - 245 lt.
Each Compressor is driven by HT Motor ( 1400 Kw, 6.6 KV Volt) which is
Started through FCMA soft starter connected with HT switch board. ( Client
scope )
Cooling water supply & System: Existing pump house ,Cooling Tower ,Cooling
water supply and Return pipe lines will be utilized for these new
Compressors. Motorized Butterfly valves ( MOV-013/ MOV-015/MOV-017
for Compressor (1 ,2 & 3 ) are installed in water Inlet line of the
Compressor. Motorized Butterfly valves ( MOV-014/ MOV-016/MOV-018 ) are
installed on water outlet line of compressor ( 1, 2 & 3 ).
Cooling water maintains air & lubrication oil temperature within design limits.
The coolers are shell and fined tube type. Cooling water passes through the
tubes and cooled medium through the shell and around tubes.
Cooling water supply is to be limited to maximum pressure of 8.6 bar for the
intercoolers and 10.3 bar for the standard oil coolers.
Note : An insufficient pressure drop across the cooler connections or
insufficient water flow will result in inadequate cooling .
Water inlet temperature exceeding the design value will have a negative effect
on compressor aerodynamic performance may result in alarms or trips due
to high lube oil or inter stage air temperature.
Excessive water velocity will lead to erosion problems, noise or insufficient
heat transfer .Lower velocities will result in increased cooling water
discharge temperature .
Compressor are furnished with electric actuated inlet guide vane (1 IGV / 2 IGV/3 IGV).
The valve will need to have 110 v Ac / 1 phase provided to it from control Panel. The 4-
20 mA signal is wired from the control Panel to the valve.
The Seal air Pressure switch (SAPS) senses the buffer pressure in the compressor seals.
The seal air pressure (SAPS) is used in conjunction with intermittent mode or dual mode
control. The SAPS is ignored during base mode and suction throttle mode control. A low
seal air pressure condition also prevents. The inlet valve/guide vanes from closing ( un
load compressor) and prevents the auxiliary oil pump from continuously running during
start up. The switch is set so that the contacts close at (0.27 bar) and open at (0.13 bar).
A blow off regulator is installed on the sal air harness to vent air should the air pressure
exceeds 0.45 bar.
Control and instrumentation :
Individual Compressor will be communicated to BSL PLC through RS 485 Modbus
protocol.
The PAP PLC control system regulates the inlet and unloading valves, monitors the
operating Parameters (temperatures, pressure etc), provides alarm and trip indication,
sequence start - up and shut down of the unit, governs the different modes of operation,
stores pertinent data and provides hard copy output information via serial printer interface
and communicate with common PLC.
The control panel utilizes a PLC to perform these functions. Integral with PLC is the
HMI LC Touch panel display.
Primary communication with the PLC is through the integral HMI Touch screen display
on the front of the control panel. Commands for starting compressor, selecting control
modes, entering set points, acknowledge alarms, etc are entered on the Touch screen, the
display informs the operator of the unit's operating status, set points, data, control modes,
and alarm and trip conditions.
The inlet inlet control valve / guide vanes are positioned to maintain a deserved motor
amperage. The unloading valve opens to exhaust compressed air to atmosphere when the
compressor output flow exceeds the system demand. The valves (or guide vanes) may be
positioned manually or automatically through the PLC interface.
Per-massive Condition :
1) Breaker of respective compressor spring charged
2) Switch gear selected remote
3) Control supply healthy
4) Trip coil supervision healthy
5) Switchgear is not disturbed ( protection relays of motor are not actuated )
6) Lubrication oil pressure archived
7) Lubrication oil temperature achieved
1. Discharge air Pressure set : Utilizes the unloading valve to maintain this pressure at
the discharge of the air compressor.
2. System air Pressure Low : This set point determines the plant air pressure at which
the unit loads and /or automatically starts.
3. Minimum Motor Amps : This set point (along with max motor Amps set
point)determines the operating amperage range of the motor.The min amps set point
corresponds to the suction throttling horse power of the unit.
4. Max Motor Amps : This set point (along with minimum motor Amps set
point)determines the operating amperage range of the motor. The max. amps set point
corresponds to the suction throttling horse power of the unit.
5. Inlet valve prop band and Reset : These set points control the responsiveness of the
inlet control valve / guide vanes.
Note : The proportional band and reset settings determine the responsiveness of the
control valve ( Inlet valve and unloading valve)
6. Unloading valve Prop. Band and Reset : These set points control the responsiveness
of the unloading control valve.
7. Valve times (Inlet or unloading): These set points determine the closing speed of the
inlet valve (in seconds) and the opening speed of the unloading valve in order to obtain a
smooth unloading of the compressor during intermittent and dual mode operation.
8. Valve position to Auto unload : These set points determine the unloading valve
position, at which a timer in the PLC software is limited before unloading the compressor
on intermittent and dual mode control.
9. Aux. Oil pump shut off Pressure : This set point determines the oil pressure during
start - up of the compressor at which auxiliary oil pump is permitted to shut off.
10. Oil temp. Start permissive : The permissive start set point determines the oil
temperature at which the compressor can be started.
11. Surge DP/DT : These set point determine the sensitivity of the surge detection
system. Surge is detected when a certain pressure drop (DP) occurs within a certain time
period (DT).
12. Adaptive control increment : If the compressor surge occur, this set point
determines the amount of incremental adjustment, which the controls will move away
from surge. Every time the compressor surges, the controls make an incremental change
until compressor surge no longer exists or the maximum motor amperage is reached.
13. Suction throttle prop band and reset : These set points control the responsiveness
of the inlet control valve / guide vanes during the throttling action.
Control System:
The control system regulates the air flow through the compressor by positioning the air
inlet control value and discharge air unloading value. The controls also unload the
compressor when occurs.
The control system performs the following functions :
1) Start/Stops the air compressor unit.
2) Motor amperage control.
3) Discharge pressure control.
4) Suction throttling control.
5) Intermittent mode control.
6) Auto dual mode control.
7) Auto start stop control.
Various Controls
A) Manual operation of the inlet control valve/guide valves allows the operator to
manually adjust the compressor inlet air flow, which in turn, affects the Motor current.
Manul control can be obtained by selecting the inlet valve drop down menu.
Note : Manually closing the inlet control valve/guide valve too far during compressor
operation may result in compressor surge.
B) Automatic operation of the inlet control valve/guide valves allows the control panel to
automatically adjust the Motor current.
The control panel will automatically maintain the Motor current at the set point. This can
be obtained by selecting the Inlet valve drop down Menu.
A) Manual operation of the unloading control valve allows the operator to manually
adjust the compressor discharge pressure.
Note :Manually closing the unloading control valve too far during compressor operation
may result in compressor surge.
B) Automatic operation of the unloading control valve allows the control panel to
automatically adjust the compressor discharge pressure.
The control panel will automatically maintain the compressor discharge pressure at the
set point.
The inlet control valve/guide vanes modulate to maintain the design motor current
(amperage).
The set point required for base mode operation are listed below:
1. Discharge air pressure
2. Maximum motor current
To operate the compressor air in base mode, access the control mode drop-down menu
and select base mode.
The suction throttle control mode is a method of reducing the motor power consumption
by throttling the inlet air flow when the plant air system demand is satisfied. When the
plant air pressure (compressor discharge pressure) is satisfied, the inlet control
valve/guide vanes throttle the inlet air flow. The inlet control valve/guide vanes throttle
the air flow until a minimum amperage set point is released. If the plant continues to
decrease, the unloading control valve will modulate to maintain design discharge pressure.
The set points require for suction throttle mode operation are listed below
Note: If the minimum amps set point valve is too low while operating in suction throttle
mode, the compressor may surge.
Intermittent mode is basically on ON-OFF type of control. The compressor loads and
unloads based on the plant air system demand. When the system air pressure is below the
low system air pressure set point, the inlet control valve/guide vanes open to maintain
design motor amperage and the unloading control valve closes to deliver all of the
compressed air to the plant air system. As the plant air system demand decreases, the
compressor discharge pressure increases and unloading valve maintains design discharge
pressure by venting excess air to atmosphere. As the plant air system demand further
decreases, the unloading valve opens further to maintain design pressure once the valve
position has exceeded the Auto unload set point (% open), a timer is initiated. If the %
open set point is exceeded for 3 mins, the compressor unloads (unloading control valve
fully opens and the inlet vane/guide vane fully close.) The compressor remains unloaded
until the plant air pressure decreases to the system pressure set point at which time the
cycle will begin again. The set points required for intermittent mode of operation are
listed below.
To operate the compressor in intermittent mode, access the control mode drop down
menu and select intermittent.
Auto dual mode control is the same as intermittent mode with the exception that once the
compressor discharge pressure rises to the design discharge pressure, the inlet control
valve/guide vanes throttle the inlet air flow to reduce the drive horse power. The inlet
control valve/guide vanes throttle air flow until the minimum amperage set point is
reached. If the system pressure (compressor discharge pressure) continuous to increase,
the unloading valve opens to maintain decrease pressure if the unloading valve opens
beyond the % open setpoint for the set point amount of time, the compressor unloads
(unloading valve fully opens and inlet valve guide vanes fully close.). The compressor
will continue to run this unloaded state until the plant air system pressure falls below the
low system pressure setpoint. The compressor will then re load and the cycle will repeat.
The setpoints required for auto dual mode operation are listed below.
1) Low system air pressure
2) Final discharge air pressure
3) Maximum Motor current
4) Minimum Motor current
5) Valve position to Auto unload
To operate the compressor in auto dual mode, access the control mode drop down menu
and select Auto dual.
2) Air pressure before inlet of 2nd stage of compressor high / low at 3.94 / 1.94
kg/cm2
3) Air pressure before inlet of 3rd stage of compressor high /low at 5.98/3.98
kg/cm2
16) Inlet air Temperature to After Cooler of Compressor high at 115 deg C
17) Final inter stage air discharge temp. High at 52..12 deg C
18) Lube oil inlet temp. High/low at 57.22/21.22 deg C
11) Average Temperature of Stator winding of Motor is high- high ,beyond 122
deg C.
12) Discharge valve of Compressor line does not open within certain time
( approx 1 min ) of switching on the compressor .
PROVIDED TO OUR ELECTRICAL PANEL. THE 3-PHASE R,Y,B POWER SUPPLY WILL
160 DEG C )
40 DEG C )
160 DEG C )
40 DEG C )
THE AIR DRYER WILL START, THE PLC OUTOUTS FROM Q-1 TO Q-7 ARE TAKEN
FOR THE OPERATION OF THE CHANGE OVER VALVES AND ELECTRIC HEATER AS
THE LOGIC FED IN THE PLC WILL BE LIKE THAT,OUTPUTS FROM Q-1 TO Q-7 WILL
ALSO ON AND THE CHANGEOVER VALVE WILL ON AND ELECTRIC HEATER WILL ON
SWITCH ON.
DEW POINT METER OF MITCHELL UK SESOR AND RADIX MAKE HAS BEEN
AIR.
INTERLOCK DETAILS
WHEN THE HEATER TEMPERATURE GOES BEYOND THE SET POINT OF THE
PROCESS DESCRIPTION:
HEATING CYCLE-
DEG C.
COOLING CYCLE-
ADSORER-1 AND THE OUTGOING HOT DRIED AIR WILL BE COOLED DOWN