EST-OLYMPIAN 2010B v1.0 ECM Replacement 02/03/2012 16:45

This document is the configuration settings for an EST-OLYMPIAN 2010B v1.0 engine control module (ECM) replacement. It lists over 100 configuration settings including engine start fault protection times, fuel types, sensor configurations, and input/output configurations. The settings control aspects of the engine like crank duration, cooldown times, voltage thresholds, sensor mapping, and more.

Uploaded by

Candiano Popescu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
75 views65 pages

EST-OLYMPIAN 2010B v1.0 ECM Replacement 02/03/2012 16:45

This document is the configuration settings for an EST-OLYMPIAN 2010B v1.0 engine control module (ECM) replacement. It lists over 100 configuration settings including engine start fault protection times, fuel types, sensor configurations, and input/output configurations. The settings control aspects of the engine like crank duration, cooldown times, voltage thresholds, sensor mapping, and more.

Uploaded by

Candiano Popescu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 65

Page 1 of 65

EST-OLYMPIAN 2010B v1.0


ECM Replacement

02/03/2012 16:45

X - Configuration
X Engine Start Fault Protection Activation Delay Time 30 Sec
X Crank Duration 300 Sec
X Crank Cycle Rest Interval 1 Sec
X Purge Cycle Duration 70 Sec
X Maximum Number of Crank Cycles 0
X Cooldown Duration 3 min
X Start Aid Activation Time 0 Sec
X Crank Alert Activation Time 0 Sec
X Crank Terminate RPM 0 RPM
Engine Fuel Type Configuration Unavailable
X Fuel Shutoff Solenoid Type Configuration Diesel
X Engine Type Configuration Energized to Run
Engine Controller J1939 Data Link Support Configuration Unavailable
X Engine Cooldown Speed Configuration No J1939 Support
X Engine Operating State Input Configuration Rated Speed
X Fuel Priming Feature Enable Status Hardwired Input
X Engine Forced Idle Feature Enable Status Enabled
X Maximum Generator Voltage Output Bias Percentage 33 %
X Generator Nominal Output Voltage 500 Volts
X High Battery Voltage Warning Event Threshold 0,4 Volts
High Battery Voltage Warning Event Notification Delay
X 1500 Sec
Time
X High Battery Voltage Shutdown Event Threshold 0,3 Volts
High Battery Voltage Shutdown Event Notification Delay
X 30 Sec
Time
X Low Battery Voltage Warning Event Threshold 11,3 Volts
Low Battery Voltage Warning Event Notification Delay
X 30 Sec
Time
Low Battery Charging System Voltage Warning Event
X 12,5 Volts
Threshold
Low Battery Charging System Voltage Warning Event

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 2 of 65

X Notification Delay Time 30 Sec


X Low Cranking Voltage Warning Event Threshold 0,0 Volts
Low Cranking Voltage Warning Event Notification Delay
X 2 Sec
Time
Customer Password Security Level to Reset Crank/Start
X 3-Factory, Single Use
Counters
X SCADA Data Link Baud Rate 9600 baud
X SCADA Data Link Parity None
X SCADA Data Link Slave Address 1
X SCADA Data Link Access Password 00000000
X SCADA Data Link Connection Timeout Interval 30,0 Sec
X RS-485 Bias Resistor Enable Status Disabled
X Digital Input #1 Active State Configuration Low
X Digital Input #2 Active State Configuration Low
X Digital Input #3 Active State Configuration Low
X Digital Input #4 Active State Configuration Low
X Digital Input #5 Active State Configuration Low
X Digital Input #6 Active State Configuration Low
X Digital Input #7 Active State Configuration Low
X Digital Input #8 Active State Configuration Low
X Digital Output #1 Active State Configuration Low
X Digital Selector #1 Source Configuration Input #2
X Digital Selector #2 Source Configuration Disabled
X Digital Selector #3 Source Configuration Disabled
X Digital Selector #4 Source Configuration Disabled
X Digital Selector #5 Source Configuration Input #5
X Digital Selector #6 Source Configuration Input #5
X Digital Selector #7 Source Configuration Input #1
X Digital Selector #8 Source Configuration Disabled or Not Installed
X Digital Selector #9 Source Configuration Disabled or Not Installed
X Digital Selector #10 Source Configuration Disabled or Not Installed
X Engine Coolant Temperature Sensor Configuration Sensor
High Engine Coolant Temperature Warning Event
X 95 Deg C
Threshold
High Engine Coolant Temperature Warning Event
X 15 Sec
Notification Delay Time
High Engine Coolant Temperature Shutdown Event
X 107 Deg C
Threshold
X High Engine Coolant Temperature Shutdown Event 5 Sec

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 3 of 65

Notification Delay Time


Low Engine Coolant Temperature Warning Event
X 1 Deg C
Threshold
Low Engine Coolant Temperature Warning Event
X 10 Sec
Notification Delay Time
X Engine Coolant Temperature Sensor Configuration Code Map #1
X Engine Oil Pressure Sensor Configuration Sensor
X Low Engine Oil Pressure Warning Event Threshold 200 kPa
Low Idle Low Engine Oil Pressure Warning Event
X 160 kPa
Threshold
Low Engine Oil Pressure Warning Event Notification Delay
X 10 Sec
Time
X Low Engine Oil Pressure Shutdown Event Threshold 100 kPa
Low Idle Low Engine Oil Pressure Shutdown Event
X 100 kPa
Threshold
Low Engine Oil Pressure Shutdown Event Notification
X 10 Sec
Delay Time
X Low Engine Oil Pressure Step Speed 1350 RPM
X Engine Oil Pressure Sensor Configuration Code Map #1
X Flywheel Teeth 126
X Engine Overspeed Setpoint 1700 RPM
X Engine Underspeed Warning Event Threshold 1350 RPM
X Engine Underspeed Warning Event Notification Delay Time 2,0 Sec
X Engine Underspeed Shutdown Event Threshold 1250 RPM
Engine Underspeed Shutdown Event Notification Delay
X 2,0 Sec
Time
X Engine Speed Sensor Configuration Sensor
X Event Input Function #1 Suspect Parameter Number Engine Coolant Temperature
X Event Input Function #1 Failure Mode Identifier High Shutdown
X Event Input Function #1 Event Notification Delay Time 0 Sec
X Event Input Function #1 Active State Configuration High
X Event Input Function #2 Suspect Parameter Number Engine Oil Pressure
X Event Input Function #2 Failure Mode Identifier Low Shutdown
X Event Input Function #2 Event Notification Delay Time 0 Sec
X Event Input Function #2 Active State Configuration High
X Event Input Function #3 Suspect Parameter Number Custom Event
X Event Input Function #3 Failure Mode Identifier High Warning
X Event Input Function #3 Event Notification Delay Time 0 Sec
X Event Input Function #3 Active State Configuration High
X Event Input Function #4 Suspect Parameter Number Custom Event

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 4 of 65

X Event Input Function #4 Failure Mode Identifier High Warning


X Event Input Function #4 Event Notification Delay Time 0 Sec
X Event Input Function #4 Active State Configuration High
X Event Input Function #5 Suspect Parameter Number Air Filter Differential Pressure
X Event Input Function #5 Failure Mode Identifier High Warning
X Event Input Function #5 Event Notification Delay Time 0 Sec
X Event Input Function #5 Active State Configuration High
X Event Input Function #6 Suspect Parameter Number Air Filter Differential Pressure
X Event Input Function #6 Failure Mode Identifier High Warning
X Event Input Function #6 Event Notification Delay Time 0 Sec
X Event Input Function #6 Active State Configuration High
X Event Input Function #7 Suspect Parameter Number Disabled or Not Installed
X Event Input Function #7 Failure Mode Identifier Disabled or Not Installed
X Event Input Function #7 Event Notification Delay Time Disabled or Not Installed
X Event Input Function #7 Active State Configuration Disabled or Not Installed
X Event Input Function #8 Suspect Parameter Number Disabled or Not Installed
X Event Input Function #8 Failure Mode Identifier Disabled or Not Installed
X Event Input Function #8 Event Notification Delay Time Disabled or Not Installed
X Event Input Function #8 Active State Configuration Disabled or Not Installed
X Event Output Function #1 Suspect Parameter Number Engine Oil Pressure
X Event Output Function #1 Trigger Condition **Disabled
X Event Output Function #2 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #2 Trigger Condition Disabled or Not Installed
X Event Output Function #3 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #3 Trigger Condition Disabled or Not Installed
X Event Output Function #4 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #4 Trigger Condition Disabled or Not Installed
X Event Output Function #5 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #5 Trigger Condition Disabled or Not Installed
X Event Output Function #6 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #6 Trigger Condition Disabled or Not Installed
X Event Output Function #7 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #7 Trigger Condition Disabled or Not Installed
X Event Output Function #8 Suspect Parameter Number Disabled or Not Installed
X Event Output Function #8 Trigger Condition Disabled or Not Installed
X Accessory Data Link Diagnostic Response Configuration Activate Warning Condition
X Accessory Data Link Diagnostic Audible Alert Yes
X Accessory Data Link Diagnostic Breaker #1 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 5 of 65

X Accessory Data Link Diagnostic Breaker #2 Trip No


Air Filter Differential Pressure Sensor Diagnostic Response
X Activate Warning Condition
Configuration
Air Filter Differential Pressure Sensor Diagnostic Audible
X No
Alert
Air Filter Differential Pressure Sensor Diagnostic Breaker
X No
#1 Trip
Air Filter Differential Pressure Sensor Diagnostic Breaker
X No
#2 Trip
Ambient Air Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Ambient Air Temperature Sensor Diagnostic Audible Alert No
Ambient Air Temperature Sensor Diagnostic Breaker #1
X No
Trip
Ambient Air Temperature Sensor Diagnostic Breaker #2
X No
Trip
X Digital Output #1 Diagnostic Response Configuration Activate Warning Condition
X Digital Output #1 Diagnostic Audible Alert No
X Digital Output #1 Diagnostic Breaker #1 Trip No
X Digital Output #1 Diagnostic Breaker #2 Trip No
Engine Coolant Level Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Engine Coolant Level Sensor Diagnostic Audible Alert No
X Engine Coolant Level Sensor Diagnostic Breaker #1 Trip No
X Engine Coolant Level Sensor Diagnostic Breaker #2 Trip No
Engine Coolant Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
Engine Coolant Temperature Sensor Diagnostic Audible
X No
Alert
Engine Coolant Temperature Sensor Diagnostic Breaker
X No
#1 Trip
Engine Coolant Temperature Sensor Diagnostic Breaker
X No
#2 Trip
X Engine Oil Level Sensor Diagnostic Response Configuration Activate Warning Condition
X Engine Oil Level Sensor Diagnostic Audible Alert No
X Engine Oil Level Sensor Diagnostic Breaker #1 Trip No
X Engine Oil Level Sensor Diagnostic Breaker #2 Trip No
Engine Oil Pressure Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Engine Oil Pressure Sensor Diagnostic Audible Alert No
X Engine Oil Pressure Sensor Diagnostic Breaker #1 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 6 of 65

X Engine Oil Pressure Sensor Diagnostic Breaker #2 Trip No


Engine Oil Temperature Sensor Diagnostic Response
X Disable Condition
Configuration
X Engine Oil Temperature Sensor Diagnostic Audible Alert No
X Engine Oil Temperature Sensor Diagnostic Breaker #1 Trip No
X Engine Oil Temperature Sensor Diagnostic Breaker #2 Trip No
Activate Hard Shutdown
X Engine Speed Sensor Diagnostic Response Configuration
Condition
X Engine Speed Sensor Diagnostic Audible Alert Yes
X Engine Speed Sensor Diagnostic Breaker #1 Trip No
X Engine Speed Sensor Diagnostic Breaker #2 Trip No
Exhaust Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Exhaust Temperature Sensor Diagnostic Audible Alert No
X Exhaust Temperature Sensor Diagnostic Breaker #1 Trip No
X Exhaust Temperature Sensor Diagnostic Breaker #2 Trip No
Right Exhaust Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
Right Exhaust Temperature Sensor Diagnostic Audible
X No
Alert
Right Exhaust Temperature Sensor Diagnostic Breaker #1
X No
Trip
Right Exhaust Temperature Sensor Diagnostic Breaker #2
X No
Trip
Left Exhaust Temperature Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Left Exhaust Temperature Sensor Diagnostic Audible Alert No
Left Exhaust Temperature Sensor Diagnostic Breaker #1
X No
Trip
Left Exhaust Temperature Sensor Diagnostic Breaker #2
X No
Trip
Fire Extinguisher Pressure Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Fire Extinguisher Pressure Sensor Audible Alert No
X Fire Extinguisher Pressure Sensor Breaker #1 Trip No
X Fire Extinguisher Pressure Sensor Breaker #2 Trip No
Fuel Filter Differential Pressure Sensor Diagnostic
X Activate Warning Condition
Response Configuration
Fuel Filter Differential Pressure Sensor Diagnostic Audible
X No
Alert

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 7 of 65

Fuel Filter Differential Pressure Sensor Diagnostic Breaker


X No
#1 Trip
Fuel Filter Differential Pressure Sensor Diagnostic Breaker
X No
#2 Trip
X Fuel Level Sensor Diagnostic Response Configuration Activate Warning Condition
X Fuel Level Sensor Diagnostic Audible Alert No
X Fuel Level Sensor Diagnostic Breaker #1 Trip No
X Fuel Level Sensor Diagnostic Breaker #2 Trip No
External Tank Fuel Level Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X External Tank Fuel Level Sensor Diagnostic Audible Alert No
External Tank Fuel Level Sensor Diagnostic Breaker #1
X No
Trip
External Tank Fuel Level Sensor Diagnostic Breaker #2
X No
Trip
Generator Bearing #1 Temperature Sensor Diagnostic
X Activate Warning Condition
Response Configuration
Generator Bearing #1 Temperature Sensor Diagnostic
X No
Audible Alert
Generator Bearing #1 Temperature Sensor Diagnostic
X No
Breaker #1 Trip
Generator Bearing #1 Temperature Sensor Diagnostic
X No
Breaker #2 Trip
Generator Output Sensing System Diagnostic Response
X Activate Warning Condition
Configuration
X Generator Output Sensing System Diagnostic Audible Alert Yes
Generator Output Sensing System Diagnostic Breaker #1
X No
Trip
Generator Output Sensing System Diagnostic Breaker #2
X No
Trip
Engine Oil Filter Differential Pressure Sensor Diagnostic
X Activate Warning Condition
Response Config
Engine Oil Filter Differential Pressure Sensor Diagnostic
X No
Audible Alert
Engine Oil Filter Differential Pressure Sensor Diagnostic
X No
Breaker #1 Trip
Engine Oil Filter Differential Pressure Sensor Diagnostic
X No
Breaker #2 Trip
X Primary Data Link Diagnostic Response Configuration Activate Warning Condition
X Primary Data Link Diagnostic Audible Alert No
X Primary Data Link Diagnostic Breaker #1 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 8 of 65

X Primary Data Link Diagnostic Breaker #2 Trip No


X SCADA Data Link Diagnostic Response Configuration Activate Warning Condition
X SCADA Data Link Diagnostic Audible Alert No
X SCADA Data Link Diagnostic Breaker #1 Trip No
X SCADA Data Link Diagnostic Breaker #2 Trip No
X SCADA Data Link Diagnostic Fault Protection Timer No
Starting Air Pressure Sensor Diagnostic Response
X Activate Warning Condition
Configuration
X Starting Air Pressure Sensor Diagnostic Audible Alert No
X Starting Air Pressure Sensor Diagnostic Breaker #1 Trip No
X Starting Air Pressure Sensor Diagnostic Breaker #2 Trip No
X Battery Charger Failure Diagnostic Response Configuration Activate Warning Condition
X Battery Charger Failure Diagnostic Audible Alert Yes
Engine Controller Not Responding Diagnostic Response
X Activate Warning Condition
Configuration
X Engine Controller Not Responding Diagnostic Audible Alert No
Engine Controller Not Responding Diagnostic Breaker #1
X No
Trip
Engine Controller Not Responding Diagnostic Breaker #2
X No
Trip
Hard Shutdown & Active Only
X Air Damper Closed Event Response Configuration
Condition
X Air Damper Closed Event Audible Alert Yes
High Air Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Configuration
High Air Filter Differential Pressure Warning Event Audible
X Yes
Alert
High Air Filter Differential Pressure Warning Event Breaker
X No
#1 Trip
High Air Filter Differential Pressure Warning Event Breaker
X No
#2 Trip
High Air Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
High Air Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
High Air Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
High Air Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Air Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 9 of 65

Low Air Filter Differential Pressure Warning Event Audible


X Yes
Alert
Low Air Filter Differential Pressure Warning Event Breaker
X No
#1 Trip
Low Air Filter Differential Pressure Warning Event Breaker
X No
#2 Trip
Low Air Filter Differential Pressure Warning Event Fault
X Yes
Protection Timer
Low Air Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
Low Air Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
Low Air Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
Low Air Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Air Filter Differential Pressure Shutdown Event Fault
X Yes
Protection Timer
Activate Hard Shutdown
X Emergency Stop Activated Event Response Configuration
Condition
X Emergency Stop Activated Event Audible Alert Yes
X Emergency Stop Activated Event Breaker #1 Trip No
X Emergency Stop Activated Event Breaker #2 Trip No
High Engine Coolant Level Warning Event Response
X Activate Warning Condition
Configuration
X High Engine Coolant Level Warning Event Audible Alert Yes
X High Engine Coolant Level Warning Event Breaker #1 Trip No
X High Engine Coolant Level Warning Event Breaker #2 Trip No
High Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Engine Coolant Level Shutdown Event Audible Alert Yes
High Engine Coolant Level Shutdown Event Breaker #1
X No
Trip
High Engine Coolant Level Shutdown Event Breaker #2
X No
Trip
Low Engine Coolant Level Warning Event Response
X Activate Warning Condition
Configuration
X Low Engine Coolant Level Warning Event Audible Alert Yes
X Low Engine Coolant Level Warning Event Breaker #1 Trip No
X Low Engine Coolant Level Warning Event Breaker #2 Trip No

Low Engine Coolant Level Shutdown Event Response Activate Hard Shutdown

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 10 of 65

X Configuration Condition
X Low Engine Coolant Level Shutdown Event Audible Alert Yes
Low Engine Coolant Level Shutdown Event Breaker #1
X No
Trip
Low Engine Coolant Level Shutdown Event Breaker #2
X No
Trip
High Engine Coolant Temperature Warning Event
X Activate Warning Condition
Response Configuration
High Engine Coolant Temperature Warning Event Audible
X Yes
Alert
High Engine Coolant Temperature Warning Event Breaker
X No
#1 Trip
High Engine Coolant Temperature Warning Event Breaker
X No
#2 Trip
High Engine Coolant Temperature Warning Event Fault
X Yes
Protection Timer
High Engine Coolant Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
High Engine Coolant Temperature Shutdown Event Audible
X Yes
Alert
High Engine Coolant Temperature Shutdown Event
X No
Breaker #1 Trip
High Engine Coolant Temperature Shutdown Event
X No
Breaker #2 Trip
High Engine Coolant Temperature Shutdown Event Fault
X Yes
Protection Timer
Low Engine Coolant Temperature Warning Event Response
X Disable Condition
Configuration
Low Engine Coolant Temperature Warning Event Audible
X No
Alert
Low Engine Coolant Temperature Warning Event Breaker
X No
#1 Trip
Low Engine Coolant Temperature Warning Event Breaker
X No
#2 Trip
Low Engine Coolant Temperature Warning Event Fault
X No
Protection Timer
Engine Failure To Start Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Engine Failure To Start Shutdown Event Audible Alert Yes
X Engine Failure To Start Shutdown Event Breaker #1 Trip No
X Engine Failure To Start Shutdown Event Breaker #2 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 11 of 65

High Engine Oil Level Warning Event Response


X Activate Warning Condition
Configuration
X High Engine Oil Level Warning Event Audible Alert Yes
X High Engine Oil Level Warning Event Breaker #1 Trip No
X High Engine Oil Level Warning Event Breaker #2 Trip No
High Engine Oil Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Engine Oil Level Shutdown Event Audible Alert Yes
X High Engine Oil Level Shutdown Event Breaker #1 Trip No
X High Engine Oil Level Shutdown Event Breaker #2 Trip No
Low Engine Oil Level Warning Event Response
X Activate Warning Condition
Configuration
X Low Engine Oil Level Warning Event Audible Alert Yes
X Low Engine Oil Level Warning Event Breaker #1 Trip No
X Low Engine Oil Level Warning Event Breaker #2 Trip No
Low Engine Oil Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Low Engine Oil Level Shutdown Event Audible Alert Yes
X Low Engine Oil Level Shutdown Event Breaker #1 Trip No
X Low Engine Oil Level Shutdown Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Response
X Activate Warning Condition
Configuration
X Low Engine Oil Pressure Warning Event Audible Alert Yes
X Low Engine Oil Pressure Warning Event Breaker #1 Trip No
X Low Engine Oil Pressure Warning Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Fault Protection
X Yes
Timer
Low Engine Oil Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Low Engine Oil Pressure Shutdown Event Audible Alert Yes
X Low Engine Oil Pressure Shutdown Event Breaker #1 Trip No
X Low Engine Oil Pressure Shutdown Event Breaker #2 Trip No
Low Engine Oil Pressure Shutdown Event Fault Protection
X Yes
Timer
High Engine Oil Temperature Warning Event Response
X Disable Condition
Configuration
X High Engine Oil Temperature Warning Event Audible Alert No
High Engine Oil Temperature Warning Event Breaker #1
X No
Trip
X High Engine Oil Temperature Warning Event Breaker #2 No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 12 of 65

Trip
High Engine Oil Temperature Warning Event Fault
X No
Protection Timer
High Engine Oil Temperature Shutdown Event Response
X Disable Condition
Configuration
High Engine Oil Temperature Shutdown Event Audible
X No
Alert
High Engine Oil Temperature Shutdown Event Breaker #1
X No
Trip
High Engine Oil Temperature Shutdown Event Breaker #2
X No
Trip
High Engine Oil Temperature Shutdown Event Fault
X No
Protection Timer
Low Engine Oil Temperature Warning Event Response
X Disable Condition
Configuration
X Low Engine Oil Temperature Warning Event Audible Alert No
Low Engine Oil Temperature Warning Event Breaker #1
X No
Trip
Low Engine Oil Temperature Warning Event Breaker #2
X No
Trip
Low Engine Oil Temperature Warning Event Fault
X Yes
Protection Timer
Low Engine Oil Temperature Shutdown Event Response
X Disable Condition
Configuration
X Low Engine Oil Temperature Shutdown Event Audible Alert No
Low Engine Oil Temperature Shutdown Event Breaker #1
X No
Trip
Low Engine Oil Temperature Shutdown Event Breaker #2
X No
Trip
Low Engine Oil Temperature Shutdown Event Fault
X No
Protection Timer
Unexpected Engine Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Unexpected Engine Shutdown Event Audible Alert Yes
X Unexpected Engine Shutdown Event Breaker #1 Trip No
X Unexpected Engine Shutdown Event Breaker #2 Trip No
Engine Overspeed Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Engine Overspeed Shutdown Event Audible Alert Yes
X Engine Overspeed Shutdown Event Breaker #1 Trip No
X Engine Overspeed Shutdown Event Breaker #2 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 13 of 65

Engine Underspeed Warning Event Response


X Activate Warning Condition
Configuration
X Engine Underspeed Warning Event Audible Alert Yes
X Engine Underspeed Warning Event Breaker #1 Trip No
X Engine Underspeed Warning Event Breaker #2 Trip No
X Engine Underspeed Warning Event Fault Protection Timer Yes
Engine Underspeed Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Engine Underspeed Shutdown Event Audible Alert Yes
X Engine Underspeed Shutdown Event Breaker #1 Trip No
X Engine Underspeed Shutdown Event Breaker #2 Trip No
Engine Underspeed Shutdown Event Fault Protection
X Yes
Timer
High Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
X High Exhaust Temperature Warning Event Audible Alert Yes
X High Exhaust Temperature Warning Event Breaker #1 Trip No
X High Exhaust Temperature Warning Event Breaker #2 Trip No
High Exhaust Temperature Warning Event Fault Protection
X No
Timer
High Exhaust Temperature Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Exhaust Temperature Shutdown Event Audible Alert Yes
High Exhaust Temperature Shutdown Event Breaker #1
X No
Trip
High Exhaust Temperature Shutdown Event Breaker #2
X No
Trip
High Exhaust Temperature Shutdown Event Fault
X No
Protection Timer
Low Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
X Low Exhaust Temperature Warning Event Audible Alert Yes
X Low Exhaust Temperature Warning Event Breaker #1 Trip No
X Low Exhaust Temperature Warning Event Breaker #2 Trip No
Low Exhaust Temperature Warning Event Fault Protection
X Yes
Timer
Low Exhaust Temperature Shutdown Event Response
X Disable Condition
Configuration
X Low Exhaust Temperature Shutdown Event Audible Alert No
Low Exhaust Temperature Shutdown Event Breaker #1
X No
Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 14 of 65

Low Exhaust Temperature Shutdown Event Breaker #2


X No
Trip
Low Exhaust Temperature Shutdown Event Fault
X No
Protection Timer
High Right Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
High Right Exhaust Temperature Warning Event Audible
X Yes
Alert
High Right Exhaust Temperature Warning Event Breaker
X No
#1 Trip
High Right Exhaust Temperature Warning Event Breaker
X No
#2 Trip
High Right Exhaust Temperature Warning Event Fault
X No
Protection Timer
High Right Exhaust Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
High Right Exhaust Temperature Shutdown Event Audible
X Yes
Alert
High Right Exhaust Temperature Shutdown Event Breaker
X No
#1 Trip
High Right Exhaust Temperature Shutdown Event Breaker
X No
#2 Trip
High Right Exhaust Temperature Shutdown Event Fault
X No
Protection Timer
Low Right Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
Low Right Exhaust Temperature Warning Event Audible
X Yes
Alert
Low Right Exhaust Temperature Warning Event Breaker
X No
#1 Trip
Low Right Exhaust Temperature Warning Event Breaker
X No
#2 Trip
Low Right Exhaust Temperature Warning Event Fault
X Yes
Protection Timer
Low Right Exhaust Temperature Shutdown Event
X Disable Condition
Response Configuration
Low Right Exhaust Temperature Shutdown Event Audible
X No
Alert
Low Right Exhaust Temperature Shutdown Event Breaker
X No
#1 Trip
Low Right Exhaust Temperature Shutdown Event Breaker
X No
#2 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 15 of 65

Low Right Exhaust Temperature Shutdown Event Fault


X No
Protection Timer
High Left Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
High Left Exhaust Temperature Warning Event Audible
X Yes
Alert
High Left Exhaust Temperature Warning Event Breaker #1
X No
Trip
High Left Exhaust Temperature Warning Event Breaker #2
X No
Trip
High Left Exhaust Temperature Warning Event Fault
X No
Protection Timer
High Left Exhaust Temperature Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
High Left Exhaust Temperature Shutdown Event Audible
X Yes
Alert
High Left Exhaust Temperature Shutdown Event Breaker
X No
#1 Trip
High Left Exhaust Temperature Shutdown Event Breaker
X No
#2 Trip
High Left Exhaust Temperature Shutdown Event Fault
X No
Protection Timer
Low Left Exhaust Temperature Warning Event Response
X Activate Warning Condition
Configuration
Low Left Exhaust Temperature Warning Event Audible
X Yes
Alert
Low Left Exhaust Temperature Warning Event Breaker #1
X No
Trip
Low Left Exhaust Temperature Warning Event Breaker #2
X No
Trip
Low Left Exhaust Temperature Warning Event Fault
X Yes
Protection Timer
Low Left Exhaust Temperature Shutdown Event Response
X Disable Condition
Configuration
Low Left Exhaust Temperature Shutdown Event Audible
X No
Alert
Low Left Exhaust Temperature Shutdown Event Breaker
X No
#1 Trip
Low Left Exhaust Temperature Shutdown Event Breaker
X No
#2 Trip
Low Left Exhaust Temperature Shutdown Event Fault
X No
Protection Timer

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 16 of 65

High Fuel Filter Differential Pressure Warning Event


X Activate Warning Condition
Response Configuration
High Fuel Filter Differential Pressure Warning Event
X Yes
Audible Alert
High Fuel Filter Differential Pressure Warning Event
X No
Breaker #1 Trip
High Fuel Filter Differential Pressure Warning Event
X No
Breaker #2 Trip
High Fuel Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Config Condition
High Fuel Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
High Fuel Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
High Fuel Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Configuration
Low Fuel Filter Differential Pressure Warning Event Audible
X Yes
Alert
Low Fuel Filter Differential Pressure Warning Event
X No
Breaker #1 Trip
Low Fuel Filter Differential Pressure Warning Event
X No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Warning Event Fault
X Yes
Protection Timer
Low Fuel Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
Low Fuel Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
Low Fuel Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
Low Fuel Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Shutdown Event Fault
X Yes
Protection Timer
X High Fuel Level Warning Event Response Configuration Activate Warning Condition
X High Fuel Level Warning Event Audible Alert Yes
X High Fuel Level Warning Event Breaker #1 Trip No
X High Fuel Level Warning Event Breaker #2 Trip No
Activate Hard Shutdown
X High Fuel Level Shutdown Event Response Configuration
Condition

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 17 of 65

X High Fuel Level Shutdown Event Audible Alert Yes


X High Fuel Level Shutdown Event Breaker #1 Trip No
X High Fuel Level Shutdown Event Breaker #2 Trip No
X Low Fuel Level Warning Event Response Configuration Activate Warning Condition
X Low Fuel Level Warning Event Audible Alert Yes
X Low Fuel Level Warning Event Breaker #1 Trip No
X Low Fuel Level Warning Event Breaker #2 Trip No
Activate Hard Shutdown
X Low Fuel Level Shutdown Event Response Configuration
Condition
X Low Fuel Level Shutdown Event Audible Alert Yes
X Low Fuel Level Shutdown Event Breaker #1 Trip No
X Low Fuel Level Shutdown Event Breaker #2 Trip No
External Tank High Fuel Level Warning Event Response
X Activate Warning Condition
Configuration
X External Tank High Fuel Level Warning Event Audible Alert Yes
External Tank High Fuel Level Warning Event Breaker #1
X No
Trip
External Tank High Fuel Level Warning Event Breaker #2
X No
Trip
External Tank High Fuel Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
External Tank High Fuel Level Shutdown Event Audible
X Yes
Alert
External Tank High Fuel Level Shutdown Event Breaker #1
X No
Trip
External Tank High Fuel Level Shutdown Event Breaker #2
X No
Trip
External Tank Low Fuel Level Warning Event Response
X Activate Warning Condition
Configuration
X External Tank Low Fuel Level Warning Event Audible Alert Yes
External Tank Low Fuel Level Warning Event Breaker #1
X No
Trip
External Tank Low Fuel Level Warning Event Breaker #2
X No
Trip
External Tank Low Fuel Level Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
External Tank Low Fuel Level Shutdown Event Audible
X Yes
Alert
External Tank Low Fuel Level Shutdown Event Breaker #1
X No
Trip
External Tank Low Fuel Level Shutdown Event Breaker #2

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 18 of 65

X Trip No
X Fuel Leak Event Response Configuration Activate Warning Condition
X Fuel Leak Event Audible Alert Yes
X Fuel Leak Event Breaker #1 Trip No
X Fuel Leak Event Breaker #2 Trip No
High Engine Oil Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Config
High Engine Oil Filter Differential Pressure Warning Event
X Yes
Audible Alert
High Engine Oil Filter Differential Pressure Warning Event
X No
Breaker #1 Trip
High Engine Oil Filter Differential Pressure Warning Event
X No
Breaker #2 Trip
High Engine Oil Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Config Condition
High Engine Oil Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
High Engine Oil Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
High Engine Oil Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Event
X Activate Warning Condition
Response Config
Low Engine Oil Filter Differential Pressure Warning Event
X Yes
Audible Alert
Low Engine Oil Filter Differential Pressure Warning Event
X No
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Warning Event
X No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Fault
X Yes
Protection Timer
Low Engine Oil Filter Differential Pressure Shutdown Event Activate Hard Shutdown
X
Response Config Condition
Low Engine Oil Filter Differential Pressure Shutdown Event
X Yes
Audible Alert
Low Engine Oil Filter Differential Pressure Shutdown Event
X No
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Shutdown Event
X No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Shutdown Fault
X Yes
Protection Timer

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 19 of 65

Service Maintenance Interval Warning Event Response


X Activate Warning Condition
Configuration
X Service Maintenance Interval Warning Event Audible Alert No
High Starting Air Pressure Warning Event Response
X Activate Warning Condition
Configuration
X High Starting Air Pressure Warning Event Audible Alert Yes
X High Starting Air Pressure Warning Event Breaker #1 Trip No
X High Starting Air Pressure Warning Event Breaker #2 Trip No
High Starting Air Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Starting Air Pressure Shutdown Event Audible Alert Yes
High Starting Air Pressure Shutdown Event Breaker #1
X No
Trip
High Starting Air Pressure Shutdown Event Breaker #2
X No
Trip
Low Starting Air Pressure Warning Event Response
X Activate Warning Condition
Configuration
X Low Starting Air Pressure Warning Event Audible Alert Yes
X Low Starting Air Pressure Warning Event Breaker #1 Trip No
X Low Starting Air Pressure Warning Event Breaker #2 Trip No
Low Starting Air Pressure Warning Event Fault Protection
X Yes
Timer
Low Starting Air Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Low Starting Air Pressure Shutdown Event Audible Alert Yes
X Low Starting Air Pressure Shutdown Event Breaker #1 Trip No
X Low Starting Air Pressure Shutdown Event Breaker #2 Trip No
Low Starting Air Pressure Shutdown Event Fault Protection
X Yes
Timer
X High Gas Pressure Warning Event Response Configuration Activate Warning Condition
X High Gas Pressure Warning Event Audible Alert Yes
X High Gas Pressure Warning Event Breaker #1 Trip No
X High Gas Pressure Warning Event Breaker #2 Trip No
High Gas Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X High Gas Pressure Shutdown Event Audible Alert Yes
X High Gas Pressure Shutdown Event Breaker #1 Trip No
X High Gas Pressure Shutdown Event Breaker #2 Trip No
X Low Gas Pressure Warning Event Response Configuration Activate Warning Condition
X Low Gas Pressure Warning Event Audible Alert Yes

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 20 of 65

X Low Gas Pressure Warning Event Breaker #1 Trip No


X Low Gas Pressure Warning Event Breaker #2 Trip No
Low Gas Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Low Gas Pressure Shutdown Event Audible Alert Yes
X Low Gas Pressure Shutdown Event Breaker #1 Trip No
X Low Gas Pressure Shutdown Event Breaker #2 Trip No
Engine Intake Manifold Charge Combustion Event Activate Hard Shutdown
X
Response Configuration Condition
Engine Intake Manifold Charge Combustion Event Audible
X Yes
Alert
Engine Intake Manifold Charge Combustion Event Loss of
X No
Utility
Engine Intake Manifold Charge Combustion Event Breaker
X No
#1 Trip
Engine Intake Manifold Charge Combustion Event Breaker
X No
#2 Trip
Engine Intake Manifold Charge Combustion Event Fault
X No
Protection Timer
High Generator Bearing #1 Temperature Warning Event
X Activate Warning Condition
Response Configuration
High Generator Bearing #1 Temperature Warning Event
X Yes
Audible Alert
High Generator Bearing #1 Temperature Warning Event
X No
Breaker #1 Trip
High Generator Bearing #1 Temperature Warning Event
X No
Breaker #2 Trip
High Generator Bearing #1 Temperature Warning Event
X No
Fault Protection Timer
High Generator Bearing #1 Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
High Generator Bearing #1 Temperature Shutdown Event
X Yes
Audible Alert
High Generator Bearing #1 Temperature Shutdown Event
X No
Breaker #1 Trip
High Generator Bearing #1 Temperature Shutdown Event
X No
Breaker #2 Trip
High Generator Bearing #1 Temperature Shutdown Event
X No
Fault Protection Timer
Low Generator Bearing #1 Temperature Warning Event
X Activate Warning Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 21 of 65

Low Generator Bearing #1 Temperature Warning Event


X Yes
Audible Alert
Low Generator Bearing #1 Temperature Warning Event
X No
Breaker #1 Trip
Low Generator Bearing #1 Temperature Warning Event
X No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Warning Event
X Yes
Fault Protection Timer
Low Generator Bearing #1 Temperature Shutdown Event
X Disable Condition
Response Configuration
Low Generator Bearing #1 Temperature Shutdown Event
X No
Audible Alert
Low Generator Bearing #1 Temperature Shutdown Event
X No
Breaker #1 Trip
Low Generator Bearing #1 Temperature Shutdown Event
X No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Shutdown Event
X No
Fault Protection Timer
Generator Overcurrent Warning Event Response
X Activate Warning Condition
Configuration
X Generator Overcurrent Warning Event Audible Alert Yes
X Generator Overcurrent Warning Event Breaker #1 Trip No
X Generator Overcurrent Warning Event Breaker #2 Trip No
Generator Overcurrent Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Overcurrent Shutdown Event Audible Alert Yes
X Generator Overcurrent Shutdown Event Breaker #1 Trip No
X Generator Overcurrent Shutdown Event Breaker #2 Trip No
Generator Over Frequency Warning Event Response
X Activate Warning Condition
Configuration
X Generator Over Frequency Warning Event Audible Alert Yes
X Generator Over Frequency Warning Event Breaker #1 Trip No
X Generator Over Frequency Warning Event Breaker #2 Trip No
Generator Over Frequency Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Over Frequency Shutdown Event Audible Alert Yes
Generator Over Frequency Shutdown Event Breaker #1
X No
Trip
Generator Over Frequency Shutdown Event Breaker #2
X No
Trip
Generator Under Frequency Warning Event Response

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 22 of 65

X Configuration Activate Warning Condition


X Generator Under Frequency Warning Event Audible Alert Yes
Generator Under Frequency Warning Event Breaker #1
X No
Trip
Generator Under Frequency Warning Event Breaker #2
X No
Trip
Generator Under Frequency Warning Event Fault
X Yes
Protection Timer
Generator Under Frequency Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Under Frequency Shutdown Event Audible Alert Yes
Generator Under Frequency Shutdown Event Breaker #1
X No
Trip
Generator Under Frequency Shutdown Event Breaker #2
X No
Trip
Generator Under Frequency Shutdown Event Fault
X Yes
Protection Timer
Generator Reverse Power Warning Event Response
X Activate Warning Condition
Configuration
X Generator Reverse Power Warning Event Audible Alert Yes
X Generator Reverse Power Warning Event Breaker #1 Trip No
X Generator Reverse Power Warning Event Breaker #2 Trip No
Generator Reverse Power Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Reverse Power Shutdown Event Audible Alert Yes
Generator Reverse Power Shutdown Event Breaker #1
X No
Trip
Generator Reverse Power Shutdown Event Breaker #2
X No
Trip
Generator Over Voltage Warning Event Response
X Activate Warning Condition
Configuration
X Generator Over Voltage Warning Event Audible Alert Yes
X Generator Over Voltage Warning Event Breaker #1 Trip No
X Generator Over Voltage Warning Event Breaker #2 Trip No
Generator Over Voltage Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Over Voltage Shutdown Event Audible Alert Yes
X Generator Over Voltage Shutdown Event Breaker #1 Trip No
X Generator Over Voltage Shutdown Event Breaker #2 Trip No
Generator Under Voltage Warning Event Response
X Activate Warning Condition
Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 23 of 65

X Generator Under Voltage Warning Event Audible Alert Yes


X Generator Under Voltage Warning Event Breaker #1 Trip No
X Generator Under Voltage Warning Event Breaker #2 Trip No
Generator Under Voltage Warning Event Fault Protection
X Yes
Timer
Generator Under Voltage Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Under Voltage Shutdown Event Audible Alert Yes
X Generator Under Voltage Shutdown Event Breaker #1 Trip No
X Generator Under Voltage Shutdown Event Breaker #2 Trip No
Generator Under Voltage Shutdown Event Fault Protection
X Yes
Timer
Activate Hard Shutdown
X Earth Fault Event Response Configuration
Condition
X Earth Fault Event Audible Alert Yes
X Earth Fault Event Breaker #1 Trip No
X Earth Fault Event Breaker #2 Trip No
Generator Winding #1 High Temperature Warning Event
X Activate Warning Condition
Response Configuration
Generator Winding #1 High Temperature Warning Event
X Yes
Audible Alert
Generator Winding #1 High Temperature Warning Event
X No
Breaker #1 Trip
Generator Winding #1 High Temperature Warning Event
X No
Breaker #2 Trip
Generator Winding #1 High Temperature Warning Event
X No
Fault Protection Timer
Generator Winding #2 High Temperature Warning Event
X Activate Warning Condition
Response Configuration
Generator Winding #2 High Temperature Warning Event
X Yes
Audible Alert
Generator Winding #2 High Temperature Warning Event
X No
Breaker #1 Trip
Generator Winding #2 High Temperature Warning Event
X No
Breaker #2 Trip
Generator Winding #2 High Temperature Warning Event
X No
Fault Protection Timer
Generator Winding #3 High Temperature Warning Event
X Activate Warning Condition
Response Configuration
Generator Winding #3 High Temperature Warning Event
X Yes
Audible Alert

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 24 of 65

Generator Winding #3 High Temperature Warning Event


X No
Breaker #1 Trip
Generator Winding #3 High Temperature Warning Event
X No
Breaker #2 Trip
Generator Winding #3 High Temperature Warning Event
X No
Fault Protection Timer
Generator Winding #1 High Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
Generator Winding #1 High Temperature Shutdown Event
X Yes
Audible Alert
Generator Winding #1 High Temperature Shutdown Event
X No
Breaker #1 Trip
Generator Winding #1 High Temperature Shutdown Event
X No
Breaker #2 Trip
Generator Winding #1 High Temperature Shutdown Event
X No
Fault Protection Timer
Generator Winding #2 High Temperature Shutdown Event
Unavailable
Response Configuration
Generator Winding #2 High Temperature Shutdown Event
X Yes
Audible Alert
Generator Winding #2 High Temperature Shutdown Event
X No
Breaker #1 Trip
Generator Winding #2 High Temperature Shutdown Event
X No
Breaker #2 Trip
Generator Winding #2 High Temperature Shutdown Event
X No
Fault Protection Timer
Generator Winding #3 High Temperature Shutdown Event Activate Hard Shutdown
X
Response Configuration Condition
Generator Winding #3 High Temperature Shutdown Event
X Yes
Audible Alert
Generator Winding #3 High Temperature Shutdown Event
X No
Breaker #1 Trip
Generator Winding #3 High Temperature Shutdown Event
X No
Breaker #2 Trip
Generator Winding #3 High Temperature Shutdown Event
X No
Fault Protection Timer
Generator High Power Warning Event Response
X Activate Warning Condition
Configuration
X Generator High Power Warning Event Audible Alert Yes
X Generator High Power Warning Event Breaker #1 Trip No
X Generator High Power Warning Event Breaker #2 Trip No
High Ambient Air Temperature Warning Event Response

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 25 of 65

X Configuration Activate Warning Condition


High Ambient Air Temperature Warning Event Audible
X Yes
Alert
High Ambient Air Temperature Warning Event Breaker #1
X No
Trip
High Ambient Air Temperature Warning Event Breaker #2
X No
Trip
High Ambient Air Temperature Warning Event Fault
X No
Protection Timer
High Ambient Air Temperature Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
High Ambient Air Temperature Shutdown Event Audible
X Yes
Alert
High Ambient Air Temperature Shutdown Event Breaker
X No
#1 Trip
High Ambient Air Temperature Shutdown Event Breaker
X No
#2 Trip
High Ambient Air Temperature Shutdown Event Fault
X No
Protection Timer
Low Ambient Air Temperature Warning Event Response
X Activate Warning Condition
Configuration
X Low Ambient Air Temperature Warning Event Audible Alert Yes
Low Ambient Air Temperature Warning Event Breaker #1
X No
Trip
Low Ambient Air Temperature Warning Event Breaker #2
X No
Trip
Low Ambient Air Temperature Shutdown Event Response
X Disable Condition
Configuration
Low Ambient Air Temperature Shutdown Event Audible
X No
Alert
Low Ambient Air Temperature Shutdown Event Breaker #1
X No
Trip
Low Ambient Air Temperature Shutdown Event Breaker #2
X No
Trip
Automatic Transfer Switch In Normal Position Event
X Active Only Condition
Response Configuration
Automatic Transfer Switch In Normal Position Event
X No
Audible Alert
Automatic Transfer Switch In Emergency Position Event
X Active Only Condition
Response Config
Automatic Transfer Switch In Emergency Position Event
X No
Audible Alert

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 26 of 65

High Battery Voltage Warning Event Response


X Activate Warning Condition
Configuration
X High Battery Voltage Warning Event Audible Alert Yes
X High Battery Voltage Warning Event Breaker #1 Trip No
X High Battery Voltage Warning Event Breaker #2 Trip No
High Battery Voltage Shutdown Event Response Activate Soft Shutdown
X
Configuration Condition
X High Battery Voltage Shutdown Event Audible Alert Yes
X High Battery Voltage Shutdown Event Breaker #1 Trip No
X High Battery Voltage Shutdown Event Breaker #2 Trip No
Low Battery Voltage Warning Event Response
X Disable Condition
Configuration
X Low Battery Voltage Warning Event Audible Alert No
X Low Battery Voltage Warning Event Breaker #1 Trip No
X Low Battery Voltage Warning Event Breaker #2 Trip No
X Low Battery Voltage Warning Event Fault Protection Timer No
Low Battery Charging System Voltage Warning Event
X Activate Warning Condition
Response Configuration
Low Battery Charging System Voltage Warning Event
X Yes
Audible Alert
Low Battery Charging System Voltage Warning Event
X No
Breaker #1 Trip
Low Battery Charging System Voltage Warning Event
X No
Breaker #2 Trip
Low Battery Charging System Voltage Warning Event Fault
X No
Protection Timer
Generator Breaker Failure To Open Event Response
X Activate Warning Condition
Configuration
X Generator Breaker Failure To Open Event Audible Alert Yes
X Generator Breaker Failure To Open Event Breaker #1 Trip No
X Generator Breaker Failure To Open Event Breaker #2 Trip No
Generator Breaker Failure To Close Event Response Activate Hard Shutdown
X
Configuration Condition
X Generator Breaker Failure To Close Event Audible Alert Yes
X Generator Breaker Failure To Close Event Breaker #1 Trip No
X Generator Breaker Failure To Close Event Breaker #2 Trip No
X Generator Breaker Open Event Response Configuration Active Only Condition
X Generator Breaker Open Event Audible Alert No
X Generator Breaker Closed Event Response Configuration Active Only Condition
X Generator Breaker Closed Event Audible Alert No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 27 of 65

Utility Breaker Failure To Open Event Response Activate Hard Shutdown


X
Configuration Condition
X Utility Breaker Failure To Open Event Audible Alert Yes
X Utility Breaker Failure To Open Event Breaker #1 Trip No
X Utility Breaker Failure To Open Event Breaker #2 Trip No
Utility Breaker Failure To Close Event Response
X Activate Warning Condition
Configuration
X Utility Breaker Failure To Close Event Audible Alert Yes
X Utility Breaker Failure To Close Event Breaker #1 Trip No
X Utility Breaker Failure To Close Event Breaker #2 Trip No
X Utility Breaker Open Event Response Configuration Active Only Condition
X Utility Breaker Open Event Audible Alert No
X Utility Breaker Closed Event Response Configuration Active Only Condition
X Utility Breaker Closed Event Audible Alert No
Emergency Shutdown Override Mode Active Warning
X Activate Warning Condition
Event Response Config
Emergency Shutdown Override Mode Active Warning
X No
Event Audible Alert
X Engine In Cooldown Event Response Configuration Active Only Condition
X Engine In Cooldown Event Audible Alert No
Engine Speed-Generator Output Freq Mismatch Warning
X Activate Warning Condition
Event Response Config
Engine Speed-Generator Output Freq Mismatch Warning
X Yes
Event Audible Alert
Engine Speed-Generator Output Freq Mismatch Warning
X No
Event Breaker #1 Trip
Engine Speed-Generator Output Freq Mismatch Warning
X No
Event Breaker #2 Trip
High Fire Extinguisher Pressure Warning Event Response
X Activate Warning Condition
Configuration
High Fire Extinguisher Pressure Warning Event Audible
X Yes
Alert
High Fire Extinguisher Pressure Warning Event Breaker #1
X No
Trip
High Fire Extinguisher Pressure Warning Event Breaker #2
X No
Trip
High Fire Extinguisher Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
High Fire Extinguisher Pressure Shutdown Event Audible
X Yes
Alert
High Fire Extinguisher Pressure Shutdown Event Breaker

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 28 of 65

X #1 Trip No
High Fire Extinguisher Pressure Shutdown Event Breaker
X No
#2 Trip
Low Fire Extinguisher Pressure Warning Event Response
X Activate Warning Condition
Configuration
Low Fire Extinguisher Pressure Warning Event Audible
X Yes
Alert
Low Fire Extinguisher Pressure Warning Event Breaker #1
X No
Trip
Low Fire Extinguisher Pressure Warning Event Breaker #2
X No
Trip
Low Fire Extinguisher Pressure Warning Event Fault
X No
Protection Timer
Low Fire Extinguisher Pressure Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
Low Fire Extinguisher Pressure Shutdown Event Audible
X Yes
Alert
Low Fire Extinguisher Pressure Shutdown Event Breaker
X No
#1 Trip
Low Fire Extinguisher Pressure Shutdown Event Breaker
X No
#2 Trip
Low Fire Extinguisher Pressure Shutdown Event Fault
X No
Protection Timer
Generator Control Not in Automatic Warning Event Warning & Active Only
X
Response Configuration Condition
Generator Control Not in Automatic Warning Event Audible
X Yes
Alert
Generator Breaker Locked Out Warning Event Response Warning & Active Only
X
Configuration Condition
Generator Breaker Locked Out Warning Event Audible
X Yes
Alert
Generator Breaker Locked Out Warning Event Breaker #1
X No
Trip
Generator Breaker Locked Out Warning Event Breaker #2
X No
Trip
Utility Breaker Locked Out Warning Event Response Warning & Active Only
X
Configuration Condition
X Utility Breaker Locked Out Warning Event Audible Alert Yes
X Utility Breaker Locked Out Warning Event Loss of Utility Yes
X Utility Breaker Locked Out Warning Event Breaker #1 Trip No
X Utility Breaker Locked Out Warning Event Breaker #2 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 29 of 65

Warning & Active Only


X Loss of Utility Event Response Configuration
Condition
X Loss of Utility Event Audible Alert Yes
Utility to Generator Transfer Failure Warning Event
X Activate Warning Condition
Response Configuration
Utility to Generator Transfer Failure Warning Event Audible
X Yes
Alert
Utility to Generator Transfer Failure Warning Event
X No
Breaker #1 Trip
Utility to Generator Transfer Failure Warning Event
X No
Breaker #2 Trip
Utility to Generator Transfer Failure Shutdown Event
Unavailable
Response Configuration
Utility to Generator Transfer Failure Shutdown Event
X Yes
Audible Alert
Utility to Generator Transfer Failure Shutdown Event
X Yes
Breaker #1 Trip
Utility to Generator Transfer Failure Shutdown Event
X No
Breaker #2 Trip
Generator to Utility Transfer Failure Warning Event
X Activate Warning Condition
Response Configuration
Generator to Utility Transfer Failure Warning Event Audible
X Yes
Alert
Generator to Utility Transfer Failure Warning Event
X No
Breaker #1 Trip
Generator to Utility Transfer Failure Warning Event
X No
Breaker #2 Trip
Activate Hard Shutdown
X Earth Leakage Event Response Configuration
Condition
X Earth Leakage Event Audible Alert Yes
X Earth Leakage Event Breaker #1 Trip No
X Earth Leakage Event Breaker #2 Trip No
X Utility Breaker System Fault Event Response Configuration Activate Warning Condition
X Utility Breaker System Fault Event Audible Alert Yes
X Utility Breaker System Fault Event Breaker #1 Trip No
X Utility Breaker System Fault Event Breaker #2 Trip No
Emergency Power System Supplying Load Event Response Warning & Active Only
X
Configuration Condition
Emergency Power System Supplying Load Event Audible
X No
Alert
X Low Cranking Voltage Warning Event Response Disable Condition

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 30 of 65

Configuration
X Low Cranking Voltage Warning Event Audible Alert No
X Low Cranking Voltage Warning Event Breaker #1 Trip No
X Low Cranking Voltage Warning Event Breaker #2 Trip No
Custom Event #1 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #1 High Warning Event Audible Alert Yes
X Custom Event #1 High Warning Event Breaker #1 Trip No
X Custom Event #1 High Warning Event Breaker #2 Trip No
Custom Event #1 High Warning Event Fault Protection
X No
Timer
Custom Event #1 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #1 High Shutdown Event Audible Alert Yes
X Custom Event #1 High Shutdown Event Breaker #1 Trip No
X Custom Event #1 High Shutdown Event Breaker #2 Trip No
Custom Event #1 High Shutdown Event Fault Protection
X No
Timer
Custom Event #1 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #1 Low Warning Event Audible Alert Yes
X Custom Event #1 Low Warning Event Breaker #1 Trip No
X Custom Event #1 Low Warning Event Breaker #2 Trip No
Custom Event #1 Low Warning Event Fault Protection
X No
Timer
Custom Event #1 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #1 Low Shutdown Event Audible Alert Yes
X Custom Event #1 Low Shutdown Event Breaker #1 Trip No
X Custom Event #1 Low Shutdown Event Breaker #2 Trip No
Custom Event #1 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #1 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #1 Condition Exists Event Audible Alert No
X Custom Event #1 Condition Exists Event Loss of Utility No
X Custom Event #1 Condition Exists Event Breaker #1 Trip No
X Custom Event #1 Condition Exists Event Breaker #2 Trip No
Custom Event #1 Condition Exists Event Fault Protection
X No
Timer

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 31 of 65

Custom Event #2 High Warning Event Response


X Activate Warning Condition
Configuration
X Custom Event #2 High Warning Event Audible Alert Yes
X Custom Event #2 High Warning Event Breaker #1 Trip No
X Custom Event #2 High Warning Event Breaker #2 Trip No
Custom Event #2 High Warning Event Fault Protection
X No
Timer
Custom Event #2 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #2 High Shutdown Audible Alert Yes
X Custom Event #2 High Shutdown Breaker #1 Trip No
X Custom Event #2 High Shutdown Breaker #2 Trip No
X Custom Event #2 High Shutdown Fault Protection Timer No
Custom Event #2 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #2 Low Warning Audible Alert Yes
X Custom Event #2 Low Warning Breaker #1 Trip No
X Custom Event #2 Low Warning Breaker #2 Trip No
X Custom Event #2 Low Warning Fault Protection Timer No
Custom Event #2 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #2 Low Shutdown Event Audible Alert Yes
X Custom Event #2 Low Shutdown Event Breaker #1 Trip No
X Custom Event #2 Low Shutdown Event Breaker #2 Trip No
Custom Event #2 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #2 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #2 Condition Exists Event Audible Alert No
X Custom Event #2 Condition Exists Event Loss of Utility No
X Custom Event #2 Condition Exists Event Breaker #1 Trip No
X Custom Event #2 Condition Exists Event Breaker #2 Trip No
Custom Event #2 Condition Exists Event Fault Protection
X No
Timer
Custom Event #3 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #3 High Warning Event Audible Alert Yes
X Custom Event #3 High Warning Event Breaker #1 Trip No
X Custom Event #3 High Warning Event Breaker #2 Trip No
Custom Event #3 High Warning Event Fault Protection

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 32 of 65

X Timer No
Custom Event #3 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #3 High Shutdown Event Audible Alert Yes
X Custom Event #3 High Shutdown Event Breaker #1 Trip No
X Custom Event #3 High Shutdown Event Breaker #2 Trip No
Custom Event #3 High Shutdown Event Fault Protection
X No
Timer
Custom Event #3 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #3 Low Warning Event Audible Alert Yes
X Custom Event #3 Low Warning Event Breaker #1 Trip No
X Custom Event #3 Low Warning Event Breaker #2 Trip No
Custom Event #3 Low Warning Event Fault Protection
X No
Timer
Custom Event #3 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #3 Low Shutdown Event Audible Alert Yes
X Custom Event #3 Low Shutdown Event Breaker #1 Trip No
X Custom Event #3 Low Shutdown Event Breaker #2 Trip No
Custom Event #3 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #3 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #3 Condition Exists Event Audible Alert No
X Custom Event #3 Condition Exists Event Loss of Utility No
X Custom Event #3 Condition Exists Event Breaker #1 Trip No
X Custom Event #3 Condition Exists Event Breaker #2 Trip No
Custom Event #3 Condition Exists Event Fault Protection
X No
Timer
Custom Event #4 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #4 High Warning Event Audible Alert Yes
X Custom Event #4 High Warning Event Breaker #1 Trip No
X Custom Event #4 High Warning Event Breaker #2 Trip No
Custom Event #4 High Warning Event Fault Protection
X No
Timer
Custom Event #4 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #4 High Shutdown Event Audible Alert Yes

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 33 of 65

X Custom Event #4 High Shutdown Event Breaker #1 Trip No


X Custom Event #4 High Shutdown Event Breaker #2 Trip No
Custom Event #4 High Shutdown Event Fault Protection
X No
Timer
Custom Event #4 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #4 Low Warning Event Audible Alert Yes
X Custom Event #4 Low Warning Event Breaker #1 Trip No
X Custom Event #4 Low Warning Event Breaker #2 Trip No
Custom Event #4 Low Warning Event Fault Protection
X No
Timer
Custom Event #4 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #4 Low Shutdown Event Audible Alert Yes
X Custom Event #4 Low Shutdown Event Breaker #1 Trip No
X Custom Event #4 Low Shutdown Event Breaker #2 Trip No
Custom Event #4 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #4 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #4 Condition Exists Event Audible Alert No
X Custom Event #4 Condition Exists Event Loss of Utility No
X Custom Event #4 Condition Exists Event Breaker #1 Trip No
X Custom Event #4 Condition Exists Event Breaker #2 Trip No
Custom Event #4 Condition Exists Event Fault Protection
X No
Timer
Custom Event #5 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #5 High Warning Event Audible Alert Yes
X Custom Event #5 High Warning Event Breaker #1 Trip No
X Custom Event #5 High Warning Event Breaker #2 Trip No
Custom Event #5 High Warning Event Fault Protection
X No
Timer
Custom Event #5 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #5 High Shutdown Event Audible Alert Yes
X Custom Event #5 High Shutdown Event Breaker #1 Trip No
X Custom Event #5 High Shutdown Event Breaker #2 Trip No
Custom Event #5 High Shutdown Event Fault Protection
X No
Timer

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 34 of 65

Custom Event #5 Low Warning Event Response


X Activate Warning Condition
Configuration
X Custom Event #5 Low Warning Event Audible Alert Yes
X Custom Event #5 Low Warning Event Breaker #1 Trip No
X Custom Event #5 Low Warning Event Breaker #2 Trip No
Custom Event #5 Low Warning Event Fault Protection
X No
Timer
Custom Event #5 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #5 Low Shutdown Event Audible Alert Yes
X Custom Event #5 Low Shutdown Event Breaker #1 Trip No
X Custom Event #5 Low Shutdown Event Breaker #2 Trip No
Custom Event #5 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #5 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #5 Condition Exists Event Audible Alert No
X Custom Event #5 Condition Exists Event Loss of Utility No
X Custom Event #5 Condition Exists Event Breaker #1 Trip No
X Custom Event #5 Condition Exists Event Breaker #2 Trip No
Custom Event #5 Condition Exists Event Fault Protection
X No
Timer
Custom Event #6 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #6 High Warning Event Audible Alert Yes
X Custom Event #6 High Warning Event Breaker #1 Trip No
X Custom Event #6 High Warning Event Breaker #2 Trip No
Custom Event #6 High Warning Event Fault Protection
X No
Timer
Custom Event #6 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #6 High Shutdown Event Audible Alert Yes
X Custom Event #6 High Shutdown Event Breaker #1 Trip No
X Custom Event #6 High Shutdown Event Breaker #2 Trip No
Custom Event #6 High Shutdown Event Fault Protection
X No
Timer
Custom Event #6 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #6 Low Warning Event Audible Alert Yes
X Custom Event #6 Low Warning Event Breaker #1 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 35 of 65

X Custom Event #6 Low Warning Event Breaker #2 Trip No


Custom Event #6 Low Warning Event Fault Protection
X No
Timer
Custom Event #6 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #6 Low Shutdown Event Audible Alert Yes
X Custom Event #6 Low Shutdown Event Breaker #1 Trip No
X Custom Event #6 Low Shutdown Event Breaker #2 Trip No
Custom Event #6 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #6 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #6 Condition Exists Event Audible Alert No
X Custom Event #6 Condition Exists Event Loss of Utility No
X Custom Event #6 Condition Exists Event Breaker #1 Trip No
X Custom Event #6 Condition Exists Event Breaker #2 Trip No
Custom Event #6 Condition Exists Event Fault Protection
X No
Timer
Custom Event #7 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #7 High Warning Event Audible Alert Yes
X Custom Event #7 High Warning Event Breaker #1 Trip No
X Custom Event #7 High Warning Event Breaker #2 Trip No
Custom Event #7 High Warning Event Fault Protection
X No
Timer
Custom Event #7 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #7 High Shutdown Event Audible Alert Yes
X Custom Event #7 High Shutdown Event Breaker #1 Trip No
X Custom Event #7 High Shutdown Event Breaker #2 Trip No
Custom Event #7 High Shutdown Event Fault Protection
X No
Timer
Custom Event #7 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #7 Low Warning Event Audible Alert Yes
X Custom Event #7 Low Warning Event Breaker #1 Trip No
X Custom Event #7 Low Warning Event Breaker #2 Trip No
Custom Event #7 Low Warning Event Fault Protection
X No
Timer
X Custom Event #7 Low Shutdown Event Response Activate Hard Shutdown

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 36 of 65

Configuration Condition
X Custom Event #7 Low Shutdown Event Audible Alert Yes
X Custom Event #7 Low Shutdown Event Breaker #1 Trip No
X Custom Event #7 Low Shutdown Event Breaker #2 Trip No
Custom Event #7 Low Shutdown Event Fault Protection
X No
Timer
Custom Event #7 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #7 Condition Exists Event Audible Alert No
X Custom Event #7 Condition Exists Event Loss of Utility No
X Custom Event #7 Condition Exists Event Breaker #1 Trip No
X Custom Event #7 Condition Exists Event Breaker #2 Trip No
Custom Event #7 Condition Exists Event Fault Protection
X No
Timer
Custom Event #8 High Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #8 High Warning Event Audible Alert Yes
X Custom Event #8 High Warning Event Breaker #1 Trip No
X Custom Event #8 High Warning Event Breaker #2 Trip No
Custom Event #8 High Warning Event Fault Protection
X No
Timer
Custom Event #8 High Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #8 High Shutdown Event Audible Alert Yes
X Custom Event #8 High Shutdown Event Breaker #1 Trip No
X Custom Event #8 High Shutdown Event Breaker #2 Trip No
Custom Event #8 High Shutdown Event Fault Protection
X No
Timer
Custom Event #8 Low Warning Event Response
X Activate Warning Condition
Configuration
X Custom Event #8 Low Warning Event Audible Alert Yes
X Custom Event #8 Low Warning Event Breaker #1 Trip No
X Custom Event #8 Low Warning Event Breaker #2 Trip No
Custom Event #8 Low Warning Event Fault Protection
X No
Timer
Custom Event #8 Low Shutdown Event Response Activate Hard Shutdown
X
Configuration Condition
X Custom Event #8 Low Shutdown Event Audible Alert Yes
X Custom Event #8 Low Shutdown Event Breaker #1 Trip No
X Custom Event #8 Low Shutdown Event Breaker #2 Trip No

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 37 of 65

Custom Event #8 Low Shutdown Event Fault Protection


X No
Timer
Custom Event #8 Condition Exists Event Response
X Active Only Condition
Configuration
X Custom Event #8 Condition Exists Event Audible Alert No
X Custom Event #8 Condition Exists Event Loss of Utility No
X Custom Event #8 Condition Exists Event Breaker #1 Trip No
X Custom Event #8 Condition Exists Event Breaker #2 Trip No
Custom Event #8 Condition Exists Event Fault Protection
X No
Timer
DIO #1 Custom Event # 1 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 1 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 1 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 1 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 1 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 1 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 2 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 2 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 2 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 2 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 2 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 2 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 3 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 3 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 3 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 3 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 38 of 65

DIO #1 Custom Event # 3 Condition Exists Event Breaker


X No
#2 Trip
DIO #1 Custom Event # 3 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 4 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 4 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 4 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 4 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 4 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 4 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 5 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 5 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 5 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 5 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 5 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 5 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 6 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 6 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 6 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 6 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 6 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 6 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 7 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 39 of 65

DIO #1 Custom Event # 7 Condition Exists Event Audible


X No
Alert
DIO #1 Custom Event # 7 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 7 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 7 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 7 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 8 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 8 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 8 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 8 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 8 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 8 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event # 9 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event # 9 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event # 9 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event # 9 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event # 9 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event # 9 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event #10 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event #10 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event #10 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event #10 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 40 of 65

DIO #1 Custom Event #10 Condition Exists Event Breaker


X No
#2 Trip
DIO #1 Custom Event #10 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event #11 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event #11 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event #11 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event #11 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event #11 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event #11 Condition Exists Event Fault
X No
Protection Timer
DIO #1 Custom Event #12 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #1 Custom Event #12 Condition Exists Event Audible
X No
Alert
DIO #1 Custom Event #12 Condition Exists Event Loss of
X No
Utility
DIO #1 Custom Event #12 Condition Exists Event Breaker
X No
#1 Trip
DIO #1 Custom Event #12 Condition Exists Event Breaker
X No
#2 Trip
DIO #1 Custom Event #12 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 1 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 1 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 1 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 1 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 1 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 1 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 2 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 41 of 65

DIO #2 Custom Event # 2 Condition Exists Event Audible


X No
Alert
DIO #2 Custom Event # 2 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 2 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 2 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 2 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 3 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 3 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 3 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 3 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 3 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 3 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 4 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 4 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 4 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 4 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 4 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 4 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 5 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 5 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 5 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 5 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 42 of 65

DIO #2 Custom Event # 5 Condition Exists Event Breaker


X No
#2 Trip
DIO #2 Custom Event # 5 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 6 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 6 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 6 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 6 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 6 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 6 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 7 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 7 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 7 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 7 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 7 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 7 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 8 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event # 8 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event # 8 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 8 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 8 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 8 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event # 9 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 43 of 65

DIO #2 Custom Event # 9 Condition Exists Event Audible


X No
Alert
DIO #2 Custom Event # 9 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event # 9 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event # 9 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event # 9 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event #10 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event #10 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event #10 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event #10 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event #10 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event #10 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event #11 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event #11 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event #11 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event #11 Condition Exists Event Breaker
X No
#1 Trip
DIO #2 Custom Event #11 Condition Exists Event Breaker
X No
#2 Trip
DIO #2 Custom Event #11 Condition Exists Event Fault
X No
Protection Timer
DIO #2 Custom Event #12 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #2 Custom Event #12 Condition Exists Event Audible
X No
Alert
DIO #2 Custom Event #12 Condition Exists Event Loss of
X No
Utility
DIO #2 Custom Event #12 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 44 of 65

DIO #2 Custom Event #12 Condition Exists Event Breaker


X No
#2 Trip
DIO #2 Custom Event #12 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 1 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 1 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 1 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 1 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 1 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 1 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 2 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 2 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 2 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 2 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 2 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 2 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 3 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 3 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 3 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 3 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 3 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 3 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 4 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 45 of 65

DIO #3 Custom Event # 4 Condition Exists Event Audible


X No
Alert
DIO #3 Custom Event # 4 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 4 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 4 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 4 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 5 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 5 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 5 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 5 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 5 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 5 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 6 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 6 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 6 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 6 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 6 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 6 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 7 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 7 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 7 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 7 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 46 of 65

DIO #3 Custom Event # 7 Condition Exists Event Breaker


X No
#2 Trip
DIO #3 Custom Event # 7 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 8 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 8 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 8 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 8 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 8 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 8 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event # 9 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event # 9 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event # 9 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event # 9 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event # 9 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event # 9 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event #10 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event #10 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event #10 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event #10 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event #10 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event #10 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event #11 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 47 of 65

DIO #3 Custom Event #11 Condition Exists Event Audible


X No
Alert
DIO #3 Custom Event #11 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event #11 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event #11 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event #11 Condition Exists Event Fault
X No
Protection Timer
DIO #3 Custom Event #12 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #3 Custom Event #12 Condition Exists Event Audible
X No
Alert
DIO #3 Custom Event #12 Condition Exists Event Loss of
X No
Utility
DIO #3 Custom Event #12 Condition Exists Event Breaker
X No
#1 Trip
DIO #3 Custom Event #12 Condition Exists Event Breaker
X No
#2 Trip
DIO #3 Custom Event #12 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 1 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 1 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 1 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 1 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 1 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 1 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 2 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 2 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 2 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 2 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 48 of 65

DIO #4 Custom Event # 2 Condition Exists Event Breaker


X No
#2 Trip
DIO #4 Custom Event # 2 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 3 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 3 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 3 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 3 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 3 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 3 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 4 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 4 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 4 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 4 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 4 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 4 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 5 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 5 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 5 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 5 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 5 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 5 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 6 Condition Exists Event
X Active Only Condition
Response Configuration

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 49 of 65

DIO #4 Custom Event # 6 Condition Exists Event Audible


X No
Alert
DIO #4 Custom Event # 6 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 6 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 6 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 6 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 7 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 7 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 7 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 7 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 7 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 7 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 8 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 8 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 8 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 8 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event # 8 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event # 8 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event # 9 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event # 9 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event # 9 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event # 9 Condition Exists Event Breaker
X No
#1 Trip

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 50 of 65

DIO #4 Custom Event # 9 Condition Exists Event Breaker


X No
#2 Trip
DIO #4 Custom Event # 9 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event #10 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event #10 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event #10 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event #10 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event #10 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event #10 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event #11 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event #11 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event #11 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event #11 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event #11 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event #11 Condition Exists Event Fault
X No
Protection Timer
DIO #4 Custom Event #12 Condition Exists Event
X Active Only Condition
Response Configuration
DIO #4 Custom Event #12 Condition Exists Event Audible
X No
Alert
DIO #4 Custom Event #12 Condition Exists Event Loss of
X No
Utility
DIO #4 Custom Event #12 Condition Exists Event Breaker
X No
#1 Trip
DIO #4 Custom Event #12 Condition Exists Event Breaker
X No
#2 Trip
DIO #4 Custom Event #12 Condition Exists Event Fault
X No
Protection Timer
Event Warning Condition Response Auto Reset Enable
X Enabled
Status

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 51 of 65

X Event Audible Alert Response Auto Reset Enable Status Enabled


X Event Loss Of Utility Response Auto Reset Enable Status Enabled
X Event Breaker #1 Trip Response Auto Reset Enable Status Enabled
X Event Breaker #2 Trip Response Auto Reset Enable Status Enabled
X Generator Connection Configuration Wye (or Star) Connection
X Generator Potential Transformer Primary Winding Rating 1 Volts
Generator Potential Transformer Secondary Winding
X 1 Volts
Rating
X Generator Current Transformer Primary Winding Rating 150 Amps
X Generator Current Transformer Secondary Winding Rating 5 Amps
X Number of Generator Poles 4 Poles
X Generator Rated Frequency 50 Hz
X Generator Rated Voltage 400 Volts
X Generator Rated Power 70 kW
X Generator Rated Apparent Power 88 kVA
Customer Password Security Level to Reset Generator
X 3-Factory, Single Use
Energy Meters
X Generator Breaker Closing Pulse Active Time Disabled or Not Installed
X Generator Breaker Closing Pulse Rest Interval Disabled or Not Installed
X Generator Breaker Maximum Closing Time Disabled or Not Installed
X Generator Breaker Maximum Opening Time Disabled or Not Installed
X Generator Breaker Lockout Configuration Disabled or Not Installed
X Generator Breaker Type Configuration Disabled or Not Installed
X Automatic Generator Breaker Control Source Configuration Disabled or Not Installed
Generator Definite Time Overcurrent Warning Event
X 100 %
Percentage Threshold
Generator Inverse Time Overcurrent Shutdown Event
X 0,27 Sec
Time Multiplier
Generator Definite Time Overcurrent Shutdown Event
X 125 %
Percentage Threshold
Generator Definite Time Overcurrent Shutdown Event
X 10,0 Sec
Notification Delay Time
Generator Over Frequency Warning Event Percentage
X 105,0 %
Threshold
Generator Over Frequency Warning Event Notification
X 10 Sec
Delay Time
Generator Over Frequency Shutdown Event Percentage
X 110,0 %
Threshold
Generator Over Frequency Shutdown Event Notification
X 2 Sec
Delay Time

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 52 of 65

Generator Under Frequency Warning Event Percentage


X 95,0 %
Threshold
Generator Under Frequency Warning Event Notification
X 10 Sec
Delay Time
Generator Under Frequency Shutdown Event Percentage
X 90,0 %
Threshold
Generator Under Frequency Shutdown Event Notification
X 4 Sec
Delay Time
Generator Over Voltage Warning Event Percentage
X 105 %
Threshold
Generator Over Voltage Warning Event Notification Delay
X 10 Sec
Time
Generator Over Voltage Shutdown Event Percentage
X 110 %
Threshold
Generator Over Voltage Shutdown Event Notification Delay
X 2 Sec
Time
Generator Under Voltage Warning Event Percentage
X 95 %
Threshold
Generator Under Voltage Warning Event Notification Delay
X 10 Sec
Time
Generator Under Voltage Shutdown Event Percentage
X 90 %
Threshold
Generator Under Voltage Shutdown Event Notification
X 4 Sec
Delay Time
X Maximum Engine Speed Bias 400 RPM
X Generator Nominal Output Frequency 50,0 Hz
X Programmable Cycle Timer #1 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #1 Activation Day - Monday Deactivate
X Programmable Cycle Timer #1 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #1 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #1 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #1 Activation Day - Friday Deactivate
X Programmable Cycle Timer #1 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #1 Activation Start Time 0 min
X Programmable Cycle Timer #1 Active Time 1 min
Programmable Cycle Timer #1 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #1 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #2 Activation Day - Sunday Deactivate

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 53 of 65

X Programmable Cycle Timer #2 Activation Day - Monday Deactivate


X Programmable Cycle Timer #2 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #2 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #2 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #2 Activation Day - Friday Deactivate
X Programmable Cycle Timer #2 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #2 Activation Start Time 0 min
X Programmable Cycle Timer #2 Active Time 1 min
Programmable Cycle Timer #2 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #2 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #3 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #3 Activation Day - Monday Deactivate
X Programmable Cycle Timer #3 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #3 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #3 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #3 Activation Day - Friday Deactivate
X Programmable Cycle Timer #3 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #3 Activation Start Time 0 min
X Programmable Cycle Timer #3 Active Time 1 min
Programmable Cycle Timer #3 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #3 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #4 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #4 Activation Day - Monday Deactivate
X Programmable Cycle Timer #4 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #4 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #4 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #4 Activation Day - Friday Deactivate
X Programmable Cycle Timer #4 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #4 Activation Start Time 0 min
X Programmable Cycle Timer #4 Active Time 1 min
Programmable Cycle Timer #4 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #4 Output #2 Activation

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 54 of 65

X Configuration Inactive
X Programmable Cycle Timer #5 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #5 Activation Day - Monday Deactivate
X Programmable Cycle Timer #5 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #5 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #5 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #5 Activation Day - Friday Deactivate
X Programmable Cycle Timer #5 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #5 Activation Start Time 0 min
X Programmable Cycle Timer #5 Active Time 1 min
Programmable Cycle Timer #5 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #5 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #6 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #6 Activation Day - Monday Deactivate
X Programmable Cycle Timer #6 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #6 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #6 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #6 Activation Day - Friday Deactivate
X Programmable Cycle Timer #6 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #6 Activation Start Time 0 min
X Programmable Cycle Timer #6 Active Time 1 min
Programmable Cycle Timer #6 Output #1 Activation
X Inactive
Configuration
Programmable Cycle Timer #6 Output #2 Activation
X Inactive
Configuration
X Programmable Cycle Timer #7 Activation Day - Sunday Deactivate
X Programmable Cycle Timer #7 Activation Day - Monday Deactivate
X Programmable Cycle Timer #7 Activation Day - Tuesday Deactivate
Programmable Cycle Timer #7 Activation Day -
X Deactivate
Wednesday
X Programmable Cycle Timer #7 Activation Day - Thursday Deactivate
X Programmable Cycle Timer #7 Activation Day - Friday Deactivate
X Programmable Cycle Timer #7 Activation Day - Saturday Deactivate
X Programmable Cycle Timer #7 Activation Start Time 0 min
X Programmable Cycle Timer #7 Active Time 1 min
Programmable Cycle Timer #7 Output #1 Activation

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 55 of 65

X Configuration Inactive
Programmable Cycle Timer #7 Output #2 Activation
X Inactive
Configuration
Electronic Control Module Reduced Power Mode Enable
X Enabled
Status
Electronic Control Module Reduced Power Mode Delay
X 20 min
Time
X Relay Output #1 Active State Configuration High
X Relay Output #2 Active State Configuration High
X Relay Output #3 Active State Configuration High
X Relay Output #4 Active State Configuration High
X Relay Output #5 Active State Configuration High
X Relay Output #6 Active State Configuration High
X Relay Output #7 Active State Configuration High
X Relay Output #8 Active State Configuration High
X Maintenance Level 1 Cycle Interval Hours 500 hours
X Maintenance Level 1 Cycle Interval Days 180
Customer Password Security Level to Reset Service
X 3-Factory, Single Use
Maintenance Interval
X Spare Analog Input Enable Status Enabled
X Spare Analog Input Type Configuration Temperature
X Spare Analog Input Suspect Parameter Number Engine Oil Temperature
Spare Analog Input High Warning Event Percentage
X 99 %
Threshold
Spare Analog Input High Temperature Warning Event
X 190 Deg C
Threshold
Spare Analog Input High Pressure Warning Event
X 900 kPa
Threshold
Spare Analog Input High Warning Event Notification Delay
X 10 Sec
Time
Spare Analog Input High Shutdown Event Percentage
X 100 %
Threshold
Spare Analog Input High Temperature Shutdown Event
X 195 Deg C
Threshold
Spare Analog Input High Pressure Shutdown Event
X 1000 kPa
Threshold
Spare Analog Input High Shutdown Event Notification
X 10 Sec
Delay Time
Spare Analog Input Low Warning Event Percentage
X 10 %
Threshold
Spare Analog Input Low Temperature Warning Event

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 56 of 65

X Threshold 15 Deg C
Spare Analog Input Low Pressure Warning Event
X 100 kPa
Threshold
Spare Analog Input Low Warning Event Notification Delay
X 10 Sec
Time
Spare Analog Input Low Shutdown Event Percentage
X 5%
Threshold
Spare Analog Input Low Temperature Shutdown Event
X 10 Deg C
Threshold
Spare Analog Input Low Pressure Shutdown Event
X 75 kPa
Threshold
Spare Analog Input Low Shutdown Event Notification
X 10 Sec
Delay Time
X Spare Analog Input Sensor Configuration Code Map #1
X Programmable Trip Point Function #1 Trigger Condition Trip Above Threshold
Programmable Trip Point Function #1 Percentage
X 90 %
Threshold
Programmable Trip Point Function #1 Hysteresis
X 5%
Percentage
Programmable Trip Point Function #1 Trip Activation
X 10 Sec
Delay Time
Programmable Trip Point Function #1 Trip Deactivation
X 1 Sec
Delay Time
X Programmable Trip Point Function #2 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #2 Percentage
X Disabled or Not Installed
Threshold
Programmable Trip Point Function #2 Hysteresis
X Disabled or Not Installed
Percentage
Programmable Trip Point Function #2 Trip Activation
X Disabled or Not Installed
Delay Time
Programmable Trip Point Function #2 Trip Deactivation
X Disabled or Not Installed
Delay Time
X Programmable Trip Point Function #3 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #3 Percentage
X Disabled or Not Installed
Threshold
Programmable Trip Point Function #3 Hysteresis
X Disabled or Not Installed
Percentage
Programmable Trip Point Function #3 Trip Activation
X Disabled or Not Installed
Delay Time
Programmable Trip Point Function #3 Trip Deactivation
X Disabled or Not Installed
Delay Time

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 57 of 65

X Programmable Trip Point Function #4 Trigger Condition Disabled or Not Installed


Programmable Trip Point Function #4 Percentage
X Disabled or Not Installed
Threshold
Programmable Trip Point Function #4 Hysteresis
X Disabled or Not Installed
Percentage
Programmable Trip Point Function #4 Trip Activation
X Disabled or Not Installed
Delay Time
Programmable Trip Point Function #4 Trip Deactivation
X Disabled or Not Installed
Delay Time
X DIO #1 Event Input Function # 1 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 1 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 2 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 2 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 3 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 3 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 4 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 4 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 5 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 5 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 6 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 6 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 7 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 7 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function # 8 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 8 Failure Mode Identifier Disabled or Not Installed
X DIO #1 Event Input Function # 8 Suspect Parameter Disabled or Not Installed

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 58 of 65

Number
X DIO #1 Event Input Function # 9 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function # 9 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function # 9 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function #10 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function #10 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function #10 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function #11 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function #11 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function #11 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Input Function #12 Notification Delay Time Disabled or Not Installed
X DIO #1 Event Input Function #12 Failure Mode Identifier Disabled or Not Installed
DIO #1 Event Input Function #12 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 1 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 1 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 2 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 2 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 3 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 3 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 4 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 4 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 5 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 5 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 6 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 6 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 6 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 59 of 65

X Number Disabled or Not Installed


X DIO #2 Event Input Function # 7 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 7 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 8 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 8 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function # 9 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function # 9 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function # 9 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function #10 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function #10 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function #10 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function #11 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function #11 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function #11 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Input Function #12 Notification Delay Time Disabled or Not Installed
X DIO #2 Event Input Function #12 Failure Mode Identifier Disabled or Not Installed
DIO #2 Event Input Function #12 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 1 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 1 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 2 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 2 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 3 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 3 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 4 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 4 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 4 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 60 of 65

X Number Disabled or Not Installed


X DIO #3 Event Input Function # 5 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 5 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 6 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 6 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 7 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 7 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 8 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 8 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function # 9 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function # 9 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function # 9 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function #10 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function #10 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function #10 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function #11 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function #11 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function #11 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Input Function #12 Notification Delay Time Disabled or Not Installed
X DIO #3 Event Input Function #12 Failure Mode Identifier Disabled or Not Installed
DIO #3 Event Input Function #12 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 1 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 1 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 2 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 2 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 2 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 61 of 65

X Number Disabled or Not Installed


X DIO #4 Event Input Function # 3 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 3 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 4 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 4 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 5 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 5 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 6 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 6 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 7 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 7 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 8 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 8 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function # 9 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function # 9 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function # 9 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function #10 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function #10 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function #10 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function #11 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function #11 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function #11 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Input Function #12 Notification Delay Time Disabled or Not Installed
X DIO #4 Event Input Function #12 Failure Mode Identifier Disabled or Not Installed
DIO #4 Event Input Function #12 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 62 of 65

X Number Disabled or Not Installed


DIO #1 Event Output Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 1 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 2 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 3 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 4 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 5 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 6 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 7 Trigger Condition Disabled or Not Installed
DIO #1 Event Output Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #1 Event Output Function # 8 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 1 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 2 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 3 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 4 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 5 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 6 Suspect Parameter

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 63 of 65

X Number Disabled or Not Installed


X DIO #2 Event Output Function # 6 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 7 Trigger Condition Disabled or Not Installed
DIO #2 Event Output Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #2 Event Output Function # 8 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 1 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 2 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 3 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 4 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 4 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 5 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 6 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 7 Trigger Condition Disabled or Not Installed
DIO #3 Event Output Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #3 Event Output Function # 8 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 1 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 1 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 2 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 2 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 3 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 3 Trigger Condition Disabled or Not Installed

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 64 of 65

DIO #4 Event Output Function # 4 Suspect Parameter


X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 4 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 5 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 5 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 6 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 6 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 7 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 7 Trigger Condition Disabled or Not Installed
DIO #4 Event Output Function # 8 Suspect Parameter
X Disabled or Not Installed
Number
X DIO #4 Event Output Function # 8 Trigger Condition Disabled or Not Installed
X DIO #1 Digital Output #1 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #2 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #3 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #4 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #5 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #6 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #7 Source Configuration Disabled or Not Installed
X DIO #1 Digital Output #8 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #1 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #2 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #3 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #4 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #5 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #6 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #7 Source Configuration Disabled or Not Installed
X DIO #2 Digital Output #8 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #1 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #2 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #3 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #4 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #5 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #6 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #7 Source Configuration Disabled or Not Installed
X DIO #3 Digital Output #8 Source Configuration Disabled or Not Installed

file://C:\ProgramData\Perkins\Olympian Service Tool\temp\STPLReport3.HTM 02/03/2012


Page 65 of 65

X DIO #4 Digital Output #1 Source Configuration Disabled or Not Installed


X DIO #4 Digital Output #2 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #3 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #4 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #5 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #6 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #7 Source Configuration Disabled or Not Installed
X DIO #4 Digital Output #8 Source Configuration Disabled or Not Installed
X Generator/Utility Automatic Transfer Enable Status Disabled or Not Installed
X Loss of Utility Event Notification Delay Time Disabled or Not Installed
X Utility to Generator Transfer Delay Time Disabled or Not Installed
X Generator to Utility Transfer Delay Time Disabled or Not Installed
X Generator to Utility Fast Transfer Delay Time Disabled or Not Installed
Utility to Generator Transfer Failure Warning Event
X Disabled or Not Installed
Threshold
Utility to Generator Transfer Failure Shutdown Event
X Disabled or Not Installed
Threshold
Generator to Utility Transfer Failure Warning Event
X Disabled or Not Installed
Threshold
Generator/Utility Automatic Transfer Unpowered Load
X Disabled or Not Installed
Time
X Generator Ready to Load Threshold Percentage Disabled or Not Installed
X Generator Ready to Load Delay Time Disabled or Not Installed
X Generator to Utility Transfer Mode Disabled or Not Installed
X Utility Breaker Closing Pulse Active Time Disabled or Not Installed
X Utility Breaker Closing Pulse Rest Interval Disabled or Not Installed
X Utility Breaker Maximum Closing Time Disabled or Not Installed
X Utility Breaker Maximum Opening Time Disabled or Not Installed
X Utility Breaker Lockout Configuration Disabled or Not Installed
X Utility Breaker Type Configuration Disabled or Not Installed
X Automatic Utility Breaker Control Source Configuration Disabled or Not Installed
Engine Serial Number Not Programmed
X Display Pressure Units Configuration bar
X Display Temperature Units Configuration Degrees Centigrade (Celsius)