TechDaten Man 7SJ85 V0700 EnUS
TechDaten Man 7SJ85 V0700 EnUS
TechDaten Man 7SJ85 V0700 EnUS
00 and higher
Overcurrent Protection 7SJ82/7SJ85
Technical Data
Energy Automation
NOTE
i For your own safety, observe the warnings and safety instructions contained in this document, if available.
Target Audience
Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main-
tenance of automation, selective protection and control equipment, and operational crew in electrical installa-
tions and power plants.
Scope
This manual applies to the SIPROTEC 5 device family.
Further Documentation
[dwprefdm-221012-01.tif, 3, en_US]
Device manuals
Each Device manual describes the functions and applications of a specific SIPROTEC 5 device. The
printed manual and the online help for the device have the same informational structure.
Hardware manual
The Hardware manual describes the hardware building blocks and device combinations of the
SIPROTEC 5 device family.
Operating manual
The Operating manual describes the basic principles and procedures for operating and assembling the
devices of the SIPROTEC 5 range.
Product information
The Product information includes general information about device installation, technical data, limiting
values for input and output modules, and conditions when preparing for operation. This document is
provided with each SIPROTEC 5 device.
Engineering Guide
The Engineering Guide describes the essential steps when engineering with DIGSI 5. In addition, the
Engineering Guide shows you how to load a planned configuration to a SIPROTEC 5 device and update
the functionality of the SIPROTEC 5 device.
SIPROTEC 5 catalog
The SIPROTEC 5 catalog describes the system features and the devices of SIPROTEC 5.
Indication of Conformity
This product complies with the directive of the Council of the European Communi-
ties on harmonization of the laws of the Member States relating to electromagnetic
compatibility (EMC Council Directive 2004/108/EC valid until April, 19th of 2016,
EMC Council Directive 2014/30/EU valid from April, 20th of 2016) and concerning
electrical equipment for use within specified voltage limits (Low Voltage Directive
2006/95/EG valid until April, 19th of 2016, Low Voltage Directive 2014/35/EU
valid from April, 20th of 2016).
This conformity has been proved by tests performed according to the Council Direc-
tive in accordance with the product standard EN 60255-26 (for EMC directive) and
with the product standard EN 60255-27 (for Low Voltage Directive) by Siemens AG.
The device is designed and manufactured for application in an industrial environ-
ment.
The product conforms with the international standards of IEC 60255 and the
German standard VDE 0435.
Other Standards
IEEE Std C 37.90
The technical data of the product is approved in accordance with UL.
For more information about the UL database, see www.ul.com
Select Online Certifications Directory and enter E194016 as UL File Number.
[ul_listed_c_us, 1, --_--]
Additional Support
For questions about the system, please contact your Siemens sales partner.
Support
Our Customer Support Center provides a 24-hour service.
Phone: +49 (180) 524-7000
Fax: +49 (180) 524-2471
E-Mail: [email protected]
Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG
Siemens Power Academy TD
Humboldtstrae 59
90459 Nrnberg
Germany
Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment
(module or device). However, it comprises important information that must be followed for personal safety, as
well as to avoid material damage. Information is highlighted and illustrated as follows according to the degree
of danger:
! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
Comply with all instructions, in order to avoid death or severe injuries.
! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
Comply with all instructions, in order to avoid death or severe injuries.
! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
Comply with all instructions, in order to avoid moderate or minor injuries.
NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
Comply with all instructions, in order to avoid property damage.
NOTE
i Important information about the product, product handling or a certain section of the documentation which
must be given particular attention.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
Proper transport
Proper storage, setup and installation
Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.
Current Inputs
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Protection-class current trans- Rated current Irated Measuring range of Measuring range of the
formers the modular devices non-modular devices
5A 0 A to 500 A 0 A to 250 A
1A 0 A to 100 A 0 A to 50 A
Instrument transformers 5A 0 A to 8 A 0 A to 8 A
1A 0 A to 1.6 A 0 A to 1.6 A
Power consumption per current Approx. 0.1 VA
circuit at rated current
Thermal rating 500 A for 1 s
(protection and instrument trans- 150 A for 10 s
formers) 20 A continuously
25 A for 3 min
30 A for 2 min
Dynamic load-carrying capacity 1250 A one half wave
Voltage Input
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Input and output modules IO202/IO208/IO211/IO214 IO215
Measuring range 0 V to 200 V 0 V to 7.07 V
Input impedance 200 k 7 k
Thermal rating 230 V continuously 20 V continuously
NOTE
i Due to possible EMC interference, pay attention to ensure that only the connections for current or for
voltage are used on the device.
Use shielded cables.
28 The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or as current input.
29 The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or as current input.
Masses
Device Size
Weight of the Modular Devices
Type of construction 1/3 1/2 2/3 5/6 1/1
Flush-mounting device 4.8 kg 8.1 kg 11.4 kg 14.7 kg 18.0 kg
Surface-mounted device with inte- 7.8 kg 12.6 kg 17.4 kg 22.2 kg 27.0 kg
grated on-site operation panel
Surface-mounted device with 5.1 kg 8.7 kg 12.3 kg 15.9 kg 19.5 kg
detached on-site operation panel
Size Weight
Detached on-site operation panel 1/3 1.9 kg
Detached on-site operation panel 1/6 1.1 kg
Device Size
Weight of the Non-Modular Devices 7xx82
Type of construction 1/3
Flush-mounting device 3.7 kg
Bracket for non-modular surface- 1.9 kg
mounting variant
Type of Construction (Maximum Dimensions) Width over all x Height over all x Depth 30(in Inches)
Flush-mounting device 150 mm x 268 mm x 229 mm (5.91 x 10.55 x 9.02)
Surface-mounted device with integrated on-site oper- 150 mm x 314 mm x 337 mm (5.91 x 12.36 x 13.27)
ation panel
Surface-mounted device with detached on-site opera- 150 mm x 314 mm x 230 mm (5.91 x 12.36 x 9.06)
tion panel
Type of Width over all x Height over all x Depth 31(in Inches)
Construction
(Maximum
Dimensions)
Type of 1/3 1/2 2/3 5/6 1/1
construction
Flush-mounting 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
device 268 mm x 268 mm x 268 mm x 268 mm x 268 mm x
229 mm (5.91 x 229 mm (8.86 x 229 mm(11.81 x 229 mm (14.76 x 229 mm (17.72 x
10.55 x 9.02) 10.55 x 9.02) 10.55 x 9.02) 10.55 x 9.02) 10.55 x 9.02)
Surface- 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
mounted device 314 mm x 314 mm x 314 mm x 314 mm x 314 mm x
with integrated 337 mm (5.91 x 337 mm (8.86 x 337 mm (11.81 x 337 mm (14.76 x 337 mm (17.72 x
on-site operation 12.36 x 13.27) 12.36 x 13.27) 12.36 x 13.27) 12.36 x 13.27) 12.36 x 13.27)
panel
Type of Width over all x Height over all x Depth 31(in Inches)
Construction
(Maximum
Dimensions)
Surface- 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
mounted device 314 mm x 314 mm x 314 mm x 314 mm x 314 mm x
with detached 230 mm (5.91 x 230 mm (8.86 x 230 mm (11.81 x 230 mm (14.76 x 230 mm (17.72 x
on-site operation 12.36 x 9.06) 12.36 x 9.06) 12.36 x 9.06) 12.36 x 9.06) 12.36 x 9.06)
panel
Minimum Bending Radii of the Connecting Cables Between the On-Site Operation Panel and the Base Module
Fiber-optic cable R = 50 mm
Pay attention to the length of the cable protection
sleeve, which you must also include in calculations.
D-Sub cable R = 50 mm (minimum bending radius)
UL Note
Type of Line Current Terminal Voltage Terminal with Voltage Terminal with
Spring-Loaded Terminals Screw Connection
Litz wire with ring-type lug 2.7 Nm No ring-type lug No ring-type lug
Stranded wires with boot- 2.7 Nm 1.0 Nm 0.6 Nm
lace ferrules or pin-type
lugs
Solid conductor, bare 2.0 Nm 1.0 Nm
(2 mm2)
NOTE
Mode On
Off
PPS Synchronization Telegr. and PPS
Telegr. or PPS
PPS synchronization off
Blocking of the unbalanced Yes
runtimes No
Maximum signal runtime threshold 0.1 ms to 30.0 ms Increments of 0.1 ms
Maximum runtime difference 0.000 ms to 3.000 ms Increments of 0.001 ms
Failure indication after 0.05 s to 2.00 s Increments of 0.01 s
Failure indication after 0.0 s to 6.0 s Increments of 0.1 s
Max. error rate/h 0.000 % to 100.000 % Increments of 0.001 %
Max. error rate/min 0.000 % to 100.000 % Increments of 0.001 %
PPS failure indication after 0.5 s to 60.0 s Increments of 0.1 s
Transmission Rate
Direct connection:
Transmission rate 2048 kbit/s
Connection via communication networks:
Supported network interfaces G703.1 with 64 kBit/s
G703-T1 with 1.455 MBit/s
G703-E1 with 2.048 MBit/s
X.21 with 64 kBit/s or 128 kBit/s or 512 kBit/s
Pilot wires with 128 kbit/s
Transmission rate 64 kBit/s at G703.1
1.455 MBit/s at G703-T1
2.048 MBit/s at G703-E1
512 kBit/s or 128 kBit/s or 64 kBit/s at X.21
128 kBit/s for pilot wires
Transmission Times
Priority 1
Response time, total approx.
For 2 ends Minimum 8 ms
Typical 10 ms
For 3 ends Minimum 10 ms
Typical 14 ms
For 6 ends Minimum 15 ms
Typical 18 ms
Dropout times, total approx.
For 2 ends Typical 20 ms
For 3 ends Typical 20 ms
For 6 ends Typical 26 ms
Priority 2
Response time, total approx.
For 2 ends Minimum 9 ms
Typical 16 ms
For 3 ends Minimum 12 ms
Typical 18 ms
For 6 ends Minimum 17 ms
Typical 23 ms
Dropout times, total approx.
For 2 ends Typical 24 ms
For 3 ends Typical 25 ms
For 6 ends Typical 32 ms
Priority 333
Response time, total approx.
For 2 ends Minimum
Typical 100 ms
For 3 ends Minimum
Typical 150 ms
For 6 ends Minimum
Typical 200 ms
Dropout times, total approx.
For 2 ends Typical 100 ms
For 3 ends Typical 150 ms
For 6 ends Typical 200 ms
34 If provided
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
35 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
36 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Tolerances
Setting Values
Dropout Ratio
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Extension of the operate time during operation with transformer inrush- Approx. 10 ms
current detection
[dwocpki1-080213-01.tif, 1, en_US]
Figure 12-1 Operate Curves and Dropout-Time Characteristic Curves according to IEC
[dwocpki2-080213-01.tif, 1, en_US]
Figure 12-2 Operate Curves and Dropout-Time Characteristic Curves According to IEC
[dwocpka1-080213-01.tif, 1, en_US]
Figure 12-3 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
[dwocpka2-080213-01.tif, 1, en_US]
Figure 12-4 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
[dwocpka3-080213-01.tif, 1, en_US]
Figure 12-5 Tripping Characteristic Curves and Dropout Characteristic Curves According to ANSI/IEEE
[dwocpka4-080213-01.tif, 1, en_US]
Figure 12-6 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
Tolerances
Setting Values
Dropout Ratio
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
f < 10 Hz Active
f > 80 Hz
Tolerances
Extension of the operate time during operation with transformer inrush- Approx. 10 ms
current detection
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 %
for undercurrent/undervoltage functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Voltage transformer 150 mV sec.
The operate curves and dropout-time characteristic curves according to IEC can be found in the chapter
Technical Data under Inverse-Time Overcurrent Protection.
Tolerances
Transient excess pickup in method of measurement = fundamental component, for > < 5 %
100 ms (with complete unbalance)
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
38 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
39 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Tolerances
3I0 measured via I440, method of measurement = 1 % of the setting value or 5 mA (Irated = 1 A)
fundamental component or 25 mA (Irated = 5 A), (frated 10 %)
3I0 measured via I441, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated 10 %)
Time delays 1 % of the setting value or 10 ms
Setting Values
Dropout Ratio
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
40 Slightlyexpanded tolerances will occur during the calculation of 3I0, maximum factor of 2
41 Slightlyexpanded tolerances will occur during the calculation of 3I0, maximum factor of 2
42 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 l
rated,sec.
Extension of the operate time during operation with transformer inrush- Approx. 10 ms
current detection
[dwocpki1-080213-01.tif, 1, en_US]
Figure 12-7 Operate Curves and Dropout-Time Characteristic Curves According to IEC
[dwocpki2-080213-01.tif, 1, en_US]
Figure 12-8 Operate Curves and Dropout-Time Characteristic Curves According to IEC
[dwocpka1-080213-01.tif, 1, en_US]
Figure 12-9 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
[dwocpka2-080213-01.tif, 1, en_US]
Figure 12-10 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
[dwocpka3-080213-01.tif, 1, en_US]
Figure 12-11 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
[dwocpka4-080213-01.tif, 1, en_US]
Figure 12-12 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
Tolerances
3I0 measured via I443, method of measurement = 1 % of the setting value or 5 mA (Irated = 1 A)
fundamental component or 25 mA (Irated = 5 A), (frated 10 %)
3I0 measured via I444, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated 10 %)
Operate time for 2 I/I threshold value 20 5 % of the setting value or +2 % current tolerance or
30 ms
43 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
44 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
Dropout time for 2 I/threshold value I 0.90 5 % of the setting value or +2 % current tolerance or
30 ms
Setting Values
Dropout Ratio
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Tolerances
3I0 measured via I445, method of measurement = 1 % of the setting value or 5 mA (Irated = 1 A)
fundamental component or 25 mA (Irated = 5 A), (frated 10 %)
3I0 measured via I446, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A), (frated 10 %)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated 10 %)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A), (frated 10 %)
Operate time for 2 I/I threshold value 20 5 % of the setting value or +2 % current tolerance or
30 ms
Dropout time for I/I threshold value 0.90 5 % of the setting value or +2 % current tolerance or
30 ms
45 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
46 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
Setting Values for the IEC/ANSI Characteristic Curve Stage Type (Inverse-Time)
Type of characteristic curve Characteristic curves according to IEC (see Table 12-3) and
ANSI (see Table 12-4)
Dropout Disk emulation
Instantaneous
Time multiplier 0.00 to 15.00 Increments of 0.01
Minimum time of the curve 0.00 to 1.00 s Increments of 0.01 s
Additional time delay 0.00 to 60.00 s Increments of 0.01 s
Dropout Ratio for the IEC/ANSI Characteristic Curve Stage Type (Inverse-Time)
Setting Values for Stage Type with User-Defined Characteristic Curve (Inverse Time)
47 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
Dropout Ratio for Stage Type with User-Defined Characteristic Curve (Inverse Time)
Direction Determination
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Times
Tolerances
48 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Extremely inverse: type C Refer to the respective picture of the technical data for the non-
Long-time inverse: type B dir-OC-ground function 12.7.2 Inverse-Time Overcurrent Protec-
tion, Ground
Long-time inverse
Moderately inverse
Very inverse
Extremely inverse
Uniformly inverse
[dwloginv-300913, 2, en_US]
Setting Values for Stage Type Logarithmic Inverse Time with Knee-Point Overcurrent Protection
[dwdrloinkn-171013, 1, en_US]
Figure 12-14 Operate Curve of the Logarithmic Inverse Time with Knee-Point Characteristic (In the
Example of Threshold = 0.004 A)
Dropout value for Stage Type Logarithmic Inverse Time with Knee-Point Overcurrent Protection
Setting Values for Stage Type User-Defined Characteristic Curve Overcurrent Protection
Dropout Values for Stage Type User-Defined Characteristic Curve Overcurrent Protection
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
Tolerances
Inverse-time dropout time to IEC, ANSI, logarithmic 5 % of setting value or +2 % current tolerance or
inverse-time characteristic, logarithmic inverse time with 30 ms
knee-point characteristic, and user-defined character-
istic curve
Direction-determination angle error 1
Operat.-range limit Imax 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Content 2nd harmonic 10 % to 45 % Increments of 1 %
Duration of the cross-blocking 0.03 s to 200.00 s Increments of 0.01 s
Times
Dropout Ratios
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Operating Range
Tolerances
Threshold value I> 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold value 3I0> 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
External trip initiation Yes
No
Operating mode Light only
Current and light
Channel Possible settings, application-dependent
Dropout Ratio
Times
49 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter
12.1.4 Relay Outputs
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
Operating Range
Tolerances
50 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Tolerances
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
51 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
52 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Tolerances
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
53 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
Extension of the operate time during operation with transformer inrush- Approx. 10 ms
current detection
The tripping characteristic curves and dropout characteristic curves according to IEC can be found in the
Technical Data chapter under Inverse Time-Overcurrent Protection.
Tolerances
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Tolerances
Extension of the operate time during operation with transformer inrush- Approx. 10 ms
current detection
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
Tolerances
54 OOT (Output Operating Time) additional time delay of the output medium used, for example, 5 ms with fast relay
Threshold value For current transformer type protec- 0.030 A to 35.000 A Increments of 0.001 A
3I0> interm. tion and Irated = 1 A
For current transformer type protec- 0.15 A to 175.00 A Increments of 0.01 A
tion and Irated = 5 A
For IN transformer For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A
type sensitive For Iph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A
and IN-rated = 1 A
For IN transformer For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A
type sensitive For Iph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A
and IN-rated = 5 A
Number of pickups until intermittent ground fault 2 to 10 Increments of 1
Pickup extension time 0.00 s to 10.00 s Increments of 0.01 s
Sum of extended pickup times 0.00 s to 100.00 s Increments of 0.01 s
Reset time 1.00 s to 600.00 s Increments of 0.01 s
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
55 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Tolerances
Threshold value 3I0> For current transformer type 0.030 A to 35.000 A Increments of 0.001 A
protection and Irated = 1 A
For current transformer type 0.15 A to 175.00 A Increments of 0.01 A
protection and Irated = 5 A
For IN transformer For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A
type sensitive and For Iph-rated = 5 A 0.001 A to 175.00 A Increments of 0.001 A
IN-rated = 1 A
For IN transformer For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A
type sensitive and For Iph-rated = 5 A 0.005 A to 175.00 A Increments of 0.001 A
IN-rated = 5 A
Number of pulses until intermittent ground 2 to 10 Increments of 1
fault
Pickup extension time 0.00 s to 10.00 s Increments of 0.01 s
Sum of extended pickup times 0.00 s to 100.00 s Increments of 0.01 s
Reset time 1.00 s to 600.00 s Increments of 0.01 s
Number of pulses for operate 2 to 100 Increments of 1
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
56 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Tolerances
12.18.1 General
Setting Values
Tolerances
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
You can find the the Technical data of the overvoltage protection stage with zero-sequence system/residual
voltage chapter 12.29 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage .
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
59 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
60 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
Tolerances
61 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
Tolerances
Setting Values
62 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Times
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
63 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
64 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout difference
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
Tolerances
65 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fast relays, see Chapter Relay
Outputs
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
Dropout difference of 3 % of the object rated current
Times
66 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Tolerances
Pickup value
I2/Irated, obj Approx. 2 % of the setting value or 0.8 % of the absolute value
I2/I1 Approx. 2 % of the setting value or 4 % of the absolute value (I1 > 50
mA (Irated = 1 A) or 250 mA (Irated = 5 A))
Time delays 1 % of the setting value or 10 ms
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
Dropout difference of 3 % of the object rated current
Times
Dropout Ratio
67 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Normal inverse: type A See chapter 12.5.2 Inverse Time-Overcurrent Protection, Phases ,
Very inverse: type B Figure 12-1
Extremely inverse: type C See chapter 12.5.2 Inverse Time-Overcurrent Protection, Phases ,
Long-time inverse: type B Figure 12-2
Tolerances
Extension time of the blocking after a 1-pole pause 0.00 s to 60.00 s Increments of 0.01 s
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
Dropout difference of 3 % of the object rated current
Times
Operating Range
Tolerances
Threshold values:
Negative-sequence voltage V2 1 % of the setting value or 0.5 V
Negative-sequence current I2 2 % of the setting value or 10 mA at Irated = 1 A
1 % of the setting value or 5 mA at Irated = 5 A
Times:
Independent time delays 1 % of the setting value or 10 ms
68 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Threshold current warning 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Threshold thermal warn. 50% to 100% Increments of 1 %
Dropout threshold operate 50% to 99% Increments of 1 %
Emerg. start T overtravel 0 s to 15 000 s Increments of 10 s
K-factor acc. to IEC 60225-8 0.10 to 4.00 Increments of 0.01
Thermal time constant 10 s to 60 000 s Increments of 1 s
Cooling time constant 10 s to 60 000 s Increments of 1 s
Imax thermal 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Imin cooling 1 A @ 50 and 100 Irated 0.000 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.00 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.000 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.000 A to 8.000 A Increments of 0.001 A
temperature rise at Irated 40 K to 200 K Increments of 1 K
Default temperature -55C to 55C Increments of 1C
Minimal temperature -55C to 40C Increments of 1C
Dropout Ratios
Tripping threshold (fixed at 100 %) Dropout if value drops below operate indication dropout
threshold
Thermal warning threshold About 0.99 of the setting value
Current warning threshold About 0.95 of the setting value
Tolerances
With reference to k* Irated For Irated = 1 A 2 % or 10 mA, class 2 % acc. to IEC 60255-8
For Irated = 5 A 2 % or 50 mA, class 2 % acc. to IEC 60255-8
With reference to operate time 3 % or 1 s, class 3 % acc. to IEC 60255-8 for I/(k *
Irated) > 1.25
Operate Curve
Operate curve
[dwauslke-100611-01.tif, 1, en_US]
Dropout Ratio
Operate Characteristics
[dwunbaop-300913, 1, en_US]
Times
69 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fast relays
Tolerances
Harmonics 1%
Up to 10 % 3rd harmonic 1%
Up to 10 % 5th harmonic
Dropout Ratio
Times
70 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
f < 10 Hz Active
f > 80 Hz
Tolerances
Current threshold Iunbal. 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.150 A to 175.000 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.005 A
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Measured value compensated
non-compensated
Dropout Ratio
Times
71 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Tolerances
Dropout Ratio
Times
Operate time with time delay = 0 ms Approx. 30 ms + OOT (Output Operating Time) at 50 Hz
Approx. 27 ms + OOT (Output Operating Time) at 60 Hz
Dropout time Approx. 20 ms + OOT (Output Operating Time) at 50 Hz
Approx. 18 ms + OOT (Output Operating Time) at 60 Hz
Tolerances
Operate Curve
Threshold value I/IratedObj 0.05 to 2.00 Increments of 0.01
Gradient 1 0.00 to 0.80 Increments of 0.01
Intersection 1 Irest I/IratedObj 0.00 to 5.00 Increments of 0.01
Gradient 2 0.25 to 0.95 Increments of 0.01
Intersection 2 Irest I/IratedObj 1.00 to 20.00 Increments of 0.01
Startup Recognition
Startup threshold value I/IratedObj 0.1 to 2.0 Increments of 0.1
Characteristic-curve increase factor 1.0 to 5.0 Increments of 0.1
Maximum starting time 0.1 s to 180.0 s Increments of 0.1 s
DC-Component Recognition
Characteristic-curve increase factor DC 1.0 to 5.0 Increments of 0.1
Inrush-current detection
Content 2nd harmonic 10 % to 45 % Increments of 1 %
Duration of crossblk. 2. har. 0.00 s to 200.00 s or Increments of 0.01 s
Recognition of External Faults
Additional stabilization threshold value I/IratedObj 1.00 to 20.00 Increments of 0.01
Additional stabilization duration 0.00 s to 5.00 s or Increments of 0.01 s
Operate curve See Figure 12-17
Idiff Fast
Dropout Ratio
Response Tolerance
For preset characteristic-curve parameters; for 2 sides with one measuring point each
Idiff stage and characteristic curve 2 % of the setting value
Idiff fast stage 2 % of the setting value
Time Delays
[dwdifaus-030912-01.tif, 1, en_US]
Operating Times
Frequency tracking 10 Hz to 80 Hz
Where
Top Operate delay
Tinv Inverse-time delay
Tadd Additional time delay (parameter Additional time delay)
Where
Tinv Inverse-time delay
Tp Time multiplier (parameter Time dial)
V Measured voltage
Vthresh Threshold value (parameter Threshold)
k Curve constant k (parameter Charact. constant k)
Curve constant (parameter Charact. constant )
73 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
74 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
75 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
76 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Tolerances
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
Tolerances
77 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Setting Values
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
Tolerances
78 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
Tolerances
79 If the function Overvoltage protection with any voltage is used in a 1-phase function group, the measured-value parameter is not
visible.
80 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
81 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Threshold value
Inverse-time stage 0.80 to 3.00 p.u. Increments of 0.01
Definite-time stage 0.80 to 10.00 p.u. Increments of 0.01
User-defined characteristic curve 0.80 to 3.00 p.u. Increments of 0.01
Tripping delay 0.01 s to 3600.00 s Increments of 0.01 s
Dropout delay 0.00 s to 3600.00 s Increments of 1.00 s
Down integration time 1 min to 1500 min Increments of 1 min
Time multiplier 0.05 to 15.00 Increments of 0.01
Number of value pairs for the operate curve 30 Increments of 1
X values of the operate curve 1.00 p.u. to 4.00 p.u. Increments of 0.01 p.u.
Y values of the operate curve 0.00 s to 9999.99 s Increments of 0.01 s
Number of value pairs for the dropout characteristic 30 Increments of 1
curve
X values of the dropout characteristic curve 0.01 p.u. to 0.95 p.u. Increments of 0.01 p.u.
Y values of the dropout characteristic curve 0.00 s to 9999.99 s Increments of 0.01 s
[dw_pecinv-230813, 2, en_US]
The points on the characteristic curve defined in the standards result from a threshold setting of 1.1. These
single points are connected via semi-logarithmic line segments.
Table 12-7 Peak Overvoltage Inverse-Time Characteristic (for Threshold Setting 1.1)
Times
Tolerances
Peak overvoltage
(33 % harmonics, with reference to fundamental component)
Up to 30th harmonic 1 % of the setting value or 0.005 p.u. (frated 10%)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 0.02 p.u. (frated 10%)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 0.02 p.u. (frated 10%)
Time delays
Measured value of inverse-time stage 5 % of the setting value +1 % of the measured value
or 30 ms
Measured value of definite-time stage 1 % of the setting value or 10 ms
Down integration time 5 % of the setting value or 30 ms
Operate Curve
Top=TInv+Tadd
Where:
Top Operate delay
TInv Inverse-time delay
82 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
[fo_UVP3ph_inverse, 1, en_US]
Where
TInv Inverse-time delay
Tp Time multiplier (Parameter Time dial)
V Measured undervoltage
VThresh Threshold value (Parameter Threshold)
k Curve constant k (Parameter Charact. constant k)
Curve constant (Parameter Charact. constant )
c Curve constant c (Parameter Charact. constant c)
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
83 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
Tolerances
84 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Dropout
The greater dropout difference (= | pickup value dropout value |) of the following 2 criteria
applies:
Dropout difference derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-
voltage functionality.
Minimum absolute dropout difference 150 mV sec.
Times
Tolerances
85 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
86 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
Times
Dropout Ratio
Operating Ranges
Tolerances
Frequency f>
frated - 0.20 Hz < f < frated + 0.20 Hz 5 mHz at V = Vrated
frated - 3.0 Hz < f < frated + 3.0 Hz 10 mHz at V = Vrated
Time delay T(f>) 1 % of the setting value or 10 ms
Minimum voltage 1 % of the setting value or 0.5 V
87 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter
12.1.4 Relay Outputs
Times
Dropout Ratio
Operating Ranges
Tolerances
Frequency f<
frated - 0.20 Hz < f < frated + 0.20 Hz 5 mHz at V = Vrated
frated - 3.0 Hz < f < frated + 3.0 Hz 10 mHz at V = Vrated
Time delay T(f<) 1 % of the setting value or 10 ms
Minimum voltage 1 % of the setting value or 0.5 V
88 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter
12.1.4 Relay Outputs
Times
Dropout Ratio
Tolerances
Times
Tolerances
89 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Times
Tolerances
Reverse power 0.15 % Srated or 5 % of the setting value when Q < 0.5 Srated
Time delays 1 % or 10 ms
Frequency tracking 10 Hz to 80 Hz
Operating Times
Dropout Ratios
Operate Curve
Tolerances
Influencing Quantities
Harmonics
up to 10 % of 3rd harmonics 1%
up to 10 % of 5th harmonics 1%
[dwrsasuf-070513-01.tif, 1, en_US]
Figure 12-19 Operate Curve from the Thermal Replica of the Overexcitation Protection (Default Setting)
Dropout Ratio
Protection stage
Reactive-power flow Q Approx. 0.95
Voltage Approx. 1.05
Release current Approx. 0.95
Reclosure stage
Voltage Approx. 0.95
Release current Approx. 0.95
Times
Tolerances
91 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Setting Values
Dropout Ratios
Circuit-Breaker Supervision
NOTE
i The circuit-breaker failure protection can also work without the circuit-breaker auxiliary contacts stated.
Auxiliary contacts are required for circuit-breaker failure protection in cases where the current flow is
absent or too low for tripping (for example with a transformer or a Buchholz protection).
Times
92 Via
binary inputs
93 Thedropout time is the time required by the CBFP function to detect that the CB is open. The time for mechanically switching a
contact is not included.
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current
Times 1 % of the setting value or 10 ms
Dropout Ratio
Times
Tolerances
Dropout Ratio
Times
7UT82/7UT85/7UT86/7UT87
Frequency 50 Hz 60 Hz
Operate time Operate time
At 1,5 setting value threshold value 33 ms + OOT 32 ms + OOT
At 2.5 setting value threshold value 27 ms + OOT 26 ms + OOT
Dropout time approx. 80 ms 67 ms
Dropout ratio 0.7
94 The specified setting limit can be dynamically further limited, depending on the transformer adaptation factor, (for this refer to Chapter
6.39.4 Application and Setting Notes ).
[dwausken-170712-01.tif, 1, en_US]
Figure 12-20 Operate Curve of the Restricted Ground-Fault Protection Depending on the Phase Angle
Between I 0* and I 0** at |I 0*| = |I 0**| (180 = External Fault)
Times
Tolerance
95 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter
12.1.4 Relay Outputs
Reactance per unit length of the line per kilometer or per mile
Line length for the correct output of the fault distance as a percentage of the line length
The residual compensation factors in the setting format Kr and Kx or K0 and angle (K0)
Consideration of the load current for 1-pole ground Correction of the X value, for connection and discon-
faults nection
Fault Distance
Tolerances
Measuring tolerances during sinusoidal measurands 1.5 % from fault location at VK/Vrated 0.01 and one
and error duration of the following scenarios:
> 25 ms at 60 Hz or Metal fault
> 30 ms at 50 Hz Non-metallic fault for one-side infeed without
load
96 The output of the fault distance in km, miles and percent presupposes a homogenous line.
Dropout Conditions
Dropout differential 3 C or 6 F
Tolerances
Operating Range
10 Hz to 80 Hz Function active
Behavior outside the operating range Function inactive
Tolerances
97 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Working area
10 Hz to 80 Hz Function active
Behavior outside the operating range Function inactive
Tolerances
98 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Synchrocheck
Switching synchronous systems
Switching asynchronous systems
De-energized switching
Direct closing command
Setting Values
Supervision/Delay times:
Max. Duration of synchronization 0.00 s to 3 600.00 s or (ineffec- Increments of 0.01 s
process tive)
Supervision time de-energized 0.00 s to 60.00 s Increments of 0.01 s
switching
Closure delay 0.00 s to 60.00 s Increments of 0.01 s
Voltage threshold values:
Upper voltage limit Vmax 0.300 V to 340.000 V (phase-to- Increments of 0.001 V
phase)
Lower voltage limit Vmin 0.300 V to 340.000 V (phase-to- Increments of 0.001 V
phase)
V<, for off-circuit conditions 0.300 V to 170.000 V (phase-to- Increments of 0.001 V
V>, for voltage present phase) Increments of 0.001 V
0.300 V to 340.000 V (phase-to-
phase)
Differential values, changeover thresholds asynchronous/synchronous:
Voltage differences 0.000 V to 170.000 V Increments of 0.001 V
V2 > V1; V2 < V1
Frequency difference f2 > f1; 0.000 Hz to 2.000 Hz (synchro- Increments of 0.001 Hz
f2 < f1 nous)
0.000 Hz to 4.000 Hz (asynchro-
nous)
Angular difference 2 > 1; 0o to 90o Increments of 1o
2 < 1
f threshold ASYN <-> SYN 0.010 Hz to 0.200 Hz Increments of 0.001 Hz
Adjustments of the sides:
Angle adjustment 0.0o to 360.0o Increments of 0.1o
Voltage adjustment 0.500 to 2.000 Increments of 0.001
Circuit breaker
Closing time of the circuit breaker 0.01 s to 0.60 s Increments of 0.01 s
Dropout Ratio
Times
Operating Range
Voltage 20 V to 340 V
Frequency frated -4 Hz frated frated +4 Hz
Tolerances
General Information
I reference for % values 0.20 A to 100 000.00 A Increments of 0.01 A
V reference for % values 0.20 kV to 1 200.00 kV Increments of
0.01 kV
Volt. cont. 2W
Target voltage 1
Target voltage 2 Increments of
40.00 kV to 1 360.00 kV
Target voltage 3 0.01 kV
Target voltage 4
Volt. cont. 3W and GC
Target voltage 1 w1
Target voltage 2 w1
Target voltage 3 w1
Target voltage 4 w1 Increments of
40.00 kV to 1 360.00 kV
Target voltage 1 w2 0.01 kV
Target voltage 2 w2
Target voltage 3 w2
Target voltage 4 w2
Volt. cont. 2W, 3W, and GC
Bandwidth 0.2 % to 10.0 % Increments of 0.1 %
T1 delay 5 s to 600 s Increments of 1 s
T1 Inverse Min 5 s to 100 s Increments of 1 s
T2 delay 0 s to 100 s Increments of 1 s
Fast step down limit 0.0 % to 50.0 % Increments of 0.1 %
Fast step down T delay 0.0 s to 10.0 s Increments of 0.1 s
Fast step up limit -50.0 % to 0.0 % Increments of -0.1 %
Fast step up T delay 0.0 s to 10.0 s Increments of 0.1 s
Function monitoring 1 min to 120 min Increments of 1 min
Line compensation LDC-Z
Target voltage rising 0.0 % to 20.0 % Increments of 0.1 %
Max load current 0.0 % to 500.0 % Increments of 0.1 %
Line compensation LDC-X and R
R line 0.0 to 30.0 Increments of 0.1
X line -30.0 to 30.0 Increments of 0.1
Limiting values
Vmin threshold 40.00 kV to 1 360.00 kV Increments of
0.01 kV
Vmin time delay 0 s to 20 s Increments of 1 s
Vmax threshold 40.00 kV to 1 360.00 kV Increments of
0.01 kV
Vmax time delay 0 s to 20 s Increments of 1 s
Blockings
V< Threshold 40.00 kV to 1 360.00 kV Increments of
0.01 kV
V< Time delay 0 s to 20 s Increments of 1 s
Dropout Ratio
Dropout Ratio
Times
Dropout Ratio
Times
Dropout Ratio
Times
Dropout Ratio
Times
Dropout Ratio
Times
Dropout Ratio
Times
Blockings
Blocked functions All functions that process the measured values from this current meas-
uring point (for example, differential protection).
Dropout Ratio
Times
Times
Operating Range
99 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs
100 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fast relays, see chapter
12.1.4 Relay Outputs
101 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fast relays, see chapter
12.1.4 Relay Outputs
Tolerances
Rated currents 1 A, 5 A
Measuring range 0.1 to 25 A
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.1 % of the measured value in the above mentioned measuring range
Frequency range 40 Hz to 60 Hz at frated = 50 Hz
(expanded) 50 Hz to 70 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above mentioned measuring range
3I0 A secondary
Current range < 1.6 Irated
Rated currents 1 A, 5 A
Measuring range (0.1 to 1.6) Irated
Frequency range 49 Hz to 51 Hz at frated = 50 Hz
59 Hz to 61 Hz at frated = 60 Hz
Tolerance 0.1 % of the measured value in the above mentioned measuring range
Frequency range 40 Hz to 60 Hz at frated = 50 Hz
(expanded) 50 Hz to 70 Hz at frated = 60 Hz
Tolerance 0.3 % of the measured value in the above mentioned measuring range
Phase Angle
V
Frequency range 47.5 Hz to 52.5 Hz at frated = 50 Hz
57.5 Hz to 62.5 Hz at frated = 60 Hz
Tolerance V 0.2 at rated voltage
I
Frequency range 47.5 Hz to 52.5 Hz at frated = 50 Hz
57.5 Hz to 62.5 Hz at frated = 60 Hz
Tolerance I 0.2 at rated current
Power Values
Frequency
Frequency f Hz
Range frated - 0.20 Hz < frated + 0.20 Hz
Tolerance 5 mHz in the Vrated range
Range frated - 3.00 Hz < frated + 3.00 Hz
Tolerance 10 mHz in the Vrated range
Frequency range 25 Hz to 80 Hz; operational measured values
(expanded) 10 Hz to 80 Hz; functional measured values, system frequency
Tolerance 20 mHz in the range frated 10 % for rated values
Synchrophasor Standard
Tolerances
12.69 CFC
Typical response times and maximum number of ticks of the CFC task levels:
Task Level Time (in ms) Ticks for Non- Ticks for Modular Ticks for Modular
Modular Devices Devices with CP200 Devices with CP300
with CP100
Fast Event- <1 500 500 1000
Triggered
Event-Triggered <10 12 367 12757 14702
Interlocking <10 117 564 in total 121 537 in total 141 398 in total
Measurement 250
The times describe the response time of a typical CFC chart at the respective task level. The maximum
number of ticks applies to a typical load for the device based on the application template Directional time-
overcurrent protection, grounded electrical power system. The maximum number can be lower in case of
extensive protection applications.
The task level Measurement runs in cycles every 500 ms. All other task levels are event-triggered.
In order to estimate the tick consumption of a CFC chart, you can use the following formula:
Tchart = 5 nInp + 5 nOutp + TTLev + i Tint + j TBlock
where:
nInp Number of indications routed as input in the CFC chart
nOutp Number of indications routed as output in the CFC chart
TTLev 101 Ticks in Fast Event-Triggered Level
104 Ticks in Event-Triggered Level
54 Ticks in Measurement Level
74 Ticks in Interlocking Level
Tint Number of internal connections between 2 CFC blocks in one chart
TBlock Used ticks per CFC block (see Technical Data)
Element Ticks
ABS_D 2.3
ABS_R 1.5
ACOS_R 6.9
ADD_D4 3.4
ADD_R4 3.3
ADD_XMV 6.4
ALARM 1.8
AND_SPS 1.1
AND10 2.9
APC_DEF 1.2
APC_EXE 1.0
ASIN_R 1.3
ATAN_R 1.2
BLINK 1.3
BOOL_CNT 2.0
BOOL_INT 1.5
BSC_DEF 1.3
Element Ticks
BSC_EXE 1.1
BUILD_ACD 2.9
BUILD_ACT 2.2
BUILD_BSC 1.2
BUILD_DPS 1.4
BUILD_ENS 1.3
BUILD_Q 0.8
BUILD_SPS 0.6
BUILD_XMV 1.1
BUILDC_Q 3.0
CHART_STATE 5.9
CMP_DPS 1.5
CON_ACD 0.7
CON_ACT 0.5
CONNECT 0.4
COS_R 2.5
CTD 1.8
CTU 1.6
CTUD 2.3
DINT_REAL 3.0
DINT_UINT 3.0
DIV_D 2.9
DIV_R 1.6
DIV_XMV 2.2
DPC_DEF 0.4
DPC_EXE 0.4
DPC_INFO 1.1
DPC_OUT 1.3
DPS_SPS 1.0
DRAGI_R 1.7
EQ_D 1.0
EQ_R 1.9
EXP_R 1.5
EXPT_R 2.7
F_TRGM 0.3
F_TRIG 0.3
FF_D 0.9
FF_D_MEM 1.4
FF_RS 0.7
FF_RS_MEM 1.2
FF_SR 0.8
FF_SR_MEM 1.1
GE_D 0.9
GE_R 1.1
GT_D 0.9
GT_R 1.2
HOLD_D 1.1
Element Ticks
HOLD_R 1.0
INC_INFO 0.9
LE_D 1.1
LE_R 1.1
LIML_R 1.5
LIMU_R 1.5
LN_R 3.3
LOG_R 1.2
LOOP 1.5
LT_D 0.9
LT_R 0.9
MAX_D 0.9
MAX_R 1.4
MEMORY_D 0.9
MEMORY_R 1.1
MIN_D 0.7
MIN_R 1.3
MOD_D 1.5
MUL_D4 2.5
MUL_R4 2.7
MUL_XMV 2.8
MUX_D 1.2
MUX_R 0.9
NAND10 3.5
NE_D 0.9
NE_R 0.9
NEG 1.2
NEG_SPS 0.8
NLC_LZ 7.1
NLC_XMV 4.4
NLC_ZP 3.0
NOR10 3.2
OR_DYN 1.1
OR_SPS 1.3
OR10 2.6
R_TRGM 0.4
R_TRIG 0.4
REAL_DINT 3.0
REAL_SXMV 3.0
SIN_R 0.8
SPC_DEF 0.4
SPC_EXE 0.4
SPC_INFO 0.4
SPC_OUT 0.4
SPLIT_ACD 3.4
SPLIT_ACT 1.0
SPLIT_BSC 1.3
Element Ticks
SPLIT_DPS 1.0
SPLIT_Q 0.7
SPLIT_SPS 0.8
SPLIT_XMV 0.8
SQRT_R 0.6
SUB_D 1.3
SUB_R 1.6
SUB_XMV 2.4
SUBST_B 1.0
SUBST_BQ 1.5
SUBST_D 1.0
SUBST_R 1.0
SUBST_XQ 1.4
SXMV_REAL 3.0
TAN_R 1.1
TLONG 2.2
TOF 1.0
TON 1.1
TT 2.5
TSHORT 1.9
UINT_DINT 3.0