0% found this document useful (0 votes)
446 views44 pages

30HX PD

Uploaded by

abuMalak
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
446 views44 pages

30HX PD

Uploaded by

abuMalak
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

Product 30HXA076-186

30HXC076-271
Data Condenserless
and Fluid-Cooled Chillers
50/60 Hz
75 to 265 Tons (264 to 931 kW)

Fluid-cooled and condenserless chill-


ers designed from the ground up to
meet the needs of today and to-
morrow, including:
• Fits through a standard door with
no disassembly required
• Chlorine-free HFC-134a refrigerant
• Smooth compression using screw
compressors
• Mechanically cleanable coolers
and condensers (30HXC)

Features/Benefits
Quality design and con-
struction make the 30HXC
(Fluid Cooled) and the 30HXA
(Condenserless) units the
preferred choice
Easy installation
The 30HX chiller has a compact
design that fits through a standard
door opening and requires minimal
indoor space. The 30HX chiller is
delivered as a complete package for
easy installation. There are no extra
controls, clocks, starters, or other
items to install.
The 30HX unit also provides a
single point electrical power entrance
(using the accessory field-installed
control transformer) and quick, easy
piping using either welded or accessory
victaulic-type clamp-on couplings for
the cooler.
The 30HX 208/230-v and 460-v
units are designed in accordance with
UL (Underwriters’ Laboratory, U.S.A.)
standards and the 575-v units are
designed in accordance with CSA
(Canadian Standards Association)
standards to minimize electrical
inspections.
Copyright 1997 Carrier Corporation Form 30HX-2PD
A quick start-up is assured once costs. All 30HX units are also rated in From a service standpoint, the
installation is complete, since each accordance with ARI (Air Condition- 30HX units offer the following
30HX unit is manufactured at an ing and Refrigeration Institute, U.S.A.) features:
ISO 9002-listed manufacturing facility standards. The 60 Hz 30HXC units • Use of HFC-134a refrigerant, which
to guarantee quality. In addition, all are ARI certified. has no planned phase-out in its
units are tested under full load at the The 30HX controls are fully auto- future
factory to provide reliable start-up. matic. The leaving-fluid temperature is • Mechanically-cleanable cooler and
Easy to live with directly controlled, and the entering- condenser (30HXC units)
The 30HX units have a quiet, fluid temperature is continuously moni-
• Twin-screw compressors, which
low-vibration design featuring screw tored to detect load and flow changes.
require no routine service or
compressors. This combination provides the most
maintenance
precise temperature control available.
Efficiency levels of the 30HX units • Easily accessed suction and dis-
exceed minimums established by Dual, independent refrigerant cir-
charge pressure and temperature
ASHRAE (American Society of Heat- cuits provide reliable, dependable
information using either standard or
ing and Refrigeration Engineers) cooling, and the 30HX units use
accessory display module
and CSA for both full- and part-load medium-pressure HFC-134a refriger-
operation, thus saving on operat- ant to minimize stress on the com-
ing costs through lower electrical pressors and ensure a long life.

STANDARD DISPLAY MODULE ENVIRONMENTAL


LEADERSHIP

EXPN TEST
STAT
EDIT
1 2 3 SRVC
ALRM

SET SCHD 4 5 6 HIST ALGO

7 8 9 CLEAR

– 0 • ENTER

FITS THROUGH
STANDARD DOORWAY
TWIN-SCREW COMPRESSOR DESIGN

2
Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-15
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-25
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-38
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40,41

Model number nomenclature

LEGEND
FIOPS — Factory-Installed Options
*30HXC only.

3
Physical data, English
30HXA,HXC UNIT SIZE 076 086 096 106 116 126
UNIT WEIGHT (lb)*
Fluid Cooled 5700 5723 5855 6177 6415 6465
Condenserless 4717 4744 4835 5151 5162 5205
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 2 2 2
Nominal Capacity per Compressor (tons) 39/39 46/39 56/39 66/39 66/46 66/56
Economizer No No No No No No
No. Capacity Steps
Standard 6 6 6 6 6 6
Optional 7 7 7 7 7 7
Minimum Step Capacity (%)
Standard 20 20 20 20 20 20
Optional 10 10 10 10 10 10
REFRIGERANT HFC-134a
Charge† (lb), Circuit A/B 55/55 66/55 79/55 95/55 95/66 95/79
COOLER TYPE Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 17.0 17.0 19.0 22.6 21.4 21.4
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220
Maximum Fluid-Side Pressure (psig) 300** 300** 300** 300** 300** 300**
CONDENSER (Water Cooled) Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 16.8 16.8 18.3 18.3 23.9 23.9
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220
Maximum Water-Side Pressure (psig) 300** 300** 300** 300** 300** 300**
CONDENSERLESS
Maximum Refrigerant Pressure (psig) 320 320 320 320 320 320

30HXA,HXC UNIT SIZE 136 146 161 171 186


UNIT WEIGHT (lb)*
Fluid Cooled 6688 6718 7452 7660 7854
Condenserless 5308 5333 5752 5777 5946
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 2 2
Nominal Capacity per Compressor (tons) 80/56 66/80 56/80 66/80 80/80
Economizer No No Yes Yes Yes
No. Capacity Steps
Standard 6 6 6 6 6
Optional 7 7 7 7 7
Minimum Step Capacity (%)
Standard 20 20 20 20 20
Optional 10 10 10 10 10
REFRIGERANT HFC-134a
Charge† (lb), Circuit A/B 114/79 114/95 130/90 109/130 130/130
COOLER TYPE Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 24.0 24.0 28.5 28.5 33.4
Maximum Refrigerant Pressure (psig) 220 220 220 220 220
Maximum Fluid-Side Pressure (psig) 300** 300** 300** 300** 300**
CONDENSER (Water Cooled) Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 27.5 27.5 30.6 37.6 37.6
Maximum Refrigerant Pressure (psig) 220 220 220 220 220
Maximum Water-Side Pressure (psig) 300** 300** 300** 300** 300**
CONDENSERLESS
Maximum Refrigerant Pressure (psig) 320 320 320 320 320

*Weight includes weight of water or brine and refrigerant.


†For 30HXC units. The 30HXA units are shipped with a holding charge of HFC-134a only (nitrogen optional).
**In Canada, 250 psig per Canadian National Registry.

30HXC UNIT SIZE 206 246 261 271


UNIT WEIGHT (lb)* 10,457 10,914 10,944 11,006
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 3 3 3 3
Nominal Capacity per Compressor (tons) 66/39/80 80/56/80 80/66/80 80/80/80
Economizer Yes Yes Yes Yes
No. Capacity Steps
Standard 7 7 7 7
Optional 9 9 9 9
Minimum Step Capacity (%)
Standard 15 15 15 15
Optional 10 10 10 10
REFRIGERANT HFC-134a
Charge (lb), Circuit A/B 145/120 190/120 202/120 220/120
COOLER TYPE Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 43.0 47.3 47.3 47.3
Maximum Refrigerant Pressure (psig) 220 220 220 220
Maximum Fluid-Side Pressure (psig) 300† 300† 300† 300†
CONDENSER (Water Cooled) Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 47.0 55.1 55.1 55.1
Maximum Refrigerant Pressure (psig) 220 220 220 220
Maximum Water-Side Pressure (psig) 300† 300† 300† 300†

*Weight includes weight of water or brine and refrigerant.


†In Canada, 250 psig per Canadian National Registry.

4
Physical data, SI
30HXA,HXC UNIT SIZE 076 086 096 106 116 126
UNIT WEIGHT (Kg)*
Fluid Cooled 2586 2596 2656 2802 2910 2933
Condenserless 2140 2152 2193 2336 2341 2361
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 2 2 2
Nominal Capacity per Compressor (kW) 137/137 162/137 197/137 232/137 232/137 232/197
Economizer No No No No No No
No. Capacity Steps
Standard 6 6 6 6 6 6
Optional 7 7 7 7 7 7
Minimum Step Capacity (%)
Standard 20 20 20 20 20 20
Optional 10 10 10 10 10 10
REFRIGERANT HFC-134a
Charge† (Kg), Circuit A/B 24.9/24.9 29.9/24.9 35.8/24.9 43.1/24.9 43.1/29.9 43.1/35.8
COOLER TYPE Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 64.3 64.3 71.9 85.5 81.0 81.0
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517 1517
Maximum Fluid-Side Pressure (kPa) 2068** 2068** 2068** 2068** 2068** 2068**
CONDENSER (Water Cooled) Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 63.6 63.6 69.3 69.3 90.5 90.5
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517 1517
Maximum Water-Side Pressure (kPa) 2068** 2068** 2068** 2068** 2068** 2068**
CONDENSERLESS
Maximum Refrigerant Pressure (kPa) 2205 2205 2205 2205 2205 2205

30HXA,HXC UNIT SIZE 136 146 161 171 186


UNIT WEIGHT (Kg)*
Fluid Cooled 3034 3047 3380 3476 3563
Condenserless 2408 2419 2609 2620 2697
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 2 2
Nominal Capacity per Compressor (kW) 281/197 232/281 197/281 232/281 281/281
Economizer No No Yes Yes Yes
No. Capacity Steps
Standard 6 6 6 6 6
Optional 7 7 7 7 7
Minimum Step Capacity (%)
Standard 20 20 20 20 20
Optional 10 10 10 10 10
REFRIGERANT HFC-134a
Charge* (Kg), Circuit A/B 51.7/35.8 51.7/43.1 59.0/40.8 49.4/59.0 59.0/59.0
COOLER TYPE Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 90.8 90.8 107.9 107.9 126.4
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517
Maximum Fluid-Side Pressure (kPa) 2068** 2068** 2068** 2068** 2068**
CONDENSER (Water Cooled) Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 104.1 104.1 115.8 142.3 142.3
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517
Maximum Water-Side Pressure (kPa) 2068** 2068** 2068** 2068** 2068**
CONDENSERLESS
Maximum Refrigerant Pressure (kPa) 2205 2205 2205 2205 2205

*Weight includes weight of water or brine and refrigerant.


†For 30HXC units. The 30HXA units are shipped with a holding charge of HFC-134a only (nitrogen optional).
**In Canada, 1724 kPa per Canadian National Registry.

30HXC UNIT SIZE 206 246 261 271


UNIT WEIGHT (Kg)* 4743 4951 4964 4993
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 3 3 3 3
Nominal Capacity per Compressor (kW) 232/137/281 281/197/181 281/232/281 281/281/281
Economizer Yes Yes Yes Yes
No. Capacity Steps
Standard 7 7 7 7
Optional 9 9 9 9
Minimum Step Capacity (%)
Standard 15 15 15 15
Optional 10 10 10 10
REFRIGERANT HFC-134a
Charge (kg), Circuit A/B 65.8/54.4 86.2/54.4 91.6/54.4 99.8/54.4
COOLER TYPE Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 162.8 179.0 179.0 179.0
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517
Maximum Fluid-Side Pressure (kPa) 2068† 2068† 2068† 2068†
CONDENSER (Water Cooled) Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 177.9 208.6 208.6 208.6
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517
Maximum Water-Side Pressure (kPa) 2068† 2068† 2068† 2068†

*Weight includes weight of water or brine and refrigerant.


†In Canada, 1724 kPa per Canadian National Registry.

5
Dimensions
30HXC SIZES 076-146
LEGEND
K.O. — Knockout
THK — Thickness
TYP — Typical

NOTES:
1. Denotes center of gravity. See page 11 for weight
distribution.
2. Dimensions are in inches. Dimensions in ( ) are in
millimeters.
3. Recommended service clearance around unit (front,
back, and one side) is 36 in. (914).
DIMENSIONS — in. (mm)
UNIT
30HXC A B C D E F G H J K L M N P

076 102.12 45.87 45.87 9.87 9.36 43.50 15.60 85.15 4.00 95.00 65.22 1.90 47.00 30.80
(2594) (1165) (1165) (251) (236) (1105) (396) (2163) (102) (2413) (1657) (48) (1194) (782)
086 102.12 45.87 45.87 9.87 9.36 43.50 15.60 85.15 4.00 95.00 65.22 1.90 47.00 30.80
(2594) (1165) (1165) (251) (236) (1105) (396) (2163) (102) (2413) (1657) (48) (1194) (782)
102.12 54.12 37.63 9.87 9.36 43.50 15.60 85.15 4.00 95.00 65.22 1.90 47.00 30.80
096 (2594) (1375) (956) (251) (236) (1105) (396) (2163) (102) (2413) (1657) (48) (1194) (782)
102.12 54.12 37.63 10.47 10.28 45.50 15.60 85.15 5.00 95.00 67.22 1.90 47.00 30.80
106
(2594) (1375) (956) (266) (261) (1156) (396) (2163) (127) (2413) (1707) (48) (1194) (782)
132.56 72.12 50.63 9.87 9.36 43.50 31.11 100.66 4.00 126.00 65.22 1.70 62.20 29.40
116 (3367) (1832) (1286) (251) (236) (1105) (790) (2557) (102) (3200) (1657) (43) (1580) (747)
126 132.56 72.12 50.63 9.87 9.36 43.50 31.11 100.66 4.00 126.00 65.22 1.70 62.20 29.40
(3367) (1832) (1286) (251) (236) (1105) (790) (2557) (102) (3200) (1657) (43) (1580) (747)
132.56 72.12 50.63 9.87 9.36 43.50 31.11 100.66 4.00 126.00 65.22 1.70 62.20 29.40
136 (3367) (1832) (1286) (251) (236) (1105) (790) (2557) (102) (3200) (1657) (43) (1580) (747)
146 132.56 72.12 50.63 9.87 9.36 43.50 31.11 100.66 4.00 126.00 65.22 1.70 62.20 29.40
(3367) (1832) (1286) (251) (236) (1105) (790) (2557) (102) (3200) (1657) (43) (1580) (747)

6
30HXC SIZES 161-186
LEGEND
K.O. — Knockout
THK — Thickness
TYP — Typical

NOTES:
1. Denotes center of gravity. See page 11 for weight
distribution.
2. Dimensions are in inches. Dimensions in ( ) are in
millimeters.
3. Recommended service clearance around unit (front,
back, and one side) is 36 in. (914).

DIMENSIONS — in. (mm)


UNIT
30HXC A B C D E
161 72.12 (1832) 50.63 (1286) 2.00 (51) 63.50 (1588) 31.00 (787)
171 61.37 (1559) 61.37 (1559) 2.00 (51) 63.50 (1588) 31.00 (787)
186 61.37 (1559) 61.37 (1559) 2.00 (51) 63.50 (1588) 31.00 (787)

7
Dimensions (cont)
30HXC SIZES 206-271
LEGEND
K.O. — Knockout
THK — Thickness
TYP — Typical

NOTES:
1. Denotes center of gravity. See page 11 for weight
distribution.
2. Dimensions are in inches. Dimensions in ( ) are in
millimeters.
3. Recommended service clearance around unit (front,
back, and one side) is 36 in. (914).

DIMENSIONS — in. (mm)


UNIT
30HXC A B C D E
206 83.38 (2118) 55.38 (1407) 33.88 (860) 60.22 (1529) 2.01 (51)
246 83.38 (2118) 55.38 (1407) 34.38 (873) 60.22 (1529) 2.01 (51)
261 83.38 (2118) 55.38 (1407) 34.38 (873) 60.22 (1529) 2.01 (51)
271 83.38 (2118) 55.38 (1407) 34.38 (873) 60.22 (1529) 2.01 (51)

8
30HXA SIZES 076-146
LEGEND
K.O. — Knockout
SAE — Society of Automotive
Engineers, U.S.A.
THK — Thickness
TYP — Typical

NOTES:
1. Denotes center of gravity. See page 11 for weight
distribution.
2. Dimensions are in inches. Dimensions in ( ) are in
millimeters.
3. Recommended service clearance around unit (front,
back, and one side) is 36 in. (914).

DIMENSIONS — in. (mm)


UNIT
30HXA A B C D E F G H J K L M N P R S T U V

076 102.12 45.87 45.87 27.81 9.36 43.50 15.60 85.15 4.00 95.00 65.22 13.93 59.48 5.72 45.81 46.25 2.40 46.40 35.00
(2594) (1165) (1165) (706) (236) (1105) (396) (2163) (102) (2413) (1657) (354) (1511) (145 ) (1164) (1175) (61) (1179) (889)
102.12 45.87 45.87 27.81 9.36 43.50 15.60 85.15 4.00 95.00 65.22 13.93 59.48 5.72 45.81 46.25 2.40 46.40 35.00
086 (2594) (1165) (1165) (706) (236) (1105) (396) (2163) (102) (2413) (1657) (354) (1511) (145) (1164) (1175) (61) (1179) (889)
102.12 54.12 37.63 27.81 9.36 43.50 15.60 85.15 4.00 95.00 65.22 22.15 42.77 5.72 54.06 38.00 2.40 46.40 35.00
096 (2594) (1375) (956) (706) (236) (1105) (396) (2163) (102) (2413) (1657) (563) (1086) (145) (1373) (965) (61) (1179) (889)
102.12 54.12 37.63 28.41 10.28 45.50 15.60 85.15 5.00 95.00 67.22 22.15 42.77 5.87 54.06 38.00 2.40 46.40 35.00
106
(2594) (1375) (956) (721) (261) (1156) (396) (2163) (127) (2413) (1707) (563) (1086) (149) (1373) (965) (61) (1179) (889)
132.56 72.12 50.63 27.81 9.36 43.50 31.11 100.66 4.00 126.00 65.22 40.16 64.23 5.72 72.06 51.01 2.30 61.00 34.30
116
(3367) (1832) (1286) (706) (236) (1105) (790) (2557) (102) (3200) (1657) (1020) (1631) (145) (1830) (1296) (58) (1549) (871)
126 132.56 72.12 50.63 27.81 9.36 43.50 31.11 100.66 4.00 126.00 65.22 40.16 64.23 5.72 72.06 51.01 2.30 61.00 34.30
(3367) (1832) (1286) (706) (236) (1105) (790) (2557) (102) (3200) (1657) (1020) (1631) (145) (1830) (1296) (58) (1549) (871)
132.56 72.12 50.63 27.81 9.36 43.50 31.11 100.66 4.00 126.00 65.22 40.16 64.23 5.72 72.06 51.01 2.30 61.00 34.30
136 (3367) (1832) (1286) (706) (236) (1105) (790) (2557) (102) (3200) (1657) (1020) (1631) (145) (1830) (1296) (58) (1549) (871)
132.56 72.12 50.63 27.81 9.36 43.50 31.11 100.66 4.00 126.00 65.22 40.16 64.23 5.72 72.06 51.01 2.30 61.00 34.30
146 (3367) (1832) (1286) (706) (236) (1105) (790) (2557) (102) (3200) (1657) (1020) (1631) (145) (1830) (1296) (58) (1549) (871)

9
Dimensions (cont)
30HXA SIZES 161-186
LEGEND
K.O. — Knockout
SAE — Society of Automotive
Engineers, U.S.A.
THK — Thickness
TYP — Typical

NOTES:
1. Denotes center of gravity. See page 11 for weight
distribution.
2. Dimensions are in inches. Dimensions in ( ) are in
millimeters.
3. Recommended service clearance around unit (front,
back, and one side) is 36 in. (914).

DIMENSIONS — in. (mm)


UNIT
30HXA A B C D E F G H J
161 72.12 (1832) 50.63 (1386) 48.56 (1233) 46.62 (1184) 72.06 (1830) 51.00 (1295) 2.70 (69) 62.50 (1588) 35.20 (894)
171 61.37 (1559) 61.37 (1559) 43.25 (1099) 46.62 (1184) 61.31 (1572) 61.75 (1568) 2.70 (69) 62.50 (1588) 35.20 (894)
186 61.37 (1559) 61.37 (1559) 43.25 (1099) 46.62 (1184) 61.31 (1572) 61.75 (1568) 2.70 (69) 62.50 (1588) 35.20 (894)

10
WEIGHT DISTRIBUTION — 30HXC, 30HXA

WEIGHT DISTRIBUTION AT EACH MOUNTING PLATE,


30HXC UNITS — Lb (Kg)

UNIT MOUNTING PLATE NO.


30HXC 1 2 3 4 5 6
076 738 (335) 943 (428) 595 (270) 1110 (503) 1418 (643) 896 (406)
086 738 (335) 947 (430) 597 (271) 1112 (504) 1427 (647) 902 (409)
096 686 (311) 968 (439) 693 (314) 1027 (466) 1447 (656) 1034 (469)
106 730 (331) 1028 (466) 744 (337) 1073 (487) 1510 (685) 1092 (495)
116 728 (330) 1114 (505) 777 (352) 1053 (478) 1615 (733) 1127 (511)
126 738 (335) 1127 (511) 780 (354) 1061 (481) 1628 (738) 1131 (513)
136 758 (344) 1176 (533) 811 (368) 1083 (491) 1689 (766) 1171 (531)
146 763 (346) 1182 (536) 815 (370) 1085 (492) 1697 (770) 1172 (532)
161 817 (371) 1272 (577) 908 (412) 1219 (553) 1890 (857) 1346 (610)
171 936 (425) 1318 (598) 840 (381) 1379 (626) 1946 (883) 1241 (563)
186 962 (436) 1361 (617) 860 (390) 1410 (640) 1996 (905) 1265 (574)
206 948 (430) 2406 (1091) 1243 (564) 1201 (545) 3133 (1421) 1650 (748)
246 985 (447) 2515 (1141) 1306 (592) 1154 (523) 3276 (1486) 1733 (786)
261 985 (447) 2520 (1143) 1311 (595) 1154 (523) 3283 (1489) 1739 (789)
271 985 (447) 2529 (1147) 1318 (598) 1154 (523) 3294 (1494) 1749 (793)

WEIGHT DISTRIBUTION AT EACH MOUNTING PLATE,


30HXA UNITS — Lb (Kg)

UNIT MOUNTING PLATE NO.


30HXA 1 2 3 4 5 6
076 555 (252) 793 (360) 418 (190) 926 (420) 1326 (601) 699 (317)
086 555 (252) 798 (362) 418 (190) 928 (421) 1340 (608) 705 (320)
096 509 (231) 808 (367) 493 (224) 848 (385) 1350 (612) 827 (375)
106 555 (252) 869 (394) 541 (245) 896 (406) 1410 (640) 880 (399)
116 530 (240) 895 (406) 540 (245) 855 (388) 1456 (660) 887 (402)
126 540 (245) 905 (410) 541 (245) 864 (392) 1468 (666) 887 (402)
136 548 (249) 926 (420) 555 (252) 873 (396) 1498 (679) 908 (412)
146 551 (250) 930 (422) 555 (252) 883 (400) 1506 (683) 908 (412)
161 560 (254) 965 (438) 598 (271) 954 (433) 1650 (748) 1025 (465)
171 627 (284) 968 (439) 534 (242) 1072 (486) 1658 (752) 918 (416)
186 648 (294) 1004 (455) 552 (250) 1110 (504) 1703 (772) 939 (426)
NOTE: See pages 6-10 center of gravity details.

11
Options and accessories
FACTORY- FIELD- Field-installed accessories
ITEM INSTALLED INSTALLED Control power transformer — The transformer is sized
OPTION ACCESSORY
Wye-Delta Start X
to supply the needs of the control circuit, sourcing power
Brine X
from the main unit power connection.
Non-Fused Disconnect X Minimum load control — This accessory allows addi-
Expanded Display X tional capacity reduction for unit operation below the mini-
Control Power Transformer X mum step of unloading (down to 10% of the minimum unit
Minimum Load Control X X capacity). Minimum load control is also available as a factory-
Sound Reduction Enclosure X installed option.
Vibration Isolation X Sound reduction enclosure — This kit contains a sound
Victaulic Connection X enclosure that covers the entire unit to reduce sound levels.
Temperature Reset Sensor X
Vibration isolation — Neoprene isolators are field in-
Chilled Fluid Flow Switch X
stalled to reduce vibration transmission from the compres-
Flotronic™ System Manager X
sor through the floor and into the conditioned space.
Expanded display — This accessory kit contains an indoor-
mounted display panel for remote unit diagnostics. The panel
Factory-installed options displays 16 lines with 40 characters per line.
Wye-delta start — Generally, Wye-delta start is not re-
Victaulic connection — The kit contains a victaulic-type
quired when using multiple compressors since the starting
cooler connection to replace the standard weld-type
current is generally less than with one larger compressor
connection.
using Wye-delta start. Wye-delta start is standard on 208/
230 v, 60 Hz and 230 v and 346 v, 50 Hz units. It is avail- Temperature reset sensor — This accessory sensor pro-
able as a factory-installed option for all other unit voltages. vides temperature reset capability from either the occupied
space or outdoor-air temperature.
Brine — The brine option permits supply liquid tempera-
tures to be set below 40 F (4.4 C). Refrigeration circuit com- NOTE: Temperature reset capability using return tempera-
ponents, such as the expansion device, are modified at the ture is standard.
factory to correct for the lower refrigeration flow rates. Chilled fluid flow switch — This accessory is available
Non-fused disconnect — This disconnect will provide dis- for field installation and provides loss of flow protection for
connect capability for main unit power located at the unit. the 30HX chillers. Loss of flow protection is required for all
30HX chillers.
Minimum load control — This option allows additional
capacity reduction for unit operation below the minimum Flotronic system manager — This control can be used
step of unloading (down to 10% of the minimum unit ca- to regulate up to eight 30HXA or 30HXC chillers.
pacity). Minimum load control is also available as a field-
installed accessory.

12
Application data
Leveling unit table. High flow rate is limited by pressure drop that can be
To assure proper oil return, be sure that unit is level, tolerated. If another temperature rise is used, apply LCWT
particularly in its major lengthwise dimension. Deter- correction as given in the electronic catalog chiller
mine whether special treatment is required to assure level program.
unit before unit installation. Minimum cooler flow — Flow (maximum cooler tem-
perature rise) for standard units is shown in the Minimum
Cooler fluid temperature Flow Rates table. Minimum flow rate must be maintained
1. Maximum leaving chilled-fluid temperature (LCWT) is to prevent fouling. When gpm (L/s) required is lower (or
60 F (21 C). Unit can start and pull down with up to rise is higher), follow recommendations below:
95 F (35 C) entering-fluid temperature due to MOP (maxi-
1. Multiple smaller chillers can be applied in series, each
mum operating pressure) feature of the expansion valve.
providing a portion of the design temperature rise.
For sustained operation, it is recommended that enter-
ing fluid temperature not exceed 85 F (29 C). 2. Chilled fluid can be recirculated to raise flow rate. How-
ever, mixed temperature entering cooler must be main-
2. Minimum LCWT is 40 F (4 C) for standard units. Special-
tained at a minimum of at least 5° F (2.8° C) above the
order brine units are required for operation with leaving
leaving chilled fluid temperature.
fluid temperatures in the range of 39 to 15 F (4 to −9 C).
For ratings below 40 F (4 C) LCWT, contact your local 3. Special 1-pass cooler can be used. Contact your Carrier
Carrier representative. representative for further information.
3. Minimum entering chilled-fluid temperature (ECWT) is
45 F (7.2 C). Maximum ECWT is 70 F (21.1 C). MINIMUM FLOW RATES

Leaving-fluid temperature reset DEVICE UNIT SIZE FLOW RATE,


GPM (L/s)
The accessory reset sensor can be applied to the chiller to 076 105 ( 6.6)
provide reset of LCWT in constant fluid flow systems. Re- 086,096 125 ( 7.9)
set reduces compressor power usage at part load when de- 106-126 155 ( 9.8)
136 200 (12.6)
sign LCWT is not necessary. Humidity control should be 146 210 (13.2)
considered, since higher coil temperatures resulting from COOLER 161,171 240 (15.1)
reset will reduce latent heat capacity. Three reset applica- 186 270 (17.0)
206 324 (20.4)
tions are offered: 246 358 (22.6)
261 358 (22.6)
From return-fluid temperature — Increases LCWT set 271 358 (22.6)
point as return (or entering) fluid temperature decreases 076,086 105 ( 6.6)
(indicating load decrease). Option may be used in any 096,106 135 ( 8.5)
application where return fluid provides accurate load indi- 116,126 170 (10.7)
136,146 195 (12.3)
cation. Limitation of return-fluid reset is that the LCWT may 161 235 (14.8)
CONDENSER
only be reset to value of design return-fluid temperature. No 171,186 255 (16.1)
additional hardware is required. 206 273 (17.2)
246 333 (21.0)
From outdoor-air temperature — Increases LCWT as 261 333 (21.0)
271 333 (21.0)
outdoor ambient temperature decreases (indicating load de-
crease). This reset should be applied only where outdoor
ambient temperature is an accurate indication of load. A Maximum cooler flow (. 5 gpm/ton or , 5° F rise
field-supplied thermistor is required. [. 0.09 L/s • kW or , 2.7° C rise]) — Maximum flow
From occupied space temperature — Increases LCWT results in practical maximum pressure drop through cooler.
as space temperature decreases (indicating load decrease). Return fluid can bypass the cooler to keep pressure drop
This reset should be applied only where space temperature through cooler within acceptable limits. This permits a higher
is an accurate indication of load. A field-supplied thermistor DT with lower fluid flow through cooler and mixing after
is required. the cooler. Contact your Carrier representative if pressure
Condenser fluid temperature drop appears excessive.
1. Maximum leaving condenser fluid temperature is Variable cooler flow rates — These variable rates may
105 F (40.5 C) on all 30HXC units. be applied to standard 30HX series chillers. However, the
unit will attempt to maintain a constant leaving chilled-fluid
2. Minimum entering condenser fluid temperature without temperature. In such cases, minimum flow must be in ex-
condenser flow regulation is 70 F (21.1 C) at full load. cess of 3 gpm per ton (3.2 L per kW) and flow rate must
Cooler and fluid-cooled condenser change in steps of less than 10% per minute. Apply 6 gal
temperature rise per ton (6.5 L per kW) fluid loop volume minimum if flow
Ratings and performance data in this publication are for a rate changes more rapidly.
cooling temperature rise of 10° F (5.6° C). Units may be Minimum fluid-cooled condenser flow — This value
operated at a different temperature rise, provided flow lim- (maximum rise) is shown in Minimum Flow Rates table. Con-
its are not exceeded and corrections to capacity, etc., are densers may be piped in series. Ensure leaving-fluid tem-
made. For minimum flow rates, see the Minimum Flow Rates perature does not exceed 105 F (40.5 C).

13
Application data (cont)
Chilled fluid loop volume — The chilled fluid loop vol- 30HXA remote condenser requirements
ume in circulation must equal or exceed 2 gal per nominal 1. Ensure each refrigerant circuit has its own head pres-
ton of cooling (2 L per kW) for temperature stability and sure control.
accuracy in normal air conditioning applications. For ex-
ample, a 30HXC096 with a nominal capacity of 92.8 tons 2. Condenser must provide 15° F (8.3° C) subcooling, a
would require 185.6 gal (702 L) in circulation in the system maximum of 40° F (22.2° C) difference between sat-
loop. urated condensing temperature and outdoor ambient
temperature (to prevent overload at high ambient tem-
For process jobs where accuracy is vital, or for operation peratures), and a minimum of 20° F (11.1° C) difference
at ambient temperatures below 32 F (0° C) with low unit (to assure subcooling).
loading conditions, there should be from 6 to 10 gal per
ton (6.5 to 10.8 L per kW). To achieve this volume, it is 3. Minimum saturated discharge temperature (SDT) is
often necessary to install a tank in the loop. Tank should be 105 F (40.5 C) at design conditions. Maximum SDT is
baffled to ensure there is no stratification, and that water 135 F (57.2 C).
(or brine) entering tank is adequately mixed with liquid in 4. Do not manifold independent refrigerant circuits into a
the tank. See below. single condenser.
5. Condenser should not be located more than 50 ft
TANK INSTALLATION (15 m) below chiller to maintain subcooling.
6. Design discharge and liquid piping according to Carrier
System Design Manual. Piping must be sized for
HFC-134a. Also see 30HX Installation instructions.
Oversizing chillers
Oversizing chillers by more than 15% at design conditions
must be avoided as the system operating efficiency will be
adversely affected (resulting in greater and/or excessive elec-
trical demand and cycling of compressors). When future ex-
pansion of equipment is anticipated, install a single chiller
to meet present load requirements, and install a second chiller
to meet the additional load demand.
It is also recommended that the installation of 2 smaller
chillers be considered where operation at minimum load is
critical. The operation of 2 small chillers at higher loading
Fouling factor — The factor used to calculate tabulated is preferred to operating a single chiller at or near its mini-
ratings was 0.00025 ft2 • hr • F/Btu (.000044 m2 • K/W). mum recommended value.
As fouling factor is increased, unit capacity decreases and
compressor power increases. To determine selections at The minimum load control accessory should not be used
other fouling factors, use the chiller program in the elec- as a means to allow oversizing chillers. Minimum load
tronic catalog. control should be given consideration where substantial op-
Cooler and fluid-cooled condenser freeze protection erating time is anticipated below the minimum unloading
— If chiller refrigerant or fluid lines are in an area where step.
ambient conditions fall below 32 F (0° C), it is recom- Parallel chillers
mended that an antifreeze solution be added to protect Where chiller capacities greater than can be supplied by a
the unit and fluid piping to a temperature 15° F (8.3° C) single 30HX chiller are required, or where stand-by cap-
below the lowest anticipated temperature. For corrections ability is desired, chillers may be installed in parallel. Units
to performance, refer to the chiller program in the elec- may be of the same or different sizes. However, cooler and
tronic catalog. condenser flow rates must be balanced to ensure proper
Use only antifreeze solutions approved for heat exchanger flow to each chiller. The accessory Flotronic™ System Man-
duty. Use of automotive antifreezes is not recommended ager control should be used for proper leaving chilled fluid
because of the fouling that can occur once their relatively temperature control and to ensure proper staging sequence
short-lived inhibitors break down. of up to 8 chillers. Refer to the accessory Flotronic System
If not protected with an antifreeze solution, draining cooler Manager installation instructions for further details.
and outdoor piping is recommended if system will not be
used during freezing weather conditions.

14
Series chillers Duty cycling
Where a large temperature drop (greater than 25 F Duty cycling will cycle an electrical load at regular inter-
[13.9 C]) is desired and higher fluid pressure drop across vals, regardless of electrical demand. This reduces the elec-
the cooler can be tolerated, chillers may be installed in trical demand by ‘‘fooling’’ demand measuring devices. Duty
series. The leaving fluid temperature sensors need not be cycling of the entire compressor is NOT recommended since
relocated. However, the cooler minimum entering fluid tem- motor windings and bearings will be damaged by constant
perature limitations should be considered for the chillers cycling.
located downstream of other chillers. Condensers should be
piped in parallel to maximize capacity and efficiency. This
Wye-delta start
should also minimize condenser pressure drop and satu- Wye-delta start is standard on 30HX 208/230 V 60 Hz
rated condensing temperatures. However, if condensers are units and 230 v 50 Hz units and optional on all other 30HX
piped in series, ensure that the leaving water temperature units. This feature is not always required on 30HX units due
does not exceed 105 F (40.5 C). to the use of multiple compressors that allow small electri-
cal load increments, but is available if required. Maximum
Energy management instantaneous current flow (see ICF in Electrical Data tables
Demand limiting and load shedding are popular techniques on pages 27-29, 34 and 35) should be used in determining
used to reduce peak electric demands typically experienced need.
during hot summer days when air conditioning loads are
highest. When utility electricity demands exceed a certain
Vibration isolation
level, electrical loads are turned off to keep the peak de- External vibration isolators are available as field-installed
mands below a prescribed maximum limit. Compressor accessories.
unloading reduces electrical demand while allowing the chiller Strainers
to operate under part-load capacity and to maintain partial A strainer with a minimum screen size of 20 mesh should
chilled fluid cooling. be installed in both the cooler and condenser fluid lines, just
Electrical demand can be limited by unloading the chiller ahead of the cooler and condenser, and as close to the cooler
to a predetermined percentage of the load. One stage of and condenser as possible. For 30HXA units, this recom-
unloading can be initiated by a remote signal to significantly mendation applies only to the cooler.
reduce the chiller power consumption. This power reduc-
tion applies to the full load power at nominal conditions.
The demand limit control should not be cycled less than
10 minutes on and 5 minutes off.

15
Selection procedure (with example)
Carrier’s electronic catalog chiller selection program pro- SI (50 Hz)
vides quick, easy selection of Carrier chillers. The program I Determine unit size and operating conditions
considers specific temperature and flow requirements and required to meet given capacity at given
other factors, such as fouling and altitude correction. It can conditions.
also select an air-cooled condenser for the condenserless
30HXA unit to match the required conditions. To select a Given:
30HXA unit, use the electronic catalog or contact your Capacity . . . . . . . . . . . . . . . . . . . . . . . . . 617 kW
Carrier representative. To select a 30HXC chiller, use the Leaving Chilled Water Temp (LCWT) . . . . . . . . 7 C
electronic catalog or follow one of the procedures below. Cooler Water Temp Rise . . . . . . . . . . . . . . . 5.6° C
Condenser Entering Water Temp . . . . . . . . . . 30 C
ENGLISH (60 Hz) Condenser Water Temp Rise . . . . . . . . . . . . 5.6° C
Fouling Factor (Cooler and
I Determine 30HXC unit size and operating con-
Condenser) . . . . . . . . . . . . . . . . . . . . .000044
ditions required to meet given capacity at given
conditions. NOTE: For other than 5.6° C temperature rise, data
Given: corrections must be made using the chiller program in
Capacity . . . . . . . . . . . . . . . . . . . . . . . . 175 Tons the electronic catalog. On some units, a change of con-
Leaving Chilled Water Temp (LCWT) . . . . . . . 44 F trols is also necessary.
Cooler Water Temp Rise . . . . . . . . . . . . . . . 10° F II From Cooling Capacity table on page 22 and
Condenser Entering Water Temp . . . . . . . . . . 85 F pressure drop curves on pages 24 and 25, de-
Condenser Water Temp Rise . . . . . . . . . . . . 10° F termine operating data for selected unit.
Fouling Factor (Cooler and Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 30HXC186
Condenser) . . . . . . . . . . . . . . . . . . . . . .00025 Capacity . . . . . . . . . . . . . . . . . . . . . . . . 620.6 kW
NOTE: For other than 10° F temperature rise, data Compressor Motor Power Input . . . . . . . 135.0 kW
corrections must be made using the chiller program in Cooler Water Flow . . . . . . . . . . . . . . . . . 26.7 L/s
the electronic catalog. On some units, a change of con- Cooler Pressure Drop . . . . . . . . . . . . . . . 60.0 kPa
trols is also necessary. Condenser Water Flow . . . . . . . . . . . . . . 32.2 L/s
Condenser Pressure Drop . . . . . . . . . . . . 49.0 kPa
II From Cooling Capacities table on page 18 and
pressure drop curves on pages 24 and 25, de-
termine operating data for selected unit.
Unit . . . . . . . . . . . . . . . . . . . . . . . . . 30HXC186
Capacity . . . . . . . . . . . . . . . . . . . . . . . 175.8 tons
Compressor Motor Power Input . . . . . . . 133.4 kW
Cooler Water Flow . . . . . . . . . . . . . . . . 421.4 gpm
Cooler Pressure Drop . . . . . . . . . . 13.0 ft of water
Condenser Water Flow . . . . . . . . . . . . . 508.0 gpm
Condenser Pressure Drop . . . . . . . 16.4 ft of water

16
Performance data
Ratings 2. Combining 30HXA units with remote condensers which
1. All performance data is based on: have greater than (less than) the 10° F (5.6° C) subcool-
ing in the ratings, increases (decreases) system capacity.
a. Cooler water temperature rise of 10° F (5.6° C). To adjust capacity, multiply capacity ratings by 0.96; then
b. Cooler fouling factor of .00025 ft2 • hr • F/Btu adjust this result upward by 0.4% for each degree F (0.7%
(.000044 m2 • K/W) (same for condenser on for each degree C) of available subcooling.
30HXC).
c. 10° F (5.6° C) subcooling.
d. Refrigerant 134a.

ARI* RATINGS (60 Hz only)

CAPACITY COOLER FLOW COOLER CONDENSER CONDENSER


UNIT INPUT PRESSURE DROP FLOW PRESSURE DROP
30HXC POWER EER IPLV†
Tons kW (kW) Gpm L/s Ft of kPa Gpm L/s Ft of kPa
Water Water
076 74.5 262.0 54.9 179.0 11.3 12.3 36.8 224.0 14.1 7.3 21.8 16.3 19.6
086 82.0 288.4 61.5 197.0 12.4 14.6 43.6 246.0 15.5 8.8 26.3 16.0 19.0
096 92.8 326.4 68.8 223.0 14.1 14.4 43.0 278.0 17.6 9.0 26.9 16.2 19.2
106 103.1 362.6 77.3 247.0 15.6 13.0 38.9 309.0 19.5 10.9 32.6 16.0 18.5
116 112.1 394.3 81.9 269.0 17.0 11.3 33.8 336.0 21.2 13.8 41.2 16.4 19.3
126 121.3 426.6 89.4 291.0 18.4 13.1 39.2 364.0 23.0 16.0 47.8 16.3 19.3
136 134.6 473.4 100.1 323.0 20.4 12.4 37.1 404.0 25.5 15.2 45.4 16.1 18.7
146 143.8 505.7 108.4 345.0 21.8 14.0 41.8 431.0 27.2 17.1 51.1 15.9 18.5
161 155.1 545.5 116.5 372.0 23.5 11.7 35.0 465.0 29.4 17.8 53.2 16.0 17.7
171 164.4 578.2 122.9 395.0 24.9 13.0 38.9 493.0 31.1 14.6 43.6 16.1 18.6
186 176.0 619.0 132.7 422.0 26.6 11.9 35.6 528.0 33.3 16.6 49.6 15.9 17.9
206 211.5 743.8 152.6 508.0 32.0 12.7 38.0 635.0 40.0 17.5 52.3 16.6 19.4
246 246.7 867.6 179.2 592.0 37.4 13.9 41.5 740.0 46.7 18.3 54.7 16.5 18.7
261 255.1 897.2 187.1 612.0 38.6 14.7 43.9 765.0 48.3 19.5 58.3 16.4 18.8
271 265.1 932.4 197.2 636.0 40.1 15.8 47.2 795.0 50.2 21.1 63.1 16.1 18.8

LEGEND 3. IPLV is a single number part-load efficiency value calculated from the
EER — Energy Efficiency Ratio (Capacity [Btuh] ÷ Input Power [W]) system full-load efficiency values and corrected for a typical building
IPLV — Integrated Part-Load Value air-conditioning application.
4. All data in this table is rated (60 Hz only) in accordance with ARI
*Air Conditioning and Refrigeration Institute (U.S.A.). Standard 590-92 as represented in the Ecologic™ Chiller Selection
†IPLV shown is for unloading sequence A. Program (E-Cat) version 1.10.
NOTES:
1. Rated (60 Hz only) in accordance with ARI Standard 590-92 at stand-
ard rating conditions.
2. Standard rating conditions are as follows:
Cooler Conditions: Rated in accordance with
Leaving water temperature: 44 F (6.7 C) ARI Standard 590-92.
Entering water temperature: 54 F (12.2 C)
Condenser Conditions:
Entering water temperature: 85 F (29.4 C)
Flow: 3 gpm per ton (0.054 L/s per kW)
Fouling Factor (Cooler and Condenser): 60 Hz Only
0.00025 hr x sq ft x F per Btuh (0.000044 m2 x k per W)

17
Performance data (cont)
COOLING CAPACITIES
60 Hz, ENGLISH

CONDENSER ENTERING WATER TEMPERATURE (F)


75 80 85 90
LCWT 30HXC
UNIT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
(F) SIZE Input Flow Fow Input Flow Flow Cap Input Flow Flow Input Flow Flow
Cap kW Rate Rate Cap kW Rate Rate kW Rate Rate Cap kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 73.8 48.4 176.5 208.0 70.8 51.1 169.4 202.7 67.8 54.0 162.3 197.5 65.0 57.0 155.7 192.9
086 81.2 54.1 194.4 229.6 77.9 57.3 186.5 223.8 74.8 60.4 179.0 218.3 71.9 63.8 172.2 213.8
096 91.7 60.5 219.6 259.0 88.1 64.1 210.9 252.6 84.5 67.7 202.3 246.4 81.3 71.5 194.5 241.2
106 102.0 67.8 244.1 288.2 97.9 72.0 234.4 281.3 93.7 76.2 224.3 273.9 90.2 80.7 215.8 268.5
116 110.7 71.8 265.0 311.7 106.6 76.3 255.2 304.9 102.0 80.8 244.2 296.9 97.8 85.5 234.2 290.1
126 119.7 78.5 286.6 337.6 115.1 83.3 275.5 329.7 110.4 88.2 264.3 321.9 106.1 93.4 253.9 315.0
136 132.8 88.4 318.0 375.4 127.7 93.5 305.6 366.5 122.7 98.7 293.6 358.0 118.3 104.1 283.1 351.1
40 146 142.0 95.6 339.9 402.0 136.4 101.3 326.6 392.5 130.8 106.9 313.2 382.9 126.4 113.2 302.6 376.4
161 148.7 99.1 356.1 420.5 146.3 108.2 350.2 420.6 143.6 117.5 343.8 420.3 142.1 128.1 340.2 423.7
171 157.4 105.5 376.8 445.4 155.1 114.5 371.2 445.7 152.6 124.1 365.3 446.1 151.1 134.9 361.8 449.8
186 168.7 113.8 403.7 477.7 166.3 123.8 398.1 478.6 163.5 134.1 391.4 478.7 162.0 145.6 387.9 482.9
206 202.4 131.3 484.5 569.9 199.4 142.1 477.3 569.9 196.0 154.5 469.1 569.9 193.5 168.1 463.2 573.0
246 236.0 153.4 565.1 664.9 232.9 166.9 557.5 666.2 228.1 181.2 545.9 664.2 225.2 197.2 539.0 667.8
261 244.2 160.5 584.7 689.1 240.7 174.4 576.2 689.7 236.9 189.3 567.2 690.6 234.0 205.3 560.1 694.2
271 254.0 169.1 608.0 717.9 250.2 183.9 599.0 718.7 246.5 199.4 590.0 720.0 243.7 216.3 583.3 724.5
076 77.1 49.1 184.7 216.5 74.1 51.7 177.3 210.8 71.0 54.6 170.0 205.5 67.9 57.5 162.7 200.2
086 84.9 54.8 203.3 238.8 81.6 57.9 195.4 233.0 78.2 61.1 187.4 227.1 75.0 64.3 179.6 221.5
096 95.9 61.4 229.6 269.4 92.2 64.6 221.0 262.9 88.4 68.4 211.8 256.3 84.8 72.1 203.1 250.0
106 106.6 68.6 255.3 299.7 102.4 72.7 245.4 292.6 98.2 76.9 235.1 285.2 93.9 81.2 224.9 277.8
116 115.7 72.6 277.1 324.2 111.3 76.9 266.7 316.7 106.9 81.6 256.0 309.1 102.2 86.2 244.9 301.1
126 125.1 79.2 299.7 351.1 120.4 83.9 288.5 343.0 115.6 89.0 277.0 334.9 110.9 94.2 265.6 327.1
136 138.8 89.7 332.5 390.6 133.7 94.3 320.2 381.4 128.3 99.6 307.4 372.1 123.2 104.8 295.3 363.6
42 146 148.4 96.7 355.4 418.0 142.8 102.1 342.2 408.5 137.0 107.9 328.1 398.3 131.7 113.9 315.5 389.7
161 154.2 99.2 369.3 433.6 151.9 107.9 363.8 433.9 149.1 117.4 357.3 433.6 146.7 127.4 351.3 434.3
171 163.0 105.4 390.6 458.9 161.2 114.0 386.2 460.2 158.2 123.9 379.1 459.7 156.3 134.6 374.3 462.0
186 174.6 114.0 418.2 492.0 172.3 123.3 412.7 492.8 169.6 133.8 406.2 493.2 167.1 144.7 400.4 494.6
206 209.7 131.2 502.3 587.4 206.9 142.0 495.7 588.0 203.6 154.2 487.7 588.2 200.3 167.6 480.0 589.3
246 244.5 153.7 585.7 685.4 241.5 166.1 578.5 686.4 237.4 181.1 568.7 686.6 233.2 196.5 558.6 686.7
261 252.9 161.0 605.8 710.2 249.8 173.6 598.4 711.2 245.6 188.8 588.5 711.3 241.8 204.5 579.3 712.6
271 262.9 169.7 629.8 739.7 259.6 183.1 621.9 740.8 255.4 198.8 611.8 741.2 251.5 215.1 602.5 742.7
076 80.5 49.8 193.0 225.1 77.5 52.1 185.8 219.6 74.3 55.1 178.1 213.9 71.1 58.2 170.4 208.3
086 88.6 55.7 212.4 248.4 85.3 58.3 204.5 242.3 81.8 61.7 196.1 236.2 78.4 65.0 187.9 230.2
096 100.1 62.3 239.9 280.1 96.5 65.2 231.2 273.5 92.5 69.0 221.8 266.6 88.6 72.9 212.5 259.9
106 111.2 69.4 266.6 311.4 107.1 73.1 256.8 304.2 102.8 77.6 246.4 296.8 98.2 82.0 235.5 288.8
116 120.8 73.5 289.5 337.0 116.4 77.4 279.1 329.3 111.8 82.3 267.9 321.4 107.1 87.0 256.7 313.3
126 130.6 80.1 313.0 364.8 125.9 84.6 301.8 356.6 120.9 89.8 289.9 348.2 115.9 95.0 277.9 339.7
136 144.9 90.8 347.2 405.9 139.8 94.9 335.2 396.7 134.2 100.4 321.8 387.0 128.9 105.9 308.9 377.9
44 146 154.8 97.6 371.2 434.2 149.3 102.8 358.0 424.6 143.4 108.8 343.8 414.4 137.4 114.8 329.4 404.0
161 159.6 99.5 382.5 446.8 157.6 107.3 377.7 447.3 154.9 117.2 371.3 447.4 152.0 127.3 364.3 447.1
171 168.8 105.6 404.5 472.8 166.8 113.9 399.8 473.6 164.2 123.6 393.7 473.9 161.5 134.0 387.2 474.4
186 180.5 114.3 432.7 506.6 178.5 122.8 427.8 507.3 175.8 133.4 421.4 508.0 173.0 144.5 414.7 508.7
206 216.2 131.1 518.4 603.2 214.5 141.9 514.2 606.2 211.2 153.7 506.3 606.2 207.5 167.1 497.3 606.1
246 253.1 153.7 606.6 706.0 250.1 165.8 599.5 707.0 246.3 180.4 590.5 707.8 242.1 196.3 580.4 708.2
261 261.7 161.2 627.2 731.4 258.7 173.3 620.1 732.4 254.8 188.3 610.9 733.2 250.8 204.4 601.1 734.2
271 271.9 169.8 651.9 761.6 268.9 182.4 644.6 762.7 264.8 198.3 634.8 763.6 260.7 215.0 625.0 764.9
LEGEND
Cap — Capacity, Tons of Refrigeration
Cond — Condenser
kW — Compressor Motor Input Power at
Rated Voltage
LCWT — Leaving Chilled-Water Temperature (F)

18
COOLING CAPACITIES (cont)
60 Hz, ENGLISH (cont)

CONDENSER ENTERING WATER TEMPERATURE (F)


75 80 85 90
LCWT 30HXC
UNIT Cooler Cond Cooler Cond Cooler Cond Cooler Cond
(F) SIZE Input Flow Fow Input Flow Flow Cap Input Flow Flow Input Flow Flow
Cap kW Rate Rate Cap kW Rate Rate kW Rate Rate Cap kW Rate Rate
(Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm) (Gpm)
076 83.9 50.4 201.2 233.6 81.0 52.9 194.2 228.4 77.7 55.6 186.5 222.5 74.4 58.7 178.4 216.6
086 92.4 56.4 221.7 258.1 89.1 59.0 213.8 251.9 85.5 62.3 205.2 245.6 81.9 65.8 196.5 239.3
096 104.4 63.1 250.4 291.0 100.7 66.1 241.5 284.3 96.8 69.6 232.1 277.3 92.7 73.6 222.3 270.1
106 116.0 70.2 278.2 323.4 111.9 73.9 268.3 316.1 107.5 78.3 257.7 308.5 102.8 82.8 246.7 300.5
116 125.8 74.1 301.7 349.5 121.6 78.2 291.6 342.2 116.9 82.8 280.4 334.1 111.8 87.6 268.4 325.4
126 135.9 80.8 325.9 378.0 131.5 85.3 315.4 370.5 126.4 90.3 303.3 361.9 121.3 95.9 290.9 353.2
136 151.1 91.8 362.4 421.6 145.9 96.2 350.1 412.3 140.4 101.2 336.8 402.5 134.7 106.9 323.1 392.5
46 146 161.4 98.7 387.1 450.7 155.9 103.8 374.0 441.1 150.0 109.6 359.8 430.9 143.7 115.8 344.7 420.0
161 165.1 99.5 396.0 460.2 163.1 107.4 391.3 460.7 160.7 116.8 385.4 461.1 157.7 127.2 378.3 460.9
171 173.9 105.5 417.2 485.2 172.6 113.8 413.9 487.5 170.3 123.2 408.4 488.2 167.4 133.9 401.4 488.5
186 186.6 114.4 447.5 521.2 184.6 122.9 442.8 522.2 182.2 132.9 437.1 523.2 179.1 144.3 429.6 523.4
206 222.6 130.6 533.9 618.1 222.0 141.8 532.4 624.2 219.0 153.4 525.3 624.9 215.2 166.8 516.1 624.7
246 260.5 153.0 624.8 723.5 258.8 166.1 620.7 728.2 255.3 179.5 612.3 728.8 250.9 195.7 601.8 729.1
261 269.6 160.9 646.8 750.5 267.6 173.8 641.8 754.3 264.0 187.5 633.2 754.8 259.5 203.9 622.5 755.1
271 280.8 169.7 673.5 782.9 278.1 183.0 667.2 785.5 274.3 197.5 657.8 785.9 269.8 214.6 647.3 786.7
076 86.9 50.8 208.6 241.2 84.5 53.6 202.8 237.4 81.3 56.1 195.1 231.4 77.8 59.3 186.7 225.2
086 96.0 57.0 230.5 267.1 93.0 59.9 223.2 261.9 89.4 62.7 214.7 255.3 85.6 66.4 205.5 248.6
096 108.1 63.6 259.5 300.4 105.1 67.1 252.1 295.4 101.2 70.1 242.8 288.2 96.9 74.3 232.5 280.8
106 120.5 70.8 289.3 334.8 116.7 74.8 280.1 328.3 112.3 78.8 269.5 320.5 107.6 83.7 258.2 312.5
116 130.4 74.4 312.9 360.8 126.8 79.1 304.4 355.5 122.2 83.3 293.2 347.2 117.2 88.5 281.2 338.6
126 141.0 81.2 338.4 390.6 137.1 86.3 329.1 384.8 132.1 91.0 317.0 376.0 126.7 96.6 304.2 366.9
136 156.5 92.5 375.6 435.1 152.3 97.5 365.4 428.3 146.8 101.8 352.3 418.3 140.8 107.9 338.0 408.0
48 146 167.5 99.3 401.9 465.7 162.6 104.9 390.3 458.0 156.7 110.4 376.1 447.6 150.4 116.9 360.9 436.7
161 169.8 99.0 407.6 471.3 168.8 107.7 405.0 474.5 166.5 116.2 399.5 474.8 163.7 126.9 392.7 475.1
171 179.0 105.2 429.6 497.2 178.5 114.0 428.3 501.9 176.1 123.1 422.7 502.4 173.4 133.6 416.1 502.8
186 191.6 113.9 459.9 533.1 190.8 123.2 458.0 537.4 188.5 132.3 452.3 537.9 185.5 143.9 445.1 538.5
206 228.9 129.9 549.3 632.9 228.9 141.8 549.4 641.0 226.6 153.4 543.8 643.3 223.0 166.2 535.3 643.3
246 267.0 151.5 640.8 738.3 267.6 166.3 642.2 749.6 264.4 179.1 634.5 750.6 260.1 195.1 624.3 751.1
261 276.3 159.6 663.1 765.8 276.6 174.1 663.8 776.2 273.4 186.8 656.1 777.1 269.1 203.4 645.7 777.8
271 287.6 168.4 690.3 798.6 287.4 183.3 689.8 808.0 284.1 196.4 681.9 809.0 279.5 213.9 670.9 809.8
076 89.9 51.0 215.9 248.6 88.0 54.3 211.4 246.4 84.8 56.9 203.7 240.5 81.4 59.8 195.4 234.2
086 99.3 57.3 238.5 275.3 96.9 60.8 232.8 271.9 93.4 63.5 224.3 265.3 89.5 67.0 215.0 258.4
096 111.8 63.9 268.5 309.5 109.5 67.9 263.0 306.7 105.5 71.2 253.4 299.4 101.3 74.9 243.2 291.8
106 124.6 70.9 299.3 344.8 121.6 75.6 292.0 340.7 117.2 79.5 281.5 332.8 112.5 84.3 270.0 324.6
116 134.8 74.5 323.7 371.6 132.1 79.9 317.2 368.7 127.5 84.2 306.2 360.6 122.5 89.0 294.1 351.8
126 145.9 81.4 350.3 402.5 142.7 87.1 342.6 398.7 137.9 91.8 331.0 390.4 132.4 97.2 318.0 381.1
136 161.8 92.9 388.5 448.1 158.7 98.7 381.0 444.5 153.2 103.3 367.8 434.5 147.2 108.7 353.5 424.0
50 146 173.5 99.8 416.5 480.5 169.5 106.1 406.9 475.2 163.5 111.5 392.7 464.7 157.2 117.8 377.4 453.8
161 174.1 98.0 418.0 481.0 174.5 107.7 418.9 488.3 172.3 116.3 413.7 488.9 169.5 126.6 407.1 489.1
171 183.6 104.5 440.8 507.8 183.8 114.1 441.4 514.9 182.2 122.9 437.6 517.0 179.6 133.2 431.1 517.5
186 196.3 112.9 471.3 543.7 197.0 123.4 473.1 552.6 194.9 132.5 467.9 553.5 192.0 143.6 461.0 554.1
206 234.9 129.0 564.1 646.9 235.4 141.4 565.2 656.3 234.5 153.3 563.1 662.3 231.1 165.9 554.8 662.5
246 273.7 149.7 657.2 753.3 275.6 165.6 661.7 768.5 273.4 179.6 656.5 772.6 269.6 194.2 647.2 773.3
261 283.2 158.1 679.9 781.4 285.3 173.9 685.1 797.1 282.5 187.7 678.4 799.8 278.7 202.7 669.2 800.7
271 294.6 166.7 707.4 814.3 296.8 183.1 712.6 830.5 293.5 197.3 704.7 832.2 289.5 213.2 695.0 833.3

19
Performance data (cont)
COOLING CAPACITIES (cont)
60 Hz, SI

CONDENSER ENTERING WATER TEMPERATURE (F)


30HXC 25 30 35
LCWT UNIT Cooler Cond Cooler Cond Cooler Cond
(C) SIZE Input Flow Flow Input Flow Flow Input Flow Flow
Cap kW Rate Rate Cap kW Rate Rate Cap kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 250.6 49.2 10.8 12.8 232.0 54.3 10.0 12.2 217.3 60.1 9.3 11.8
086 275.9 55.2 11.8 14.1 255.9 60.7 11.0 13.5 240.7 67.2 10.3 13.1
096 311.9 61.7 13.4 15.9 289.4 68.1 12.4 15.2 272.0 75.4 11.7 14.8
106 346.6 69.3 14.9 17.7 320.5 76.6 13.8 16.9 301.9 85.5 13.0 16.5
116 376.3 73.4 16.2 19.2 349.0 81.4 15.0 18.3 327.9 90.6 14.1 17.8
126 407.1 80.1 17.5 20.8 378.4 89.0 16.2 19.9 355.7 99.0 15.3 19.4
136 451.6 90.1 19.4 23.1 420.3 99.3 18.0 22.1 396.8 109.8 17.0 21.6
4 146 482.8 97.6 20.7 24.7 449.2 107.8 19.3 23.7 424.3 119.7 18.2 23.2
161 512.0 102.9 22.0 26.2 496.1 119.5 21.3 26.2 491.1 140.1 21.1 26.9
171 542.4 109.0 23.3 27.8 528.4 126.4 22.7 27.9 522.8 147.1 22.4 28.5
186 580.9 118.0 24.9 29.8 565.4 136.3 24.3 29.9 560.5 158.6 24.1 30.6
206 697.5 135.5 29.9 35.5 677.6 157.3 29.1 35.6 667.3 183.3 28.6 36.2
246 813.9 158.6 34.9 41.5 789.2 184.7 33.9 41.5 778.2 215.8 33.4 42.3
261 842.1 165.9 36.2 43.0 818.4 192.4 35.1 43.1 809.2 224.2 34.7 44.0
271 875.5 175.1 37.6 44.8 851.4 202.7 36.6 44.9 843.0 236.0 36.2 45.9
076 261.1 49.7 11.2 13.3 241.8 54.9 10.4 12.6 225.4 60.6 9.7 12.2
086 287.5 55.6 12.4 14.6 266.7 61.4 11.5 14.0 249.5 67.8 10.7 13.5
096 324.9 62.1 14.0 16.5 301.5 68.8 13.0 15.8 282.1 76.0 12.1 15.3
106 361.0 69.8 15.5 18.4 334.3 77.4 14.4 17.5 312.9 86.0 13.4 17.0
116 392.1 73.8 16.8 19.9 364.0 82.1 15.6 19.0 339.9 91.2 14.6 18.4
126 424.1 80.6 18.2 21.5 394.0 89.6 16.9 20.6 368.7 99.6 15.8 19.9
136 470.6 90.7 20.2 23.9 437.7 100.2 18.8 22.9 411.3 110.6 17.7 22.2
5 146 503.0 98.1 21.6 25.6 466.9 108.5 20.1 24.5 439.6 120.4 18.9 23.8
161 529.6 102.5 22.8 26.9 512.9 119.4 22.0 26.9 505.0 139.7 21.7 27.4
171 560.6 108.8 24.1 28.5 544.8 126.0 23.4 28.6 537.4 146.8 23.1 29.1
186 600.6 117.5 25.8 30.6 583.6 136.0 25.1 30.7 576.0 158.2 24.7 31.3
206 720.8 135.5 31.0 36.5 699.8 156.9 30.1 36.5 686.3 182.8 29.5 37.0
246 840.7 158.3 36.1 42.6 816.7 184.4 35.1 42.7 800.0 214.9 34.4 43.2
261 870.0 165.4 37.4 44.2 846.0 192.1 36.3 44.2 831.6 223.5 35.7 44.9
271 904.5 174.3 38.9 46.0 879.8 202.4 37.8 46.1 866.2 235.2 37.2 46.9
076 271.8 50.3 11.7 13.7 252.0 55.4 10.8 13.1 233.7 61.0 10.0 12.6
086 299.2 56.2 12.9 15.2 277.7 62.0 11.9 14.5 258.6 68.3 11.1 13.9
096 338.0 62.9 14.5 17.1 313.9 69.4 13.5 16.3 292.4 76.6 12.6 15.7
106 375.7 70.3 16.2 19.0 348.5 78.1 15.0 18.2 324.2 88.0 13.9 17.6
116 408.0 74.5 17.5 20.6 379.5 82.8 16.3 19.7 352.2 92.4 15.1 18.9
126 441.2 81.3 19.0 22.3 410.6 90.4 17.7 21.4 382.0 100.9 16.4 20.6
136 489.6 91.7 21.0 24.8 455.7 101.0 19.6 23.7 426.2 111.3 18.3 22.9
6 146 523.3 99.2 22.5 26.5 486.5 109.4 20.9 25.4 455.4 121.1 19.6 24.6
161 547.1 102.3 23.5 27.7 530.5 119.3 22.8 27.7 519.0 139.1 22.3 28.0
171 580.5 107.9 24.9 29.4 562.9 125.8 24.2 29.4 552.2 146.2 23.7 29.8
186 619.6 117.4 26.6 31.4 603.2 135.8 25.9 31.5 591.7 157.5 25.4 31.9
206 744.1 135.4 32.0 37.5 724.2 156.7 31.1 37.6 705.5 182.0 30.3 37.8
246 867.8 158.5 37.3 43.8 844.4 183.9 36.3 43.9 822.6 214.5 35.4 44.2
261 897.6 165.9 38.6 45.4 873.7 191.7 37.6 45.4 854.8 222.5 36.7 45.9
271 933.1 174.7 40.1 47.3 908.3 201.8 39.0 47.3 890.1 234.1 38.3 47.9
076 282.6 51.0 12.2 14.2 262.5 55.9 11.3 13.6 242.4 61.4 10.4 13.0
086 311.1 56.9 13.4 15.7 289.1 62.6 12.4 15.0 268.0 68.7 11.5 14.4
096 351.4 63.7 15.1 17.7 327.0 70.0 14.1 16.9 303.0 77.0 13.0 16.2
106 390.4 71.1 16.8 19.7 363.2 78.7 15.6 18.8 335.8 89.6 14.4 18.1
116 424.1 75.2 18.2 21.3 395.1 83.4 17.0 20.4 365.2 92.1 15.7 19.5
126 458.6 82.1 19.7 23.1 427.4 91.0 18.4 22.1 396.3 100.8 17.0 21.2
136 508.9 92.9 21.9 25.7 474.6 101.8 20.4 24.6 441.6 111.9 19.0 23.6
7 146 543.9 99.9 23.4 27.5 506.9 110.3 21.8 26.3 471.6 123.1 20.3 25.3
161 564.2 102.6 24.3 28.5 548.7 119.1 23.6 28.5 533.4 140.6 22.9 28.7
171 596.9 108.8 25.7 30.1 582.0 125.6 25.0 30.2 567.6 145.7 24.4 30.4
186 638.5 117.7 27.5 32.3 622.8 135.5 26.8 32.3 608.0 156.8 26.2 32.6
206 767.1 135.4 33.0 38.5 748.4 156.2 32.2 38.6 727.6 181.7 31.3 38.8
246 895.0 158.6 38.5 45.0 872.9 183.3 37.5 45.1 845.8 212.9 36.4 45.1
261 925.5 166.2 39.8 46.6 902.9 191.3 38.8 46.7 878.1 221.4 37.8 46.9
271 961.8 175.0 41.4 48.5 938.3 201.4 40.4 48.6 914.4 233.1 39.3 48.9
LEGEND
Cap — Capacity, kW
Cond — Condenser
kW — Compressor Motor Input Power at
Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

20
COOLING CAPACITIES (cont)
60 Hz, SI (cont)

CONDENSER ENTERING WATER TEMPERATURE (F)


30HXC 25 30 35
LCWT UNIT Cooler Cond Cooler Cond Cooler Cond
(C) SIZE Input Flow Flow Input Flow Flow Input Flow Flow
Cap kW Rate Rate Cap kW Rate Rate Cap kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 293.7 51.6 12.6 14.7 273.5 56.3 11.8 14.1 252.3 62.0 10.9 13.4
086 323.2 57.7 13.9 16.3 300.9 63.1 13.0 15.5 278.3 69.3 12.0 14.8
096 365.1 64.5 15.7 18.3 340.5 70.6 14.7 17.5 314.9 77.7 13.6 16.7
106 405.6 71.9 17.5 20.4 378.0 79.3 16.3 19.5 348.3 87.5 15.0 18.6
116 440.6 76.0 19.0 22.1 411.4 83.9 17.7 21.1 380.1 92.8 16.4 20.2
126 476.4 82.9 20.5 23.9 444.9 91.6 19.1 22.9 412.1 101.5 17.7 21.9
136 528.7 93.9 22.8 26.6 494.2 102.5 21.3 25.5 458.6 112.7 19.7 24.4
8 146 564.9 101.0 24.3 28.4 527.9 111.0 22.7 27.3 489.5 124.7 21.1 26.2
161 581.9 102.7 25.0 29.2 567.2 118.7 24.4 29.3 548.7 139.1 23.6 29.3
171 614.9 108.9 26.5 30.9 601.1 125.2 25.9 31.0 584.7 145.4 25.2 31.1
186 657.9 117.9 28.3 33.1 643.3 135.0 27.7 33.2 625.2 156.2 26.9 33.3
206 787.2 135.1 33.9 39.4 773.3 155.8 33.3 39.7 749.9 181.2 32.3 39.7
246 921.7 158.4 39.7 46.1 901.2 182.6 38.8 46.3 873.3 212.6 37.6 46.3
261 953.6 166.3 41.0 47.8 932.0 190.6 40.1 47.9 905.3 221.1 39.0 48.0
271 991.1 175.2 42.7 49.8 968.6 200.7 41.7 49.9 941.5 232.5 40.5 50.1
076 304.4 52.1 13.1 15.2 284.8 56.7 12.3 14.6 262.7 62.6 11.3 13.9
086 335.3 58.4 14.4 16.8 313.3 63.5 13.5 16.1 289.6 70.0 12.5 15.3
096 378.6 65.2 16.3 18.9 354.4 71.0 15.3 18.2 327.7 78.4 14.1 17.3
106 420.8 72.5 18.1 21.1 393.4 79.8 16.9 20.2 362.9 88.3 15.6 19.2
116 456.3 76.5 19.6 22.8 428.2 84.3 18.4 21.9 396.1 93.6 17.1 20.9
126 492.9 83.4 21.2 24.6 462.9 92.1 19.9 23.7 428.8 102.2 18.5 22.7
136 548.4 94.8 23.6 27.5 514.6 103.1 22.2 26.4 477.2 113.8 20.5 25.2
9 146 585.5 101.8 25.2 29.3 549.2 111.7 23.6 28.2 508.4 123.3 21.9 27.0
161 599.3 102.6 25.8 30.0 585.6 118.3 25.2 30.0 566.6 137.9 24.4 30.1
171 630.9 108.8 27.2 31.6 619.8 125.0 26.7 31.8 602.2 145.0 25.9 31.9
186 676.7 117.9 29.1 33.9 663.0 134.5 28.5 34.0 644.7 156.1 27.8 34.2
206 807.4 134.7 34.8 40.2 797.3 155.9 34.3 40.7 773.6 180.8 33.3 40.7
246 944.2 157.5 40.7 47.1 930.4 181.9 40.1 47.5 902.1 212.3 38.8 47.6
261 977.2 165.6 42.1 48.8 962.1 189.6 41.4 49.2 934.2 221.0 40.2 49.3
271 1017.3 174.6 43.8 50.9 999.6 199.6 43.0 51.2 971.1 232.3 41.8 51.3
076 313.9 52.4 13.5 15.6 296.0 57.4 12.8 15.1 273.4 63.2 11.8 14.4
086 346.8 58.8 14.9 17.3 325.9 64.1 14.0 16.7 301.2 70.7 13.0 15.9
096 390.5 65.6 16.8 19.5 368.4 71.8 15.9 18.8 340.8 79.1 14.7 17.9
106 435.2 73.0 18.7 21.7 409.0 80.4 17.6 20.9 378.0 89.1 16.3 19.9
116 470.9 76.7 20.3 23.4 445.1 85.0 19.2 22.6 412.4 94.4 17.8 21.6
126 509.4 83.8 21.9 25.3 481.1 92.9 20.7 24.5 446.3 103.1 19.2 23.5
136 565.3 95.3 24.4 28.2 534.7 104.1 23.0 27.3 496.1 114.7 21.4 26.1
10 146 605.1 102.4 26.1 30.2 570.8 112.7 24.6 29.2 529.1 124.4 22.8 27.9
161 614.0 102.1 26.4 30.6 604.2 118.1 26.0 30.8 585.3 137.8 25.2 30.9
171 647.4 108.5 27.9 32.3 639.1 124.9 27.5 32.6 621.3 144.8 26.8 32.7
186 692.5 117.2 29.8 34.6 683.7 134.3 29.4 34.9 664.7 155.9 28.6 35.0
206 827.5 133.8 35.6 41.1 822.5 155.8 35.4 41.8 798.8 180.5 34.4 41.8
246 965.4 156.2 41.6 47.9 959.1 182.3 41.3 48.8 931.4 211.8 40.1 48.8
261 998.8 164.5 43.0 49.7 991.6 190.3 42.7 50.5 963.4 220.5 41.5 50.5
271 1039.2 173.4 44.8 51.8 1030.1 199.9 44.4 52.5 1001.2 231.8 43.1 52.6

21
Performance data (cont)
COOLING CAPACITIES (cont)
50 Hz, SI

CONDENSER ENTERING WATER TEMPERATURE (F)


30HXC 25 30 35
LCWT UNIT Cooler Cond Cooler Cond Cooler Cond
(C) SIZE Input Flow Flow Input Flow Flow Input Flow Flow
Cap kW Rate Rate Cap kW Rate Rate Cap kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 245.7 48.1 10.5 12.5 227.4 53.1 9.8 12.0 212.9 58.8 9.1 11.6
086 274.3 54.8 11.8 14.0 255.9 60.8 11.0 13.5 240.1 67.1 10.3 13.1
096 312.4 61.8 13.4 16.0 292.2 68.8 12.5 15.4 274.5 76.2 11.8 14.9
106 343.5 68.5 14.7 17.6 317.6 75.8 13.6 16.8 300.5 85.0 12.9 16.4
116 376.5 73.5 16.2 19.2 350.6 81.8 15.1 18.4 329.9 91.2 14.2 17.9
126 410.5 80.9 17.6 20.9 382.8 90.2 16.4 20.1 360.1 100.5 15.5 19.6
136 455.0 90.9 19.5 23.3 425.4 100.7 18.3 22.4 401.2 111.2 17.2 21.8
4 146 482.2 97.4 20.7 24.7 448.9 107.7 19.3 23.7 425.2 120.1 18.3 23.2
161 496.4 99.0 21.3 25.4 475.6 113.5 20.4 25.1 466.6 131.7 20.0 25.5
171 538.2 108.1 23.1 27.5 520.5 124.2 22.3 27.5 509.1 142.7 21.9 27.7
186 579.7 117.7 24.9 29.7 561.1 135.1 24.1 29.6 552.6 156.1 23.7 30.2
206 686.3 133.2 29.5 34.9 661.7 153.4 28.4 34.7 644.2 176.4 27.7 34.9
246 797.0 154.9 34.2 40.6 766.4 178.7 32.9 40.3 748.6 206.5 32.1 40.7
261 838.0 165.0 36.0 42.8 808.7 189.8 34.7 42.5 792.1 218.9 34.0 43.0
271 874.2 174.8 37.5 44.7 845.5 201.1 36.3 44.6 831.7 232.4 35.7 45.3
076 256.0 48.5 11.0 13.0 237.0 53.6 10.2 12.4 220.9 59.2 9.5 11.9
086 285.1 55.1 12.2 14.5 266.3 61.3 11.4 14.0 249.0 67.7 10.7 13.5
096 324.7 62.0 13.9 16.5 304.1 69.5 13.1 15.9 284.7 76.8 12.2 15.4
106 357.7 69.0 15.4 18.2 331.2 76.6 14.2 17.4 311.1 85.5 13.4 16.9
116 391.6 73.7 16.8 19.8 365.4 82.5 15.7 19.1 341.8 91.7 14.7 18.5
126 426.6 81.3 18.3 21.7 398.5 90.9 17.1 20.9 373.0 101.0 16.0 20.2
136 473.3 91.3 20.3 24.1 442.8 101.5 19.0 23.2 416.0 112.0 17.9 22.5
5 146 502.4 98.0 21.6 25.6 466.3 108.3 20.0 24.5 440.3 120.7 18.9 23.9
161 514.2 98.7 22.1 26.1 493.4 113.8 21.2 25.9 480.5 131.5 20.6 26.1
171 557.0 108.1 23.9 28.4 537.9 124.2 23.1 28.2 524.6 142.8 22.5 28.4
186 600.0 117.3 25.8 30.6 580.1 135.1 24.9 30.5 568.8 155.9 24.4 30.9
206 710.4 133.5 30.5 36.0 684.9 153.3 29.4 35.7 664.1 176.4 28.5 35.8
246 824.2 154.9 35.4 41.8 794.9 178.8 34.2 41.5 770.8 206.0 33.1 41.6
261 866.6 164.7 37.2 44.0 837.7 190.0 36.0 43.8 816.1 218.7 35.1 44.1
271 904.1 174.3 38.8 46.0 874.9 201.1 37.6 45.8 856.1 232.1 36.8 46.3
076 266.4 49.2 11.5 13.5 247.0 54.1 10.6 12.8 229.0 59.6 9.8 12.3
086 296.1 55.5 12.7 15.0 277.0 61.9 11.9 14.4 258.3 68.2 11.1 13.9
096 337.1 62.7 14.5 17.1 316.3 70.0 13.6 16.5 295.3 77.4 12.7 15.9
106 372.3 69.6 16.0 18.8 345.3 77.3 14.8 18.0 322.0 87.3 13.8 17.4
116 406.8 74.2 17.5 20.5 380.6 83.1 16.4 19.8 353.9 92.9 15.2 19.0
126 443.0 81.7 19.0 22.4 414.9 91.5 17.8 21.6 386.3 102.2 16.6 20.8
136 491.6 92.1 21.1 24.9 460.6 102.3 19.8 24.0 431.2 112.8 18.5 23.2
6 146 522.6 99.0 22.5 26.5 485.9 109.2 20.9 25.4 455.8 121.2 19.6 24.6
161 531.7 98.8 22.9 26.9 511.6 114.0 22.0 26.7 494.7 131.3 21.3 26.7
171 575.4 108.2 24.7 29.2 557.2 124.3 24.0 29.1 540.5 142.7 23.2 29.1
186 619.5 117.4 26.6 31.4 600.2 135.0 25.8 31.3 585.5 155.5 25.2 31.6
206 734.4 133.6 31.6 37.0 709.9 153.3 30.5 36.8 684.7 176.2 29.4 36.7
246 851.5 155.2 36.6 43.0 823.3 178.7 35.4 42.7 794.1 205.9 34.1 42.6
261 894.8 165.3 38.5 45.2 866.8 190.0 37.3 45.1 840.4 218.2 36.1 45.1
271 933.1 174.7 40.1 47.3 904.4 200.8 38.9 47.1 880.8 231.3 37.9 47.4
076 277.0 49.8 11.9 13.9 257.4 54.6 11.1 13.3 237.6 60.0 10.2 12.7
086 307.4 56.1 13.2 15.5 288.2 62.4 12.4 15.0 267.8 68.7 11.5 14.3
096 349.9 63.4 15.0 17.6 328.6 70.4 14.1 17.0 306.1 77.9 13.2 16.4
106 386.9 70.4 16.6 19.5 360.0 77.9 15.5 18.7 333.1 88.9 14.3 18.0
116 422.3 74.9 18.2 21.2 396.0 83.7 17.0 20.5 366.8 92.6 15.8 19.6
126 459.8 82.3 19.8 23.1 431.6 92.1 18.6 22.3 400.7 102.1 17.2 21.4
136 510.4 93.2 22.0 25.8 479.2 103.0 20.6 24.8 446.9 113.4 19.2 23.9
7 146 543.2 99.8 23.4 27.4 506.3 110.1 21.8 26.3 471.7 123.2 20.3 25.3
161 548.8 99.2 23.6 27.7 530.2 114.1 22.8 27.5 510.0 132.5 21.9 27.4
171 594.3 108.3 25.6 30.0 576.4 124.3 24.8 29.9 557.4 142.7 24.0 29.8
186 638.6 117.8 27.5 32.3 620.6 135.0 26.7 32.2 602.2 155.1 25.9 32.3
206 757.7 133.7 32.6 38.0 734.9 153.1 31.6 37.9 708.0 176.4 30.5 37.7
246 879.0 155.4 37.8 44.2 852.3 178.3 36.7 44.0 818.3 204.9 35.2 43.6
261 923.1 165.7 39.7 46.5 897.0 189.8 38.6 46.4 865.1 217.6 37.2 46.2
271 962.2 175.1 41.4 48.5 935.4 200.7 40.2 48.5 905.9 230.6 39.0 48.4
LEGEND
Cap — Capacity, kW
Cond — Condenser
kW — Compressor Motor Input Power at
Rated Voltage
LCWT — Leaving Chilled-Water Temperature (C)

22
COOLING CAPACITIES (cont)
50 Hz, SI (cont)

CONDENSER ENTERING WATER TEMPERATURE (F)


30HXC 25 30 35
LCWT UNIT Cooler Cond Cooler Cond Cooler Cond
(C) SIZE Input Flow Flow Input Flow Flow Input Flow Flow
Cap kW Rate Rate Cap kW Rate Rate Cap kW Rate Rate
(L/s) (L/s) (L/s) (L/s) (L/s) (L/s)
076 287.9 50.4 12.4 14.4 268.1 55.0 11.5 13.8 247.3 60.6 10.6 13.1
086 318.9 56.8 13.7 16.0 299.4 62.8 12.9 15.5 278.2 69.3 12.0 14.8
096 363.0 64.1 15.6 18.2 341.3 70.7 14.7 17.6 318.0 78.5 13.7 16.9
106 402.0 71.1 17.3 20.2 374.6 78.5 16.1 19.3 345.1 86.6 14.9 18.4
116 438.3 75.5 18.9 21.9 411.6 84.0 17.7 21.2 381.8 93.3 16.4 20.3
126 477.0 83.0 20.5 23.9 448.6 92.5 19.3 23.1 416.9 102.9 17.9 22.2
136 529.7 94.1 22.8 26.6 498.0 103.5 21.4 25.7 464.2 114.3 20.0 24.7
8 146 564.2 100.8 24.3 28.4 527.3 110.9 22.7 27.2 489.2 124.5 21.1 26.2
161 566.4 99.4 24.4 28.4 548.7 113.9 23.6 28.3 524.9 130.6 22.6 28.0
171 612.5 108.5 26.4 30.8 596.2 124.1 25.7 30.7 575.3 142.7 24.8 30.6
186 658.4 118.0 28.3 33.1 641.8 134.7 27.6 33.1 620.2 154.8 26.7 33.0
206 778.5 133.5 33.5 38.9 760.4 153.1 32.7 39.0 731.5 176.4 31.5 38.7
246 905.1 155.3 39.0 45.3 881.2 177.8 37.9 45.2 846.6 205.1 36.4 44.9
261 951.8 165.9 41.0 47.7 927.0 189.4 39.9 47.6 894.0 217.9 38.5 47.4
271 991.9 175.4 42.7 49.8 966.4 200.2 41.6 49.8 934.2 230.5 40.2 49.7
076 298.1 50.8 12.8 14.9 279.2 55.4 12.0 14.3 257.5 61.2 11.1 13.6
086 330.3 57.3 14.2 16.5 310.9 63.0 13.4 16.0 289.2 70.0 12.5 15.3
096 376.1 64.7 16.2 18.8 354.3 71.0 15.3 18.2 330.5 79.2 14.2 17.5
106 416.8 71.7 17.9 20.9 389.9 79.0 16.8 20.0 359.7 87.4 15.5 19.1
116 453.4 76.0 19.5 22.6 427.7 84.2 18.4 21.9 397.6 94.1 17.1 21.0
126 492.9 83.5 21.2 24.6 465.8 92.9 20.1 23.9 433.6 103.6 18.7 22.9
136 548.9 94.9 23.6 27.5 517.5 103.8 22.3 26.5 482.6 115.3 20.8 25.5
9 146 584.8 101.7 25.2 29.3 548.6 111.5 23.6 28.2 507.8 123.1 21.9 26.9
161 584.1 99.4 25.1 29.2 567.2 113.7 24.4 29.1 543.9 131.0 23.4 28.8
171 628.8 108.4 27.1 31.5 616.2 124.0 26.5 31.6 594.1 142.8 25.6 31.4
186 677.4 118.0 29.2 34.0 662.2 134.4 28.5 34.0 640.5 154.9 27.6 33.9
206 799.4 133.3 34.4 39.8 785.2 153.4 33.8 40.1 756.4 176.4 32.6 39.8
246 928.3 154.5 40.0 46.2 910.6 177.6 39.2 46.5 876.5 205.2 37.7 46.2
261 975.6 165.3 42.0 48.7 958.2 188.7 41.3 49.0 924.3 218.2 39.8 48.8
271 1018.4 174.8 43.8 50.9 998.9 199.5 43.0 51.2 965.3 230.7 41.6 51.0
076 307.5 51.1 13.2 15.3 290.2 56.1 12.5 14.8 268.1 61.7 11.5 14.1
086 341.2 57.7 14.7 17.0 322.0 63.3 13.9 16.4 300.6 70.5 12.9 15.8
096 387.7 65.1 16.7 19.3 367.5 71.6 15.8 18.8 343.5 79.8 14.8 18.1
106 431.1 72.2 18.6 21.5 405.3 79.6 17.5 20.7 374.6 88.2 16.1 19.7
116 467.6 76.1 20.1 23.2 443.8 84.7 19.1 22.6 413.7 94.8 17.8 21.7
126 509.0 83.7 21.9 25.3 483.2 93.4 20.8 24.6 451.0 104.4 19.4 23.7
136 565.8 95.4 24.4 28.2 537.0 104.6 23.1 27.4 501.5 116.2 21.6 26.4
10 146 604.3 102.2 26.0 30.2 570.1 112.5 24.6 29.1 528.5 124.2 22.8 27.9
161 597.9 98.8 25.8 29.8 586.0 113.7 25.2 29.9 563.3 131.2 24.3 29.6
171 645.6 108.2 27.8 32.2 635.5 124.1 27.4 32.4 614.1 142.9 26.5 32.3
186 693.1 117.4 29.9 34.6 683.5 134.3 29.4 34.9 661.2 155.0 28.5 34.8
206 820.3 132.6 35.3 40.7 811.2 153.5 34.9 41.2 782.3 176.4 33.7 40.9
246 949.5 153.3 40.9 47.1 939.6 178.0 40.5 47.7 906.6 205.2 39.1 47.5
261 997.3 164.2 43.0 49.6 988.2 189.6 42.6 50.3 955.1 218.3 41.1 50.1
271 1040.2 173.5 44.8 51.8 1030.0 199.9 44.4 52.5 996.5 230.6 42.9 52.4

23
Performance data (cont)
COOLER PRESSURE DROP
ENGLISH

— Unit size range


NOTE: Ft of water = 2.31 x change in psig.

SI

— Unit size range

24
CONDENSER PRESSURE DROP
ENGLISH

— Unit size range


NOTE: Ft of water = 2.31 x change in psig.

SI

— Unit size range

25
26
TO EXPANSION FD
TANK FD
FROM FD
COOLING FD FIELD
TOWER CHILLED WATER POWER
FIELD-SUPPLIED PUMP POWER SUPPLY
SHUT-OFF VALVE FIELD SUPPLIED
TO COOLING SHUT-OFF VALVE ST ST
TOWER ST
STRAINER*

FAN
MOTOR
POWER

SEE BASE UNIT


INSTALLATION
INSTRUCTIONS
FOR CONNECTION
TYPE
FIELD-
SUPPLIED
SHUT-OFF CHILLED
VALVES WATER PUMP
Typical piping and wiring

FROM ADDITIONAL
AIR HANDLING UNITS
STRAINER*

CONDENSER
WATER PUMP TO ADDITIONAL
AIR HANDLING UNITS

AIR HANDLING
UNIT

30HXC
CHILLER

LEGEND NOTES:
Airflow Through Air-Handling Unit 1. Chiller must be installed levelly to maintain proper compressor oil return.
2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation.
Power Wiring Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards.
3. All wiring must comply with applicable local and national codes.
Chilled Fluid Piping 4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE
ST — Starter (American Society of Heating, Refrigeration, and Air Conditioning Engineers) handbook for details.
5. See Application Data section on page 13 for minimum cooler loop volume. This system may require the addition of a
FD — Field-Supplied Disconnect holding tank to ensure adequate volume.
* Field Supplied.
Electrical data — 30HXC fluid-cooled units
UNIT ELECTRICAL DATA
VOLTAGE
POWER CIRCUIT* CONTROL CIRCUIT ICF
UNIT Supplied
Nameplate
30HXC V-Hz Recommended Voltage
(3 Ph) Min Max MCA MOCP (Single Min Max MCA MOCP WD XL
Fuse Size Ph)
208/230-60
Ckt A 187 253 123 200 175 115-60 104 127 15 15 307 †
Ckt B 187 253 123 200 150 115-60 104 127 15 15 307 †
460-60 414 506 100 150 125 115-60 104 127 15 15 148 374
076 575-60 518 633 80 110 100 115-60 104 127 15 15 118 299
380-60 342 418 121 175 150 230-60 207 254 15 15 169 419
230-50
Ckt A 207 253 115 200 150 230-50 198 254 15 15 266 †
Ckt B 207 253 115 200 150 230-50 198 254 15 15 266 †
380/415-50 342 440 126 175 150 230-50 198 254 — — 165 400
208/230-60
Ckt A 187 253 148 250 200 115-60 104 127 15 15 307 †
Ckt B 187 253 123 200 150 115-60 104 127 15 15 307 †
460-60 414 506 111 150 125 115-60 104 127 15 15 148 374
086 575-60 518 633 89 125 100 115-60 104 127 15 15 118 299
380-60 342 418 135 200 175 230-60 207 254 15 15 169 419
230-50
Ckt A 207 253 140 250 75 230-50 198 254 15 15 305 †
Ckt B 207 253 115 200 150 230-50 198 254 15 15 305 †
380/415-50 342 440 140 200 175 230-50 198 254 — — 190 479
208/230-60
Ckt A 187 253 181 300 225 115-60 104 127 15 15 354 †
Ckt B 187 253 122 200 150 115-60 104 127 15 15 354 †
460-60 414 506 126 175 150 115-60 104 127 15 15 172 449
096 575-60 518 633 101 150 125 115-60 104 127 15 15 137 359
380-60 342 418 153 225 175 230-60 207 254 15 15 195 502
230-50
Ckt A 207 253 169 300 225 230-50 198 254 15 15 347 †
Ckt B 207 253 115 200 150 230-50 198 254 15 15 347 †
380/415-50 342 440 158 225 200 230-50 198 254 — — 216 562
208/230-60
Ckt A 187 253 219 350 300 115-60 104 127 15 15 405 †
Ckt B 187 253 123 200 150 115-60 104 127 15 15 405 †
460-60 414 506 143 200 175 115-60 104 127 15 15 197 529
575-60 518 633 115 175 150 115-60 104 127 15 15 158 423
106 380-60 342 418 174 250 200 230-60 207 254 15 15 223 590
230-50
Ckt A 207 253 202 350 250 230-50 198 254 15 15 397 †
Ckt B 207 253 115 200 150 230-50 198 254 15 15 397 †
380/415-50 342 440 178 250 225 230-50 198 254 — — 247 661
208/230-60
Ckt A 187 253 219 350 300 115-60 104 127 15 15 426 †
Ckt B 187 253 148 250 200 115-60 104 127 15 15 426 †
460-60 414 506 153 225 175 115-60 104 127 15 15 207 539
116 575-60 518 633 122 175 150 115-60 104 127 15 15 166 431
380-60 342 418 185 250 225 230-60 207 254 15 15 234 601
230-50
Ckt A 207 253 202 350 250 230-50 198 254 15 15 417 †
Ckt B 207 253 140 250 175 230-50 198 254 15 15 417 †
380/415-50 342 440 190 250 225 230-50 198 254 — — 259 673
208/230-60
Ckt A 187 253 219 350 300 115-60 104 127 15 15 452 †
Ckt B 187 253 181 300 225 115-60 104 127 15 15 452 †
460-60 414 506 165 225 200 115-60 104 127 15 15 219 551
126 575-60 518 633 131 175 150 115-60 104 127 15 15 175 440
380-60 342 418 199 250 225 230-60 207 254 15 15 248 615
230-50
Ckt A 207 253 202 350 250 230-50 198 254 15 15 440 †
Ckt B 207 253 169 300 225 230-50 198 254 15 15 440 †
380/415-50 342 440 204 300 250 230-50 198 254 — — 273 687
208/230-60
Ckt A 187 253 263 450 350 115-60 104 127 15 15 512 †
Ckt B 187 253 181 300 225 115-60 104 127 15 15 512 †
460-60 414 506 184 250 225 115-60 104 127 15 15 249 646
136 575-60 518 633 147 200 175 115-60 104 127 15 15 199 536
380-60 342 418 222 300 300 230-60 207 254 15 15 282 720
230-50
Ckt A 207 253 245 400 300 230-50 198 254 15 15 496 †
Ckt B 207 253 169 300 225 230-50 198 254 15 15 496 †
380/415-50 342 440 230 300 300 230-50 198 254 — — 308 797

See legend and notes on page 29.

27
Electrical data —
30HXC fluid-cooled units (cont)
UNIT ELECTRICAL DATA (cont)
VOLTAGE
POWER CIRCUIT* CONTROL CIRCUIT ICF
UNIT Supplied
Nameplate
30HXC V-Hz Recommended Voltage
(3 Ph) Min Max MCA MOCP (Single Min Max MCA MOCP WD XL
Fuse Size Ph)
208/230-60
Ckt A 187 253 263 450 350 115-60 104 127 15 15 542 †
Ckt B 187 253 219 350 300 115-60 104 127 15 15 542 †
460-60 414 506 198 250 225 115-60 104 127 15 15 262 659
146 575-60 518 633 158 225 200 115-60 104 127 15 15 210 547
380-60 342 418 240 350 300 230-60 207 254 15 15 299 737
230-50
Ckt A 207 253 245 400 300 230-50 198 254 15 15 523 †
Ckt B 207 253 202 350 250 230-50 198 254 15 15 523 †
380/415-50 342 440 246 350 300 230-50 198 254 — — 324 813
208/230-60
Ckt A 187 253 285 500 350 115-60 104 127 15 15 591 †
Ckt B 187 253 197 350 250 115-60 104 127 15 15 591 †
460-60 414 506 200 300 250 115-60 104 127 15 15 287 756
161 575-60 518 633 160 225 200 115-60 104 127 15 15 230 605
380-60 342 418 242 350 300 230-60 207 254 15 15 325 843
230-50
Ckt A 207 253 266 450 350 230-50 198 254 15 15 578 †
Ckt B 207 253 182 300 225 230-50 198 254 15 15 578 †
380/415-50 342 440 249 350 300 230-50 198 254 — — 358 944
208/230-60
Ckt A 187 253 238 400 300 115-60 104 127 15 15 624 †
Ckt B 187 253 285 500 400 115-60 104 127 15 15 624 †
460-60 414 506 215 300 250 115-60 104 127 15 15 302 771
171 575-60 518 633 172 250 200 115-60 104 127 15 15 242 617
380-60 342 418 260 350 300 230-60 207 254 15 15 343 861
230-50
Ckt A 207 253 219 350 300 230-50 198 254 15 15 607 †
Ckt B 207 253 266 450 350 230-50 198 254 15 15 607 †
380/415-50 342 440 267 350 300 230-50 198 254 — — 376 962
208/230-60
Ckt A 187 253 285 500 400 115-60 104 127 15 15 661 †
Ckt B 187 253 285 500 400 115-60 104 127 15 15 661 †
460-60 414 506 232 300 300 115-60 104 127 15 15 319 788
575-60 518 633 185 250 225 115-60 104 127 15 15 255 630
186 380-60 342 418 281 400 350 230-60 207 254 15 15 364 882
230-50
Ckt A 207 253 266 450 350 230-50 198 254 15 15 645 †
Ckt B 207 253 266 450 350 230-50 198 254 15 15 645 †
380/415-50 342 440 289 400 350 230-50 198 254 — — 399 985
208/230-60
Ckt A 187 253 345 500 400 115-60 104 127 15 15 907 †
Ckt B 187 253 285 500 350 115-60 104 127 15 15 907 †
460-60 414 506 263 350 300 115-60 104 127 15 15 247 716
575-60 518 633 210 250 250 115-60 104 127 15 15 198 573
206 380-60 342 418 319 400 350 230-60 207 254 15 15 277 795
346-50 325 380 358 450 400 230-50 198 254 15 15 338 †
230-50
Ckt A 207 253 318 450 400 230-50 198 254 15 15 892 †
Ckt B 207 253 266 450 350 230-50 198 254 15 15 892 †
380/415-50 342 440 327 450 400 230-50 198 254 — — 307 893
See legend and notes on page 29.

28
UNIT ELECTRICAL DATA (cont)
VOLTAGE
POWER CIRCUIT* CONTROL CIRCUIT ICF
UNIT Supplied
Nameplate
30HXC V-Hz Recommended Voltage
(3 Ph) Min Max MCA MOCP (Single Min Max MCA MOCP WD XL
Fuse Size Ph)
208/230-60
Ckt A 187 253 443 600 600 115-60 104 127 15 15 1024 †
Ckt B 187 253 285 500 350 115-60 104 127 15 15 1024 †
460-60 414 506 303 400 350 115-60 104 127 15 15 287 756
575-60 518 633 242 300 300 115-60 104 127 15 15 230 605
246 380-60 342 418 367 450 400 230-60 207 254 15 15 325 843
346-50 325 380 414 500 450 230-50 198 254 15 15 394 †
230-50
Ckt A 207 253 411 600 500 230-50 198 254 15 15 1010 †
Ckt B 207 253 266 450 350 230-50 198 254 15 15 1010 †
380/415-50 342 440 378 500 450 230-50 198 254 — — 358 944
208/230-60
Ckt A 187 253 476 700 600 115-60 104 127 15 15 1057 †
Ckt B 187 253 285 500 350 115-60 104 127 15 15 1057 †
460-60 414 506 318 400 350 115-60 104 127 15 15 302 771
575-60 518 633 254 300 300 115-60 104 127 15 15 242 617
261 380-60 342 418 385 500 450 230-60 207 254 15 15 343 861
346-50 325 380 433 500 500 230-50 198 254 15 15 413 †
230-50
Ckt A 207 253 400 600 500 230-50 198 254 15 15 1039 †
Ckt B 207 253 266 450 350 230-50 198 254 15 15 1039 †
380/415-50 342 440 395 500 450 230-50 198 254 — — 376 962
208/230-60
Ckt A 187 253 514 700 600 115-60 104 127 15 15 1094 †
Ckt B 187 253 285 500 350 115-60 104 127 15 15 1094 †
460-60 414 506 335 400 400 115-60 104 127 15 15 319 788
75-60 518 633 268 350 300 115-60 104 127 15 15 255 630
271 380-60 342 418 406 500 450 230-60 207 254 15 15 364 882
346-50 325 380 458 500 500 230-50 198 254 15 15 438 †
230-50
Ckt A 207 253 478 600 600 230-50 198 254 15 15 1077 †
Ckt B 207 253 266 450 350 230-50 198 254 15 15 1077 †
380/415-50 342 440 418 500 350 230-50 198 254 — — 399 985

LEGEND 6. The MOCP is calculated as follows:


FLA — Full Load Amps MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size
ICF — Maximum Instantaneous Current Flow during start-up the fuse one size down from the result. The RLAs are listed on the
(the point in the starting sequence where the sum of the unit nameplate.
LRA for the start-up compressor, plus the total RLA for The recommended fuse size in amps (RFA) is calculated as
all running compressors, plus the total FLA for all run- follows:
ning fan motors is at a maximum)
LRA — Locked Rotor Amps RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the
MCA — Minimum Circuit Ampacity (for wire sizing) fuse one size up from the result. The RLAs are listed on the unit
MOCP — Maximum Overcurrent Protection nameplate.
RLA — Rated Load Amps 7. Units have the following power wiring terminal blocks and parallel
WD — Wye-Delta Start conductors:
XL — Across-the-Line Start
*Units with one MCA, MOCP, and fuse size value have one terminal TERMINAL
block and require one power supply. Units with one MCA, MOCP, and VOLTAGE BLOCKS CONDUCTORS
fuse value for Circuit A and another for Circuit B have 2 terminal blocks OR NON-FUSED
and require 2 power supplies. DISCONNECTS
†Wye-Delta Start is standard. Not available in across-the-line start. 208/230 2 6
NOTES: 460 1 3
1. Each main power source must be supplied from a field-supplied 575 1 3
fused electrical service with a (factory- or field-installed) disconnect 380 1 3
located in sight from the unit.
2. Control circuit power must be supplied from a separate source through 230 2 6
a field-supplied disconnect (except for 380/415-50 units). The con- 380/415 1 3
trol circuit accessory transformer may be applied to power from the
main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Use copper conductors only.

29
Electrical data —
30HXC fluid-cooled units (cont)
COMPRESSOR ELECTRICAL DATA

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE V-Hz A1 B1
30HXC (3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
460-60 44.3 330 44.3 330
575-60 35.4 264 35.4 264
076-XL
380-60 53.7 365 53.7 365
230-50 * * * *
380/415-50 55.8 344 55.8 344
208/230-60 98.1 209 98.1 209
460-60 44.3 104 44.3 104
575-60 35.4 83 35.4 83
076-WD
380-60 53.7 115 53.7 115
230-50 92.1 174 92.1 174
380/415-50 55.8 109 55.8 109
208/230-60 * * * *
460-60 53.6 330 44.3 330
575-60 42.8 264 35.4 264
086-XL
380-60 64.9 365 53.7 365
230-50 * * * *
380/415-50 67.7 423 55.8 344
208/230-60 118.6 209 98.1 209
460-60 53.6 104 44.3 104
575-60 42.8 83 35.4 83
086-WD
380-60 64.9 115 53.7 115
230-50 111.8 213 92.1 174
380/415-50 67.7 134 55.8 109
208/230-60 * * * *
460-60 65.5 405 44.3 330
575-60 52.3 324 35.4 264
096-XL
380-60 79.2 448 53.7 365
230-50 * * * *
380/415-50 81.7 506 55.8 344
208/230-60 144.9 256 98.1 209
460-60 65.5 128 44.3 104
575-60 52.3 102 35.4 83
096-WD
380-60 79.2 141 53.7 115
230-50 134.9 255 92.1 174
380/415-50 81.7 160 55.8 109
208/230-60 * * * *
460-60 79.2 485 44.3 330
575-60 63.3 388 35.4 264
106-XL
380-60 95.9 536 53.7 365
230-50 * * * *
380/415-50 97.8 605 55.8 344
208/230-60 175.4 307 98.1 209
460-60 79.2 153 44.3 104
575-60 63.3 123 35.4 83
106-WD
380-60 95.9 169 53.7 115
230-50 161.7 305 92.1 174
380/415-50 97.8 191 55.8 109

LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

30
COMPRESSOR ELECTRICAL DATA (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE V-Hz A1 B1
30HXC (3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
460-60 79.2 485 53.6 330
575-60 63.3 388 42.8 264
116-XL
380-60 95.9 536 64.9 365
230-50 * * * *
380/415-50 87.8 605 67.7 423
208/230-60 175.4 307 118.6 209
460-60 79.2 153 53.6 104
575-60 63.3 123 42.8 83
116-WD
380-60 95.5 169 64.9 115
230-50 161.7 305 111.8 213
380/415-50 97.8 191 67.7 134
208/230-60 * * * *
460-60 79.2 485 65.5 405
575-60 63.3 388 52.3 324
126-XL
380-60 95.9 536 79.2 448
230-50 * * * *
380/415-50 97.8 605 81.7 506
208/230-60 175.4 307 144.9 256
460-60 79.2 153 65.5 128
575-60 63.3 123 52.3 102
126-WD
380-60 95.9 169 79.2 141
230-50 161.7 305 134.9 255
380/415-50 97.8 191 81.7 160
208/230-60 * * * *
460-60 94.9 580 65.5 405
575-60 75.8 484 52.3 324
136-XL
380-60 114.9 641 79.2 448
230-50 * * * *
380/415-50 118.8 715 81.7 506
208/230-60 210.0 367 144.9 256
460-60 94.6 183 65.5 128
575-60 75.8 147 52.3 102
136-WD
380-60 114.9 203 79.2 141
230-50 196.3 361 134.9 255
380/415-50 118.8 226 81.7 160
208/230-60 * * * *
460-60 94.9 580 79.2 485
575-60 75.8 484 63.3 388
146-XL
380-60 114.9 641 95.9 536
230-50 * * * *
380/415-50 118.8 715 97.8 605
208/230-60 210.0 367 175.4 307
460-60 94.9 183 79.2 153
575-60 75.8 147 63.3 123
146-WD
380-60 114.9 203 95.9 169
230-50 196.3 361 161.7 305
380/415-50 118.8 226 97.8 191

LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

31
Electrical data —
30HXC fluid-cooled units (cont)
COMPRESSOR ELECTRICAL DATA (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE V-Hz A1 B1
30HXC (3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
460-60 103.1 685 71.2 525
575-60 82.4 548 56.9 420
161-XL
380-60 124.8 757 86.2 580
230-50 * * * *
380/415-50 128.6 856 88.2 600
208/230-60 228.8 433 157.6 350
460-60 103.1 216 71.2 175
575-60 82.4 173 56.9 140
161-WD
380-60 124.8 239 86.2 193
230-50 212.5 432 145.7 348
380/415-50 128.6 270 88.2 200
208/230-60 * * * *
460-60 86.1 580 103.1 685
575-60 68.8 484 82.4 548
171-XL
380-60 104.2 641 124.8 757
230-50 * * * *
380/415-50 105.8 715 128.6 856
208/230-60 190.6 367 228.8 433
460-60 86.1 183 103.1 216
575-60 68.8 147 82.4 173
171-WD
380-60 104.2 203 124.8 239
230-50 174.8 361 212.5 432
380/415-50 105.8 233 128.6 270
208/230-60 * * * *
460-60 103.1 685 103.1 685
575-60 82.4 548 82.4 548
186-XL
380-60 124.8 757 124.8 757
230-50 * * * *
380/415-50 128.6 856 128.6 856
208/230-60 228.8 433 228.8 433
460-60 103.1 216 103.1 216
575-60 82.4 173 82.4 173
186-WD
380-60 124.8 239 124.8 239
230-50 212.5 432 212.5 432
380/415-50 128.6 270 128.6 270

LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

32
COMPRESSOR ELECTRICAL DATA (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE V-Hz A1 A2 B1
30HXC (3 Phase) RLA LRA RLA LRA RLA LRA
208/230-60 * * * * * *
460-60 86.1 580 44.3 330 103.1 685
575-60 68.8 484 35.4 264 82.4 548
206-XL 380-60 104.2 641 53.7 365 124.8 757
230-50 * * * * * *
346-50 * * * * * *
380/415-50 105.8 715 55.8 344 128.6 856
208/230-60 190.6 367 98.1 209 228.8 433
460-60 86.1 183 44.3 104 103.1 216
575-60 68.8 147 35.4 83 82.4 173
206-WD 380-60 104.2 203 53.7 115 124.8 239
230-50 174.8 361 92.1 174 212.5 432
346-50 116.0 248 61.1 120 141.0 297
380/415-50 105.8 233 55.8 109 128.6 270
208/230-60 * * * * * *
460-60 103.1 685 71.2 525 103.1 685
575-60 82.4 548 56.9 420 82.4 548
246-XL 380-60 124.8 757 86.2 580 124.8 757
230-50 * * * * * *
346-50 * * * * * *
380/415-50 128.6 856 88.2 600 128.6 856
208/230-60 228.8 433 157.6 350 228.8 433
460-60 103.1 216 71.2 175 103.1 216
575-60 82.4 173 56.9 140 82.4 173
246-WD 380-60 124.8 239 86.2 193 124.8 239
230-50 212.5 432 145.7 348 212.5 432
346-50 141.0 297 96.7 232 141.0 297
380/415-50 128.6 270 88.2 200 128.6 270
208/230-60 * * * * * *
460-60 103.1 685 86.1 580 103.1 685
575-60 82.4 548 68.8 484 82.4 548
261-XL 380-60 124.8 757 104.2 641 124.8 757
230-50 * * * * * *
346-50 * * * * * *
380/415-50 128.6 856 105.8 715 128.6 856
208/230-60 228.8 433 190.6 367 228.8 433
460-60 103.1 216 86.1 183 103.1 216
575-60 82.4 173 68.8 147 82.4 173
261-WD 380-60 124.8 239 104.2 203 124.8 239
230-50 212.5 432 174.8 361 212.5 432
346-50 141.0 297 116.0 248 141.0 297
380/415-50 128.6 270 105.8 233 128.6 270
208/230-60 * * * * * *
460-60 103.1 685 103.1 685 103.1 685
575-60 82.4 548 82.4 548 82.4 548
271-XL 380-60 124.8 757 124.8 757 124.8 757
230-50 * * * * * *
346-50 * * * * * *
380/415-50 128.6 856 128.6 856 128.6 856
208/230-60 228.8 433 228.8 433 228.8 433
460-60 103.1 216 103.1 216 103.1 216
575-60 82.4 173 82.4 173 82.4 173
271-WD 380-60 124.8 239 124.8 239 124.8 239
230-50 212.5 432 212.5 432 212.5 432
346-50 141.0 297 141.0 297 141.0 297
380/415-50 128.6 270 128.6 270 128.6 270

LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

33
Electrical data —
30HXA condenserless units
UNIT ELECTRICAL DATA
VOLTAGE
POWER CIRCUIT* CONTROL CIRCUIT ICF
UNIT Supplied
Nameplate
30HXA V-Hz Recommended Voltage
(3 Ph) Min Max MCA MOCP (Single Min Max MCA MOCP WD XL
Fuse Size Ph)
208/230-60
Ckt A 187 253 180 300 225 115-60 104 127 15 15 451 †
Ckt B 187 253 180 300 225 115-60 104 127 15 15 451 †
460-60 414 506 146 200 175 115-60 104 127 15 15 218 550
076 575-60 518 633 117 150 150 115-60 104 127 15 15 175 440
380-60 342 418 177 250 200 230-60 207 254 15 15 248 615
230-50
Ckt A 207 253 169 300 225 230-50 198 254 15 15 440 †
Ckt B 207 253 169 300 225 230-50 198 254 15 15 440 †
380/415-50 342 440 183 250 225 230-50 198 254 — — 273 687
208/230-60
Ckt A 187 253 215 350 300 115-60 104 127 15 15 511 †
Ckt B 187 253 180 300 225 115-60 104 127 15 15 511 †
460-60 414 506 162 225 200 115-60 104 127 15 15 248 645
086 575-60 518 633 130 175 150 115-60 104 127 15 15 199 536
380-60 342 418 196 250 225 230-60 207 254 15 15 282 720
230-50
Ckt A 207 253 205 350 250 230-50 198 254 15 15 496 †
Ckt B 207 253 169 300 225 230-50 198 254 15 15 496 †
380/415-50 342 440 206 300 250 230-50 198 254 — — 308 797
208/230-60
Ckt A 187 253 262 450 350 115-60 104 127 15 15 577 †
Ckt B 187 253 180 300 225 115-60 104 127 15 15 577 †
460-60 414 506 183 250 225 115-60 104 127 15 15 281 750
096 575-60 518 633 147 200 175 115-60 104 127 15 15 225 600
380-60 342 418 222 300 300 230-60 207 254 15 15 318 836
230-50
Ckt A 207 253 248 400 300 230-50 198 254 15 15 567 †
Ckt B 207 253 169 300 225 230-50 198 254 15 15 567 †
380/415-50 342 440 231 350 300 230-50 198 254 — — 352 938
208/230-60
Ckt A 187 253 319 500 400 115-60 104 127 15 15 662 †
Ckt B 187 253 180 300 225 115-60 104 127 15 15 662 †
460-60 414 506 209 300 250 115-60 104 127 15 15 324 885
575-60 518 633 167 250 200 115-60 104 127 15 15 259 708
106 380-60 342 418 253 350 300 230-60 207 254 15 15 365 985
230-50
Ckt A 207 253 300 500 400 230-50 198 254 15 15 620 †
Ckt B 207 253 169 300 225 230-50 198 254 15 15 620 †
380/415-50 342 440 263 400 300 230-50 198 254 — — 385 1042
208/230-60
Ckt A 187 253 319 500 400 115-60 104 127 15 15 690 †
Ckt B 187 253 215 350 300 115-60 104 127 15 15 690 †
460-60 414 506 222 300 300 115-60 104 127 15 15 337 898
116 575-60 518 633 177 250 200 115-60 104 127 15 15 269 718
380-60 342 418 269 400 350 230-60 207 254 15 15 380 1000
230-50
Ckt A 207 253 300 500 400 230-50 198 254 15 15 649 †
Ckt B 207 253 205 350 250 230-50 198 254 15 15 649 †
380/415-50 342 440 281 400 350 230-50 198 254 — — 402 1059
208/230-60
Ckt A 187 253 319 500 400 115-60 104 127 15 15 728 †
Ckt B 187 253 262 450 350 115-60 104 127 15 15 728 †
460-60 414 506 239 350 300 115-60 104 127 15 15 354 915
126 575-60 518 633 191 250 225 115-60 104 127 15 15 283 732
380-60 342 418 289 400 350 230-60 207 254 15 15 401 1021
230-50
Ckt A 207 253 300 500 400 230-50 198 254 15 15 683 †
Ckt B 207 253 248 400 300 230-50 198 254 15 15 683 †
380/415-50 342 440 302 400 350 230-50 198 254 — — 423 1080
208/230-60
Ckt A 187 253 389 700 500 115-60 104 127 15 15 791 †
Ckt B 187 253 262 450 350 115-60 104 127 15 15 791 †
460-60 414 506 271 400 350 115-60 104 127 15 15 386 1015
136 575-60 518 633 216 300 250 115-60 104 127 15 15 309 812
380-60 342 418 328 450 400 230-60 207 254 15 15 436 1132
230-50
Ckt A 207 253 369 600 450 230-50 198 254 15 15 817 †
Ckt B 207 253 248 400 300 230-50 198 254 15 15 817 †
380/415-50 342 440 343 500 400 230-50 198 254 — — 507 1346

See legend and notes on page 35.

34
UNIT ELECTRICAL DATA (cont)
VOLTAGE
POWER CIRCUIT* CONTROL CIRCUIT ICF
UNIT Supplied
Nameplate
30HXA V-Hz Recommended Voltage
(3 Ph) Min Max MCA MOCP (Single Min Max MCA MOCP WD XL
Fuse Size Ph)
208/230-60
Ckt A 187 253 389 700 500 115-60 104 127 15 15 837 †
Ckt B 187 253 319 500 400 115-60 104 127 15 15 837 †
460-60 414 506 291 400 350 115-60 104 127 15 15 406 1035
146 575-60 518 633 233 300 300 115-60 104 127 15 15 325 828
380-60 342 418 353 500 400 230-60 207 254 15 15 461 1157
230-50
Ckt A 207 253 369 600 450 230-50 198 254 15 15 859 †
Ckt B 207 253 300 500 400 230-50 198 254 15 15 859 †
380/415-50 342 440 369 500 450 230-50 198 254 — — 532 1371
208/230-60
Ckt A 187 253 437 700 600 115-60 104 127 15 15 979 †
Ckt B 187 253 295 500 400 115-60 104 127 15 15 979 †
460-60 414 506 304 450 350 115-60 104 127 15 15 478 1282
161 575-60 518 633 243 350 300 115-60 104 127 15 15 382 1025
380-60 342 418 368 500 450 230-60 207 254 15 15 539 1428
230-50
Ckt A 207 253 415 700 500 230-50 198 254 15 15 858 †
Ckt B 207 253 275 450 350 230-50 198 254 15 15 858 †
380/415-50 342 440 385 500 450 230-50 198 254 — — 533 1398
208/230-60
Ckt A 187 253 359 600 450 115-60 104 127 15 15 1030 †
Ckt B 187 253 437 700 600 115-60 104 127 15 15 1030 †
460-60 414 506 327 450 400 115-60 104 127 15 15 501 1305
171 575-60 518 633 261 350 300 115-60 104 127 15 15 401 1044
380-60 342 418 396 500 450 230-60 207 254 15 15 567 1456
230-50
Ckt A 207 253 334 600 450 230-50 198 254 15 15 905 †
Ckt B 207 253 415 700 500 230-50 198 254 15 15 905 †
380/415-50 342 440 413 600 500 230-50 198 254 — — 562 1427
208/230-60
Ckt A 187 253 437 700 600 115-60 104 127 15 15 1093 †
Ckt B 187 253 437 700 600 115-60 104 127 15 15 1093 †
460-60 414 506 355 500 400 115-60 104 127 15 15 529 1333
575-60 518 633 284 400 350 115-60 104 127 15 15 539 1066
186 380-60
Ckt A 342 418 239 400 300 230-60 207 254 15 15 601 1490
Ckt B 342 418 239 400 300 230-60 207 254 15 15 601 1490
230-50
Ckt A 207 253 415 700 500 230-50 198 254 15 15 970 †
Ckt B 207 253 415 700 500 230-50 198 254 15 15 970 †
380/415-50 342 440 453 600 600 230-50 198 254 — — 601 1466

LEGEND 5. Use copper conductors only.


FLA — Full Load Amps 6. The MOCP is calculated as follows:
ICF — Maximum Instantaneous Current Flow during start-up MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size
(the point in the starting sequence where the sum of the the fuse one size down from the result. The RLAs are listed on the
LRA for the start-up compressor, plus the total RLA for unit nameplate.
all running compressors, plus the total FLA for all run-
ning fan motors is at a maximum) The recommended fuse size in amps (RFA) is calculated as
LRA — Locked Rotor Amps follows:
MCA — Minimum Circuit Ampacity (for wire sizing) RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the
MOCP — Maximum Overcurrent Protection fuse one size up from the result. The RLAs are listed on the unit
RLA — Rated Load Amps nameplate.
WD — Wye-Delta Start 7. Units have the following power wiring terminal blocks and parallel
XL — Across-the-Line Start conductors:
*Units with one MCA, MOCP, and fuse size value have one terminal
block and require one power supply. Units with one MCA, MOCP, and TERMINAL
fuse value for Circuit A and another for Circuit B have 2 terminal blocks VOLTAGE BLOCKS CONDUCTORS
and require 2 power supplies. OR NON-FUSED
†Wye-Delta Start is standard. Not available in across-the-line start. DISCONNECTS
**The 30HXA186 units have 2 terminal blocks/non-fused disconnects 208/230 2 6
and 6 parallel conductors. 460 1 3
NOTES: 575 1 3
1. Main power must be supplied from a field-supplied fused electrical 380** 1 3
service with a (factory- or field-installed) disconnect located in sight 230 2 6
from the unit. 380/415 1 3
2. Control circuit power must be supplied from a separate source through
a field-supplied disconnect (except for 380/415-50 units). The con-
trol circuit accessory transformer may be applied to power from the
main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.

35
Electrical data —
30HXA condenserless units (cont)
COMPRESSOR ELECTRICAL DATA

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE V-Hz A1 B1
30HXA (3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
460-60 64.9 485 64.9 485
575-60 51.9 388 51.9 388
076-XL
380-60 78.7 536 78.7 536
230-50 * * * *
380/415-50 81.5 605 81.5 605
208/230-60 143.8 307 143.8 307
460-60 64.9 153 64.9 153
575-60 51.9 123 51.9 123
076-WD
380-60 78.7 169 78.7 169
230-50 134.8 305 134.8 305
380/415-50 81.5 191 81.5 191
208/230-60 * * * *
460-60 77.6 580 64.9 485
575-60 62.1 484 51.9 388
086-XL
380-60 94.0 641 78.7 536
230-50 * * * *
380/415-50 99.2 715 81.5 605
208/230-60 171.9 367 143.8 307
460-60 77.6 183 64.9 153
575-60 62.1 147 51.9 123
086-WD
380-60 94.0 203 78.7 169
230-50 163.9 361 134.8 305
380/415-50 99.2 226 81.5 191
208/230-60 * * * *
460-60 94.8 685 64.9 485
575-60 75.7 548 51.9 388
096-XL
380-60 114.7 757 78.7 536
230-50 * * * *
380/415-50 119.9 856 81.5 685
208/230-60 209.8 433 143.8 307
460-60 94.8 216 64.9 153
575-60 75.5 173 51.9 123
096-WD
380-60 114.7 239 78.7 169
230-50 198.2 432 134.8 305
380/415-50 119.9 270 81.5 191
208/230-60 * * * *
460-60 115.4 820 64.9 485
575-60 92.2 656 51.9 388
106-XL
380-60 139.7 906 78.7 536
230-50 * * * *
380/415-50 145.4 960 81.5 605
208/230-60 255.5 518 143.8 307
460-60 115.4 259 64.9 153
575-60 92.2 207 51.9 123
106-WD
380-60 139.7 286 78.7 169
230-50 240.2 485 134.8 305
380/415-50 145.4 303 81.5 191

LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

36
COMPRESSOR ELECTRICAL DATA (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE V-Hz A1 B1
30HXA (3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
460-60 115.4 820 77.6 580
575-60 92.2 656 62.1 484
116-XL
380-60 139.7 906 94.0 641
230-50 * * * *
380/415-50 145.4 960 99.2 715
208/230-60 255.5 578 171.9 367
460-60 115.4 259 77.6 183
575-60 92.2 207 62.1 147
116-WD
380-60 139.7 286 94.0 203
230-50 240.2 485 163.9 361
380/415-50 145.4 303 99.2 226
208/230-60 * * * *
460-60 115.4 820 94.8 685
575-60 92.2 656 75.7 548
126-XL
380-60 139.7 906 114.7 757
230-50 * * * *
380/415-50 145.4 960 119.9 856
208/230-60 255.5 518 209.8 447
460-60 115.4 259 94.8 216
575-60 92.2 207 75.7 173
126-WD
380-60 139.7 286 114.7 239
230-50 240.2 485 198.2 432
380/415-50 145.4 303 119.9 270
208/230-60 * * * *
460-60 140.7 920 94.8 685
575-60 112.4 736 75.7 548
136-XL
380-60 170.2 1017 114.7 757
230-50 * * * *
380/415-50 178.8 1226 119.9 856
208/230-60 311.4 581 209.8 433
460-60 140.7 291 94.8 216
575-60 112.4 233 75.7 173
136-WD
380-60 170.2 321 114.7 239
230-50 295.3 619 198.2 432
380/415-50 178.8 387 119.9 276
208/230-60 * * * *
460-60 140.7 920 115.4 820
575-60 112.4 736 92.2 656
146-XL
380-60 170.2 1017 139.7 906
230-50 * * * *
380/415-50 178.8 1226 145.4 960
208/230-60 311.4 581 255.5 518
460-60 140.7 291 115.4 259
575-60 112.4 233 92.2 207
146-WD
380-60 170.2 321 139.7 286
230-50 295.3 619 240.2 485
380/415-50 178.8 387 145.4 303

LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

37
Electrical data —
30HXA condenserless units (cont)
COMPRESSOR ELECTRICAL DATA (cont)

NAMEPLATE COMPRESSOR NUMBERS


UNIT SIZE V-Hz A1 B1
30HXA (3 Phase) RLA LRA RLA LRA
208/230-60 * * * *
460-60 157.9 1175 106.6 790
575-60 126.2 940 85.1 630
161-XL
380-60 191.2 1299 129.0 870
230-50 * * * *
380/415-50 201.2 1265 133.4 1045
208/230-60 349.6 743 235.9 527
460-60 157.9 371 106.6 263
575-60 126.2 297 85.1 211
161-WD
380-60 191.2 410 129.0 290
230-50 332.3 638 220.3 607
380/415-50 201.2 400 133.4 348
208/230-60 * * * *
460-60 129.6 920 157.9 1175
575-60 103.6 736 126.2 940
171-XL
380-60 156.9 1017 191.2 1299
230-50 * * * *
380/415-50 161.7 1226 201.2 1265
208/230-60 286.9 581 349.6 743
460-60 129.6 291 157.9 371
575-60 103.6 233 126.2 297
171-WD
380-60 156.9 321 191.2 410
230-50 267.2 619 332.3 638
380/415-50 161.7 387 201.2 400
208/230-60 * * * *
460-60 157.9 1175 157.9 1175
575-60 126.2 940 126.2 940
186-XL
380-60 191.2 1299 191.2 1299
230-50 * * * *
380/415-50 201.2 1265 201.2 1265
208/230-60 349.6 743 349.6 743
460-60 157.9 371 157.9 371
575-60 126.2 297 126.2 297
186-WD
380-60 191.2 410 191.2 410
230-50 332.3 638 332.3 638
380/415-50 201.2 400 201.2 400

LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD — Wye-Delta Start
XL — Across-the-Line Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.

38
Controls
The standard microprocessor-based control in the 30HX Start-up — The circulating pump is energized (either
units provides the following functions: externally or by the internal timeclock). The chiller starts.
• leaving fluid temperature control (using both entering and (If the flow switch is applied, the chiller starts after the flow
leaving fluid sensors) has been proven. All 30HX chillers require loss of flow pro-
• 7-day time sequence of both pump and chiller tection.) The compressor starts unloaded.
• temperature reset from return fluid (standard) or from NOTE: Which compressor starts first is determined by the
outdoor ambient (accessory), occupied space tempera- automatic lead/lag feature.
ture (accessory), 4-20 mA signal (accessory), or via the
If the entering fluid temperature is 85 F (29 C) or higher,
optional Carrier Comfort Network (CCN)
the maximum operating pressure (MOP) feature limits the
• automatic compressor lead-lag switching based on com-
suction pressure to keep the chiller on line.
pressor accumulated run times and number of cycles
• automatic temperature range across the cooler Normal operation — The entering fluid temperature
adjustment sensor monitors changes in entering fluid temperature to
• fully automatic control of the chiller components anticipate changes in the cooling load. Based on leaving
fluid temperature, the control adds or subtracts capacity to
A standard 2-line, 24-character per line display is used to maintain a constant leaving fluid temperature.
accomplish the following (see figure below): Transition to off — The chiller unloads once the ‘‘time-
• set schedules and set points to-stop’’ signal has been given. This signal can be either
• identify operating mode internal or external.
• display current temperatures and pressures being used by Safeties — The 30HX control as shipped from the fac-
the control for internal calculations tory automatically deenergizes any active compressor that
• identify abnormal (alarm or alert) conditions experiences any of the following:
An accessory 16-line, 40-character per line expanded dis- • electrical overload
play is also available (see figure below). This accessory dis- • thermal overload protection
plays the same information as the standard display, but has • high pressure
the advantage of being able to display multiple points • low oil pressure
simultaneously. • loss of refrigerant charge
• loss of phase protection
Sequence of operation • reverse rotation (control prevents compressor start)
The control has a 44 F (6.2 C) leaving fluid temperature • voltage imbalance
(LWT) set point as shipped from the factory. If temperature • ground current
reset or demand limiting is in effect, this set point may • low chilled fluid temperature
change.

STANDARD DISPLAY ACCESSORY EXPANDED DISPLAY

30HX

EXPN TEST
STAT
EDIT
1 2 3 SRVC
ALRM

SET SCHD 4 5 6 HIST ALGO

7 8 9 CLEAR

– 0 • ENTER

39
Guide specifications
Fluid-Cooled and Condenserless 2. Shall be mechanically cleanable shell-and-tube type
Liquid Chillers with removable heads.
HVAC Guide Specifications 3. Tubes shall be internally-enhanced, seamless-
copper type, and shall be rolled into tube sheets.
Size Range: 75 to 265 Tons (264 to 931 kW)
Carrier Model Number: 30HXA — Condenserless 4. Shall be equipped with weld-on fluid connections.
30HXC — Fluid Cooled 5. Shell shall be insulated with 3⁄4-in. (19-mm) closed-
Part 1 — General cell, polyvinyl-chloride foam with a maximum K
factor of 0.28.
1.01 SYSTEM DESCRIPTION
6. Shall have a cooler drain and vent.
Microprocessor controlled, fluid-cooled (30HXC) or
condenserless (30HXA) liquid chiller utilizing screw 7. Design shall incorporate 2 independent refrig-
compressors and electronic expansion valves. erant circuits.
1.02 QUALITY ASSURANCE D. Condenser (30HXC units):
A. Unit shall be rated in accordance with ARI 1. Shall be tested and stamped in accordance with
Standard 590, latest revision (U.S.A.). The 60 Hz ASME Code (U.S.A.) for a refrigerant working-
30HXC units shall be ARI certified for performance. side pressure of 220 psig (1517 kPa) and a maxi-
mum water-side pressure of 300 psig (2068 kPa).
B. Unit construction shall comply with ASHRAE 15 In Canada, maximum water-side pressure shall be
Safety Code, NEC, and ASME applicable codes 250 psig (1724 kPa), per the Canadian National
(U.S.A. codes). Registry.
C. Unit shall be manufactured at an ISO 9002 registered 2. Shall be mechanically cleanable shell-and-tube type
facility. with removable heads.
D. All 208/230 v, 460 v, 575 v, 60 Hz units shall be 3. Tubes shall be internally-enhanced, seamless-
constructed in accordance with UL or CSA standards copper type, and shall be rolled into tube sheets.
and shall be tested and listed by ETL or ETL, Canada,
as conforming to those standards. Units shall carry 4. Shall be equipped with weld-on water
the ETL and ETL, Canada, labels. connections.
1.03 DELIVERY, STORAGE, AND HANDLING 5. Design shall incorporate 2 independent refrig-
erant circuits.
A. Unit controls shall be capable of withstanding
150 F (66 C) storage temperatures in the control E. Oil Separator (30HXA Units):
compartment. 1. Shall be tested and stamped in accordance with
B. Unit shall be stored and handled per unit manufac- ASME Code (U.S.A.) for a refrigerant working-
turer’s recommendations. side pressure of 320 psig (2206 kPa).
2. Design shall incorporate 2 independent refrig-
Part 2 — Products erant circuits.
2.01 EQUIPMENT F. Refrigeration Components:
A. General: Refrigerant circuit components shall include oil sep-
Factory assembled, single-piece, fluid-cooled (30HXC) arator, high and low side pressure relief devices,
or condenserless (30HXA) liquid chiller. Contained discharge and liquid line shutoff valves, filter drier,
within the unit cabinet shall be all factory wiring, pip- moisture indicating sight glass, expansion valve, re-
ing, controls, refrigerant charge (HFC-134a), and frigerant economizer (unit sizes 161-271), and com-
special features required prior to field start-up. plete charge of compressor oil. The 30HXC units shall
have a complete operating charge of refrigerant
B. Compressors:
HFC-134a; 30HXA units shall have a holding charge
1. Semi-hermetic twin-screw compressors with inter- only.
nal muffler and check valve.
G. Controls, Safeties, and Diagnostics:
2. Each compressor shall be equipped with a dis-
1. Controls:
charge shutoff valve.
a. Unit controls shall include as a minimum:
C. Cooler:
Microprocessor, LOCAL/OFF/REMOTE
1. Shall be tested and stamped in accordance with switch, 2-line, 24-character per line diagnos-
ASME code (U.S.A.) for a refrigerant working- tic display with keypad.
side pressure of 220 psig (1517 kPa) and a maxi-
mum fluid-side pressure of 300 psig (2068 kPa).
In Canada, maximum water-side pressure shall be
250 psig (1724 kPa), per the Canadian National
Registry.

40
b. Shall be capable of performing the following J. Special Features:
functions: Certain standard features are not applicable when the
1) Automatic compressor lead/lag switching. features designated by * are specified. For assistance
2) Capacity control based on leaving chilled in amending the specifications, contact your local
fluid temperature with return fluid tem- Carrier Sales office.
perature sensing.
* 1. Wye-Delta Starter:
3) Limit the chilled fluid temperature pull-
down rate at start-up to an adjustable range Unit shall have a factory-installed, Wye-Delta
of 0.2° F to 2 F (0.1° C to 1.1° C) per starter to minimize electrical inrush current.
minute to prevent excessive demand spikes 2. Sound Reduction Enclosure:
at start-up. Unit shall have field-installed sound reduction en-
4) Seven-day time scheduling of pump(s) and closure which covers the entire unit to muffle com-
chiller(s). pressor noise.
2. Diagnostics: 3. Vibration Isolation:
a. Display module shall be capable of display- Unit shall be supplied with rubber-in-shear
ing set points, time, system status (including vibration isolators for field installation.
temperatures, pressures, and percent load-
ing), and any alarm or alert conditions. 4. Control Power Transformer:
b. Control module, in conjunction with the micro- Unit shall be supplied with a field installed trans-
processor, shall be capable of displaying the former that will supply control circuit power from
output of a run test to verify operation of ev- the main unit power supply.
ery switch, sensor, potentiometer, and com- 5. Non-Fused Disconnect:
pressor before chiller is started. Unit shall be supplied with factory-installed,
3. Safeties: non-fused electrical disconnect for main power
Unit shall be equipped with all necessary compo- supply.
nents, and in conjunction with the control system 6. Chilled Fluid Flow Switch:
shall provide the unit with protection against the Unit shall be supplied with field-installed differ-
following: ential pressure type proof-of-flow sensing switch.
a. Loss of refrigerant charge. 7. Victaulic Connection:
b. Reverse rotation. Unit shall be supplied with victaulic-type cooler
c. Low chilled fluid temperature. connections (field installed).
d. Low oil pressure. 8. Expanded Display:
e. Voltage imbalance. Unit shall be supplied with indoor-mounted, re-
f. Ground current. mote 40-character per line, 16-line display panel.
Display shall be field installed.
g. Thermal overload.
9. Temperature Reset Sensor:
h. High pressure.
Unit shall reset leaving chilled fluid temperature
i. Electrical overload. based on outdoor ambient temperature or space
j. Loss of phase. temperature when this sensor is installed.
H. Operating Characteristics: * 10. Brine Option:
Unit shall be capable of starting up with 95 F (35 C) Unit shall be factory modified to start and oper-
entering fluid temperature to the cooler. ate at leaving chilled fluid temperatures of be-
I. Electrical Requirements: tween 15 F (–9 C) and 40 F (5 C).
1. Unit primary electrical power supply shall enter * 11. Minimum Load Control:
the unit at a single location (some units have mul- Unit shall be equipped with factory (or field) in-
tiple power poles). stalled, microprocessor-controlled, minimum-load
2. Unit shall operate on 3-phase power at the volt- control that shall permit unit operation down to
age shown in the equipment schedule. 10% of full capacity.
3. Control voltage shall be 115-v (60 Hz) or 230-v 12. Flotronic™ System Manager:
(50 Hz), single-phase, separate power supply. Control shall enable management of multiple chill-
4. Unit shall be shipped with factory control and ers (up to 8) in a single system.
power wiring installed.

41
Carrier Corporation • Syracuse, New York 13221 3-97
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Page 44 Catalog No. 523-050 Printed in U.S.A. PC 903 Form 30HX-2PD
Tab 5c Replaces: 30HX-1PD

You might also like