Beckhoff Bus Terminal Controllers
Beckhoff Bus Terminal Controllers
Power LEDs
Fieldbus connection
K-bus
Bus Terminal
580
Power contacts
Address selector
Configuration
interface Input for power contacts
The Bus Terminal Controllers of the BC The main distinguishing features between The devices of the BX family have two serial
and BX series are small controllers with the BX series and the BC series are the larger interfaces. The device itself comprises an
a high degree of flexibility. The I/O system memory capacity and a larger number of illuminated LC display with 2 lines of 16 char-
consisting of modularly expandable elec- expandable interfaces. acters each, a joystick switch and a real-time
tronic terminal blocks, interfaces for all The BCxx00 Bus Terminal Controllers clock. Further peripheral devices, e.g. displays,
market-relevant fieldbus systems and the form a unit consisting of the controller, any can be connected via the integrated Beckhoff
integrated IEC 61131-3 PLC enables the number (up to 64) of terminals and a bus end Smart System Bus (SSB).
Bus Terminal Controllers to be used as terminal. In contrast to the BCxx50, BCxx20
stand-alone control systems or as intelli- and BXxx00 series, a terminal bus extension
gent fieldbus slaves. The Bus Terminal cannot be used.
Controller is programmed using the The Compact BCxx50 and BCxx20
TwinCAT programming system according Bus Terminal Controllers are fitted in cost-
to IEC 61131-3. The configuration or field- optimised, compact housings and support
bus interface of the controller is used for the K-bus extension (up to 255 Bus Termi-
Bus Terminal
loading the PLC program. nals).
581
www.beckhoff.com/Bus-Terminal-Controller
Max. number of bytes 128 byte input and 128 byte output
fieldbus
Current supply K-bus 1,750 mA 1,000 mA
+60 C
-25 C
Bus Terminal
The Bus Terminal Controller BC3100 is a Bus Coupler with The Compact BC3150 Bus Terminal Controller is housed in
582 integrated PLC functionality and has a fieldbus interface a cost-optimised and compact housing. Unlike the BC3100,
for PROFIBUS. It is an intelligent slave and can be used as the BC3150 supports up to 255 Bus Terminals via the K-bus
distributed intelligence in the PROFIBUS system. extension.
PROFIBUS Bus Terminal Controller CANopen Compact Bus Terminal CANopen Bus Terminal Controller
for up to 64 Bus Terminals Controller for up to 64 Bus Terminals for up to 64 Bus Terminals
(255 with K-bus extension), 12 Mbaud (255 with K-bus extension) (255 with K-bus extension)
244 byte input and 244 byte output 16 Tx/Rx PDOs 32 Tx/Rx PDOs
Bus Terminal
The BX3100 Bus Terminal Controller has a The Compact BC5150 Bus Terminal Controller The BX5100 Bus Terminal Controller has a
PROFIBUS slave interface with automatic baud for CANopen extends the Beckhoff small controller CANopen slave interface. It has automatic baud 583
rate detection up to 12 Mbaud and an address series by a cost-optimised version in a compact rate detection up to 1 Mbaud and an address
selection switch for address assignment. housing. selection switch for address assignment.
1 x D-sub socket, 9-pin open style connector, 5-pin open style connector, 5-pin
automatic detection up to 12 Mbaud automatic detection up to 1 Mbaud automatic detection up to 1 Mbaud
256 kbytes 48 kbytes 256 kbytes
256 kbytes 32 kbytes 256 kbytes
2 kbytes 2 kbytes 2 kbytes
yes yes yes
approx. 250 g approx. 100 g approx. 250 g
-25+60 C -25+60 C -25+60 C
CE, UL CE, UL, Ex CE, UL
www.beckhoff.com/BX3100 www.beckhoff.com/BC5150 www.beckhoff.com/BX5100
Max. number of bytes 512 byte input and 512 byte output
fieldbus
Current supply K-bus 1,000 mA 1,450 mA
+60 C +60 C
-25 C -25 C
Bus Terminal
The BC5250 Bus Terminal Controller with DeviceNet interface The BX5200 Bus Terminal Controller has a DeviceNet
584 extends the Beckhoff small controller series by a cost-opti- slave interface. It has automatic baud rate detection
mised version in a compact housing. The DeviceNet Controller up to 500 kbaud and an address selection switch
offers automatic baud rate detection up to 500 kbaud and for address assignment. Up to 512 byte of input and
two address selection switches for address assignment. 512 byte of output can be exchanged with the controller.
Bus interface open style connector, 5-pin open style connector, 5-pin
Data transfer rates automatic detection up to 500 kbaud automatic detection up to 500 kbaud
BC7300 BC8050
512 byte input and 512 byte output 512 byte input and 512 byte output
1,750 mA 1,000 mA
+60 C
-25 C
Bus Terminal
The Bus Terminal Controller BC7300 is a Bus Coupler with integrated PLC The Bus Terminal Controller BC8050 with serial RS485 interface extends the
functionality and has a fieldbus interface for Modbus. The BC7300 is an Beckhoff small controller series by a cost-optimised version in a compact 585
intelligent slave and can be used as a non-central intelligence in the Modbus housing. An open serial protocol like in the BK8x00 Bus Couplers and the
system. Modbus RTU/ASCII protocol are implemented. The address and the protocol
are selected via the two rotary selection switches.
Max. number of bytes 512 byte input and 512 byte output
fieldbus
Current supply K-bus 1,000 mA 1,450 mA
+60 C +60 C
-25 C -25 C
Bus Terminal
The Bus Terminal Controller BC8150 with serial RS232 The BX8000 Bus Terminal Controller is a stand-alone PLC.
586 interface extends the Beckhoff small controller series by One unit consists of the BX8000 Bus Terminal Controller
a cost-optimised version in a compact housing. An open with up to 64 Bus Terminals and a bus end terminal. With
serial protocol like in the BK8x00 Bus Couplers and the terminal bus extension system, the connection of up to
the Modbus RTU/ASCII protocol are implemented. 255 Bus Terminals is possible. The controller is programmed
via the COM1 interface. In addition, the BX8000 has a second
COM port, optionally RS232 or RS485. This can be used for
connecting serial devices, such as displays.
Ethernet Bus Terminal Controller Ethernet Bus Terminal Controller Ethernet TCP/IP Bus Terminal
for up to 64 Bus Terminals for up to 64 Bus Terminals Controller for up to 64 Bus Terminals
(255 with K-bus extension) (255 with K-bus extension)
+60 C +60 C
-25 C -25 C
Bus Terminal
The Bus Terminal Controller BC9000 is a Bus The BC9050 Bus Terminal Controller with Ethernet The BC9020 Bus Terminal Controller is a
Coupler with integrated PLC functionality and has interface extends the Beckhoff small controller Bus Coupler with integrated PLC functionality 587
a fieldbus interface for Ethernet. It is an intelligent series by a cost-optimised version in a compact and has a fieldbus interface for Ethernet.
slave that can be used as a non-central intelli- housing. It is an intelligent slave and can be used as
gence in the Ethernet system. One unit consists of decentralised intelligence in the Ethernet
the Bus Terminal Controller, any number of termi- system.
nals between 1 and 64, and a bus end terminal.
Ethernet TCP/IP Bus Terminal Controller Ethernet TCP/IP Bus Terminal Controller
for up to 64 Bus Terminals for up to 64 Bus Terminals
(255 with K-bus extension, (with integrated 2-channel switch)
with integrated 2-channel switch)
Max. number of bytes 512 byte input and 512 byte output
fieldbus
Current supply K-bus 1,750 mA 1,750 mA
+60 C +60 C
-25 C -25 C
Bus Terminal
In contrast to the BC9020, the BC9120 has The Bus Terminal Controller BC9100 is a
588 an additional RJ45 port. Both Ethernet ports Bus Coupler with integrated PLC functional-
operate as 2-channel switches. ity and has a fieldbus interface for Ethernet.
The BC9100 is an intelligent slave and can
be used as a non-central intelligence in the
Ethernet system.
Ethernet Bus Terminal Controller Building Automation Room Controller, Building Automation Room Controller,
for up to 64 Bus Terminals 48 kbyte, sub bus for KL6583 (EnOcean) 128 kbyte, RS485 interface
(255 with K-bus extension)
1,450 mA 200 mA
Digital inputs:
3 contacts (e.g. win-
dow contact, dew point,
occupancy sensor)
Analog inputs:
1 x PT/Ni1000; 1 x resis-
tance measurement for
set point; 3 x 010 V
Digital outputs:
1 x LED, 10 mA;
1 x 230 V AC, 10 A, relay;
3 x 230 V AC, 1 A, relay;
2 x 230 V AC, 1 A, triac
Analog outputs:
Bus Terminal
2 x 010 V
The BX9000 Bus Terminal Controller has an Ethernet The BC9191 and BC9191-0100 Ethernet Room Controllers cover the standard func-
slave/master interface. The controller has automatic tionalities for room control in a compact design. The two versions differ in terms of 589
baud rate detection up to 100 Mbaud. The address can the memory capacity of the integrated PLC and the sub bus. The BC9191 has an inte-
optionally be entered via DHCP, BootP, ARP or with grated interface to the KL6583 (EnOcean), the BC9191-0100 has an RS485 interface.
the joystick switch. Both versions have the necessary I/O signals and two switched Ethernet interfaces.
They can be extended with Bus Terminals. A parameterisable PLC program for room
temperature control is included in the delivery.