POWER PLANT AND ENVIRONMENT CHECKS

1) Check rectifier system for alarms, taking readings (42-57V).


2) Check air conditioner system working status / equipment room
temperature (5 to 70 degrees Celsius) and humidity (5-95 rh%).
3) Check power plant status as well generator physical checks (fuel ,
operational state) .

MSC HEALTH CHECKS PROCEDURE / COMMAND

1) CP state / usage DSP CPUR (should be less than 80%)


2) System clock DSP TIME
3) Signalling link / route state DSP N7LNK =>choose module numbers 135
and 136

4) M3UA , SCCP states DSP SCCPDSP,DSP M3LNK => also


modules 135 and 136
5) Routes DSP M3RT ,LST TKC ,DSP TKC ,DSP
OFTKC
6) Licence checks DSP LICENSE
7) System device state ON LMT SELECT DEVICE PANEL
8) Backup checks Check if the BamYYYYMMDD.dat and
BamMonthBak.dat files in the path F:\CSOFTX3000
9) Alarms BROWSE ALARMS ON LMT ,LOOK
FOR CRITICAL STATES

HLR HEALTH CHECKS PROCEDURE / COMMAND

1) CP state / usage DSP CPUR (get average of modules


loads)< 80%
2) System clock DSP TIME
3) Signalling link / route state LST N7LKS,DSP N7LKS => use index 1
DSP M3RT => use destination index 1 to
4
4) System device state ON LMT SELECT DEVICE PANEL
5) Redundancy state LST REDUNDANCY
6) Backup Check if the BamYYYYMMDD.dat and
BamMonthBak.dat files in the path F:\HLR9820Back
7) Alarms BROWSE ALARMS ON LMT ,LOOK
FOR CRITICAL STATES

MGW HEALTH CHECKS PROCEDURE / COMMAND

1) CP state / usage DSP CPUR (should be less than


80%)
2) System clock DSP TIME
3) Signalling link DSP M3LNK , DSP
SCTPRUN:BT=PPU,LT=H248;
DSP L2UALNK , DSP H248LNK,DSP N7DSP
4) System device state DSP BRD , LST BRD .OPEN THE
DEVICE PANEL FOR
VISUAL CHECKS
5) Service bearer and media resources DSP VMGWRSC,
DSP GWADDR:BN=0;
DSP MEDIARES
6) Performance system task state LST TSK
7) Alarms BROWSE ALARMS ON LMT ,LOOK
FOR CRITICAL STATES