0% found this document useful (0 votes)
70 views88 pages

Fire & Gas Panel PDF

Uploaded by

ben
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
70 views88 pages

Fire & Gas Panel PDF

Uploaded by

ben
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 88

Intelligent Control Panel

SLC
Wiring Manual

Document 51309
9/17/2014
P/N 51309:P4
Rev: P4
ECN 14-790
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm systemtypically made up of smoke (caused by escaping gas, improper storage of flammable materi-
detectors, heat detectors, manual pull stations, audible warning als, etc.).
devices, and a fire alarm control panel (FACP) with remote notifi- Heat detectors do not sense particles of combustion and alarm
cation capabilitycan provide early warning of a developing fire. only when heat on their sensors increases at a predetermined
Such a system, however, does not assure protection against rate or reaches a predetermined level. Rate-of-rise heat detec-
property damage or loss of life resulting from a fire. tors may be subject to reduced sensitivity over time. For this
An emergency communication systemtypically made up of reason, the rate-of-rise feature of each detector should be tested
an automatic fire alarm system (as described above) and a life at least once per year by a qualified fire protection specialist.
safety communication system that may include an autonomous Heat detectors are designed to protect property, not life.
control unit (ACU), local operating console (LOC), voice commu- IMPORTANT! Smoke detectors must be installed in the same
nication, and other various interoperable communication meth- room as the control panel and in rooms used by the system for
odscan broadcast a mass notification message. Such a the connection of alarm transmission wiring, communications,
system, however, does not assure protection against property signaling, and/or power. If detectors are not so located, a devel-
damage or loss of life resulting from a fire or life safety event. oping fire may damage the alarm system, compromising its abil-
The Manufacturer recommends that smoke and/or heat ity to report a fire.
detectors be located throughout a protected premises following Audible warning devices such as bells, horns, strobes,
the recommendations of the current edition of the National Fire speakers and displays may not alert people if these devices
Protection Association Standard 72 (NFPA 72), manufacturer's are located on the other side of closed or partly open doors or
recommendations, State and local codes, and the are located on another floor of a building. Any warning device
recommendations contained in the Guide for Proper Use of may fail to alert people with a disability or those who have
System Smoke Detectors, which is made available at no charge recently consumed drugs, alcohol, or medication. Please note
to all installing dealers. This document can be found at http:// that:
www.systemsensor.com/appguides/. A study by the Federal An emergency communication system may take priority over
Emergency Management Agency (an agency of the United a fire alarm system in the event of a life safety emergency.
States government) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm systems are Voice messaging systems must be designed to meet intelligi-
designed to provide early warning against fire, they do not bility requirements as defined by NFPA, local codes, and
guarantee warning or protection against fire. A fire alarm system Authorities Having Jurisdiction (AHJ).
may not provide timely or adequate warning, or simply may not Language and instructional requirements must be clearly dis-
function, for a variety of reasons: seminated on any local displays.
Smoke detectors may not sense fire where smoke cannot Strobes can, under certain circumstances, cause seizures in
reach the detectors such as in chimneys, in or behind walls, on people with conditions such as epilepsy.
roofs, or on the other side of closed doors. Smoke detectors Studies have shown that certain people, even when they hear
also may not sense a fire on another level or floor of a building. a fire alarm signal, do not respond to or comprehend the
A second-floor detector, for example, may not sense a first-floor meaning of the signal. Audible devices, such as horns and
or basement fire. bells, can have different tonal patterns and frequencies. It is
Particles of combustion or smoke from a developing fire the property owner's responsibility to conduct fire drills and
may not reach the sensing chambers of smoke detectors other training exercises to make people aware of fire alarm
because: signals and instruct them on the proper reaction to alarm sig-
Barriers such as closed or partially closed doors, walls, chim- nals.
neys, even wet or humid areas may inhibit particle or smoke In rare instances, the sounding of a warning device can cause
flow. temporary or permanent hearing loss.
Smoke particles may become cold, stratify, and not reach A life safety system will not operate without any electrical
the ceiling or upper walls where detectors are located. power. If AC power fails, the system will operate from standby
Smoke particles may be blown away from detectors by air batteries only for a specified time and only if the batteries have
outlets, such as air conditioning vents. been properly maintained and replaced regularly.
Smoke particles may be drawn into air returns before reach- Equipment used in the system may not be technically compat-
ing the detector. ible with the control panel. It is essential to use only equipment
listed for service with your control panel.
The amount of smoke present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at var- Telephone lines needed to transmit alarm signals from a prem-
ious levels of smoke density. If such density levels are not cre- ises to a central monitoring station may be out of service or tem-
ated by a developing fire at the location of detectors, the porarily disabled. For added protection against telephone line
detectors will not go into alarm. failure, backup radio transmission systems are recommended.
Smoke detectors, even when working properly, have sensing The most common cause of life safety system malfunction is
limitations. Detectors that have photoelectronic sensing cham- inadequate maintenance. To keep the entire life safety system in
bers tend to detect smoldering fires better than flaming fires, excellent working order, ongoing maintenance is required per the
which have little visible smoke. Detectors that have ionizing-type manufacturer's recommendations, and UL and NFPA stan-
sensing chambers tend to detect fast-flaming fires better than dards. At a minimum, the requirements of NFPA 72 shall be fol-
smoldering fires. Because fires develop in different ways and lowed. Environments with large amounts of dust, dirt, or high air
are often unpredictable in their growth, neither type of detector is velocity require more frequent maintenance. A maintenance
necessarily best and a given type of detector may not provide agreement should be arranged through the local manufacturer's
adequate warning of a fire. representative. Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be per-
Smoke detectors cannot be expected to provide adequate warn- formed by authorized professional life safety system installers
ing of fires caused by arson, children playing with matches only. Adequate written records of all inspections should be kept.
(especially in bedrooms), smoking in bed, and violent explosions Limit-D-1-2013

2 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be Like all solid state electronic devices, this system may
connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light-
sources of power before servicing. Control unit and associ- ning induced transients. Although no system is completely
ated equipment may be damaged by removing and/or insert- immune from lightning transients and interference, proper
ing cards, modules, or interconnecting cables while the unit is grounding will reduce susceptibility. Overhead or outside aerial
energized. Do not attempt to install, service, or operate this wiring is not recommended, due to an increased susceptibility
unit until manuals are read and understood. to nearby lightning strikes. Consult with the Technical Ser-
CAUTION - System Re-acceptance Test after Software vices Department if any problems are anticipated or encoun-
Changes: To ensure proper system operation, this product tered.
must be tested in accordance with NFPA 72 after any pro- Disconnect AC power and batteries prior to removing or
gramming operation or change in site-specific software. Re- inserting circuit boards. Failure to do so can damage circuits.
acceptance testing is required after any change, addition or Remove all electronic assemblies prior to any drilling, filing,
deletion of system components, or after any modification, reaming, or punching of the enclosure. When possible, make
repair or adjustment to system hardware or wiring. All compo- all cable entries from the sides or rear. Before making modifi-
nents, circuits, system operations, or software functions known cations, verify that they will not interfere with battery, trans-
to be affected by a change must be 100% tested. In addition, former, or printed circuit board location.
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected Do not tighten screw terminals more than 9 in-lbs. Over-
by the change, up to a maximum of 50 devices, must also be tightening may damage threads, resulting in reduced terminal
tested and proper system operation verified. contact pressure and difficulty with screw terminal removal.

This system meets NFPA requirements for operation at 0-49 This system contains static-sensitive components.
C/32-120 F and at a relative humidity 93% 2% RH (non- Always ground yourself with a proper wrist strap before han-
condensing) at 32C 2C (90F 3F). However, the useful dling any circuits so that static charges are removed from the
life of the system's standby batteries and the electronic com- body. Use static suppressive packaging to protect electronic
ponents may be adversely affected by extreme temperature assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this Follow the instructions in the installation, operating, and pro-
system and its peripherals be installed in an environment with gramming manuals. These instructions must be followed to
a normal room temperature of 15-27 C/60-80 F. avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation.
cating device loops. Most devices cannot tolerate more than a Precau-D1-9-2005
10% I.R. drop from the specified device voltage.

FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.

LiteSpeed is a trademark; and FireLite Alarms is a registered trademark of Honeywell International Inc. Microsoft and Windows are registered
trademarks of the Microsoft Corporation.
2014 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 3


Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a
specific application.

Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our
online Help or printed manuals, you can email us.
Please include the following information:
Product name and version number (if applicable)
Printed manual or online Help
Topic Title (for online Help)
Page number (for printed manual)
Brief description of content you think should be improved or corrected
Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.

4 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Table of Contents
Section 1: Introduction............................................................................................................. 8
1.1: Scope..............................................................................................................................................................8
1.1.1: Reference Documentation ...................................................................................................................9
1.2: Overview......................................................................................................................................................10
1.3: Polling Protocols .........................................................................................................................................10
1.3.1: Available Protocols............................................................................................................................10
1.3.2: Protocol Use ......................................................................................................................................10
1.4: Devices ........................................................................................................................................................11
1.4.1: Isolator Modules ................................................................................................................................11
1.4.2: Monitor Modules ...............................................................................................................................11
1.4.3: Control Modules ................................................................................................................................11
1.4.4: Relay Modules...................................................................................................................................11
1.4.5: Multiple Input/Output Modules.........................................................................................................11
1.4.6: Intelligent Detectors ..........................................................................................................................11
1.4.7: Manual Pull Station ...........................................................................................................................12
1.4.8: Wireless Gateway ..............................................................................................................................12
1.4.9: 300 Series Addressable Devices........................................................................................................13
1.5: SLC Capacity...............................................................................................................................................13
1.6: SLC Performance.........................................................................................................................................13
1.7: Surge Suppression........................................................................................................................................13
1.8: LED Operation.............................................................................................................................................13
Section 2: Wiring Requirements............................................................................................ 14
2.1: Wire Sizing ..................................................................................................................................................14
2.1.1: CLIP (Classic Loop Interface Protocol) Mode..................................................................................14
2.1.2: LiteSpeed Mode.................................................................................................................................14
2.2: Measuring Resistance & Length..................................................................................................................15
2.2.1: Two-Wire SLC - Style 4 (Class B)....................................................................................................15
2.2.2: Four-Wire SLC Style 6 & 7 (Class A) ..............................................................................................16
2.3: Shield Wire Termination..............................................................................................................................17
2.4: Control Panel Terminal Blocks....................................................................................................................18
2.4.1: MS-9200 ............................................................................................................................................18
2.4.2: MS-9600, MS-9600LS, & MS-9600UDLS.......................................................................................18
2.4.3: MS-9200UDLS (Software Version 3.0)............................................................................................19
2.4.4: MS-9200UD & MS-9200UDLS (Versions 1 and 2) .........................................................................19
2.4.5: MS-9050UD ......................................................................................................................................20
Section 3: SLC Circuits without Isolators ............................................................................ 21
3.1: Overview......................................................................................................................................................21
3.2: NFPA Style 4 SLC .......................................................................................................................................21
3.3: NFPA Style 6 SLC .......................................................................................................................................22
Section 4: SLC Circuits with Isolators .................................................................................. 23
4.1: Fault Isolator Devices ..................................................................................................................................23
4.1.1: Isolating an SLC Branch....................................................................................................................23
4.1.2: Wiring an Isolator Module ................................................................................................................24
4.2: NFPA Style 4 SLC Using Isolator Modules ................................................................................................25
4.3: NFPA Style 6 SLC Using Isolator Modules ................................................................................................27
4.4: NFPA Style 7 SLC Using Isolator Modules ................................................................................................28
Section 5: Monitor Modules ................................................................................................... 29
5.1: Descriptions .................................................................................................................................................29
5.1.1: Addressable Monitor Modules ..........................................................................................................29
5.1.2: Zone Interface Modules.....................................................................................................................31
5.1.3: Dual Monitor Module........................................................................................................................33

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 5


Table of Contents

5.1.4: Mini Monitor Module ........................................................................................................................33


5.2: Installation....................................................................................................................................................33
5.2.1: Setting an SLC address for a Single Point Module ...........................................................................34
5.2.2: Setting an SLC address for a Multi-Point Module ............................................................................35
5.3: MMF-300 Wiring Diagrams ........................................................................................................................36
5.3.1: Wiring a NFPA Style B IDC with an MMF-300...............................................................................36
5.3.2: Wiring a NFPA Style D IDC with an MMF-300 ..............................................................................37
5.3.3: MMF-300 Wiring for Emergency Alarm System Applications ........................................................38
5.4: MMF-300-10 Wiring Diagrams...................................................................................................................39
5.4.1: Wiring a NFPA Style B IDC with an MMF-300-10 .........................................................................39
5.4.2: Wiring a NFPA Style D IDC with an MMF-300-10 .........................................................................40
5.5: MDF-300 Wiring Diagrams.........................................................................................................................41
5.5.1: Wiring a NFPA Style B IDC with an MDF-300 ...............................................................................41
5.6: MMF-302 Wiring Diagrams ........................................................................................................................42
5.6.1: Wiring a NFPA Style B IDC with an MMF-302...............................................................................42
5.6.2: Wiring a NFPA Style D IDC with an MMF-302 ..............................................................................43
5.7: MMF-302-6 Wiring Diagrams.....................................................................................................................44
5.7.1: Wiring a NFPA Style B IDC with an MMF-302-6 ...........................................................................44
5.7.2: Wiring a NFPA Style D IDC with an MMF-302-6 ...........................................................................45
Section 6: Control Modules ................................................................................................... 46
6.1: Description ...................................................................................................................................................46
6.2: CMF-300 Installation...................................................................................................................................46
6.2.1: Setting an SLC address for a CMF-300 Module ...............................................................................46
6.2.2: Wiring a Notification Appliance Circuit (NAC) with a CMF-300....................................................46
6.3: Wiring a CMF-300 Module .........................................................................................................................47
6.3.1: Wiring a Style Y NAC (Two-Wire) with Addressable Control Modules .........................................47
6.3.2: Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules .........................................48
6.4: CMF-300-6 Installation ...............................................................................................................................48
6.4.1: Cabinet Installation ............................................................................................................................48
6.4.2: Setting an SLC address for an CMF-300-6 Module ..........................................................................48
6.4.3: Setting NACs as Style Y or Style Z...................................................................................................49
6.4.4: Disabling Unused Module Addresses................................................................................................49
6.4.5: Short Circuit Protection .....................................................................................................................49
6.4.6: Features Not Supported .....................................................................................................................50
6.4.7: Circuit Board Information .................................................................................................................50
6.5: Wiring a CMF-300-6 Module ......................................................................................................................51
6.5.1: Wiring a Style Y NAC (Two-Wire) .................................................................................................51
6.5.2: Wiring a Style Z NAC (Four-Wire)...................................................................................................52
Section 7: Relay Modules ...................................................................................................... 53
7.1: Description ...................................................................................................................................................53
7.2: CRF-300 Installation & Wiring ...................................................................................................................53
7.2.1: Setting an SLC address for a CRF-300 Module ................................................................................53
7.2.2: Wiring a CRF-300 Module (Form-C Relay) ....................................................................................53
7.3: CRF-300-6 Circuit Board Information ........................................................................................................54
7.4: CRF-300-6 Installation & Wiring ................................................................................................................54
7.4.1: Cabinet Installation ............................................................................................................................54
7.4.2: Setting an SLC address for a CRF-300-6 Module.............................................................................55
7.4.3: Disabling Unused Module Addresses................................................................................................55
7.4.4: Wiring a CRF-300-6 Module (Form-C Relay) ..................................................................................55
Section 8: Multiple Input/Output Modules............................................................................ 57
8.1: Description ...................................................................................................................................................57
8.2: CDRM-300 Installation & Wiring ...............................................................................................................57
8.2.1: Setting an SLC address for a CDRM-300 Module ............................................................................57
8.2.2: Wiring a CDRM-300 Module (Form-C Relay) ................................................................................58

6 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Table of Contents

Section 9: Intelligent Detector Bases and Wireless Gateway............................................. 59


9.1: Description...................................................................................................................................................59
9.2: Setting the Detector Address .......................................................................................................................59
9.3: Wiring a Detector Base................................................................................................................................60
9.4: Wiring an Isolator Base ...............................................................................................................................61
9.5: Wiring a Relay Base ....................................................................................................................................61
9.6: Wiring a Sounder Base ................................................................................................................................62
9.7: Wiring the W-GATE ....................................................................................................................................62
9.7.1: SLC Connections...............................................................................................................................62
9.7.2: W-GATE Powered by the SLC .........................................................................................................63
9.7.3: W-GATE Powered by a Regulated, External +24VDC Power Source.............................................64
Section 10: Addressable Beam Detectors............................................................................ 65
10.1: Description.................................................................................................................................................65
10.2: Installation and Wiring ..............................................................................................................................65
10.2.1: Setting an SLC Address for a Beam Detector .................................................................................65
10.2.2: Wiring a Beam Detector ..................................................................................................................66
Section 11: Addressable Manual Pull Station ...................................................................... 67
11.1: Description.................................................................................................................................................67
11.2: Installation..................................................................................................................................................67
11.2.1: Setting an SLC address....................................................................................................................67
11.2.2: Wiring a Manual Pull Station ..........................................................................................................67
Appendix A: Power Considerations...................................................................................... 68
A.1: Supplying Power to 24 VDC Detectors and NACs ....................................................................................68
A.1.1: Resistance and Size...........................................................................................................................68
A.2: Supervising 24 VDC Power........................................................................................................................69
Appendix B: Surge Suppression........................................................................................... 71
B.1: Introduction .................................................................................................................................................71
B.2: Installation...................................................................................................................................................71
B.2.1: Wiring Diagram for MS-9200 ..........................................................................................................72
B.2.2: Wiring Diagram for MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, and
MS-9050UD ................................................................................................................................................73
Appendix C: Terminal Conversion Charts for New & Legacy Devices.............................. 74
C.1: CRF-300......................................................................................................................................................74
C.2: CMF-300 and MMF-302 ............................................................................................................................75
C.3: MMF-300 ....................................................................................................................................................76
C.4: MDF-300.....................................................................................................................................................77
Appendix D: Intelligent Detector Base Layouts for Legacy Devices ................................. 78
D.1: B350LP or B501 Detector Base..................................................................................................................78
D.2: B224BI Isolator Base.................................................................................................................................79
D.3: B224RB Relay Base ...................................................................................................................................79
D.4: B501BH(-2) and B501BHT(-2) Sounder Bases .........................................................................................80
Appendix E: Canadian Versions of SLC Devices ................................................................ 82
Index......................................................................................................................................... 84

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 7


Section 1: Introduction
1.1 Scope
This document describes the operation, installation and wiring of various Signaling Line Circuit
(SLC) devices when used with the Fire-Lite MS-9200/MS-9200E, MS-9600/MS-9600E, MS-
9600LS/MS-9600LSC/MS-9600LSE, MS-9600UDLS/MS-9600UDLSE, MS-9200UD/MS-
9200UDE, MS-9200UDLS/MS-9200UDLSE/MS-9200UDLSC, and MS-9050UD/MS-
9050UDC/MS-9050UDE control panels. It also provides basic information that applies to FireLite
SLC loops in general, such as the branch resistance measurements.

NOTE: Any reference in this manual to the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600,
MS-9600LS, MS-9600UDLS, or MS-9050UD includes the MS-9200E, MS-9200UDE,
MS-9200UDLSE, MS-9200UDLSC, MS-9600E, MS-9600LSE, MS-9600LSC, MS-9600UDLSE,
MS-9050UDC, or MS-9050UDE respectively unless otherwise specified.

Additional information about the specific control panel and the modules and detectors referenced in
this document can be found in the respective installation manual as listed in Table 1.1, Reference
Documentation.
Currently, there are two styles of modules available, legacy version and newer version. The obvious
difference between the two styles is the orientation of the rotary dials. Refer to the diagram below
for an example of each.

CMF-300 CMF-300
Legacy Version Module Newer Version Module
(Vertical Rotary Dial) (Horizontal Rotary Dial)

NOTE: Only the MMF-300, MMF-302, CRF-300, CMF-300, and MDF-300 modules are available
as newer type modules. Both the legacy and newer versions share the same part numbers. The
newer version modules will be phased in, replacing the legacy version. This manual contains
information and wiring diagrams for the newer version of the modules. Refer to Terminal
Conversion Charts for New & Legacy Devices on page 74 for additional information.

8 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Scope Introduction

Currently, there are two styles of detector bases available, legacy version and newer version. The
obvious difference between the two styles is the orientation of the screw terminals. Refer to
Section 9 and Appendix D for an illustration of each.

NOTE: Only the B501 Detector Base, B210LP Detector Base (replacement base for B350LP),
B224RB Relay Base, and B224BI Isolator Base are available as newer type bases. Both the
legacy and newer versions share the same part numbers. The newer version bases will be
phased in, replacing the legacy version. This manual contains information and wiring diagrams for
the newer version of the bases. Refer to Intelligent Detector Base Layouts for Legacy Devices
on page 78 for additional information.

1.1.1 Reference Documentation


The table below accommodates a list of document sources containing additional information
regarding the devices used on a Signaling Line Circuit:

For information on... Refer to... Part Number


MS-9200/MS-9200E Instruction Manual 51003
MS-9600/MS-9600E Instruction Manual 51335
MS-9200UD/MS-9200UDE Instruction Manual 51906
MS-9200UDLS/MS-9200UDLSE/MS-9200UDLSC Instruction Manual 52750
MS-9600LS/MS-9600LS(C/E) & MS-9600UDLS/MS9600UDLSE Instruction Manual 52646
MS-9050UD/MS-9050UDC/MS-9050UDE Instruction Manual 52413
Compatible Devices Device Compatibility Document 15384
Wireless Sensor Network Instruction Manual LS10036-000FL-E
BG-12LX Pull Station Installation Instructions I56-3655
MMF-300 Monitor Module Installation Instructions I56-1191 / I56-3653
MMF-300-10 Monitor Module Installation Instructions I56-1873
MMF-301 Mini Monitor Module Installation Instructions I56-1193 / I56-3654
MMF-302 Monitor Module Installation Instructions I56-1192 / I56-3652
MMF-302-6 Interface Module Installation Instructions I56-1900
MDF-300 Dual Monitor Module Installation Instructions I56-0013 / I56-3665
CMF-300 Control Module Installation Instructions I56-1189 / I56-3650
CMF-300-6 Control Module Installation Instructions I56-1874
CRF-300 Relay Module Installation Instructions I56-1190 / I56-3651
CRF-300-6 Relay Module Installation Instructions I56-1875
CDRM-300 Multiple Input/Output Module Installation Instructions I56-3726
I300 Isolator Module Installation Instructions I56-1381
ISO-6 Isolator Module Installation Instructions I56-4096
AD350 Multicriteria Detector Installation Instructions F300-17-00
AD355 Multicriteria Detector Installation Instructions I56-3660
SD350 & SD350T Photo Detector Installation Instructions I56-0035
SD355 & SD355T Photo Detector Installation Instructions I56-3660
CP350 Ionization Detector Installation Instructions I56-0036
CP355 Ionization Detector Installation Instructions I56-3656
H350 Heat Detector Installation Instructions I56-0038
H350R Heat Detector w/ROR Installation Instructions I56-0037
H355 Heat Detector (135) Installation Instructions I56-3657
H355R Heat Detector w/ROR Installation Instructions I56-3657
H355HT Heat Detector (190) Installation Instructions I56-3657
D350P Duct Detector Installation Instructions F300-10-00
D350PL(A) Duct Detector - low flow Installation Instructions I56-1975

Table 1.1 Reference Documentation

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 9


Introduction Overview

For information on... Refer to... Part Number


D350RP Duct Detector w/Relay Installation Instructions I56-0047
D350RPL(A) Duct Detector w/Relay - low flow Installation Instructions I56-1974
D355PL Duct Detector - low flow Installation Instructions I56-3255
BEAM355(S) Addressable Beam Detector Installation Instructions I56-2425
B210LP Plug-in Detector Base Installation Instructions I56-3739
B501 Detector Base Installation Instructions I56-0357 / I56-3738
B501BH Sounder Detector Base Installation Instructions I56-0491
B501BH-2 Sounder Detector Base Installation Instructions I56-2813
B501BHT Temporal Sounder Detector Base Installation Instructions I56-1367
B501BHT-2 Temporal Sounder Detector Base Installation Instructions I56-2819
B200SR Sounder Detector Base Installation Instructions I56-3387
B200SR-LF Low Frequency Sounder Detector Base Installation Instructions I56-4152
B224RB Relay Detector Base Installation Instructions I56-2815 / I56-3737
B224BI Isolator Detector Base Installation Instructions I56-0725 / I56-3736

Table 1.1 Reference Documentation

1.2 Overview
Communication between the control panel and intelligent addressable monitor and control devices
takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of
NFPA Style 4, Style 6, or Style 7.
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC
wiring runs outside the building. For detailed information refer to Surge Suppression on page 71.

1.3 Polling Protocols


The MS-9200UDLS, MS-9600LS, and MS-9600UDLS support LiteSpeed protocol or Classic
Loop Interface Protocol (CLIP). The MS-9200/E, MS-9600/E, MS-9200UD/E, and MS-9050UD
support Classic Loop Interface Protocol (CLIP) only.

1.3.1 Available Protocols


LiteSpeed is a communication protocol that greatly enhances the speed of communication between
analog intelligent devices. Only the MS-9200UDLS, MS-9600LS, and MS-9600UDLS are capable
of operating in LiteSpeed mode. This is the default mode of operation for these FACPs.
CLIP (Classic Loop Interface Protocol) polls devices in sequential order. All Fire-LiteFireWarden
addressable fire alarm control panels can operate in CLIP mode. This is the default mode of
operation for all other FACPs.

1.3.2 Protocol Use


Use one of the following options with LiteSpeed/CLIP mode:
1. Program all modules and detectors on an FACP as LiteSpeed.
2. Program all modules and detectors on an FACP as CLIP.

NOTE: FACPs with more than one SLC loop must be programmed for only LiteSpeed or CLIP
mode of operation. Communication protocols cannot be split between SLC loops.

When switching between polling protocols, the loop circuit must be powered down for at least 30
seconds to reset the devices.

10 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Devices Introduction

1.4 Devices
1.4.1 Isolator Modules
Isolator Modules permit a zone of detectors and modules to be fault isolated from the remainder of
the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator
modules are required to meet the requirements of an NFPA Style 7 circuit.
I300 - Single fault isolator module
ISO-6 - Six fault isolator module

1.4.2 Monitor Modules


Addressable modules that allow the control panel to monitor entire circuits of conventional alarm
initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and
supervisory devices.
MMF-300 - Monitors a Style B (Class B) or Style D (Class A) circuit of dry-contact input devises.
MMF-300-10 - Monitors ten (10) Style B (Class B) or five (5) Style D (Class A) normally open
contact device circuits.
MMF-301 - Same as the MMF-300 except offered in a smaller package for mounting with Style B
wired devices. This module does not have an LED.
MMF-302 - Monitors a single IDC of two-wire smoke detectors.
MMF-302-6 - An addressable module that provides an interface between the control panel and six
(6) Style B (Class B) or three (3) Style D (Class A) IDCs of two-wire smoke detectors.
MDF-300 - Similar to MMF-300, but provides for two independent Style B IDCs.

1.4.3 Control Modules


Through the CMF-300 addressable control module, the control panel can selectively activate a
Notification Appliance Circuit (NAC).
CMF-300-6 - Similar in operation to the CMF-300, except it can activate six (6) Style Y (Class B)
or three (3) Style Z (Class A) NACs.

1.4.4 Relay Modules


The CRF-300 addressable relay module provides the control panel with a dry-contact output for
activating a variety of auxiliary devices.
CRF-300-6 - Similar in operation to the CRF-300, except it provides six (6) Form-C relays.

1.4.5 Multiple Input/Output Modules


The CDRM-300 addressable multiple input/output module monitors two (2) Style B input devices
and provides two (2) independent Form-C relay contacts.

1.4.6 Intelligent Detectors


AD350 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135F
(57.2C) fixed temperature heat detection. The sensor uses addressable communication to transmit
smoke density and other information to the control panel. It adjusts its detection parameters and
alarm threshold depending on the ambient conditions it samples in its environment.
AD355 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135F
(57.2C) fixed temperature heat detection. The sensor uses addressable communication to transmit
smoke density and other information to the control panel. It adjusts its detection parameters and
alarm threshold depending on the ambient conditions it samples in its environment.

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 11


Introduction Devices

CP350 - An addressable ionization smoke detector which measures the level of combustion
products in its chamber using the ionization principle.
CP355 - An addressable ionization smoke detector which measures the level of combustion
products in its chamber using the ionization principle.
D350P - An addressable photoelectric duct detector. The D350RP includes an alarm relay. Air
velocity rating is 500 to 4,000 feet per minute.
D350PL -An addressable low flow photoelectric duct detector (D350PLA for Canada). The
D350RPL includes an alarm relay (D350RPLA for Canada). Low Flow refers to the air velocity
rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec).
D355PL - An addressable non-relay photoelectric low flow smoke detector. Low Flow refers to
the air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec).
H3501 - An addressable detector using a thermistor sensing circuit for fast response. H350R
incorporates a thermal rate of rise of 15F (9.4C)/minute.
H3551 - An addressable 135 fixed temperature heat detector using a thermistor sensing circuit for
fast response. H355R incorporates a thermal rate of rise of 15 F (9.4 C)/minute.
H355HT1 - An addressable 190 fixed temperature heat detector using a thermistor sensing circuit
for fast response.
SD350 - An addressable photoelectric smoke detector which provides smoke sensing utilizing
optical sense technology. The SD350T includes a 135 F fixed thermal sensor.
SD355 - An addressable photoelectric smoke detector which provides smoke sensing utilizing
optical sense technology. The SD355T includes a 135 F fixed thermal sensor. The SD355R is a
low profile, intelligent, photoelectric sensor that is remote test capable.
BEAM355 - An addressable long range projected beam smoke detector designed to provide open
area protection. The BEAM355S has an integral sensitivity test feature that consists of a test filter
attached to a servomotor inside the detector optics.
DNR(W) - Innovair Flex, intelligent, non-relay, low flow, photoelectric duct detector housing.
This requires the SD355R photoelectric smoke detector. Accomodates the installation of the CRF-
300 relay module. The DNRW is a watertight housing.

1.4.7 Manual Pull Station


The BG-12LX is a dual-action pull station that, when activated, provides an addressable
identification and its location to the control panel. An addressable monitor module is mounted
inside the pull station to facilitate servicing and replacement.

1.4.8 Wireless Gateway


W-GATE: The Wireless Gateway acts as a bridge between a group of wireless fire devices and a
LiteSpeed SLC loop on the MS-9200UDLS. It is powered by the SLC loop or by a regulated,
external 24VDC UL listed power supply. Available wireless devices include a photo detector, a
photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitor
module. For details about wireless devices, system setup, and operation, see the SWIFT Smart
Wireless Integrated Fire Technology Instruction Manual.

NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the
Federal Communications Commission (FCC) requirements of the United States Government. It
has not been evaluated for use outside the USA. Use of this system outside the USA is subject to
local laws and rules to which this product may not conform. It is the sole responsibility of the user
to determine if this product may be legally used outside the USA.

1. Addressable Heat Detectors are not compatible with the MS-9200(E).

12 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


SLC Capacity Introduction

1.4.9 300 Series Addressable Devices


FireLites 300 Series of addressable devices are fully compatible with the MS-9200, MS-9200UD,
MS-9200UDLS, MS-9600, MS-9600LS(C/E), MS-9600UDLS/E, and MS-9050UD FACPs. The
devices must be configured for CLIP (Classic Loop Interface Protocol) Mode operation. The
address of 300 series devices cannot be set above 99. Compatible devices include:
SD300 Photo M300 Monitor Module
SD300T Photo w/Thermal M301 Mini Monitor Module
CP300 Ionization M302 2-wire Monitor Module
BG-10LX Pull Station C304 Control/Relay Module

1.5 SLC Capacity


The protocol selected for an SLC loop determines the maximum number of devices that can be
handled by the loop. See Section 1.3, Polling Protocols, on page 10. Within those limits, the
individual control panel may have additional restrictions. See the specific installation manual for
this information.

1.6 SLC Performance


SLC performance depends on the type of circuit (Style 4, Style 6, or Style 7) and the components
on the circuit.

NOTE: SLC operation meeting Style 7 requirements isolates each device on the SLC from faults
that may occur within other areas of the SLC.

Wiring style requirements are determined by national and local codes. Consult with the Authority
Having Jurisdiction before wiring the SLC. The table below (derived from NFPA 72-1999) lists
the trouble conditions that result when a fault exists on an SLC.
Type of Fault Style 4 Style 6 Style 7
Single Open Trouble Alarm, Trouble Alarm, Trouble
Single Ground Alarm, Trouble (ground) Alarm, Trouble (ground) Alarm, Trouble (ground)
Short Trouble Trouble Alarm, Trouble
Short and open Trouble Trouble Trouble
Short and ground Trouble Trouble Alarm, Trouble
Open and ground Trouble Alarm, Trouble Alarm, Trouble
Communications loss Trouble Trouble Trouble
Trouble - The control panel will indicate a trouble condition for this type of fault.
Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.

Table 1.2 SLC Performance

1.7 Surge Suppression


One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs
outside the building. For detailed information refer to Surge Suppression on page 71.

1.8 LED Operation


The table below lists the LED operation on the various devices on an SLC.
Device Standby Activated

Monitor Module Blinks RED Steady RED


Control Module Blinks GREEN Steady GREEN
Detector Blinks RED Steady RED

Table 1.3 LED Operation

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 13


Section 2: Wiring Requirements
2.1 Wire Sizing
The SLC requires use of a specific wire type, depending on the mode of operation, to ensure proper
circuit functioning. Wire size should be no smaller than 18 AWG (0.75 mm2) and no larger than 12
AWG (3.25 mm2) wire. The wire size depends on the length of the SLC circuit. It is recommended
that all SLC wiring be twisted-pair to minimize the effects of electrical interference.

2.1.1 CLIP (Classic Loop Interface Protocol) Mode


All addressable FACPs can operate in CLIP (Classic Loop Interface Protocol) mode. It is
recommended that all SLC wiring be twisted-pair and shielded when operating in CLIP mode to reduce
the effects of electrical interference. Use the table below to determine the specific wiring requirements
for the SLC.

Wire Requirements Distance in Feet (meters) Wire Size Wire Type

10,000 feet (3,048 m) 12 AWG (3.1 mm2) Belden 9583, Genesis 4410,
Signal 98230, WPW D999
8,000 feet (2,438 m) 14 AWG (2.0 mm2) Belden 9581, Genesis 4408,
Signal 98430, WPW D995

Twisted-pair, shielded 4,875 feet (1,486 m) 16 AWG (1.3 mm2) Belden 9575, Genesis 4406, &
4606, Signal 98630, WPW
D991
3,225 feet (983 m) 18 AWG (0.75 mm2) Belden 9574, Genesis 4402 &
4602, Signal 98300, WPW
D975
MS-9200 = 1,000 feet (305 m)

Untwisted, unshielded MS-9600, MS-9600LS(C) &


wire, inside conduit or MS-9600UDLS = 3,000 feet (914 m) 12 to 18 AWG
not in conduit MS-9200UD & MS-9200UDLS = 3,000 feet (914
m)

MS-9050UD = 3,000 feet (914 m)

Table 2.1 SLC Wiring Requirements in CLIP Mode

2.1.2 LiteSpeed Mode


The MS-9200UDLS, MS-9600LS, and MS-9600UDLS SLC can be programmed to operate in
LiteSpeed mode for a quicker device response time. While shielded wire is not required, it is
recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference.
Use the following table to determine the specific wiring requirements for the SLC.
Wire Requirements Distance in Feet (meters) Wire Size Wire Type
10,000 feet (3,048 m) 12 AWG (3.1 mm2) Belden 5020UL & 6020UL,
Genesis WG-4315 & WG-4515
8,000 feet (2,438 m) 14 AWG (2.0 mm2) Belden 5120UL & 6120UL,
Twisted-pair, Genesis WG-4313 & WG-4513
unshielded 4,875 feet (1,486 m) 16 AWG (1.3 mm2) Belden 5220UL & 6220UL,
Genesis WG-4311 & WG-4511
3,225 feet (983 m) 18 AWG (0.75 mm2) Belden 5320UL & 6320UL,
Genesis WG-4306 & WG-4506

Table 2.2 SLC Wiring Requirements in LiteSpeed Mode

14 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Measuring Resistance & Length Wiring Requirements

2.2 Measuring Resistance & Length


2.2.1 Two-Wire SLC - Style 4 (Class B)
Loop Resistance
T-tapping of the SLC wiring is permitted for 2-wire Style 4 configurations. The total DC resistance
from the control panel to each branch end cannot exceed 40 ohms. Measure DC resistance as
detailed and shown below:
1. With power removed, short the termination point of one branch at a time and measure the DC
resistance from the beginning of the SLC to the end of that particular branch.
2. Repeat this procedure for all remaining branches in the SLC.

Short Point

SLC Out

SLC-meas1.wmf
Branch

Figure 2.1 Measuring DC Resistance of a Two-Wire SLC

Total Wire Length


The total wire length of all combined branches of one SLC cannot exceed the limits set forth in
each systems instruction manual. Determine the total length in each SLC by summing the wire
lengths of all branches of one SLC.
In the following figure, the total length of the SLC is determined by adding the lengths of Branch A
plus Branch B plus Branch C.

Branch A Branch B Branch C

SLC-meas2.wmf

SLC Terminal
Block

Figure 2.2 Measuring the Total Wire Length - Two-Wire SLC

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 15


Wiring Requirements Measuring Resistance & Length

2.2.2 Four-Wire SLC Style 6 & 7 (Class A)


Loop Resistance
The total DC resistance of the SLC pair cannot exceed 40 ohms. Measure DC resistance as detailed
and shown below.
1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.
2. Short the two leads of SLC channel A (Return).
3. Measure the resistance across the SLC channel B (Out) leads.

SLC Out

SLC-meas3.wmf
Short Point

SLC Return

Figure 2.3 Measuring DC Resistance of a Four-Wire SLC

Total Wire Length


The total wire length in a four-wire SLC cannot exceed the limits set forth in each systems
instruction manual. The figure below identifies the output and return loops from SLC terminal on
the control panel:

SLC channel B SLC channel A


(output loop) (return loop) SLC-meas4.wmf

SLC Terminal
Block B+ B A A+

Figure 2.4 Measuring the Wire Length Four-Wire SLC

16 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Shield Wire Termination Wiring Requirements

2.3 Shield Wire Termination


The drawing below shows the method of proper termination of the shield.
Connect the metal conduit to the cabinet by using the proper connector. Feed the shielded wire
through the conduit, into the control box. The shield drain wire must be connected to the shield
terminal on the SLC terminal block.

NOTE: Use of good wiring practice consistent with local electrical codes is expected.

CAUTION: DO NOT LET THE SHIELD DRAIN WIRE OR THE SHIELD FOIL TOUCH THE
! SYSTEM CABINET OR BE CONNECTED TO EARTH GROUND AT ANY POINT.

MS-9600
MS-9600LS
MS-9600UDLS
MS-9200UD
MS-9200UDLS
MS-9050UD MS-9200
Shield Drain Wire
Cabinet

SLC-shieldterm.wmf
Shield Foil

Conduit

Figure 2.5 Shield Termination

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 17


Wiring Requirements Control Panel Terminal Blocks

2.4 Control Panel Terminal Blocks


The terminal blocks on the control panel circuit board that concern the SLC circuit are described
below. For more information on this subject refer to the control panels Instruction Manual.

2.4.1 MS-9200
TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable.
TB6 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
Unregulated Power
Nonresettable Power
Resettable Power
Connections for wire shield

SLC-9200tb.wmf
SHIELD SLC SLC
TB4

TB6
SLC
Return
SLC Out

Figure 2.6 MS-9200 Terminal Blocks

2.4.2 MS-9600, MS-9600LS, & MS-9600UDLS


TB3 provides two types of 24 VDC power; Nonresettable and Resettable.
TB8 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules) while operating in CLIP mode.
318 addresses are available per loop (159 detectors and 159 modules) while operating in LiteSpeed
mode.
Resettable Power
Nonresettable Connections for
Power wire shield
SLC SLC SLC SLC SHIELD
SLC-9600tb.wmf

TB3 TB8

SLC Return
SLC Out

Figure 2.7 MS-9600 Series Terminal Blocks

18 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Control Panel Terminal Blocks Wiring Requirements

2.4.3 MS-9200UDLS (Software Version 3.0)


TB1 provides two types of 24 VDC power; Nonresettable and Resettable, jumper selectable by JP4
and JP6.
TB10 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
Nonresettable Power- jumper selectable by JP4
Resettable Power- Connections for
jumper selectable by JP6 wire shield

SLC

SLC-9200udtb.wmf
TB1

TB10

SLC Return
SLC Out

Figure 2.8 MS-9200UDLS (Rev 3) Terminal Blocks

2.4.4 MS-9200UD & MS-9200UDLS (Versions 1 and 2)


TB1 provides two types of 24 VDC power; Nonresettable and Resettable.
TB10 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
Nonresettable Power
Resettable Connections for
Power wire shield

SLC

SLC-9200udtb.wmf
TB1

TB10

SLC Return
SLC Out

Figure 2.9 MS-9200UD & MS-9200UDLS (Rev 1 & 2) Terminal Blocks

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 19


Wiring Requirements Control Panel Terminal Blocks

2.4.5 MS-9050UD
24 VDC power may be supplied by a remote power supply such as the Fire-Lite FCPS-24FS6/8.
TB2 provides connections for the SLC wiring.
50 addresses are available (any combination of detectors and modules).

Connections for wire shield

SLC-9050udtb.wmf
SLC Return
SLC Out

Figure 2.10 MS-9050UD Terminal Block

20 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Section 3: SLC Circuits without Isolators

3.1 Overview
This chapter concerns itself with the two styles of circuits that do not require isolation devices:
NFPA Style 4
NFPA Style 6

3.2 NFPA Style 4 SLC


NFPA Style 4 requirements can be met by using the diagram below.
T-tapping of the SLC wiring is allowed for Style 4 configuration.

Two-wire Addressable Detector

Addressable Module

T-tapped Circuits

B+ B
SLC-style4.wmf

Control Panel
SLC

Figure 3.1 Basic NFPA Style 4 SLC

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 21


SLC Circuits without Isolators NFPA Style 6 SLC

3.3 NFPA Style 6 SLC


NFPA Style 6 requirements can be met by using the diagram below.
T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.

Two-wire Addressable Detector

SLC Out

Addressable Module

SLC Return

SLC-style6.cdrwmf
B+ B A A+
Control Panel
SLC

Figure 3.2 Basic NFPA Style 6 SLC

22 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Section 4: SLC Circuits with Isolators

4.1 Fault Isolator Devices


There are three isolator devices used to protect critical elements of the SLC from faults on other
SLC branches or segments.
Fault Isolator Module I300
Six Fault Isolator Module ISO-6
Isolator Detector Base B224BI
A Fault Isolator Module on both sides of a device, or the combination of Isolator Base and Isolator
Module is required to comply with NFPA Style 7 requirements.

CAUTION: MAXIMUM ADDRESSABLE DEVICES


!
If relay or sounder bases are not used, a maximum of 25 addressable devices can be
connected between Isolator Modules and/or Bases. When relay or sounder bases are used,
the maximum number of addressable devices that can be connected between Isolators is
reduced to seven. Isolator modules will not function properly when these limits are exceeded.
When more than 100 Isolator Modules are connected to an SLC loop, the address capacity
of the loop is reduced by two (2) addresses for every isolator device in excess of 100.

4.1.1 Isolating an SLC Branch


The module continuously monitors the circuit connected to terminals 3() and 4(+). Upon power-
up, an integral relay is latched on. The module periodically pulses the coil of this relay. A short cir-
cuit on the SLC resets the relay. The module detects the short and disconnects the faulted SLC
branch or segment by opening the positive side of the SLC (terminal 4). This isolates the faulty
branch from the remainder of the loop preventing a communication problem with all other address-
able devices on the remaining branches (labeled Continuation of the SLC in the figure below).
During a fault condition, the control panel registers a trouble condition for each addressable device
which is isolated on the SLC segment or branch. Once the fault is removed, the module automati-
cally reapplies power to the SLC branch or segment.

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 23


SLC Circuits with Isolators Fault Isolator Devices

4.1.2 Wiring an Isolator Module


The figure below shows typical wiring of an I300Isolator Module:
Continuation
of the SLC

IN (-)
IN (+)
OUT (-)
OUT (+)

SLC-isowire2.wmf
SLC
Isolated branch
of the SLC

Figure 4.1 Wiring an I300 Module

The figure below shows typical wiring of an ISO-6 Isolator Module:


status indicators
SLC in from FACP
or previous device
ISOLATOR 6
ISOLATOR 5
ISOLATOR 4
ISOLATOR 3
ISOLATOR 2

+
iso-6wire.wmf
ISOLATOR 1

-
SLC out to +
next device -

Figure 4.2 Wiring an ISO-6 Module

24 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


NFPA Style 4 SLC Using Isolator Modules SLC Circuits with Isolators

4.2 NFPA Style 4 SLC Using Isolator Modules


A variation of a Style 4 operation using an I300 isolator module to protect each branch of the SLC
is shown below. Refer to Figure 4.1 for I300 wiring and to Section 4.1 for limitations.

Isolator Module
Two-wire Addressable Detector
Isolated Branch

Isolator Module

Isolated Branch

Addressable Pull Station

Isolator Module

Isolated Branch

SLC-style4iso.wmf
B B+ Control Panel
SLC

Figure 4.3 NFPA Style 4 SLC Using an I300 Isolator Module

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 25


SLC Circuits with Isolators NFPA Style 4 SLC Using Isolator Modules

A variation of a Style 4 operation using an ISO-6 isolator module to protect each branch of the SLC
is shown below. Each terminal on the ISO-6 acts as a single I300 module. Refer to Figure 4.2 for
ISO-6 wiring and to Section 4.1 for limitations. Note that the ISO-6 cannot accept two wires at one
pin. Wire Style 4 SLC loops as shown in the figure below.

Two-wire Addressable Detector


Out -
ISOLATOR 1

Out +
In -
In + Isolated Branch
Addressable Pull Station
ISOLATOR 2
ISOLATOR 3

Isolated Branch
ISOLATOR 4
ISOLATOR 5

Isolated Branch
SLC-style4ISO-6.wmf

ISOLATOR 6

Control Panel
SLC

ISO-6

Figure 4.4 NFPA Style 4 SLC Using an ISO-6 Isolator Module

26 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


NFPA Style 6 SLC Using Isolator Modules SLC Circuits with Isolators

4.3 NFPA Style 6 SLC Using Isolator Modules


A variation of Style 6 operation using isolator modules to protect a section of the SLC. By flanking
each group of devices with an I300 fault isolator module each group is protected from faults that
may occur in the other groups. For example, a fault in Section B will not effect Sections A & C.
The isolator modules on either side of Section B will open the loop. Section A will still operate
from power on the SLC Out side and Section C will operate from the SLC Return side.
A combination of isolator modules and isolator bases may be used.
T-tapping is NOT allowed within the Style 6 configuration.
Isolator modules shall be within 20 feet (6.1 meters) of device and must be enclosed in metal
conduit.

Isolator Isolator
Module Module

Section B

Two-wire
Addressable Section C
Detector

Addressable
Pull Station

Section A

Additional isolator module required when first device in the


Isolator section is more than 20 feet from the control panel. Isolator
Module Module

Isolator Isolator
Module Module

SLC Out SLC Return


SLC-style6iso.wmf

Control Panel

Figure 4.5 NFPA Style 6 SLC Using Isolator Modules

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 27


SLC Circuits with Isolators NFPA Style 7 SLC Using Isolator Modules

4.4 NFPA Style 7 SLC Using Isolator Modules


Style 7 operation requires using isolator modules (or a combination of isolator modules and isolator
bases) before and after each device. Flanking each device with an isolator provides fault protection
to all other devices on the loop.
T-tapping is NOT allowed within the Style 7 wiring configuration.
When a detector base or pull station is used, install isolator modules on both sides of the
device.
Connections between isolator modules and the device they isolate must be close-nippled
conduit, within 3 feet (91.44 cm).

1 3 1 3
Isolator Isolator
Module Module

Two-wire
Addressable
Detector
3 4 2 1
Isolator Isolator
Module Module

Two-Wire
Addressable
Addressable
Pull Station
Detector

3 4 2 1
Isolator Isolator
Module Module

3 4 2 1
Isolator Isolator
Module Module
SLC Out SLC Return
SLC-style7iiso.wmf

Control Panel

Figure 4.6 NFPA Style 7 SLC Using Isolator Modules

28 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Section 5: Monitor Modules

5.1 Descriptions
These addressable modules monitor conventional contact-type alarm initiating devices. You can
configure module circuits as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Cir-
cuits (IDC). There is no limit to the number of contact-type devices installed on a monitor module
circuit.

NOTE: For more information on the individual module specifications refer to the Installation
Instructions that are provided with these devices.

5.1.1 Addressable Monitor Modules


MMF-300 Monitor Module
This is an addressable module that monitors either a Style B (Class B) or Style D (Class A) circuit
of dry-contact input devices. This module is capable of participating in degraded mode where sup-
ported by the FACP.

SLC
IDC Return Rotary
SLC+
Switches
IDC Return +
IDC Out +

FMMtpH.wmf
IDC Out -

Areas used to record the device


address and SLC number.

Figure 5.1 MMF-300 Monitor Module

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 29


Monitor Modules Descriptions

MMF-300-10 Monitor Module


This is an addressable monitor module intended to interface between the FACP and up to ten (10)
Style B (Class B) or five (5) Style D (Class A) IDCs containing normally open contact devices.
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up
to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into a cabinet.

mmf-300-10.wmf

Style Y or Style Z Select


Remove shunt for Style Z circuits

Disable Address SLC Address


Place shunt in: Set rotary switches to base
Disable 1 position to disable highest module address (first) address of modules
Disable 2 position to disable highest two module addresses

Figure 5.2 MMF-300-10 Monitor Module

30 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Descriptions Monitor Modules

5.1.2 Zone Interface Modules


MMF-302 Module
Similar to the MMF-300, this module is used to monitor a single IDC of UL listed compatible two-
wire 24 volt conventional smoke detectors. Refer to the Device Compatibility Document.

24 VDC
24 VDC + SLC
Rotary
IDC Return SLC+ Switches
IDC Return +
IDC Out +
IDC Out -

FZMtpH.wmf
Areas used to record the device
address and SLC number.

Figure 5.3 MMF-302 Interface Module

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 31


Monitor Modules Descriptions

MMF-302-6 Interface Module


This monitor module is intended to interface between the FACP and a conventional alarm system
with up to six (6) Style B (Class B) or three (3) Style D (Class A) IDCs containing normally open
contact devices.
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up
to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabinet.

T1 T2 T3 T4
T0
+ + + + + + + + + +

T6 T5
A/B SELECT
A/B SELECT
DISABLE 2
DISABLE 1

4
3
2

5
1 0

6 7 8 9

BASE ADDRESS
15 14

J1
13

10
12
11

SW1
4
3
2

5
10

6 7 8 9

BASE ADDRESS +0 BASE ADDRESS +1 BASE ADDRESS +2 BASE ADDRESS +3 BASE ADDRESS +4 BASE ADDRESS +5

Style Y or Style Z Select


Remove shunt for Style Z circuits

SLC Address
Disable Address Set rotary switches to base
Place shunt in: (first) address of modules
Disable 1 position to disable highest module address
Disable 2 position to disable highest two module addresses

Figure 5.4 MMF-302-6 Interface Module

32 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Installation Monitor Modules

5.1.3 Dual Monitor Module


MDF-300 Module
The MDF-300 is similar to the MMF-300 but provides for two independent 2-wire IDCs at two
separate, consecutive addresses.

Rotary
Switches

Address +1 { 89 H+
H
SLC
7L+ SLC+
Base Address { 6L

fmmtph.wmf
Areas used to record the device
address and SLC number.

Figure 5.5 MDF-300 Dual Monitor Module

5.1.4 Mini Monitor Module


MMF-301 Monitor Module
The MMF-301 is functionally and electrically identical to an MMF-300, but is offered in a smaller
package for mounting directly in the electrical box of the Style B (Class B) device being monitored.

Label Use to record


Rotary Switches
the device address and
SLC number.

IDC (+) SLC (+)

IDC (-) SLC (-)


FMM-101.wmf

Figure 5.6 MMF-301 Mini Monitor Module

5.2 Installation
When installing any of these modules DO NOT mix the following services that the IDC provides:
Fire alarm service
Automatic and manual waterflow alarm service with normally open contact devices
Sprinkler supervision with normally open contact devices

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 33


Monitor Modules Installation

5.2.1 Setting an SLC address for a Single Point Module


Each module can be set to one of 159 addresses (01-159) and is factory preset with an address of
00.

NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-
9600UDLS can support module addresses 01 - 159. The plastic stop located on the Tens switch
must be removed to set addresses above 99.

To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired
address. The module below is set at 35. When finished, mark the address on the module face in
the place provided.

SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
6 7 8 910 6789
5 5
4 11 4 Breakaway Tab - Modules come with
3 12 3 a raised breakaway tab on the TENS
2 13 2 rotary switch. This tab must be
1 0 1514 10 removed when the module is on an
TENS ONES FACP that uses more than 99
addresses.
Modules with Rotary
Switches in
horizontal position

Modules with
Rotary Switches Dual monitor modules: On dual monitor modules, only even
in vertical numbers appear on the ONES rotary switch. The module takes
position both the selected address and the next-higher address.

Figure 5.7 Setting an SLC Address on a Single Point Module

34 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Installation Monitor Modules

5.2.2 Setting an SLC address for a Multi-Point Module


The SLC address of a multi-point module is set in the same fashion as a single-point module.
In Class B operation, each MMF-300-10, MMF-302-6, CMF-300-6, and CRF-300-6 module is set
to a base address. The remaining module points are automatically assigned to the next higher SLC
addresses. For example, if the base address of a MMF-300-10 is set to 28, the next module points
will be addressed to 29, 30, 31, 32, 33, 34, 35, 36 and 37.
In Class A operation, alternate module points are paired together, resulting in a total of five module
points. For example, if the base address of a MMF-300-10 is set to 28, then 30, 32, 34 and 36 will
be automatically assigned to the remaining module points and 29, 31, 33, 35 and 37 are available
for use by other modules.

NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-
9600UDLS can support module addresses 01 - 159 (the plastic stop located on the Tens switch
must be removed to set addresses above 99).

To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to
the desired address. The module below is set at 28.

4
3
2

5
10

6 7 8 9
TENS
15 14
13

10
Plastic Stop
12
11

Rotary Switches
4
3
2

multroty.wmf
10

6 7 8 9

ONES

Figure 5.8 Setting an SLC Address on a Multi-Point Module

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 35


Monitor Modules MMF-300 Wiring Diagrams

5.3 MMF-300 Wiring Diagrams


Following are wiring diagrams that depict NFPA Style B (Class B) and D (Class A) Initiating
Device Circuits (IDCs) using MMF-300 monitor modules.
The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamperes @ 24
VDC (nominal).

5.3.1 Wiring a NFPA Style B IDC with an MMF-300


Connect the SLC wiring to the module terminals 1 () and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to Setting an SLC address for a Single Point Module on page 34.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC
using an MMF-300 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See Power Considerations on page 68 for information on supervising 24 VDC power.

From Supply

24 VDC
Four-wire
Detector Base 24 VDC Power
Filtered, Regulated,
Resettable
Manual pull
station

To Next IDC
or
47K ELR
Supervision Device
(supplied
with module)
SLC
Heat
detector MMF-300

SLC-idcB1tpH.wmf

IDC

Figure 5.9 Typical Style B IDC Wiring with an MMF-300

36 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


MMF-300 Wiring Diagrams Monitor Modules

5.3.2 Wiring a NFPA Style D IDC with an MMF-300


Connect the SLC wiring to the module terminals 1 () and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to Setting an SLC address for a Single Point Module on page 34.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-300 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See Power Considerations on page 68 for information on supervising 24 VDC power.

From
Supply

24 VDC
Four-wire
24 VDC Power
Detector Base
Filtered, Regulated,
Resettable

Manual pull
station

To Next IDC
or
Supervision Device

SLC

Heat MMF-300
detector

SLC-idcD1tpH.wmf
IDC

Figure 5.10 Typical Style D IDC Wiring with an MMF-300

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 37


Monitor Modules MMF-300 Wiring Diagrams

5.3.3 MMF-300 Wiring for Emergency Alarm System Applications


Connect the SLC wiring to the module terminals 1 () and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to Setting an SLC address for a Single Point Module on page 34.
The figure below shows typical wiring for a supervised and power-limited Emergency Signaling
circuit using an MMF-300 module.
See Power Considerations on page 68 for information on supervising 24 VDC power.
See Section 6, Control Modules for instructions on using control modules as NACs on an
SLC.
For compatible output devices refer to the Device Compatibility Document #15384.

47K ELR
(supplied
with module)

SLC + -
- +
UL-listed Signaling
applicance such as the
Fire-Lite FSS-2400E

IDC

SLC-emer.wmf
MMF-300 Module
programmed for Tornado,
Hazard, or Medical operation.
Refer to the control panel
installation manual.

Figure 5.11 Emergency Signaling Wiring with an MMF-300

38 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


MMF-300-10 Wiring Diagrams Monitor Modules

5.4 MMF-300-10 Wiring Diagrams


Following are wiring diagrams that depict NFPA Style B (Class B) and D (Class A) Initiating
Device Circuits (IDCs) using MMF-300-10 monitor modules.
The Initiating Device Circuit (IDC) is supervised and current-limited to 1.0 milliampere @ 24
VDC (nominal).

5.4.1 Wiring a NFPA Style B IDC with an MMF-300-10


Connect the SLC wiring to the module terminals T5 as shown below.
Use the rotary switches on the module to set the base SLC address. Each module takes ten
addresses on the SLC. The remaining module points are automatically assigned to the next nine
higher addresses. Refer to Setting an SLC address for a Multi-Point Module on page 35.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC
using an MMF-300-10 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See Power Considerations on page 68 for information on supervising 24 VDC power.

24 VDC Power
Filtered, Regulated, Resettable

47K ELR Heat


(supplied Manual Pull Detector
with module) Station

24 VDC Four-wire
Detector Base

IDC
Out
SLC MMF-300-10
SLC-idcB4.wmf

Figure 5.12 Typical Style B IDC Wiring with an MMF-300-10

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 39


Monitor Modules MMF-300-10 Wiring Diagrams

5.4.2 Wiring a NFPA Style D IDC with an MMF-300-10


Connect the SLC wiring to the module terminals T5 as shown below.
Use the rotary switches on the module to set the base SLC address. Each module takes five alternat-
ing addresses on the SLC. The remaining module points are automatically assigned to the next four
higher addresses. (Example: 28, 30, 32, 34 and 36). Refer to Setting an SLC address for a Multi-
Point Module on page 35.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-300-10 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See Power Considerations on page 68 for information on supervising 24 VDC power.

24 VDC Power
Filtered, Regulated, Resettable

Heat
Manual Pull Detector
24 VDC Four-wire Station
Detector Base

IDC IDC
Return Out

SLC MMF-300-10

SLC-idcD3.cdwmf

Figure 5.13 Typical Style D IDC Wiring with an MMF-300-10

40 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


MDF-300 Wiring Diagrams Monitor Modules

5.5 MDF-300 Wiring Diagrams


Following is a wiring diagrams that depict NFPA Style B (Class B) Initiating Device Circuits
(IDCs) using MDF-300 Dual Monitor Modules.

5.5.1 Wiring a NFPA Style B IDC with an MDF-300


Connect the SLC wiring to the module terminals 1 () and 2 (+).
Use the rotary switches on the module to set it to the SLC address. Each dual module takes two
addresses on the SLC. Circuit L corresponds to the address set on the rotary switches, which will
be an even number. Circuit H will automatically respond to the next higher address, which will be
an odd number. Use caution to avoid duplicate addressing of modules on the system. Refer to Set-
ting an SLC address for a Single Point Module on page 34.
Each IDC (H & L) is power limited to 230 microamperes @ 24 VDC.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC
using an MDF-300-10 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See Power Considerations on page 68 for information on supervising 24 VDC power.

Manual Manual
Pull Pull
Station Station

47K 47K SLC


ELR ELR
Heat
Detector MDF-300

Base +1 Address T11


Base Address (IDC Circuit H) T10 T1
(IDC Circuit L) T9 T2

SLC-idcB3fdm1tph.wmf
T8 T3
T7 T4
T6 T5

Figure 5.14 Typical Style B IDC Wiring with an MDF-300

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 41


Monitor Modules MMF-302 Wiring Diagrams

5.6 MMF-302 Wiring Diagrams


Following are wiring diagrams that concern NFPA Style B (Class B) and D (Class A) Initiating
Device Circuits (IDCs) using MMF-302 Zone Interface Modules.

5.6.1 Wiring a NFPA Style B IDC with an MMF-302


Connect the SLC wiring to the module terminals 1 () and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to Setting an SLC address for a Single Point Module on page 34.
The IDC is supervised and power limited to 230 microamperes @ 24 VDC.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC
using an MMF-302 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This
power is inherently supervised by the module.
See Power Considerations on page 68 for information on 24 VDC power.

24 VDC Resettable power.


Two-wire 90 mA External 24 volt
smoke supply required
detectors
3.9K ELR
(supplied with module)
SLC

MMF-302

IDC
SLC-idcB2tpH.wmf

Figure 5.15 Typical Style B IDC Wiring with an MMF-302

42 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


MMF-302 Wiring Diagrams Monitor Modules

5.6.2 Wiring a NFPA Style D IDC with an MMF-302


Connect the SLC wiring to the module terminals 1 () and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to Setting an SLC address for a Single Point Module on page 34.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-302 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This
power is inherently supervised by the module.
See Power Considerations on page 68 for information on 24 VDC power.

Two-wire
smoke 24 VDC Resettable power.
detectors 90 mA External 24 volt supply required

SLC

MMF-302

IDC

SLC-idcD2tpH.wmf
3.9K ELR
(supplied with module)

Figure 5.16 Typical Style D IDC Wiring with an MMF-302

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 43


Monitor Modules MMF-302-6 Wiring Diagrams

5.7 MMF-302-6 Wiring Diagrams


Following are wiring diagrams that concern NFPA Style B (Class B) and D (Class A) Initiating
Device Circuits (IDCs) using MMF-302-6 monitor modules.

5.7.1 Wiring a NFPA Style B IDC with an MMF-302-6


Connect the SLC wiring to the module terminals T0 as shown below.
Use the rotary switches on the module to set the base SLC address. Each module takes six
addresses on the SLC. The remaining module points are automatically assigned to the next five
higher addresses. Refer to Setting an SLC address for a Multi-Point Module on page 35.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC
using an MMF-302-6 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This
power is inherently supervised by the module.
See Power Considerations on page 68 for information on 24 VDC power.

Two-wire smoke detectors


3.9K ELR
(supplied with
module)

24 VDC resettable power

IDC
Out

SLC MMF-302-6
SLC-idcB5.wmf

Figure 5.17 Typical Style B IDC Wiring with an MMF-302-6

44 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


MMF-302-6 Wiring Diagrams Monitor Modules

5.7.2 Wiring a NFPA Style D IDC with an MMF-302-6


Connect the SLC wiring to the module terminals T0 as shown below.
Use the rotary switches on the module to set it to the SLC addresses. Each module takes three alter-
nating addresses on the SLC. The remaining module points are automatically assigned to the next
two higher addresses. (Example: 28, 30 and 32). Refer to Setting an SLC address for a Multi-
Point Module on page 35.
DO NOT set the lowest address above 150 (41 for the MS-9050UD, 90 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-302-6 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This
power is inherently supervised by the module.
See Power Considerations on page 68 for information on 24 VDC power.

Two-wire smoke detectors

24 VDC resettable power

IDC IDC
Return Out

SLC MMF-302-6
SLC-idcD4.wmf

Figure 5.18 Typical Style D IDC Wiring with an MMF-302-6

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 45


Section 6: Control Modules
When using a Control Module as a Notification Appliance Circuit (NAC), the isolation described in
the section titled Section 4, SLC Circuits with Isolators which begins on page 23, is required or
Riser Conductors must be installed in accordance with the survivability from attack by fire require-
ments in National Fire Alarm Code, NFPA 72.

6.1 Description
The CMF-300 and CMF-300-6 modules are addressable modules that can be used for monitoring
and switching 24 VDC Notification Appliance Circuit (NAC) power for NFPA Style Y (Class B)
and NFPA Style Z (Class A) circuits.
Ratings for the relay contacts on the module are:
Load Description Application Maximum Voltage Current Rating

Resistive Non-Coded 30 VDC 3.0 A

Resistive Coded 30 VDC 2.0 A

Resistive Non-Coded 110 VDC 0.9 A

Resistive Non-Coded 125 VAC (CMF-300) 0.9 A


70.7 VAC (CMF-300-6)

Inductive (L/R = 5ms) Coded 30 VDC 0.5 A

Inductive (L/R = 2ms) Coded 30 VDC 1.0 A

Inductive (PF = 0.35) Non-Coded 125 VAC (CMF-300) 0.5 A


70.7 VAC (CMF-300-6)

NOTE: For more information on module specifications, refer to the Installation Instructions
provided with these devices.

6.2 CMF-300 Installation


6.2.1 Setting an SLC address for a CMF-300 Module
Each module is factory preset with an address of 00. To set an SLC address refer to Setting an
SLC address for a Single Point Module on page 34.

6.2.2 Wiring a Notification Appliance Circuit (NAC) with a CMF-300


The figure below shows the connections to wire a module for powering a 24 VDC NAC:

24 VDC Nonresettable Power ()


24 VDC Nonresettable Power (+) SLC ()
Style Z NAC (+) SLC (+)
Style Z NAC ()
Style Y/Z NAC ()
Style Y/Z NAC (+)
FCMFZMtph.wmf

NOTE: Module polarities are shown in alarm condition.

Figure 6.1 CMF-300 Wiring Connections

46 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Wiring a CMF-300 Module Control Modules

6.3 Wiring a CMF-300 Module


This section contains instructions and diagrams for wiring a Signaling Line Circuit with a
CMF-300 as a Notification Appliance Circuit (NAC).

6.3.1 Wiring a Style Y NAC (Two-Wire) with Addressable Control


Modules
A supervised and power-limited NFPA Style Y (Class B) NAC using a CMF-300 module. Polar-
ized alarm notification appliances are shown connected to the module in a two-wire configuration.
Refer to the Device Compatibility Document for compatible notification appliances and relays.
See Power Considerations on page 68 for information on monitoring 24 VDC power.
Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Y circuit.
Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt,
P/N SSD A2143-00 (ELR-47K in Canada).
Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.
SLC
24 VDC Nonresettable power
CMF-300
NOTE: A power
supervision relay is
required only on the
ELR last module of the
24 VDC Notification power run.
47K, 1/2-watt
Appliances

SLC-nacY.wmf
NAC

Note: Module polarities are shown in alarm condition

Figure 6.2 NFPA Style Y Notification Appliance Circuit

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 47


Control Modules CMF-300-6 Installation

6.3.2 Wiring a Style Z NAC (Four-Wire) with Addressable Control


Modules
A supervised and power-limited NFPA Style Z (Class A) NAC using a CMF-300 module. Polarized
alarm notification appliances are shown connected to the module in a four-wire configuration.

NOTE: Refer to the Device Compatibility Document for compatible notification appliances and
relays.

See Power Considerations on page 68 for information on monitoring 24 VDC power.


Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Z circuit.
Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.

NOTE: A power supervision relay is required only


on the last module of the power.

24 VDC Nonresettable power SLC

CMF-300
24 VDC
notification
appliances

NAC Return

NAC Out

SLC-nacZtpH.wmf
Note: Module polarities are shown in alarm condition.

Figure 6.3 NFPA Style Z Notification Appliance Circuit

6.4 CMF-300-6 Installation


6.4.1 Cabinet Installation
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up
to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabinet.

6.4.2 Setting an SLC address for an CMF-300-6 Module


In Style Y operation each CMF-300-6 module can be set to one of 154 base addresses (01-154).
The remaining module points are automatically assigned to the next five higher SLC addresses. For
example, if the base address is set to 28, the next five module points will be addressed to 29, 30, 31,
32 and 33.

48 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


CMF-300-6 Installation Control Modules

In Style Z operation alternate module points are paired together, resulting in a total of three mod-
ule points. For example, if the base address is set to 28, then 30 and 32 will be automatically
assigned to the remaining module points and 29, 31 and 33 are available to be used for other mod-
ules on the SLC.
DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.

NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, MS-9600LSC,
and MS-9600UDLS can support module addresses 01 - 159.

To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to
the desired address. See Figure 6.4 on page 50.

NOTE: For use with the MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS, remove the
stop on the upper rotary switch.

6.4.3 Setting NACs as Style Y or Style Z


To use this module for Style Y (Class B) operation ascertain that a small shunt is installed on the
A/B SELECT set of pins. (As shipped).
To use this module for Style Z (Class A) operation remove the small shunt from the A/B
SELECT set of pins. See drawing below and Figure 6.4 on page 50.

6.4.4 Disabling Unused Module Addresses


A shunt is used, in conjunction with a pin block, to disable a maximum of

A/B SELECT
DISABLE 3
DISABLE 2
DISABLE 1
three (3) unused module addresses. If two module addresses are disabled,
the lowest four addresses will be functional, while the highest two will be
disabled. For example, if the shunt is placed on DISABLE 2 and the base
address is set to 28, the module addresses will be assigned to 28, 29, 30
and 31.

SLC-disable1.wmf
In Style Z operation, placing a small shunt on DISABLE 3 will disable
all three addresses. Placing it on DISABLE 2 will disable two out of
three addresses. J1
To disable addresses, securely place one of the supplied small shunts onto
the desired set of pins. See drawing and Figure 6.4 on page 50.

6.4.5 Short Circuit Protection


Protection is disabled for each module address when there is a large shunt installed on the corre-
sponding pins of the pin block (as shipped, all six addresses are disabled).
When enabled, the module will not switch power supply if a short circuit condition exists on a
NAC.
To enable Short Circuit Protection for an address, remove the large shunt from the corresponding
pins of the pin block. See Figure 6.4 on page 50. Place unused shunts on single pin to store on
board for future use.

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 49


Control Modules CMF-300-6 Installation

6.4.6 Features Not Supported


The Synchronization and Power Supply Monitoring features are not supported at this time.

6.4.7 Circuit Board Information


Synchronization Generator - Power Supply Monitors -
Not Supported. DO NOT Not Supported. DO NOT
remove shunts. remove shunts.

#1 #2 #3 #4 #5 #6

Status Indicators
Green LEDs are
CMF-300-6.wmf
controlled by FACP to
indicate status of each
module address.

Disable Address - SLC Address


Place shunt onto required pins. Set rotary switches to
address required.
Select
Style Y (Class B) or
Style Z (Class A) - Short Circuit Protection - Remove
Remove shunt for Style Z (Class A). shunt from the corresponding pins to
enable. Shunt #1 for first address, #2
for second address, etc.

Figure 6.4 CMF-300-6 Control Module Settings

50 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Wiring a CMF-300-6 Module Control Modules

6.5 Wiring a CMF-300-6 Module


This section contains basic instructions and diagrams for wiring a Signaling Line Circuit with a
CMF-300-6 as a Notification Appliance Circuit (NAC).
For more detailed information on wiring a CMF-300-6 Control Module refer to the Installation
Instructions provided with the module. Included in these instructions are wiring diagrams concern-
ing a single power supply being shared by multiple NACs and audio NAC configurations.

6.5.1 Wiring a Style Y NAC (Two-Wire)


A supervised and power-limited NFPA Style Y (Class B) NAC with a single power supply dedi-
cated to a single NAC using a CMF-300-6 module. Polarized alarm notification appliances are
shown connected to the module in a two-wire configuration.

NOTE: Refer to the Device Compatibility Document for compatible notification appliances and
relays.

See Power Considerations on page 68 for information on monitoring 24 VDC power.


Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Y circuit.
Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt,
P/N SSD A2143-00 (ELR-47K in Canada).
Do not loop wiring under the screw terminals of any notification appliance. To maintain super-
vision, break the wire run at each device.
Power Supervision
Relay
(EOLR-1)

24 VDC
nonresettable
power

ELR 47K,
1/2-watt 24 VDC notification appliances

+
NAC Out

SLC
Relay Connector Assembly +

CMF-300-6

T0
+0 + + + + + + + + + +

T1 T2 T3 T4 T5
+ +
SLC-nacY2.wmf

+1 +2 +3 +4 +5
T12 T13 T14 T15
T10 T11 T16

Figure 6.5 NFPA Style Y Notification Appliance Circuit

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 51


Control Modules Wiring a CMF-300-6 Module

6.5.2 Wiring a Style Z NAC (Four-Wire)


A supervised and power-limited NFPA Style Z (Class A) NAC with a single power supply dedi-
cated to a single NAC using a CMF-300-6 module. Polarized alarm notification appliances are
shown connected to the module in a four-wire configuration.

NOTE: Refer to the Device Compatibility Document for compatible notification appliances and
relays.

See Power Considerations on page 68 for information on monitoring 24 VDC power.


Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Z circuit.
Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.

Power Supervision
Relay
(EOLR-1)

24 VDC
nonresettable
power

24 VDC notification appliances

NAC
Out

SLC
NAC
Return

CMF-300-6
SLC-nacZ3.cwmf

Power Supply Jumper


Relay Connector Assembly

Figure 6.6 NFPA Style Z Notification Appliance Circuit

52 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Section 7: Relay Modules

7.1 Description
The CRF-300 and the CRF-300-6 modules are addressable modules that provides Form-C relay
contacts.
Ratings for the relay contacts on the module are:

Maximum Current
Load Description Application
Voltage Rating

Resistive Non-Coded 30 VDC 3.0 A

Resistive Coded 30 VDC 2.0 A

Resistive Non-Coded 110 VDC 0.9 A

Resistive Non-Coded 125 VAC 0.9 A

Inductive (L/R = 5ms) Coded 30 VDC 0.5 A


Inductive (L/R = 2ms) Coded 30 VDC 1.0 A

Inductive (PF = 0.35) Non-Coded 70.7 VAC 0.7 A

Inductive (PF = 0.35) Non-Coded 125 VAC 0.5 A

NOTE: For more information on the module specifications refer to the Installation Instructions
provided with these devices.

7.2 CRF-300 Installation & Wiring


7.2.1 Setting an SLC address for a CRF-300 Module
Each module is factory preset with an address of 00. To set an SLC address, refer to Setting an
SLC address for a Single Point Module on page 34.

7.2.2 Wiring a CRF-300 Module (Form-C Relay)


The figure below shows a CRF-300 module wired to the Control Panel:
SLC

CRF-300

C
NC
NO
C
NC NO
SLC-frmCtpH.wmf

Figure 7.1 CRF-300 Wiring Connections

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 53


Relay Modules CRF-300-6 Circuit Board Information

7.3 CRF-300-6 Circuit Board Information

T102

COMM
COMM
COMM

N.O.
N.C.
COMM

N.O.
N.C.
COMM

N.O.
N.C.
N.O.
N.C.
N.O.
N.C.
BASE ADDRESS +0 BASE ADDRESS +1 BASE ADDRESS +2 BASE ADDRESS +4 BASE ADDRESS +5

THREE

NONE
TWO
ONE

ADDRESS
DISABLE

Disable Address
Place shunt onto
required pins.

crf-300-6.wmf
Status Indicators
Green LEDs are
controlled by FACP to
indicate status of each
module address.
SLC Address
Set rotary switches to
address required.

Figure 7.2 CRF-300-6 Control Relay Module

7.4 CRF-300-6 Installation & Wiring


7.4.1 Cabinet Installation
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up
to 2 modules and the BB-6, which requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabinet.

54 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


CRF-300-6 Installation & Wiring Relay Modules

7.4.2 Setting an SLC address for a CRF-300-6 Module


Each CRF-300-6 module can be set to one of 154 base addresses (01-154). The remaining module
points are automatically assigned to the next five higher SLC addresses. For example, if the base
address is set to 28, the next five module points will be addressed to 29, 30, 31, 32 and 33.
DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.

NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-
9600UDLS can support module addresses 01 - 159. To set an SLC address, use a common
screwdriver to adjust the rotary switches on the module to the desired address. See Figure 6.4 on
page 50.
For use with an MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS, remove the stop on
the upper rotary switch.

7.4.3 Disabling Unused Module Addresses


A shunt is provided on the circuit board to disable a maximum of three (3)
unused module addresses. If two module addresses are disabled, the low-
est four addresses will be functional, while the highest two will be dis-
abled. For example, if the shunt is placed on TWO and the base address

SLC-disable2.wmf
is set to 28, the module addresses will be assigned to 28, 29, 30 and 31.
To disable addresses, remove the shunt from its storage location and
securely place it onto the desired set of pins. See illustration. J1
Shunt Storage
Location

7.4.4 Wiring a CRF-300-6 Module (Form-C Relay)


The figure below shows a CRF-300-6 module wired to the Control Panel.
SLC Out SLC In Relay Connections

CRF-300-6

+ +
SLC-fmC1.wmf

Figure 7.3 CRF-300-6 Wiring Connections

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 55


Notes

56 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Section 8: Multiple Input/Output Modules

8.1 Description
The CDRM-300 is an addressable module that functions as two individual relay control modules
(two isolated sets of Form-C relay contacts) and two Class B monitor modules.
Ratings for the relay contacts on the module are:

Maximum Current
Load Description Application
Voltage Rating

Inductive (PF = 0.35) Non-Coded 25 VAC 2.0 A

Resistive Non-Coded 30 VDC 3.0 A

Resistive Coded 30 VDC 2.0 A

Inductive (L/R = 20ms) Non-Coded 30 VDC 0.46 A

Inductive (PF = 0.35) Non-Coded 70.7 VAC 0.7 A


Resistive Non-Coded 125 VDC 0.9 A

Inductive (PF = 0.75) Non-Coded 125 VAC 0.5 A

Inductive (PF = 0.35) Non-Coded 125 VAC 0.3 A

NOTE: For more information on the module specifications refer to the Installation Instructions
provided with these devices.

8.2 CDRM-300 Installation & Wiring


8.2.1 Setting an SLC address for a CDRM-300 Module
Each module is factory preset with an address of 00. To set an SLC address, use a screwdriver to
adjust the rotary switches on the module to the desired address. Each module can use up to four (4)
addresses. The base address selected via the rotary address switches will be assigned to relay output
#1 from 00 to 156. The module will automatically assign the next three addresses as appropriate to
monitored input #1, relay output #2, and monitored input #2.

FireLite SLC Wiring Manual P/N 51309:P4 9/17/20149/17/2014 57


Multiple Input/Output Modules CDRM-300 Installation & Wiring

8.2.2 Wiring a CDRM-300 Module (Form-C Relay)


The figure below shows a CDRM-300 module wired to the Control Panel.
SLC
CDRM-300

NC
C
NO IDC 1 (+)
NC IDC 1 (-)
C IDC 2 (+)
NO IDC 2 (-)

fdrm-1.wmf
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open

Figure 8.1 CDRM-300 Wiring Connections

58 FireLite SLC Wiring Manual P/N 51309:P4 9/17/20149/17/2014


Section 9: Intelligent Detector Bases and Wireless
Gateway

9.1 Description
The following bases provide connection between the SLC and these detector heads:
AD350 and AD355 Multi-criteria Photoelectric Smoke Detector
CP350 and CP355 Ionization Smoke Detector
H350, H350R, H355, H355R and H355HT Thermal Detector
SD350, SD350T, SD355 and SD355T Photoelectric Smoke Detector
The B501 and B210LP bases are standard plug-in detector bases.
The B501BH, B501BHT, B501BH-2, B501BHT-2, B200SR, and B200SR-LF Sounder Detector
Bases include a horn that will sound when the sensors visible LEDs are latched on for approxi-
mately 10 seconds.
On the MS-9200 Control Panel, the sounder will activate when the sensors visible LEDs are
latched on for approximately 10 seconds (Alarm Verification does not delay sounder).
If the MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, or MS-9050UD
Control Panel is set with Alarm Verification ON, the sounder will activate at the end of the
verification cycle, providing an alarm is verified, approximately 10 seconds after the sensors
LEDs are latched on. If Alarm Verification is OFF, the sounder will activate when the sensors
visible LEDs are latched on for approximately 10 seconds.
The B224RB Relay Detector Base includes Form-C latching relay contacts for the control of an
auxiliary function. The relay operates 12 seconds (nominally) after activation of the sensor head
remote annunciator output.
The B224BI Isolator Detector Base prevents an entire communications loop from being disabled
when a short circuit occurs.
The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a
LiteSpeed SLC loop on the MS-9200UDLS. The gateway can be powered by the SLC loop or by a
regulated, external UL-listed, 24VDC power supply. See Section 9.7.

NOTE: When using a Wireless Gateway on the SLC loop, the panel cannot have ANY modules
(wired or wireless) in the address range from 140 to 159.

For details about the wireless network and its devices, see the SWIFT Smart Wireless Integrated
Fire Technology Instruction Manual #LS10036-000FL-E.

9.2 Setting the Detector Address


Each intelligent detector is factory preset with an address of 00. To set an SLC address, use a
common screwdriver to adjust the rotary switches on the detector to the desired address (see Set-
ting an SLC address for a Single Point Module on page 34). When finished, mark the address in
the place provided on the base and the detector.

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 59


Intelligent Detector Bases and Wireless Gateway Wiring a Detector Base

9.3 Wiring a Detector Base


Typical wiring of a detector base (B501 shown) connected to an SLC is shown in the figure below.
An optional RA100Z/RA400Z Remote LED Annunciator is shown connected to the detector.
From Control Panel SLC
+


To Next Device
on SLC
+

RA100Z /
RA400Z

SLC-B5012wire.wmf
Remote LED
Annunciator
(Optional)
+

Figure 9.1 Wiring a B210LP or B501 Detector Base

NOTE: The B210LP base wiring is identical to the B501. B501 is the flangeless model.

60 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Wiring an Isolator Base Intelligent Detector Bases and Wireless Gateway

9.4 Wiring an Isolator Base


The B224BI Isolator Base will isolate its detector from short circuits that occur on the SLC con-
nected at terminals 2 and 3. It will not isolate its installed detector from short circuits that occur on
the SLC connected at terminals 1 and 2. In Style 7 applications, the loss of a single detector during
a short circuit is not acceptable, and an isolator module must be installed as shown in the figure
below.
SLC Out
+
Note: The grid pattern on the
redesigned B224BI mounting
plate has been removed for
illustration purposes only.

SLC In
+

Conduit

slc-224bi2wire.wmf
I300 Isolator Module

Figure 9.2 Wiring of a B224BI Isolator Base Mounting Plate

9.5 Wiring a Relay Base


Figure 9.3 shows typical wiring of a B224RB plug-in relay detector base connected to an SLC.

Note: The grid pattern on the


redesigned B224RB mounting
To next device plate has been removed for
on SLC illustration purposes only.
+-

Normally Closed
Common
Normally Open
slc-b224rb2wire.wmf

+-
SLC

Figure 9.3 Wiring of a B224RB Relay Base Mounting Plate

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 61


Intelligent Detector Bases and Wireless Gateway Wiring a Sounder Base

9.6 Wiring a Sounder Base


Figure 9.4 shows typical wiring of the B200SR or B200SR-LF Sounder Base.
Note: The grid pattern on the
sounder base has been removed
To next device for illustration purposes only.
on SLC
+-

Optional Sounder
Interconnect

slc-b200srwire.wmf
+ -
UL-Listed
24V Power
+- Supply
SLC

Figure 9.4 Wiring of a B200SR/B200SR-LF Sounder Base

NOTE: For more detailed wiring on the sounder base, refer to the devices installation instructions.

9.7 Wiring the W-GATE


NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the
Federal Communications Commission (FCC) requirements of the United States Government. It
has not been evaluated for use outside the USA. Use of this system outside the USA is subject to
local laws and rules to which this product may not conform. It is the sole responsibility of the user
to determine if this product may be legally used outside the USA.

NOTE: It is recommended to use the same wire gauge if there are multiple connections to the
same terminal.

9.7.1 SLC Connections


The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a
LiteSpeed SLC loop on the MS-9200UDLS. It is powered by the SLC loop or by a regulated,
external 24VDC UL-listed power supply. Available wireless devices include a photo detector, a
photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitor
module. For details about wireless devices, system setup, and operation, see the SWIFT Smart
Wireless Integrated Fire Technology Instruction Manual.

62 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Wiring the W-GATE Intelligent Detector Bases and Wireless Gateway

A7- SLC OUT+

A6- SLC IN+


A5- SLC- (Common)
A4- SLC Power Select 2
A3- Power +24VDC
A2- Power Ground

A1- SLC Power Select 1

2.4.wmf
Figure 9.5 W-GATE Mounting Plate - Terminal Layout

9.7.2 W-GATE Powered by the SLC


The W-GATE provides isolation of short circuits on the SLC in Class A (Style 6) installations. SLC
connections are power-limited by the panel. An interruption in the SLC that causes a loss of power
at the W-GATE for more than 100ms may result in a trouble condition and loss of fire protection
provided by the wireless devices for approximately 15 minutes. Use of a regulated, external
+24VDC power source (not SLC power) is recommended for installations that require fire protec-
tion in the presence of short circuits, including Class A applications and applications that use isola-
tor modules. Figure 9.6 shows typical wiring of a Wireless Network Gateway connected to an SLC
when power is supplied by the SLC loop

SLC out to next device (Class B) +


or SLC return to FACP (Class A) -
SLC in from FACP/device +-

Jumpers
2.5.wmf

Figure 9.6 W-GATE Powered by the SLC

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 63


Intelligent Detector Bases and Wireless Gateway Wiring the W-GATE

9.7.3 W-GATE Powered by a Regulated, External +24VDC Power


Source
The FWSG provides isolation of short circuits of the SLC in Class A (Style 6) installations. SLC
connections are power-limited by the panel. +24VDC must be power-limited by the source..

SLC out to next device (Class B) +


or SLC return to FACP (Class A) -
+-

2.6.wmf
SLC in from FACP/device

External 24VDC Power


+
-

Figure 9.7 W-GATE Powered by a Regulated, External Source

64 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Section 10: Addressable Beam Detectors

10.1 Description
The BEAM355 and BEAM355S are intelligent, addressable projected beam smoke detectors,
designed for protecting open areas with high and sloping ceilings and wide-open areas, where spot
type smoke detectors are difficult to install and maintain. The BEAM355S has an integral sensitiv-
ity test feature that consists of a test filter attached to a servomotor inside the detector optics.

NOTE: This section provides basic wiring and addressing information. For critical information
on device installation, operation and alignment, refer to the Installation Instructions provided with
these devices.

10.2 Installation and Wiring


10.2.1 Setting an SLC Address for a Beam Detector
Each beam detector is factory preset with an address of 00. To set an SLC address, use a com-
mon screwdriver to adjust the address rotary code switches on the detector to the desired address
(refer to 5.2.1Setting an SLC address for a Single Point Module on page 34).

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 65


Addressable Beam Detectors Installation and Wiring

10.2.2 Wiring a Beam Detector


Typical wiring of a beam detector connected to an SLC is illustrated in the figure below.

Alignment Mirror
Alignment Gunsight Digital Signal
Strength Readout
Alignment Position
Indicator

Horizontal Adjustment
Optics Lock-down
Screws
Alignment Switch

Sensitivity Switch
ONES
ADDRESSING
SWITCHES
CODE

Test Switch
TENS

Vertical Adjustment

Style 7 Isolator Shunts


Reset Switch
Remote Alarm Out

Reset Input
Test Input
Aux (-)

Test Option (-) SLC (-) to next device


Test Option (+) SLC (+) to next device
not used SLC (-) from panel or previous device
not used SLC (+) from panel or previous device

RTS151/KEY& RTS-451/KEY
Connections

Figure 10.1 Beam Detector Terminal Block Wiring

66 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Section 11: Addressable Manual Pull Station

11.1 Description
The BG-12LX is an addressable manual pull station with a key-lock reset feature.

NOTE: For more information refer to the Installation Instructions provided with this device.

11.2 Installation
11.2.1 Setting an SLC address
Each unit is factory preset with an address of 00. To set an SLC address refer to Setting an SLC
address for a Single Point Module on page 34.

11.2.2 Wiring a Manual Pull Station


Figure 11.1 shows typical wiring for a BG-12LX Manual Pull Station to an SLC:


To next device
+ on SLC
SLC +

US PAT 4440991

SLC-bg12lx2.wmf

Figure 11.1 Wiring of a BG-12LX Pull Station to an SLC

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 67


Appendix A: Power Considerations

A.1 Supplying Power to 24 VDC Detectors and NACs


A.1.1 Resistance and Size
To determine the minimum resistance that can be tolerated in supplying power to 24 VDC 4-wire
devices and NACs, use the calculation below. Use this resistance to select the proper gauge wire for
the power run from the manufacturers specifications for the desired wire.
For Four-Wire Detectors:

(Vms - Vom)
Rmax =
(N)(Is) + (Na)(Ia) + (Ir)

For NACs:

(Vms - Vom)
Rmax =
(Nb)(Ib)

Where:
Rmax = maximum resistance of the 24 VDC wires
Vms = minimum supply voltage
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts
N = total number of detectors on the 24 VDC supply circuit
Is = detector current in standby
Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm
Ia = detector current in alarm
Ir = end-of-line relay current
Nb = number of Notification Appliance Devices
Ib = Notification Appliance current when activated

NOTE: This simplified equation assumes that the devices are at the end of a long wire run.

The minimum supply voltages produced by FireLite power supplies are listed below:
FACP Vms Power Supply Vms
MS-9200 16.0 FCPS-24F 19.1
MS-9600 16.0 FCPS-24FS6/FCPS-24FS8 19.1
MS-9200UD/MS-9200UDLS 19.05
MS-9050UD 18.75

Table A.1 Minimum Supply Voltage

68 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Supervising 24 VDC Power Power Considerations

A.2 Supervising 24 VDC Power


Power used to supply 24 VDC detectors, notification appliances (using the CMF-300), and two
wire detectors (using the MMF-302) can be supervised with a power supervision relay. This relay,
energized by the 24 VDC power itself, is installed at the end of each respective power run and
wired in-line with the supervised circuit of any intelligent module.
24 VDC power must be provided from a UL-listed power supply for fire protection use.
When power is removed from the relay, the normally closed contacts open the supervised circuit,
generating a trouble condition. Therefore, the relay needs to be installed at the end of the super-
vised circuit, so it will not disrupt the operating capability of all the devices on that circuit. The
relay can be installed in-line with any leg (+ or ) of the supervised NAC circuit, either a Style B
(Class B) or a Style D (Class A) circuit.
The drawing below illustrates this concept.
24 VDC Power from
Control Panel or
Power Supply
Last device on the SLC loop

Power Supervision
Relay
(EOLR-1)

SLC-psrtpH.cdr
Supervised NAC
ELR
47K
Figure A.1 Supervised 24 VDC Circuit

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 69


Power Considerations Supervising 24 VDC Power

An alternate method is shown below.

24 VDC Power from


Control Panel or Power Supply

CMF-300
ELR 47K

Power Supervision
Relay
(EOLR-1)

ELR 47K Supervised NAC

MMF-300

SLC-psr-2addresstpH.wmf
Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit

70 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Appendix B: Surge Suppression

B.1 Introduction
NOTE: Surge protection is not required in Canadian applications.

There are three (3) primary surge protectors that are approved for use with the MS-9200, MS-
9200UD, MS-9200UDLS, MS-9600, MS-9600LS, MS-9600UDLS, and MS-9050UD.
DTK-2LVLP-F Diversified Technology Group, Inc. 1720 Starkey Rd. Largo, FL 33771
(727) 812-5000
SLCP-30 EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
PLP-42N Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019
(800) 727-9119

NOTE: For detailed information, refer to the Installation Instructions supplied with the unit.

One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs
outside the building.
Install primary protection only as shown in this document.
Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional
suppressors in series with the SLC wiring at the building entry/exit.
Wiring connected to the surge suppressor output must remain within the building while wiring con-
nected to the surge suppressor input may be routed outside the building as shown below.
Building #2 Building #1

P P
FACP
P = Primary
S = Secondary S

P P S
SLC-ssbuild1.wmf

Surge Suppressor

Primary devices meet Secondary devices meet


NEC Requirements UL1459 (UL1950)

B.2 Installation
Mounting of the surge suppressor must be inside the FACP enclosure or in a separate enclosure
listed for fire protective signaling use.
Locate on an available stud and secure with nut.
Unit is connected in series with the SLC Loop to protect the Control Panel.
Provide a common ground to eliminate the possibility of a differential in ground potentials.

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 71


Surge Suppression Installation

B.2.1 Wiring Diagram for MS-9200


DTK-2LVLP-F Connections
2LVLP-F

Optional Four-wire Return Loop


Style 6 (Class A)

IN OUT
SLC Terminal Block

2LVLP-F A-
B-
A+
+
B+
A Shield

SLC-lvlp1.wmf
SLC Loop B Shield
IN OUT

PLP-42N Connections
PLP-42N
GRND
L4

L4

Optional Four-wire Return Loop


OUTPUT
L3
INPUT

L3

Style 6 (Class A)
L2

L2
L1

L1

SLC Terminal Block


PLP-42N A-
B-
GRND
L4

L4

A+
+

SLC-plpn1.wmf
OUTPUT
L3
INPUT

L3

B+
L2

A Shield
L2

SLC Loop
L1

B Shield
L1

NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect
the units ground terminal to equipment ground. Wire length must be minimized to provide best
protection.

SLCP-30 Connections
2LCP-30

Optional Four-wire Return Loop


Style 6 (Class A)

IN OUT
SLC Terminal Block
2LCP-30 A-
SLC Loop
B-
+ A+
SLC-slcp1.wmf

B+
A Shield
B Shield

IN OUT

72 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Installation Surge Suppression

B.2.2 Wiring Diagram for MS-9600, MS-9600LS, MS-9600UDLS,


MS-9200UD, MS-9200UDLS, and MS-9050UD
DTK-2LVLP-F Connections
2LVLP-F

Optional 4-wire Return Loop


Style 6 (Class A)

IN OUT

2LVLP-F SLC Terminal Block


+ B+
A+

SLC-lvlp4.wmf
B-
SLC Loop A-
IN OUT A Shield
B Shield

PLP-42N Connections
PLP-42N

GRND
L4

L4
Optional 4-wire Return Loop
OUTPUT
L3
INPUT

L3
Style 6 (Class A)
L2

L2
L1

L1

SLC Terminal Block

PLP-42N B+
A+
+
GRND
L4

B-
L4


OUTPUT
L3
INPUT

A-
L3

SLC-plpn4.wmf
A Shield
L2

L2

SLC Loop B Shield


L1

L1

NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect
the units ground terminal to equipment ground. Wire length must be minimized to provide best
protection.

SLCP-30 Connections
2LCP-30

Optional 4-wire Return Loop


Style 6 (Class A)

IN OUT
SLC Terminal Block
2LCP-30
SLC Loop
+ B+
A+
SLC-slcp4.wmf

B-
A-
A Shield
B Shield
IN OUT

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 73


Appendix C: Terminal Conversion Charts for New &
Legacy Devices

C.1 CRF-300

Common 2 Common 2
SLC - SLC -
Closed 2 Closed 2 SLC +
Open 2 SLC + Open 2
Common 1 Common 1
Closed 1 Open 1
Closed 1 Open 1

Legacy Module Newer Module


(V-Type) (H-Type)

Legacy Module Terminal Number Newer Module Terminal Number


Terminal Function
(V-Type) (H-Type)

1 SLC - 1

2 SLC + 2

3 Unused 3

4 Normally Open (1) 5

5 Normally Closed (1) 6

6 Relay Common (1) 7

7 Normally Open (2) 8

8 Normally Closed (2) 9

9 Relay Common (2) 10

N/A Unused 4

N/A Unused 11

Table C.1 CRF-300Terminal Conversions

74 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


CMF-300 and MMF-302 Terminal Conversion Charts for New & Legacy Devices

C.2 CMF-300 and MMF-302


All module polarities are shown in standby condition, which reflects the labels on the new mod-
ules.

A- VDC -
SLC - VDC + SLC -
A+ A- SLC +
B/A + SLC + A+
B/A - VDC - B/A +
VDC + B/A -

Legacy Module Newer Module


(V-Type) (H-Type)

Legacy Module Terminal Number Newer Module Terminal Number


Terminal Function
(V-Type) (H-Type)

1 SLC - 1

2 SLC + 2

3 VDC - 11

4 VDC + 10

5 Unused 5

6 Solenoid B/A - 6

7 Solenoid B/A + 7

8 Solenoid A + 8

9 Solenoid A - 9

N/A Unused 3

N/A Unused 4

Table C.2 CMF-300 and MMF-302 Terminal Conversions

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 75


Terminal Conversion Charts for New & Legacy Devices MMF-300

C.3 MMF-300

Class A Supervision -
SLC -
Class A Supervision+ SLC - Class A Supervision - SLC +
Class A/B Supervision + SLC + Class A Supervision+
Class A/B Supervision - Class A/B Supervision +
Class A/B Supervision -

Legacy Module Newer Module


(V-Type) (H-Type)

Legacy Module Terminal Number Newer Module Terminal Number


Terminal Function
(V-Type) (H-Type)

1 SLC - 1

2 SLC + 2

3 Unused 3

4 Unused 4

5 Unused 5

6 Class A/B Supervision - 6

7 Class A/B Supervision + 7

8 Class A Supervision + 8

9 Class A Supervision - 9

N/A Unused 10

N/A Unused 11

Table C.3 MMF-300 Terminal Conversions

76 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


MDF-300 Terminal Conversion Charts for New & Legacy Devices

C.4 MDF-300

Address +1 (H) - 9 6 7 8 910


0
5 SLC -
Address +1 (H) + 8
4
3
11
12 1 SLC -
2 13
Address +1 (H) - SLC +
Base Address (L) + 7 TENS
1 0 1514
2 SLC +
8 Address +1 (H) +
Base Address (L) - 6 6
3
4 Base Address (L) +
2
5 ONES
0 4 Base Address (L) -
LOOP
LOOP ADDRESS

Legacy Module
(V-Type) Newer Module
(H-Type)

Legacy Module Terminal Number Newer Module Terminal Number


Terminal Function
(V-Type) (H-Type)

1 SLC - 1

2 SLC + 2

3 Unused 3

4 Unused 4

5 Unused 5

6 Base Address (L) - 6

7 Base Address (L) + 7

8 Address +1 (H) + 8

9 Address +1 (H) - 9

N/A Unused 10

N/A Unused 11

Table C.4 MDF-300 Terminal Conversions

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 77


Appendix D: Intelligent Detector Base Layouts for
Legacy Devices

D.1 B350LP or B501 Detector Base


SLC +

Use a female disconnect


to wire the
RA100Z/RA400Z () to
2(+) Terminal 1 ().

3 1()
To next device
on SLC
+

B501 only: For connection of


cable shield
SLC-B501wire.wmf

RA100Z/
RA400Z
Remote LED
Annunciator
(Optional)
+

Figure D.1 Wiring the Legacy B350LP or B501 Detector Base

NOTE: The B350LP base wiring is identical to the B501, except there is no shield terminal.

78 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


B224BI Isolator Base Intelligent Detector Base Layouts for Legacy Devices

D.2 B224BI Isolator Base


SLC Out

SLC In

Conduit

SLC-224BIwire.wmf
I300
Isolator Module

Figure D.2 Wiring the Legacy B224BI Isolator Base

D.3 B224RB Relay Base

To next device
on SLC
For connection of
cable shield

3 Relay Common
2 Normally Open
1 Normally Closed
SLC
b224rb.wmf

Figure D.3 Wiring the Legacy B224RB Relay Base

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 79


Intelligent Detector Base Layouts for Legacy Devices B501BH(-2) and B501BHT(-2) Sounder Bases

D.4 B501BH(-2) and B501BHT(-2) Sounder Bases


UL-Listed
24V Power
Supply

+ -

Optional
Sounder
Interconnect

slc-b501bhwiring.wmf
SLC + SLC -

Figure D.4 Wiring the Legacy B501BH(-2) and B501BHT(-2) Sounder Bases

80 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Notes

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 81


Appendix E: Canadian Versions of SLC Devices
UL-listed SLC Device ULC-listed SLC Device Description
Detectors
AD350/AD355 AD350A/AD355A Intelligent detector that combines a photoelectric sensing chamber and fixed
temperature heat detection (135F/57.2C).
CP350/CP355 CP350A/CP-355A Addressable, intelligent smoke detector that incorporates an ionization sensing
chamber. Designed to provide open area protection.
SD350/SD355 SD350A/SD355A Addressable intelligent smoke detector that uses a photoelectric sensing
chamber. Listed for use in ducts. Designed to provide open area protection.
SD350T/SD355T SD350TA/SD355TA Adds thermal sensors that will alarm at a fixed temperature of 135F (57C).
H350/H355 H350A/H355A Intelligent thermistor sensing circuit for fast response. Designed to provide
open area protection with 50 foot spacing capability. A fixed temperature
sensor with 135F fixed temperature alarm.
H350R/H355R H350RA/H355RA Incorporates a thermal rate of rise of 15F (9.4C).
H355HT H355HTA High temperature sensor with 190F (87.8C) fixed temperature alarm.
DNR DNRA Photoelectric Duct Detector, Low-flow. Requires SD350(A)/SD355(A) detector.
Bases
B210LP B210LPA Standard U.S. Low-Profile base (6", 15.24 cm).
B501 B501A Standard European flangeless base (4", 10.16 cm).
B501BH, B501BHT B501BHA, B501BHTA Sounder base, includes Sounder base with temporal sounder (UL 8th Edition).
B501BH-2, B501BHT-2 N/A Sounder base, includes Sounder base with temporal sounder (UL 9th Edition).
B224RB B224RBA Low Profile Intelligent relay base.
B224BI B224BIA Low Profile Intelligent isolator base.
B200SR B200SRA Intelligent sounder base, temporal or steady.
B200SR-LF N/A Intelligent sounder base for low frequency applications
Monitor and Zone Interface Modules
MMF-300 MMF-300A Used for normally open contact alarm initiating devices, such as manual pull
stations, four-wire smoke detectors, heat detectors, waterflow, and supervisory
devices.
MMF-302 MMF-302A Used to interface with two-wire smoke detectors in addition to normally open
contacts.
MDF-300 MDF-300A Two independent 2-wire Initiating Device Circuits (IDCs) at two separate,
consecutive addresses. Wire supervised IDCs as NFPA Style B (Class B) or
Style D (Class A) circuits. The modules come with a thermoplastic cover for
mounting to a 4-inch (10.16 cm) square mounting box.
MMF-301 MMF-301A Functionally similar to the MMF-300 Monitor Module, but offered in a smaller
package for mounting directly in the electrical box of the device being
monitored. (Class B input circuit only.)
BG-12LX BG-12LX An addressable manual pull station with key-lock reset feature. The
addressable module is housed within the pull station.
Control Modules
CMF-300 CMF-300A Control Module, NAC: Addressable Control Module used as Notification
Appliance Circuits (NACs) to power and supervise compatible, UL-listed
notification appliances. Wired supervised NACs as NFPA Style Y (Class B) or
Style Z (Class A). The modules come with a thermoplastic cover for mounting
to a 4-inch (10.16 cm) square mounting box.
CRF-300 CRF-300A Relay Control Module is similar to the CMF-300(A) except used as a Form-C
control relay module.

82 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Canadian Versions of SLC Devices

UL-listed SLC Device ULC-listed SLC Device Description


Fault Isolator Module
I300 I300A The Fault Isolator Module protects the system against wire-to-wire short circuits
on the SLC. It should be placed between groups of sensors in a Style 6 or
Style 7 SLC to isolate short- and open-circuit problems and protect the rest of
the loop so it can continue to operate normally. It is not addressable, but listed
here due to its use in an SLC.
ISO-6 ISO-6A The Six Fault Isolator Module protects the system against wire-to-wire short
circuits on six isolated SLC circuits. Functionally the same as six I300 modules.
Multi-input/output modules
MMF-300-10 MMF-300-10A Supervises ten Class-B addressable Initiating Device Circuits (IDC) which
monitor normally open contact initiating devices.
MMF-302-6 MMF-302-6A Monitors six zones of conventional two-wire detectors.
CDRM-300 CDRM-300A Dual Class B monitor / Form-C relay module.
CMF-300-6 CMF-300-6A Similar in operation to the CMF-300, except it can activate six (6) Style Y
(Class B) or three (3) Style Z (Class A) NACs.
CRF-300-6 CRF-300-6A Similar in operation to the CRF-300, except it provides six (6) Form-C relays.

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 83


Index
Numerics CMF-300-6 Control Module 11, 46, 51, 52
24 VDC detectors 68 address disabling 49
address setting 48
24 VDC NAC power 46
circuit board 50
24 VDC power
installation 48
MS-9200, MS-9600 18
short circuit protection 49
Style selection 49
A wiring 51
AD350 Detector 11 common ground 71
AD355 Detector 11, 59 communication protocol 10
address capacity 23 conduit, close nippled 28
addressable connectors, crimp-on 72, 73
modules 11, 29 Control Modules 11
addressable devices 23 Overview 82
Addressable Modules (Overview) 82 control panel 8
Addressable Monitor Modules 29 CP350 Detector 12
Alarm Verification 59 CP355 12
analog intelligent devices 10 CP355 Detector 59
Authority Having Jurisdiction 13 CRF-300 Relay Module 11, 53
auxiliary devices 11 wiring 53
CRF-300-6 Relay Module 11, 53
B address disabling 55
address setting 55
B200SR Sounder Detector Base 59
circuit board 54
B200SR-LF Sounder Detector Base for Low Fre- wiring 54, 55
quency 59
B210LP 59
B224BI Isolator Detector Base 23, 59 D
B224RB Relay Detector Base 59 D350P Detector 12
B350LP Detector Base 78 D350RP Detector 12
B501 Detector Base 59, 78 D355PL detector 12
B501BH Sounder Detector Base 59 DC resistance 15, 16
B501BH-2 Sounder Detector Base 59 detector bases 59
B501BHT Temporal Sounder Detector Base 59 detector bases, wiring of 60
B501BHT-2 Temporal Sounder Detector Base 59 detectors 59
base 60, 61, 62 detector bases 82
BEAM355 12, 65 listing 12, 82
BEAM355S 12, 65 devices
BG-12LX 12, 67 addressable 23
building entry/exit 71 auxiliary 11
maximum number between isolators 23
C supervised 69
document sources 9
CDRM-300 57
drain wire 17
CDRM-300 Multiple Input/Output Module dry-contact 11
wiring 58 DTK-2LVLP-F 71
circuit fault 11 Dual Monitor Module 33
Classic Loop Interface Protocol 10
CLIP (Classic Loop Interface Protocol) 10
CLIP Mode 13 E
close nippled conduit 28 electrical interference 14
CMF-300 Control Module 11, 46, 47, 48 emergency signaling circuit 38
installation 46 End-of-Line Resistor 47, 51
wiring 47

84 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Index FP

F MMF-300-10 Monitor Module 11, 30, 39, 40


fault 13, 27 wiring 39
MMF-301 Mini Monitor Module 11, 33
fault condition 23
MMF-302 Zone Interface Module 11, 31, 42, 43
Fault Isolator Module 23
wiring 42
FCPS-24F 68
MMF-302-6 Interface Module 11, 32, 44, 45
Fire alarm service 33
wiring 44
foil 17
module circuits 29
Form-C contacts 57
modules
Form-C relay contacts 11, 53, 59
four-wire configuration 48, 52 addressable 11
control 11
isolator 11
G monitor 11
ground terminal 72, 73 relay 11
Monitor Modules 11, 29
H Overview 82
Multicriteria Detector 59
H350 Detector 12
multiple input/output module 57
H350R Detector 12
Multi-Point Module 35
H355 Detector 12, 59
H355HT Detector 12
H355R Detector 12 N
Heat Detector 59 NAC 11
NAC power 46, 69
I NAC wiring 46
NEC Article 800 71
I300 Isolator Module 11, 23
NFPA Style 4
Initiating Device Circuits 29, 36, 39, 41
wiring of 21
integral relay 23
with I300 25, 26
Ionization Detector 59
NFPA Style 6
ISO-6 Isolator Module 23
wiring of 22
ISO-6 Isolator module 11
with I300 27
isolator base 23
NFPA Style 7 23
isolator base, wiring of 61
with isolator modules 28
Isolator Module 11, 27, 28
NFPA Style B
how it works 23
IDC wiring 36, 39, 41, 42, 44
wiring of 24
NFPA Style D
IDC wiring 37, 40, 43, 45
K NFPA Style Y 46
key-lock reset 67 wiring of 47, 51
NFPA Style Z 46
wiring of 48, 52
L Nonresettable power 18
LEDs 59 normally closed contacts 69
LiteSpeed 10 Notification Appliance Circuit 11
local building code 71
loop resistance 15, 16
loops 16 O
older version and newer version modules 8, 9
M
MDF-300 Dual Monitor Module 11, 33, 41 P
wiring 41 performance 13
metal conduit 17, 27 Photoelectric Detector 59
Mini Monitor Module 33 PLP-42N 71
minimum resistance 68 Polling Protocols 10
MMF-300 Monitor Module 11, 29, 36, 37, 38 power run 68, 69
wiring 36 power supervision relay 47, 48, 51, 52, 69

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 85


RZ Index

power supplies 68 T-tapping 15, 21, 22, 27, 28


proper gauge wire 68 twisted-pair shielded wiring 14
pull station 12, 28 two-wire configuration 47, 51
wiring of 67 two-wire detectors 69

R U
RA100Z 60 Unregulated power 18
RA400Z 60
rate of rise 12 V
ratings, relay contact 46, 53, 57
verification cycle 59
relay base 23
wiring of 61
relay contact ratings 46, 53, 57 W
Relay Module 11 Waterflow alarm service, automatic and manual
relays 33
Form-C 11 W-GATE 12, 62
Remote LED Annunciator 60 external power 64
Resettable power 18 SLC connections 62
resistance 15, 16 SLC power 63
rotary switches 34, 40, 41, 42, 43, 44, 45, 59 wire length 15, 16
wire size 14
S wireless gateway 12, 62
SD350 Detector 12 external power 64
SLC connections 62
SD350T Detector 12
SLC power 63
SD355 Detector 12, 59
wiring
SD355R Detector 12
SD355T Detector 12 I300 24
ISO-6 24
sensing circuit, thermistor 12
MDF-300 41
short circuit 23
MMF-300 36
Signaling Line Circuit 10
MMF-300-10 39
Single Point Module 34
MMF-302 42
SLC address, setting of 34, 59
MMF-302-6 44
SLC connections 18
NACs 46
SLC terminal block 17
wiring pair 71
SLC wiring 36, 37, 38, 39, 40, 41, 42, 43, 44,
wiring requirements 14
45
wiring style requirements 13
SLCP-30 71
Smoke Detectors 59
sounder base 23 Z
sounder base, wiring of 62 Zone Interface Module 31
Sprinkler supervision 33
supervised
circuit 69
devices 69
supplying power 68
suppressors, surge 71
surge protector 10, 13, 71
switching 46

T
terminal blocks 18
termination of shield 17
Thermal Detector 59
thermistor sensing circuit 12
trouble conditions 13, 23

86 FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014


Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein,
Manufacturer warrants that the Products manufactured by it in its
Northford, Connecticut facility and sold by it to its authorized
Distributors shall be free, under normal use and service, from defects
in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The
Products manufactured and sold by Manufacturer are date stamped at
the time of production. Manufacturer does not warrant Products that
are not manufactured by it in its Northford, Connecticut facility but
assigns to its Distributor, to the extent possible, any warranty offered
by the manufacturer of such product. This warranty shall be void if a
Product is altered, serviced or repaired by anyone other than
Manufacturer or its authorized Distributors. This warranty shall also
be void if there is a failure to maintain the Products and the systems in
which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND
DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER
EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS,
TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY
MANUFACTURER INCLUDING WITHOUT LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR
ANY PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE
LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY
ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,
COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer
with respect to its products and replaces all previous warranties and is
the only warranty made by Manufacturer. No increase or alteration,
written or verbal, of the obligation of this warranty is authorized.
Manufacturer does not represent that its products will prevent any loss
by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at
Manufacturer's discretion, each part returned by its authorized
Distributor and acknowledged by Manufacturer to be defective,
provided that such part shall have been returned to Manufacturer with
all charges prepaid and the authorized Distributor has completed
Manufacturer's Return Material Authorization form. The replacement
part shall come from Manufacturer's stock and may be new or
refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND
EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.

Warn-HL-08-2009.fm

FireLite SLC Wiring Manual P/N 51309:P4 9/17/2014 87


World Headquarters
1 Firelite Place
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118

www.firelite.com

You might also like