Fire & Gas Panel PDF
Fire & Gas Panel PDF
SLC
Wiring Manual
Document 51309
9/17/2014
P/N 51309:P4
Rev: P4
ECN 14-790
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm systemtypically made up of smoke (caused by escaping gas, improper storage of flammable materi-
detectors, heat detectors, manual pull stations, audible warning als, etc.).
devices, and a fire alarm control panel (FACP) with remote notifi- Heat detectors do not sense particles of combustion and alarm
cation capabilitycan provide early warning of a developing fire. only when heat on their sensors increases at a predetermined
Such a system, however, does not assure protection against rate or reaches a predetermined level. Rate-of-rise heat detec-
property damage or loss of life resulting from a fire. tors may be subject to reduced sensitivity over time. For this
An emergency communication systemtypically made up of reason, the rate-of-rise feature of each detector should be tested
an automatic fire alarm system (as described above) and a life at least once per year by a qualified fire protection specialist.
safety communication system that may include an autonomous Heat detectors are designed to protect property, not life.
control unit (ACU), local operating console (LOC), voice commu- IMPORTANT! Smoke detectors must be installed in the same
nication, and other various interoperable communication meth- room as the control panel and in rooms used by the system for
odscan broadcast a mass notification message. Such a the connection of alarm transmission wiring, communications,
system, however, does not assure protection against property signaling, and/or power. If detectors are not so located, a devel-
damage or loss of life resulting from a fire or life safety event. oping fire may damage the alarm system, compromising its abil-
The Manufacturer recommends that smoke and/or heat ity to report a fire.
detectors be located throughout a protected premises following Audible warning devices such as bells, horns, strobes,
the recommendations of the current edition of the National Fire speakers and displays may not alert people if these devices
Protection Association Standard 72 (NFPA 72), manufacturer's are located on the other side of closed or partly open doors or
recommendations, State and local codes, and the are located on another floor of a building. Any warning device
recommendations contained in the Guide for Proper Use of may fail to alert people with a disability or those who have
System Smoke Detectors, which is made available at no charge recently consumed drugs, alcohol, or medication. Please note
to all installing dealers. This document can be found at http:// that:
www.systemsensor.com/appguides/. A study by the Federal An emergency communication system may take priority over
Emergency Management Agency (an agency of the United a fire alarm system in the event of a life safety emergency.
States government) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm systems are Voice messaging systems must be designed to meet intelligi-
designed to provide early warning against fire, they do not bility requirements as defined by NFPA, local codes, and
guarantee warning or protection against fire. A fire alarm system Authorities Having Jurisdiction (AHJ).
may not provide timely or adequate warning, or simply may not Language and instructional requirements must be clearly dis-
function, for a variety of reasons: seminated on any local displays.
Smoke detectors may not sense fire where smoke cannot Strobes can, under certain circumstances, cause seizures in
reach the detectors such as in chimneys, in or behind walls, on people with conditions such as epilepsy.
roofs, or on the other side of closed doors. Smoke detectors Studies have shown that certain people, even when they hear
also may not sense a fire on another level or floor of a building. a fire alarm signal, do not respond to or comprehend the
A second-floor detector, for example, may not sense a first-floor meaning of the signal. Audible devices, such as horns and
or basement fire. bells, can have different tonal patterns and frequencies. It is
Particles of combustion or smoke from a developing fire the property owner's responsibility to conduct fire drills and
may not reach the sensing chambers of smoke detectors other training exercises to make people aware of fire alarm
because: signals and instruct them on the proper reaction to alarm sig-
Barriers such as closed or partially closed doors, walls, chim- nals.
neys, even wet or humid areas may inhibit particle or smoke In rare instances, the sounding of a warning device can cause
flow. temporary or permanent hearing loss.
Smoke particles may become cold, stratify, and not reach A life safety system will not operate without any electrical
the ceiling or upper walls where detectors are located. power. If AC power fails, the system will operate from standby
Smoke particles may be blown away from detectors by air batteries only for a specified time and only if the batteries have
outlets, such as air conditioning vents. been properly maintained and replaced regularly.
Smoke particles may be drawn into air returns before reach- Equipment used in the system may not be technically compat-
ing the detector. ible with the control panel. It is essential to use only equipment
listed for service with your control panel.
The amount of smoke present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at var- Telephone lines needed to transmit alarm signals from a prem-
ious levels of smoke density. If such density levels are not cre- ises to a central monitoring station may be out of service or tem-
ated by a developing fire at the location of detectors, the porarily disabled. For added protection against telephone line
detectors will not go into alarm. failure, backup radio transmission systems are recommended.
Smoke detectors, even when working properly, have sensing The most common cause of life safety system malfunction is
limitations. Detectors that have photoelectronic sensing cham- inadequate maintenance. To keep the entire life safety system in
bers tend to detect smoldering fires better than flaming fires, excellent working order, ongoing maintenance is required per the
which have little visible smoke. Detectors that have ionizing-type manufacturer's recommendations, and UL and NFPA stan-
sensing chambers tend to detect fast-flaming fires better than dards. At a minimum, the requirements of NFPA 72 shall be fol-
smoldering fires. Because fires develop in different ways and lowed. Environments with large amounts of dust, dirt, or high air
are often unpredictable in their growth, neither type of detector is velocity require more frequent maintenance. A maintenance
necessarily best and a given type of detector may not provide agreement should be arranged through the local manufacturer's
adequate warning of a fire. representative. Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be per-
Smoke detectors cannot be expected to provide adequate warn- formed by authorized professional life safety system installers
ing of fires caused by arson, children playing with matches only. Adequate written records of all inspections should be kept.
(especially in bedrooms), smoking in bed, and violent explosions Limit-D-1-2013
This system meets NFPA requirements for operation at 0-49 This system contains static-sensitive components.
C/32-120 F and at a relative humidity 93% 2% RH (non- Always ground yourself with a proper wrist strap before han-
condensing) at 32C 2C (90F 3F). However, the useful dling any circuits so that static charges are removed from the
life of the system's standby batteries and the electronic com- body. Use static suppressive packaging to protect electronic
ponents may be adversely affected by extreme temperature assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this Follow the instructions in the installation, operating, and pro-
system and its peripherals be installed in an environment with gramming manuals. These instructions must be followed to
a normal room temperature of 15-27 C/60-80 F. avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation.
cating device loops. Most devices cannot tolerate more than a Precau-D1-9-2005
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.
LiteSpeed is a trademark; and FireLite Alarms is a registered trademark of Honeywell International Inc. Microsoft and Windows are registered
trademarks of the Microsoft Corporation.
2014 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our
online Help or printed manuals, you can email us.
Please include the following information:
Product name and version number (if applicable)
Printed manual or online Help
Topic Title (for online Help)
Page number (for printed manual)
Brief description of content you think should be improved or corrected
Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
NOTE: Any reference in this manual to the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600,
MS-9600LS, MS-9600UDLS, or MS-9050UD includes the MS-9200E, MS-9200UDE,
MS-9200UDLSE, MS-9200UDLSC, MS-9600E, MS-9600LSE, MS-9600LSC, MS-9600UDLSE,
MS-9050UDC, or MS-9050UDE respectively unless otherwise specified.
Additional information about the specific control panel and the modules and detectors referenced in
this document can be found in the respective installation manual as listed in Table 1.1, Reference
Documentation.
Currently, there are two styles of modules available, legacy version and newer version. The obvious
difference between the two styles is the orientation of the rotary dials. Refer to the diagram below
for an example of each.
CMF-300 CMF-300
Legacy Version Module Newer Version Module
(Vertical Rotary Dial) (Horizontal Rotary Dial)
NOTE: Only the MMF-300, MMF-302, CRF-300, CMF-300, and MDF-300 modules are available
as newer type modules. Both the legacy and newer versions share the same part numbers. The
newer version modules will be phased in, replacing the legacy version. This manual contains
information and wiring diagrams for the newer version of the modules. Refer to Terminal
Conversion Charts for New & Legacy Devices on page 74 for additional information.
Currently, there are two styles of detector bases available, legacy version and newer version. The
obvious difference between the two styles is the orientation of the screw terminals. Refer to
Section 9 and Appendix D for an illustration of each.
NOTE: Only the B501 Detector Base, B210LP Detector Base (replacement base for B350LP),
B224RB Relay Base, and B224BI Isolator Base are available as newer type bases. Both the
legacy and newer versions share the same part numbers. The newer version bases will be
phased in, replacing the legacy version. This manual contains information and wiring diagrams for
the newer version of the bases. Refer to Intelligent Detector Base Layouts for Legacy Devices
on page 78 for additional information.
1.2 Overview
Communication between the control panel and intelligent addressable monitor and control devices
takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of
NFPA Style 4, Style 6, or Style 7.
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC
wiring runs outside the building. For detailed information refer to Surge Suppression on page 71.
NOTE: FACPs with more than one SLC loop must be programmed for only LiteSpeed or CLIP
mode of operation. Communication protocols cannot be split between SLC loops.
When switching between polling protocols, the loop circuit must be powered down for at least 30
seconds to reset the devices.
1.4 Devices
1.4.1 Isolator Modules
Isolator Modules permit a zone of detectors and modules to be fault isolated from the remainder of
the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator
modules are required to meet the requirements of an NFPA Style 7 circuit.
I300 - Single fault isolator module
ISO-6 - Six fault isolator module
CP350 - An addressable ionization smoke detector which measures the level of combustion
products in its chamber using the ionization principle.
CP355 - An addressable ionization smoke detector which measures the level of combustion
products in its chamber using the ionization principle.
D350P - An addressable photoelectric duct detector. The D350RP includes an alarm relay. Air
velocity rating is 500 to 4,000 feet per minute.
D350PL -An addressable low flow photoelectric duct detector (D350PLA for Canada). The
D350RPL includes an alarm relay (D350RPLA for Canada). Low Flow refers to the air velocity
rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec).
D355PL - An addressable non-relay photoelectric low flow smoke detector. Low Flow refers to
the air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec).
H3501 - An addressable detector using a thermistor sensing circuit for fast response. H350R
incorporates a thermal rate of rise of 15F (9.4C)/minute.
H3551 - An addressable 135 fixed temperature heat detector using a thermistor sensing circuit for
fast response. H355R incorporates a thermal rate of rise of 15 F (9.4 C)/minute.
H355HT1 - An addressable 190 fixed temperature heat detector using a thermistor sensing circuit
for fast response.
SD350 - An addressable photoelectric smoke detector which provides smoke sensing utilizing
optical sense technology. The SD350T includes a 135 F fixed thermal sensor.
SD355 - An addressable photoelectric smoke detector which provides smoke sensing utilizing
optical sense technology. The SD355T includes a 135 F fixed thermal sensor. The SD355R is a
low profile, intelligent, photoelectric sensor that is remote test capable.
BEAM355 - An addressable long range projected beam smoke detector designed to provide open
area protection. The BEAM355S has an integral sensitivity test feature that consists of a test filter
attached to a servomotor inside the detector optics.
DNR(W) - Innovair Flex, intelligent, non-relay, low flow, photoelectric duct detector housing.
This requires the SD355R photoelectric smoke detector. Accomodates the installation of the CRF-
300 relay module. The DNRW is a watertight housing.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the
Federal Communications Commission (FCC) requirements of the United States Government. It
has not been evaluated for use outside the USA. Use of this system outside the USA is subject to
local laws and rules to which this product may not conform. It is the sole responsibility of the user
to determine if this product may be legally used outside the USA.
NOTE: SLC operation meeting Style 7 requirements isolates each device on the SLC from faults
that may occur within other areas of the SLC.
Wiring style requirements are determined by national and local codes. Consult with the Authority
Having Jurisdiction before wiring the SLC. The table below (derived from NFPA 72-1999) lists
the trouble conditions that result when a fault exists on an SLC.
Type of Fault Style 4 Style 6 Style 7
Single Open Trouble Alarm, Trouble Alarm, Trouble
Single Ground Alarm, Trouble (ground) Alarm, Trouble (ground) Alarm, Trouble (ground)
Short Trouble Trouble Alarm, Trouble
Short and open Trouble Trouble Trouble
Short and ground Trouble Trouble Alarm, Trouble
Open and ground Trouble Alarm, Trouble Alarm, Trouble
Communications loss Trouble Trouble Trouble
Trouble - The control panel will indicate a trouble condition for this type of fault.
Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.
10,000 feet (3,048 m) 12 AWG (3.1 mm2) Belden 9583, Genesis 4410,
Signal 98230, WPW D999
8,000 feet (2,438 m) 14 AWG (2.0 mm2) Belden 9581, Genesis 4408,
Signal 98430, WPW D995
Twisted-pair, shielded 4,875 feet (1,486 m) 16 AWG (1.3 mm2) Belden 9575, Genesis 4406, &
4606, Signal 98630, WPW
D991
3,225 feet (983 m) 18 AWG (0.75 mm2) Belden 9574, Genesis 4402 &
4602, Signal 98300, WPW
D975
MS-9200 = 1,000 feet (305 m)
Short Point
SLC Out
SLC-meas1.wmf
Branch
SLC-meas2.wmf
SLC Terminal
Block
SLC Out
SLC-meas3.wmf
Short Point
SLC Return
SLC Terminal
Block B+ B A A+
NOTE: Use of good wiring practice consistent with local electrical codes is expected.
CAUTION: DO NOT LET THE SHIELD DRAIN WIRE OR THE SHIELD FOIL TOUCH THE
! SYSTEM CABINET OR BE CONNECTED TO EARTH GROUND AT ANY POINT.
MS-9600
MS-9600LS
MS-9600UDLS
MS-9200UD
MS-9200UDLS
MS-9050UD MS-9200
Shield Drain Wire
Cabinet
SLC-shieldterm.wmf
Shield Foil
Conduit
2.4.1 MS-9200
TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable.
TB6 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
Unregulated Power
Nonresettable Power
Resettable Power
Connections for wire shield
SLC-9200tb.wmf
SHIELD SLC SLC
TB4
TB6
SLC
Return
SLC Out
TB3 TB8
SLC Return
SLC Out
SLC
SLC-9200udtb.wmf
TB1
TB10
SLC Return
SLC Out
SLC
SLC-9200udtb.wmf
TB1
TB10
SLC Return
SLC Out
2.4.5 MS-9050UD
24 VDC power may be supplied by a remote power supply such as the Fire-Lite FCPS-24FS6/8.
TB2 provides connections for the SLC wiring.
50 addresses are available (any combination of detectors and modules).
SLC-9050udtb.wmf
SLC Return
SLC Out
3.1 Overview
This chapter concerns itself with the two styles of circuits that do not require isolation devices:
NFPA Style 4
NFPA Style 6
Addressable Module
T-tapped Circuits
B+ B
SLC-style4.wmf
Control Panel
SLC
SLC Out
Addressable Module
SLC Return
SLC-style6.cdrwmf
B+ B A A+
Control Panel
SLC
IN (-)
IN (+)
OUT (-)
OUT (+)
SLC-isowire2.wmf
SLC
Isolated branch
of the SLC
+
iso-6wire.wmf
ISOLATOR 1
-
SLC out to +
next device -
Isolator Module
Two-wire Addressable Detector
Isolated Branch
Isolator Module
Isolated Branch
Isolator Module
Isolated Branch
SLC-style4iso.wmf
B B+ Control Panel
SLC
A variation of a Style 4 operation using an ISO-6 isolator module to protect each branch of the SLC
is shown below. Each terminal on the ISO-6 acts as a single I300 module. Refer to Figure 4.2 for
ISO-6 wiring and to Section 4.1 for limitations. Note that the ISO-6 cannot accept two wires at one
pin. Wire Style 4 SLC loops as shown in the figure below.
Out +
In -
In + Isolated Branch
Addressable Pull Station
ISOLATOR 2
ISOLATOR 3
Isolated Branch
ISOLATOR 4
ISOLATOR 5
Isolated Branch
SLC-style4ISO-6.wmf
ISOLATOR 6
Control Panel
SLC
ISO-6
Isolator Isolator
Module Module
Section B
Two-wire
Addressable Section C
Detector
Addressable
Pull Station
Section A
Isolator Isolator
Module Module
Control Panel
1 3 1 3
Isolator Isolator
Module Module
Two-wire
Addressable
Detector
3 4 2 1
Isolator Isolator
Module Module
Two-Wire
Addressable
Addressable
Pull Station
Detector
3 4 2 1
Isolator Isolator
Module Module
3 4 2 1
Isolator Isolator
Module Module
SLC Out SLC Return
SLC-style7iiso.wmf
Control Panel
5.1 Descriptions
These addressable modules monitor conventional contact-type alarm initiating devices. You can
configure module circuits as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Cir-
cuits (IDC). There is no limit to the number of contact-type devices installed on a monitor module
circuit.
NOTE: For more information on the individual module specifications refer to the Installation
Instructions that are provided with these devices.
SLC
IDC Return Rotary
SLC+
Switches
IDC Return +
IDC Out +
FMMtpH.wmf
IDC Out -
mmf-300-10.wmf
24 VDC
24 VDC + SLC
Rotary
IDC Return SLC+ Switches
IDC Return +
IDC Out +
IDC Out -
FZMtpH.wmf
Areas used to record the device
address and SLC number.
T1 T2 T3 T4
T0
+ + + + + + + + + +
T6 T5
A/B SELECT
A/B SELECT
DISABLE 2
DISABLE 1
4
3
2
5
1 0
6 7 8 9
BASE ADDRESS
15 14
J1
13
10
12
11
SW1
4
3
2
5
10
6 7 8 9
BASE ADDRESS +0 BASE ADDRESS +1 BASE ADDRESS +2 BASE ADDRESS +3 BASE ADDRESS +4 BASE ADDRESS +5
SLC Address
Disable Address Set rotary switches to base
Place shunt in: (first) address of modules
Disable 1 position to disable highest module address
Disable 2 position to disable highest two module addresses
Rotary
Switches
Address +1 { 89 H+
H
SLC
7L+ SLC+
Base Address { 6L
fmmtph.wmf
Areas used to record the device
address and SLC number.
5.2 Installation
When installing any of these modules DO NOT mix the following services that the IDC provides:
Fire alarm service
Automatic and manual waterflow alarm service with normally open contact devices
Sprinkler supervision with normally open contact devices
NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-
9600UDLS can support module addresses 01 - 159. The plastic stop located on the Tens switch
must be removed to set addresses above 99.
To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired
address. The module below is set at 35. When finished, mark the address on the module face in
the place provided.
SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
6 7 8 910 6789
5 5
4 11 4 Breakaway Tab - Modules come with
3 12 3 a raised breakaway tab on the TENS
2 13 2 rotary switch. This tab must be
1 0 1514 10 removed when the module is on an
TENS ONES FACP that uses more than 99
addresses.
Modules with Rotary
Switches in
horizontal position
Modules with
Rotary Switches Dual monitor modules: On dual monitor modules, only even
in vertical numbers appear on the ONES rotary switch. The module takes
position both the selected address and the next-higher address.
NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-
9600UDLS can support module addresses 01 - 159 (the plastic stop located on the Tens switch
must be removed to set addresses above 99).
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to
the desired address. The module below is set at 28.
4
3
2
5
10
6 7 8 9
TENS
15 14
13
10
Plastic Stop
12
11
Rotary Switches
4
3
2
multroty.wmf
10
6 7 8 9
ONES
From Supply
24 VDC
Four-wire
Detector Base 24 VDC Power
Filtered, Regulated,
Resettable
Manual pull
station
To Next IDC
or
47K ELR
Supervision Device
(supplied
with module)
SLC
Heat
detector MMF-300
SLC-idcB1tpH.wmf
IDC
From
Supply
24 VDC
Four-wire
24 VDC Power
Detector Base
Filtered, Regulated,
Resettable
Manual pull
station
To Next IDC
or
Supervision Device
SLC
Heat MMF-300
detector
SLC-idcD1tpH.wmf
IDC
47K ELR
(supplied
with module)
SLC + -
- +
UL-listed Signaling
applicance such as the
Fire-Lite FSS-2400E
IDC
SLC-emer.wmf
MMF-300 Module
programmed for Tornado,
Hazard, or Medical operation.
Refer to the control panel
installation manual.
24 VDC Power
Filtered, Regulated, Resettable
24 VDC Four-wire
Detector Base
IDC
Out
SLC MMF-300-10
SLC-idcB4.wmf
24 VDC Power
Filtered, Regulated, Resettable
Heat
Manual Pull Detector
24 VDC Four-wire Station
Detector Base
IDC IDC
Return Out
SLC MMF-300-10
SLC-idcD3.cdwmf
Manual Manual
Pull Pull
Station Station
SLC-idcB3fdm1tph.wmf
T8 T3
T7 T4
T6 T5
MMF-302
IDC
SLC-idcB2tpH.wmf
Two-wire
smoke 24 VDC Resettable power.
detectors 90 mA External 24 volt supply required
SLC
MMF-302
IDC
SLC-idcD2tpH.wmf
3.9K ELR
(supplied with module)
IDC
Out
SLC MMF-302-6
SLC-idcB5.wmf
IDC IDC
Return Out
SLC MMF-302-6
SLC-idcD4.wmf
6.1 Description
The CMF-300 and CMF-300-6 modules are addressable modules that can be used for monitoring
and switching 24 VDC Notification Appliance Circuit (NAC) power for NFPA Style Y (Class B)
and NFPA Style Z (Class A) circuits.
Ratings for the relay contacts on the module are:
Load Description Application Maximum Voltage Current Rating
NOTE: For more information on module specifications, refer to the Installation Instructions
provided with these devices.
SLC-nacY.wmf
NAC
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and
relays.
CMF-300
24 VDC
notification
appliances
NAC Return
NAC Out
SLC-nacZtpH.wmf
Note: Module polarities are shown in alarm condition.
In Style Z operation alternate module points are paired together, resulting in a total of three mod-
ule points. For example, if the base address is set to 28, then 30 and 32 will be automatically
assigned to the remaining module points and 29, 31 and 33 are available to be used for other mod-
ules on the SLC.
DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for the MS-9200, MS-
9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent
addresses.
NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, MS-9600LSC,
and MS-9600UDLS can support module addresses 01 - 159.
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to
the desired address. See Figure 6.4 on page 50.
NOTE: For use with the MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS, remove the
stop on the upper rotary switch.
A/B SELECT
DISABLE 3
DISABLE 2
DISABLE 1
three (3) unused module addresses. If two module addresses are disabled,
the lowest four addresses will be functional, while the highest two will be
disabled. For example, if the shunt is placed on DISABLE 2 and the base
address is set to 28, the module addresses will be assigned to 28, 29, 30
and 31.
SLC-disable1.wmf
In Style Z operation, placing a small shunt on DISABLE 3 will disable
all three addresses. Placing it on DISABLE 2 will disable two out of
three addresses. J1
To disable addresses, securely place one of the supplied small shunts onto
the desired set of pins. See drawing and Figure 6.4 on page 50.
#1 #2 #3 #4 #5 #6
Status Indicators
Green LEDs are
CMF-300-6.wmf
controlled by FACP to
indicate status of each
module address.
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and
relays.
24 VDC
nonresettable
power
ELR 47K,
1/2-watt 24 VDC notification appliances
+
NAC Out
SLC
Relay Connector Assembly +
CMF-300-6
T0
+0 + + + + + + + + + +
T1 T2 T3 T4 T5
+ +
SLC-nacY2.wmf
+1 +2 +3 +4 +5
T12 T13 T14 T15
T10 T11 T16
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and
relays.
Power Supervision
Relay
(EOLR-1)
24 VDC
nonresettable
power
NAC
Out
SLC
NAC
Return
CMF-300-6
SLC-nacZ3.cwmf
7.1 Description
The CRF-300 and the CRF-300-6 modules are addressable modules that provides Form-C relay
contacts.
Ratings for the relay contacts on the module are:
Maximum Current
Load Description Application
Voltage Rating
NOTE: For more information on the module specifications refer to the Installation Instructions
provided with these devices.
CRF-300
C
NC
NO
C
NC NO
SLC-frmCtpH.wmf
T102
COMM
COMM
COMM
N.O.
N.C.
COMM
N.O.
N.C.
COMM
N.O.
N.C.
N.O.
N.C.
N.O.
N.C.
BASE ADDRESS +0 BASE ADDRESS +1 BASE ADDRESS +2 BASE ADDRESS +4 BASE ADDRESS +5
THREE
NONE
TWO
ONE
ADDRESS
DISABLE
Disable Address
Place shunt onto
required pins.
crf-300-6.wmf
Status Indicators
Green LEDs are
controlled by FACP to
indicate status of each
module address.
SLC Address
Set rotary switches to
address required.
NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-
9600UDLS can support module addresses 01 - 159. To set an SLC address, use a common
screwdriver to adjust the rotary switches on the module to the desired address. See Figure 6.4 on
page 50.
For use with an MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS, remove the stop on
the upper rotary switch.
SLC-disable2.wmf
is set to 28, the module addresses will be assigned to 28, 29, 30 and 31.
To disable addresses, remove the shunt from its storage location and
securely place it onto the desired set of pins. See illustration. J1
Shunt Storage
Location
CRF-300-6
+ +
SLC-fmC1.wmf
8.1 Description
The CDRM-300 is an addressable module that functions as two individual relay control modules
(two isolated sets of Form-C relay contacts) and two Class B monitor modules.
Ratings for the relay contacts on the module are:
Maximum Current
Load Description Application
Voltage Rating
NOTE: For more information on the module specifications refer to the Installation Instructions
provided with these devices.
NC
C
NO IDC 1 (+)
NC IDC 1 (-)
C IDC 2 (+)
NO IDC 2 (-)
fdrm-1.wmf
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open
9.1 Description
The following bases provide connection between the SLC and these detector heads:
AD350 and AD355 Multi-criteria Photoelectric Smoke Detector
CP350 and CP355 Ionization Smoke Detector
H350, H350R, H355, H355R and H355HT Thermal Detector
SD350, SD350T, SD355 and SD355T Photoelectric Smoke Detector
The B501 and B210LP bases are standard plug-in detector bases.
The B501BH, B501BHT, B501BH-2, B501BHT-2, B200SR, and B200SR-LF Sounder Detector
Bases include a horn that will sound when the sensors visible LEDs are latched on for approxi-
mately 10 seconds.
On the MS-9200 Control Panel, the sounder will activate when the sensors visible LEDs are
latched on for approximately 10 seconds (Alarm Verification does not delay sounder).
If the MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, or MS-9050UD
Control Panel is set with Alarm Verification ON, the sounder will activate at the end of the
verification cycle, providing an alarm is verified, approximately 10 seconds after the sensors
LEDs are latched on. If Alarm Verification is OFF, the sounder will activate when the sensors
visible LEDs are latched on for approximately 10 seconds.
The B224RB Relay Detector Base includes Form-C latching relay contacts for the control of an
auxiliary function. The relay operates 12 seconds (nominally) after activation of the sensor head
remote annunciator output.
The B224BI Isolator Detector Base prevents an entire communications loop from being disabled
when a short circuit occurs.
The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a
LiteSpeed SLC loop on the MS-9200UDLS. The gateway can be powered by the SLC loop or by a
regulated, external UL-listed, 24VDC power supply. See Section 9.7.
NOTE: When using a Wireless Gateway on the SLC loop, the panel cannot have ANY modules
(wired or wireless) in the address range from 140 to 159.
For details about the wireless network and its devices, see the SWIFT Smart Wireless Integrated
Fire Technology Instruction Manual #LS10036-000FL-E.
To Next Device
on SLC
+
RA100Z /
RA400Z
SLC-B5012wire.wmf
Remote LED
Annunciator
(Optional)
+
NOTE: The B210LP base wiring is identical to the B501. B501 is the flangeless model.
SLC In
+
Conduit
slc-224bi2wire.wmf
I300 Isolator Module
Normally Closed
Common
Normally Open
slc-b224rb2wire.wmf
+-
SLC
Optional Sounder
Interconnect
slc-b200srwire.wmf
+ -
UL-Listed
24V Power
+- Supply
SLC
NOTE: For more detailed wiring on the sounder base, refer to the devices installation instructions.
NOTE: It is recommended to use the same wire gauge if there are multiple connections to the
same terminal.
2.4.wmf
Figure 9.5 W-GATE Mounting Plate - Terminal Layout
Jumpers
2.5.wmf
2.6.wmf
SLC in from FACP/device
10.1 Description
The BEAM355 and BEAM355S are intelligent, addressable projected beam smoke detectors,
designed for protecting open areas with high and sloping ceilings and wide-open areas, where spot
type smoke detectors are difficult to install and maintain. The BEAM355S has an integral sensitiv-
ity test feature that consists of a test filter attached to a servomotor inside the detector optics.
NOTE: This section provides basic wiring and addressing information. For critical information
on device installation, operation and alignment, refer to the Installation Instructions provided with
these devices.
Alignment Mirror
Alignment Gunsight Digital Signal
Strength Readout
Alignment Position
Indicator
Horizontal Adjustment
Optics Lock-down
Screws
Alignment Switch
Sensitivity Switch
ONES
ADDRESSING
SWITCHES
CODE
Test Switch
TENS
Vertical Adjustment
Reset Input
Test Input
Aux (-)
RTS151/KEY& RTS-451/KEY
Connections
11.1 Description
The BG-12LX is an addressable manual pull station with a key-lock reset feature.
NOTE: For more information refer to the Installation Instructions provided with this device.
11.2 Installation
11.2.1 Setting an SLC address
Each unit is factory preset with an address of 00. To set an SLC address refer to Setting an SLC
address for a Single Point Module on page 34.
To next device
+ on SLC
SLC +
US PAT 4440991
SLC-bg12lx2.wmf
(Vms - Vom)
Rmax =
(N)(Is) + (Na)(Ia) + (Ir)
For NACs:
(Vms - Vom)
Rmax =
(Nb)(Ib)
Where:
Rmax = maximum resistance of the 24 VDC wires
Vms = minimum supply voltage
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts
N = total number of detectors on the 24 VDC supply circuit
Is = detector current in standby
Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm
Ia = detector current in alarm
Ir = end-of-line relay current
Nb = number of Notification Appliance Devices
Ib = Notification Appliance current when activated
NOTE: This simplified equation assumes that the devices are at the end of a long wire run.
The minimum supply voltages produced by FireLite power supplies are listed below:
FACP Vms Power Supply Vms
MS-9200 16.0 FCPS-24F 19.1
MS-9600 16.0 FCPS-24FS6/FCPS-24FS8 19.1
MS-9200UD/MS-9200UDLS 19.05
MS-9050UD 18.75
Power Supervision
Relay
(EOLR-1)
SLC-psrtpH.cdr
Supervised NAC
ELR
47K
Figure A.1 Supervised 24 VDC Circuit
CMF-300
ELR 47K
Power Supervision
Relay
(EOLR-1)
MMF-300
SLC-psr-2addresstpH.wmf
Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit
B.1 Introduction
NOTE: Surge protection is not required in Canadian applications.
There are three (3) primary surge protectors that are approved for use with the MS-9200, MS-
9200UD, MS-9200UDLS, MS-9600, MS-9600LS, MS-9600UDLS, and MS-9050UD.
DTK-2LVLP-F Diversified Technology Group, Inc. 1720 Starkey Rd. Largo, FL 33771
(727) 812-5000
SLCP-30 EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
PLP-42N Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019
(800) 727-9119
NOTE: For detailed information, refer to the Installation Instructions supplied with the unit.
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs
outside the building.
Install primary protection only as shown in this document.
Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional
suppressors in series with the SLC wiring at the building entry/exit.
Wiring connected to the surge suppressor output must remain within the building while wiring con-
nected to the surge suppressor input may be routed outside the building as shown below.
Building #2 Building #1
P P
FACP
P = Primary
S = Secondary S
P P S
SLC-ssbuild1.wmf
Surge Suppressor
B.2 Installation
Mounting of the surge suppressor must be inside the FACP enclosure or in a separate enclosure
listed for fire protective signaling use.
Locate on an available stud and secure with nut.
Unit is connected in series with the SLC Loop to protect the Control Panel.
Provide a common ground to eliminate the possibility of a differential in ground potentials.
IN OUT
SLC Terminal Block
2LVLP-F A-
B-
A+
+
B+
A Shield
SLC-lvlp1.wmf
SLC Loop B Shield
IN OUT
PLP-42N Connections
PLP-42N
GRND
L4
L4
L3
Style 6 (Class A)
L2
L2
L1
L1
L4
A+
+
SLC-plpn1.wmf
OUTPUT
L3
INPUT
L3
B+
L2
A Shield
L2
SLC Loop
L1
B Shield
L1
NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect
the units ground terminal to equipment ground. Wire length must be minimized to provide best
protection.
SLCP-30 Connections
2LCP-30
IN OUT
SLC Terminal Block
2LCP-30 A-
SLC Loop
B-
+ A+
SLC-slcp1.wmf
B+
A Shield
B Shield
IN OUT
IN OUT
SLC-lvlp4.wmf
B-
SLC Loop A-
IN OUT A Shield
B Shield
PLP-42N Connections
PLP-42N
GRND
L4
L4
Optional 4-wire Return Loop
OUTPUT
L3
INPUT
L3
Style 6 (Class A)
L2
L2
L1
L1
PLP-42N B+
A+
+
GRND
L4
B-
L4
OUTPUT
L3
INPUT
A-
L3
SLC-plpn4.wmf
A Shield
L2
L2
L1
NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect
the units ground terminal to equipment ground. Wire length must be minimized to provide best
protection.
SLCP-30 Connections
2LCP-30
IN OUT
SLC Terminal Block
2LCP-30
SLC Loop
+ B+
A+
SLC-slcp4.wmf
B-
A-
A Shield
B Shield
IN OUT
C.1 CRF-300
Common 2 Common 2
SLC - SLC -
Closed 2 Closed 2 SLC +
Open 2 SLC + Open 2
Common 1 Common 1
Closed 1 Open 1
Closed 1 Open 1
1 SLC - 1
2 SLC + 2
3 Unused 3
N/A Unused 4
N/A Unused 11
A- VDC -
SLC - VDC + SLC -
A+ A- SLC +
B/A + SLC + A+
B/A - VDC - B/A +
VDC + B/A -
1 SLC - 1
2 SLC + 2
3 VDC - 11
4 VDC + 10
5 Unused 5
6 Solenoid B/A - 6
7 Solenoid B/A + 7
8 Solenoid A + 8
9 Solenoid A - 9
N/A Unused 3
N/A Unused 4
C.3 MMF-300
Class A Supervision -
SLC -
Class A Supervision+ SLC - Class A Supervision - SLC +
Class A/B Supervision + SLC + Class A Supervision+
Class A/B Supervision - Class A/B Supervision +
Class A/B Supervision -
1 SLC - 1
2 SLC + 2
3 Unused 3
4 Unused 4
5 Unused 5
8 Class A Supervision + 8
9 Class A Supervision - 9
N/A Unused 10
N/A Unused 11
C.4 MDF-300
Legacy Module
(V-Type) Newer Module
(H-Type)
1 SLC - 1
2 SLC + 2
3 Unused 3
4 Unused 4
5 Unused 5
8 Address +1 (H) + 8
9 Address +1 (H) - 9
N/A Unused 10
N/A Unused 11
3 1()
To next device
on SLC
+
RA100Z/
RA400Z
Remote LED
Annunciator
(Optional)
+
NOTE: The B350LP base wiring is identical to the B501, except there is no shield terminal.
SLC In
Conduit
SLC-224BIwire.wmf
I300
Isolator Module
To next device
on SLC
For connection of
cable shield
3 Relay Common
2 Normally Open
1 Normally Closed
SLC
b224rb.wmf
+ -
Optional
Sounder
Interconnect
slc-b501bhwiring.wmf
SLC + SLC -
Figure D.4 Wiring the Legacy B501BH(-2) and B501BHT(-2) Sounder Bases
R U
RA100Z 60 Unregulated power 18
RA400Z 60
rate of rise 12 V
ratings, relay contact 46, 53, 57
verification cycle 59
relay base 23
wiring of 61
relay contact ratings 46, 53, 57 W
Relay Module 11 Waterflow alarm service, automatic and manual
relays 33
Form-C 11 W-GATE 12, 62
Remote LED Annunciator 60 external power 64
Resettable power 18 SLC connections 62
resistance 15, 16 SLC power 63
rotary switches 34, 40, 41, 42, 43, 44, 45, 59 wire length 15, 16
wire size 14
S wireless gateway 12, 62
SD350 Detector 12 external power 64
SLC connections 62
SD350T Detector 12
SLC power 63
SD355 Detector 12, 59
wiring
SD355R Detector 12
SD355T Detector 12 I300 24
ISO-6 24
sensing circuit, thermistor 12
MDF-300 41
short circuit 23
MMF-300 36
Signaling Line Circuit 10
MMF-300-10 39
Single Point Module 34
MMF-302 42
SLC address, setting of 34, 59
MMF-302-6 44
SLC connections 18
NACs 46
SLC terminal block 17
wiring pair 71
SLC wiring 36, 37, 38, 39, 40, 41, 42, 43, 44,
wiring requirements 14
45
wiring style requirements 13
SLCP-30 71
Smoke Detectors 59
sounder base 23 Z
sounder base, wiring of 62 Zone Interface Module 31
Sprinkler supervision 33
supervised
circuit 69
devices 69
supplying power 68
suppressors, surge 71
surge protector 10, 13, 71
switching 46
T
terminal blocks 18
termination of shield 17
Thermal Detector 59
thermistor sensing circuit 12
trouble conditions 13, 23
Warn-HL-08-2009.fm
www.firelite.com