Types of Bonding
Types of Bonding
The raising environmental pressure is creating new Figure 1. Diagram of a single core cable
markets for the power transmission systems based on
very high voltage XLPE-isolated cables. Nowadays
XLPE-cables are being applied up to 500 kV. In many In this section, it has been dealt with cables that have the
countries high voltage overhead power lines are not features shown in table I.
allowed in large cities which are densely populated. TABLE I. Main characteristics of the single core 110 kV cable
These mentioned countries dont authorize overhead under study
power lines in populated areas and promote the
progressive burying of the existent overhead power lines Conductors material: copper
in such areas. Catalunya is an example of this situation, Diameter of the conductor: 32.8 mm
and its government wants that in few years almost all the Resistivity of the conductor (20 C): 28,3 /m
high voltage power lines in populated areas will be Resistivity of the conductor (70 C): 33,86 /m
buried. Number of strings of the conductor: 127
Therefore, it is not desirable an indiscriminate burying of Coefficient of the cable: 127 = 0.776
the high voltage power lines. The burying of the power Sheaths material: aluminium
lines should be carried out mainly in populated and in Diameter of the sheath: 48 mm
ecological areas, whereas in rural areas the electric power Resistivity of the conductor (20 C): 0,18 m/m
lines should be overhead. Resistivity of the conductor (60 C): 0,209 m/m
Figure 4. Crossbonding
When dealing with triangular formation power cables,
crossbonding eliminates totally the sheath currents.
When dealing with flat formation power cables, the
crossbonding system doesnt eliminate totally the sheath
currents due to the lack of symmetry of the three cables,
Figure 2. Single-point bonding but crossbonding reduces outstandingly the sheath
currents.
3.2 Multiple-point bonding 3.4 Crossbonding with transposition
When dealing with a multiple-point bonding scheme, as If the crossbonding scheme doesnt allow to reduce
shown in figure 7, the metallic sheaths are grounded at totally the sheath currents, the crossbonding with
least at the two extremes of the cable. This system transposition allows to reduce even more the sheath
doesnt allow high values of the induced voltages in the currents. It consists on transposing cyclically the three
metallic sheaths. In this situation, appear sheath main conductors in each minor section. This is the more
circulating currents because of there is a closed circuit suitable disposition in order to reduce the sheath currents.
between the sheath and the return path through the
ground. This is the scheme studied in this paper. Figure 5 shows a flat formation power line with
crossbonding with transposition.
Minor section
Major section
Figure 3. Multiple-point bonding
Figure 5. Crossbonding with transposition
The circulating currents produce different effects:
- Circulating sheath currents generate power losses by
heating.
TABLE II. Sheath currents induced in example 1 Sheath currrents sR1S1 = 0.1 m sR1S1 = 0.2 m
Sheath currents s = 0.1 m s = 0.2 m IR,1 (A) 20.51-126.24 27.07-130.71
IR,2 (A) 19.11-115.88 26.29-124.81
IR (A) 45.89-131.44 56.82-134.94 IS,1 (A) 17.75130.73 25.40120.94
IS (A) 33.84130.22 49.39120.41 IS,2 (A) 16.54129.08 24.35119.35
IT (A) 52.929.32 65.17-2.09 IT,1 (A) 19.6910.73 27.45-0.41
IT,2 (A) 23.439.28 30.21-1.34
From table II it can be deduced that by increasing the
distance between the conductors, the mutual inductance 4.5 Example 5
between the conductors also increases (due to an increase
of the sheath induced voltage) and it induces an increase In this example, it has been considered a three-phase flat
of the sheath currents. line with two conductors in each phase (p = 2), with
configuration R1S1T1T2S2R2 and an intensity of 100 A per
4.2 Example 2 phase. The results of the simulations are shown in tables
VII and VIII.
In this example, it has been considered a three-phase flat
line with a single conductor in each phase (p = 1), with TABLE VII. Conductors currents computed from example 5
configuration SRT and an intensity of 100 A. The results Conductor currents sR1S1 = 0.1 m sR1S1 = 0.2 m
of the simulations are shown in table III.
IR,1 (A) 50.000 50.000
TABLE III. Sheath currents induced in example 2 IR,2 (A) 50.000 50.000
Sheath currents s = 0.1 m s = 0.2 m IS,1 (A) 50.00-120.00 50.00-120.00
IS,2 (A) 50.00-120.00 50.00-120.00
IR (A) 33.84-109.78 49.39-119.59 IT,1 (A) 50.00120.00 50.00120.00
IS (A) 52.92129.32 65.17117.91 IT,2 (A) 50.00120.00 50.00120.00
IT (A) 45.89-11.44 56.82-14.94
TABLE VIII. Sheath currents induced in example 5
4.3 Example 3
Sheath currents sR1S1 = 0.1 m sR1S1 = 0.2 m
In this example, it has been considered a three-phase flat IR,1 (A) 23.82-136.93 28.72-138.79
line with a single conductor in each phase (p = 1), with IR,2 (A) 23.82-136.93 28.72-138.79
configuration STR and an intensity of 100 A. The results IS,1 (A) 17.59131.84 25.30121.16
of the simulations are shown in table IV. IS,2 (A) 17.59131.84 25.30121.16
TABLE IV. Sheath currents induced in example 3 IT,1 (A) 42.9847.32 34.80-4.50
IT,2 (A) 42.9847.32 34.80-4.50
Sheath voltages s = 0.1 m s = 0.2 m
-110.68
IR (A) 52.92 65.17-122.09
4.6 Example 6
IS (A) 45.89108.56 56.82105.06
In this example, it has been considered a three-phase flat
IT (A) 33.8410.22 49.390.41 line with two conductors in each phase (p = 2), with
configuration R1R2S1S2T1T2 and an intensity of 100 A per
phase. The results of the simulations are shown in tables
IX and X.
50
IT,2 (A) 50.00120.00 50.00120.00
40