The document contains diagrams and descriptions of various models of protective relays, including: - The 2TJM10 relay which provides IDMT earth fault protection and IDMT overcurrent and earth fault protection. - The 2TJM11 relay which provides IDMT and instantaneous earth fault protection as well as IDMT and instantaneous overcurrent and earth fault protection. - The 2TJM12 relay which provides directional overcurrent protection at 45 degrees leading power factor, directional earth fault protection at 121⁄2 degrees lagging power factor, and directional overcurrent protection. - Additional models including the 2TJM20, 2TJM21, 2TJM30, 2TJM31, and

Uploaded by

Vishal Patel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views9 pages

TJM Section7 Diagrams

The document contains diagrams and descriptions of various models of protective relays, including: - The 2TJM10 relay which provides IDMT earth fault protection and IDMT overcurrent and earth fault protection. - The 2TJM11 relay which provides IDMT and instantaneous earth fault protection as well as IDMT and instantaneous overcurrent and earth fault protection. - The 2TJM12 relay which provides directional overcurrent protection at 45 degrees leading power factor, directional earth fault protection at 121⁄2 degrees lagging power factor, and directional overcurrent protection. - Additional models including the 2TJM20, 2TJM21, 2TJM30, 2TJM31, and

Uploaded by

Vishal Patel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

DIAGRAMS 7

DIAGRAMS 7

Contents

FIGURE 1 2TJM10 IDMT EARTH FAULT PROTECTION 1


FIGURE 2 2TJM10 IDMT OVERCURRENT AND
EARTH FAULT PROTECTION 1
FIGURE 3 2TJM11 IDMT AND INSTANTANEOUS
EARTH FAULT PROTECTION 2
FIGURE 4 2TJM11 IDMT AND INSTANTANEOUS
OVERCURRENT AND EARTH FAULT PROTECTION 2
FIGURE 5 2TJM12 DIRECTIONAL OVERCURRENT,
45 LEADING POWER FACTOR 3
FIGURE 6 2TJM12 DIRECTIONAL EARTH FAULT,
121/2 LAGGING POWER FACTOR AND
DIRECTIONAL OVERCURRENT 4
FIGURE 7 2TJM20 IDMT EARTH FAULT PROTECTION 5
FIGURE 8 2TJM21 IDMT AND INSTANTANEOUS
EARTH FAULT PROTECTION 5
FIGURE 9 2TJM21 IDMT AND INSTANTANEOUS
OVERCURRENT AND EARTH FAULT PROTECTION 5
FIGURE 10 2TJM30 IDMT EARTH FAULT PROTECTION 6
FIGURE 11 2TJM30 IDMT OVERCURRENT AND
EARTH FAULT PROTECTION 6
FIGURE 12 2TJM31 IDMT AND INSTANTANEOUS
OVERCURRENT AND EARTH FAULT PROTECTION 6
FIGURE 13 2TJM60 IDMT EARTH FAULT PROTECTION 7
FIGURE I4 2TJM60 WITH INTERNAL MCAA REPEAT RELAY 7
DIAGRAMS 7

2TJM10 2TJM10

EF
9 10 1 2
P1
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1
A B C (2) (4)
transformers
S2 S2 S2

P2

Figure 1 2TJM10 IDMT Earth Fault Protection

2TJM10 2TJM10

OC A
5 6 1 2
IDMT O/C
(23) (24) (1) (3)
EF 3 4
8 7 IDMT O/C & EF
(2) (4)
EF
(26) (25) 11 12
OC IDMT EF
9 10 (5) (7)
Line current P1
transformers (27) (28)

S1 S1 S1 case earth C
A B C
S2 S2 S2

P2

Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.

Figure 2 2TJM10 IDMT Overcurrent & Earth Fault Protection

1
7 DIAGRAMS

2TJM11 2TJM11
IDMT Inst
EF EF IDMT
9 10 1 2
P1 IDMT & Inst
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1 IDMT & Inst
A B C (2) (4)
transformers Inst
S2 S2 S2

P2

Figure 3 2TJM11 IDMT and Instantaneous Earth Fault Protection

2TJM11 2TJM11
IDMT Inst
OC OC A-IDMT
5 6 1 2
IDMT & Inst O/C
(23) (24) (1) (3)
IDMT Inst
EF EF 3 4
8 7 IDMT O/C & EF
(2) (4)
A-Inst
(26) IDMT Inst (25)
9 OC OC 10
P1
(27) (28)
Line current case earth
transformers S1 S1 S1 C-IDMT
A B C
S2 S2 S2

P2
C-Inst

EF-IDMT
11 12
IDMT & Inst EF
(5) (7)

EF-Inst

Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.

Figure 4 2TJM11 IDMT and Instantaneous Overcurrent and Earth Fault Protection

2
DIAGRAMS 7

2TJM12 (A) 2TJM12 (B) 2TJM12 (C)

OC OC OC
10 9 10 9 10 9

5 6 5 6 5 6
P1

Line current
S1 S1 S1 case earth case earth case earth
transformers
A B C
S2 S2 S2

P2

C Phase B
Rotation Voltage Transformer
A

Relays will operate B


for a fault in this
direction C

2TJM12 2TJM12 2TJM12

A A A
1 2 1 2 1 2

3 4 3 4 3 4

Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.

Figure 5 2TJM12 Directional Overcurrent, 45 Leading Power Factor (using 90 connection)

3
7 DIAGRAMS

2TJM12 (A) 2TJM12 (B) 2TJM12 (C)

OC OC OC
10 9 10 9 10 9

5 6 5 6 5 6
P1

Line current
S1 S1 S1 case earth case earth case earth
transformers
A B C
S2 S2 S2

P2

C Phase B
Rotation Voltage Transformer
A

Relays will operate B


for a fault in this
direction C

VL Vn

Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.

Figure 6 2TJM12 showing Directional Earth Fault 12.5 Lagging Power Factor
and Directional Overcurrent (with 90 connection, 0 power factor)

4
DIAGRAMS 7

2TJM20 2TJM20

EF
9 10 1 2
P1
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1
A B C (2) (4)
transformers
S2 S2 S2

P2

Figure 7 2TJM20 IDMT Earth Fault Protection

2TJM21 2TJM21
IDMT Inst
EF EF IDMT
9 10 1 2
P1 IDMT & Inst
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1 IDMT & Inst
A B C (2) (4)
transformers Inst
S2 S2 S2

P2

Figure 8 2TJM21 IDMT and Instantaneous Earth Fault Protection

2TJM21 2TJM21
IDMT Inst
OC OC A-IDMT
5 6 1 2
IDMT & Inst O/C
(23) (24) (1) (3)
IDMT Inst
EF EF 3 4 IDMT & Inst
8 7 O/C & EF
(2) (4)
A-Inst
(26) IDMT Inst (25)
9 OC OC 10
P1
(27) (28)
Line current case earth
transformers S1 S1 S1 C-IDMT
A B C
S2 S2 S2

P2
C-Inst

EF-IDMT
11 12
IDMT & Inst EF
(5) (7)

Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing. EF-Inst
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.

Figure 9 2TJM21 IDMT and Instantaneous Overcurrent and Earth Fault Protection

5
7 DIAGRAMS

2TJM30 2TJM30 Circuit Breaker


Reed Trip
EF Relay Coil
9 10 1 2
P1 + -
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1
A B C (2) (4)
transformers
S2 S2 S2

P2 Note:
Circuit breaker trip coil circuit must
be connected to terminals 1 and 2

Figure 10 2TJM30 IDMT Fault Protection

2TJM30 2TJM30 Circuit Breaker


Reed Trip
OC OC Relay Coil
5 6 1 2
+ -
(23) (24) (14) (13)
EF
EF
8 7
(26) (25) OC
OC
Line current 9 10
P1
transformers (27) (28) 3 4

case earth (1) (3)


S1 S1 S1
A B C
S2 S2 S2
Note:
Circuit breaker trip coil circuit must
P2 be connected to terminals 1 and 2

Figure 11 2TJM30 IDMT and Overcurrent Earth Fault Protection

2TJM31 2TJM31 Circuit Breaker


IDMT Inst Reed Trip
OC OC OC Relay Coil
5 6 1 2
+ -
(23) (24) (1) (3)
IDMT Inst EF
EF EF IDMT
8 7
(26) IDMT Inst (25) OC

9 OC OC 10
P1 OC
(27) (28)
Line current case earth
S1 S1 S1 EF
transformers
A B C Inst
S2 S2 S2
OC

P2
3 4
IDMT & Inst O/C & EF
(2) (4)
OC-Inst
11 12
Inst O/C & EF
(5) (7)
EF-Inst
Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets) OC-Inst
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.

Figure 12 2TJM31 IDMT and Instantaneous Overcurrent and Earth Fault Protection

6
DIAGRAMS 7

2TJM60 2TJM60 Circuit Breaker


Reed Trip
EF Relay Coil
9 10 1 2
P1 + -
(27) (28) (1) (3)
case earth 3 4
Line current S1 S1 S1
transformers A B C (2) (4)
S2 S2 S2

P2 Note:
Reed relay must be connected in series
with circuit breaker trip coil.

Figure 13 2TJM60 IDMT Earth Fault Protection, with Series Operated Reed Relay

2TJM60

OC MCAA2
2 1
-
(13) (14)
Circuit Breaker
Trip
3 4 Coil
+ -
(1) (3)
5 6
(2) (4)

Notes:
1 The diagrams show relay safety earthing and typical current circuit earthing.
2 All relay terminals show the Vedette case numbering and Reymos numbering (in brackets)
3 Relay contacts are shown as supplied with standard wiring, where a different
arrangement is required please enquire.

Figure 14 Alternative Connections for Fig.13 with Internal MCAA Repeat Relay