Settings Calculation For Distance Protection Relay

This document contains the calculations of zone setting values for distance protection relays on three different transmission line types: a 220kV line, a 132kV line, and a 400kV line. It lists the principle line length, longest line length, and shortest line length for each type of line, then calculates the impedance values and resistance values that correspond to the zone settings for distance protection on each.

Uploaded by

arun singh
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views

Settings Calculation For Distance Protection Relay

This document contains the calculations of zone setting values for distance protection relays on three different transmission line types: a 220kV line, a 132kV line, and a 400kV line. It lists the principle line length, longest line length, and shortest line length for each type of line, then calculates the impedance values and resistance values that correspond to the zone settings for distance protection on each.

Uploaded by

arun singh
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 8

Settings calculation for Distance protection Relay

Principle line(km)= 24 Rarc= 20 R1=


Longest line(km)= 86 Rft= 5 X1=
Shortest line(km)= 26.37

Calculated values of different zone settings- 220 kv

ZONE1 ZONE2 ZONE3 ZONE4 (REV)


X() 3.100109 4.6501632 17.76104 2.128903
Rph-ph() 4.615475 4.9232128 8.231392 4.422658
Rph-e() 10.61548 10.923213 14.23139 10.42266
0.08014 Primary current= 800 Secondry current= 1
0.40366 Primary voltage= 220,000 Secondry voltage= 110

CTR/PTR= 0.4

Line S C Cond - dear


CTR= 800
PTR= 2000
Settings calculation for Distance protection Relay

Principle line(km)= 15.925 Rarc= 20 R1= 0.08109


Longest line(km)= 37.431 Rft= 5 X1= 0.19306
Shortest line(km)= 15.925

Calculated values of different zone settings- 132 KV Line Conduc

ZONE1 ZONE2 ZONE3 ZONE4 (REV)


X() 0.819861 1.229792 3.433636 0.512413
Rph-ph() 3.677696 3.849877 5.063989 3.54856
Rph-e() 8.677696 8.849877 10.06399 8.54856
Primary current= 400 Secondry c 1 CTR= 400
Primary voltage= 132,000 Secondry v 110 PTR= 1200

CTR/PTR= 0.333333

132 KV Line Conductor = Panther (D.C.)


Settings calculation for Distance protection Relay

Principle line(km)= 112 Rarc= 20 R1= 0.03252


Longest line(km)= 175 Rft= 5 X1= 0.33086
Shortest line(km)= 103
C

alculated values of different zone settings- 400 KV Line Conducto

ZONE1 ZONE2 ZONE3 ZONE4 (REV)


X() 8.1523912.22859 26.11313 4.6858048
Rph-ph() 3.951939 5.829969 3.2105645
Rph-e() 7.676293 8.076939 9.954969 7.3355645
Primary current= 1000 Secondry current= 1 CTR=
Primary voltage= 400,000 Secondry voltage= 110 PTR=

CTR/PTR=
CTR/PTR= 0.275

400 KV Line Conductor = 2* Moose


1000
3636.364