Compensation in Control System
Compensation in Control System
Necessary of Compensation
1. In order to obtain the desired performance of the system, we use compensating
networks. Compensating networks are applied to the system in the form of feed
forward path gain adjustment.
2. Compensate a unstable system to make it stable.
3. A compensating network is used to minimize overshoot.
4. These compensating networks increase the steady state accuracy of the system. An
important point to be noted here is that the increase in the steady state accuracy
brings instability to the system.
5. Compensating networks also introduces poles and zeros in the system thereby
causes changes in the transfer function of the system. Due to this, performance
specifications of the system change.
Methods of Compensation
Series Compensator
Load Compensator
A system which has one pole and one dominating zero (the zero which is closer to
the origin than all over zeros is known as dominating zero.) is known as lead
network. If we want to add a dominating zero for compensation in control system
then we have to select lead compensation network. The basic requirement of the
phase lead network is that all poles and zeros of the transfer function of the network
must lie on (-)ve real axis interlacing each other with a zero located at the origin of
nearest origin. Given below is the circuit diagram for the phase lead compensation
network.
On substituting the = (R1 +R2)/ R2 and T = {(R1R2) /(R1 +R2)} in the above
equation, where, T and are respectively the time constant and attenuation constant,
we have
The above network can be visualized as an amplifier with a gain of 1/. Let us
draw the pole zero plot for the above transfer function.
Now in order to find put the maximum phase lead occurs at a frequency let us
differentiate this phase function and equate it to zero. On solving the above equation
we get
Where, m is the maximum phase lead angle. And the corresponding magnitude of
the transfer function at maximum m is 1/a.
A system which has one zero and one dominating pole ( the pole which is closer to
origin that all other poles is known as dominating pole) is known as lag network. If
we want to add a dominating pole for compensation in control system then, we have
to select a lag compensation network. The basic requirement of the phase lag
network is that all poles and zeros of the transfer function of the network must lie in
(-)ve real axis interlacing each other with a pole located or on the nearest to the
origin. Given below is the circuit diagram for the phase lag compensation network.
We will have the output at the series combination of the resistor R2 and the capacitor
C. From the above circuit diagram, we get
Now let us determine the transfer function for the given network and the transfer
function can be determined by finding the ratio of the output voltage to the input
voltage.
Taking Laplace transform of above two equation we get,
On substituting the T = R2C and = {(R2 + R1 ) / R1} in the above equation (where
T and are respectively the time constant and dc gain), we have
The above network provides a high frequency gain of 1 / . Let us draw the pole
zero plot for the above transfer function.
Clearly we have -1/T (which is a zero of the transfer function) is far to origin than
the -1 / (T)(which is the pole of the transfer function). Thus we can say in the lag
compensator pole is more dominating than the zero and because of this lag network
introduces negative phase angle to the system when connected in series.
Let us substitute s = j in the above transfer function and also we have a < 1. On
finding the phase angle function for the transfer function we have
Now in order to find put the maximum phase lag occurs at a frequency let us
differentiate this phase function and equate it to zero. On solving the above equation
we get
With single lag or lead compensation may not satisfied design specifications. For an
unstable uncompensated system, lead compensation provides fast response but does
not provide enough phase margin whereas lag compensation stabilize the system but
does not provide enough bandwidth. So we need multiple compensators in cascade.
Given below is the circuit diagram for the phase lag- lead compensation network.
Let us draw the pole zero plot for the above transfer function.
Clearly we have -1/T (which is a zero of the transfer function) is far to the origin
than the -1/(T)(which is the pole of the transfer function). Thus we can say in the
lag-lead compensation pole is more dominating than the zero and because of this
lag-lead network may introduces positive phase angle to the system when connected
in series.