Dry-Type, Air-Core Shunt Reactors: Proven
Dry-Type, Air-Core Shunt Reactors: Proven
Dry-Type, Air-Core Shunt Reactors: Proven
dry-type shunt reactors versus The dimensions of the winding depend on several factors.
oil immersed types As a matter of course, dimensions and weight will
increase with the reactors power (Mvar) rating. To meet
requirements for transportation and installation, the upper
n
o environmental concern, no oil collection limits for outline dimensions of a single reactor unit are
system required in the range of 4.5 meters (14.5 feet) in both, height and
no fire hazard, no fire deluge system diameter. These dimensions translate into a maximum unit
power rating per phase of approximately 100 Mvar at
e
ssentially no efforts and ongoing costs for
50 Hz (based on a single coil per phase). Higher ratings are
maintenance possible using multiple coils per phase. In addition to the
less civil work, lower weight basic Mvar rating, other factors such as low loss or voltage
less efforts for transport and handling requirements may also govern the design and dimensions
of the reactor. The winding length of air core shunt reactors
simplicity of insulation to ground (self healing)
is selected to meet the voltage stress imposed by the system
simple protection scheme voltage to which the reactors are connected. Shunt reactors
no risk of bushing failures which are approximately 4 m tall may be connected to
n
o excessive magnetizing inrush current system voltages up to 110 kV, when configured in wye.
no iron core For higher voltages, two or more coils per phase may be
put in series to keep the winding voltage stresses within
typically lower investment cost acceptable limits.
less expenses for spare units (single phase unit only)
Dry type shunt reactors do not have an iron core or iron
typically shorter lead time
shield. Therefore, the magnetic field is not constrained and
will occupy the space around the reactor. Although the
magnetic field reduces in strength with increased distance
from the reactor, the presence of this field, particularly for
high power reactors, needs to be taken into consideration
for possible effects on metallic components (grounding
grids, beam structures, concrete rebar etc.) in the vicinity
of the reactor.
(3) (3)
(2)
(1)
The majority of shunt reactors which are connected directly Fig. 3 shows two 132 kV, 20 Mvar 3-phase, 60 Hz direct
to the high voltage bus or transmission line are of oil-filled connected shunt reactor banks. Each phase consists of two
type. However, a number of shunt reactors of dry type stacked sub-coils, each being about 4 m tall. As shown in
design have already been applied at voltages up to 345 kV the figure, if required, the reactors can be elevated off the
and the demand is growing. One factor driving this demand ground using support pedestals, so that live parts are not
increase is the integration of renewable generation such as accessible to station personnel.
wind parks to the grid. The connecting overhead lines or
cables require shunt compensation with ratings for reactive For higher system voltages more than two coils must be
compensation in the range of some tens of Mvars. Usually connected in series. In principle, by connecting several coils
such wind parks are located in environmentally sensitive in series, dry type shunt reactors may be applied at any
areas thereby favoring dry type air core technology. system voltage.
For dry type shunt reactors applied at sub-transmission Fig. 4 shows a shunt reactor bank for 345 kV, 20 Mvar
or transmission voltages the steady state voltage drop 3-phase, 60 Hz, consisting of two series connected reactor
along the surface of the reactor is a decisive design stacks, mounted side by side, resulting in a total of four
parameter. As mentioned earlier, reactor windings which series connected coils per phase.
are approximately 4 m tall may be connected to system
voltages up to 110 kV when connected in wye. For systems
with voltage levels above, two single units, stacked one
above the other and connected in series are required.
Fig. 3: 132 kV, 20 Mvar 3-phase shunt reactor (2 banks) Fig. 4: 345 kV, 20 Mvar 3-phase shunt reactor
The majority of faults on transmission lines are single- During normal operation, the neutral reactor is practically
phase-to-ground faults caused by flashovers of the air unloaded. In case of a SPAR operation, for less than one or
insulation. Clearing of such faults is achieved by making two seconds the reactor is loaded by typically 15 to 25 %
use of the dielectric recovery of the air. For this purpose the of the system voltage, depending on the parameters of the
affected phase of the line is temporarily isolated by opening line to which the shunt reactor is connected. The short-time
the circuit breaker at both line ends and reclosing the power rating of the neutral reactor is only a few percent of
breakers after a certain dead time. This operation is termed the shunt reactors continuous power rating.
single-phase auto-reclosing (SPAR).
Due to the advantages of dry type over oil type reactors,
Long EHV transmission lines are usually operated with practically all neutral reactors are dry type, for both oil
shunt reactors permanently connected to the lines at their immersed and dry type shunt reactors.
terminal stations, even when the lines are switched-off.
Successful SPAR on such compensated lines is hampered
by a phenomenon called secondary arcing. Instead of the
extinction of the (primary) arc, the arc is further maintained
due to capacitive and inductive coupling with the two
healthy phases. A successful auto-reclosing is achieved only
if this secondary arc extinguishes during the dead time
when the breakers are open. For mitigation of secondary
arcing it is a well proven practice to increase the zero
sequence impedance of the shunt reactor by providing
an additional single-phase reactor between the reactors
neutral and ground.
Placement of
Phase Reactors
In line
In triangle
Table 1: Conceptual data of wye connected air-core, dry-type shunt reactors for 50 Hz systems
U Mvar X-50 Hz L I D H1 H2 H3 C M1 M2 Q
(kV) (3-phase) (ohm) (mH) (A) (mm) (mm) (mm) (mm) (mm) (kg) (kg) 75C
20 5,0 15,9 1155 3100 1100 4200 5200 1600 1900 125
10 50 2,0 6,4 2887 3300 1300 4400 5400 3200 3500 210
60 1,7 5,3 3465 3400 1450 4550 5500 3500 3800 235
20 20,0 63,7 578 3150 1350 4450 5400 1700 2000 110
20 50 8,0 25,5 1444 3350 1400 4500 5500 2900 3200 185
100 4,0 12,8 2887 3500 1900 5000 5800 5000 5600 295
20 54,5 173,3 350 2900 2050 5150 5200 2100 2400 110
33 50 21,8 69,4 875 3100 2100 5200 5600 3200 3500 180
100 10,9 34,7 1750 3200 2300 5500 5700 5100 5700 275
20 238,0 757,8 168 2900 2950 6050 6800 5500 2700 3000 95
69 50 95,3 303,1 419 3000 3000 6100 6850 5700 5000 5600 165
100 47,7 151,6 837 3400 3100 6200 6950 6300 5600 6200 220
20 605,0 1926,0 105 3100 3600 6700 7450 6200 2900 3200 85
110 40 302,5 963,0 210 3200 3650 6750 7500 6400 4200 4600 140
60 201,7 642,0 315 3250 3700 6800 7550 6500 6000 6600 170
1. winding
2. winding conductor
3. spider
4. terminal
5. duct stick
6. base insulator
7. mounting bracket
A dry type air core reactor consists of a cylindrical winding The winding is impregnated by epoxy resin resulting (after
(1) made of one or several concentric layers of film/glass curing) in a mechanically strong and compact unit. The
tape insulated aluminum conductor (2). All layers are reactors are mounted on several base insulators (6) and
electrically connected in parallel by welding their top and according mounting brackets (7).
bottom ends to metallic cross arms, commonly referred
to as spiders (3). Each spider carries a terminal (4) for
electrical connection of the reactor. The individual layers
are configured such that radial voltage stress is virtually
nil and the remaining axial voltage stress results in surface
stress values that are less than those on porcelain insulators
and turn-to-turn steady state operating voltages that are
well below the level at which partial discharges can occur.
All layers are radially spaced by several glass fiber sticks
(5) which form air ducts necessary for the cooling of the
winding. Cooling is provided by natural convection of
ambient air, which enters at the bottom end of the winding
and exits at its top end.