TECHNICAL DATA

AWR318HLE - AER318SH3
AWR318HLE - AER318SH
AWR322HLE - AER322SH3
AWR322HLE - AER322SH

SPLIT SYSTEM AIR CONDITIONER

0.8180.053.0 06/99
Table of Contents
Page

1. OPERATING RANGE ......................................................................... 1

2. SPECIFICATIONS .............................................................................. 2

3. DIMENSIONAL DATA ......................................................................... 17

4. HEATING CAPACITY ......................................................................... 21

5. AIR THROW DISTANCE CHART ....................................................... 22

6. REFRIGERANT FLOW DIAGRAM ..................................................... 24

7. ELECTRICAL DATA ............................................................................ 26

8. ELECTRIC WIRING DIAGRAMS ........................................................ 30

9. REFRIGERANT R407C ...................................................................... 33

i
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Maximum 32C DB / 23C WB 43C DB
Cooling
Minimum 19C DB / 14C WB 19C DB
Maximum 25C DB 22C DB / 17C WB
Heating
Minimum // 8 C DB / 9C WB

1
2. SPECIFICATIONS

2-1. UNIT SPECIFICATIONS

INDOOR UNIT AWR318HLE


MODELS
OUTDOOR UNIT AER318SH3
Power source 380 - 400 V - 3N ~ 50 Hz
Control circuit 220 - 240 V ~ 50 Hz
PERFORMANCE COOLING HEATING
W 4800 6300
Capacity
BTU/h 16400 21500
Air circulation (high) m/h 800
Moisture removal (high) l/h 2,7 //
ELECTRICAL RATING
Voltage rating V 400
Available voltage range V 342 to 440
Running amperes A 3,6 3,7
Power input W 2200 2300
Power factor % // //
C.O.P. W/W 2,2 2,7
Compressor locked rotor amperes A 22 22
FEATURES
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours & daily program
Fan speeds Indoor / Outdoor 3 and Auto / 2 (Auto)
Horizontal Manual
Airflow direction (indoor)
Vertical Auto
Air filter Washable, anti-mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R407C / 1650
Refrigerant control Capillary tube
Indoor Hi / Me / Lo dB-A 45,0 / 41,0 / 36,0
Operation sound
Outdoor Hi dB-A 51
Refrigerant tubing connections Flare type
Max. allowable tubing lenght at shipment m 10
Narrow tube mm (") 6,35 (1/4)
Refrigerant tube diameter
Wide tube mm (") 12,7 (1/2)
DIMENSIONS AND WEIGHT Indoor unit Outdoor unit
Height mm 360 630
Unit dimensions Width mm 1000 830
Depth mm 205 305
Height mm 282 713
Package dimensions Width mm 1080 994
Depth mm 443 413
Net kg 13,5 59
Weight
Shipping kg 17,7 64
Shipping volume m3 0,13 0,29

Data subject to change without notice.

2
INDOOR UNIT AWR318HLE
MODELS
OUTDOOR UNIT AER318SH
Power source 220 - 240 V ~ 50 Hz
PERFORMANCE COOLING HEATING
W 4900 6300
Capacity
BTU/h 16700 21500
Air circulation (high) m/h 800
Moisture removal (high) l/h 2,7 //
ELECTRICAL RATING
Voltage rating V 230
Available voltage range V 198 to 264
Running amperes A 10,5 11
Power input W 2200 2350
Power factor % 91 93
C.O.P. W/W 2,2 2,7
Compressor locked rotor amperes A 57 57
FEATURES
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours & daily program
Fan speeds Indoor / Outdoor 3 and Auto / 2 (Auto)
Horizontal Manual
Airflow direction (indoor)
Vertical Auto
Air filter Washable, anti-mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R407C / 1660
Refrigerant control Capillary tube
Indoor Hi / Me / Lo dB-A 45,0 / 41,0 / 36,0
Operation sound
Outdoor Hi dB-A 51
Refrigerant tubing connections Flare type
Max. allowable tubing lenght at shipment m 10
Narrow tube mm (") 6,35 (1/4)
Refrigerant tube diameter
Wide tube mm (") 12,7 (1/2)
DIMENSIONS AND WEIGHT Indoor unit Outdoor unit
Height mm 360 630
Unit dimensions Width mm 1000 830
Depth mm 205 305
Height mm 282 713
Package dimensions Width mm 1080 994
Depth mm 443 413
Net kg 13,5 56,5
Weight
Shipping kg 17,7 61,5
Shipping volume m3 0,13 0,29

Data subject to change without notice.

3
INDOOR UNIT AWR322HLE
MODELS
OUTDOOR UNIT AER322SH3
Power source 380 - 400 V - 3N ~ 50 Hz
Control circuit 220 - 240 V ~ 50 Hz
PERFORMANCE COOLING HEATING
W 6200 7450
Capacity
BTU/h 21150 25400
Air circulation (high) m/h 900
Moisture removal (high) l/h 3,3 //
ELECTRICAL RATING
Voltage rating V 400
Available voltage range V 342 to 440
Running amperes A 4,8 5
Power input W 2800 3000
Power factor % // //
C.O.P. W/W 2,2 2,5
Compressor locked rotor amperes A 28 28
FEATURES
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours & daily program
Fan speeds Indoor / Outdoor 3 and Auto / 2 (Auto)
Horizontal Manual
Airflow direction (indoor)
Vertical Auto
Air filter Washable, anti-mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R407C / 2360
Refrigerant control Capillary tube
Indoor Hi / Me / Lo dB-A 47,0 / 44,0 / 40,0
Operation sound
Outdoor Hi dB-A 55
Refrigerant tubing connections Flare type
Max. allowable tubing lenght at shipment m 10
Narrow tube mm (") 6,35 (1/4)
Refrigerant tube diameter
Wide tube mm (") 15,88 (5/8)
DIMENSIONS AND WEIGHT Indoor unit Outdoor unit
Height mm 360 835
Unit dimensions Width mm 1000 850
Depth mm 205 305
Height mm 282 913
Package dimensions Width mm 1080 1000
Depth mm 443 400
Net kg 13,5 70
Weight
Shipping kg 17,7 79
Shipping volume m3 0,13 0,37

Data subject to change without notice.

4
INDOOR UNIT AWR322HLE
MODELS
OUTDOOR UNIT AER322SH
Power source 220 - 240 V ~ 50 Hz
PERFORMANCE COOLING HEATING
W 6200 7450
Capacity
BTU/h 21150 25400
Air circulation (high) m/h 900
Moisture removal (high) l/h 3,3 //
ELECTRICAL RATING
Voltage rating V 230
Available voltage range V 198 to 264
Running amperes A 12,8 13,8
Power input W 2800 3000
Power factor % 95 95
C.O.P. W/W 2,2 2,5
Compressor locked rotor amperes A 70 70
FEATURES
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours & daily program
Fan speeds Indoor / Outdoor 3 and Auto / 2 (Auto)
Horizontal Manual
Airflow direction (indoor)
Vertical Auto
Air filter Washable, anti-mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R407C / 2290
Refrigerant control Capillary tube
Indoor Hi / Me / Lo dB-A 47,0 / 44,0 / 40,0
Operation sound
Outdoor Hi dB-A 55
Refrigerant tubing connections Flare type
Max. allowable tubing lenght at shipment m 10
Narrow tube mm (") 6,35 (1/4)
Refrigerant tube diameter
Wide tube mm (") 15,88 (5/8)
DIMENSIONS AND WEIGHT Indoor unit Outdoor unit
Height mm 360 835
Unit dimensions Width mm 1000 850
Depth mm 205 305
Height mm 282 913
Package dimensions Width mm 1080 1000
Depth mm 443 400
Net kg 13,5 70
Weight
Shipping kg 17,7 79
Shipping volume m3 0,13 0,37

Data subject to change without notice.

5
2-2. MAJOR COMPONENT SPECIFICATIONS

2-2-1. INDOOR UNIT

MODEL AWR318HLE
Source 220 - 240 V ~ 50 Hz
CONTROLLER PCB
Part No. POW-K186GHS/E
Controls Microprocessor
Control circuit fuse 250 V - 3 A
REMOTE CONTROL UNIT RCS-2SH2
FAN AND FAN MOTOR
Type Cross-flow
Number ... Dia. / Leghth mm 1 ... 100 / 760
Fan motor model ... Number UF2Q-21A5PA-S ...1
No. of poles ... rpm (220 V, High) 2 ... 1,490
Nominal output W 20
WHT - BRN 163,7
WHT - VLT 68,8
Coil resistance (Ambient temp. 20C) VLT - ORG 33,2
ORG - YEL 73,6
YEL - PNK 43,7
Safety devices: Type Internal protector
Open C 130 8
Operating temp.
Close Automatic reclosing
F 1,5
Run capacitor
VAC 440
FLAP MOTOR
Model M2LJ24ZE31
Rating AC 208 / 230 V 50-60 Hz
No. of poles ... rpm 8 ... 2,5 / 3
Nominal output W 3 / 2,5
Coil resistance (Ambient temp. 20C) k 16,45 15%
HEAT EXCH. COIL
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1,8
Face area m2 0,192

Data subject to change without notice.

6
MODEL AWR322HLE
Source 220 - 240 V ~ 50 Hz
CONTROLLER PCB
Part No. POW-K226GHS/E
Controls Microprocessor
Control circuit fuse 250 V - 3 A
REMOTE CONTROL UNIT RCS-2SH2
FAN AND FAN MOTOR
Type Cross-flow
Number ... Dia. / Leghth mm 1 ... 100 / 760
Fan motor model ... Number UF2Q-31A5P-S ...1
No. of poles ... rpm (220 V, High) 2 ... 1,750
Nominal output W 30
WHT - BRN 145,3
WHT - VLT 53,6
Coil resistance (Ambient temp. 20C) VLT - ORG 30,9
ORG - YEL 70,4
YEL - PNK 38,8
Safety devices: Type Internal protector
Open C 130 5
Operating temp.
Close Automatic reclosing
F 1,8
Run capacitor
VAC 440
FLAP MOTOR
Model M2LJ24ZE31
Rating AC 208 / 230 V 50-60 Hz
No. of poles ... rpm 8 ... 2,5 / 3
Nominal output W 3 / 2,5
Coil resistance (Ambient temp. 20C) k 16,45 15%
HEAT EXCH. COIL
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1,8
Face area m2 0,192

Data subject to change without notice.

7
2-2-2. OUTDOOR UNIT

MODEL AER318SH3
Power source 380 - 400 V - 3N ~ 50 Hz
Control circuit 220 - 240 V ~ 50 Hz
CONTROLLER PCB POW-C186GH
COMPRESSOR
Type Rotary (Hermetic)
Compressor model C-2RN173H8A 80242088
Source 380 - 400 V - 3N ~ 50 Hz
Nominal output W 1700
Compressor oil ... Amount cc FV68S ... 800
C-R 5,62
Coil resistance (Ambient temp. 25C) C-S 5,51
R-S 5,62
Safety devices: Type Internal protector External protector
Overload relay // HOE-10TB TH-7A
Open C 120 5 //
Operating temp.
Close C Automatic reclosing //
Operating amp. (Ambient temp. 25C) // 0
F //
Run capacitor
VAC //
Crank case heater 240 V - 30 W
FAN AND FAN MOTOR
Type Propeller
Number ... Dia. mm 1 ... 400
Fan motor model ... Number SG6S-51B5P ... 1
Source 220 - 240 V ~ 50 Hz
No. of poles ... rpm (220 V) 6 ... 900
Nominal output W 50
WHT - BRN 89,1
Coil resistance (Ambient temp. 20C) WHT - YEL 111,8
YEL - PNK 55,9
Safety devices: Type Internal protector
Open C 130 8
Operating temp.
Close Automatic reclosing
F 2
Run capacitor
VAC 440
HEAT EXCH. COIL
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1,6
Face area m2 0,453
EXTERNAL FINISH Acrylic baked-on enamel finish

Data subject to change without notice.

8
MODEL AER318SH
CONTROLLER PCB
Part No. POW-C186GH
Control circuit fuse //
COMPRESSOR
Type Rotary (Hermetic)
Compressor model C-2RN170H5W 80807045
Nominal output W 1700
Compressor oil ... Amount cc FV68S ... 800
C-R 1,353
Coil resistance (Ambient temp. 25C)
C-S 3,422
Safety devices: Type Internal protector
Overload relay //
Open C Automatic opening
Operating temp.
Close C Automatic reclosing
Operating amp. (Ambient temp. 25C) //
F 40
Run capacitor
VAC 400
Crank case heater 240 V - 30 W
FAN AND FAN MOTOR
Type Propeller
Number ... Dia. mm 1 ... 400
Fan motor model ... Number SG6S-51B5P ... 1
No. of poles ... rpm (230 V, High) 6 ... 900
Nominal output W 50
WHT - BRN 89,1
Coil resistance (Ambient temp. 20C) WHT - YEL 111,8
YEL - PNK 55,9
Safety devices: Type Internal protector
Open C 130 8
Operating temp.
Close Automatic reclosing
F 2
Run capacitor
VAC 440
HEAT EXCH. COIL
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1,6
Face area m2 0,453
EXTERNAL FINISH Acrylic baked-on enamel finish

Data subject to change without notice.

9
MODEL AER322SH3
Power source 380 - 400 V - 3N ~ 50 Hz
Control circuit 220 - 240 V ~ 50 Hz
CONTROLLER PCB POW-C226GH
COMPRESSOR
Type Rotary (Hermetic)
Compressor model C-RN223H8A 80244088
Source 380 - 400 V - 3N ~ 50 Hz
Nominal output W 2200
Compressor oil ... Amount cc FV68S ... 1350
C-R 4,97
Coil resistance (Ambient temp. 25C) C-S 4,64
R-S 4,88
Safety devices: Type Internal protector External protector
Overload relay // HOE-10TB TH-7A
Open C Automatic opening //
Operating temp.
Close C Automatic reclosing //
Operating amp. (Ambient temp. 25C) // 7A
F //
Run capacitor
VAC //
Crank case heater 240 V - 30 W
FAN AND FAN MOTOR
Type Propeller
Number ... Dia. mm 1 ... 460
Fan motor model ... Number KFC6S-51B5P ... 1
Source 220 - 240 V ~ 50 Hz
No. of poles ... rpm (220 V) 6 ... 840
Nominal output W 50
WHT - BRN 95,9
Coil resistance (Ambient temp. 20C) WHT - YEL 55,4
YEL - PNK 7,2
Safety devices: Type Internal protector
Open C 130 8
Operating temp.
Close Automatic reclosing
F 5
Run capacitor
VAC 440
HEAT EXCH. COIL
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1,9
Face area m2 0,61
EXTERNAL FINISH Acrylic baked-on enamel finish

Data subject to change without notice.

10
MODEL AER322SH
CONTROLLER PCB
Part No. POW-C226GH
Control circuit fuse //
COMPRESSOR
Type Rotary (Hermetic)
Compressor model C-RN221H5A 80244035
Source 220 - 240 V ~ 50 Hz
Nominal output W 2200
Compressor oil ... Amount cc FV68S ... 1350
C-R 0,777
Coil resistance (Ambient temp. 25C)
C-S 2,408
Safety devices: Type Internal protector External protector
Overload relay // OL-D24
Open C Automatic opening 150 5
Operating temp.
Close C Automatic reclosing 63 10
Operating amp. (Ambient temp. 25C) // Trip in 6 to 16 s at 59A
F 40
Run capacitor
VAC 400
Crank case heater 240 V - 30 W
FAN AND FAN MOTOR
Type Propeller
Number ... Dia. mm 1 ... 460
Fan motor model ... Number KFC6S-51B5P ... 1
No. of poles ... rpm (230 V, High) 6 ... 860
Nominal output W 50
WHT - BRN 95,9
Coil resistance (Ambient temp. 20C) WHT - YEL 55,4
YEL - PNK 7,2
Safety devices: Type Internal protector
Open C 130 8
Operating temp.
Close Automatic reclosing
F 5
Run capacitor
VAC 440
HEAT EXCH. COIL
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1,9
Face area m2 0,61
EXTERNAL FINISH Acrylic baked-on enamel finish

Data subject to change without notice.

11
2-3. Other Component Specifications

Indoor Unit AWR318HLE, AWR322HLE

Transformer (TR) ATR-J105


Rating Primary AC 230V, 50Hz
Secondary 19V, 0.526A
Capacity 10VA
Coil resistance (at 21C) Primary (WHT WHT): 205 10%
Secondary (BRN BRN): 2.0 10%
Thermal cut-off temp. 150C

Thermistor (Coil sensor TH1) PBC-41E-S4


Resistance k 20C 40.1 5% 20C 6.5 5%
10C 24.4 5% 30C 4.4 5%
0C 15.3 5% 40C 3.0 5%
10C 9.9 5% 50C 2.1 5%

Thermistor (Room sensor TH2) KTEC-35-S6


Resistance k 10C 10.0 4% 30C 4.0 4%
15C 7.9 4% 35C 3.3 4%
20C 6.3 4% 40C 2.7 4%
25C 5.0 4% 50C 1.8 4%

12
Outdoor Unit AER318SH3
Electro Magnetic Contactor (MG) HOE-10TB TH-5A
Magnetic contactor
Coil rating AC 220240V, 50Hz / AC 240260V, 60Hz
Coil resistance (at 25C) 1,260 10%
Contact rating (Main) AC 440V, 8A
Thermal relay (Overcurrent relay)
Operating amperes 5A

Negative Phase Relay (47C) RDR-S400


Rating AC 415V, 3-phase 50Hz
Contact rating AC 400V, 1A
Operation Positive phase: ON
Negative phase: OFF

Relay (PR) MY2-TSDF


Coil rating DC 24V
Coil resistance (at 20C) 650 10%
Contact rating AC 200V, 5A

4-way Valve (SC) LB60012 (Coil), V26-110B (Valve)


Coil rating AC 220/240V, 50Hz, 6W
Coil resistance (at 20C) 1,740 7%

Thermostat (Defrost thermo. 23D) TRS02-12MSR


Operating temp. C ON 12 2
Diff. 8 deg. below

Thermostat (Fan Speed Control 23S) MQT5S-27YZJ


Switching temp. C high LOW 23.5C 1.5
low HIGH 27.0C +0
3
Contact rating AC 220V, 3A

High Pressure Switch (HPS) ACB-IB29


Operating press. setting OFF 25 1
ON 20 1.5

13
Outdoor Unit AER318SH
Power Relay DFU24D1F
Coil rating DC 24V
Coil resistance (at 20C) 650 10%
Contact rating AC 250V, 20A

High Pressure Switch (HPS) ACB-IB29


Operating press. setting OFF 25 1
ON 20 1.5

Thermostat (Defrost thermo. 23D) TRS02-12MSR


Operating temp. C ON 12 2
Diff. 8 deg. below

Thermostat (Fan Speed Control 23S) MQT5S-27YZJ


Switching temp. C high LOW 23.5C 1.5
low HIGH 27.0C +0
3
Contact rating AC 220V, 3A

4-way Valve (SC) LB60012 (Coil), V26-110B (Valve)


Coil rating AC 220/240V, 50Hz, 6W
Coil resistance (at 20C) 1,740 7%

14
Outdoor Unit AER322SH3
Electro Magnetic Contactor (MG) HOE-10TB TH-7A
Magnetic Contactor
Coil rating AC 220240V, 50Hz / AC 240260V, 60Hz
Coil resistance (at 25C) 1,260 10%
Contact rating (Main) AC 440V, 8A
Thermal relay (Overcurrent relay)
Operating amperes 7A

Negative Phase Relay (47C) RDR-S400


Rating AC 415V, 3-phase 50Hz
Contact rating AC 400V, 1A
Operation Positive phase: ON
Negative phase: OFF

4-way Valve (20S) LB60012 (Coil), V26-110D (Valve)


Coil rating AC 220/240V, 50Hz, 6W
Coil resistance (at 20C) 1,740 7%

Solenoid Valve (SV) NEV-J041B0 (Coil), NEV202DXF (Valve)


Rating AC 240V, 50/60Hz
7/6W, 45/35mA

Thermostat (Defrost thermo. 23D) TRS02-12MSR316


Operating temp. C ON 12 2
Diff. 8 deg. below

Thermostat (Fan Speed Control 23S) YTB-S383


Switching temp. C high LOW 28.5C 1
low HIGH 31C 1

15
Outdoor Unit AER322SH
Magnetic Contactor (MG) HE-20FT31B
Coil rating AC 220/240V, 50Hz
Coil resistance (at 25C) 1,050 15%
Contact rating (Main) AC 220V, 20A

Thermostat (Defrost thermo. 23D) TRS02-12MSR316


Operating temp. C ON 12 2
Diff. 8 deg. below

Thermostat (Fan Speed Control 23S) YTB-S383


Switching temp. C high LOW 28.5C 1
low HIGH 31C 1

Solenoid Valve (SV) NEV-J041B0 (Coil), NEV202DXF (Valve)


Rating AC 240V, 50/60Hz
7/6W, 45/35mA

4-way Valve (SC) LB60012 (Coil), V26-110B (Valve)


Coil rating AC 220/240V, 50Hz, 6W
Coil resistance (at 20C) 1,740 7%

16
3. DIMENSIONAL DATA

Indoor Unit AWR318HLE


AWR322HLE

1000 205

360
Rear panel (center point of gravity)
Remote control unit

172.5
61 18.5
49

61

64 74

Drain hose 26
Narrow tube 6.35 (1/4")
Center of tubing hole
(for right rear) Wide tube 12.70 (1/2") ---- AWR318HLE
Wide tube 15.88 (5/8") ---- AWR322HLE

Unit : mm

17
Outdoor Unit AER318SH3

538 146

Air intake

307
337
4 12 holes
Air discharge Wide tube service valve
12.7 (1/2")

Narrow tube service valve


6.35 (1/4")
4 3.3 Holes
Check port 6.35 (1/4")
830
305
380 357
630
380

95 61
146
19

Unit : mm

18
Outdoor Unit AER318SH

538 146

Air intake

307
337
4 12 holes
Air discharge Wide tube service valve
12.7 (1/2")

Narrow tube service valve


6.35 (1/4")
4 3.3 holes

830
305
380 357
630
380

95 61
146
19

Unit : mm

19
Outdoor Unit AER322SH3
AER322SH

Air intake

20

325
20

Air discharge

130 620 100 55

Wide tube service valve 15.88 (5/8")

Narrow tube service valve 6.35 (1/4")


6 3.1 holes
850 Check port 6.35 (1/4")
250 250 285
560

835

57
229

86 73

86
88
155

Unit : mm

20
4. HEATING CAPACITY
Indoor unit Outdoor unit
AER318SH3
AWR318HLE
AER318SH
AER322SH3
AWR322HLE
AER322SH
Heating capacity ratio (%)

120

110

100

90

80

70

60

50

40

30

20

10

0
8 5 0 5 7 10 15

Outdoor temperature (C DB)


NOTE

1) Point of Rating condition


Black dot in the chart indicate the following rating condition.
Indoor : 20C DB
Outdoor : 7C DB / 6C WB
2) Above characteristics indicate instantaneous operation, which does not take into
consideration defrost operation.
3) Fan speed : High

21
5. AIR THROW DISTANCE CHART
Indoor Unit AWR318HLE

Cooling

Room air temp. : 27C


Fan speed : High

Horizontal distance (m)


1 2 3 4 5 6 7 8 9
0
Axis air velocity (m/s)
Vertical distance (m)

4
Axis air velocity
0
Flap angle
30

Heating

Room air temp. : 20C


Fan speed : High

Horizontal distance (m)


1 2 3 4 5 6 7 8 9
0
Axis air velocity (m/s)
Vertical distance (m)

4
Axis air velocity
45
Flap angle
60

22
Indoor Unit AWR322HLE

Cooling

Room air temp. : 27C


Fan speed : High

Horizontal distance (m)


1 2 3 4 5 6 7 8 9
0
Axis air velocity (m/s)
Vertical distance (m)

4
Axis air velocity
0
Flap angle
30

Heating

Room air temp. : 20C


Fan speed : High

Horizontal distance (m)


1 2 3 4 5 6 7 8 9
0
Axis air velocity (m/s)
Vertical distance (m)

4
Axis air velocity
45
Flap angle
60

23
6. REFRIGERANT FLOW DIAGRAM

Insulation of Refrigerant Tubing


Insulation

IMPORTANT Thickness: Thickness:


Min. 8 mm Min. 8 mm
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of Narrow tube
condensation, both tubes must be well insulated with a proper Wide tube
insulation material. The thickness of the insulation should be a
min. 8 mm.

After a tube has been insulated,


CAUTION

! never try to bend it into a narrow


curve because it can cause the tube
to break or crack.

INDOOR UNIT AWR318HLE


OUTDOOR UNIT AER318SH3

24
INDOOR UNIT AWR318HLE
OUTDOOR UNIT AER318SH

INDOOR UNIT AWR322HLE


OUTDOOR UNIT AER322SH3
AER322SH

25
7. ELECTRICAL DATA
Electrical Characteristics

Indoor Unit AWR318HLE


Outdoor Unit AER318SH3

Cooling

Indoor Unit Outdoor Unit


Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50 Hz 400 V 3N ~ 50 Hz
Running Amps. A 0.29 0.42 2.89 3.60
Rating Conditions
Power Input kW 0.067 0.085 2.05 2.20
Running Amps. A 0.29 0.42 4.29 5.00
Full Load Conditions
Power Input kW 0.067 0.085 2.85 3.00

Rating Conditions: Indoor Air Temperature 27C DB / 19C WB


Outdoor Air Temperature 35C DB
Full Load Conditions: Indoor Air Temperature 32C DB / 23C WB
Outdoor Air Temperature 43C DB

Heating

Indoor Unit Outdoor Unit


Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50 Hz 400 V 3N ~ 50 Hz
Running Amps. A 0.29 0.42 2.99 3.70
Rating Conditions
Power Input kW 0.067 0.085 2.15 2.30
Running Amps. A 0.29 0.42 4.33 5.04
Full Load Conditions
Power Input kW 0.067 0.085 3.10 3.25

Rating Conditions: Indoor Air Temperature 20C DB


Outdoor Air Temperature 7C DB / 6C WB
Full Load Conditions: Indoor Air Temperature 25C DB
Outdoor Air Temperature 22C DB / 17C WB

26
Indoor Unit AWR318HLE
Outdoor Unit AER318SH

Cooling

Indoor Unit Outdoor Unit


Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50 Hz
Running Amps. A 0.29 0.42 9.79 10.5
Rating Conditions
Power Input kW 0.067 0.085 2.05 2.20
Running Amps. A 0.29 0.42 11.9 12.6
Full Load Conditions
Power Input kW 0.067 0.085 2.50 2.65

Rating Conditions: Indoor Air Temperature 27C DB / 19C WB


Outdoor Air Temperature 35C DB
Full Load Conditions: Indoor Air Temperature 32C DB / 23C WB
Outdoor Air Temperature 43C DB

Heating

Indoor Unit Outdoor Unit


Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50 Hz
Running Amps. A 0.29 0.42 10.3 11.0
Rating Conditions
Power Input kW 0.067 0.085 2.20 2.35
Running Amps. A 0.29 0.42 13.4 14.1
Full Load Conditions
Power Input kW 0.067 0.085 2.85 3.00

Rating Conditions: Indoor Air Temperature 20C DB


Outdoor Air Temperature 7C DB / 6C WB
Full Load Conditions: Indoor Air Temperature 25C DB
Outdoor Air Temperature 22C DB / 17C WB

27
Indoor Unit AWR322HLE
Outdoor Unit AER322SH3

Cooling

Indoor Unit Outdoor Unit


Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50 Hz 400 V 3N ~ 50 Hz
Running Amps. A 0.36 0.52 3.92 4.80
Rating Conditions
Power Input kW 0.083 0.117 2.60 2.80
Running Amps. A 0.36 0.52 6.22 7.10
Full Load Conditions
Power Input kW 0.083 0.117 3.97 4.17

Rating Conditions: Indoor Air Temperature 27C DB / 19C WB


Outdoor Air Temperature 35C DB
Full Load Conditions: Indoor Air Temperature 32C DB / 23C WB
Outdoor Air Temperature 43C DB

Heating

Indoor Unit Outdoor Unit


Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50 Hz 400 V 3N ~ 50 Hz
Running Amps. A 0.36 0.52 4.12 5.00
Rating Conditions
Power Input kW 0.083 0.117 2.80 3.00
Running Amps. A 0.36 0.52 6.30 7.18
Full Load Conditions
Power Input kW 0.083 0.117 4.00 4.20

Rating Conditions: Indoor Air Temperature 20C DB


Outdoor Air Temperature 7C DB / 6C WB
Full Load Conditions: Indoor Air Temperature 25C DB
Outdoor Air Temperature 22C DB / 17C WB

28
Indoor Unit AWR322HLE
Outdoor Unit AER322SH

Cooling

Indoor Unit Outdoor Unit


Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50 Hz
Running Amps. A 0.36 0.52 11.9 12.8
Rating Conditions
Power Input kW 0.083 0.117 2.60 2.80
Running Amps. A 0.36 0.52 15.0 15.9
Full Load Conditions
Power Input kW 0.083 0.117 3.28 3.48

Rating Conditions: Indoor Air Temperature 27C DB / 19C WB


Outdoor Air Temperature 35C DB
Full Load Conditions: Indoor Air Temperature 32C DB / 23C WB
Outdoor Air Temperature 43C DB

Heating

Indoor Unit Outdoor Unit


Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50 Hz
Running Amps. A 0.36 0.52 12.9 13.8
Rating Conditions
Power Input kW 0.083 0.117 2.80 3.00
Running Amps. A 0.36 0.52 15.7 16.6
Full Load Conditions
Power Input kW 0.083 0.117 3.38 3.58

Rating Conditions: Indoor Air Temperature 20C DB


Outdoor Air Temperature 7C DB / 6C WB
Full Load Conditions: Indoor Air Temperature 25C DB
Outdoor Air Temperature 22C DB / 17C WB

29
8. ELECTRIC WIRING DIAGRAMS
To avoid electrical shock hazard, be sure to
WARNING disconnect power before checking, servicing
and/or cleaning any electrical parts.
Indoor unit : AWR318HLE

Indoor unit : AWR322HLE

30
Outdoor unit: AER318SH3

Outdoor unit: AER318SH

31
Outdoor unit: AER322SH3

Outdoor unit: AER322SH

32
9. REFRIGERANT R407C :
SPECIAL PRECAUTIONS WHEN SERVICING UNIT
9-1. Characteristics of new refrigerant R407C
9-1-1. What is new refrigerant R407C
R407C is a new refrigerant that contains three types of non-azeotropy-type mixed refrigerant which does
not adversely affect the Earth's ozone layer. Its refrigeration capacity and energy efficiency are about the
same level as the conventional refrigerant R22

9-1-2. Components (mixing proportions)


HFC32 (23%) / HFC125 (25%) / HFC134a (52%)
9-1-3. Characteristics
Less toxic, more chemically stable refrigerant.
Composition of refrigerant R407C changes whether it is in gaseous phase or liquid phase. Thus, when there is a
refrigerant leak the basic performance of the air conditioner may be degraded because of a change in
composition of the remaining refrigerant. Therefore, do not add new refrigerant. Instead, recover the
remaining refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified
amount of refrigerant with the new refrigerant at its normal mixed composition state (liquid phase).
When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or liquid
phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in
gaseous state. Thus, always charge the refrigerant while it is in the liquid phase.

Ether-type oil is used for the compressor oil for R407C-type units, which is
CAUTION different from the mineral oil used for R22. Thus more attention to moisture
prevention and faster replacement work compared with conventional models are
required.

9-2. Checklist before servicing


Tubing precautions
Refrigerant R407C is more easily affected by dust or moisture compared with R22, thus be sure to temporarily
cover the ends of the tubing with caps or tape prior to installation.

No addition of compressor oil for R407C


No additional charge of compressor oil is permitted.

No use of refrigerant other than R407C


Never use a refrigerant other than R407C.

If refrigerant R407C is exposed to fire


Through welding, etc., toxic gas may be released when R407C refrigerant is exposed to fire. Therefore, be sure
to provide ample ventilation during installation work.

Caution in case of R407C leak


Check for possible leak points with the special leak detector for R407C. If a leak occurs inside the room,
immediately provide thorough ventilation.

33
9-3. Tools specifically for R407C
For servicing, use the following tools for R407C
Tool Distinction Tool Name
Gauge manifold
Charging hose
Gas leak detector
Refrigerant cylinder
Charging cylinder
Tools specifically for R407C Refrigerant recovery unit
Vacuum pump with anti-reverse flow (1)
(Solenoid valve-installed type, which prevents oil from flowing back into the unit
when the power is off, is recommended.)
Vacuum pump (2) ..... can be used if the following adapter is attached.
Vacuum pump adapter (reverse-flow prevention adapter) (3).
(Solenoid valve-installed adapter attached to a conventional vacuum pump.)
Electronic scale for charging refrigerant
Flare tool
Bender
Tools which can be commonly Torque wrench
used for R22 and R407C Cutter, Reamer
Welding machine, nitrogen gas cylinder

The above tools specifically for R407C must not be used for R22. Doing so will
CAUTION cause malfunction of the unit.

For the above vacuum pump (1, 2) and vacuum pump adapter (3) , those for
R22-type units can be used for R407C-type. However, they must be used
exclusively for R407C and never alternately with R22.

9-4. For tubing installation procedures


When the tubes are connected, always apply HAB oil on the flare portions to improve the sealing of
tubing.
The following is the HAB oil generally used:
Esso: ZERICE S32

NOTE For details on tubing installation procedures, refer to the installation manuals attached to the indoor
unit and outdoor unit.

34
21040 Oggiona con S. Stefano (VA) - Via Per Solbiate, 49 - Italy
Direzione e Uffici: Via Varese, 90 - 21013 GALLARATE (VA)
Tel. 0331/755.111 - Telex. 331060 ARGO I - FAX 0331/776.240