Aacalc 9 Demo 1

This document contains the results of a hydraulic calculation for a sprinkler system according to NFPA 13 standards. It analyzes a system with 24 pipes of varying sizes that connect to 12 operating sprinkler heads. It provides details on flow rates, velocities, pressures, and heights for each pipe and sprinkler head. The most remote area of the system is serviced by sprinkler head number 8 with a flow of 58.5 L/min and pressure of 0.535 bar.

Uploaded by

Avk Sanjeevan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
943 views2 pages

Aacalc 9 Demo 1

This document contains the results of a hydraulic calculation for a sprinkler system according to NFPA 13 standards. It analyzes a system with 24 pipes of varying sizes that connect to 12 operating sprinkler heads. It provides details on flow rates, velocities, pressures, and heights for each pipe and sprinkler head. The most remote area of the system is serviced by sprinkler head number 8 with a flow of 58.5 L/min and pressure of 0.535 bar.

Uploaded by

Avk Sanjeevan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Free Sprinkler Hydraulics Program AACALC9 22:00 31 January 2017 Page 1 of 2

First Demonstration Example from NFPA 13 Source duty [775.1L/[email protected]]

Results presentation from AACALC9 [16.10.14] for NFPA 13 / 15 Rules

[Q 1] Project Name/Ref = First Demonstration Example from NFPA 13


[Q 2] Owner/Occupant = ABC Company
[Q 3] Location =
[Q 4] Building No/Ref = Employee Garage
[Q 5] Hazard = Ordinary Hazard Group 1
[Q 6] Contractor/Designer = Contractor
[Q 7] Address = Address
[Q 8] Approving Agency = Do not know
[Q 9] Comments/Limitations =
[Q10] Remote Area Ref = Top Left Hand Corner
[Q11] Design Area m2 [0>1000] = 140.40
[Q12] Density mm/min [0>100] = 5.00
[Q13] Max Head Area m2 [0>40] = 11.70
[Q14] Head "K" factor [2>6000] = 80.0
[Q15] Spare for future = -
[Q16] Spare for future = -
[Q17] Static Pressure bars [0>15] = 0.00
[Q18] Residual Pressure bars [0>15] = 0.00
[Q19] At Flow Rate L/min [0>15000] = 0
[Q20] Pressure Test Comments = -
[Q21] Velocity Pressure [Y/N] = No
[Q22] Start height in m [-20>20] = 0.000
Number of pipes = 24
Pipe sizes = 25 to 80 mm
Flow rates = 58.5 to 775.1 L/min
Velocities = 1.75 to 4.18 m/s
Lengths = 0.300 to 32.700 m
End pressures = 0.535 to 3.072 bar
Pressure drops = 0.006 to 0.708 bar
Pressure drops per m run = 8.9 to 36.2 mbar/m

Number of operating heads = 12


"K" factors = 80.0 to 80.0
Heights above source = 4.800 to 4.800 m
Flow rates = 58.5 to 70.9 L/min
Minimum flow margin = 0.00 to 12.40 L/min
Pressures = 0.535 to 0.785 bar
Minimum pressure margin = 0.000 to 0.251 bar

Most remotest head = 8


Volume of pipework = 0.383 cu.m
Data file name = aacalc9demo1.aa9

SOURCE DUTY AT PIPE 1 = 775.1 L/min at 3.072 bar

Operating sprinkler heads / nozzles / hosereels / hydrants

+-----+--------+--------------+---------+--------------+-------+---------------+---+------------------------------+
| Head| "K" |Flows in L/min| A r e a |Density mm/min| Height| Pipe to head |MRH| P r e s s u r e s b a r s|
| no | factor |Minimum:Actual| m2 |Minimum:Actual| m | No mm Vel | | Minimum:Normal: Vel : Total|
+-----+--------+--------------+---------+--------------+-------+---------------+---+------------------------------+
| 1 80.0 58.5 70.9 11.700 5.00 6.06 4.800 9 40 3.3 0.535 0.785 0.785|
| 2 80.0 58.5 67.3 11.700 5.00 5.75 4.800 10 40 2.4 0.535 0.707 0.707|
| 3 80.0 58.5 63.6 11.700 5.00 5.44 4.800 11 32 2.1 0.535 0.633 0.633|
| 4 80.0 58.5 59.8 11.700 5.00 5.11 4.800 12 25 1.8 0.535 0.558 0.558|
| 5 80.0 58.5 69.4 11.700 5.00 5.93 4.800 15 40 3.2 0.535 0.753 0.753|
| 6 80.0 58.5 65.9 11.700 5.00 5.63 4.800 16 40 2.4 0.535 0.678 0.678|
| 7 80.0 58.5 62.3 11.700 5.00 5.33 4.800 17 32 2.1 0.535 0.607 0.607|
| 8 80.0 58.5 58.5 11.700 5.00 5.00 4.800 18 25 1.8 Yes 0.535 0.535 0.535|
| 9 80.0 58.5 69.8 11.700 5.00 5.97 4.800 21 40 3.3 0.535 0.761 0.761|
| 10 80.0 58.5 66.2 11.700 5.00 5.66 4.800 22 40 2.4 0.535 0.685 0.685|
+-----+--------+--------------+---------+--------------+-------+---------------+---+------------------------------+
| 11 80.0 58.5 62.6 11.700 5.00 5.35 4.800 23 32 2.1 0.535 0.613 0.613|
| 12 80.0 58.5 58.8 11.700 5.00 5.03 4.800 24 25 1.8 0.535 0.540 0.540|
+-----+--------+--------------+---------+--------------+-------+---------------+---+------------------------------+
Printout from AACALC9 by Alan Ashfield continues on page 2
Free Sprinkler Hydraulics Program AACALC9 22:00 31 January 2017 Page 2 of 2
First Demonstration Example from NFPA 13 Source duty [775.1L/[email protected]]

All pipes to above sprinkler heads / nozzles


+-----+----+----+---+------+-------+-------+-----------+--------+-----+------+-------+----------------------------+
| Pipe|Size|Type|H-W| Bore | Flow | Length|E4LTGGABCAS|Total Eq| Vel |Static| Height| P r e s s u r e s b a r s|
| no | mm | |"C"| mm | L/min | m |L5TEVLVVVNT|Length m| m/s | m | m | Start :Frict: Vel : E n d|
+-----+----+----+---+------+-------+-------+-----------+--------+-----+------+-------+----------------------------+
| 1 80 CM 150 75.70 775.1 0.300 1 6.306 2.9 0.000 0.000 3.072 -0.056 3.016|
| 2 80 CM 150 75.70 775.1 0.300 1 0.707 2.9 0.000 0.000 3.016 -0.006 3.009|
| 3 80 CM 150 75.70 775.1 14.400 1 17.199 2.9 0.000 0.000 3.009 -0.153 2.856|
| 4 80 S40 120 77.90 775.1 1.200 1 1.510 2.7 1.200 1.200 2.856 -0.018 2.721|
| 5 80 S40 120 77.90 775.1 3.300 1 5.740 2.7 3.300 4.500 2.721 -0.067 2.330|
| 6 80 S40 120 77.90 775.1 32.700 1 34.830 2.7 0.000 4.500 2.330 -0.408 1.922|
| 7 65 S40 120 62.70 775.1 21.000 21.000 4.2 0.000 4.500 1.922 -0.708 1.214|
| 8 40 S40 120 40.90 261.5 0.300 1 2.740 3.3 0.300 4.800 1.214 -0.099 1.085|
| 9 40 S40 120 40.90 261.5 5.850 1 8.290 3.3 0.000 4.800 1.085 -0.300 0.785|
| 10 40 S40 120 40.90 190.6 3.900 3.900 2.4 0.000 4.800 0.785 -0.079 0.707|
+-----+----+----+---+------+-------+-------+-----------+--------+-----+------+-------+----------------------------+
| 11 32 S40 120 35.10 123.4 3.900 3.900 2.1 0.000 4.800 0.707 -0.074 0.633|
| 12 25 S40 120 26.60 59.8 3.900 3.900 1.8 0.000 4.800 0.633 -0.075 0.558|
| 13 65 S40 120 62.70 513.6 3.000 3.000 2.8 0.000 4.500 1.214 -0.047 1.167|
| 14 40 S40 120 40.90 256.1 0.300 1 2.740 3.2 0.300 4.800 1.167 -0.095 1.042|
| 15 40 S40 120 40.90 256.1 5.850 1 8.290 3.2 0.000 4.800 1.042 -0.289 0.753|
| 16 40 S40 120 40.90 186.7 3.900 3.900 2.4 0.000 4.800 0.753 -0.076 0.678|
| 17 32 S40 120 35.10 120.8 3.900 3.900 2.1 0.000 4.800 0.678 -0.071 0.607|
| 18 25 S40 120 26.60 58.5 3.900 3.900 1.8 0.000 4.800 0.607 -0.072 0.535|
| 19 50 S40 120 52.50 257.5 3.000 3.000 2.0 0.000 4.500 1.167 -0.031 1.136|
| 20 40 S40 120 40.90 257.5 0.300 1 1.520 3.3 0.300 4.800 1.136 -0.053 1.053|
+-----+----+----+---+------+-------+-------+-----------+--------+-----+------+-------+----------------------------+
| 21 40 S40 120 40.90 257.5 5.850 1 8.290 3.3 0.000 4.800 1.053 -0.291 0.761|
| 22 40 S40 120 40.90 187.7 3.900 3.900 2.4 0.000 4.800 0.761 -0.076 0.685|
| 23 32 S40 120 35.10 121.4 3.900 3.900 2.1 0.000 4.800 0.685 -0.072 0.613|
| 24 25 S40 120 26.60 58.8 3.900 3.900 1.8 0.000 4.800 0.613 -0.073 0.540|
+-----+----+----+---+------+-------+-------+-----------+--------+-----+------+-------+----------------------------+

AACALC9 is in metric units only so not acceptable in America or Burma


For more information about all my programs, please visit https:\\www.freehc.net