1.0 Introduction
1.1 Background
1.2 Purpose of Report
4.0 Conclusion
1.1 Background
Perunding THD Sdn. Bhd. has been engaged to provide consulting engineering
services for the design of civil infrastructure services including water supply works for
"CADANGAN MENDIRI DAN MENYIAPKAN 9 UNIT KEDAI / PEJABAT 3 - TINGKAT
DI ATAS PLOT 1 - 9, PT 2529 - 2537 (LOT ASAL 10112 HINGGA 10118 YANG TELAH
PENYERAHAN MILIK DAN PEMBERIMILIKAN SEMULA), MUKIM GURUN,
KEDAH DARUL AMAN.
The purpose of this report is to present to Syarikat Air Darul Aman (SADA), Negeri kedah.
The Consultant's detailed design proposal for the water supply works for approval, prior to the
commencement of construction.
Water demand for the development has been based on SADA guidelines. Reference is also
made to "Design Criteria & Standard for Water Supply System" published by Water Supply
Branch of JKR Headquarters.
The basis of assessing the water demand for the proposed scheme is as in Table 1 attached.
COMPUTATION OF TOTAL WATER DEMAND FOR PERMOHONAN KEBENARAN MERANCANG
BAGI CADANGAN (6) UNIT RUMAH TERES 3 TINGKAT DI ATAS LOT 2549 (PT 61249) DAN
LOT 3311, SEKSYEN 47, BANDAR SUNGAI PETANI, DAERAH KUALA MUDA, KEDAH DARUL AMAN.
UNTUK TETUAN : GANDA PRESTASI SDN. BHD.
TABLE 1
L AMAN.
2.2 Design Criteria
a) Reticulation main are sized to carry the peak demand with peak factor of 2.5 I.e 2.5 x
A.D.D. (Average Daily Demand)
c) Fire fighting is based on one hydrant discharging at 18.94 l/s (250 gpm).
H = 10.6461 x Q 1.85
x 1
L C ( D ) 4.87
From the existing SADA's reservoir, water is supplied to the water tank.
Water is tapped off from the bulk metered at the entrance to the water tank.
Water supply is proposed to be tapered off from the existing main pipe.
The available pressure head at tapping point as carried out by SADA is 14.33m.
2.5 Conveyance and reticulation pipe network
(I) The reticulation system shall consist of min. 6" dia. HDPE ' PN12.5' pipes,
valve, hydrants and appertenances to JKA requirements. At all road, culvert
and drain crossing, mild steel or ductile iron pipes complying with BS534 and
3601 shall be used.
(ii) The design criteria adopted for the proposed reticulation network are
summarized as below :
4.0 Conclusion
As the design is in compliance with the requirement of Syarikat Air Darul Aman (SADA) Kedah,
we wish to seek approval for the design.
PERUNDING THD SDN. BHD.
20250
b) Demand data : -