TROUBLESHOOTING B62755EN/01
8.22
ALARM 414 (DIGITAL
SERVO SYSTEM IS
EXAMPLE OF DISPLAY
ABNORMAL) 414 SERVO ALARM:XAXIS AXIS NAME DETECTED
DETECTION IS DISPLAYED
SYSTEM ERROR
Points Check details by CNCs diagnostic fucntion and LED display on the servo
amplifier.
1)
#7 #6 #5 #4 #3 #2 #1 #0
DGN 0200 LV OVC HCA HVA DCA FBA OFA
STATUS
3)
#7 #6 #5 #4 #3 #2 #1 #0
DGN 0204 OFS MCC
352
B62755EN/01 8.TROUBLESHOOTING
D #6(LV):Insufficient
voltage alarm 1) Servo amp LED [2] turns on (control power shortage)
(START)
YES
Voltage is
normal ?
NO
Servo amplifier is
faulty
NO
Is voltage
normal ?
YES
Breaker off ?
NO
Turn off breaker and
check again
Is voltage NO
normal ?
353
8. TROUBLESHOOTING B62755EN/01
D #5(OVC):Over current
detection by software (START)
Larger than NO
* 1.7 times for motor 20S or
1.4 times ? larger.
YES
NO
Correct ?
YES
354
B62755EN/01 8.TROUBLESHOOTING
D #4(HCA):Abnormal
current alarm (START)
(Servo amp. LED:[8]
lights)
Give a move command
and check wether the
alarm is generated
NO
Alarmed ?
YES
YES
Alarmed ?
NO
355
8. TROUBLESHOOTING B62755EN/01
Is voltage NO
normal ?
NO
Is acc/dec time is correct ?
Isnt load inertial too large ?
Is friction reduced by aging of
Servo amp. is faulty machine ?
356
B62755EN/01 8.TROUBLESHOOTING
D #2(DCA):Discharge alarm 1 Servo amp LED 4 lights (discharge control circuit is abnormal)
(START)
Generate at YES
power on ?
NO
Generate dur- NO
ing lowering of NO
vertical axis Frequent ?
YES
YES
Servo amp. is faulty
357
8. TROUBLESHOOTING B62755EN/01
Generate at YES 4 16
power on?
0V ALM
NO YES Is unit hot ?
Short betrween 15 and 16
when not used.
NO
Check resistance
across terminals
T1(15) and (16).
0W ? NO
NO
Disconnection of
cable between sep-
Separate type discharge arate type dischrge
unit is faulty unit and servo amp.
358
B62755EN/01 8.TROUBLESHOOTING
NOTE
This alarm is related with fullclosed system.
D Causes
1 Signal cable is disconnected or shortcircuited.
2 Serial pulse coder or position detector is faulty Refer to Notes 1.
3 Main CPU board or option 2 board is faulty. Refer to Notes 2.
CAUTION
1 After the pulse coder is replaced, reference position or
machines standard position is different from former one.
Adjust and set it correctly.
2 When the main CPU board is replaced, all the data stored
in memory is lost. Set NC data again, referring to chapter 3
input/output of data.
SCALEx
x is an axis number
From 1st axis to 4th axis are main CPU board. 5th axis or later are
option 2 board.
359
8. TROUBLESHOOTING B62755EN/01
D #0(OFA):Overflow alarm
CAUTION
When the main CPU board is replaced, all the data stored
in memory is lost. Set NC data again, referring to chapter
3 input/output of data.
When 1 is displayed at
DGN 204
#7 #6 #5 #4 #3 #2 #1 #0
DGN 0204 OFS MCC
#6(OFS): A/D converter used for current feedback in the digital servo is abnormal.
#5(MCC): Contacts of electromagnetic contactor in the servo amp. is blown.LED
7 lights.
D #5(MCC):Contacts of
electromagnetic
contactor is blown within (START)
servo amp.
Check LED of
servo amplifier LED [7] Contacts of electromagnetic
contactor is blown in servo
amplifier
YES
Check input power
voltage of servo amp.
<Normal input power voltage>
YES Correct? AC200/220/230V
+10%,15%
NO
360
B62755EN/01 8.TROUBLESHOOTING
D LED display
Display Meaning Explanation
Power off Power to the servo converter is not supplied.
NOTE
1st axis is L, 2nd axis is M.
D LVDC alarm When the electromagnetic contactor is turned on in the servo amp. or DC
voltage for the main circuit becomes low, this LED is lit.
Causes are;
1) Input voltage is insufficient.
2) Contacts of electromagnetic contactor in servo amp. is poor.
3) Power circuit in servo amp. is abnormal.
361
8. TROUBLESHOOTING B62755EN/01
D DCSW alarm This alarm is lit when the transistor for regenerative discharging turns on
more than 1 second.
Its causes are;
1) Mulfunction of servo amplifier such as regenerative discharge circuit.
2) Regenerative discharge energy is excessive due to cutting conditions.
D DCOH alarm This alarm is lit when regenerative discharge registance is overheated and
the thermost operates.
Its causes are ;
1) Average discharge energy is excessive due to frequent acc./dec. or no
use of balancer in vertical axis
2) Functioning of a thermostat in the power transformer when thermostat
signal TH1 and TH2 are connected.
D MCC alarm When turning on MCC, if the contacts are already on.
D Check terminals on When you open the cover of the terminal board, you can see the check
servo amp. terminal below LED.
OV 0V
D Current/volt
Type of unit A/V Type of unit (A/V)
A06B6066H234 3/10
A06B6066H244 10/10
362
B62755EN/01 8.TROUBLESHOOTING
D Current waveform
(Servo amplifier)
Check terminal
IRL IRM
Current check terminal
ISL ISM
0V +5V
Convert this
voltage into
current value
0V
Alarm display
363