WinCC Runtime Advanced (RT Advanced)
WinCC Runtime Advanced
WinCC Runtime Advanced
The following tables of system limits help you assess whether your project conforms to the system
limits of a given HMI device.
The specified maximum values are not additive. It cannot be guaranteed that configurations running
on the devices at the full system limits will be functional.
In addition to the specified limits, allowances must be made for restrictions imposed by configuration
memory resources.
Tags
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of tags in the project 6144 12288
Number of PowerTags 128 - 4096 128 8192
Number of elements per array 1600 1600
Number of local tags 2048 4096
Number of structures 999 999
Number of structure elements 400 400
Alarms
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of alarm classes 32 32
Number of discrete alarms 4000 6000
Number of analog alarms 500 500
Length of an alarm in characters 80 80
Number of process values per alarm 8 8
Size of the alarm buffer 1024 2048
Number of queued alarm events 500 500
Screens
-1-
WinCC Runtime Advanced (RT Advanced)
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of screens 500 750
Number of fields per screen 400 600
Number of tags per screen 400 400
Number of complex objects per screen
1) 40 40
Complex objects include: Bars, sliders, symbol library, clock, and all objects from the Con
1)
trols area.
Recipes
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of recipes 999 1000
Number of elements per recipe
1) 2000 2000
User data length in KB per data record 256 512
Number of data records per recipe 5000 5000
Reserved memory for data records in the in
-- --
ternal Flash
1) If arrays are used, each array element counts as one recipe element
Logs
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of logs 100 100
Number of entries per log (including all log
segments)
1) 500000 500000
Number of log segments 400 400
Cyclic trigger for tag logging 1 s 1 s
Number of tags that can be logged per log 6144 12288
-2-
WinCC Runtime Advanced (RT Advanced)
The number of entries for the "segmented circular log" logging method is the total number
1) for all sequential logs. The product of the number of sequential logs and the number of data
records per sequential log may not exceed the system limit
Trends
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of trends 800 800
Text lists and graphics lists
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of graphics lists 500 500
Number of text lists 500 500
Number of entries per text or graphics list 3500 500
Number of graphic objects 2000 4000
Number of text elements 30000 40000
Scripts
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of scripts 200 200
Communication
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of connections 8 8
Number of OPC connections including OPC
8 8
UA
Number of connections based on "SIMATIC
16 16
HMI HTTP"
-3-
WinCC Runtime Advanced (RT Advanced)
Maximum number of connected
4
1) 4
1)
Sm@rtClients (including a service client)
Help system
KTP400 TP700, TP1500 TP1900 TP2200
KP400 KP700 KP1500
TP900,
KP900
TP1200,
KP1200
Number of characters in a
320
1) 320
1) 320
1) 320
1) 320
1)
help text
500
2) 500
2) 500
2) 500
2) 500
2)
1) For devices with HMI device version 12 or lower
2) For devices with HMI device version higher than 12
Languages
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of runtime languages 32 32
Scheduler
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Time-triggered tasks
1) 48 48
1) Event-triggered tasks are not relevant for the system limits
User administration
-4-
WinCC Runtime Advanced (RT Advanced)
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Number of user groups 50 50
Number of authorizations 32 32
Number of users 100 100
Project
WinCC Runtime Ad WinCC Runtime Advanced
vanced Device version as of 13
Device version prior to
13
Size of the project file "*.fwc" No limiting No limiting
-5-