Generator Protection
Generator Protection
2164/01 EN
This Circular supersedes:
2164/00
Generator protection
Valid for: MWM Gas gensets
Contents:
General information
General generator protection
Differential protection relay
Earth fault protection relay
Synchronization
General mains protection
In the case of queries
General information
This technical circular was created in response to frequent requests in the field relating to
the setting of the generator protection.
Protection devices are to be provided which fully meet the requirements of the existing plant
and the regulations of the network operator, and which exhibit the following functions.
The setting values are to be coordinated with the respective network operator in coopera-
tion with the plant designer / person responsible for the plant. The setting values of the gen-
erator protection functions stated here are to be observed as maximum limits.
Imprint: Note:
Caterpillar Energy Solutions GmbH The part numbers stated in this documentation are not subject to the modification service.
Servicedokumentation For identifying spare parts, the spare part documentation has to be referred to.
M.Granson
Carl-Benz-Str. 1
68167 Mannheim
Germany
Phone: +49 621 384-8455
Fax: +49 621 384-8841
Copies to:
Date:
- TR
2016-05-13 - According to SIT 7010
OBJ_DOKU-67119-001.fm 1 2016
Technical Bulletin
2164/01 EN
OBJ_DOKU-67119-001.fm 2
Technical Bulletin
2164/01 EN
- I2 / IN (current in the negative sequence component / rated current) = 8% for continuous operation
OBJ_DOKU-67119-001.fm 3
Technical Bulletin
2164/01 EN
OBJ_DOKU-67119-001.fm 4
Technical Bulletin
2164/01 EN
- I2 / IN (current in the negative sequence component / rated current) = 8% for continuous operation
OBJ_DOKU-67119-001.fm 5
Technical Bulletin
2164/01 EN
Synchronization
The slip synchronization is advisable as a synchronization method.
At the switch-on moment, the voltage and frequency difference between the generator and
mains must be minimal.
The breaker closing times of the entire chain are to be observed and set accordingly in the
synchronization device.
OBJ_DOKU-67119-001.fm 6
Technical Bulletin
2164/01 EN
Protection devices that fully meet the requirements of the existing plant and the regulations
of the local network operator are to be provided.
The setting values are to be coordinated with the respective network operator in coopera-
tion with the plant designers / persons responsible for the plant.
The abovementioned setting values of the generator protection functions are to be ob-
served.
If permitted by the mains operator, the use of a vector shift relay is recommended which
initiates a power decoupling when triggered. The respectively valid technical connection
conditions of the network operator are to be observed. Once power has settled, an auto-
matic reverse synchronization is recommended.