D9412 Control Panel Installation Manual enUS 4674028939 PDF
D9412 Control Panel Installation Manual enUS 4674028939 PDF
D9412 Control Panel Installation Manual enUS 4674028939 PDF
Control Panels
Table of Contents
1 System Requirements 6
2 Introduction 7
2.1 Using this Program Entry Guide 7
2.2 Guide to UL 864 Programming Requirements for D9412GV4 and D7412GV4 Control Panels 7
2.3 Guide to UL 636 Programming Requirements for D9412GV4/ D7412GV4/D7212GV4 Control Panels 10
2.4 Guide to Programming Descriptions 11
2.5 Guide to Keypad Tools 11
2.5.1 Keypad Programming Menu 12
2.5.2 Service Bypass Menu 14
2.5.3 RF Points Menu 14
2.5.4 RF Repeaters Menu 15
2.5.5 RF Diagnostics Menu 15
2.5.6 IP Diagnostics Menu 16
5 Points 130
5.1 Point Index 130
5.2 Point Responses 132
5.2.1 Applications for Point Responses 9, D, and E: 132
5.2.2 Characteristics of a Fire Point: 133
5.3 Point Assignments 146
5.4 Cross Point Parameters 149
5.5 COMMAND 7 and COMMAND 9 151
7 AUXPARM 174
7.1 Automation 174
7.2 Miscellaneous 175
1 System Requirements
WARNING!
Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2007: UL
Listed and Classified control unit Model D9412GV4 or D7412GV4 or D7212GV4.
UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255 RW.
UL Listed Local Bell.
2 Introduction
For IP
Communications to
a D6600 Receiver
Enhanced Comm Yes Yes / No Set to Yes 40
Path1 IP Add1 (2, 3 Yes 000 to 255 Program a valid IP 41
or 4) address
Path 1 Poll Rate Yes 0, 5 to 65535 Program as 41
sec* necessary
Path 1 Ack Wait Yes 0, 5 to 65535 Program as 45
sec* necessary
P## Invisible Point = Yes (Keypads do not display alarm activity from this point.)
When using Modem IIIa2 communication type, the unique point text should be set to Hold-
Up, or equivalent language per the AHJ.
When using ContactID communication type, because the ContactID system doesnt provide
custom text, the hold-up point should be associated as a hold-up point at the receiving
station. Set Area # Delay Restorals as follows:
Area # Delay Restorals = No (Restoral report is sent when point restores.)
COMMUNICATIONS ........................................... 40
PATH 1 - 4 .......................................................... 40
IP MODULE CONFIG [ENT] B420 MODULE (1-2)
MODULE PARAM
NOTICE! DHCP ENABLE 180
To move UPnP ENABLE 184
through the ADDRESS PARAM
PROGRAMMING
IP ADDRESS .. 180
menu and
SUBNET
submenus, press
MASK ................ 181
[NEXT] or [PREV].
DEFAULT
GATEWAY .......... 182
To open a
PORT
menu or submenu,
NUMBER ........... 184
press [ENT].
DNS PARAM
To exit to the SERVER
previous level, press ADDRESS .......... 183
[ESC]. MODULE
HOSTNAME ....... 186
To send saved ENCRYPTION
changes to the AES KEY SIZE 185
control panel,
AES KEY ......... 185
exit from ROUTING GRP 1 - 4 ............................................... 30
ROUTING [ENT]
PROGRAMMING
RPS PARAMETERS [ENT]
mode.
RPS PASSCODE ................................................ 55
RPS PHONE NUMBER ....................................... 58
RPS IP ADDRESS .............................................. 41
RPS IP PORT ..................................................... 48
AREA PARAMETERS [ENT] AREA NUMBER 1-32 ............................................. 61
(1 - 8 for D7412GV4)(1 - 4 for D7212GV4)
COMMAND CENTER [ENT] CC NUM 1 - 16 ...................................................... 80 and
81
USER PASSCODE [ENT]............................................................................................. 126
POINT PARAMETERS [ENT] PT NUM 1-247 ....................................................... 146
(1-75 for D7412GV4)(1-40 for D7212GV4)
DISABLE KP PROG [ENT].......................................................................................... 101
Communications.................................................... 40
Select IP Path Path 1-4............................ 40
IP Module Config [ENTER] B420 Module (1-2)
Module Parameters
NOTICE! DHCP Enable.. 180
To move UPnP Enable.. 184
through the Address Parameters
Programming
IP ADDRESS... 180
menu and
Subnet Mask.. 181
submenus, press
Default
the Next softkey.
Gateway............. 182
Port Number.. 184
To open a
menu or submenu, DNS Parameters
press [ENTER]. Server
Address.............. 183
To exit to the Module
previous level, Hostname.......... 186
press the Exit Encryption
softkey. AES Key Size.. 185
AES
To send saved
Encryption Key... 185
changes to the Route Group 1-4....................................................... 30
Routing [ENTER]
control panel,
RPS Parameters [ENTER]
exit from
Programming RPS Passcode....................................................... 55
mode. RPS Phone Number............................... 58
RPS IP Address..................................... 41
RPS IP Port........................................... 48
Area Parameters [ENTER] Area Number 1-32..................................................... 61
(1 - 8 for D7412GV4)(1 - 4 for D7212GV4)
Command Center [ENTER] CC Number 1-16...................................................... 80 and
81
User Passcode [ENTER].............................................................................................. 126
Point Parameters [ENTER] PT NUM 1-247.......................................................... 146
(1-75 for D7412GV4)(1-40 for D7212GV4)
Disable Keypad Programming [ENT]........................................................................... 101
RF POINTS [ENT]
STATES ....................... 193
SIGNAL STRENGTH..... 193
RF REPEATER ........................................................................................
NOTICE!
Press [NEXT] or [PREV] to move through the RF DIAGNOSTICS menu and submenus.
Press [ENT] to open a menu or submenu.
Press [ESC] to exit to the previous level.
RF Points [ENTER]
States ........................ 193
Signal Strength........... 193
RF Repeater ..........................................................................................
NOTICE!
Press Next softkey to move through the RF Diagnostics menu and submenus.
Press [ENTER] to open a menu or submenu.
Press the Exit softkey to exit to the previous level.
3.1 Phone
The control panel can dial as many as four different telephone numbers when sending event
reports. Refer to Section 3.3 Routing, page 23 for information about event report routing and
communication protocols.
NOTICE!
When using PSTN telephone lines, program two telephone numbers to meet UL 864
requirements (D9412GV4 and D7412GV4).
Phone #
Default: Blank
Selection: Up to 24 characters
0 to 9 Numbers 0 through 9
C 3-sec pause
D 7-sec dial-tone detection
# or * Used for the same purpose as pressing this key on a telephone keypad
when manually dialing. For example, an asterisk (*) may be needed to
access your long distance service. Do not use these characters when
pulse dialing.
Blank Control panel dials no phone number.
Programming this item Blank does not disable phone routing. To
disable reporting to this phone, refer to Section 3.3 Routing, page 23.
This is the telephone number the control panel dials to contact the central station receiver
when sending event reports. This number is Phone 1 referred to in the prompts in
Section 3.3 Routing, page 23.
The control panel waits for a break in the dial tone after dialing the first digit. If the control
panel must dial a digit (for example, 9) to access an outside line, place a C before the phone
number. The control panel waits 2 sec and does not wait for the dial tone break.
The control panel is programmed with a 7-sec dial tone detect period. When a dial tone is
detected or the waiting period ends, the control panel begins to dial. To extend the dial tone
detect period, place a D before the phone number. To insert a pause during or after dialing,
use C in the number sequence. For example, if the control panel hangs up before it hears the
ModemIIIa2 ACK tone from the D6500 or D6600, program extra Cs after the phone number.
The control panel waits on line for two extra seconds for each C programmed.
Enter up to 24 of the characters shown in the Phone # table to define dialing characteristics.
For SIA CP-01 Compliance
Call Waiting Disable
If the telephone system at the installation site uses the Call Waiting feature, ensure that the
primary telephone reporting number is programmed to disable Call Waiting.
If you program the primary phone number with a sequence to temporarily disable Call Waiting
(typically *70 pause, but verify with the phone service provider) followed by the phone
number, you should program the backup phone number without the Call Waiting cancel
sequence. If the subscriber cancels Call Waiting without notifying their alarm installing
company, the control panel can still send reports using the backup number.
CAUTION!
Dialing a Call Waiting sequence on a non-Call Waiting line prevents the system from dialing the
central station receiver successfully.
NOTICE!
Example: If the central station telephone number is 555-1234, and the primary Route Group
destination is Phone 1, program Phone 2 with the following sequence: *70C5551234.
4. The Pause (3-sec pause - "C") and DT Detect (Dial Tone Detect - "D") softkeys enter
special characters. The Backspace softkey allows you to erase characters. The Clear
softkey allows you to clear the entire phone number. The [COMMAND] and [ENTER] keys
allow you to enter an * or a #. Use the softkeys, the number buttons, and the
[COMMAND] and [ENTER] keys on the keypad to enter the new phone number.
5. Press the Save softkey.
When the keypad reads Parameter Saved, your selection has been configured.
Phone # Format
Default: ModemIIIa2
Selection: ModemIIIa2 or Contact ID
ModemIIIa2 ModemIIIa2 Communication Format
Contact ID ANSI-SIA Contact ID
Central Station Receiver Format for Transmission of Reports: Modem format provides many
reporting advantages over the Contact ID format. Refer to the D6500 Report Directory (P/N:
74-04651-001) for more information about the effect of reporting formats.
Reports identify points as 001 through 247 and passcode User ID codes as 000 through 999 at
the D6500 or D6600 Receiver (unless Point/User Flag is programmed Yes; refer to
Section Point/User Flag, page 19 in this section). When reporting point events, ModemIIIa2
Communication Format also sends point text to the D6500 or D6600 as programmed in Point
Assignments.
Point/User Flag
Default: No
Selection: Yes or No
Yes The control panel sends a flag with each report telling the D6500 or
D6600 to convert point numbers and User ID numbers to COMEX
format. Refer to Table 3.1, Page 20 and Table 3.2, Page 21 for
conversion information. When this parameter is programmed Yes,
points and User ID numbers are converted, regardless of the
programming of the D6500 or D6600 Receiver for output to the
computer system. Refer to Appendix C in the Conettix D6600/D6100
Receiver/Gateway Computer Interface Manual (P/N: 4998122703).
No The control panel does not send the flag. The D6500 or D6600 outputs
point numbers as 001 to 247 (rather than 100 to 732) and User ID
numbers as 000 to 999 (rather than 000 to F08), as indicated in
Table 3.1, Page 20 and Table 3.2, Page 21.
This program item determines how point and User ID numbers are presented at the D6500 or
D6600 display, printer, and computer RS-232 output.
When Phone # Format is ModemIIIa2, the control panel sends expanded Bosch ModemIIIa2
Communication Format reports to the D6500 or D6600. If your central station data files are
not set up for point and User ID number reporting, you can use this program item to convert
these numbers to COMEX Reports.
When Phone # Format is ModemIIIa2, the control panel sends expanded Bosch ModemIIIa2
Communication Format Reports to the receiver. Point/User Flag affects Bosch ModemIIIa2
Communication Format data as shown in Table 3.1, Page 20. The Bosch Security Systems, Inc.
D6500 or D6600 Receiver adds the leading zero in the User ID number with Point/User Flag
programmed No.
1 B 91 1
2 C 92 2
3 D 93 3
4 E 04 4
5 F 95 5
6 6 96 0
7 7
8 8
DTMF Dialing
Default: Yes
Selection: Yes or No
Yes Dials the programmed phone number(s) using DTMF.
No Pulse dialing only.
Use dual-tone multi-frequency (DTMF) to dial the central station receiver phone number(s) for
event reports, or to dial the remote programming software (RPS).
Default: 0
Selection: 0, 10 to 240
0 No phone line supervision.
10 to 240 Enter the number of seconds (in 10 sec increments) you wish to wait
before indicating trouble. After a faulted phone line restores, it takes
the same amount of time to start restoral responses.
Phone line trouble responses: Keypads display SERVC PH LINE # to indicate which phone line
failed. The keypad initiates a trouble tone if Buzz on Fail is Yes and CC Trouble Tone is Yes.
With dual phone lines (using the D928 Module), the restored phone line handles all messages
regardless of the phone lines number.
Phone, Trouble, and Restoral Events report when they occur. They report also when a
Diagnostic Report is initiated from a keypad or by a Sked.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to a non-zero
value.
Alarm On Fail
Default: No
Selection: Yes or No
Yes Generate alarm responses when a phone line fails.
No Phone failures report as trouble responses for Area 1 or the account
number associated with Area 1.
NOTICE!
To meet UL 864 requirements, set this parameter to No.
Phone Supervision Time must be programmed to use this feature.
Phone Failure Alarm Responses: The Alarm Bell relay for Area 1 activates. All Phone Event
messages report as Area 1 and the account number for Area 1.
Buzz On Fail
Default: Yes
Selection: Yes or No
Yes Generate panel-wide trouble tones and display PHONE FAIL # at
keypads when a Phone Fail Event occurs.
No Does not generate trouble tones at keypads when a Phone Fail Event
occurs. PHONE FAIL # still displays.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to Yes.
NOTICE!
Phone Supervision Time must be programmed to use this feature.
When Buzz on Fail is Yes, users can disable the resulting trouble tone on individual keypads
by setting CC# Trouble Tone to No.
Default: No
Selection: Yes or No
Yes The D928 Dual Phone Line Module is installed. The LEDs on the D928
light to indicate primary or secondary line trouble and COMM FAIL.
No D928 Dual Phone Line Module is not installed.
NOTICE!
When using two telephone lines, set this parameter to Yes to meet UL 864 requirements
(D9412GV4 and D7412GV4).
NOTICE!
Program Phone Supervision Time when using two phone lines.
NOTICE!
The D7212GV4 does not support the use of the D928 Dual Phone Line Switcher. Leave this
prompt set to its default value.
Default: No
Selection: Yes or No
Yes Off-normal events listed in Routing Group Test Reports are reported to
the central station.
No Off-normal conditions for the events listed in the Routing Group Test
Reports at test time are not reported.
Use this program item to add system event information to scheduled Test Reports. Refer to
Section 6 Schedules (Skeds), page 154.
NOTICE!
This parameter relates to Sked Function Code 9 (Test Report) because it allows a Sked to
send Expanded Test Report information. Expand Test Report does not affect Sked Function
Codes 28 (Expanded Off-Normal Test Report) and 29 (Non-Expanded Off-Normal Test
Report).
3.3 Routing
Use routing to select full or partial groups of events to report to up to eight different
destinations (four over phone, four over network). Routing includes choosing the most
important destination (route number), reporting the events to a single or multiple destination,
and selecting a backup destination if the events fail.
Event routing can be sent over one of the following:
Standard telephone lines
Local-area network (LAN)
Wide-area network (WAN)
General Packet Radio System (GPRS)
Sending events over a LAN or WAN requires a network interface module (NIM), such as the
DX4020 or B420. Sending events over GPRS requires a special (ITS-DX4020-G).
Event Priority
Table 3.5, Page 29 shows the description of each event, its priority, and Modem IIIa2 Event
Code.
Default Yes
Selection: Yes or No
Yes The control panel uses the same authentication keys to communicate
with both the primary and backup paths that are the same receiver and
upon detection of a Communication Trouble on either the primary or
backup enhanced communication paths, the working path immediately
changes to the faster poll rate.
No The control panel uses separate authentication keys to communicate
with the primary and backup receivers and upon detection of a
Communication Trouble on either the primary or backup enhanced
communication paths, the working path continues to use its configured
poll rate.
For Example: This would be used when a DX4020 is reporting to a receiver over a LAN/ WAN
and a ITS-DX4020-G is reporting to the same receiver over the Internet from the cellular
service provider. This configuration also typically has the poll rate for the ITS-DX4020-G set to
a slower poll rate than the primary such as every 4 hours.
NOTICE!
In the above example, if there is a Communication Trouble Condition on the DX4020, then the
ITS-DX4020-G will poll at the configured poll rate of the DX4020. If the poll rate of the DX4020
is set to 5 minutes or faster, there is a possibility of excessive data usage that may exceed
your data plan with the cellular service provider. Be sure that any Communication Trouble
events are addressed as soon as possible.
R# Primary Device
Default: No Device
Selection: No Device, Phone 1..4, SDI ## Path 1..4
Phone 1 Phone 1 is this groups primary destination.
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), program a Primary Device.
R# Backup Device
Default: No Device
Selection: No Device, Phone 1..4, SDI ## Path 1..4
Phone 1 Phone 1 is this groups backup destination if the primary destination
fails.
Phone 2 Phone 2 is this groups backup destination if the primary destination
fails.
Phone 3 Phone 3 is this groups backup destination if the primary destination
fails.
Phone 4 Phone 4 is this groups backup destination if the primary destination
fails.
SDI 88 Path 1 Path 1 on SDI 88 is this group's backup destination if the primary
destination fails.
SDI 88 Path 2 Path 2 on SDI 88 is this group's backup destination if the primary
destination fails.
SDI 88 Path 3 Path 3 on SDI 88 is this group's backup destination if the primary
destination fails.
SDI 88 Path 4 Path 4 on SDI 88 is this group's backup destination if the primary
destination fails.
SDI 92 Path 1 Path 1 on SDI 92 is this group's backup destination if the primary
destination fails.
SDI 92 Path 2 Path 2 on SDI 92 is this group's backup destination if the primary
destination fails.
SDI 92 Path 3 Path 3 on SDI 92 is this group's backup destination if the primary
destination fails.
SDI 92 Path 4 Path 4 on SDI 92 is this group's backup destination if the primary
destination fails.
SDI2-1 Path 1 Path 1 on SDI2-1 is this group's backup destination if the primary
destination fails.
SDI2-1 Path 2 Path 2 on SDI2-1is this group's backup destination if the primary
destination fails.
SDI2-1 Path 3 Path 3 on SDI2-1 is this group's backup destination if the primary
destination fails.
SDI2-1 Path 4 Path 4 on SDI2-1 is this group's backup destination if the primary
destination fails.
SDI2-2 Path 1 Path 1 on SDI2-2 is this group's backup destination if the primary
destination fails.
SDI2-2 Path 2 Path 2 on SDI2-2 is this group's backup destination if the primary
destination fails.
SDI2-2 Path 3 Path 3 on SDI2-2 is this group's backup destination if the primary
destination fails.
SDI2-2 Path 4 Path 4 on SDI2-2 is this group's backup destination if the primary
destination fails.
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), program a Backup Device.
Select the communication device and the backup destination. The backup device is used
when the primary device fails to reach the programmed destination.
Refer to Section 3.4 Programming Path Numbers and Network Addresses for Enhanced
Communications, page 40 to enable enhanced communication paths.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the Route Group 1 - 4 option.
2. At the Route Group 1 - 4 prompt, enter the route group number you wish to configure
and press [ENTER]. The keypad reads Rt Group 1 Primary, and then the current
configuration (for example, SDI 88 PATH 4).
3. Press the Backup softkey. The keypad reads Rt Group 1 Primary, and then the current
configuration (for example, SDI 88 PATH 4). The Primary device cannot be set to No
Device before setting the Backup Destination.
4. To change the configuration, press the Edit softkey, and then press the Next or the
Previous softkey to scroll through the options, as listed in Section R# Backup Device,
page 32.
5. When the keypad reads the desired configuration option, press the Save softkey to select
it.
When the keypad reads Parameter Saved, your selection has been configured.
Burglar Reports
Select Yes to send a report when the event occurs. Refer to Table 3.7, Page 34.
NOTICE!
R# Unverified Evt is sent when a single point programmed in Cross Point Group faults into an
alarm condition, then restores before the Cross Point Time elapses.
R# Unverified Evt encompasses both Fire and Non-fire points, but is not related to the A#
Verify Time used for smoke detectors.
NOTICE!
Restoral Reports are not sent if the control panel resets after a point is bypassed and then
unbypassed. This is true for both Fire and Non-fire points.
User Reports
Select Yes to send a report when the event occurs.
Test Reports
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), enable Test Reports.
Diagnostic Reports
Selecting Yes enables sending a report when the event occurs. If the off-normal state of the
events indicated by footnote 1 in Table 3.10, Page 37 still exists, the events report when a
Test Report is enabled and Expanded Test Report is programmed Yes. Refer to the Test
Reports sub-prompt in Section 3.3.9 Communication Attempts, page 30.
NOTICE!
Enable Rt Comm Fail and Rt Comm Restore in only one route group.
Relay Reports
Selecting Yes enables sending a report when the event occurs.
NOTICE!
When activating an on-board relay using remote automation software, the GV4 Series Control
Panels log and print the resulting event as:
Relay 250 (Relay A)
Relay 251 (Relay B)
Relay 252 (Relay C)
RPS Reports
Selecting Yes enables sending a report when the RPS Passcode Event occurs.
NOTICE!
"RPS Access Fail" might indicate a wrong RPS passcode when communicating with the control
panel, or a valid RPS session was abnormally terminated. "Remote Reset" indicates a Reset
command was issued from RPS. "Fail to Call RPS" indicates that control panel called RPS, but
was unable to connect.
Point Reports
Selecting Yes enables a report to be sent when the event occurs.
Acces Reports
Selecting Yes enables a report to be sent when the event occurs.
Enhanced Comm
Default Yes
Selection: Yes or No
Yes Enable enhanced communications over the SDI or SDI2 bus.
No Do not enable enhanced communications over the SDI or SDI2 bus.
NOTICE!
If using a network as the communication means for UL 864 Commercial Fire applications
(D9412GV4 and D7412GV4), set this parameter to Yes.
Determines if the control panel allows enhanced communications over the SDI bus.
Events can be routed to as many as four possible network destinations over communication
modules on either the SDI or SDI2 bus. The communication device and path destination are
called the route and are selected for each route group with the RG# Primary Device and RG#
Backup Device prompts.
If events are to be routed to an IP address (in a private LAN or WAN application), determine
which path is used (Path 1 to Path 4), and enter the appropriate IP Address for that path
(refer to Section Path # Network Address, page 41).
If events are to be routed to an SDI Path but not to an IP Address, allow the setting for Path #
Network Address to remain at 0. Path # Poll Rate, Path # Ack Wait, and Path # Retry Count
must be programmed.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the Enhanced Comm option. Press the Enhanced Comm softkey.
2. The current Enhanced Enabled configuration shows (for example, Enhanced Enabled:
Yes).
3. Press the Edit softkey to change the configuration.
4. Press the Yes or No softkey, and then press the Save softkey to save the changes.
When the keypad reads Parameter Saved, your selection is configured.
Default Blank
Selection: 0.0.0.0 to 255.255.255.255 or [host name]
0 to 255 There are four numbers for an IPV4 address. Leading zeros are not
required. A host name can be used if a B420 network communication
module is installed on the control panel.
NOTICE!
If using a network as the communication means for UL 864 Commercial Fire applications
(D9412GV4 and D7412GV4), set Path # Network Address as necessary.
Path # Network Address contains the network host name or the IPV4 address for each of the
four enhanced communication paths available.
A network address has four fields. Each field has a range of 0 to 255. For example, an IPv4
address is expressed as 110.227.64.190. Contact your network administrator to obtain the
appropriate IPv4 address or host name to contact a central station receiver. If a B420
Ethernet Communication Module is installed, then the control panel has the option to use a
host name for the Path route Network Address. For example, www.bosch.com.
Refer to Section Keypad Programming of Path # Network Address, Path # Port Number, and Path
# Poll Rate, 42 and Section Path # Poll Rate, page 41.
Default 7700
Selection: 1 to 65535
This prompt specifies the destination port number for each of the four enhanced
communication route path destinations.
NOTICE!
Whenever a network address or port number configured in the control panel is changed, the
central station must resynchronize the control panels anti-replay/anti-substitution static key.
Refer to Section Keypad Programming of Path # Network Address, Path # Port Number, and Path
# Poll Rate, page 42.
Default 0
Selection: 0, 5 to 65535 sec
0 Disables the heartbeat poll (not recommended, refer to the first
Important Note that follows).
5 to 65534 Enables the poll rate for the amount of time programmed here.
65535 The maximum number of 65535 sets the poll rate to once every 24 hr.
This prompt and the next two prompts determine how the SDI Path is supervised between the
SDI device and the central station receiver(s). Do not confuse the SDI Path supervision with
the supervision of the SDI device itself (the connection of the SDI device to the control panel).
Each SDI Path can be configured to transmit a Heartbeat Poll to the central station for
supervision purposes. This ensures the integrity of the connection at all times.
NOTICE!
If using Network Addresses as the communication means for UL 864 Commercial Fire
applications (D9412GV4 and D7412GV4), program this parameter as necessary.
NOTICE!
In order to supervise the virtual link between the control panel and a central station receiver
over a network path, you must set Path # Poll Rate to a non-zero value.
NOTICE!
If the control panel is programmed to send Heartbeat Poll to the central station, a rate of 75
sec maintains the virtual link in most network configurations. Decreasing the value for Path #
Poll Rate increases the amount of idle communication between the SDI device and the central
station receiver. Increased idle communication between the control panel and the receiver
decreases the control panels event reporting efficiency.
NOTICE!
The control panel readjusts a Heartbeat Poll rate of less than 300 sec to 300 sec when online
with RPS. The poll rate returns to the programmed value after the RPS session ends.
The value programmed in Path # Poll Rate is the interval at which the control panel sends a
Heartbeat Poll to the central station receiver. The value programmed in Path # Ack Wait is the
length of time the control panel waits for an acknowledgment of a Heartbeat poll. If the
acknowledgment is not received, the control panel checks to determine if the Path # Retry
Count entry is greater than 0. If so, the control panel retries the number of times programmed
(in Path # Retry Count) to send the Heartbeat Poll before declaring the Path failed and
generating a COMM TROUBLE SDI ## for the SDI paths. Refer to Table 3.4, Page 25.
For SDI2-2 (Path 1 = SDI 21, Path 2 = SDI 22, Path 3 = SDI 23, Path 4 = SDI 24).
If Path # Poll Rate is programmed with a value and the central station does not acknowledge
the poll from the control panel, keypads annunciate a trouble condition. To send this event to
the central station, refer to the Comm Trouble prompt in Section 3.14.2 Panel-Wide Relays,
page 121.
Keypad Programming of Path # Network Address, Path # Port Number, and Path # Poll Rate
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the ENHANCED COMM option. Press [ENT].
2. The keypad alternates between COMMUNICATIONS> and ENHANCED> YES. Press
[NEXT] to access the PATH 1 - 4 prompt.
3. Enter the path number you wish to configure and press [ENT]. The currently configured
network address shows.
4. Press [ENT] to change the network address. An invisible editing cursor is enabled for the
first byte.
5. The [PREV] button acts as a [Backspace] key. Press [PREV] to delete the characters of
the byte, and then enter the new byte numbers, or press [NEXT] to move to the next
byte.
NOTICE!
The keypad only accepts byte numbers valid for the current prompt.
8. The keypad shows the currently configured network address. Press [NEXT]. The currently
configured port number shows.
9. Press [ENT] to change the port number.
10. The [PREV] button acts as a [Backspace] key. Press [PREV] to delete the characters of
the port number and then enter the new port number.
11. Press [ENT] to save the changes.
When the keypad reads PARAMETER SAVED, your selection is configured.
12. Press [NEXT]. The currently configured path poll rate shows.
13. Press [ENT] to change the path poll rate.
14. The [PREV] button acts as a [Backspace] key. Press [PREV] to delete the characters of
the poll rate then enter the new poll rate.
15. Press [ENT] to save the changes.
When the keypad reads PARAMETER SAVED, your selection is configured.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the Enhanced Comm option. Press [ENT].
2. The Enhanced Enabled configuration shows, as does the Select IP Path option. Press the
Select IP Path to access the Path (1 4) prompt.
3. Enter the path number you wish to configure and press [ENTER]. The currently
configured network address shows.
4. Press the Select IP Path softkey to change the IP address. An editing cursor is enabled
for the first byte.
5. The Previous and Next softkeys move the cursor through the bytes. The Backspace
softkey allows you to erase characters. The Clear softkey allows you to clear the entire IP
address. Use the softkeys and the number buttons on the keypad to enter the new
network address.
NOTICE!
The keypad only accepts byte numbers valid for the current prompt.
When the control panel first powers up, the first Heartbeat Poll for Path 1 is sent and is
acknowledged in 1 sec. 120 sec after the first Heartbeat Poll is sent, the second Heartbeat
Poll for Path 1 is generated and sent to the central station receiver.
Example of Heartbeat as shown in Figure 3.1, Page 44:
Path # Poll Rate is set to 120 sec
Path # Ack Wait time is set to 1 sec
Path # Retry Count is set to 3
Callout Description
1 Heartbeat Poll sent
2 Acknowledgment received
3 Second Heartbeat Poll sent
4 No acknowledgment, Heartbeat re-sent, retry #1
5 No acknowledgment, Heartbeat re-sent, retry #2
6 Path declared failed
7 10-sec interval
8 Additional Heartbeats sent at the poll rate time until acknowledged
Example of Retry Count:
An acknowledgment of the heartbeat was not received within 10 sec. The control panel sends
the next Heartbeat Poll after the first 10-sec ACK wait period expires. If the central station
does not acknowledge this Heartbeat Poll, the control panel continues to re-send. When the
resend count is reached, the control panel declares this path as failed (and generates the
Comm Trouble SDI ## Event). The control panel continues to re-send the Heartbeat Poll at the
original poll rate time until it receives an acknowledgment, even after declaring a Comm
Trouble.
When the control panel receives acknowledgment from the central station, the control panel
returns to the normal Poll Rate (which, in this example, is 120 sec).
If more than one SDI Path is used, the control panel handles them on a successive basis. For
example, if acknowledgment from SDI Path 1 is not received within 10 sec (using the previous
example), the control panel moves to SDI Path 2 to send its Heartbeat Poll (and subsequently
waits for the ack) before returning to SDI Path 1 to re-send its heartbeat.
NOTICE!
If Heartbeat Polls are enabled to send by an SDI path, and the Path # Ack Wait time is
exceeded, a COMM TRBL SDI ## event occurs. When this condition occurs, all events routed
to this path go immediately to the backup path destination.
NOTICE!
5 min = 300 sec
1 hour = 3600 sec
12 hours = 43,200 sec
18 hours = 64,800 sec
Default 10
Selection: 5 sec to 65535 sec
5 to 65535 The control panel waits this amount of time to receive an
acknowledgment from the central station.
Determines how long the control panel waits for an acknowledgment from the central station
after a Heartbeat Poll or an actual event was transmitted. This prompt is applicable to SDI
transmitted events and Heartbeat Polls. Entries are made in one-sec increments.
Default 5
Selection: 0 to 255
0 COMM FAIL RG# SDI ### Events are not generated.
1 to 255 COMM FAIL RG# SDI ### Events are generated after resending
Heatbeat Poll the number of times selected for a given SDI path.
Determines how many times the control panel resends the Heartbeat Poll before declaring a
path failure and generating a COMM FAIL RG8 SDI ###, SDI ###. Refer to Table 3.4, Page 25
for valid SDI ### values.
NOTICE!
If using Network Addresses as the communication means for UL 864 Commercial Fire
applications (D9412GV4 and D7412GV4), program this parameter as necessary.
The default settings meet or exceed the UL specifications.
Default Yes
Selection: Yes or No
Yes The anti-replay protocol is expected on the central station receiver and
will uniquely authenticate each event from the control panel.
No The anti-replay protocol is not expected on the central station receiver.
computer on which RPS is installed needs a network card. See your information systems
administrator for network requirements.
This section allows you to:
Provide for local programming by a DX4010V2 Serial Interface Module.
Provide remote programming by a Conettix DX4020 Network Interface Module, an
ITSDX4020-G, or a B420-G.
Provide enhanced route paths for event reporting through a network using a Conettix
DX4020 Network Interface Module, an ITSDX4020-G, or a B420-G.
Although not listed in this section, RPS checks for the RPS passcode (refer to Section 3.8 RPS
Parameters, page 54), Datalock Code, and control panel type to determine if this RPS session
should continue.
Default Yes
Selection: Yes or No
Yes Enable automatic answer of RPS initiated sessions over the network.
No Do not automatically answer RPS initiated sessions over the network.
This prompt determines if the control panel automatically answers RPS initiated sessions
through a network interface module on the SDI bus.
This prompt can be momentarily disabled by selecting ALLOW ANSWER through COMMAND
43 (Remote Programming) menu (refer to Figure 3.2, Page 47 and Figure 3.3, Page 48).
NOTICE!
If the Reset switch (labeled S1) label is in the locked position, network RPS programming is
allowed even if this prompt is set to No.
Default No
Selection: Yes or No
Yes Verifies that the incoming RPS network address matches the address
entered in RPS Network Address.
No Do not verify the RPS network address. Allow RPS to connect to the
control panel from any network source .
When enabled, this feature will verify that the Remote Programming Software connecting to
the control panel is coming from a known IP address.
NOTICE!
If the Reset switch (labeled S1) label is in the locked position, network RPS programming is
allowed even if this prompt is set to No.
Default Blank
Selection: 0.0.0.0 to 255.255.255.255 or [host name]
0 to 255 There are four numbers for an IPV4 address. Leading zeros are not
required. A host name can be used if a B420 network communication
module is installed on the control panel.
This prompt contains the network host name or the IP address for RPS that the control panel
uses to call RPS.
An IPv4 address has four fields. Each field has a range of 0 to 255. For example, an IP address
is expressed as 110.227.64.190. Contact your network administrator to determine the IP
address to which the RPS computer is connected. If a B420 Ethernet Communication Module
is installed, then the control panel has the option to use a host name (for example,
www.bosch.com), for the RPS Network Address .
Refer to Section RPS Network Address, page 48 and Section RPS Port Number, page 48.
Default 7750
Selection: 1 to 65535
This prompt specifies the destination port for outgoing RPS session requests to the IP
address specified in RPS Network Address.
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the RPS PARAMETERS option. Press [ENT]. The keypad shows the RPS
PASSCODE option and the currently configured passcode.
2. Press [NEXT] twice to advance to the RPS IP ADDRESS option and press [ENT]. The
currently configured IP address shows.
3. An invisible editing cursor is enabled for the first byte.
4. The [PREV] button acts as a [Backspace] key. Press [PREV] to delete the characters of
the byte, and then enter the new byte numbers, or press [NEXT] to move to the next
byte.
NOTICE!
The keypad does not accept numbers 256 to 999.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the RPS Parameters option. Press [ENTER]. The keypad shows the RPS
Passcode option and the currently configured passcode.
2. Press Phone Number softkey. The keypad shows the currently configured phone number
and the IP Address option.
3. Press the IP Address softkey. The currently configured IP address shows.
4. Press the Edit softkey to change the IP address.
5. The Previous and Next softkeys move the cursor through the bytes. The Backspace
softkey allows you to erase characters. The Clear softkey allows you to clear the entire IP
address. Use the softkeys and the number buttons on the keypad to enter the new IP
Address.
NOTICE!
The keypad does not accept invalid byte numbers.
Default: 1:00
Selection: 0:01 to 90:00 (minutes:seconds)
Program the amount of time that AC power must be off before the control panel responds to
the AC failure. The response to restoral of AC power is delayed for the same amount of time.
AC power is continuously monitored by the control panel, any installed SDI2 bus Power
Supply modules and any installed RF Repeaters. The response to this prompt is the actuation
of the relay programmed in the Panel-Wide Relays prompt AC Failure (refer to
Section 3.14.2 Panel-Wide Relays, page 121) and the AC Fail report enabled by the AC Fail/
Restoral Report prompt. Local annunciation of an AC failure is controlled by the AC Fail
Display prompt.
NOTICE!
UL 864 requirements, Section 50.2.1.b states: A trouble signal shall be transmitted for
remote station, central station, and proprietary-type protected premises units after a delay of
between 60 and 180 min.
Exception: Products are not prohibited from providing capability of selecting that the primary
power failure trouble signal transmission be delayed other time periods, including no delay,
provided the 60 180 min delay is also included.
To meet UL 864 requirements (D9412GV4 and D7412GV4), program AC Fail Time with 1:00.
Always check with the Authority Having Jurisdiction for local requirements.
Resend AC Fail
Default: No Responses
Selection: No Responses, 6 hrs, 12 hrs
No Response Only send the AC Fail report upon failure.
6 hr Send AC Fail report upon failure and every 6 hours after this while the
failure persists.
12 hr Send AC Fail report upon failure and every 12 hours after this while the
failure persists.
This prompt controls the repeated transmission of the AC Failure report to the central station
while the fault persists. AC Fail/Restoral Report must be set to Yes, and AC Tag Along must
be set to No for this feature to work. This prompt applies to AC failure events generated by
the control panel, any installed SDI2 bus power supply modules and any installed RF
Repeaters.
NOTICE!
For the following items to be true, AC Fail/Restoral Report must be programmed as Yes and
AC Tag Along must be programmed as No.
NOTICE!
To eliminate AC Reporting, AC Tag Along and AC Fail/Restoral Report must be programmed
as No.
AC Fail Display
Default: 60 sec
Selection: 10 to 300 sec (in 5-sec increments)
Program the length of time the AC power must be off before the message SERVC AC FAIL
shows on the keypads. The response to restoral of AC power is delayed for the same amount
of time. This prompt applies to AC failure events generated by the control panel, any installed
SDI2 bus power supply modules and any installed RF Repeaters.
AC Fail/Restoral Report
Default: No
Selection: Yes or No
Yes Send AC Fail and AC Restoral Reports.
No Do not send AC Fail and AC Restoral Reports.
AC Power Supervision Reports are sent to the central station and local printer at the time
programmed for AC Fail Time. This prompt applies to AC failure events generated by the
control panel, any installed SDI2 bus power supply modules, and any installed RF repeaters.
AC Tag Along
Default: Yes
Selection: Yes or No
Yes Send AC messages as tag along events.
No Do not send AC messages as tag along events.
Send AC Reports only if any other event occurs while AC is off-normal.
NOTICE!
If AC Tag Along is set to Yes and a subsequent event is generated, the AC Fail Event is sent
first, before sending any subsequent events.
NOTICE!
AC Tag Along is required for NFPA and UL 864 Commercial Fire systems (D9412GV4 and
D7412GV4). Be sure to program AC Fail/Restoral Report as No if AC Tag Along is
programmed Yes.
AC/Battery Buzz
Default: No
Selection: Yes or No
Yes Initiates panel-wide trouble tone at all keypads.
No Does not initiate panel-wide trouble tone at keypads.
Initiates a panel-wide trouble tone at keypads when AC fails or battery is low or missing. This
program item does not prevent the SERVC AC FAIL or SERVC BATT LOW displays.
NOTICE!
To comply with NFPA standards and UL 864 requirements for Commercial Fire systems
(D9412GV4 and D7412GV4), program this item as Yes.
NOTICE!
If annunciating panel-wide troubles at a keypad with CC# Scope set to Panel Wide is
undesirable, set CC# Trouble Tone to No. Refer to Section Command Center, page 79 for
keypad configurations.
Default: Yes
Selection: Yes or No
Yes Battery Failure and Restoral Reports are sent to the central station.
Modem Reports: Missing or shorted: BATTERY MISSING
Default: 1
Selection: 1 to 32 for D9412GV4
1 to 8 for D7412GV4
1 to 4 for D7212GV4
Assign an area to the printer programmed in Printer Address.
P## Supervised
Default: No
Selection: Yes or No
Yes Only one printer can be installed for this printers SDI address.
No More than one unsupervised printer can be installed using this printers
SDI address and the same address DIP switch setting.
Supervise this SDI address. Generate Trouble SDI ## Reports and local trouble annunciation if
a problem occurs with this printer or the SDI bus.
NOTICE!
Unsupervised printers sharing the same address setting print the same text.
NOTICE!
Trouble SDI ## Reports are always reported as Area 1, Account 1 Events regardless of where
the SDI device is assigned.
NOTICE!
When P## Supervised is set to Yes and all Printer Event Groups (such as P## Fire Events, P##
Burglar Event, or P## Usr Chng Evt) are set to No, the control panel does not generate
Trouble SDI ## Reports for the printer if the D9131A becomes disconnected.
NOTICE!
The printer cannot show area numbers greater than Area 8. When printed, Areas 9 and higher
print as 00.
P## Scope
Default: No Printer
Selection: No Printer, Area, Account, Panel Wide, Custom
Panel Wide Printer prints all designated events that occur panel-wide. A panel-wide
printer can cross account boundaries.
Account Printer prints all designated events that occur within any area with the
same account number in which this printer is assigned.
Area Printer prints all designated events that occur in the area to which this
printer is assigned.
Custom Printer prints all events occurring in areas programmed Yes for this
prompt regardless of any boundary restrictions.
No Printer No printer installed at this address. If a printer is connected, data does
not print.
Supervise this SDI address. Generate Trouble SDI ## Reports and local trouble annunciation if
a problem occurs with this printer or the SDI bus.
Default: No
Selection: Yes or No
Yes Include Area # Events in the scope of this printer.
No Does not include Area # Events in the scope of this printer.
Only available if P## Scope is programmed Custom. This program item determines if events
occurring in an area print at this printer.
NOTICE!
Refer to the report tables in Section 3.3 Routing, page 23 to identify the events that print.
Events programmed as No in Routing still print at the local printer. Individual events within
the report group cannot be suppressed for events printed at the local printer.
Fail to Call RPS Events are logged only locally. If properly configured, the control panel makes
multiple attempts to reach RPS before sending the reports. To enable transmission of the
events when the Log Threshold is reached, set a valid phone number in RPS Phone Number
(refer to Section RPS Phone #, page 58) or set a valid IP address in RPS Network Address
(refer to Section RPS Network Address, page 48).
RPS Passcode
Default: 999999
Selection: 0 to 9, A to F (six characters required)
Enter six characters. Do not use a space in the passcode.
The control panel verifies the remote programming software at the central station has valid
access before connecting using the RPS passcode.
it. The Previous and Next softkeys advance through the letter characters (A, B, C, D, E,
F).
4. Press the Save softkey to save the passcode. When the keypad reads Parameter Saved,
your selection has been configured.
Log % Full
Default: 0
Selection: 0 to 99
When the event log reaches the percentage full indicated in this prompt, the control panel
logs a Log Threshold event. If Contract RPS if Log % Full is set to Yes, then the control panel
will attempt to contact Unattended RPS and copy the event log before messages are
overwritten.
A setting of 0 disables the Log Threshold and Log Overflow Events. These events are not
entered in the log or reported to the central station receiver or the local printer.
The control panel continues to log events after the Log Threshold Report is sent. When the
event log reaches 100%, a Log Overflow event is generated and the oldest events are
overwritten.
The control panel does not call RPS again until it downloads the log and the Log % Full
percentage is reached. These events are also sent to the control panels event log and to the
local printer(s) if installed.
NOTICE!
The Log Overflow Event is not sent to the central station unless Expanded Test Report is
programmed Yes.
NOTICE!
Failure to program the RPS telephone number and the RPS IP address number results in a
FAIL TO CALL RPS trouble event sent to the central station when the log threshold is reached.
Refer to Section RPS Phone #, page 58 for information about programming the RPS telephone
number. Refer to the Section Path # Network Address, page 41 for information about enabling
network RPS.
Default: No
Selection: Yes or No
Yes Directs the control panel to automatically communicate with
Unattended RPS over network or phone when Log Threshold is
reached.
No The control panel will not automatically contact RPS when Log
Threshold is reached.
When the event log reaches the percentage full indicated by Log % Full the Log Threshold
event is put in the event log. If this prompt is set to Yes and either the RPS Network Address
or RPS Phone # are programmed, then the control panel will attempt to contact Unattended
RPS as described in Section 3.8.3 Panel Initiated Unattended RPS, page 55.
Default: No
Selection: Yes or No
Yes When the control panel hears the correct RPS passcode, it hangs up the
phone, seizes the phone line, then dials the programmed RPS phone
number (refer to Section RPS Phone #, page 58). This ensures that the
control panel only communicates with RPS units connected to the
programmed phone number.
If the call is answered manually, the call back must be initiated
manually.
No The RPS session starts immediately. No call back is required. The
control panel can engage in RPS sessions when called from any phone
number and a proper RPS passcode is identified.
This function allows the control panel, after it verifies the RPS passcode, to provide an
additional level of security by hanging up and dialing the RPS phone number at the central
station before allowing any upload or download.
NOTICE!
When using the RPS Call Back feature, be sure to program the character C as the last digit in
the RPS phone number when using DTMF Dialing.
Default: Yes
Selection: Yes or No
Yes Allows the control panel to communicate with RPS after the answering
machine answers the phone.
No Use No if the control panel does not share the phone line with an
answering machine.
This program item enables a control panel that shares a phone line with an answering
machine to communicate with RPS at the central station, even though the answering machine
answers the phone. You must program Answer Armed or Answer Disarmed. The control
panel must be in the correct armed state.
NOTICE!
Program this item No if it causes false seizures of the phone line or if you do not use RPS. This
indicates that a device using the same frequency tone is also using the phone line to which the
control panel is connected.
NOTICE!
If RPS Call Back is programmed Yes, the control panel hangs up the phone after the RPS tone
and a proper RPS passcode is identified. It then calls the RPS phone number.
Answer Armed
Default: 7
Selection: 0 to 15
0 No answer.
1 to 15 The control panel answers the phone after the specified number of
rings when all areas are master armed.
Set the telephone ring counter to answer when all areas are master armed. If any area in the
control panel is perimeter armed or disarmed, the Answer Disarmed ring counter is used.
NOTICE!
For the purposes of answering the RPS phone call, the control panel considers Perimeter
Armed a disarmed state.
Answer Disarmed
Default: 7
Selection: 0 to 15
0
1 to 15 The control panel answers the phone after the specified number of
rings when any area in the system is in a perimeter armed or disarmed
state.
Set telephone ring counter to answer when any area is in a perimeter armed or disarmed
state.
NOTICE!
For the purposes of answering the RPS phone call, the control panel considers Perimeter
Armed a disarmed state.
RPS Phone #
Default: Blank
Selection: Blank or up to 24 characters
Blank Control panel does not dial a phone number for RPS.
1 to 24 characters Enter up to 24 characters to define dialing characteristics.
This is the phone number the control panel dials to contact RPS. Refer to
Section 3.8.1 Uploading and Downloading Reports, page 54 for instructions on configuring
special phone number digits to detect dial-tone detect and to pause dialing. The control panel
dials this number when any of the following events occur:
Log % Full threshold is achieved.
NOTICE!
If Log % Full is programmed with a value (1 to 99) and an RPS phone number or RPS IP
address are programmed, the control panel attempts to communicate with Unattended RPS
when the log threshold is reached.
The control panel is contacted by RPS and RPS Call Back is programmed Yes.
The user enters and selects the call RPS option from the menu. On the D1255:
1. Press [COMAND][4][3].
2. Press [NEXT] until RPS via Phone? appears, then press [ENTER].
NOTICE!
The control panel tries to contact RPS only once using this method.
Refer to Section 3.5 SDI RPS/Enhanced Communications Configuration, page 45 for other
connection methods.
NOTICE!
Refer to Section Phone #, page 17 descriptions of special programming values for the RPS
Phone number.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the RPS Parameters option. Press [ENTER]. The keypad shows the RPS
Passcode and the currently configured passcode.
2. Press Phone Number softkey.
3. The keypad shows the currently configured phone number.
4. Press the Edit softkey to change the phone number.
5. The Pause and DT Detect (Dialtone Detect) softkeys enter special characters. The
Backspace softkey allows you to erase characters. The Clear softkey allows you to clear
the entire phone number. The [COMMAND] and [ENTER] keys allow you to enter an * or a
#. Use the softkeys, the number buttons, and the [COMMAND] and [ENTER] keys on the
keypad to enter the new phone number.
6. Press [ENT] to save the phone number. When the keypad reads Parameter Saved, your
selection has been configured.
Default: 1200
Selection: 300, 1200, 2400
Select the baud rate for RPS-to-control panel communication when using a PSTN connection.
3.9 Miscellaneous
Duress Type
Default: 0
Selection: 0, 1, 2, or 3
0 Do not send a duress event with any passcode.
1 Increase the last digit by 1 to generate an alarm. For example, if the
passcode is 6123, 6124 activates a duress alarm.
If the last digit of the passcode is 0, a duress alarm occurs when the
user enters 1 as the last digit of the passcode.
If the last digit of the passcode is 9, a duress alarm occurs when the
user enters 0 as the last digit of the passcode.
NOTICE!
The duress alarm activates when a user enters the duress passcode followed by the
termination keys ([ESC] or [ENT]).
Cancel Report
Default: Yes
Selection: Yes or No
Yes Send Cancel and Fire Cancel Reports according to routing.
No Do not send Cancel and Fire Cancel Reports.
A Cancel and Fire Cancel Report is created when a passcode is entered to silence an Alarm
Bell or a Fire Bell before the bell time expires.
For SIA CP-01 Compliance Duress Type this prompt must be set to Yes.
Default: No
Selection: Yes or No
Yes Authorized personnel on-site must enter the authorization code at one
of the command centers at the designated time during the remote
firmware update process.
No No on-site authorization is required.
Perform firmware updates using RPS. RPS Online Help includes instructions for using the
Firmware update feature.
NOTICE!
It is recommend that a full system test be performed whenever firmware is updated locally or
remotely.
Area# Area On
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set A# Area On to Yes.
Default: 0000
Selection: For Modem format and Contact ID (four-digit account numbers): 0000
to 9999, BBBB to FFFF
For Modem format (ten-digit account numbers): 0000000000 to
9999999999, BBBBBBBBBB to FFFFFFFFFF
Determines the account number for this area. An account number must be assigned to each
active area.
Account numbers are used to group areas together. Each area can have a different account
number, or several areas can share the same account number. The control panel uses the
account number as a reference for arming and keypad text displays.
Contact ID: Only the last four digits are sent.
Modem IIIa2: Enter a four-digit or ten-digit number.
5. Press the [PREV] or [NEXT] button to toggle between YES and NO, and then press [ENT]
when the desired configuration option shows.
When the keypad reads PARAMETER SAVED, your selection is configured.
6. When the keypad reads AREA STATUS, press [NEXT] to advance to the A# ACCOUNT
NUMBER option. The keypad shows the currently configured account number.
7. Press [ENT] to change the account number.
8. The [PREV] button acts as a [Backspace] key. The [COMMAND] key cycles though the
special account number characters (B, C, D, E, F); [NEXT] select the account number
character. Press [PREV] to delete the characters of the account number and then enter
the new account number.
9. Press [ENT] to save the changes.
When the keypad reads PARAMETER SAVED, your selection is configured.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the Area Parameters option. Press [ENT].
2. The keypad reads Area Number 1 32 (1 - 8 for D7412GV4 and 1 - 4 for D7212GV4).
3. Enter the area number you wish to configure and press [Enter]. The current area status
shows (for example, Area 1 On: Yes).
4. Press the Edit softkey to change the areas status.
5. Press the Yes or No softkey, and then press the Save softkey to save the changes.
When the keypad reads Parameter Saved, your selection is configured.
6. When the keypad reads Area Status, press the Account Number softkey. The keypad
shows the currently configured account number.
7. Press the Edit softkey to change the account number.
8. Use the softkeys and the number buttons on the keypad to enter the new account
number. The Backspace softkey allows you to erase characters. The Clear softkey allows
you to clear the entire account number. When entering a letter character, press the
letter's softkey to select it. The Previous and Next softkeys advance through the letter
characters (A, B, C, D, E, F).
9. Press the Save softkey to save the changes.
When the keypad reads Parameter Saved, your selection is configured.
Default: 2
Selection: 0 to 99
Specify the maximum number of combined Controlled points that can be faulted or bypassed
when arming this area.
Refer to the prompts P## Force Arm Returnable and P## Bypass Returnable in Section P##
Force Arm Returnable, page 140 and Section P## Bypass Returnable, page 140 for returning a
point to the system when the point returns to normal or when the area is disarmed.
NOTICE!
Users can bypass more points than the number entered here during the disarmed state. It is
only when the user attempts to Bypass Arm an area (or areas) that this restriction is enforced.
Default: No
Selection: Yes or No
Yes Point Restoral Report is not sent until the bell time expires or user
acknowledges alarm condition.
No Restoral Reports are sent when point restores, regardless of bell time.
A# Exit Tone
Default: Yes
Selection: Yes or No
Sounds an exit tone during exit delay at all keypads assigned to this area.
NOTICE!
You can turn off exit tones for individual keypads by programming the appropriate CC# 1 to 8
as No in CC# Exit Tone.
Default: 60 sec
Selection: 0 to 600 (in 5 sec increments)
Exit delay time for this area when Master Exit or Perimeter Exit arming.
NOTICE!
Points programmed for instant alarm response generate alarms immediately, even during exit
delay. To avoid instant alarms on points adjacent to the perimeter when leaving the area,
program P## Type as 3 (Interior Follower).
For SIA CP-01 Compliance the Exit Delay Time must be between 45 sec and 255 sec.
A# Auto Watch
Default: No
Selection: Yes or No
Yes When the area is disarmed, Watch Mode turns on automatically.
No When the area is disarmed, Watch Mode must be turned on or off
manually.
NOTICE!
Controlled points must be programmed as P## Watch Point to generate a watch tone.
A# Verify Time
Default: 60
Selection: 10 to 60 (in 1-sec increments)
Use alarm verification with smoke detectors to reduce the number of false fire alarms. When
Verify Time is programmed, the control panel can check smoke detector point activations
before generating alarm signals.
NOTICE!
Do not enable the Cross Point feature in point indexes designated for Fire points.
Check with your authority having jurisdiction (AHJ) to determine the maximum
verification time allowed.
When an Alarm Verification point senses an alarm, the control panel automatically removes
power to all Resettable points connected to the areas Reset Sensors relay. The sensor reset
removes power to the sensors for the amount of time programmed in Verify Time. When
power is reapplied, a 60-sec confirmation window begins. If the detector is still in alarm or
experiences another alarm during the confirmation window, or a different Resettable
Verification point in the area senses an alarm, an alarm occurs.
Example: Verify Time is set for 20 sec. The alarm verification cycle starts when the detector
senses smoke or fire. No report occurs.
When the detector senses smoke or fire, the areas sensor reset relay interrupts power to
points connected to it for the time in Verify Time.
When power restores to the points, the 60-sec confirmation window starts. If any detector,
reset during the verification time, experiences another alarm during the confirmation window,
an alarm occurs. If no activity occurs during this period, no alarm occurs and the verification
window ends. If a Verification point senses another alarm after the window ends, a new
verification cycle begins. Refer to Table 3.15 for an example of Verify Time.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set A# Verify Time to 60 sec.
A# Duress Enable
Default: No
Selection: Yes or No
Yes Enable Duress alarm for this area
No Disable Duress alarm for this area
Refer to Duress Type in Section 3.9 Miscellaneous, page 59 for an explanation of duress.
For SIA CP-01 Compliance:
A# Duress Enable must be set to Yes.
CAUTION!
The passcode you normally use for duress is not valid in an area with A# Duress Enable set to
No.
If a passcode with the appropriate L# Disarm authority is used to duress disarm an area with
A# Duress Enable set to No, NO AUTHORITY appears in the display. Also, if the keypad display
is moved to an area with A# Duress Enable set to No using [COMMAND][5][0], a valid duress
disarm passcode does not send a duress report.
A# Area Type
Default: Regular
Selection: Regular, Master, Associate, Shared
Regular
NOTICE!
Using the arming sked (S## Function 1) requires that you first use an arming sked to arm the
associate areas before using an arming sked to arm the master area. Arming master areas with
RPS, Keyswitch, or Auto Close parameters (refer to Section 3.10.4 Open/Close Options,
page 69) occurs before all associate areas are armed
Associate
Allows arming and disarming regardless of the armed state of the other areas with the same
A# account number. Use this area type with a master area and associate it by using the same
account number.
NOTICE!
Keypads assigned to associate areas, when used with shared areas, must have CC# Scope
programmed.
Shared
Is not associated to other areas by account number, they are shared panel wide.
Are armed when all Associate areas in the control panel are Master Delay armed.
Are disarmed when at least one Associate area in the control panel is taken out of Master
Delay armed state.
Cannot be individually armed using a passcode, key switch, keyfob, sked, or RPS.
NOTICE!
Arming commands intended for a shared area must be executed on a keypad with Panel Wide
scope by a user with appropriate authority in all Associate areas. Shared areas associate with
all Associate areas regardless of their account assignments. The shares area does not begin to
arm until all Associates finish arming.
When the Fire and Burg Bells share the same output and a Fire Bell occurs while the Burg Bell
is ringing, the Fire Bell pattern overrides the Burg Bell pattern. At the end of the fire time, the
burg pattern resumes.
When the Fire and Burg Bells share the same output and a Burg Bell occurs while a Fire Bell
sounds, the control panel waits until the Fire time expires before starting the Burg Bell.
Either a single bell (panel-wide) or a number of bells (area-wide) can be used on the control
panel. For programming these applications, refer to Section 3.14.1 Area Relays, page 118.
When both Fire and Burg Bells occur simultaneously and a user enters a valid passcode, a Fire
Cancel Report for the fire alarm and a Cancel Report for the burg alarm is sent to the central
station if Cancel Reports is programmed Yes.
A# Fire Time
Default: 6 min
Selection: 1 min to 90 min
Enter the number of minutes the bell rings for Fire Alarm points. The relay activated for this
time is programmed in A# Fire Bell in Area Relays.
The bell output begins as soon as the fire alarm occurs. It shuts off the bell when the
programmed number of minutes expires.
If programmed for 1 min, the output can be anywhere from 0 to 60 sec of bell time. Program
Fire Time for 2 min or more to ensure you have ample output time.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), program A# Fire Time for at least
5 min. Check with your AHJ to determine the appropriate bell time for your geographical area.
A# Fire Pattern
Default: Pulse
Selection: Steady, Pulse, CA Standard, TempCode3
Steady Steady Output
Pulse Pulse March Time
120 beats per minute, at an even tempo
CA Standard California Standard
10 sec On + 5 sec Off + 10 sec On + 5 sec Off. This sequence repeats
until bell time expires.
TempCode3 Temporal Code 3
0.5 sec On, 0.5 sec Off, 0.5 sec On, 0.5 sec Off, 0.5 sec On, 1.5 sec Off;
pattern repeats. This sequence repeats for a minimum of 3 min and
with a 10% tolerance.
Select the bell pattern this area uses to signal an alarm on a Fire point.
NOTICE!
When an alarm occurs on two Fire points sharing the same relay, the bell pattern of the most
recent fire event takes precedence.
A# Burg Time
Default: 6 min
Selection: 1 min to 90 min (in one-minute increments)
NOTICE!
For D9412GV4 and D7412GV4 Control Panels, use:
4 min for UL
5 min for ULC
Enter the number of minutes the bell rings for Burglary Alarm points. The relay activated for
this time is programmed in A# Alarm Bell in Area Relays.
The bell output begins as soon as the burglary alarm occurs. It shuts off the bell when the
programmed number of minutes expires.
When the control panels internal clock begins a new minute, it considers the first minute
expired. Program Burg Time for 2 min or more.
NOTICE!
Check with your AHJ to determine the appropriate bell time for your geographical area.
A# Burg Pattern
Default: Steady
Selection: Steady, Pulse, CA Standard,TempCode3
Steady Steady Output
Pulse Pulse March Time
120 beats per minute, at an even tempo
CA Standard California Standard
10 sec On + 5 sec Off + 10 sec On + 5 sec Off. This sequence repeats
until bell time expires.
TempCode3 Temporal Code 3
0.5 sec On, 0.5 sec Off, 0.5 sec On, 0.5 sec Off, 0.5 sec On, 1.5 sec Off;
pattern repeats. This sequence repeats for a minimum of 3 min and
with a 10% tolerance.
Select the bell pattern this area uses to signal an alarm on a Non-fire point.
A# Single Ring
Default: No
Selection: Yes or No
Yes One bell output per arming period. After one alarm, alarms on any Non-
fire points in the same area cannot restart the bell until the armed state
changes. An alarm on a different point in same area restarts bell output.
No Restart bell output with each alarm event.
Determines if an alarm from a non-fire point can restart the alarm bell time with each Alarm
Event, or only start alarm output once per arming period.
This does not silence the keypad alarm bell tone, or prevent any reports. This feature does not
affect Fire points. Fire points restart bell time with each new alarm.
NOTICE!
If an alarm occurs on a 24-hour point while the area is disarmed, arming that area with a key
switch does not clear the A# Single Ring flag.
NOTICE!
Silencing the bell resets A# Single Ring.
A# Bell Test
Default: No
Selection: Yes or No
Yes Start Bell Test.
No Do not start Bell Test.
Provides alarm output from the relay programmed at A# Alarm Bell after the Closing Report is
confirmed or the exit delay time expires.
To suppress reports:
Use Opening/Closing Windows to suppress reports for a specified period of time and
then automatically turn them on again.
Use the Restricted O/C options. A Closing Report is sent if the user is force arming,
sending duress, or bypass arming. An Opening Report is sent if the user is disarming
during an alarm condition or unbypasses points when disarming. If the system is normal,
no Opening or Closing Report is sent.
NOTICE!
For the scheduled suppression of Opening and Closing Reports, refer to Section 6.1.1 Opening
and Closing, page 154) to define Opening and Closing Windows.
A# Account O/C
Default: No
Selection: Yes or No
A# Area O/C
Default: Yes
Selection: Yes or No
Yes Include the Area # and generate Opening and Closing Reports for this
area when it is armed.
No Do not include the Area # or generate Opening and Closing Reports for
this area.
Determines if the area number and the account number are reported at arming and disarming.
As long as Account O/C is No, the account number sends a report when arming this area
individually. If Account O/C is Yes, all areas with the same account number must also be
armed.
An Area Opening Report is generated when each area is opened (disarmed). An Area Closing
Report is generated when each individual area is closed (armed).
NOTICE!
Do not program this item as Yes if the control panel reports to an automation system that
cannot interpret multiple Area Opening and Closing Reports.
Default: Yes
Selection: Yes or No
Yes Do not send Opening and Closing Reports to the central station if they
occur inside an active window.
If an Opening or Closing Report occurs outside a window, send it with
an early or late modifier. Refer to Section 6.1.1 Opening and Closing,
page 154.
The active window must be a Closing Window for Closing Reports. It
must be an Opening Window for Opening Reports.
No Send Opening and Closing Reports to the central station even when
they occur inside a programmed window. If an opening or closing
occurs outside of the appropriate window, it reports but does not have
an early or late modifier.
If you want to monitor all opening and closing activity and use features
provided by Opening and Closing Windows, program this item as No,
and program the appropriate O/C Windows.
Determines if opening and closing activity is reported when it occurs inside an Opening or
Closing Window, as programmed in O/C Windows.
Reports are always logged and printed on a local printer, if installed.
A# Auto Close
Default: No
Selection: Yes or No
Yes The area automatically master arms at the end of the Close Window.
When the area is armed automatically, a Closing Report is sent if the
Area or Account Reports are programmed to do so.
No Do not automatically arm the area at the end of the Close Window.
With this program item, the control panel can automatically master arm the area at the end of
the Closing Window regardless of the previous armed state.
NOTICE!
When an area master arms automatically at the end of a Close window, the system disregards
the settings in A# Force Arm Max and P## Bypassable for any faulted points. The faulted
points arm when they return to normal state.
A# Fail to Open
Default: No
Selection: Yes or No
Yes Fail to Open Report is sent for this area if the area was not disarmed
when the Opening Window stop time occurred.
No Fail to Open Report is not sent for this area.
Use to determine if a Fail to Open Report is sent for this area. This can determine if a user
failed to disarm the area before the Opening Window expiring. Normal Opening and Closing
Reports do not need to be programmed to use this feature.
A# Fail to Close
Default: No
Selection: Yes or No
Yes Fail to Close Report is sent for this area if the area is not armed when
the Closing Window stop time occurs.
Note:
Program an exit delay time in Exit Dly Time.
No Fail to Close Report is not sent for this area.
If Auto Close is programmed Yes, a Fail to Close Report is sent
because it occurs when the Closing Window stop time occurred.
If Disable O/C in Window is Yes, the Fail to Close Report is
followed by Closing Late or Force) Close Late.
This item determines if a Fail to Close Report is sent for this area. Use to determine if a user
failed to arm the area before the Closing Window expires. Normal Opening and Closing
Reports do not need to be programmed to use this feature.
Default: 00:00
Selection: 00:00 to 24:00
Use to set a Latest Close Time boundary value for this area. If the Latest Close Time value is
non-zero, the time of day specified with the Extend Close feature cannot be greater than or
equal to this value. A zero value for A# Latest Close Time disables the feature for the area.
Example: If A# Latest Close Time is set for 17:30, the user can extend the close time to as late
as 17:29.
This prompt is used only when an O/C Window is assigned to an area. Make entries in 30-min
increments using a 24-hour format. Use times that begin on the hour or the half-hour only. For
example, enter 2:30 PM as 14:30. Enter 1:00 AM as 01:00. To set the Latest Close Time for
midnight, use a value of 24:00. The latest close time allowed by the Extend Close feature is
24:58, because of internal limitations in the control panel.
NOTICE!
The default entry of 00:00 disables the Latest Close Time feature for this area.
The control panel sets all windows for the next day when the control panel clock turns to
midnight. The control panel must cross the midnight boundary before any changes in that
default setting occur.
To extend across midnight, you must use two windows:
To suppress reports before midnight, use one window (for example, 20:00 start to 23:59
stop).
To suppress reports immediately after midnight, use another window (for example, 00:01
start to 02:00 stop).
A# Restricted O/C
Default: No
Selection: Yes or No
Yes Restrict Opening and Closing Reports for this area. A# Area O/C must
be programmed Yes to generate Restricted Opening and Closing
Reports.
Note:
If a passcode is not required for arming or disarming and this item is
Yes, the area sends only Restricted Opening and Closing Reports. In
this case, Restricted Reports are sent without User ID.
Opening/Closing Window does not affect this report. Windows do not
prevent sending Restricted Opening and Closing Reports from being
sent. Early or late designations are not added to Opening or Closing
Reports when they are sent according to the rules for Restricted
Opening or Closing Reports.
No Do not Restrict Opening and Closing Reports for this area.
Regardless of programming in Authority Levels L## Restricted O/C,
reports are not restricted in this area when this item is programmed as
No.
Note:
Was Force Armed and Forced Close Events can still be sent to the
central station if enabled in Routing when force arming the system.
This item determines if this area can restrict Opening and Closing Report activity.
A Restricted Opening Report refers to the control panel sending an Area Opening Report only
when the area is disarmed after a non-fire alarm.
A Restricted Closing Report refers to the control panel sending a Force Closed Report only
when the area was master armed with Controlled points that were faulted during the arming
sequence. The sequence of reports generated by a restricted closing is: Was Force Armed,
Forced Point, and Force Closed.
A# Perimeter O/C
Default: No
Selection: Yes or No
Yes This area can send Perimeter Opening and Closing Reports.
No This area cannot send Perimeter Opening and Closing Reports.
This item determines if this area can send Perimeter Instant and Perimeter Delay Closing
Reports and normal Opening Reports to the central station. Opening and Closing Windows do
not suppress this event. Refer to Section L## Perimeter O/C, page 113.
NOTICE!
This reporting requires ModemIIIa2 reporting format reporting. Some central station
automation systems cannot process these reports.
Default: No
Selection: Yes or No
Yes Two valid unique passcodes are required to disarm the area.
No A single passcode with a valid authority level can disarm the area.
NOTICE!
The D720 Keypad does not support the Two-Man Rule feature.
Use this parameter when disarming an area that is Master Armed. After recognizing the first
valid passcode, the system requests a second passcode to disarm the area. If the entry delay
expires before the entry of a second valid unique passcode, an alarm condition occurs. This
function works only when you use Passcode Disarm.
NOTICE!
When you are disarming an area with A# Two Man Rule set to Yes, the keypad waits for the
time equal to the A# Exit Delay Time. If the second passcode is not entered before the
prompt times out, the rule resets and waits for the first passcode again.
NOTICE!
If the area is already in an alarm condition, the first valid passcode entered after the alarm
occurs silences the bell but does not disarm the area. Enter Code 2 appears on the display. A
second valid unique passcode is necessary to disarm the area.
NOTICE!
This feature is not allowed for use with SIA CP-01 compliant installations. Consult the local
authority having jurisdiction (AHJ) for proper usage. Refer to your control panels program
entry guide for programming information.
NOTICE!
Use this feature in banks or other facilities that might require a higher level of security to gain
access to a vault or other protected area.
D1255 Keypad
After the first valid passcode is entered, the D1255 replaces the scrolling DISARM NOW and
the Point Text display with the SECOND CODE:.display
When the user presses the first digit of the second code, the display changes to SECOND
CODE: *.
SECOND CODE: appears for 19 sec. If no digits are pressed, the display returns to normal and
the area does not disarm. If a second code is entered, the area disarms and an Opening report
is sent with the User ID of the first user. If the second code entered is the same as the first
code, is invalid, or does not have L## Disarm authority, the keypad shows NO AUTHORITY and
returns to idle text or entry delay.
D1260 Keypad
In the D1260, after the first valid passcode is entered, the following message appears for 3
sec.
When the first digit of the second code is pressed, the following message appears. As each
digit is pressed, an additional asterisk appears.
Early Ambush
Default: No
Selection: Yes or No
Yes Two valid passcodes are required to disarm the area within the time
period specified in Early Ambush Timer. The second valid disarm
passcode must be entered within a time limit. Refer to Section Early
Ambush Timer, page 176.
If the second passcode is not entered within the time limit, the system
generates a Duress Event based upon the primary user.
No A single passcode with a valid authority level can disarm the area.
The Early Ambush disarming feature is intended for use when you disarm an area that is in
the Master Armed state, but it can also be used with the Perimeter and Instant Armed states.
After the first valid passcode is entered, the area is disarmed and the keypad displays the
disarmed idle text normally. This function operates only when you use Passcode Disarm.
The D1260 Keypad sounds the Watch Mode tone and the following text appears.
During an alarm, after the first passcode is entered, the Early Ambush timer still begins. A
Cancel Report might be generated, depending upon the bell time, and the keypad displays
Alarm Silenced normally. If the second valid disarm passcode is entered, the keypads indicate
that the second passcode is valid. Refer to Section Secondary Ambush Code, page 176 for
information about the unique behavior of the two passcodes.
For SIA CP-01 Compliance:
NOTICE!
This feature is not allowed for use with SIA CP-01 compliant installations.
Default: Yes
Selection: Yes or No
Yes Delay armed points in this area restart the exit delay timer if violated
during the exit delay time.
No Delay armed points continue to count down normally if violated during
the exit delay time.
NOTICE!
This feature must be disabled for UL Line Security/Encryption applications.
When enabled, this feature activates when a controlled point with delay alarm response
changes from normal to faulted and back to normal during the exit delay. When activated, if
any controlled point in the same area with delay alarm response is faulted, the exit delay time
restarts. The exit delay continues until it expires or the area changes arming states. This
operation can occur only once in an arming cycle.
NOTICE!
To avoid the possibility of false alarms in Associate areas, do not use the A# Exit Restart
feature in areas with A# Area Type set to Shared.
A# Arm No Exit
Default: No
Selection: Yes or No
Yes Switch the arming state to Perimeter if no Perimeter Delay point faults
occurred.
No Keep the area in Master Arm if no Perimeter Delay point faults
occurred.
This parameter switches the arming state of an area from Master Armed to Perimeter Armed if
no perimeter points with delay response were activated during the exit delay time. Only the
final armed state is reported and displayed at the keypads.
NOTICE!
The A# Arm No Exit feature does not operate in areas with A# Area Type set to Shared.
A# Exit Warning
Default: No
Selection: Yes or No
Yes Pulse the alarm output for the last 10 sec of the Exit Delay time.
No Do not pulse the Alarm Bell out during the Exit Delay time.
When enabled, the Alarm Bell output pulses on and off every 2 sec for the remaining 10 sec of
the Exit Delay time.
NOTICE!
The A# Arm No Exit feature does not operate in areas with A# Area Type set to Shared.
A# Entry Warning
Default: No
Selection: Yes or No
Yes Pulse the alarm output for the last 10 sec of the Entry Delay time.
No Do not pulse the Alarm Bell output during the Entry Delay time.
When enabled, the Alarm Bell output pulses on and off every 2 sec for the remaining 10 sec of
the Entry Delay time.
For SIA CP-01 Compliance
A# Entry Warning must be set to Yes.
Command Center
Default: 1
Selection: 1 to 16 for D9412GV4 and D7412GV4
1 to 8 for D7212GV4
DIP Switch Setting
SDI Address 1 2 3 4 5 6
(CC#)
1 ON ON ON ON ON
2 OFF ON ON ON ON
3 ON OFF ON ON ON
4 OFF OFF ON ON ON
5 ON ON OFF ON ON
6 OFF ON OFF ON ON
7 ON OFF OFF ON ON
8 OFF OFF OFF ON ON
9 ON ON ON OFF ON
10 OFF ON ON OFF ON
11 ON OFF ON OFF ON
12 OFF OFF ON OFF ON
13 ON ON OFF OFF ON
14 OFF ON OFF OFF ON
15 ON OFF OFF OFF ON
16 OFF OFF OFF OFF ON
Enter the keypad (CC) number for the SDI address you are programming. This number
corresponds to the DIP switch address settings shown.
Switch 5: On=Encoding Tone On (default), Off=Encoding Tone Off
CC# Supervised
Default: No
Selection: Yes or No
Yes Only one keypad can be installed for this CC SDI address.
No More than one keypad can be installed using this CC SDI address with
the same address DIP switch setting.
Supervise this SDI address and generate Trouble SDI Reports and local trouble annunciation if
a problem occurs with this keypad or the SDI bus.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7212GV4), set CC# Supervised to Yes for the
fire annunciation keypad.
NOTICE!
Keypads that share the same address setting display the same text and emit the same tones,
regardless of which keypads keys are pressed.
Trouble SDI # Reports are always reported as Area 1, Account 1 Events regardless of the area
the SDI device is assigned.
NOTICE!
When this prompt is Yes, you cannot have duplicate DIP switch settings.
NOTICE!
Reboot the system to enable a D1260 Series Keypad.
To reboot the system, close and open the reset switch, labeled S1 RESET, located in the
upper right corner of the control panel.
Default: 1
Selection: 1 to 32 on D9412GV4
1 to 8 on D7412GV4
1 to 4 on D7212GV4
Enter the area number where you are installing this keypad or keypads with this address and
the same DIP switch settings.
CC# Scope
NOTICE!
The following prompt is visible only when you program CC## Scope to Custom. If you change
the keypad scope selection to Custom from Panel Wide, Account, or Area, the settings from
the previous CC# Scope selection become the default settings for the custom parameters in
CC# A1 [through A#] in Scope. Before exiting from a custom program, check each area and
ensure that it is enabled and disabled correctly.
Determines whether any of the areas and doors are included in the scope of this keypad for
viewing status, arming or disarming, and controlling doors from the keypad.
Default: Yes
Selection: Yes or No
Yes Master Arming allows a user to change the armed state of the areas
within the scope of this keypad. If the areas in the scope are already at
the intended armed state, they remain in that state.
If the area to which this keypad is assigned is armed, entering a
valid passcode disarms this area and all other areas assigned to
the scope of this keypad.
If the area to which this keypad is assigned is disarmed, entering a
valid passcode arms this area and all other areas assigned to the
scope of this keypad.
No Restricts the scope of the keypad to the Area programmed in CC# Area
Assign for the purpose of executing L## Passcode Arm and L##
Passcode Disarm only.
Use this program to determine if this keypad follows CC# Scope or if it only arms or disarms
the area to which it is assigned. The user must have authority enabled in L## Passcode Arm
and L## Passcode Disarm. This feature does not affect the Function List arming and
disarming commands.
NOTICE!
Tokens and cards disarm according to this prompt. If this prompt is No, tokens disarm only
the Area to which the CC# is assigned. The user must have disarming rights for tokens and
cards programmed at the Disarm Level. The user does not need disarming and arming
authority for the keypad.
NOTICE!
You can use this prompt for a group of account-wide keypads that only arm the area to which
they are assigned, even if the user has a passcode with arming authority rights in all areas.
Default: 0
Selection: 0 to 128, A, B, C for D9412GV4
0 to 64, A, B, C for D7412GV4
0 to 24, A, B, C for D7212GV4
0 The [ENTER] key is not used to activate a relay.
1 to 128 (64, 24), A, Assign the relay number that activates when [ENTER] is pressed at this
B, C keypad after the user enters a valid passcode.
Program the relay number that activates momentarily for 10 sec when a user enters a valid
passcode and presses the [ENTER] key on the keypad. Two events are generated when this
function is used: RELAY ### SET with User ID, and RELAY ### RESET without User ID. The
system logs this action as two events.
With CC## Passcode Function is set to Cycle Relay, entering a valid code and pressing
[ENTER] at a keypad silences a ringing bell.
Using the relay programmed in CC# Enter Key Relay for a low-level access control strike
on a door does not shunt a point.
NOTICE!
When CC## Passcode Function is set to Cycle Relay, the keypad cannot be used to passcode
arm or disarm.
Relays used for this function must not be shared with any other point, sensor reset, control
panel, or bell functions. Sharing can cause errors in relay operation.
Default: Arm/Disarm
Selection: Arm/Disarm, Cycle Door (D9412GV4/D7412GV4), Cycle Relay, Auto Re-
arm
Arm/Disarm Pass Code followed by ENTER (or ENT) key will start Master Delay Arm
for all areas within the users authorized scope if the current area is
disarmed. If the area is not disarmed, then all authorized areas will be
disarmed.
Cycle Door Pass Code followed by [ENTER] (or [ENT]) key will cycle the door
programmed in CC# Assign Door, then will actuate the users authorized
post access operations (Disarm, Perimeter Instant arm, or execute a
Custom Function) if enabled.
Cycle Relay Pass Code followed by [ENTER] (or [ENT]) key will momentarily
activate the CC# Enter Key Relay for 10 seconds.
Auto Re-arm Pass Code followed by [ENTER] (or [ENT]) key will restart Master Delay
Arm for all areas within the users authorized scope if the current area is
not disarmed. If the area is disarmed, then the arm state does not
change.
For SIA CP-01 Compliance
CC# Passcode Enter Function must be left at its default value Arm/Disarm.
NOTICE!
Dual Authentication applies to CC## Passcode Enter Function settings of Arm/Disarm, Arm
Cycle Relay, Cycle Door, and Auto Re-arm. When Dual Authentication is enabled, user
commands (for example, CMD 43), require a passcode only.
Default: 10 sec
Selection: 10 to 45 (in 5-sec increments)
This is the amount of time allowed between the presentation of the users credentials to the
reader and the entry of the users passcode at the keypad. If this time elapses, the Dual
Authentication process is reset and authentication is denied.
NOTICE!
During the Add User Mode, tokens or cards, door control requests, and RTE/REX do not
function. Put the Door Mode into an unlocked state before adding users if there is heavy
activity for this door.
Default: Yes
Selection: Yes or No
Yes Panel-wide trouble tones sound and visual displays show at this
keypad.
No Panel-wide troubles do not sound. Visual displays still show.
Determines whether this keypad, or any keypad with the same address setting, emits the
panel-wide trouble tones (power, phone, SDI bus, and Zonex bus).
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set CC# Trouble Tone to Yes.
NOTICE!
Panel-wide trouble tones do not include Point Troubles, Buzz on Fault, or (for D9412GV4 and
D7412GV4) Close Door Now.
NOTICE!
Assign two CCs to the same area so one keypad emits the tone and another does not.
Default: Yes
Selection: Yes or No
Yes This keypad sounds entry tones.
No This keypad does not sound entry tones.
Determines whether this keypad, or any keypad with the same address setting, emits the
entry delay tone. Any Delay point within the area scope of this keypad starts the entry
sequence.
NOTICE!
This prompt allows you to manage the tone by keypad. Entry Tone can also be turned off when
programming your P## Entry Tone off in Point Index.
NOTICE!
Assign two CCs to the same area so one keypad emits the tone and another does not.
Default: Yes
Selection: Yes or No
Yes This keypad sounds exit tones.
No This keypad does not sound exit tones.
Determines whether this keypad, or any keypad with the same address setting, emits the exit
delay tone during the delay arming of an area(s). Any keypad with a scope to arm this area can
initiate the exit tone sequence.
This prompt allows you to manage the tone by keypad. Exit Tone can also be turned off when
programming A# Exit Tone in Area Parameters.
The cadence and pitch of the exit tone increase for the last 10 sec of the exit delay time.
NOTICE!
This SIA CP-01 required feature is not supported on the D720 Series Keypads.
NOTICE!
Assign two CCs to the same area so one keypad emits the tone and another does not. Set one
keypad for CC EXIT TONE = YES, and one to EXIT TONE = NO.
Default: Yes
Selection: Yes or No
Yes This keypad activates a tone and displays PLEASE CLOSE NOW.
No This keypad does not activate the tone or display PLEASE CLOSE NOW.
Determines whether this keypad sounds a tone and displays the PLEASE CLOSE NOW
warning on the keypad when a Closing Window activates, indicating the area automatically
arms soon.
Default: Yes
Selection: Yes or No
Yes This keypad sounds a tone and displays CLOSE DOOR #.
No This keypad does not sound the tone or activate the display..
This feature is not available with the D7212GV4. Keep the default setting.
Determines whether this keypad sounds an audible tone and displays the CLOSE DOOR #
warning on the keypad. This occurs when the door is physically held open past the shunt time
and the extend time has a value greater than zero for the door assigned to this area in CC#
Assign Door.
Default: No
Selection: Yes or No
Yes Prevents the idle system status text from scrolling automatically.
Requires user intervention to advance.
No Allows the idle system status text to scroll automatically without user
intervention.
Use this parameter to enable a special non-scrolling option for the idle system status display
text on a keypad. This keypad mode requires the user to press the [PREV] or [NEXT] key on
the keypad to unlock the display and begin scrolling through the system status displays.
Default: No
Selection: Yes or No
Yes If set to Yes, the user is prompted to enter a passcode after pressing
the Menu key on the keypad. The items programmed in the Menu List
for this specific keypad are filtered by the users authority level. Only
those items in the menu list for which the user has authority appear.
No If set to No, when the user presses the Menu key, all items that are
programmed in the Menu List for the Command Center Address
(Keypad Address) appear, regardless of the users authority level.
Determines if the Menu Key, when pressed, requires a passcode to access the functions.
NOTICE!
If this parameter is set to Yes, users must enter a passcode after pressing the Menu key. When
the passcode is validated, only those functions for which the user has authority appear in the
list. If a function in the Menu List is passcode protected, the user does not need to enter the
passcode again.
Default: Yes
Selection: Yes or No
Yes This keypad shows the Alarm Aborted message for all aborted alarms
within its scope.
No This keypad does not show the Alarm Aborted message for all aborted
alarms within its scope.
For SIA CP-01 Compliance
Default: Yes
Selection: Yes or No
Yes This keypad shows the Cancel Report Sent message for all canceled
alarms within its scope.
No This keypad does not show the Cancel Report Sent message for all
canceled alarms within its scope.
This parameter enables or disables the CANCEL REPORT SENT display message when an
alarm is canceled after transmission occurs. To show this message, Cancel Report must be
set to Yes. Refer to Section 3.9 Miscellaneous, page 59.
For SIA CP-01 Compliance
CC# Cancel Display can be set to Yes or No.
Area# Is On
Area# Is Off
Area# Account is On
A blank entry disables the ACCOUNT IS ON display for this area. An account wide area shows
the AREA # IS ON text instead of the ACCOUNT IS ON text.
Unique ACCOUNT IS ON Text
Each area can have unique ACCOUNT IS ON text, or you can program the same text in each
area of the account so when all the areas in the account are armed, they all show the same
text.
D1260 Series Keypad
Although it is not programmed in this area, the D1260 Series keypad can display up to sixteen
characters for an Area Name on line 1 of its display. The Area Text (Area # Is Off, Area # Not
Ready, Area # Is On, and Account # Is On) programmed in this module appears on line 2 of
the D1260 Alpha V Keypad. When programming custom text, it should be logical to users
viewing it on the D1260. For example, the Area Name Text can be programmed to display
Front Office and the Area # Is Off text (programmed in this section) could be programmed to
display Ready To Arm. The D1260 would then show on line 1 Front Office and on line 2, Ready
To Arm.
Custom Function
Default: Blank
Selection: Blank, 128 to 143 (on D9412GV4), 128 to 131 (on D7412GV4/
D7212GV4)
Enter the Custom Function number you want to program. You can program up to sixteen
Custom Functions, which are numbered 128 to 143.
NOTICE!
Custom Functions 132 through 143 are not available with the D7412GV4 and D7212GV4.
CF### Text
Default: Blank
Selection: Sixteen alphanumeric characters. See Section 3.11.2 Area Text, page 88
for valid character entries.
Determines the menu text displayed at the keypad for the custom function item. Use this text
to represent the functions performed by this menu item.
NOTICE!
Custom Functions 132 through 143 are not available with D7212GV4.
Default: Blank
Selection: Up to 32 characters: 0 to 9, A, B, C, D, EBlank = disabled.
Selection: D1255 Key D1255 Faceplate D1260 Key
Label
0 to 9 0 to 9 0 to 9
A [COMMAND] [COMMAND*]
B [PREV] NA
(previous)
C [ESC] MENU NA
(escape)
D [NEXT] NA
E [ENT](Enter) YES [#ENTER]
C1* NA (softkey 1)
C2* NA (softkey 2)
C3* NA (softkey 3)
C4* NA (softkey 4)
C5* NA (softkey 5)
C6* NA (softkey 6)
C7* NA (softkey 7)
C8* NA (softkey 8)
* Softkey selections are stored as two keystrokes
The keystrokes simulate any sequence of keystrokes the user can perform at a keypad. You
can program up to 32 keystrokes for each Custom Function.
Callout Description
1 Softkey 1 (C1)
2 Softkey 2 (C2)
3 Softkey 3 (C3)
4 Softkey 4 (C4)
5 Softkey 5 (C5)
6 Softkey 6 (C6)
7 Softkey 7 (C7)
8 Softkey 8 (C8)
Programming Custom Function Keystrokes
Find the command you want to execute in the User Interface section of the program
record sheet. Single digit commands must be programmed with 9 as the second digit.
Command Keystrokes
1 (Master arm area) A19
2 (Perimeter instant arm) A29
3 (Perimeter delay arm) A39
6 (Watch mode) A69
7 (Special alert) A79
8 (Perimeter partial arm) A89
9 (Special alert) A99
0 (Bypass a point) A09
Table 3.16 CF### Custom Function Keystrokes
When CF### Custom Function is programmed with P, the corresponding custom
function number is passcode protected. The CF### Custom Function prompt is under
User Interface > Cmd Center Functions. The passcode protected custom function can be
added to a keypads function list by programming its number in the Function List > M#
Function prompt.
128 to 143 Enable Custom Function 128 through 143 (128 through 131 for D7412GV4/
D7212GV4) (Menu Function only): This function determines if a passcode is needed to
access a Custom Function from the menu list. ENTER PASSCODE (or Enter Passcode +
[Enter] key on the D1260) appears when this function is passcode protected.
NOTICE!
If a command within the Custom Function is passcode protected, ENTER PASSCODE appears
at the keypad. The user must enter a valid passcode before proceeding with the rest of the
Custom Function. If a passcode is not entered within 10 sec, the Custom Function times out
and the display returns to idle text.
NOTICE!
Skeds cannot execute Custom Functions that are passcode protected. The D720 LED keypad
does not support Custom Functions that are passcode protected.
Some functions cannot be entered directly because they are nested inside a higher-level
function. To automatically execute these functions, you must add the appropriate keystrokes.
For example: The Change Display (COMMAND 49) function has three sub-functions:
Bright Display, Dim Display, and Date/Time Display.
To turn up the display, enter: [A][4][9][E]
To dim the display, enter: [A][4][9][D][E]
To display time and date, enter: [A][4][9][B][E]
Custom Functions can perform several tasks at one time. For example:
To toggle relays 7, 8, and 9 in one Custom Function enter: [A] [5] [4] [7] [E] [E] [8]
[E] [E] [9] [E] [E] [C]
To add a temporary passcode, enter: [A] [5] [6] [3] [0] [E] [E] [9] [8] [7] [E] [E] [D]
[E] [1] [E] [1] [E] [1] [E] [1] [E] [1] [E] [1] [E] [1] [E] [1] [E] [C]
This adds user 30, passcode 987 with authority level 1 in all areas.
To delete the passcode, enter: [A] [5] [3] [3] [0] [E] [E] [E] [C]
To program multiple-area Arming or Disarming functions, use keystroke sequences including
COMMAND 50 (Move to Area) and COMMAND 1.
NOTICE!
Custom function cannot be used to change time (such as Daylight Saving Time). Use Skeds
S## Function Codes 13 and 14 to adjust for Daylight Saving Time (refer to S## Custom
Function prompt in Section 6.2 Schedules (Skeds), page 164.
Example 1
Execute the third function in a keypad menu function list:
D1255: CDDE
D1260: C8C7C5
NOTICE!
The custom functions in Example 1 are not compatible between keypad types.
Example 2
Instant master Arm (CMD 11):
D1255: A11
D1260: A11
NOTICE!
The custom functions in Example 2 are compatible between keypad types.
NOTICE!
The GV4 control panel series uses separate keystrokes to program the custom functions that
accurately represent the two separate user interfaces, the D1255 and D1260 keypads.
Custom functions written for the D1255 that use the [PREV], [ESC], and [NEXT] keys do not
work on the D1260.
Custom function written for the D1260 that use the softkeys (located on the sides of the
keypad display) do not work when executed from the D1255 keypad.
3.12.1 Commands
Similar to command initiation used in other Bosch Security Systems, Inc. products, the
Commands method provides continuity in the arming commands across product lines and
makes an easy transition for dealers using other Bosch Security Systems, Inc. products. With
commands, the end user presses [COMMAND] and then the numeral of the command to
initiate. For example, [COMMAND][2] arms the perimeter of the area. Some prompts can be
accessed only from a menu. These prompts are indicated by (Menu Function only). To access
these functions, press [MENU], enter the function number, and use the [PREV] and [NEXT]
keys to scroll through the choices.
The D9412GV4/D7412GV4/D7212GV4 Program Record Sheet (P/N: F01U214958) lists the
commands available with the system. Command numbers are shown in the column labeled
Command. If a particular function does not have a command number, it can be accessed only
through the Function List.
If you plan to use only commands to operate the system, and to arm and disarm by entering a
passcode, you do not need to program Custom Function or Function List.
Selection Description
- Disable the function panel-wide. The keypad shows NO AUTHORITY if
you access the function using a command or the Function List.
E Enable the function panel-wide. The function can be executed without
entering a passcode.
P Passcode required. When the passcode is entered at the keypad, the
control panel checks the users authority level. Refer to
Section 3.12.6 Authority Level Selections, page 102.
Table 3.17 Keypad Programming Choices
NOTICE!
Refer to Section 3.12.6 Authority Level Selections, page 102 for a detailed description of the
functions on the following pages. These parameters determine only if the authority level
functions are passcode protected.
Default: P
Selection: -, E, or P
P Passcode: Required for all users with Master Arm Delay enabled for
their authority level.
E Enable: A user does not need a passcode to use [COMMAND][1].
- Disable Master Arm Delay cannot be accessed in the function menu or
started with a command even if this function is enabled for the users
authority level.
Default: - (Disabled)
Selection: -, E, or P
Perimeter Instant
Default: - (Disabled)
Selection: -, E, or P
Perimeter Delay
Default: P
Selection: -, E, or P
Watch Mode
Default: E
Selection: -, E, or P
Perimeter Partial
Default: P
Selection: -, E, or P
NOTICE!
Local Only Reporting: No Closing Report is sent to the central station, but a Perimeter Delay
Closing Event is generated in the event log.
Default: P
Selection: -, E, or P
View Memory
Default: E
Selection: -, E, or P
Default: E
Selection: -, E, or P
Walk Test
Default: E
Selection: -, E, or P
Fire Test
Default: P
Selection: -, E, or P
Send Report
Default: E
Selection: -, E, or P
Default: P
Selection: -, E, or P
Default: P
Selection: -, E, or P
Change Display
Default: E
Selection: -, E, or P
Change Time/Date
Default: P
Selection: -, E, or P
Change Passcode
Default: P
Selection: -, E, or P
NOTICE!
Regardless of whether an E or a P is entered when a COMMAND 55 is performed, the keypad
asks for the users current passcode first.
Add User
Default: P
Selection: -, E, or P
Del User
Default: P
Selection: -, E, or P
Extend Close
Default: P
Selection: -, E, or P
View Log
Default: E
Selection: -, E, or P
Print Log
Default: P
Selection: -, E, or P
User Command 7
Default: P
Selection: -, E, or P
User Command 9
Default: P
Selection: -, E, or P
Bypass a Point
Default: P
Selection: -, E, or P
Unbypass a Point
Default: P
Selection: -, E, or P
Reset Sensors
Default: E
Selection: -, E, or P
Change Relay
Default: P
Selection: -, E, or P
Remote Program
Default: P
Selection: -, E, or P
Move to Area
Default: P
Selection: -, E, or P
Display Revision
Default: E
Selection: -, E, or P
Service Walk
Default: P
Selection: -, E, or P
Default Text
Default: P
Selection: -, E, or P
Change Skeds
Default: P
Selection: -, E, or P
Default: P
Selection: -, E, or P
Default: P
Selection: -, E, or P
Default: P
Selection: - or P
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the Disable Keypad Prog option.
2. The current keypad programming configuration shows (for example, Keypad
Programming Allowed: Yes).
3. Press the Edit softkey to change the areas status.
4. Press the Yes or No softkey, and then press the Save softkey to save the changes.
5. Press the Save softkey to save the changes.
When the keypad reads Parameter Saved, your selection has been configured.
NOTICE!
You can continue using the current programming session. Keypad programming is disabled
once you exit the current session.
NOTICE!
To determine the L## default values Page 103 through Page 115, refer to the User Interface
section in the program record sheet.
L## Disarm
Default: Authority Levels 1-5, 14: Enabled (E)Authority Levels 6-13: Blank (-)
Selection: - or E
Default: Authority Levels 1-5: Enabled (E)Authority Levels 6-15: Blank (-)
Selection: - or E
Default: Authority Levels 1-2: Enabled (E)Authority Levels 3-15: Blank (-)
Selection: - or E
Default: Authority Levels 1-4: Enabled (E)Authority Levels 5-15: Blank (-)
Selection: - or E
Default: Authority Levels 1-4: Enabled (E)Authority Levels 5-15: Blank (-)
Selection: - or E
Default:: Authority Levels 1-3, 15: Enabled (E)Authority Levels 4-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-4: Enabled (E)Authority Levels 5-15: Blank (-)
Selection: - or E
NOTICE!
Local Only Reporting: No Closing Report is sent to the central station, but a Perimeter Delay
Closing Event is generated in the event log.
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-3, 15: Enabled (E)Authority Levels 4-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-3, 15: Enabled (E)Authority Levels 4-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Local alarm annunciation and event printing; no reports are sent to the central station
receiver.
Automatic smoke detectors reset for all Fire points programmed with P## Resettable as
Yes.
D1255 Keypad displays a sequential count and the text for the point after each point is
activated and restored.
If enabled in Routing, Walk Start and Walk End Reports are sent to the central station
receiver at the beginning and end of the test.
NOTICE!
A# Verify Time for Fire points that is programmed with Yes for P## Alarm Verify is ignored
during the Fire Walk Test.
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 15: Enabled (E)Authority Levels 1-14: Blank (-)
Selection: - or E
Default: Authority Levels 15: Enabled (E)Authority Levels 1-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-4, 15: Enabled (E)Authority Levels 5-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-4, 15: Enabled (E)Authority Levels 5-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-4, 15: Enabled (E)Authority Levels 5-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Points 128 and Point 248 are not accessible by this function. This is normal. These points are
used for supervising the Zonex 1 bus (Point 128) and Zonex 2 bus (Point 248).This function
allows viewing of extra points. Extra points occur under three conditions: the P### Point
Source is set to anything other than Unassigned, the P### Point Index is set to 0, and at least
two points are installed for the same Point Assignment on different Point Sources.
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Default: Authority Levels 1-6: Enabled (E)Authority Levels 7-15: Blank (-)
Selection: - or E
A user with this authority level can Force Arm.
Default: Authority Levels 1-14: Enabled (E)Authority Level 15: Blank (-)
Selection: - or E
Generates Opening and Closing Reports if the area where this authority level is assigned
sends Opening and Closing Reports.
Default: Blank
Selection: - or E
Generates an Opening Report if a bell is ringing or a Closing Report when force or bypass
arming. The area where this authority level is assigned must be programmed for restricted
openings and closings (refer to the A# Restrictd O/C prompt in Section 3.10.4 Open/Close
Options, page 69.
Default: Authority Levels 1-14: Enabled (E) Authority Level 15: Blank (-)
Selection: - or E
Generates Perimeter Opening and Closing Reports if the area where this authority level is
assigned sends Perimeter Opening and Closing Reports. Refer to the A# Perimeter O/C
prompt in Section 3.10.4 Open/Close Options, page 69.
Default: Authority Levels 1-14: Enabled (E)Authority Level 15: Blank (-)
Selection: - or E
Generates a Duress Report if the area where this authority level is assigned sends duress.
(Refer to the A# Duress Enable prompt on in Section 3.10.4 Open/Close Options, page 69.)
Default: Authority Levels 1-6: Enabled (E) Authority Levels 7-15: Blank (-)
Selection: - or E
Arm an area by entering a passcode and pressing [ENTER].
Default: Authority Levels 1-5, 14: Enabled (E) Authority Levels 6-13, 15: Blank (-)
Selection: - or E
Disarm an area by entering a passcode and pressing [ENTER].
Default: Authority Levels 1-5: Disarm (D)Authority Levels 6-15: Blank (-)
Selection: I, D, or -
I Users change the Master Armed state and Perimeter Armed state to
Perimeter Instant. The armed state does not change in other areas, and
the armed state does not change if the area is already in the perimeter
instant or disarmed state. User needs access level for Master Armed
(M) state.
D Users change the local areas Master Armed state and Perimeter Armed
state to the Disarm state. User needs access level for Master Armed (M)
or Perimeter Armed (P) state. All areas within the scope of the keypad
assigned to the D# CC# Scope in the access handler, and areas to
which the user has disarm rights, disarm as programmed.
- Users do not have disarm rights in this area.
NOTICE!
Burglar bells are silenced in the local area when a user disarms with a token or card or
presents the token or card during an alarm. The user must use a passcode to silence a Fire
Bell. Cancel Reports are sent after a valid passcode or token or card silences the bell.
NOTICE!
Opening and Closing Reports are sent to the central station receiver if programmed.
For more information on programming this prompt for a shared area, refer to Section Access
Control Readers Assigned to the Shared Area, page 66.
C User can activate the custom function assigned to the door in this area
while the area is Master Armed, Perimeter Armed or Disarmed.
- User cannot activate the custom function assigned to the door in this
area.
NOTICE!
When a token or card can also disarm an area, the custom function starts after the area
disarms.
NOTICE!
A user does not require L## Security Level or L## Disarm Level authority to activate a custom
function with a token or card.
NOTICE!
Tokens or cards that are used to execute Custom Functions must have a passcode assigned to
the corresponding User###.
Default: Authority Levels 1-6: Enabled (E)Authority Levels 7-15: Blank (-)
Selection: Blank (-) or Enabled (E)
Blank (-) This function is not authorized for the user who is assigned this
authority level.
Enabled (E) Enabled (E): This function is authorized for the user who is assigned
this authority level.
Allow a user with this authority level to arm or disarm an area by using their assigned keyfob.
NOTICE!
Authority Level 15 is reserved for the Service Passcode (User 0). Since the installer is not
allowed a keyfob, authority level 15 shall always be disabled (-).
NOTICE!
Duress operation when disarming is not applicable when using Keyfobs.
Default: Authority Levels 1-6: Enabled (E)Authority Levels 7-15: Blank (-)
Selection: Blank (-) or Enabled (E)
Blank (-) This function is not authorized for the user who is assigned this
authority level.
Enabled (E) Enabled (E): This function is authorized for the user who is assigned
this authority level.
When local authorization is required, only a security user with the Remote Firmware Update
authority enabled shall be able to authorize the update. By default, Remote Firmware Update
authority is only enabled for the Service Passcode (Authority level 15).
M## Function
Default: M1 through 15 are functions 1, 2, 29, 11, 15, 16, 17, 18, 19, 25, 26, 9,
10, 8, 21.M16 through M32 are 0.
Selection: 0 to 30, 32 to 37, and 128 to 143 (131 on D7412GV4 and D7212GV4)
Enter the function number indicated in the # column of the program record sheet or next to
the function in Section 3.12 User Interface, page 93.
NOTICE!
Function numbers 128 to 143 are custom functions and show the text programmed for CF ###
Text.
NOTICE!
There is no restriction on how many times you can assign a specific function to the menu. By
assigning a specific function more than once, you can assign the same function at different
keypads so that their order is different in different areas.
Default: M1, M2, M13, M15 are Yes for CC1 through CC16M3 .. M12, M14, M16
.. M32 are No for CC1 through CC16
Selection: Yes or No
Yes This menu item appears at this keypad address.
No This menu item does not appear at this keypad address.
Programming this prompt determines at which CC address setting this menu item appears.
Do not use the CHANGE RELAYS? function to toggle relays reserved for special functions.
Special function relays are Area and Panel Wide Relay functions as well as relays assigned
to CC Enter Key Relay and P## Relay Response Type.
Relay C is always on. Assigning any other relay (1 to 128, A or B) deactivates Relay C so
this output can be used for other functions. When Relay C is programmed for A# Rest
Sensors, power is always supplied from Terminal 8 of the control panel.
Relay Restoration: The status of relays after programming or resetting the control panel
might restore automatically or require manual restoration. All relays are turned off after
the control panel reboots. The control panel checks certain relay functions every minute
and resumes the correct state after the reset. Other relays must be manually set to the
correct state using the Change Relay Function (COMMAND 54).
Relay functions that resume the proper state within one minute of reboot:
Alarm Bell Perimeter Fault
Summary Fire Summary Trouble
Area Armed Reset Sensors
Fire Bell AC Fail
Summary Alarm Phone Fail
Silent Arm Summary SupBurg
Summary Fire Trouble Communications Fail
Watch Mode Summary SupFire
Relay functions that must be reset manually with Change Relay function (COMMAND 54):
Fail To Close Force Armed
Duress
A# Alarm Bell
Default: A
Selection: 0, 1 to 128, A, B, C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
This voltage output relay activates and provides 12 VDC output when a Non-fire point (P##
Fire is No) assigned to this area activates an alarm.
NOTICE!
A# Burg Time and A# Burg Pattern must be programmed in Area or Bell Parameters. This relay
activates according to the bell pattern and remains active until the bell time expires or a valid
passcode is entered. P## Silent Bell must be No for the bell to ring upon alarm.
A# Fire Bell
Default: A
Selection: 0, 1 to 128, A, B, C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
This voltage output relay activates and provides 12 VDC output when a Fire point (P## Fire is
Yes) assigned to this area activates an alarm.
NOTICE!
Fire Time and Fire Pattern must be programmed in Bell Parameters. This relay activates
according to the bell pattern and remains active until the bell time expires. P## Silent Bell
must be No in order for the bell to ring upon alarm.
NOTICE!
Although Relay C is a valid entry for A# Fire Bell, do not program Relay C for this entry. Use
Relay A for the A# Fire Bell.
NOTICE!
To meet UL 864 requirements, set A# Fire Bell to a value other than 0.
A# Reset Sensors
Default: C
Selection: 0, 1 to 128, A, B, C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Unlike the default relay for Alarm Bell and Fire Bell, this voltage-output relay (Relay C) de-
activates for 5 sec when the Reset Sensors? function is activated from the keypad or during a
Fire Walk Test.
NOTICE!
The Reset Sensors time converts from the 5 sec default time to the time programmed in A#
Verify Time (Section 3.10 Area Parameters, page 61) when a point programmed for P## Alarm
Verify (Section 5.1 Point Index, page 130) enters an alarm condition.
NOTICE!
When sharing one relay to reset sensors in two or more areas, you must program the
following. Failure to do so causes TROUBLE PT ### for all point types programmed as P##
Resettable.
CC # Scope must include all areas that share the relay.
L## Reset Sensors authority must be assigned to the passcode that activates the
COMMAND 47 or Reset Sensor function.
A# Verify Time must be the same number of seconds for all areas that share the relay.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set A# Reset Sensors to a value
other than 0.
A# Fail to Close
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
This relay activates when the Closing Window expires for the specified area. It remains active
until midnight, another Closing Window starts, or the control panel resets, whichever occurs
first. When Perimeter Relay (Section Perimeter Relay, page 178) is set to Yes, the A# Fail to
Close prompt becomes A# Perimeter Relay.
A# Force Armed
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
This relay activates when this area is Force Armed. It remains active until the area disarms or
the control panel resets.
NOTICE!
If Force Bypassing is required during Perimeter Arming, this relay does not activate.
A# Watch Mode
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
This relay activates when a Controlled point programmed for P## Watch Point is faulted in
the specified area while the area is in Watch Mode and the point is not armed. It remains
active for 2 sec after each point is faulted.
A# Area Armed
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
This relay activates when the specified area becomes Master Armed. The exit delay must
expire before the relay activates. The relay remains active until the area disarms. It does not
deactivate during the entry delay time.
If multiple areas use the same relay, the relay activates when all areas are armed. It
deactivates when the first area disarms.
The A# Area Armed relay function can provide visual feedback at a key switch station. Attach
a LED to the output of a D8129 Module programmed for this function.
A# Area Fault
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates whenever a controlled (P## Type 1, 2, 3 only) Perimeter or Interior point is faulted.
The relay remains active until all Perimeter and Interior points in the area are normal.
NOTICE!
Keyswitch area armed status with LEDs: Use a D8129 Module and connect an LED to indicate
that the area is not ready to arm.
A# Duress Relay
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when a Duress alarm is generated from a keypad assigned to the specified area.
NOTICE!
Burg Time needs a bell period programmed and A# Duress Enable must be Yes. This relay
activates when the Burg Bell starts and deactivates when the Burg Bell time ends. The Burg
Bell pattern has no effect on this relay function.
A# Perimeter Fault
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when a Controlled Perimeter point (P## Type 1) assigned to the specified area is
faulted, regardless of the armed state of the area. This relay provides a steady output until all
Perimeter points in the area return to normal.
NOTICE!
This relay does not activate on interior faults. To detect all area point faults, program all
points as Perimeter points in the area where this relay is assigned.
A# Silent Alarm
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
This relay activates when a point assigned to the specified area and programmed for P##
Silent Bell goes into alarm.
NOTICE!
This relay does not activate on interior faults. To detect all area point faults, program all
points as Perimeter points in the area where this relay is assigned.
AC Failure
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when the control panel responds to an AC power failure as programmed in AC Fail
Time in Section 3.6 Power Supervision, page 50. This relay automatically resets when AC power
restores.
NOTICE!
Use this relay to create audible annunciation. Enable the keypads trouble sounders for all
applications except commercial fire systems.
Battery Trouble
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when battery voltage falls below 85% of capacity (12.1 VDC) for a fully charged
(13.8 VDC) battery, or when the battery is in a missing condition. This relay automatically
resets when battery power restores.
NOTICE!
Use this relay to create audible annunciation. Enable the keypads trouble sounders for all
applications except commercial fire systems.
Phone Fail
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when a telephone line failure occurs. A time must be entered in Ph Supv Time (refer
to Section 3.2 Phone Parameters, page 19) for this relay to activate. This relay resets
automatically when restoral of the phone line(s) occurs.
Comm Fail
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when a control panel cannot communicate a report after making ten attempts to
each routing destination. At the same time, COMM FAIL RG displays at the keypad. This relay
automatically resets when a report is sent successfully.
NOTICE!
Use this relay to report primary digital report failure to an alternate communication device.
Log % Full
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
This parameter determines how full the memory log should be before initiating a call to RPS at
the central station. This allows the memory log to be copied by RPS before messges can be
overwritten. An entry of 0 (zero) disables the LOG THRESHOLD and LOG OVERFLOW events.
These events are not put in the log nor reported to the D6500/D6600 or to the local
printer.The control panel continues to log events after the LOG THRESHOLD report is sent.
When it reaches 100% capacity (memory logger is full and previously stored events will be
overwritten), the control panel generates a local LOG OVERFLOW event. The control panel
does not call RPS again until it downloads the log and the Log % Full percentage is again
reached. These events are also sent to the control panel's event log and to the local printer(s)
if installed.
Summary Fire
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Enter the number of the relay that activates when any Fire point in the system (P## Type 0,
P## Fire Yes) enters into alarm. This relay provides a steady output until all Fire points in the
system return to normal. Refer to Section Fire Summary Sustain, page 175 for details on
alternate operation.
Summary Alarm
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Enter the number of the relay that activates when a Non-fire point enters into alarm. This relay
provides a steady output until the alarm is acknowledged by a valid passcode, then cleared
from alarm memory with an acknowledgment at the keypad.
NOTICE!
This relay does not activate for silent and invisible alarms.
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when any Fire point in the control panel is in trouble, or if a Fire Supervision point is
missing. This relay provides a steady output until all Fire points restore to a normal condition.
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when any Fire Supervisory point in the control panel is in a supervisory condition
(off-normal). This relay provides a steady output until all Fire Supervisory points are restored
to a normal condition.
Summary Trouble
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when any Non-fire point in the control panel is in a trouble condition. This relay
provides a steady output until the user at the keypad acknowledges the trouble.
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Activates when any Non-fire Supervisory point in the control panel is in a supervisory
condition, or if a Supervisory Burg point is missing. This relay provides a steady output until
the user at the keypad acknowledges the condition.
4.1.2 Passcodes
In a control panel with factory default settings, only the master user has an assigned
passcode. A passcode can be three to six digits. Entering three digits in User ### chooses the
user. Programming the U001 Passcode assigns a passcode to the master user. User ID 0
(zero) is reserved for the service user and can not be assigned an access credential or a
keyfob.
Passcode Tamper
If a user enters six consecutive invalid passcodes at the same keypad, the control panel sends
a User Code Tamper report to the central station. The invalid passcode count resets when a
valid passcode is entered at the same keypad. Refer to R# Usr Code Tamper in Table 3.7,
Page 34 for information on enabling this report.
The passcode tamper condition is also reported in a manually initiated Extended Test Report
and to RPS through control panel diagnostics. As a result, the tamper condition is reset after
the successful completion of a manual report or when disconnecting from an RPS session.
The tamper condition is not reset when the control panel reboots.
NOTICE!
In reporting systems using ModemIIIa2 reporting format, all three digits of the User ID Code
are transmitted to the central station with appropriate reports. Central station automation
computer systems can accept only Zonex and Comex style User IDs. Refer to Section Point/
User Flag, page 19.
NOTICE!
User 000 is the Service Authority Level (Level 15). You cannot change the programming for
user 000.
Only the Service Authority Level (User 000) can delete User 000. When a user other than User
000 tries to delete the passcode for User 000, the keypad gives an error tone and prohibits
the operation.
User 000 cannot be added or changed by the Add/Change user command (COMMAND 56)
except by a user with the Service Passcode.
U### Passcode
Default: User 001 is 123456, All other user passcodes are Blank.
Selection: Three to six digits ( 0 to 9)
Enter three to six digits to enable a passcode for the master user in this group.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), enter at least one Passcode.
NOTICE!
User I.D.000 is the reserved user for service personnel. The default service passcode is 123.
The programmer does not allow you to enter any passcode number that might conflict with a
duress passcode. The programmer reserves the passcode number plus 1, duress passcode
number plus 2, passcode-number minus 1, and passcode number minus 2.
For example, when a passcode of 654321 is entered, 654322, 654323, 654320, and 654329
are reserved and are not available to other users.
NOTICE!
The authority to silence a bell is granted to all passcodes with authority level 1 or greater. A
user passcode can silence a Fire or Burg bell as long as any authority level of 1 or higher is
assigned to the area where the bell can be silenced.
Default: 0
Selection: 0 = no group, 1 to 8
Create a group of users whose command authority can be enabled and disabled using an
automatic user window. The user group is the number entered into the W# User Group for
any active W# User Window. Multiple windows can be programmed for one user group (up to
eight) within one 24-hour period. For example, if User Group 1 has a window running from
8:00 AM (start time) to 4:00 PM (stop time), the users for that group can use their passcodes
only between that time. Between 4:00 PM that day and 8:00 AM the next day, the users
cannot use their passcodes.
NOTICE!
To enable this users passcode at all times, leave U### User Group set to default (0).
User Group Window times cannot be changed from the keypad. When a window is assigned to
a user group, the users in that group rely on the window to be active (within the start and
stop times) for their passcodes to function. The only way to disable the window is by
reprogramming the control panel from the remote programming software (RPS).
Default: User 000 is Level 15 for All areas.User 001 is Level 1 for Area 1, 0 for
Areas 2-32.All other users are Level 0 for all areas.
Selection: 0 to 14
Assign an authority level to the user for this area. A setting of 0 means the user has no
authority in this area.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), assign an authority level of 1 to 14
to the Passcode to silence bells.
U### Name
Default: 255
Selection: 0 to 255
This feature is not available with the D7212GV4. Keep the default setting.
User ### Site Data: Enter the first three decimal numbers on the back of the token or card.
This is the first byte (bits 2 through 9) of data for a 26-bit Wiegand card. This is called the site
number. Tokens and cards with a site code of 255 are not compatible with the D9412GV4/
D7412GV4 Control Panels.
NOTICE!
Converting hexadecimal to decimal: If your card label contains letters as well as numbers,
the number is hexadecimal.* Convert the hexadecimal number to decimal using your
calculator. If you cannot convert in this way, use the reader and the Add/Chg User? Function
to add the tokens or cards.
Perform the following test to confirm that you can convert properly:
Use 319EB0 as the hexadecimal number. On your calculator, press [HEX]. Enter all the
hexadecimal characters into the calculator. Press [DEC] and your hexadecimal characters
convert to the following eight digits: 03251888. The site number is 032. Enter it in U### Site
Code. Your card data is 51888. Enter it into U### Card Data.
*A hexadecimal number can contain all numerals. If the code does not work, try converting the number from
hexadecimal to decimal.
NOTICE!
Always tag your tokens before adding them to the system so you do not mix them up. Use the
CRD ID ###-# number to index them.
Default: Blank
Selection: 00000 = (0) to 65534 or Blank (65535)
This feature is not available with the D7212GV4. Keep the default setting.
User ### Card Data: Enter the remaining five decimal numbers on the back of the token or
card. This is the second and third byte (bits 10 through 25) of data for a 26-bit Wiegand card.
This is called the card data.
You must program U### Site Code before programming this prompt.
U### Keyfob ID
Default 0
Selection: 0 - 99999999
Each user can be assigned a wireless keyfob ID. A Keyfob RFID can be Auto-Learned through
the SDI2 bus RF receiver, or it can be entered here. Auto-Learned RFIDs can be edited for
Keyfob replacement, or can be set to 0 to disable a users Keyfob. A RFID (Radio Frequency
device IDentification number) is a unique number assigned to a wireless device at the factory.
It provides a unique way for the Wireless Receiver and Wireless Repeaters to identify what
device is transmitting.
NOTICE!
Duplicate ID detection must be based on the RFID value stored in configuration memory, not
on the number printed on the device.
NOTICE!
Keyfobs are not supervised when assigned to a User.
5 Points
P## Type
Default Refer to the program record sheet
Section 0 to 9, or 11
P## Type Description
0 24-hour: A 24-hour point is not turned on and off from a keypad. 24-hour points are armed all the time,
and can be used for fire protection (refer to Section P## Fire Point, page 143), panic, medical, and
police alerts.
24-hour protection for fire doors, roof hatches, and so on. Instead of programming this type of
protection as a 24-hour point, consider using a Perimeter point type with a Point Response of 9 to E. 24-
hour points do not show faults when an arming function is entered, but Perimeter points do. When
programming this type of protection, consider also using the Buzz on Fault and Local While Disarmed
options.
1 Perimeter: Perimeter points are armed with all arming functions. Points programmed as perimeter can
also be armed as a group (using Perimeter-Arming functions) separately from points programmed as
interior. This lets the user partially arm the system to establish Perimeter protection while occupying
the interior of the protected premises.
Perimeter points can be programmed to activate entry delay time. If the point activates entry delay, it
can also activate an entry tone.
When a Perimeter point is programmed for entry delay, entry delay time is always provided. If the area is
in entry delay when a second Perimeter point is faulted, the control panel compares the remaining entry
delay time to the time programmed for the second Perimeter point. If the second Perimeter points
entry delay time is less than the remaining time, it shortens the entry delay time.
Perimeter points programmed for an instant point response, generate an alarm immediately when
faulted, even during entry or exit delay.
2 Interior: Interior points are armed only by master arming the area. They are not armed when using
Perimeter Arming functions. These points are typically used to monitor interior detection devices such
as interior doors, motion detectors, photoelectric beams, and carpet mats.
Instant Interior Points: Interior points are usually programmed for an instant alarm (refer to
Section 5.2 Point Responses, page 132). Points programmed for instant alarms generate alarms
immediately, even during entry or exit delay.
Delayed Interior Points: Interior points can be programmed for a delayed point response. A delayed
response means that if the point is faulted while the area is armed, it activates entry delay. It does not
generate an alarm until entry delay expires.
When an Interior point is programmed for entry delay, entry delay time is always provided. If the area is
in entry delay when a fault occurs for the Interior point, the control panel compares the remaining entry
delay time to the time programmed for the Interior point. If the Interior points entry delay time is less
than the remaining time, it shortens the entry delay time.
Delayed points can also activate an entry tone at the keypad (refer to the P## Entry Tone Off prompt in
Section 5.2 Point Responses, page 132).
In some cases, you might need to create an Interior point that causes an instant alarm if the entry delay
is not started first. Use Interior Follower to create this type of protection.
NOTICE!
If a point with the type of 11 Aux AC Supervision is bypassed, 24 HOUR PT BYPASSED is
shown on the keypads.
Combining Point Response 9 with the Local While Armed feature provides off-site reporting
when the area is disarmed, but only local alarm annunciation when the area is armed.
Point Response E: Use this setting for Zonex or ASIC motion detectors. The control panel can
report troubles while Master Armed.
Point Response F: Does not sound at local keypads but activates a relay when P## Relay
Response Type is set to 1 and annunciates a fault at the keypads. To annunciate the off-
normal state at a keypad, program P## Display as Device as Yes or optionally set P## BuzzOn
Fault as 1 or 2. This point response does not generate alarms nor does it activate the Alarm
Bell.
Point Response 8, 9, A, B, and C: These point responses provide supervisory (24-hour)
reporting.
Key:
I = Instant alarm
D = Delayed alarm
S = Supervisory
Blank = Audible or visual response
Example of Controlled point:
Point Type = 1
Point Response = 8
Perimeter point with delayed alarm response when armed (opened or shorted) and no
response when disarmed.
Example of 24-hour point:
Point Type = 0
Point Response = 8
If this time expires before disarming, or if the point is configured with an instant response (I),
an alarm occurs.
NOTICE!
Make entries in 5 sec increments. The programmer does not allow off-increment entries.
With Passcode Length set to a non-zero value, entering a valid Passcode during Entry Delay
disarms the system as soon as the last digit is entered. No other keys are required. When the
control panel is in Exit Delay or is armed, entering a valid Passcode must be followed by the
[ENTER] or [ENT] key.
NOTICE!
If another Perimeter or Interior Follower Delay point trips while the area is already in entry
delay, the control panel adjusts the delay time to the Delay point with the least amount of
delay time.
When a user enters an area, a Perimeter point is faulted and the entry delay starts. If an
interior point must fault during entry delay to allow the user to disarm the area at a keypad,
program P## Type as 3 (Interior Follower).
Tone Off
NOTICE!
Entry Tone can also be turned off when programming your CC Entry Tone in
Section 3.11 Keypad (Command Center), page 78, that allows you to manage the tone by
keypad.
NOTICE!
You might want to disable the entry tone in high security applications where you do not want
to annunciate entry delay.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to No.
NOTICE!
If you want this point to ring the bell because the message failed to reach the central station
receiver, program P## Audible After 2 Failures as Yes.
NOTICE!
Use this option for fire applications to meet the requirement that audible alarms cannot be
silenced until the fault condition clears or the Fire Bell time expires.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to No.
Use this option to determine whether the point appears in the keypad display upon an alarm
condition. For LED keypads, the LED does not illuminate upon an alarm condition. Point text
appears and annunciation is made for Invisible points programmed for a trouble condition in
point response.
NOTICE!
To prevent the keypad alarm tone and the A# Burg Alarm bell from sounding, program P##
Silent Bell as Yes.
NOTICE!
If a user enters a valid passcode while a bell is ringing for an invisible alarm, the keypad shows
ALARM SILENCED.
NOTICE!
Points bypassed (by the user, Sked, Swinger Bypass, or RPS) do not generate a Buzz On Fault
condition at the keypad.
NOTICE!
The buzz does not automatically stop when the point is restored when using Option 1 or 2.
The user must acknowledge the buzz before the buzz stops. However, when using Option 3,
the buzz stops automatically when the point restores to normal without user intervention.
NOTICE!
Do not use the Change Relays? function to toggle relays reserved for special functions.
Special function relays are Area and Panel Wide Relay functions as well as relays assigned to
CC## Enter Key Relay and P## Relay Response Type.
Use P## Display as Device to cause the keypad to display CHECK DEVICE when a point is off-
normal or is acknowledged after going into alarm.
NOTICE!
Use this function for devices with a dry contact output that faults a point when the device is in
a trouble condition.
Use this option to allow a Controlled point (P## Type 1, 2, 3), to report Alarms, Troubles, and
Restoral Reports only when the area is armed. This prompt does not affect local annunciation.
NOTICE!
Local While Disarmed suppresses all reports from 24-hour points. Do not use P## Type 0 for
this prompt. Remember that this option works only for Disarmed points, and a Type 0 is a 24-
hour Always Armed point. Instead, choose any type other than 0, and use a point response
that reports an alarm, whether or not the point is armed. For instance, P## Type 1 and P##
Response 9 reports an alarm on an open or a short (I) whether the area is armed or not.
Local While Disarmed affects Keyswitch points. This prompt suppresses keyswitch (troubles
and restorals) and D279 (alarms, troubles, and restorals). Do not use this parameter for these
applications.
Allows a controlled point (P## Type 1, 2, 3), to report Alarms, Troubles, and Restoral Reports
only when the area is disarmed. This prompt does not affect local annunciation.
NOTICE!
Local While Armed suppresses all reports from 24-hour points. Do not use P## Type 0 for this
prompt. This setting works only for disarmed points. Type 0 is a 24-hour, always armed point.
Choose any Type other than 0, and use a point response that reports an alarm whether or not
the point is armed. For instance, P## Type 1 and P## Response 9 reports an alarm on a trouble
or a short whether or not the area is disarmed.
Local While Armed affects Keyswitch Points. This prompt suppresses keyswitch (alarms,
troubles, and restorals) and D279 (opening, closing, troubles, and restorals). Do not use this
parameter for controlled points that arm or disarm.
Use this option to disable any Restoral Reports from this point after it returns to normal from
an alarm or trouble condition.
NOTICE!
When the point cannot return to the system through disarming, the point must be manually
unbypassed using the Unbypass keypad function, Sked Functions 4 and 5, or remote
programming software (RPS).
NOTICE!
For Force Armed points to remain bypassed, ensure that P## Force Arm Returnable is set to
No.
P## Bypassable
Bypassing a 24-hour point: When a 24-hour point or 24-hour Supervisory point is bypassed,
24 HOUR BYPASS scrolls continuously at the keypad.
Bypassing a Fire Point: FIRE BYPASS scrolls to indicate that a 24-hour Fire point or a Fire
Supervisory point is bypassed.
NOTICE!
Alternative to a 24-hour Point: For alarm capability of a 24-hour point without the continuous
scrolling, use a Perimeter point with a Point Response of 9 to E.
NOTICE!
If the P## Bypassable option is set to Yes, a point can be bypassed in several ways. Refer to
Table 5.1.
NOTICE!
If the P## Swinger Bypass option is set to Yes, a point is automatically bypassed after the
fourth alarm or trouble report is sent. A swinger Bypass report is sent at the same time.
NOTICE!
Programming Bypassable as Yes for Cross Points can cause missed Cross- Point alarms. For
example, if Points 1 and 2 were programmed as Cross Points and Point 1 was Bypassed or
Force Armed, Point 2 cannot generate an Alarm Cross Point Event. Point 2 can; however,
generate an Unverified or Alarm Event depending on how the point was faulted. Be careful
when using this feature with Cross Point applications.
Use the P## Swinger Bypass parameter to allow the control panel to bypass automatically a
point that reports two or more alarm or trouble events within the same arm cycle. The
maximum number of faults allowed on a point is set in the Swinger Count prompt (refer to
Section Swinger Count, page 177).
The control panel reports a Swinger Bypass when the Swinger Count is reached and P##
Report Bypass at Occurrence is set to Yes. If the point has a partial count (less than the
Swinger Count number of events during an hour), the count is reset to zero.
NOTICE!
P## Bypassable does not need to be programmed as Yes for swinger bypass to work.
NOTICE!
A Swinger Shunted point returns to the system if P## Bypass Returnable? is Yes. If not, return
the point to the system through manual unbypass or [COMMAND][0][0]. Refer to P## Bypass
Returnable in the program entry guide for additional information.
and any point being bypassed during the arming sequence report as POINT BYPASS along
with the Closing Report.
NOTICE!
When P## Defer Bypass Report is set to Yes and Closing Reports are suppressed by using
Closing Windows, the deferred Bypass Reports are not sent.
Bypass Reports for 24-hour points do not report If P## Report Bypass at Occurrence and P##
Defer Bypass Report are both set to No.
NOTICE!
To report the bypass at occurrence and when the area is armed, program P## Report Bypass
at Occurrence and P## Defer Bypass Report as Yes. A Command Bypass Report is sent as
soon as the user manually bypasses a point, and a supplemental Point Bypass Report is sent
with the Closing Report.
The P## Cross Point option is designed to reduce false alarms. To achieve this, program two
or more points within a Cross Point Group with this prompt enabled. The Cross point feature
is available only on points where P## Pt Response is set to a value that generates an instant
alarm response.
The Cross Point feature does not activate when a fault occurs on Controlled points (Point
Types 1, 2 and 3) in the disarmed, entry delay, or exit delay states. Refer to Section P## Cross
Point, page 143 for additional programming requirements to program the Cross Point Timer.
If an abort window delay is needed for the cross zone alarms, all cross zone points in the
group must have P## Alarm Abort (refer to Section P## Alarm Abort, page 145) set to Yes.
NOTICE!
The Cross Point function applies only to Instant Alarm conditions. It does not apply to Trouble
or Supervisory conditions.
Cross zones have the ability to individually protect the intended area (e.g. motion detectors,
which overlap).
For SIA CP-01 Compliance:
P## Cross Point can be set to Yes or No.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to Yes for all
applicable Fire points.
Use this option to make a 24-hour point a Fire point. This option makes this point the highest
priority event in the control panel when an alarm occurs for both reporting and displaying on
the keypad. Refer to Characteristics of a Fire Point Section 5.2 Point Responses, page 132.
NOTICE!
You should dedicate a fire annunciation device to all your Fire points if they are assigned to a
single area in a multiple area system. Special red keypads and annunciators with specific keys
for fire systems are designed for this type of application (D1256RB and D1257RB).
NOTICE!
Do not use the Cross point function for Fire points.
P## Resettable
Use this option if this is a Powered point that requires interruption of power to reset a latched
alarm condition. The Resettable point option is typically used with smoke detectors and glass
break detectors.
When initiated (either through a Fire Walk Test or the keypads Reset Sensor? function) or
when the remote programming software (RPS) interrupts power to the device for 5 sec, a
Sensor Reset report is sent to the central station receiver.
NOTICE!
When a sensor reset occurs, the control panel does not accept alarms from any points with
P## Resettable programmed as Yes. During the 5-sec reset time, alarms from these points are
ignored.
Do not mix fire and intrusion devices on the same powered loop.
NOTICE!
Point number 128 is reserved for supervising Zonex 1.
Point number 248 is reserved for supervising Zonex 2 (D9412GV4).
Default: 1
Selection: 1 to 32 for D9412GV4
1 to 8 for D7412GV4
1 to 4 for D7212GV4
Select the area number to which the point is assigned.
P### Debounce
Default: 2
Selection: 1 to 15
1 .300 sec
2 .600 sec
3 .900 sec
4 1.2 sec
5 1.5 sec
6 1.8 sec
7 2.1 sec
8 2.4 sec
9 2.7 sec
10 3.0 sec
11 3.3 sec
12 3.6 sec
13 3.9 sec
14 4.2 sec
15 4.5 sec
The debounce count is the number of times the control panel scans a point before generating
an alarm. Scan cycles are 300 ms.
For appropriate settings consult the manufacturers instructions for the device connected to
this point.
NOTICE!
Use an entry of two or higher. Interior Follower points need a Debounce value of at least
three.
NOTICE!
Door points assigned to D9210C modules need a Debounce value of at least four (D9412GV4
and D7412GV4).
NOTICE!
P### debounce does not apply to wireless points.
Faults Relay
Relay Code D8129 on Zonex Bus 2 D8129 on Zonex Bus 2 D8129 on Zonex Bus 1
for D9412GV4* for D9412GV4* for D7412GV4*
1 73 9 9
2 74 10 10
3 75 11 11
4 76 12 12
5 77 13 13
6 78 14 14
7 79 15 15
8 80 16 16
* Address setting = 1 (on), 2 (off), 3 (on), 4 (on)
Table 5.2 P## Relay Codes
NOTICE!
Do not assign a relay to Invisible points. To avoid activating one of the associated relays,
program this prompt as 0.
NOTICE!
Two relays can activate when this point enters into alarm if the P## Relay Response Type for
this point is programmed.
Use these codes to activate relays on the D8129 OctoRelay (or C8137 Transmitter Interface).
You can assign the same code to several points providing a summary zone alarm output. When
the point enters into alarm, the relay activates. When the alarm is acknowledged and is no
longer scrolling in the keypad display, the relay resets.
P### RFID
Default: 0
Selection: 0 to 99999999
A point RFID can be Auto-Learned through the SDI2 bus RF receiver, or it can be entered here.
Auto-Learned RFIDs can be edited for point replacement, or can be set to 0 to disable a RF
point. A RFID (Radio Frequency device IDentification number) is a unique number assigned to
a wireless device at the factory. It provides a unique way for the Wireless Receiver and
Wireless Repeaters to identify what device is transmitting.
NOTICE!
Use the Cross Point function on non-fire points only.
The Cross Point option reduces false alarms. Points can be programmed so that the control
panel needs to see an Alarm condition within a programmed period of time (called Cross
Point Time) from at least two points within a Cross Point Group (Table 38) before Cross Point
Alarm Events are generated. These points must have P## Cross Point set to Yes to generate
this event.
There are 31 Cross Point Groups in the D9412GV4 and ten in the D7412GV4. Each Cross Point
Group consists of eight points and is identified by the point numbers in them (for example,
Cross Points 1 to 8, Cross Points 9 to 16, and so on). The maximum number of points that can
be programmed to meet the Cross Point criteria is two. Point numbers from different Cross
Point Groups do not affect each other. Refer to Table 5.3, Page 151 for a complete listing of
Cross Points comprising each Cross Point Group.
When any point with P## Cross Point set to Yes detects an alarm condition, the control panel
starts a timer as programmed in the Cross Point Time prompt.
If a second Cross Point within the same Cross Point Group detects an alarm condition, the
control panel creates a Cross Point Alarm Event for both points, provided both points activate
inside the Cross Point Window. A Cross Point is considered to be in alarm when it meets the
criteria for Instant Alarm response. The Cross Point index must have P## Pt Response set to a
value that generates an instant alarm response.
If a single Cross Point detects an alarm and stays faulted throughout the duration of the Cross
Point Window, a standard Alarm Report is generated for that point.
Conversely, if a single Cross Point detects an alarm, then restores, and no other conditions
occur, an Unverified Event is generated for that point. A second alarm on the first point does
not create an Alarm Event but rather an Unverified Event.
Default 20 sec
Selection: 5 sec to 255 sec
The Cross Point Time is the duration of the cross point window or the amount of time the
control panel waits for a second point within the same cross point group to fault before
generating an Cross Zone Alarm event. If a second point is not faulted within the Cross Point
Time, then a Burglar Alarm event is generated. Refer to Table 5.3, Page 151 for Cross Point
Group assignments.
Default: 31
Selection: 0 to 31
This entry selects one of the 31 P## Index codes that define how the control panel reacts
when a COMMAND 7 is initiated.
NOTICE!
The point index code used for COMMAND 7 must not be used for any other points on the
system.
NOTICE!
If the point index for COMMAND 7 has Fire points programmed as Yes, this causes access
control doors to unlock if Fire Unlock is also programmed as Yes.
CMD7 Relay
Default: 0
Selection: 0 to 8
This entry selects a relay (73 to 80 for the D9412GV4 or 9 to 16 for the D7412GV4 and
D7212GV4) when COMMAND 7 is initiated (refer to the Section P### Relay Codes/Relays,
page 148 for relay number association).
NOTICE!
COMMAND 7 does not activate the Summary Fire Alarm relay.
Default: COMMAND 7
Selection: Up to sixteen alphanumeric characters
Enter alphabetic characters A to Z in capital letters.
Enter up to sixteen characters of text to describe the point. This point text appears at keypads
(if the point is programmed as visible) and sent to the D6500 or D6600 when transmitting in
Modem IIIa2 format (if it is a reporting point).
Default: 31
Selection: 0 to 31
This entry selects one of the 31 P## Index codes that define how the control panel reacts
when a COMMAND 9 is initiated.
NOTICE!
The point index code used for COMMAND 7 and COMMAND 9 must not be used for any other
points on the system.
NOTICE!
If the point index for COMMAND 9 has Fire points programmed as Yes, this causes access
control doors to unlock if Fire Unlock is also programmed as Yes.
CMD9 Relay
Default: 0
Selection: 0 to 8
This entry selects a relay (73 to 80 for the D9412GV4 or 9 to 16 for the D7412GV4 and
D7212GV4) when COMMAND 9 is initiated (refer to Section P### Relay Codes/Relays,
page 148 for relay number association).
NOTICE!
COMMAND 9 does not activate the Summary Fire Alarm relay.
Default: COMMAND 9
Selection: Up to sixteen alphanumeric characters
Enter alphabetic characters A to Z in capital letters.
Enter up to sixteen characters of text to describe the point. This point text appears at keypads
(if the point is programmed as visible) and sent to the D6500 or D6600 when transmitting in
Modem IIIa2 format (if it is a reporting point).
6 Schedules (Skeds)
6.1 Windows
Use this programming module to define the windows for Opening and Closing and User
Access.
Windows
W# Sunday
Default: No
Selection: Yes or No
Yes Activate this window on Sundays.
No Do not activate this window on Sundays.
This prompt and the next six day-of-the-week prompts select the days of the week the
Opening and Closing windows are active.
Exceptions:
To prevent the windows from activating on certain days of the year, program Xept Holiday as
Yes, and enable at least one Holiday Index. When Xept Holiday is Yes, the window executes
on the days of the week programmed unless the Holiday Index designates the date as a
holiday.
If Opening and Closing Windows are only needed on certain days of the year, do not program
the windows to execute on any days of the week. Instead, program Xept Holiday as No and
select a Holiday Index with the days of the year you want the window to be active.
W# Monday
Default: No
Selection: Yes or No
W# Tuesday
Default: No
Selection: Yes or No
W# Wednesday
Default: No
Selection: Yes or No
W# Thursday
Default: No
Selection: Yes or No
W# Friday
Default: No
Selection: Yes or No
W# Saturday
Default: No
Selection: Yes or No
W# Open Early Begin
Default: 00:00
Selection: HH:MM (hours and minutes)
00:00 to 23:59
Open Early Begin: This program item is one of three required to create an Opening Window.
To finish programming an Opening Window, Open Window Start and Open Window Stop must
be programmed.
The time programmed in the W# Open Early Begin field is the earliest time that the user is
allowed to open an area before the Opening Window Start time. If Opening and Closing
Reports are enabled, disarming the area between midnight and the open Early Begin time
generates an Opening Report.
If A# Disable O/C in Window is set to Yes and the area is disarmed between the Open
Early Begin time and the Open Window Start time, the Opening event is sent with an
Early to Open modifier. If the Open Early Begin time is the same as the Open Window
Start time, no Opening Event is sent.
If Disable O/C in Window is set to No and the area is disarmed at any time, an Opening
Event is sent without an Early to Open or Late to Open modifier.
Disarming the area between the Open Window Start and open Window Stop times creates a
local event in the control panel event log, but does not send the Opening Report to the central
station.
Disarming the area between the Open Window Stop time and before the next windows Open
Early Begin time (or midnight, whichever is earlier) generates an Opening Event with a Late to
Open modifier.
When configuring multiple windows to operate on the same day, ensure that they are added
to the system in chronological order. For example, if three windows are programmed to
execute on Tuesday, Window 1 (W1) must occur before Window 2 (W2), and Window 2 must
occur before Window 3 (W3).
NOTICE!
Avoid programming the Open Early Begin time before a time that is between another
windows Open Window Start and Open Window Stop times.
NOTICE!
Do not program a window to cross the midnight boundary.
Disabled windows have a beginning time of 00:00. If the entry for this prompt is 00:00, but
times are programmed for Open Window Start and Open Window Stop, the window is
disabled.
To disable the window, all hours and minutes spaces must be 00:00.
NOTICE!
Make time entries using a 24-hour clock. For example:
Midnight is entered as 00:00
7:00 AM is entered as 07:00
2:45 PM is entered as 14:45
11:59 PM is entered as 23:59
Reboot the control panel to activate todays window, if the window needs to activate on the
same day you program it.
Default: 00:00
Selection: HH:MM (hours and minutes)
Enter the time you want the control panel to start the Opening Window. The window goes into
effect at the beginning of the minute.
NOTICE!
Make time entries using a 24-hour clock. For example:
Midnight is entered as 00:00
7:00 AM is entered as 07:00
2:45 PM is entered as 14:45
11:59 PM is entered as 23:59
This program item is one of three required to create an Opening Window. To program an
Opening Window, Open Early Begin and Open Window Stop must also be programmed. Refer
to Section W# Open Early Begin, page 155 for explanations of report features.
Default: 00:00
Selection: HH:MM (hours and minutes)
Enter the time you want the control panel to end the Opening Window. The window stops at
the end of the minute.
Figure 6.1 Example Opening Window Timeline (Using Two Opening Windows on the Same Day)
Callout Description
1 Areas disarmed between midnight and 6 AM generate Opening Reports.
2 Areas disarmed between 6 AM and 7 AM generate Early to Open Reports.
3 If the area is disarmed between 7 AM and 8 AM regular Opening Reports are
generated. If Disable O/C in Window is programmed Yes the Opening Report is not
sent to the central station.
4 If the area is not disarmed by 8:01 AM, a Fail to Open Event is generated if Fail to
Open is programmed Yes in Opening and Closing Options.
5 If the user disarms the area between 8:01 AM and 12:59, PM a Late to Open Event
is generated.
6 Areas that are disarmed between 1 PM and 2 PM generate Early to Open Reports.
7 If the area is disarmed between 2 PM and 3 PM regular Opening Reports are
generated. If Disable O/C in Window is programmed Yes, the Opening Report is not
transmitted to the central station.
8 If the area is not disarmed by 3:01 PM, a Fail to Open Event is generated if Fail to
Open is programmed Yes in Opening and Closing Options.
9 If the user disarms the area between 3:01 PM and 11:59 PM, a Late to Open Event
is generated.
NOTICE!
Make time entries using a 24-hour clock. For example:
Midnight is entered as 00:00
7:00 AM is entered as 07:00
2:45 PM is entered as 14:45
11:59 PM is entered as 23:59
This program item is one of three required to create an Opening Window. To program an
Opening Window, Open Early Begin and Open Window Start must also be programmed.
If the area is not disarmed by the time the Open Window Stop time expires, the control panel
generates a Fail to Open Report if A# Fail to Open is enabled in Area-Wide Parameters.
Opening Reports generated between the Open Window Start time and Open Window Stop
time can be suppressed by programming A# Disable O/C in Window as Yes. Refer to
Section W# Open Early Begin, page 155 for additional explanations of report features.
NOTICE!
Do not use a time of 23:59 as a window stop time unless another window begins on the next
day at 00:00.
Fail to Open Reports are not sent for windows that stop at 23:59.
Figure 6.2 Programming for Two Same Day Opening Windows (refer to Figure 6.1, Page 157)
Do not program a single window to cross the midnight boundary. The window stop time must
be later than the window start time. To program a window that effectively crosses the
midnight boundary, you must program two windows.
For example, to program windows for an area that opens between 11:30 PM and 12:30 AM,
five days a week, use two windows as shown in Figure 6.3.
Default: 00:00
Selection: HH:MM (hours and minutes)
00:00 to 23:59
Close Early Begin: This program item is one of three required to create a Closing Window. To
finish programming a Closing Window, Close Window Start and Close Window Stop must be
programmed.
The time programmed in the Close Early Begin field is the earliest time the user can close an
area before the Closing Window Start time. If Opening and Closing Reports are enabled,
arming the area between midnight and the Close Early Begin time generates a Closing Report.
Additionally:
If A# Disable O/C in Window is set to Yes and the area is armed between the Close Early
Begin time and the Close Window Start time, the Closing Event is sent with an Early to
Close modifier. If the Close Early Begin time is the same as the Close Window Start time,
no Closing Event is sent.
If A# Disable O/C in Window is set to No and the area is armed at any time, a Closing
Event is sent without the Early to Close or late to Close modifiers.
Arming the area between the Close Window Start and Close Window Stop times creates a
local event in the control panel event log, but does not send the Closing Report to the central
station.
Arming the area after the Close Window Stop time and before the next windows Close Early
Begin time (or midnight, whichever is earlier) generates a Closing Event with a Late to Close
modifier.
When configuring multiple windows to operate on the same day, ensure that they are added
to the system in chronological order. For example, if three windows are programmed to
execute on Tuesday, Window 1 (W1) must occur before Window 2 (W2), and Window 2 must
occur before Window 3 (W3).
NOTICE!
Avoid programming the Open Early Begin time before a time that is between another
windows Open Window Start and Open Window Stop times.
Disabled windows have a beginning time of 00:00. If the entry for this prompt is 00:00, but
times are programmed for Close Window Start and Close Window Stop, the window is
disabled.
To disable the window, both the hours and minutes spaces must be 00:00.
00:00 is midnight, 23:59 is 11:59 PM. Make entries using a 24-hour clock (for example, 7:00
AM is entered as 07:00, 2:45 PM is entered as 14:45).
If the window must activate on the same day as it is programmed, reboot the control panel to
activate the window immediately.
Default: 00:00
Selection: HH:MM (hours and minutes)
Enter the time that you want the control panel to start the Closing Window. The window goes
into effect at the beginning of the minute.
00:00 is midnight, 23:59 is 11:59 PM. Make entries using a 24-hour clock (for example, 7:00
AM is entered as 07:00, 2:45 PM is entered as 14:45).
This program item is one of three required to create a Closing Window. To program a Closing
Window, Close Early Begin and Close Window Stop must also be programmed.
If the area is not armed when the Close Window Start time comes, a warning tone sounds and
PLEASE CLOSE NOW appears at the keypad. To temporarily silence the tone, press the [ESC]
key on the keypad. The warning tone restarts in 10 min if the area is not armed.
Refer to Section W# Close Early Begin, page 158 in this section for explanations of report
features.
Default: 00:00
Selection: HH:MM (hours and minutes)
Enter the time that you want the control panel to end the Closing Window. The window stops
at the end of the minute.
00:00 is midnight, 23:59 is 11:59 PM. Make entries using a 24-hour clock (for example, 7:00
AM is entered as 07:00, 2:45 PM is entered as 14:45).
This program item is one of three required to create a Closing Window. To program a Closing
Window, Close Early Begin and Close Window Start must also be programmed.
If the area is not armed by the time the Close Window Stop time expires, the control panel
generates a Fail to Close Report if enabled in Fail To Close.
Closing Reports generated between the Close Window Start time and Close Window Stop
time can be suppressed by programming Disable O/C in Window as Yes. Refer to Section W#
Close Early Begin, page 158 for other explanations of report features.
Do not use a time of 23:59 as a window stop time unless the window continues on the next
day at 00:00. Fail to Close Reports are not sent, and the Auto Close feature does not work for
windows that stop at 23:59.
Do not program a single window to cross the midnight boundary. The window stop time must
be later than the window start time. To program a window that effectively crosses the
midnight boundary, you must program two windows.
For example, to program windows for an area that closes between 11:30 PM and 12:30 AM,
five days a week, use two windows as shown in Figure 6.5, Page 161.
Figure 6.4 Programming Example: Linking Two Closing Windows over Midnight
W# Xept Holiday
Default: No
Selection: Yes or No
Yes Do not activate this window on holidays.
To use this selection, the window must be programmed to activate on
at least one day of the week and a Holiday Index must be enabled.
No A holiday does not prevent this window from activating.
You also use this selection if Opening or Closing Windows are needed
only on certain days of the year. Do not program the windows to
execute on any days of the week. Instead, program Xept Holiday as No,
and select at least one Holiday Index with the days of the year you want
the window to be active.
Determine if the window is disabled on holidays, or is active only on holidays.
To prevent the windows from activating on certain days of the year, program Xept Holiday as
Yes, and enable at least one Holiday Index. When Xept Holiday is programmed as Yes, the
window executes on the days of the week programmed unless the date is designated as a
Holiday by the Holiday Index(es) selected.
Holiday Indexes for O/C Windows
You can enable up to four Holiday Indexes for use with Opening/Closing Windows. Enable at
least one Holiday Index if W# Xept Holiday is programmed as Yes for this window, or if you
want this window to activate only on specific dates. Holidays are programmed in
Section 6.3 Holiday Indexes, page 173.
W# Holiday 1
Default: No
Selection: Yes or No
Yes Use Holiday Index 1 with this window.
No Do not use Holiday Index 1 with this window.
W# Holiday 2
Default: No
Selection: Yes or No
Yes Use Holiday Index 2 with this window.
No Do not use Holiday Index 2 with this window.
W# Holiday 3
Default: No
Selection: Yes or No
Yes Use Holiday Index 3 with this window.
No Do not use Holiday Index 3 with this window.
W# Holiday 4
Default: No
Selection: Yes or No
Yes Use Holiday Index 4 with this window.
No Do not use Holiday Index 4 with this window.
Default: No
Selection: Yes or No
Yes Activate the window in the area number (#) specified.
No Disable the window in the area number (#) specified.
Eight separate program items determine whether a particular window activates in each of the
eight areas of the control panel.
User Window
Default: 1
Selection: 1 to 8
Enter the number programmed for the group of users in the U### User Group prompt. This
group has its user passcodes enabled or disabled when this window runs.
NOTICE!
A User Group can be assigned to more than one window in a 24-hour period, but the windows
must not overlap or exceed the midnight boundary.
UW# Sunday
Default: No
Selection: Yes or No
This prompt, and the next six day of the week prompts, select the days of the week that the
User Group Window is active.
NOTICE!
Refer to Section W# Sunday, page 154 for more information about programming this prompt.
UW# Monday
Default: No
Selection: Yes or No
UW# Tuesday
Default: No
Selection: Yes or No
UW# Wednesday
Default: No
Selection: Yes or No
UW# Thursday
Default: No
Selection: Yes or No
UW# Friday
Default: No
Selection: Yes or No
UW# Saturday
Default: No
Selection: Yes or No
UW# Group Enable Time
Default: 00:00
Selection: HH:MM (hours and minutes)
NOTICE!
This prompt must be programmed if this User Group Window is assigned to a user group.
Enter the time of day when the window starts. Beginning at this time, users assigned to this
windows group can use their passcodes. The window goes into effect at the beginning of the
minute. Make entries using a 24-hour clock (for example, 7:00 AM is entered as 07:00, 2:45
PM is entered as 14:45).
If the window must activate on the same day that you program it, reboot the control panel to
activate it immediately.
Default: 00:00
Selection: HH:MM (hours and minutes)
NOTICE!
This prompt must be programmed if this User Group Window is assigned to a user group.
Enter the time of day when the window ends. This time marks the end of the period in which
users assigned to this windows group can use their passcodes. The window stops at the end
of the minute. Make entries using a 24-hour clock (for example, 7:00 AM is entered as 07:00,
2:45 PM is entered as 14:45).
To disable the window, set the time to the default (00:00).
Do not program a single window to cross the midnight boundary. The window stop time must
be later than the window start time.
Default: No
Selection: Yes or No
Determine if the window is disabled on holidays, or is active only on holidays. Use the
instructions provided in the Section W# Xept Holiday, page 160W# Xept Holiday prompt 115.
Default: No
Selection: Yes or No
Yes The selected holiday index can be used by users in the User Group
window.
No The selected holiday index does not apply to users in this User Group.
Determine if the window is disabled on holidays, or is active only on holidays. Use the
instructions provided in Section W# Xept Holiday, page 160.
Sked Number
S## TimeEdit
Default: Yes
Selection: Yes or No
Yes The user can edit the time of this sked from the keypad and determines
if this sked appears in the CHG SKED display.
No The user cannot edit the time of this sked from the keypad and the sked
does not appear in the CHG SKED display.
Select whether the user can edit the time of this sked from the keypad.
4 Unbypass a Point: This function emulates the S## Point Number Blank (0) No point is
Unbypass Pt? keypad function. The entry in Default: Blank 1 to 127, unbypassed.
the S## Point Number prompt defines the Selections: Blank, 1 to 127, 129 to 247 Point to unbypass.
point this sked unbypasses. The sked can 129 to 247 for D9412GV4,
unbypass one point. 1 to 75 for D7412GV4, 1 to
40 for D7212GV4
Enter the number of the
point the sked unbypasses.
5 Unbypass All Points: This function is not S## Area 1[through #] Yes Unbypass all
available as a keypad function. The entry in Default: No No points in Area #.
the S## Area # prompt defines the area(s) Selection: Yes or No Do not unbypass
where the sked unbypasses all points. The Select Yes to unbypass all all points in Area
sked unbypasses all points in the area, points in the areas #.
regardless of how they were bypassed. This indicated.
sked can unbypass all points in multiple areas.
6 Relay On: This function emulates the Change S## Relay Number Blank No relay is
Relay keypad function to turn relays on. The Default: Blank 1 to 128 activated.
entry in the S## Relay Number prompt Selections: Blank, 1 to 128 Relay to activate.
defines the specific relay this sked activates. for D9412GV4, 1 to 64 for
The sked can activate one relay. D7412GV4, 1 to 24 for
D7212GV4
Enter the number of the
relay the sked activates
7 Relay Off: This function emulates the Change S## Relay Number Blank No relay is turned
Relay? keypad function to turn relays off. The Default: Blank 1 to 128 off.
entry in the S## Relay Number prompt Selections: Blank, 1 to 128 Relay to turn off.
defines the relay this sked turns off. The sked for D9412GV4, 1 to 64 for
can turn off only relays that are set by a sked. D7412GV4, 1 to 24 for
The sked can turn off one relay. D7212GV4
Enter the number of the
relay that turns the sked off.
8 All Relays Off: This function is not available as a keypad function. This sked function turns off all relays that
are turned on by a sked. This is a panel-wide function.
No other parameters require input for this option.
9 Test Report: This function emulates the Test S## Defer Test Yes Defer the Test
Report? sub-function of the Send Report? Default: No No Report.
keypad function ([COMMAND][4][1]). This Selection: Yes or No Send the Test
function generates a Test Report only from Enable sked to defer the Report on
Area 1 but contains panel-wide status Test Report schedule.
information. The report is sent to the
phone(s) programmed for Test and Status S## Hourly Report Yes
Reports in Section 2.3.8 Communication Default: No No
Attempts 20. Selection: Yes or No Send the Test
If Expand Test Report in Phone parameters is Select Yes to send the Test Report every hour.
programmed as Yes, the Test Report also Report every hour. Send the Test
includes all off-normal states for events listed Report only as
in Test Reports (refer to scheduled.
Section Table 3.9 Test Reports, page 36) and
some events listed in Diagnostic Reports
(refer to the footnotes with Table 3.10,
Page 37)
The Test Report can be deferred for up to 24
hours if any other report was sent since the
last Test Report. To defer the Test Report,
program S## Defer Test.
The Test Report can be sent every hour
beginning at the time scheduled in S## Time.
To send a Test Report every hour, program
S## Hourly Report.
Note:
To meet UL 864 requirements (D9412GV4 and
D7412GV4), use the Sked function to meet
the daily Test Report requirement.
10 Status Report: This function generates a S## Defer Status Yes Defer the Status
Status Report for each area that is enabled. Default: No No Report.
The report is sent to the phone(s) Selection: Yes or No Send the Status
programmed for Test and Status Reports in Enable sked to defer the Report on
Routing. Status Report. schedule.
The Status Report can be deferred for up to
24 hours if any other report was sent since
the last Status Report. To defer the Status
Report, program S## Defer Status.
11 Execute Custom Func: This function emulates S## Cmd Center Blank (0) No keypad is
any of the custom functions assigned to the Default: Blank (0) specified for
keypad that can be executed by a user from Selections: Blank (0), 1 to Custom Function
the keypad. When a sked executes a custom 8 activation.
function, it is subject to the scope of the Identify the specific keypad 1 to 8
selected keypad. Cmd Center and Custom (CC #) where the Custom Command center
Func prompts appear after entering Function Function is entered. Only (keypad) address
Code 11. Both entries are required. one keypad can be assigned specified for
for this sked function. Custom Function
activation.
S## Custom Func
Default: Blank (0) Blank (0)
Selections: Blank (0), 128
to 143 for D9412GV4, 128 128 to 143 No Custom
to 131 for D7412GV4 and Function is
D7212GV4 activated.
Enter the custom function Custom Function
this sked executes. to activate.
12 Contact RPS: This function attempts to
contact an Unattended RPS at the configured
time. The control panels account in RPS
controls the operations performed upon
successful contact.
CAUTION!
Avoid having multiple functions occur at the same time at the same address. Functions can
clash and the effect on the control panel is unpredictable.
NOTICE!
Ensure that the Custom Function being executed or any of the commands nested inside the
Custom Function are not passcode protected.
NOTICE!
Do not program multiple skeds to execute at the same keypad during the same time.
Do not program skeds to execute at times when a user is likely to be executing functions at
the keypad. If it is necessary to do so, there are two ways to work around the situation:
For a D1255 keypad type, program "C","C"at the beginning of the Custom Function Key
Strokes entry. This aborts the users function and allows the sked to execute.
Program the sked to execute at an address (Command Center) with no keypad physically
attached to it. The CC # must be assigned to an area and have the appropriate scope
programmed.
Default: 0
Selection: 0 to 24, 28, 29
13 Adjust Time Forward One Hour:This sked function is used to make adjustments to the control panels clock. A
typical application is to program this to go into effect at 2:00 AM on the date that Daylight Saving Time begins
(during the springtime). No Time Change Report is sent or logged, but the new time appears in the next report
logged.
No other parameters require input for this option.
14 Adjust Time Backward One Hour: This sked function is used to make adjustments to the control panels clock.
A typical application is to program this to go into effect at 2:00 AM on the date that Daylight Saving Time ends
(during the fall). This function can operate only once in a day, even if multiple Skeds with this function are
programmed. No Time Change Report is sent or logged, but the new time appears in the next report logged.
There are no other parameters that require input for this option.
15 Sound Watch Tone at Command Center S## Cmd Center 1 Yes Watch tone sounds at
(Keypad): This function sounds the Watch [through 16] this keypad.
Tone at the keypad address programmed Default: Blank
in Parameter 1. The Watch Tone sounds at Selections: Yes or No No Watch tone does not
all keypads with the address programmed. Enable the sked to beep sound at this keypad.
Press [ESC] to silence the tone. the keypad programmed
Sound Watch Tone defines the keypad Yes.
address where the Watch Tone sounds.
Enter the specific address at the S## Cmd
Center prompt.
16 Access Control Level On: (D9412GV4 and S## Access Ctl Level # Yes Enable Access Control
D7412GV4) This function emulates the Default: No for indicated authority
ACCESS CMD LEVEL command that Selection: Yes or No No levels.
determines whether a users token or card Activate a sked, which Do not enable Access
level is ENABLED?, allowing access enables the Access Control for indicated
granted rights. This affects all doors that Level(s) 1 through 14 authority levels.
this user is assigned to with this specific with Yes.
authority level.
NOTICE!
The D9412GV4 supports eight doors; the D7412GV4 supports two doors.
NOTICE!
To regulate a users access for certain doors, assign the user a different authority level # with
the same authority functions enabled. For example, a user can be assigned Authority Level 1
for Door 1 and Authority Level 2 for the remaining doors. You can enable or disable Authority
Level 1 for Door 1 without affecting his authority level for Doors 2 through 8).
Default: 0
Selection: 0 to 24, 28, 29
17 Access Control Level Off: (D9412GV4 and S## Access Ctl Level # Yes Turn off access for
D7412GV4) This function emulates the Default: No indicated authority
ACCESS CMD LEVEL command that Selections: Yes or No No levels.
determines whether a users token or card Enables the sked to Do not turn off access for
level is disabled. This function allows access turn off access for indicated authority
to be turned off for the levels programmed. Levels 1 through 14. levels.
18 Unlock Door: (D9412GV4 and D7412GV4) S## Door 1 [through 8] Yes Unlock Door #.
This function emulates the UNLOCK? Default: No Do not unlock Door #.
12345678 keypad function for unlocking a Selection: Yes or No No
door. Enable the sked to
unlock the doors
programmed Yes.
19 Secure Door: (D9412GV4 and D7412GV4) S## Door 1 [through 8] Yes Secure Door #.
This function emulates the SECURE? Default: No
12345678 keypad function for securing a Selection: Yes or No No Do not secure Door #.
door. Enable the sked to
unlock the doors
programmed Yes to the
secured state.
20 Lock Door: (D9412GV4 and D7412GV4) This S## Door 1 [through 8] Yes Lock Door #.
function returns an unlocked (Function 18) or Default: No
secured (Function 19) door to a normal Selection: Yes or No No Do not lock Door #.
locked door state. Enable the sked to lock
the doors programmed
as Yes and return them
to the normal Door
Mode.
21 Access Authority Events On: (D9412GV4 and S## Door 1 [through 8] Yes Enable the sending of
D7412GV4) The control panel can log Access Default: No Access Granted Events
Granted Events when a valid token, RTE, REX, Selection: Yes or No for Door #.
or Unlock Door event is detected for a This parameter enables
specific door. These events can be directed to the sending of Access No Do not enable the
print at a local printer or send a report Granted Events for Door sending of Access
remotely through phone routing. This sked #. Granted Events for Door
enables Access Granted Events to be #.
reported for Door #.
22 Access Authority Events Off: (D9412GV4 and S## Door 1 [through 8] Yes Disable the sending of
D7412GV4) The control panel can log Access Default: No Access Granted Events
Granted Events when a valid token, RTE, REX, Selection: Yes or No for Door #.
or Unlock Door Event is detected for a This parameter disables
specific door. These events can be directed to the sending of Access No Do not disable the
print at a local printer or send a report Granted Events for Door sending of Access
remotely through phone routing. This sked #. Granted Events for Door
disables Access Granted Events to be #.
reported for Door #.
23 No Entry Events On: (D9412GV4 and S## Door 1 [through 8] Yes Enable the sending of No
D7412GV4) The control panel can log No Default: No Entry Events for Door #.
Entry Events when an invalid token is Selection: Yes or No
detected for a specific door. No Entry Events This parameter enables
include No Entry-Secured, No Entry-Interlock, the sending of No Entry No Do not enable the
No Entry-Unknown ID, and No Entry-Level. Events for Door #. sending of No Entry
These events can be directed to print at a Events for Door #.
local printer or send a report remotely
through phone routing. This sked enables No
Entry Events to be reported for Door #.
24 No Entry Events Off: (D9412GV4 and S## Door 1 [through 8] Yes Enable the reporting of
D7412GV4) The control panel can log No Default: No No Entry Events for Door
Entry Events when an invalid token is Selection: Yes or No #.
detected for a specific door. No Entry Events This parameter enables
include No Entry-Secured, No Entry-Interlock, the sending of No Entry No Do not enable the
No Entry-Unknown ID, and No Entry-Level. Events for Door #. reporting of No Entry
These events can be directed to print at a Events for Door #.
local printer or send a report remotely
through phone routing. This sked disables No
Entry Events to be reported for Door #.
28 Expanded Off-Normal Test Report: To generate this event, one or more points must be in an off-normal state
at the time the sked executes. In addition, any system trouble that is active also generates an Expanded Off-
Normal Test Report. Expanded Off-Normal Test Reports include the Off Normal Test Report Event as well as
the supplementary event at the time the report is generated.
The Event Log shows only a Test Report Event.
If none of these conditions exists at the time the sked executes, only a Sked Executed Event is generated and
the Off-Normal Test Report is not sent.
29 Non-Expanded Off-Normal Test Report: Non-Expanded Off-Normal Test Report Events are only sent when any
point is in the off-normal state from any area, but only sends the Off Normal Test Report Event. Any system
trouble that is active also generates a Non-Expanded Off-Normal Test Report.
The Event Log only shows a Test Report Event.
If none of these conditions exist at the time the sked executes, only a Sked Executed Event is generated and
the Non-Expanded Off-Normal Test Report is not sent.
Table 6.2
NOTICE!
To meet UL 864 daily Test Report requirements (when using two phone lines) (D9412GV4 and
D7412GV4), you must still use Sked Function Code 9, Test Report and program it to occur on
a daily basis as per AHJ requirements.
S## Time
Default: 00:00
Selection: HH:MM (hours and minutes)
Enter the time that the sked executes. Make entries using a 24-hour clock (for example, 7:00
AM is entered as 07:00, 2:45 PM is entered as 14:45).
Disabled skeds can have their time set to Disabled; however, to ensure that a sked is fully
disabled, enter [COMMAND][5][2] (Change Skeds function) and select DISABLE?
S## Date
Default: __/__
Selection: MM/DD (month and date)
Enter the date that the sked executes.
Disabled skeds have their date set to Disabled. If you receive from the control panel and the
entry for this prompt is Disabled, but dates were programmed before, the sked can be
disabled from the keypad using the Change Skeds function.
S## Sunday
Default: No
Selection: Yes or No
Yes Activate this sked on Sundays.
No Do not activate this sked on Sundays.
This prompt and the next six prompts select the days of the week when the sked is active.
Exceptions:
To prevent the sked from activating on certain days of the year, program Xept Holiday as Yes,
and enable at least one Holiday Index. When Xept Holiday is programmed as Yes, the window
executes on the days of the week programmed unless the date is designated as a holiday by
the Holiday Index selected.
If a sked is only needed on certain days of the year, do not program the sked to execute on
specific days of the week. Instead, program Xept Holiday as No, and select a Holiday Index
with the dates you want the window to be active.
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), program each day of the week to Yes for the required Test Report Sked.
S## Monday
Default: No
Selection: Yes or No
S## Tuesday
Default: No
Selection: Yes or No
S## Wedsday
Default: No
Selection: Yes or No
S## Thursday
Default: No
Selection: Yes or No
S## Friday
Default: No
Selection: Yes or No
S## Saturday
Default: No
Selection: Yes or No
S## Xept Holiday
Default: No
Selection: Yes or No
Yes Prevent this sked from operating on the holidays identified in the
specific Holiday Index(es) used with this sked. Specific Holiday Indexes
are selected in this programming section and programmed in the next
programming module.
No This sked operates on holidays programmed in the Holiday Index(es)
used with this sked.
If no days of the week are programmed, this sked operates only on the holidays programmed
in the Holiday Index(es) used with this sked. This sked also operates if the holiday falls on a
day of the week that is programmed.
S## Holiday #
Default: No
Selection: Yes or No
7 AUXPARM
7.1 Automation
Automation defines the characteristics of a serial interface module (SIM) when used with
home or business automation software. The SIM is a two-way SDI to a serial communication
module that allows the control panels to send and receive information to and from an external
software program.
NOTICE!
The SIM can be a D9133, DX4010V2, or DX4020 (configured to emulate serial
communication).
A DX4010i can be used only for programming.
This automation protocol allows external software programs to interact and perform functions
such as:
arming and disarming areas,
changing user passcodes and names, and
turning relays on and off.
The items described in this section allow some simple configuration options. To receive the
SIM automation protocol; however, you must contact Bosch Security Systems, Inc. Technical
Support at (888) 886-6189.
Supervise SDI 80
Default No
Selection: Yes or No
Yes Supervise the serial interface module (SIM).
No Do not supervise the serial interface module (SIM).
This item determines whether the serial interface module (SIM) at address 80 is supervised or
not. If the SIM is supervised, disconnecting the SIM from the control panel creates a Trouble
SDI 80 Event and the keypad annunciates a trouble tone (if programmed) and displays SERVC
SDI 80.
NOTICE!
Trouble SDI 80 Reports are always sent using the account number for Area 1.
Automation Device
Default None
Selection: SDI Address 80, SDI2 Address 1, SDI2 Address 2
None Disable Automation
SDI Address 80 Enables the automation address (SDI Address 80) for the DX4010V2 or
DX4010V2 Serial Interface Module, or DX4020 Network Interface
Module.
SDI2 Address 1 Enables automation and supervision using a B420 Ethernet
Communication Module at address 1 on the SDI2 bus.
SDI2 Address 2 Enables automation and supervision using a B420 Ethernet
Communication Module at address 2 on the SDI2 bus.
Status Rate
NOTICE!
If an SDI2 communication device is allocated for automation communication, then it cannot be
used for central station nor RPS communication.
Default 0
Selection: 0 to 255
0 Status information is sent only when requested.
1 to 255 Status information is sent at the interval programmed.
NOTICE!
If the Status Rate is set to a value less than 10, and 1 to 6 SDI devices are connected to the
system, the fastest the control panel can send the status information is in approximately 1
sec. If more than six SDI devices are connected to the control panel, the fastest the control
panel can send the information is in approximately 1.5 sec to 2 sec. .
This item determines how often the default status information is sent to the serial interface
module (SIM). The status information includes:
The current point status (normal or off-normal),
The control panels area status (Master Armed, Master Instant Armed, Perimeter Delay
Armed, Perimeter Instant Armed, Disarmed, Area Entry Delay, Perimeter Entry Delay, Area
Exit Delay, and Perimeter Exit Delay)
The control panel status (AC Fail, Battery Missing, AC Restore, Battery Low, and so on)
Relay status (relay on or relay off)
Entries are in 100 millisecond increments. If a 5 is entered, the status information is sent
every 500 milliseconds (or 0.5 sec). An entry of 10 equals 1 sec.
7.2 Miscellaneous
Fire Summary Sustain
Default Yes
Selection: Yes or No
Yes Forces the Summary Fire relay output to remain on after the Alarm
Silence command.
No Allows Summary Fire relay output to be silent when the Fire Alarm Bell
output is silenced and all Fire Points return to normal.
Use this parameter to set the Summary Fire relay output to continue or to stop after the Fire
Alarm Bell is silenced or times out. Refer to the Summary Fire prompt in Section 3.14.2 Panel-
Wide Relays, page 121.
Default 2
Selection: 0, 1, 2
0 The control panel sends a FIRE TROUBLE RESTORE when a Fire
Supervision point restores to normal.
1 The control panel sends a FIRE ALARM RESTORE when a Fire
Supervision point restores to normal.
2 The control panel sends a FIRE SUPERVISION RESTORE when a Fire
Supervision point restores to normal.
Determines how the control panel sends a Fire Supervision Restoral Event.
NOTICE!
The Fire Supervision Restore Event is part of Fire Events in Routing. If Fire Supervision
Restore Events are needed, simply enable them in Routing.
Default 10 min
Selection: 5 to 30 minutes
The programmed time is the maximum value of the Early Ambush Timer. When Early Ambush
is set to Yes for a specified area (refer to Section Early Ambush, page 76) and the area is
disarmed, the user has the amount of time programmed here to enter a second code into the
keypad.
If a second passcode is not entered within the programmed time, a Duress event is generated
based on the first user code. Duress reports must be enabled in Routing in order to be sent to
a central station.
Default 1
Selection: 0, 1, 2
0 Keypads do not re-sound the fire trouble tone.
1 Keypads re-sound the fire trouble tone at 12:00 PM if any Fire point that
falls within the scope of a keypad is in an off-normal condition.
2 Keypads re-sound the fire trouble tone at 12:00 AM if any Fire point that
falls within the scope of a keypad is in an off-normal condition.
Secondary Ambush Code
Default Unique
Selection: Unique or any
Unique The code used to end the timer must be different from the code used to
disarm the area.
Any The timer can be stopped using a different code, or the same code that
disarmed the area.
The Secondary Ambush Code determines whether the same passcode can be used to begin
and end the Early Ambush process.
Abort Window
Default 30 sec
Selection: 15 to 45 sec
This parameter determines the amount of time the control panel delays a Burglar Alarm event
from a point with P## Alarm Abort set to Yes. If an alarm silence operation is performed
before this time elapses, the alarm transmission is aborted and the keypad shows an optional
ALARM NOT SENT message. When an alarm transmission is successfully aborted, no event is
written to the control panel event log .
When an abort alarm timer starts, it does not stop until an alarm silence operation is
performed or the time expires.
NOTICE!
This feature does not apply to Fire Alarms or invisible point alarms.
NOTICE!
To meet UL requirements, the combined Entry Delay time and Abort Window time must not
exceed 60 sec. For Entry Delay time programming information, refer to Section P## Entry
Delay, page 134.
UL note: Maximum settings for residential use:
Exit Delay =120 sec
Entry Delay = 45 sec bell
Off-Premise Transmission = 60 sec
Maximum settings for commercial use:
Exit Delay = 120 sec no line security
Entry Delay = 60 sec bell
Off-Premise Transmission = 60 sec
The system must use both the bell and off-premise transmission.
Passcode Length
Default 0
Selection: 0, 3, 4, 5, or 6
0 Disabled; sets a variable length for user passcodes, allowing for
backward compatibility
3, 4, 5, or 6 Sets a fixed length to all user passcodes.
During entry delay, the code is accepted when the last digit is pressed to disarm the area.
For SIA CP-01 Compliance:
Passcode Length must be set to 3, 4, 5, or 6.
Swinger Count
Default 2
Selection: 1, 2, 3, or 4
1, 2 Number of fault or trouble bypasses allowed per hour for SIA CP-01
compliance.
3 Optional fault count
4 Value used for backward compatibility with previous control panel
operation.
When a point has P# Swinger Bypass set to Yes, the value set in Swinger Count determines
the number of times the point is faulted erroneously within an hour before it is automatically
bypassed.
For SIA CP-01 Compliance:
P## Swinger Bypass can be Yes or No. If P## Swinger Bypass is Yes, Swinger Count must be
1 or 2.
Remote Warning
Default No
Selection: Yes or No
Yes The system uses the Alarm Bell output to annunciate the arming and
disarming of an area through remote software, or a remote arming
device such as a key switch or keyfob.
No No remote warning occurs to annunciate the arming and disarming of
an area through remote software, or a remote arming device such as a
key switch or keyfob.
Upon remote arming, the output pulses on for 2 sec. Upon remote disarming, the output
pulses on, off, on, off for 2 sec each.
For SIA CP-01 Compliance:
Default No
Selection: Yes or No
Yes Set the clock time control on the control panel to the on-board crystal
frequency.
No Do not set the clock time control on the control panel to the on-board
crystal frequency.
When set to Yes, the control panel switches its clock time control from the traditional AC
frequency to the on-board crystal frequency.
Perimeter Relay
Default No
Selection: Yes or No
Yes Change the function of the area-wide fail-to-close relays to follow the
perimeter armed states of their areas.
No The area-wide fail-to-close relay operates normally.
When set to Yes, the A# Fail to Close relay becomes an area-wide perimeter armed relay. This
relay is activated when all areas assigned to the same relay have perimeter points that are
armed.
Default No
Selection: Yes or No
Yes Change activation of Area Armed or Perimeter Armed Relay to the
beginning of the exit delay time.
No Maintain the activation of Area Armed or Perimeter Armed Relay at the
end of the exit delay time.
When this prompt is set to Yes, the Area Armed or Perimeter Armed Relay activates at the
beginning of the exit delay time.
Default US Calendar
Selection: Disabled or US Calendar
Disabled The control panel clock is not adjusted for daylight saving time.
US Calendar The control panel clock is adjusted to the US start/end dates for
daylight saving.
8 SDI2 Modules
This section discusses programming for the modules that connect to the GV4 Series Control
Panel using the SDI2 bus.
Many devices on the SDI2 bus have a tamper input that you can optionally use to monitor the
devices enclosure cover or other tamper switch. This prompt has the same options and
purpose for all indicated SDI2 devices.
Enclosure Tamper
Default: No
Selection: Yes or No
Yes The control panel will monitor the tamper status of an SDI2 device and
report its state changes accordingly.
No The control panel will ignore any tamper state changes being sent by an
SDI2 device to the panel.
You can use one or both communication modules for central station reporting or RPS
communications. Optionally, you can use one of the B420 modules for communication with
automation software. While in this mode, you cannot use the module to communicate with
RPS nor with the central station.
RPS supports the configuration of the enclosure tamper on each of the Network Interface
Modules. Refer to Section Enclosure Tamper, page 179.
DHCP/AutoIP Enable
Default: Yes
Selection: Yes or No
DHCP is an auto configuration protocol that allows a computer to be automatically
configured, which eliminates the need for interaction by a network administrator. DHCP also
provides a central database that tracks computers that connect to the network, which
prevents two computers from accidentally being configured with the same IP address.
AutoIP enables dynamic IP addresses to be assigned to a device when the device is started
up. Whereas DHCP requires a DHCP server, AutoIP does not require a server when selecting
an IP address. A host configured with AutoIP receives an IP address of 169.254.xxx.xxx.
IPv4 Address
Default: 0.0.0.0
Selection: 0.0.0.0 to 255.255.255.255
A Domain Name Server (DNS) converts internet domain names or hostnames to their
corresponding IP addresses. When this is defined through the DHCP service, leave the default
value.
4. Press [ENT] at the IP ADDRESS option. The currently configured IP address shows. An
invisible editing cursor is enabled for the first byte.
5. The [PREV] button acts as a [Backspace] key. Press [PREV] to delete the characters of
the byte, and then enter the new byte numbers, or press [NEXT] to move to the next
byte.
NOTICE!
The keypad does not accept invalid byte numbers.
Default: 255.255.255.0
Selection: 0.0.0.0 to 255.255.255.255
This defines the sub-network class. When this is defined through the DHCP service, leave the
default value.
Default: 0.0.0.0
Selection: 0.0.0.0 to 255.255.255.255
This defines the address of the Internet or Intranet gateway. When this is defined through the
DHCP service, leave the default value.
Default: 0.0.0.0
Selection: 0.0.0.0 to 255.255.255.255
This This defines the address of the Doman Name Server (DNS). When this is defined through
the DHCP service, leave the default value.
NOTICE!
The keypad does not accept numbers 256 to 999.
Default: No
Selection: Yes or No
Yes The network module allows configuration to be sent from the network
through port 77FE.
No The network modules does not allow configuration to be sent from the
network through port 77FE.
Port number 77EE (hexadecimal code) is reserved for configuration of the B420 by the remote
application software.
UPnP Enable
Default: Yes
Selection: Yes or No
Yes UPnP is enabled
No UPnP is disabled
Universal Plug and Play (UPnP) allows devices to connect seamlessly and simplifies the
implementation of personal and corporate networks.
Default: 80
Selection: 1 to 65535
Use this option to configure the port number for the B420 web server.
Default: 600
Selection: 1 to 600 (in 1-sec increments)
When the B420 communicates with any device on a network, an entry is added to its ARP
table for each of those devices. The ARP Cache Timeout defines the number of seconds (1 to
600) before the ARP table of the B420 is refreshed.
Default: No
Selection: Yes or No
Yes All communication through the network module is encrypted. AES
encryption must also be set at the central station receiver and the PC
running RPS or automation software.
No All communication through the network module is unencrypted.
Use this option to enable or disable AES (Advanced Encryption Standard) encryption on the
B420.
Default: 01-02-03-04-05-06-07-08-09-10-11-12-13-14-15-16
Selection: Thirty-two hexadecimal characters
Use this option to select the ID that represents the AES Encryption Key to use to encrypt and
decrypt data blocks. Create the ID numbers in Remote Programming Software (RPS) using the
Encryption Key tab of the System Configuration dialog box.
4. Press [ENT] at the AES ENCRYPTION KEY option. If Encyption is disabled through RPS
or keypad programming, the keypad shows NO ENCRYPTION. If Encryption is enabled,
the default keypad value is NO ASSIGNED VALUE.
5. To change the setting, press [EDIT] and then enter the value using the number buttons.
6. Press [ENTER] to save the changes.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the Programming option.
2. Press [ENT] to enter the Programming option.
3. Press [ENT] at the Encryption option to enter it.
4. Press [ENT] at the AES Encryption Key option. If Encyption is disabled through RPS or
keypad programming, the keypad shows No Encryption. If Encryption is enabled, the
default keypad value is No Assigned Value.
5. To change the setting, press Edit softkey and then enter the value using the number
buttons.
6. Press the Save softkey to save the changes.
Default: No
Selection: Yes or No
Yes Web configuration is enabled
No Web configuration is disabled
When enabled, the B420 allows authorized users to view and modify its configuration
parameters through a standard web browser.
Default: B42V2
Selection: Four to ten alphanumeric characters
Use this parameter to authorize web access to the B420 Network Communication Module.
NOTICE!
The password can be programmed with up to sixteen alphanumeric characters, including: A to
Z, 0 to 9, ?, &, @, -, *, +, $, #, _, /. Characters not listed are invalid and cannot be used for text.
NOTICE!
To disable the password check, enter a space (using the [Spacebar] key), as the password.
Default: No
Selection: Yes or No
Yes Allows firmware upgrades to the B420 using the network.
No Prevents firmware upgrades.
Use this parameter to enable or disable firmware upgrades on the B420.
NOTICE!
Each display can be programmed with up to sixteen alphanumeric characters, including: A to
Z, 0 to 9, -. Characters not listed are invalid and cannot be used.
Default: Blank
Selection: Sixty-four alphanumeric characters
Keypad Programming of Unit Hostname
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the PROGRAMMING option.
2. Press [ENT] to enter the PROGRAMMING option.
3. Press [ENT] at the DNS PARAM option to enter it.
4. Press [ENT] at the MODULE HOSTNAME option. The currently configured hostname
shows. An invisible editing cursor is enabled for the first byte.
5. The [PREV] button acts as a [Backspace] key. The [COMMAND] key allows you to cycle
though the special passcode characters (A, B, C, D, E, F); the [NEXT] key selects the
passcode character.
6. Press [ENT] to save the changes.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the Programming option.
2. Press [ENTER] to enter the Programming option.
3. Press [ENTER] at the DNS Parameters option to enter it.
4. Press [ENTER] at the Module Hostname option. The current configured hostname shows.
5. To change the setting, press the Edit softkey. An invisible editing cursor is enabled.
6. Use the softkeys and the number buttons on the keypad to enter the new passcode. The
Backspace softkey allows you to erase characters. The Clear softkey allows you to clear
the entire passcode. When entering a letter character, press the letters softkey to select
it. The Previous and Next softkeys advance through the letter characters (A, B, C, D, E,
F).
7. Press the Save softkey to save the changes.
Unit Description
Use this parameter to create a unit description.
NOTICE!
The description can be programmed with up to sixteen alphanumeric characters, including: A
to Z, 0 to 9, ?, &, @, -, *, +, $, #, _, /.Characters not listed are invalid and cannot be used for
text.
Default: Blank
Selection: Twenty alphanumeric characters
Local Port Number
Default: 7700
Selection: 0 to 65535
Keypad Programming of Local Port Number
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the PROGRAMMING option.
2. Press [ENT] to enter the PROGRAMMING option.
Default: 45
Selection: 0 to 65 (in 1-sec increments)
IP Test Address
NOTICE!
Domain Name characters are in accordance with RFC 1123 Requirements for Internet Hosts --
Application and Support.
Default: 8.8.8.8
Selection: Twenty alphanumeric characters
This is the test address that the network module will use when the IP Diagnostics tests are
activated from the keypads Tools Menu. The network address in this prompt is decoded and
an ICMP ping message is sent during the test so set this to an address that allows this form of
communication. You can enter an intranet address if you do not wish the system to test an
external IP address. Refer to Section 8.3.1 IP Diagnostics Keypad Menu (B420), page 189 for
further details.
NOTICE!
For systems reporting over the internet, the test address can be set to a web server with fast
response time and high availability. This verifies that the Ethernet Communicator has at least
a limited internet connection outside the facility.
For all systems, including those that report only on private internal networks, the internet test
address can be pointed to a server or receiver in the central station. This will verify that the
Ethernet Communicator has at least a limited Ethernet connection to the specific site or
receiver to which reports will be sent. For example, receiver-01.your-company-domain.com.
D1255
1. Refer to Section 2.5.6 IP Diagnostics Menu, page 16 to access the TOOLS MENU and
navigate to the IP DIAGNOSTICS option.
2. Press [ENT] to enter the IP DIAGNOSTICS option.
3. At the B420 MOD 1-2 option, enter the number for the B420 module for which you want
to review the settings, and press [ENT].
4. Press [ENT] at the SETTINGS option. The keypad shows the Hostname.
5. Press [NEXT]. The keypad shows the MAC ID.
6. Press [NEXT]. The keypad shows the current IP address assigned to the module.
7. Press [ESC] when finished reviewing the settings.
D1260
1. Refer to Section 2.5.6 IP Diagnostics Menu, page 16 to access the Tools Menu and
navigate to the IP Diagnostics option.
2. Press the corresponding soft button to enter the IP Diagnostics option.
3. At the B420 Module 1-2 option, enter the number for the B420 module for which you
want to review the settings, and press [ENTER].
4. Press [ENTER] at the Settings option. The keypad shows the Hostname.
5. Press the Next soft button. The keypad shows the MAC ID.
6. Press the Next soft button. The keypad shows the address assigned to the module.
7. Press the Exit soft button when finished reviewing the settings.
Connection Test
NOTICE!
You must configure an IP Test Address in RPS to test the Internet function. If the IP Test
Address is not configured, the Internet test results in failure. Refer to Section IP Test Address,
page 188.
D1255
1. Refer to Section 2.5.6 IP Diagnostics Menu, page 16 to access the TOOLS MENU and
navigate to the IP DIAGNOSTICS option.
2. Press [ENT] to enter the IP DIAGNOSTICS option.
3. At the B420 MOD 1-2 option, enter the number for the B420 module for which you want
to review the settings, and press [ENT].
4. Press [ENT] at the CONNECTION TEST option. The keypad tests and shows the results
for:
Link. Tests the network cable connection, and responds with OK or FAILURE.
Gateway. Tests the connection to the gateway, and responds with OK or FAILURE.
Internet. Tests the network cable connection, and responds with OK or FAILURE.
D1260
1. Refer to Section 2.5.6 IP Diagnostics Menu, page 16 to access the TOOLS MENU and
navigate to the IP DIAGNOSTICS option.
2. Press the corresponding soft button to enter the IP Diagnostics option.
3. At the B420 Module 1-2 option, enter the number for the B420 module for which you
want to review the settings, and press [ENTER].
4. Press [ENTER] at the Connection Test option. The keypad tests and shows the results
for:
Link. Tests the network cable connection, and responds with OK or Failure.
Gateway. Tests the connection to the gateway, and responds with OK or Failure.
Internet. Tests the network cable connection, and responds with OK or Failure.
Default: 4 hours
Selection: 0, 4 hours, 12 hours, 24 hours, 48 hours, 72 hours
None No wireless device supervision
4 hr Send a missing condition after 4 hr of no contact from the wireless
repeaters.
12 hr Send a missing condition after 12 hr of no contact from the wireless
repeaters.
24 hr Send a missing condition after 24 hr of no contact from the wireless
repeaters.
48 hr Send a missing condition after 48 hr of no contact from the wireless
receiver.
72 hr Send a missing condition after 72 hr of no contact from the wireless
receiver.
Select the RF device supervision interval. If no communication has been received from a
device within the configured amount of time, a device missing trouble will be generated.
NOTICE!
For fire devices, the control panel sets System Supervision Time to 4 hours by default, and
RPS cannot change that setting. Modifying the selection in RPS for fire devices has no impact
on the programming.
Default: 0
Selection: 0 - 99999999
RFID (Radio Frequency device IDentification number). This is a unique number assigned to a
wireless device at the factory. It provides a unique way for the Wireless Receiver and Wireless
Repeaters to identify what device is transmitting. Since the Wireless Repeater is a receiver as
well as a transmitter it also is assigned an RFID so that the Wireless Receiver can determine
what Repeater is transmitting.
This RFID number is typically read off of the label that is affixed to the device. The label
location may differ for each RF device.
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the RF REPEATERS option.
2. Press [ENT] to enter the RF REPEATERS option.
3. Press [ENT] to enter the ADD REPEATERS option.
NOTICE!
Attempting to enter a repeater with an assigned RFID generates an error tone.
4. At the REPEATER 1-8 option, enter repeater number you wish to configure and press
[ENT] or scroll through the list of available repeater numbers by pressing [NEXT]. RFID:
NOT ASSIGNED shows.
5. Press [ENT]. The keypad indicates a transmission to the device.
6. Press the RESET button on the repeater to add it. The keypad reads REPEATER ADDED.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the RF Repeaters option.
2. Press [ENT] to enter the RF Repeaters option.
3. Press [ENT] to enter the Add Repeaters option.
NOTICE!
Attempting to enter a repeater with an assigned RFID generates an error tone.
4. At the Repeater 1-8 option, enter repeater number you wish to configure and press
[ENTER] or scroll through the list of available repeater numbers by pressing the Next
softkey. RFID: Not Assigned shows.
5. Press [ENTER]. The keypad indicates a transmission to the device.
6. Press the RESET button on the repeater to add it. The keypad reads Repeater Added.
Replace Repeater
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the RF REPEATERS option.
2. Press [ENT] to enter the RF REPEATERS option.
3. At the REPEATER 1-8 option, enter the repeater number you wish to configure and press
[ENT] or scroll through the available devices to replace, press [NEXT], and then press
[ENT] when the RF repeater you wish to replace shows.
NOTICE!
You must directly enter in a RF Repeater number (2) that has an assigned RFID. Attempting to
enter a repeater, without an assigned RFID will generate error tone.
4. If repeaters are available for adding as a replacement, a list of repeaters shows. To scroll
through the available repeaters to add, press [NEXT], and then press [ENT] when the
desired repeater shows.
5. The keypad indicates a transmission to the device. Press the RESET button on the device
to add it. The keypad reads REPEATER ADDED.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the RF Repeaters option.
2. Press [ENT] to enter the RF Repeaters option.
3. At the Repeater 1-8 option, enter the repeater number you wish to configure and press
[ENTER] or scroll through the available devices to replace, press the Next softkey, and
then press [ENTER] when the RF repeater you wish to replace shows.
NOTICE!
You must directly enter in a RF Repeater number (2) that has an assigned RFID. Attempting to
enter a repeater, without an assigned RFID will generate error tone..
4. If repeaters are available for adding as a replacement, a list of repeaters shows. To scroll
through the available repeaters to add, the Next softkey, and then press [ENTER] when
the desired repeater shows.
5. The keypad indicates a transmission to the device. Press the RESET button on the device
to add it. The keypad reads Repeater Added.
Remove Repeater
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the RF REPEATERS option.
2. Press [ENT] to enter the REMOVE REPEATERS option.
3. At the REPEATER 1-8 option, enter the repeater number you wish to remove and press
[ENT] or scroll through the available devices to remove by pressing [NEXT], and then
press [ENT] when the RF repeater you wish to remove shows. he keypad reads RF
REPEATER REMOVED.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the RF Repeaters option.
2. Press [ENT] to enter the Remove Repeaters option.
3. At the Repeater 1-8 option, enter the repeater number you wish to remove and press
[ENT] or scroll through the available devices to remove by pressing the Next softkey, and
then press [ENT] when the RF repeater you wish to remove shows. he keypad reads RF
Repeater Removed.
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the RF DIAGNOSTICS option.
2. Press [ENT] to enter the RF DIAGNOSTICS option.
3. Press [ENT] at the RF POINTS option to enter it.
4. Press [ENT] to enter the STATES option.
5. Press [NEXT]. Within the STATES option, the menu will scroll through the following sub-
categories, with the results of the diagnostic check:
STATE
TAMPER
LOW-BATTERY
MAINTENANCE
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the RF Diagnostics option.
2. Press [ENTER] to enter the RF Diagnostics option.
3. Press [ENTER] at the RF Points option to enter it.
4. Press [ENTER] to enter the States option.
5. Press the Next softkey. Within the States option, the menu will scroll through the
following sub-categories, with the results of the diagnostic check:
State
Tamper
Low-Battery
Maintenance
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the RF DIAGNOSTICS option.
2. Press [ENT] to enter the RF DIAGNOSTICS option.
3. Press [ENT] to enter the SIGNAL STRENGTHS option.
4. Press [NEXT]. Within the SIGNAL STRENGTHS option, the menu will scroll through the
following sub-categories, with the results of the diagnostic check:
STRENGTH
LEVEL
MARGIN
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the RF Diagnostics option.
2. Press [ENT] to enter the RF Diagnostics option.
3. Press [ENT] to enter the Signal Strengths option.
4. Press the Next softkey. Within the Signal Strengths option, the menu will scroll through
the following sub-categories, with the results of the diagnostic check:
Signal Strengths
Level
Margin
RF Repeaters - States
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the RF DIAGNOSTICS option.
2. Press [ENT] to enter the RF DIAGNOSTICS option.
3. Press [ENT] at the RF REPEATERS option to enter it.
4. Press [ENT] to enter the STATES option.
5. Press [NEXT]. Within the STATES option, the menu will scroll through the following sub-
categories, with the results of the diagnostic check:
TROUBLE
MISSING
TAMPER
LOW-BATTERY
AC FAIL
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the RF Diagnostics option.
2. Press [ENTER] to enter the RF Diagnostics option.
3. Press [ENTER] at the RF Repeaters option to enter it.
4. Press [ENTER] to enter the States option.
5. Press the Next softkey. Within the States option, the menu will scroll through the
following sub-categories, with the results of the diagnostic check:
State
Missing
Tamper
Low-Battery
AC FAIL
Door Number
NOTICE!
The D9412GV4 supports up to eight doors. The D7412GV4 supports two doors.
D# Entry Area #
Default: Disabled
Selection: Disabled, 1 to 32
1 to 32 The area assigned to the door controller to which the reader allows
access.
Disabled Door controller does not function.
Assign an area to the door controller. This entry allows the D9210C to be polled, activating
communication to the control panel. This is also the area a user exits when initiating a REX.
NOTICE!
The D# Entry Area # prompt for the D7412GV4 is limited to the first 8 areas.
NOTICE!
All SDI devices, regardless of area assigned, report to Area 1, Account 1 by default upon SDI
failure. If a D9210C becomes disconnected, an SDI Fail ## and a Missing Point ### Event is
created.
NOTICE!
If the D9210C is not programmed with a D# Entry Area, 9210 NOT READY appears at the
keypad when attempting to add access credentials to a User ID.
D# CC# Scope
Default: 1
Selection: Disabled, 1 to 16 (for D9412GV4), 1 to 8 (for D7412GV4)
1 to 16 Determines the scope of areas to affect the access disarm request if
enabled. Also, determines the keypad to be used when performing Dual
Authentication.
Disabled Only the area assigned in D# Entry Area is disarmed if the user has
access disarm rights. No keypad assignment prohibits Dual
Authentication.
Enter the keypad number (CC#) which determines the scope of the user IDs disarming rights.
Areas disarm on the basis of this keypads scope and the authority level of the user.
D# Custom Function
Default: 0 (Disabled)
Selection: 0, 128-143 (128-131 on the D7412GV4)
0 Custom function disabled.
128-143 The custom function number that executes upon a valid ID, given the
appropriate user access level and area arm state.
You can program a custom function to run at the keypad programmed for CC# Scope. This
custom function activates only for users with an L## Function Level? Assignment (refer to
Section 3.12 User Interface, page 93) in which a valid ID can execute a custom function during
the armed or disarmed state. The user number to which the token is assigned must have an
assigned passcode.
If D# Disarm On Open is set to Yes for the same door, and L## Function Level? is set to D or
C, the custom function executes when the door is physically opened.
NOTICE!
A users access level and the armed state of the area determine whether the custom function
activates. This access level is programmed in the L## Function Level? prompt. Refer to
Section 3.12 User Interface, page 93.
Table 9.1, Page 196 shows how this programming affects custom function activation.
NOTICE!
A users security level must have an M, P, or D to operate the custom function.
D# Door Point
Default: 0
Selection: 0 to 127, 129 to 247 (0 to 75 on the D7412GV4)
1 to 127, 129 to 247 The point number assigned to this door. Points 128 and 248 are
reserved by the control panel for internal use.
0 No point number is assigned to this door.
Enter the point number assigned to this door. This point cannot be used for any other point
assignments so the corresponding P### Point Source prompt is set to Door Point
automatically.
NOTICE!
Door points must be programmed as Perimeter points. If a 24-hour point type is required for
the Door point, you can use a Perimeter point type with a point response of 9 to C. Also, the
debounce count must be set to 4 in Point Assignments.
NOTICE!
When assigning Points 1 to 8 (control panel zones), the end-of-line (EOL) resistors must be
removed from the control panel.
Also, do not enable any POPIT points, OctoPOPIT points, Octo-input points, or RF points
sharing the same point number as the Door point. Failure to do so results in extra point
trouble conditions upon reboot.
D# Interlock Point
Default: 0
Selection: 0 to 127, 129 to 247 (0 to 75 on the D7412GV4)
1 to 127, 129 to 247 The point number assigned to the Interlock point. Points 128 and 248
are reserved by the control panel for internal use.
0 No point number is assigned to the Interlock point.
Enter the interlock point number. This point, when faulted, prevents the door controller from
allowing access upon a valid ID read or door request.
Do not assign this point to another D# Door Point. You can, however, assign it to another
controller to prevent multiple controllers from activating.
CAUTION!
The Interlock point is considered in a normal state if it is bypassed, swinger bypassed, or
forced armed. This results in normal access even if the door remains open.
D# Auto Door
Default: No
Selection: Yes or No
Yes When the area assigned in D# Entry Area # is disarmed, the door is in
the unlocked state. When that area is armed, the door returns to the
locked state.
No Door state is not affected by the armed state of the area.
Use this program item to automatically unlock the door (latched, shunt, and strike) when the
entry area is disarmed. The door re-locks upon Master or Perimeter Arming the area.
NOTICE!
The unlocked state activated by Auto Door operation cannot be overridden manually.
D# Fire Unlock
Default: No
Selection: Yes or No
Yes Relay activates and shunt is applied for the door contact automatically
upon a Fire Alarm.
No Door remains in its current mode upon a Fire Alarm.
Use this program item to activate the relay for the door strike and shunt the door zone
automatically upon a Fire Alarm. This feature overrides a Secure Door state, Locked Door
state, Auto Door, and an Interlock Faulted point. The relay activates for all doors with this
prompt programmed as Yes when a Fire Alarm occurs in any area. Relays that are activated by
Fire Unlock can be returned to normal only through the keypad using the Door Control
function.
NOTICE!
Doors that are activated by Fire Unlock must be returned to normal using the Door Control
function on the keypad.
CAUTION!
This command unlocks the door regardless of the armed state.
NOTICE!
Each fire alarm that is generated causes a Door Unlocked Automatic Event.
D# Disarm on Open?
Default: Yes
Selection: Yes or No
Yes The area disarms only after the door is opened for a user with a valid
disarm level.
No The area disarms whether or not the door is opened as soon as a user
with a valid disarm level presents a valid token or card. If D# Door Point
is set to 0, then this prompt is treated as if it were set to No.
Use this program item to determine if the door needs to be physically opened before
disarming the area upon a valid access request. The user initiating the access request needs
access levels that allow disarming with ID.
D# Card Type
Default: 0
Selection: 0 to 3
0 Card format is 26-bit Wiegand.
3 Do not use. Card format is 37-bit fidelity.
This item must be kept to a value of 0 (26 bit Wiegand format).
D# Strike Time
Default: 10 sec
Selection: 1 sec to 240 sec
0 Strike Time is not programmed for this door.
1 to 240 The strike activates for the amount of time programmed.
Enter the amount of time the door controller toggles the relay output to activate the door
strike. When the door strike is activated, the user can open the door. The strike activates for a
valid token, RTE, REX, and the keypad CYCLE DOOR? function.
D# Shunt Time
Default: 10 sec
Selection: 0 to 240 sec
0 Shunt Time is not programmed for this door.
1 to 240 The shunt activates for the amount of time programmed.
Enter the amount of time that the Door point is shunted to allow a user to open the door. The
duration of time should be sufficient so that the opened door does not cause the point to
enter into a trouble, alarm, or faulted condition.
D# Buzz Time
Default: 2 sec
Selection: 0 to 240 sec
0 Buzz Time is not programmed for this door.
1 to 240 The buzzer sounds for the amount of time programmed.
Enter the amount of time the buzzer output sounds to notify the user that the strike was
activated and the door is ready to open. The buzzer stops as soon as the door is opened.
NOTICE!
A separate buzzer is required. Many readers have an internal buzzer that is not affected by
Buzz Time.
D# Extend Time
Default: 10 sec
Selection: 0 to 30 sec
Enter the amount of time that strike, buzz, and shunt activation is prolonged if a door is left
open and the shunt time expires. At the end of the programmed extend time, the buzzer
continues to buzz until the door closes. If programmed, the point assigned to the door
indicates a trouble, alarm, or fault at the keypad.
NOTICE!
The CLOSE DOOR # display on keypad does not activate if D# Extend Time is set to 0.
NOTICE!
Regardless of how the Door point is programmed, the system generates a Trouble Door Left
Open Event while the system is disarmed, and an Alarm Door Left Open Event if the system is
armed and the door is held open beyond Extend Time. Door Closed - Restoral Events are
generated after the door is held open past Extend Time and the door returns to normal.
D# Deactivate On Open?
Default: Yes
Selection: Yes or No
Yes Strike deactivates when the door is opened after a valid Access Granted
request.
No Strike remains activated for the amount of the programmed strike time
whether door is opened or closed.
Determines if the strike deactivates immediately upon physically opening the door.
NOTICE!
In order for this function to work, a point needs to be assigned to the door.
NOTICE!
To Reduce False Alarms, maintain D# Deactivate on Open? as the default (Yes). This helps
prevent the door from bouncing open and causing a false alarm.
Default: No
Selection: Yes or No
Yes Programmed shunt time activates so door can be manually opened.
No RTE automatically activates the programmed strike and shunt time.
Use this program item to disable the strike, but still activate the programmed shunt time at a
Request to Enter (RTE) area.
NOTICE!
Use this parameter when a user can open a door manually without relying on a token or card
to activate the strike (such as with a push bar).
NOTICE!
When RTE Shunt Only is Yes, RTE Events are not logged, reported, or printed.
Default: No
Selection: Yes or No
Yes Programmed shunt time activates so the door can be manually opened.
No REX automatically activates the programmed strike and shunt time.
Use this program item to disable the door strike, but activate the programmed D# Shunt Time
upon a request to exit (REX) from an area.
NOTICE!
Use this parameter when a user can open a door manually without relying on a token or card
to activate the strike (such as with a push bar).
NOTICE!
When REXShunt Only is Yes, REX Events are not logged, reported, or printed.
D# Access Granted?
Default: Yes
Selection: Yes or No
Yes Access Events from this door controller are sent to the control panel for
processing.
No Access Events from this door controller are not sent to the control
panel for processing.
This program item determines if Access Granted and Door Request Events are sent to the
control panel for processing memory, printing, and remote reporting.
NOTICE!
A successful Access Event can be started by a:
Valid user ID
Valid door state changed at the keypad
Scheduled or armed state change that holds a door open
RTE or REX
D# No Entry?
Default: Yes
Selection: Yes or No
Yes Access Denied Events from this door controller are sent to the control
panel for processing.
No Access Denied Events from this door controller are not sent to the
control panel for processing.
This program item determines if No Entry Events are sent to the control panel for processing
memory, printing, and remote reporting.
NOTICE!
No Entry Event can be caused by:
Invalid or unknown user ID, interlock or secured door, or incorrect authority level
RTE or REX at an interlocked door
RTE or REX at a door in the secured mode
D# Enter Request?
Default: No
Selection: Yes or No
Yes A Door RTE Event from this door controller is sent to the control panel
for processing.
No A Door RTE Event from this door controller is not sent to the control
panel for processing.
This program item determines if RTE Events are sent to the control panel for processing
memory, printing, and remote reporting.
NOTICE!
RTE Events require D# Access Granted to be programmed as Yes.
D# Exit Request?
Default: No
Selection: Yes or No
Yes A Door REX Event from this door controller is sent to the control panel
for processing.
No A Door REX Event from this door controller is not sent to the control
panel for processing.
This program item determines if REX Events are sent to the control panel for processing
memory, printing, and remote reporting.
NOTICE!
REX Events require D# Access Granted to be programmed as Yes.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the Service Bypass option.
2. Press [ENTER] to enter the Service Bypass option.
If no points are bypassed, No Points Bypassed shows. If points are bypassed, a list of
unbypassed points shows.
3. The number of points in service bypass are below the Point Num 1-247: prompt. Enter
the point number followed by [ENTER].
4. Press [ENTER] to make a selection. The keypad reads Point Bypassed.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the Service Bypass option.
2. Press [ENTER] to enter the Service Bypass option.
The Service Bypass prompt alternates with the number of points in service bypass.
3. The number of points in service bypass display below the Point Num 1-247: prompt.
Enter the point number followed by [ENTER] or press the Next softkey to advance to the
point.
4. At the Point (###) Service Bypass: Yes prompt press the Edit softkey.
5. Press the No softkey, then press the Save softkey to remove service bypass.
6. Press the Next softkey to advance to another point, or press the Exit softkey to select
another, or press the Esc softkey to exit
When the keypad reads Parameter Saved, your selection has been configured.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the RF POINTS option.
2. Press [ENTER] to enter the RF POINTS option.
3. At the Enroll RF Point prompt, press the [ENTER] option. If all wireless devices are
enrolled, All Points Added shows. If wireless devices are available for enrolling, a list of
wireless devices shows.
4. To scroll through the available devices to enroll, press the Next softkey, and then press
[ENTER] when the desired device shows.
5. The keypad indicates a transmission to the device. Press the [RESET] button on the
device to enroll it. The keypad reads Point Enrolled.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the RF Points option.
2. Press [ENTER] to enter the RF Points option.
3. At the REPLACE RF POINT prompt, press [ENTER]. A list of enrolled wireless devices
shows.
4. To scroll through the available devices to replace, press the Next softkey, and then press
[ENTER] when the RF point you wish to replace shows.
5. If wireless devices are available for enrolling as a replacement, a list of wireless devices
shows. To scroll through the available devices to enroll, press the Next softkey, and then
press [ENTER] when the desired device shows.
6. The keypad indicates a transmission to the device. Press the [RESET] button on the
device to enroll it. The keypad reads Point Enrolled.
4. At the following prompt (PT-## RFID AUTO LEARNED if the previous device was auto-
learned, or PT-## and then the RFID) prompt, enter in the RF point number you wish to
remove and press [ENT] or to scroll through the available devices to enroll, press [NEXT],
and then press [ENT] when the desired device shows. The keypad reads RF POINT
REMOVED.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the RF Points option.
2. Press [ENT] to enter the RF Points option.
3. At the Remove RF Points prompt, press [ENTER]. A list of enrolled wireless devices
shows.
NOTICE!
By pressing the [Remove] button inside the Remove RF Point option, you will remove any
previously programmed points, and an alarm will go off. A No Points prompt will be displayed
as a result.
4. At the following prompt (PT-## RFID Auto Learned) if the previous device was auto-
learned, or PT-## and then the RFID) prompt,, enter in the RF point number you wish to
remove and press [ENTER] or to scroll through the available devices to enroll, press the
Next softkey, and then press [ENTER] when the desired device shows. The keypad reads
RF Point Removed.
NOTICE!
After selecting the RF Point for removal the panel instructs the Commercial Wireless module
to delete the device. The points RFID is unassigned and saved.