Seismic Arrestor
Seismic Arrestor
Seismic Arrestor
Seismic Co-efficient
for Zone IV Zone Factor is =
Importance of Bridge Important Bridges =
Response reduction factor, R =
Average Response Acceleration Co-efficient =
Horizontal Seismic Co-efficient =
(Ah)
Z I Sa
Ah x x
2 R g
Design Data
Assuming the Size of Longitudinal Arrestor
Plan dimension ( b x D )
800 x 800 mm
Top Width of Arrestor in Plan =
Height of Seismic Arrestor L =
Clear Cover provided C.C. =
Total Depth for Section at Height L1 =
Effective depth of Section d' =
Dist of load from face a =
1 of 8
NH-58 Design of Seismic Arrestor
2 of 8
NH-58 Design of Seismic Arrestor
Tranverse Direction
800
800
900
800 L1
Design Calculation
The Seismic Arrestor is designed for the seismic force transmitted to it from Super-Structure.
Design Horizontal Force Vu =
Design Vertical Force Hu =
(20% Design Horizontal Force) min. Hu =
No of Seismic Arrestor =
Reinforcement Calculation
Shear Friction Reinforcement Avf =
Direct Tension Reinforcement At =
Flexural Tension Reinforcement Af =
Af + At =
(2/3 x Avf) + At =
(0.04 x fc' / fsy) x b x d' =
Total Primary Tensile Reinforcement As =
0.5 x Af =
0.33 x Avf =
Cross sectional area of stirrups Ah =
3 of 8
NH-58 Design of Seismic Arrestor
Reinforcement
Total Primary Tensile Reinforcement As =
So, Provide 32 Bar - ### in
in Each Layer
As per Clause 304.7.1.3.3 of IRC:21-2000, the permissible stress in concrete can be increased by a Factor of,
= 1+ 5x P d= 2.7425
Ag x fck
Maximum Allowable Shear Stress on block =
4 of 8
NH-58 Design of Seismic Arrestor
5410.3 kN
1786.5 kN
274.8 kN
7471.6 kN
ULS
7303.89 kN
3126.38 kN
412.2 kN
10842.5 kN
0.240
1.200
1.000
2.500
0.360
400 mm
900 mm
40 mm
452.22 mm
344 mm
783 mm
11.67 MPa
29.05 MPa
435.0 MPa
1.40
5 of 8
NH-58 Design of Seismic Arrestor
6 of 8
NH-58 Design of Seismic Arrestor
Tranverse Direction
1.000
3903.3 kN
0.0 kN
780.7 kN
3903.3 kN
780.7 kN
3098.0 kNm
6409.3 mm2
1794.6 mm2
25879.1 mm2
27673.7 mm2
6067.5 mm2
639.6 mm2
27673.7 mm2
12939.6 mm2
2134.3 mm2
12939.6 mm2
7 of 8
NH-58 Design of Seismic Arrestor
27673.7 mm2
2 Layers
12939.6 mm2
82.0 mm
spacing c/c
3903.3 kN
12.198 N/mm2
0.8529 N/mm2
> 1.500
1.2793 N/mm2
< 12.198
3493.9 kN
5737.1 mm2
6409.340