1TWD026202S0101
1TWD026202S0101
1TWD026202S0101
ALL WIRE ENDS HAVE FERRULES, CABLE LUGS ETC., AND ARE MARKED WITH TERMINAL DESTINATION REFERENCE (TYPICAL X2:4, K10:13 ETC.)
EITHER BY REFERENCE PRINTED DIRECTLY ON CONDUCTOR OR BY SHRINKABLE SLEEVES. SHEET CONTENT
1 INFO
C 2. CROSS REFERENCE DOCUMENTS: 2 +AB00 120V AC UPS POWER SUPPLY C
3 +AB00 24V DC POWER SUPPLY
4 24V DC POWER SUPPLY
5 120V AC NORMAL POWER SUPPLY
6 +AB00 PANEL HEATING
7 +A02 CONNECTION OF THE CONTROL VOLTAGE SUPPLY
8 +B02 CONNECTION OF THE CONTROL VOLTAGE SUPPLY
9 +A02 EARTH FAULT MONITORING
10 +A02 EARTH FAULT MONITORING
11 +B02 EARTH FAULT MONITORING
D 12 +B02 EARTH FAULT MONITORING D
13 OVERVIEW COMMUNICATION
14 +AB00 REF / REG IRIG-B COMMUNICATION
15 +A01 TERMINAL LISTS
16 +A02 TERMINAL LISTS
17 +AB00 TERMINAL LISTS
18 +B01 TERMINAL LISTS
19 +B02 TERMINAL LISTS
20 +A01 COMPONENT LIST
21 +A02 COMPONENT LIST E
E
22 +AB00 COMPONENT LIST
23 +AB00 COMPONENT LIST
24 +B01 COMPONENT LIST
25 +B02 COMPONENT LIST
/3.A1
/3.A1
L1 L2
-Q33:2
-Q33:4
A A
-X11 1 2
/17.E3
-X11 3 4
/17.E3
+A02-Q64:2
+A02-Q64:4
+B02-Q64:2
+B02-Q64:4
4mm2 WIRING TO NEXT MCB
/9.A1
/9.B1
/11.A1
/11.B1
+A01. +AB00. +B01.
1
2
D 21 21 D
3
C2A C2A
-K10B -K10A
/2.F4 22 /2.F1 22
A1 A1
A1 A1
E -X10A 1 2 3 4 -X10B 1 2 3 4 E
/17.B3 /17.D3
-K11A -K11B
14
-K10A -K10B 14
11 1 2 1 2 11
12 L1 L2 L1 L2 12
* 24 /2.D2
3 4
120V AC 120V AC /2.C3
3 4 * 24 *
REF DWG:
TRI-NC-PAU-VD-42-02-1600
21 5 6 5 6 21
22 UPS A UPS B 22 1TWD026202N0101 SH.24
13 14 13 14
34 34 PART OF COMMON ALARM
31 21 22 21 22 31
32 /2.D4 /2.D1 32 IN +AB00
44
RECOMENDED UPSTREAM PROTECTIVE DEVICE: 44
41 T2 160 PR221 In=25A 41
42 42
-R32
-T33
+ +24V
OUT
6,3A T
L1 120V UPS -Q33 L + -X37.1 1 +24V
A /17.A7 +A02-X38.1:1 /4.A1 A
1
-X11:1
2
10A
24V DC
L2 120V UPS N
2
/2.A2 0V
-X11:3 - -X37.1 6 0V
3
K4A
/4.A1
PE - /17.B7 +A02-X38.1:3
- A2
DC OK I < IN 13 14 -K33
/3.F3
A1
-T34
6,3A T +
B -Q34 L + -X37.1 2 +24V B
1
/17.B7 +B02-X38:1
2
10A
24V DC
N
- -X37.1 7 0V
3
K4A /4.A4
PE - /17.B7 +B02-X38:3
- A2
D D
E E
REF DWG:
-K33 -K34 * TRI-NC-PAU-VD-42-02-1600
14 14 1TWD026202N0101 SH.24
11 11
12 12 PART OF COMMON ALARM
* * IN +AB00
2
+A02
B -F15.1 B
4A
1
+A02
-X15 5 6
/16.C3
+A02
-X15 7 8
/16.C3
M LINK 2 2
/7.E2
/7.D2
C +A02 +B02 C
-F15 -F15
10A 10A
1 1
+24VDC 0V
MVIEW
/7.C2
/7.C2
+A02 +B02
-X15 1 2 -X15 1 2
/16.B3 /19.C3
D D
/7.A1
/7.A1
/8.A1
/8.A1
E 24V 0V 24V 0V E
24V DC 24V DC
DISTRIBUTION BAR DISTRIBUTION BAR
2 4 6 2 4 6
+A02 +B02
-Q8 -Q8
B 35A 1 3 5 35A 1 3 5 B
480 0 480 0
+A02 +B02
-T8 -T8
480V/120V 120 0 480V/120V 120 0
3200VA 3200VA
PE PE
2 2
+A02 +B02
C C
-F8 -F8
16A 16A
1 1
D D
/7.B1
/7.B1
/8.B1
/8.B1
E E
L 0V L 0V
120V AC 120V AC
DISTRIBUTION BAR DISTRIBUTION BAR
PANEL HEATING
A A
2
-B40 0
3
X2
B -P40 B
PANEL SPACE X1
HEATERS ON
WHITE
+A02 +B02
1 3
-X43.1 1 2 -X43.1 1 2
C -S40 /16.D7 /19.B7 C
2 4
PANEL SPACE
+A02 1 +A01 1 1 +B01 1 +B02 1
HEATERS OFF/ON
-E43 -E43 -E43 -E43 -E43
2 2 2 2 2
1 3
-Q40 C10A
D 2 4 D
E -X40.1 1 2 -X40.1 3 4 E
/17.C7 /17.C7
/6.C1
/6.C1
L1 L2
120V 1 3
F PANEL HEATING F
Drw.title: AUXILIARY DRAWING
ABB AS,
BG TRINIDAD & TOBAGO, POINSETTIA Low Voltage Products LQ UPGRADE
SDRL code (s): BU LV Systems POINSETTIA
ABB O.NO: P026202 AUX.VOLTAGE AND MNS-IS COMMUNICATION
Tag No(s): Project dwg.no.: Sheet
Suppliers own drawing No: Rev.:
1TWD026202S0101 0 / 29.10.12.SAP +AB00 182-EL-1001 TRI-NC-PAU-VD-42-02-1602 6 of 25
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
120V AC
B L /5.E1 -F8:1 B
0V /5.E1 -T8:0
+A02
-A4 +A02 EC01, GA01, HC01, KA01, LC01, NA01, PC01, RA01
/4.C2 -X15:8
/4.C1 -X15:6
+A02
-A5
D M-LINK D
0V +24V
/4.C2 -X15:7
/4.C1 -X15:5
+A3F
E E
120V AC
B L /5.E4 -F8:1 B
0V /5.E4 -T8:0
D D
/10.C3
/10.D3
/10.D3
/10.D3
/10.A3
/10.A3
/10.B3
/10.B3
A A
ICSS
+A02-EC01-B64A:l
+A02-GA01-B64A:l
+A02-LC01-B64A:l
+A02-NA01-B64A:l
+A02-EC01-B64A:k
+A02-GA01-B64A:k
+A02-LC01-B64A:k
+A02-NA01-B64A:k
L1 120V UPS
-Q64
/2.B3
1
-X8:1
2
L2 120V UPS -X64 1 2 3
TRI-NC-PAU-VD-42-02-1600
/2.B4
1TWD026202N0101 SH.23
-X8:3 /16.D7
3
C6A
REF. DWG.:
B B
/9.C7
A1 A2 R T/R T k1 l k2 k5 l k6 k9 l k10
C11 C21
C11
BENDER-RCMS 460-D-2 -K64
/9.B5
-K64 C12 C14
C C
GROUND
FAULT ALARM
+A02-HC01-B64A:k
+A02-PC01-B64A:k
+A02-RA01-B64B:k
+A02-KA01-B64A:k
+A02-HC01-B64A:l
+A02-PC01-B64A:l
+A02-RA01-B64B:l
+A02-KA01-B64A:l
/10.B3
/10.B3
/10.C3
/10.C3
/10.A6
/10.A6
/10.B6
/10.B6
D D
E E
GY -K64:k1 GY -K64:k7
A +A02-EC01 k /9.A4 +A02-PC01 k /9.D4 A
-B64A l -B64A l
BK -K64:l BK -K64:l
/9.A4 /9.D4
GY -K64:k2 GY -K64:k8
+A02-GA01 k /9.A4 +A02-RA01 k /9.D5
-B64A l -B64B l
BK -K64:l BK -K64:l
/9.A4 /9.D4
B B
GY -K64:k3
+A02-HC01 k /9.D4
-B64A l
BK -K64:l
/9.D4
GY -K64:k4
+A02-KA01 k /9.D4
-B64A l
C BK -K64:l C
/9.D4
GY -K64:k5
+A02-LC01 k /9.A4
-B64A l
BK -K64:l
/9.A4
D GY D
-K64:k6
+A02-NA01 k /9.A5
-B64A l
BK -K64:l
/9.A4
E E
IEC Ref. ABB Order code Description Manufacturer NOTE 2: CT T7 IS INSTALLED IN BOTTOM OF CUBICLE
-B64A NHSN718035P0070 EARTH FAULT CURRENT TRANSFORMER W2-S 70 BENDER, DE EXTERNAL CABLES TO BE ROUTED THROUGH CTs
/12.C3
/12.D3
/12.D3
/12.D3
/12.A3
/12.A3
/12.B3
/12.B3
/12.B6
/12.B6
ICSS
A A
-X3:1
+B02-CA01-B64A:l
+B02-DC01-B64A:l
+B02-JA01-B64A:l
+B02-KC01-B64A:l
-X3:2
+B02-CA01-B64A:k
+B02-DC01-B64A:k
+B02-JA01-B64A:k
+B02-KC01-B64A:k
L1 120V UPS
-Q64 -X64 1 2 3
/2.B6
1
-X8:1 /19.C7
2
L2 120V UPS
TRI-NC-PAU-VD-42-02-1600
/2.B6
1TWD026202N0101 SH.23
-X8:3
3
C6A
REF. DWG.:
B B
/11.B7
A1 A2 R T/R T k1 l k2 k5 l k6 k9 l k10 C11
C11 C21 -K64
/11.B5
BENDER-RCMS 460-D-2 C12 C14
-K64
C12 C14 C22 C24
B A k3 l k4 k7 l k8 k11 l k12
C GROUND C
FAULT ALARM
+B02-GC01-B64A:k
+B02-RA01-B64B:k
+B02-PA01-B64A:k
+B02-FA01-B64A:k
+B02-GC01-B64A:l
+B02-RA01-B64B:l
+B02-PA01-B64A:l
+B02-FA01-B64A:l
/12.B3
/12.B3
/12.C3
/12.C3
/12.A6
/12.A6
/12.B6
/12.B6
D D
E E
GY -K64:k1 GY -K64:k7
A +B02-CA01 k /11.A4 +B02-PA01 k /11.C4 A
-B64A l -B64A l
BK -K64:l BK -K64:l
/11.A4 /11.C4
GY -K64:k2 GY -K64:k8
+B02-DC01 k /11.A4 +B02-RA01 k /11.C5
-B64A l -B64B l
BK -K64:l BK -K64:l
/11.A4 /11.C4
B B
GY -K64:k4
+B02-GC01 k /11.C4
-B64A l
C BK -K64:l C
/11.C4
GY -K64:k5
+B02-JA01 k /11.A4
-B64A l
BK -K64:l
/11.A4
D GY D
-K64:k6
+B02-KC01 k /11.A5
-B64A l
BK -K64:l
/11.A4
E E
IEC REF. ABB ORDER CODE DESCRIPTION MANUFACTURER NOTE 2: CT T7 IS INSTALLED IN BOTTOM OF CUBICLE
-B64A NHSN718035P0070 EARTH FAULT CURRENT TRANSFORMER W2-S 70 BENDER, DE EXTERNAL CABLES TO BE ROUTED THROUGH CTs
CONTROL CONTROL
COMPARTMENT COMPARTMENT
2220 MM
+A02 +B02
A A
ICSS
72E A
A
M-LINK
B
B
C
-A5 1 2
68E D
A
B
C C OUT IN
64E D A/A A/A
A
B
60E D C
D
A
-A4 OUT IN
B A/A A/A
B 56E E C B
D
A M-VIEW
OUT IN
A/A A/A OUT IN
B
52E F C
D
A/A A/A
A
B OUT IN
48E G C
D
A/A A/A
OUT IN
A A/A A/A
B
44E H C
D OUT IN
A A/A A/A
B OUT IN
40E J C
D
A/A A/A
A
C B OUT IN C
36E K C
D
A/A A/A OUT IN
A A/A A/A
B
32E L C
D OUT IN
A A/A A/A
B
28E M C
D
A
B OUT IN
24E N C
D
A/A A/A
A
B
P C OUT IN
20E A/A A/A
D
A
OUT IN
D B
A/A A/A D
16E Q C
D
A
B
12E R C
D
A
B
8E S C
D
A
B
T C OUT IN OUT IN
4E D A/A A/A A/A A/A
A BUS TERM.
B
0 U C
D
E E
W
0 MM
F OVERVIEW COMMUNICATION F
Drw.title: AUXILIARY DRAWING
ABB AS,
BG TRINIDAD & TOBAGO, POINSETTIA Low Voltage Products LQ UPGRADE
SDRL code (s): BU LV Systems POINSETTIA
ABB O.NO: P026202 AUX.VOLTAGE AND MNS-IS COMMUNICATION
Tag No(s): Project dwg.no.: Sheet
Suppliers own drawing No: Rev.:
1TWD026202S0101 0 / 29.10.12.SAP 182-EL-1001 TRI-NC-PAU-VD-42-02-1602 13 of 25
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
1
+B01
- + -R2 120
-X5C 1 2 3
C /17.E7 2 C
END TERMINATION
D D
E E
C C
D D
E E
CABLE TERMINAL LIST: -X8 120V AC CABLE TERMINAL LIST: -X38.1 24V DC
A REF. CORE NO. INTERNAL REF. CORE NO. INTERNAL A
TERMINAL LINK CONNECTION DRWG. TERMINAL TERMINAL LINK CONNECTION DRWG. TERMINAL
NO. SIDE B SIDE A REF. TYPE NO. SIDE B SIDE A REF. TYPE
B CABLE TERMINAL LIST: -X15 24V DC CABLE TERMINAL LIST: -X43 120V AC B
REF. CORE NO. INTERNAL REF. CORE NO. INTERNAL
TERMINAL LINK CONNECTION DRWG. TERMINAL TERMINAL LINK CONNECTION DRWG. TERMINAL
NO. SIDE B SIDE A REF. TYPE NO. SIDE B SIDE A REF. TYPE
2 /4.A3 ZS10
CABLE TERMINAL LIST: -X64 24V DC
D 3 -X38.1:4 -Q38:6 /4.A3 ZS10 REF. CORE NO. EXTERNAL D
4 /4.A3 ZS10 TERMINAL LINK CONNECTION DRWG. TERMINAL
NO. SIDE B SIDE A REF. TYPE
E E
CABLE TERMINAL LIST: -X4 120V AC CABLE TERMINAL LIST: -X37.1 24V DC
A REF. CORE NO. INTERNAL REF. CORE NO. INTERNAL A
TERMINAL LINK CONNECTION DRWG. TERMINAL TERMINAL LINK CONNECTION DRWG. TERMINAL
NO. SIDE B SIDE A REF. TYPE NO. SIDE B SIDE A REF. TYPE
5 /3.C5 ZS10
4 ZS4
CABLE TERMINAL LIST: -X40.1 120V AC
/2.E2
REF. CORE NO. EXTERNAL
TERMINAL LINK CONNECTION DRWG. TERMINAL
C C
NO. SIDE B SIDE A REF. TYPE
CABLE TERMINAL LIST: -X10B 120V AC
REF. CORE NO. EXTERNAL 1 -Q40:2 /6.E1 ZS4
4 ZS4
CABLE TERMINAL LIST: -X43 120V AC
/2.E3
REF. CORE NO. INTERNAL
D D
TERMINAL LINK CONNECTION DRWG. TERMINAL
CABLE 120V AC NO. SIDE B SIDE A REF. TYPE
REF. CORE NO.
TERMINAL LIST: -X11
INTERNAL 1 +A01-X43:2 -E43:1 /6.C4 ZS4
TERMINAL LINK CONNECTION DRWG. TERMINAL 2 +B01-X43:1 -B40:2 /6.C4 ZS4
NO. SIDE B SIDE A REF. TYPE
3 +A01-X43:4 -E43:2 /6.C4 ZS4
1 -Q33:2 -K10A:1 /2.A2 ZS4
4 +B01-X43:3 -S40:3 /6.C4 ZS4
2 -X4:2 /2.A2 ZS4
1 /14.C1 MA 2,5/5
2 /14.C1 MA 2,5/5
3 /14.C1 MA 2,5/5
F TERMINAL LISTS F
Drw.title: AUXILIARY DRAWING
ABB AS,
BG TRINIDAD & TOBAGO, POINSETTIA Low Voltage Products LQ UPGRADE
SDRL code (s): BU LV Systems POINSETTIA
ABB O.NO: P026202 AUX.VOLTAGE AND MNS-IS COMMUNICATION
Tag No(s): Project dwg.no.: Sheet
Suppliers own drawing No: Rev.:
1TWD026202S0101 0 / 29.10.12.SAP +AB00 182-EL-1001 TRI-NC-PAU-VD-42-02-1602 17 of 25
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
C C
D D
E E
CABLE TERMINAL LIST: -X3 24V DC CABLE TERMINAL LIST: -X43 120V AC
A REF. CORE NO. EXTERNAL REF. CORE NO. INTERNAL A
TERMINAL LINK CONNECTION DRWG. TERMINAL TERMINAL LINK CONNECTION DRWG. TERMINAL
NO. SIDE B SIDE A REF. TYPE NO. SIDE B SIDE A REF. TYPE
4 /6.C6 ZS4
CABLE TERMINAL LIST: -X8 120V AC
REF. CORE NO. INTERNAL
TERMINAL LINK CONNECTION DRWG. TERMINAL
B
NO. REF. TYPE
CABLE TERMINAL LIST: -X43.1 120V AC B
SIDE B SIDE A REF. CORE NO. INTERNAL
1 +B01-X4:2 -Q64:2 /2.B6 ZS4
TERMINAL LINK CONNECTION DRWG. TERMINAL
2 /2.B6 ZS4 NO. SIDE B SIDE A REF. TYPE
CABLE TERMINAL LIST: -X15 24V DC CABLE TERMINAL LIST: -X64 24V DC
REF. CORE NO. INTERNAL REF. CORE NO. EXTERNAL
C C
TERMINAL LINK CONNECTION DRWG. TERMINAL TERMINAL LINK CONNECTION DRWG. TERMINAL
NO. SIDE B SIDE A REF. TYPE NO. SIDE B SIDE A REF. TYPE
2 /4.A4 ZS10
4 /4.A4 ZS10
E E
IEC Ref. ABB Order code Function Description Page ref. Manufacturer
-E43 NHSN705014P1210 HEATING ELEMENT SH100 100W 110-240V AC/DC /6.C3 RUBSAMEN & HERR,DE
A A
-X4 1SNK505010R0000 TERMINAL BLOCK ZS4 /15.A2 ABB ENTRELEC, FR
1-4 (4)
B B
C C
D D
E E
IEC Ref. ABB Order code Function Description Page ref. Manufacturer
-E43 NHSN705014P1210 HEATING ELEMENT SH100 100W 110-240V AC/DC /6.C2 RUBSAMEN & HERR,DE
A A
-F8 2CSM200923R1801 FUSE BASE E 91/32 FOR 10X38 FUSE /5.C1 ABB, AS
NHSN706056P0009 FUSE LINK 16A, 500V GG (10,3X38) SIBA, DE
-F15 2CSM200923R1801 FUSE BASE E 91/32 FOR 10X38 FUSE /4.C2 ABB, AS
NHSN706056P0007 FUSE LINK 10A, 500V GG (10,3X38) SIBA, DE
-F15.1 2CSM200923R1801 FUSE BASE E 91/32 FOR 10X38 FUSE /4.B1 ABB, AS
NHSN706056P0004 FUSE LINK 4A, 500V GG (10,3X38) SIBA, DE
-Q64 2CDS252001R0064 C6A MINIATURE CIRCUIT BREAKER S202-C 6 /9.B2 ABB STOTZ, DE
C -T8 NHSN718027P0132 480V/120V 3200VA VOLTAGE TRANSFORMER 3200VA 480V/120V /5.B1 NORATEL, NO C
IEC Ref. ABB Order code Function Description Page ref. Manufacturer
-B40 O.NO THERMOSTAT TRO60 NC, 10-60C /6.A1 RUBSAMEN & HERR
A A
-E43 NHSN705014P1210 HEATING ELEMENT SH100 100W 110-240V AC/DC /6.C4 RUBSAMEN & HERR,DE
-K10A 1SBL241001R8410 CONTACTOR A 26-30-10 110V 50HZ/110-120V 60HZ /2.E1 ABB AS, FR
1SBN030100R1000 MECHANICAL INTERLOCK VM5-1 FOR A9-A40 /2.C2 ABB AS, FR
1SBN010010R1001 AUXILIARY CONTACT CA 5-01, 1NC FOR A9-A110 /2.F1 ABB AS, FR
-K10B 1SBL241001R8410 CONTACTOR A 26-30-10 110V 50HZ/110-120V 60HZ /2.E4 ABB AS, FR
1SBN010010R1001 AUXILIARY CONTACT CA 5-01, 1NC FOR A9-A110 /2.F4 ABB AS, FR
-K33 1SNA645001R0300 AUX. RELAY RB121A 24V AC/DC 10MA /3.F3 ABB STOTZ, DE
1SVR405650R1000 SOCKET CR-PSS
-K34 1SNA645001R0300 AUX. RELAY RB121A 24V AC/DC 10MA /3.F4 ABB STOTZ, DE
C 1SVR405650R1000 SOCKET CR-PSS C
-P40 1SFA619402R5135 PANEL SPACE HEATERS ON PILOT LIGHT WHITE,TYPE CL-513W LED 120V /6.B1 ABB AS, SE
D -Q33 2CDS252001R0337 K4A MINIATURE CIRCUIT BREAKER S202-K 4 /3.A2 ABB STOTZ, DE D
-Q34 2CDS252001R0337 K4A MINIATURE CIRCUIT BREAKER S202-K 4 /3.B3 ABB STOTZ, DE
-S40 NZN 000653M0002 PANEL SPACE HEATERS OFF/ON SWITCH 2-POLE CG8-A201-600-ES4 /6.E3 KRAUS & NAIMER, AT
-T33 NHSN707014P0003 PRIMARY SWITCHED POWER SUPPLY 100-240V AC,DC/24V DC, 10A, QUINT-PS/1AC /3.A3 PHOENIX CONTACT, DE
E -T34 NHSN707014P0003 PRIMARY SWITCHED POWER SUPPLY 100-240V AC,DC/24V DC, 10A, QUINT-PS/1AC /3.B3 PHOENIX CONTACT, DE E
IEC Ref. ABB Order code Function Description Page ref. Manufacturer
-X10B 1SNK505010R0000 TERMINAL BLOCK ZS4 /17.C2 ABB ENTRELEC, FR
A 1-4 (4) A
C C
D D
E E
F COMPONENT LIST F
Drw.title: AUXILIARY DRAWING
ABB AS,
BG TRINIDAD & TOBAGO, POINSETTIA Low Voltage Products LQ UPGRADE
SDRL code (s): BU LV Systems POINSETTIA
ABB O.NO: P026202 AUX.VOLTAGE AND MNS-IS COMMUNICATION
Tag No(s): Project dwg.no.: Sheet
Suppliers own drawing No: Rev.:
1TWD026202S0101 0 / 29.10.12.SAP +AB00 182-EL-1001 TRI-NC-PAU-VD-42-02-1602 23 of 25
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
IEC Ref. ABB Order code Function Description Page ref. Manufacturer
-E43 NHSN705014P1210 HEATING ELEMENT SH100 100W 110-240V AC/DC /6.C5 RUBSAMEN & HERR,DE
A A
-R2 NHSN716002P0148 RESISTOR 120 OHM 0,6W 250V /14.C4 FIRSTRONICS
B B
C C
D D
E E
IEC Ref. ABB Order code Function Description Page ref. Manufacturer
-E43 NHSN705014P1210 HEATING ELEMENT SH100 100W 110-240V AC/DC /6.C5 RUBSAMEN & HERR,DE
A A
-F8 2CSM200923R1801 FUSE BASE E 91/32 FOR 10X38 FUSE /5.C4 ABB, AS
NHSN706056P0009 FUSE LINK 16A, 500V GG (10,3X38) SIBA, DE
-F15 2CSM200923R1801 FUSE BASE E 91/32 FOR 10X38 FUSE /4.C4 ABB, AS
NHSN706056P0007 FUSE LINK 10A, 500V GG (10,3X38) SIBA, DE
-Q8 1SCA108914R1001 35A FUSED LOAD SWITCH OS 40 FD12000 /5.B4 ABB AS, FI
1SCA109015R1001 HANDLE OHBS5 /5.B3 ABB AS, FI
B NHSN706023P0035 HRC-FUSE LINK NH00- 35A-GL-500V /5.B4 SIBA, DE B
NHSN706023P0035 HRC-FUSE LINK NH00- 35A-GL-500V /5.B4 SIBA, DE
-Q64 2CDS252001R0064 C6A MINIATURE CIRCUIT BREAKER S202-C 6 /11.B2 ABB STOTZ, DE
-T8 NHSN718027P0132 480V/120V 3200VA VOLTAGE TRANSFORMER 3200VA 480V/120V /5.B4 NORATEL, NO
E E