5MLD STP Comments
5MLD STP Comments
5MLD STP Comments
1) For walls L/B >2, walls such as W1,W2 W3 etc are to be designed as fully
Cantilever with fixed base and one configuration for entire length
Refer
The inner walls where L/B<2 ,moment coefficient may be used for design
Good engineering practice all the long walls is preferable to design as free
Cantilever with fixed base and horizontal bending forces may be adopted for
M=wh^3/6
T=wh^2/2
b) On liquid retaining faces, the tensile stresses due to the combination of direct
condition:(cte/cet)+(bem/bec)<1
Where
Bec =permissible tensile stress due to bending in concrete (see Table I).
conditions of wall panels for some common cases are given in IS 3370-PART4
ok not desirable
4) WALL footings to have uniform contact surface with ground for distribution of
forces effectively for base width portion as shown above. Tapering bases is
difficult to achieve at site with compacted surface and any settlement or cracks at
checked
6) Walls and base slab to be checked for seismic forces and hydrodynamic effect as per