See Other Sheets For CLTD, CLF, SCL & U-Values.: (Btu/hr-Ft - F)
See Other Sheets For CLTD, CLF, SCL & U-Values.: (Btu/hr-Ft - F)
See Other Sheets For CLTD, CLF, SCL & U-Values.: (Btu/hr-Ft - F)
nput values in Yellow Cells Go to Worksheets below for values that can be cut and pasted into Main Worksheet.
Heating(outdoor) tdb(99.6%) = 20 CLTD/CLF/SCL Method Values in other cells are caculated - References: ASHRAE Handbook of Fundamentals, 1997 and ACCA Manual N.
(Indoor) tdb = 70
Cooling(outdoor) tdb(0.4%) = 96 twb(0.4%) = 76 DR = 20 htg. 50 Add Building Description Here
(Indoor) tdb = 75 twb = 63 T(pm) = 21 T (mean) = 86
W (Outdoor) = #VALUE! W (Indoor)= ### W #VALUE! CLTD(Cor) = 4
Elevation (ft) = 200 Latitude = 32 Zone 1 Zone 2 Zone 3 Zone 4
See other sheets for CLTD, CLF, SCL & U-values. Area (ft2) qc (am) qc(pm) qh Area (ft2) qc (am) qc(pm) qh Area (ft2) qc (am) qc(pm) qh Area (ft2) qc (am) qc(pm) qh
Solar Shade Coeff. SCL (am) SCL (pm)
Windows (N) 35 35 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Windows (E) 142 48 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Windows (S) 43 48 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Windows (W) 32 140 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Other 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Enter CLTDs directly from Tables. Program will correct for temperatures.
Conduction U (Btu/hr-ft2-F) CLTD(am) CLTD(pm) T Area (ft2) Area (ft2) Area (ft2) Area (ft2)
Windows (N) 4 14 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Windows (E) 4 14 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Windows (S) 4 14 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Windows (W) 4 14 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Other 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Other 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Conduction U (Btu/hr-ft2-F) CLTD(am) CLTD(pm) T Area (ft2) Area (ft2) Area (ft2) Area (ft2)
Walls (N) 10 25 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Walls (E) 45 38 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Walls (S) 6 39 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Walls (W) 5 33 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Other 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Other 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Conduction U (Btu/hr-ft2-F) CLTD(am) CLTD(pm) T Area (ft2) Area (ft2) Area (ft2) Area (ft2)
Doors (N) 15 30 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Doors (E) 64 31 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Doors (S) 17 43 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Doors (W) 13 59 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Other 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Other 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Roof/Ceiling U (Btu/hr-ft2-F) CLTD(am) CLTD(pm) T Area (ft2) Area (ft2) Area (ft2) Area (ft2)
Type A 15 52 50 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Type B 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Floor U (Btu/hr-ft2-F) T(flr) Area (ft2) Area (ft2) Area (ft2) Area (ft2)
50 0.00 0.00 0.00 0.00
Slab/Basement Ins. Position Insulation UP T(slab) Per. (ft.) Per. (ft.) Per. (ft.) Per. (ft.)
Vertical R5 x 48 in #VALUE! 50 #VALUE! #VALUE! #VALUE! #VALUE!
Ventilation T(am) T(pm) T cfm cfm cfm cfm
Sensible 1.1 16.85 21 50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HRU Eff. (sen.) = W W
Latent 4840 #VALUE! #VALUE! 0 #VALUE! #VALUE! 0 ### #VALUE! 0 #VALUE! #VALUE! 0 ### #VALUE!
HRU Eff. (lat.) = People People People People
People Btu/person CLF(am) CLF(pm)
Sensible 250 0.78 0.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Latent 200 1 1 0 0.00 0.00 0 0.00 0.00 0 0.00 0.00 0 0.00 0.00
Total Sensible (MBtu/h) Entire Building Totals Zone 1 Zone 2 Zone 3 Zone 4
Total Latent (MBtu/h) #VALUE! #VALUE! Sens. #VALUE! #VALUE! Sens. ### #VALUE! Sens. #VALUE! #VALUE! Sens. ### #VALUE!
Total Gain (MBtu/h) #VALUE! #VALUE! Lat. #VALUE! #VALUE! Lat. ### #VALUE! Lat. #VALUE! #VALUE! Lat. ### #VALUE!
SHR #VALUE! #VALUE! Tot. Gain #VALUE! #VALUE! Tot. Gain ### #VALUE! Tot. Gain ### #VALUE! Tot. Gain ### #VALUE!
Total Loss (MBtu/h) #VALUE! #VALUE! SHR #VALUE! #VALUE! SHR ### #VALUE! SHR ### #VALUE! SHR ### #VALUE!
#VALUE! Net Loss ### Tot. Loss #VALUE! Net Loss #VALUE! Tot. Loss ### Net Loss #VALUE! Tot. Loss ### Net Loss #VALUE! Tot. Loss ### Net Loss #VALUE!
The Table below provides only a few of the sites listed in electronic format in the 2005 ASHRAE Fundamentals Handbook.
Handbook (Chapter 27) contains tablular climatic data for over 1200 locations in the USA and Canada and 1700 international
A B C D E F G
Location Lat. Elev. Heating Cooling 1
Evaporation 2
Dehumidification
-99.60% -0.40% -0.40% -0.40%
DB MWB WB MDB DP
City/State N Ft. F F F F F F
Albuquerque, NM 35 5320 13 96 60 65 83 61
Atlanta, GA 34 1033 18 93 75 77 88 74
Baltimore, MD 39 154 11 93 75 78 88 75
Birmingham, AL 34 630 18 94 75 78 89 75
Boise, ID 44 2870 2 96 63 66 90 58
Boston, MA 42 30 7 91 73 75 87 72
Brownsville, TX 26 20 36 95 78 80 89 78
Chicago, IL 42 673 -6 91 74 77 88 74
Cleveland, OH 41 804 1 89 73 76 85 73
Dallas, TX 33 597 17 100 74 78 92 75
Denver, CO 40 5330 -3 93 60 65 81 60
Lake Charles, LA 30 33 29 93 78 80 88 78
Los Angeles, CA 34 105 43 85 64 70 78 67
Miami, FL 26 13 46 91 77 80 87 78
Minneapolis, MN 45 837 -16 91 73 76 88 73
Nashville, TN 36 590 10 94 76 78 89 75
Omaha, NE 41 1332 -8 95 75 78 90 75
Oklahoma City 35 1300 9 99 74 77 91 73
Phoenix, AZ 34 1089 34 110 70 76 97 71
Raleigh, NC 36 440 16 93 76 78 88 75
Sacramento, CA 39 23 31 100 69 72 96 62
St. Louis, MO 39 564 2 95 76 79 90 76
Salt Lake, UT 41 4230 6 96 62 66 85 60
Seattle, WA 47 450 23 85 65 66 83 60
Tallahassee, FL 30 69 25 95 77 80 89 77
Tuscaloosa, AL 33 171 20 96 76 80 90 77
1This design conditions typically result in the highest sensible cooling load and highest total load when ventilation requirem
2These design conditions will result in higher total cooling loads when the ventilation air requirements and infiltration are h
climates.
3These design conditions typically result cooling loads with the lowest sensible heat ratio (SHRLoad).
4 Gr = Grains of moisture (7000 Grains = 1 lb)
E Fundamentals Handbook. The 2001 version of the
Canada and 1700 international locations.
G H
Dehumidification 3
DB
-0.40% Range
HR DB WB
Gr4 F F F
98 68 63 25
133 82 76 17
132 83 77 19
135 83 77 19
79 72 63 30
119 80 74 15
146 83 79 17
130 84 77 20
125 82 75 19
132 82 77 20
96 69 63 27
148 84 80 16
99 75 70 11
144 83 79 11
124 83 76 19
134 83 77 19
136 85 77 20
129 83 76 21
118 82 74 23
134 82 77 19
84 82 69 33
138 85 78 18
92 73 64 28
78 71 64 18
142 83 79 19
142 84 79 20
SHRLoad).
Table 7.1 R-Values for Building Materials and Structural Units
hr-F-ft2 hr-F-ft2
Air (Heat Flow) Btu Insulation Btu
Ext. Surface (7 mph) 0.25 3 inch Fiberglass 11
Ext. Surface (15 mph) 0.17 w/ 20% wood framing 9.6
Inside Surface 0.68 3 inch Fiberglass 13
1 in. Vertical Air Gap 0.8-1.6 w/ 20% wood framing 10.5
4 in. Vertical Air Gap 0.9-1.5 5 inch Fiberglass 19
1 in. Horizontal Air Gap 0.8-1.7 w/ 10% wood framing 17.3
4 in. Horizontal Air Gap 0.8-2.2 w/ 20% wood framing 15.2
7 inch Fiberglass 25
Exterior Materials w/ 10% wood framing 21
U-Values in Btu /hr-F-ft2
4 inch Face Brick 0.45 9 inch Fiberglass 30
Steel siding 0 w/ 10% wood framing 26
Vinyl Siding (0.06 in.) 0.06 11 inch Fiberglass 38
1 inch Stucco 0.21 w/ 10% wood framing 32.5
3/4 inch Plywood 0.93 Cellulose 3.7/in.
1/2 inch Plywood 0.62 w/ 10% wood framing 3.1/in.
5/8 inch Hardboard 0.85 w/ 20% wood framing 2.7/in.
3/8 inch Hardboard 0.5 Panel-3"beadbrd.+OSB 12.8
1/2 in. Veg. (Black) Board 1.32 Panel-3"extr.poly+OSB 17
Roof Stone/Slag 0.1/in. 1 inch Duct Liner/Wrap 4
Building Wrap, Felt ~0 2 inch Duct Liner/Wrap 8
7/16" OSB 0.5 Expanded Polysty (beads) 3.5/in.
Interior Extruded Polystyrene 5.0/in.
1/2 inch Gypsum Board 0.45 Polyisocyanurate 6.0/in.
5/8 inch Gypsum Board 0.56 Polyurethane foam 6.0/in.
1/2 inch Acoustical Tile 1.79
ructural Units R-Value Calculator
hr-F-ft2 Out. Surface Out. Finish Insulation
Structural Btu R(Total)= 0.25 0.45 9.3
8 inch LW block 2 R(Total)= 11.13 hr-ft2-F/Btu
with perlite cores 5.5 U (Overall)= 0.090 Btu/hr-ft2-F
12 inch LW block 2.4
with perlite cores 7.2 R-to-U Inverter
12 inch HW block 1.11 R(Total)= 13 hr-ft2-F/Btu
Concrete 0.14/in. U (Overall)= 0.077 Btu/hr-ft2-F
Softwood 1.25/in.
Hardwood 0.9/in. U-Value Calculator for Wood Frame Walls
% Total Area Out. Surfac Out. Finish
R-Values in hr-F-ft /Btu
2
R-Insul. Path = 80 0.25 0.45
U-Values in Btu/hr-F-ft2 R-Wood Path = 20 0.25 0.45
Windows R/U
Sgl. Pane Alum. frame 0.79/1.27 U (Overall)= 0.086 Btu/hr-ft2-F
Dbl. Pane Alum. frame 1.20/0.83 R(Total)= 11.62 hr-ft2-F/Btu
Dbl. Vinyl/Alum. frame 1.75/0.57
Dbl. Wood/Vinyl frame 1.82/0.55
R-per-Inch to R-Value Calculator
Triple Vinyl/Al. frame 2.30/0.43
Doors
1- inch Solid Wood 2.50/0.40 R per Inch Inches
with storm door 3.80/0.26 1.25 3.5
1- inch Panel 1.85/0.54 R(Total)= 4.375 hr-ft2-F/Btu
with storm door 2.80//0.36 U (Overall)= 0.229 Btu/hr-ft2-F
1- inch Insul. Metal 2.50/0.40
with storm door 3.80/0.26 P a ra lle l H e a t F lo w P a th s
In s u la tio n
2- inch Solid Wood 3.7/0.27 W o o d (o r S te e l) In s u la tio n P a th F ra m in g P a th B e tw e e n W o o d F ra m e
with storm door 5.0/0.20 F ra m e
W a ll
E x te rio r F in is h
Ro
A ttic S p a c e
In
A
R o o f-
C e ilin g B
C e ilin g
R o o f-
C e ilin g B
C e ilin g
Other Other Int. Finish In. Surf.
0.45 0.68 11.13
e Walls
Insulation Wood Other Other Int. Finish In. Surface R-Path Total
13 0.45 0.68 14.83
4.4 0.45 0.68 6.23
a th s
In s u la tio n
in g P a th B e tw e e n W o o d F ra m e
E x te rio r F in is h
R oof
A ttic S p a c e R a fte rs
In s u la tio n
A b o ve Jo is t
In s u la tio n
B e tw e e n J o is t
J o is t
C e ilin g
In s u la tio n
B e tw e e n J o is t
J o is t
C e ilin g
Window and Glass Door Cooling Load Temperature Differences (F)
All Hr = 10 Hr = 15
Directions 4 14
Wall Cooling Load Temperature Differences (F) (Wall Type 1 Suggested for Opague Doors)
Wall Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N
1 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10
N 18 30 17 30 16 30 15
E 63 31 63 31 64 31 64
S 12 31 13 35 15 39 17
W 13 59 13 59 13 59 13
48 Deg. N 48 Deg. N
Hr = 10 Hr = 15
9 24
49 38
9 55
6 32
48 Deg. N 48 Deg. N
Hr = 10 Hr = 15
6 17
28 39
6 37
6 20
48 Deg. N 48 Deg. N
Hr = 10 Hr = 15
7 16
27 36
8 34
8 20
48 Deg. N 48 Deg. N
Hr = 10 Hr = 15
6 12
16 36
5 24
8 13
48 Deg. N 48 Deg. N
Hr = 10 Hr = 15
8 10
14 29
10 17
14 12
48 Deg. N 48 Deg. N
Hr = 10 Hr = 15
44 83
32 82
24 68
8 62
13 57
16 46
8 43
10 36
18 37
20 35
Shade Coefficients (SC) for Unshaded Windows SCs for Windows with Inte
Coefficients
Glass Alum Wood Vinyl BLINDS
Glass Type Gap Only Frame Frame Frame # of Panes Win. Tint
Sgl.-"Clear 1 0.86 0.72 0.72 Single Clear
Sgl.-"Acryl 0.93 0.82 0.69 0.69 Double Clear
Dbl.-"Clear " air 0.87 0.76 0.63 0.63 Double e=0.2
Dbl.-"Clear "argon 0.87 0.76 0.63 0.63 DRAPES
Dbl-"=0.2 " air 0.7 0.66 0.55 0.55 # of Panes Win. Tint
Dbl-"=0.2 "argon 0.7 0.66 0.55 0.55 Single Clear
Trpl-"Clear " air 0.71 0.68 0.59 0.59 Double Clear
Trpl-"Clear "argon 0.71 0.68 0.59 0.59 Double e=0.2
SCL - Solar Cooling Loads - (Btu/hr-ft2) Note: To determine Zone Type, go to Wall Type Works
Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N
A Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15
N 38 38 37 38 36 37 36 36
E 154 40 154 40 155 40 155 40
S 35 37 39 41 44 45 49 48
W 35 160 35 160 35 160 35 160
Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N
B Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15
N 35 37 35 36 34 35 35 35
E 141 48 142 48 142 48 142 48
S 31 36 35 40 39 44 43 48
W 32 141 32 141 32 140 32 140
Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N
C Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15
N 32 34 32 34 32 33 32 33
E 123 47 123 47 124 47 124 47
S 29 32 33 36 37 39 41 42
W 34 132 34 132 34 132 34 132
Zone Type 24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N
D Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15
N 29 33 29 33 28 32 28 32
E 108 52 108 52 109 53 109 53
S 25 30 28 33 32 37 35 40
W 32 112 32 112 33 112 33 112
Cs for Windows with Interior Shades
efficients
Med. Blind Lt. Blind Med. Blind Lt. Blind Dark RollerWhite Roller
at 45 at 45 Closed Closed Closed Closed
0.74 0.67 0.63 0.58 0.81 0.39
0.62 0.58 0.63 0.58 0.71 0.35
0.39 0.36 - - 0.4 0.22
Drape Color / Weave
Lt./Open Med./Open Dk./Open Lt./Closed Med./CloseDk./Closed
0.69 0.74 0.82 0.69 0.59 0.39
0.63 0.65 0.71 0.63 0.53 0.35
0.36 0.37 0.37 0.36 0.32 0.22
48 Deg. N
Hr = 15
34
47
109
137
48 Deg. N
Hr = 15
31
47
76
130
48 Deg. N
Hr = 15
30
53
72
110
Heat Gain From Occupants - Btu/hr person
Continuous Average
Computer 15 Monitor 110 -
- 17 Monitor 125 -
- 19 Monitor 135 -
Laser Printer - Desktop 130 100
- Small Office 320 160
- Large Office 550 275
Fax Machine 30
Other Office Equipment 25% Nameplate
ng Types (Watts voltsamps)
Chp. 29, Table 2)
Coffee Maker 10 cup 1050 +
1540 Btu/h Latent
Microwave Oven 1 ft 3 400
Electronic Ballast
Refrigerator 15 ft 3 300
Ballast Net
Water Cooler 8 gal/hr 350
Factor Wattage
- hp Motor 270
- hp Motor 750
.94 16
-
.96 24
-
.97 31
.92 31
.90 36
.90 45
1.07 59
.94 55
.92 55
g
Metal Halide
Rated Actual
Watts (w/bal)
50 72
100 128
175 215
g
Metal Halide
Rated Actual
Watts (w/bal)
50 72
100 128
175 215
ment Watts
Btu/hr)
Average
-
-
-
100
160
275
30
25% Nameplate
(Watts voltsamps)
1050 +
1540 Btu/h Latent
400
300
350
Note: To Determine Zone Type, Go To Wall & Roof Types Worksheet
Cooling Load Factors - People & Unhooded Equip. (Occupancy Begins between 7 & 8 am)
Zone Type A Zone Type B Zone Type C
Occupancy Hr = 10 Hr = 15 Hr = 10 Hr = 15 Hr = 10 Hr = 15
8 hrs/day 0.9 0.98 0.78 0.94 0.72 0.89
12 hrs/day 0.9 0.98 0.78 0.94 0.73 0.89
16 hrs/day 0.91 0.98 0.8 0.94 0.76 0.91
Cooling Load Factors - Hooded Equipment (Occupancy Begins between 7 & 8 am)
Zone Type D
Hr = 10 Hr = 15 Occupancy
0.6 0.77 8 hrs/day
0.62 0.82 12 hrs/day
0.68 0.85 16 hrs/day
ASHRAE 62.1-2004 Ventilation Rate Procedure Input Req'd Output
Max occupants 12
Diversity 0.43
Ez 1.00
Vou 132
Ev 0.8
Vo 165 cfm
Max occupants 8
Diversity2 0.53
VentEff 1.00
Vou 84
Ev 0.9
Vo 93 cfm
A (ft2) Ra*Area Vp Zp
154 9 154 0.09
176 11 176 0.23
138 8 138 0.13
390 23 390 0.21
110 7 110 0.11
110 7 110 0.29
121 7 121 0.10
72
Default Values
cfm/person Lps/person
Peo./100 m2)
17 8.6
15 7.4
13 6.7
8 4.3
10 5.1
9 4.7
11 5.5
8 4
6 2.8
17 8.5
7 3.5
6 3
6 3.1
5 2.7
17 8.5
9 4.6
16 7.8
9 4.6
15 7.6
- -
8 4
22 10.8
21 10.3
17 8.3
A (ft2) Ra*Area Vp Zp
100 6 100 0.11
92 6 92 0.11
92 6 92 0.11
92 6 92 0.11
149.5 9 150 0.09
100 6 100 0.11
110 7 110 0.11
312 19 312 0.19
44
Table 7.5 Slab Perimeter Heat Transmission Coefficients (Fs) in Btu/hr-ft-F
Slab Insulation Unheated Slabs Heated Slabs
Insulation hr-F-ft2 Insulation Depth or Width (in.) Insulation Depth or Width (in.)
Position* Btu 0 12 24 36 48 0 12
Horizontal R Ins
=5 0.73 0.72 0.7 0.68 0.67 1.35 1.31
RIns =10 0.73 0.71 0.7 0.66 0.64 1.35 1.3
Vertical RIns=5 0.73 0.61 0.58 0.56 0.54 1.35 1.06
RIns =10 0.73 0.58 0.54 0.51 0.48 1.35 1
Horz.+ Vert. For RIns=5, For RIns=10, For RIns=5,
(Fully Insul.) F=0.46 F=0.36 F=0.74
Table 7.6 Crawl Space and Basement Heat Transmission Coefficients (Fcsb) in Btu/hr-ft
Crawl Space or Fcsb (Btu/hr-ft-F)
Basement Heights {qcsb=FcsbPBldg(ft)[ti-to](F)} W
Lag Lbg Lcsb RIns.= 0 RIns.= 4 RIns.= 8 RIns.= 12
(ft.) (ft.) (ft.) hr-ft2-F/Btu hr-ft2-F/Btu hr-ft2-F/Btu hr-ft2-F/Btu R In s* .
1 2 1.13 0.39 0.24 0.17 to
1 4
7
5
8
4.42
9
2.08
4.71
1.41
3.34
1.07
2.62
L ag
1 5 2.95 0.92 0.55 0.4
4 3 7 4.96 1.91 1.22 0.9
5 9 7.62 3.41 2.3 1.75
1 8 4.76 1.45 0.86 0.61
7 2 9 5.66 1.87 1.14 0.82
3 10 6.78 2.44 1.54 1.12
F o o tin
* I n s u la t io n c a n a ls o b e lo c a
r-ft-F
Heated Slabs
Depth or Width (in.)
24 36 48
1.28 1.24 1.2
1.26 1.2 1.13
0.99 0.95 0.91
0.9 0.84 0.78
For RIns=5, For RIns=10,
F=0.74 F=0.55
(Fcsb) in Btu/hr-ft-F
W a ll
R In s * . F lo o r
to
L ag
ti
L csb
L bg
C ra w l S p a c e o r
B a s e m e n t F lo o r
F o o tin g
la t io n c a n a ls o b e lo c a t e d o n in t e r io r w a ll.