Earth Electrode and Loop Booklet V2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

Earth electrode

and
earth loop impedance testing
Theory and applications

Contents

Introduction

Earth electrode testing

Resistivity v resistance

Earth system resistance

Earth system resistance test methods

Earth loop testing

17

What is the loop and why do we test it?

18

Loop impedance test methods

19

Test instrument accuracy

24

External factors influence measured values

26

Testing at source simple work-around

31

PFC and PSCC testing

32

Loop testing summary

34

Introduction
As two of the most common testing subjects debated amongst
electricians - as well as generating the highest percentage of calls
to the Megger Technical Support desk - this series of
presentations and supporting booklet hope to clarify some of the
obstacles faced by an electrical contractor, or test and inspection
engineer, out testing today.
The intention is not to delve in to the physics of the tests, but
rather look at the practical issues relating to the measurements.
We will also clarify the different test techniques, detail some of
the reasons why fluctuating values will be seen and hopefully
instil a greater confidence in the day to day results obtained
when testing in the field.
This booklet, although designed to be read in isolation, is in no
way a definitive guide. There have been written a plethora of
articles and application notes and it is recommended that should
further information be required, a quick search of the internet
will return a wealth of additional material, from basic How To
guides, to complete scientific papers on the subjects.

Earth electrode testing

Resistivity v resistance
When talking about earth electrode testing, there are two basic
test types: earth resistivity and earth system resistance. In a
nutshell, resistivity testing is used when looking to site a new
earthing system and system resistance testing is used to check an
existing resistance is low enough for a desired application.

Resistivity
Resistivity testing is primarily used when surveying an area, prior
to sinking rods, mesh, mats etc. Soil resistivity can vary across a
site by significant amounts and the cost implications involved
make surveys invaluable in identifying the optimal location to
locate the new installation. There are numerous factors that will
influence the resistance readings obtained the soil composition,
the moisture level and temperature as well as geographic
features within the ground.
In addition, when surveying, the variables of moisture content,
water table level and temperature have to be accounted for as
these will change dependent upon the season. Fairly obviously,
as the moisture content of the soil increases, the resistance value
decreases, so an allowance would have to be made for readings
taken in mid-winter as opposed to a reading taken through the
summer months.
The most popular method for earth resistivity surveys is the
4-pole (Wenner method), utilised with the standard formula for
average earth resistivity:
p = 2 AR

Where:
is average earth resistivity to depth A in ohm-cm
A is the distance between the spikes
R is the resistance read from the earth tester

Imeas

Emeas
C1 (E)

P1 (ES)

P2 (S)

C2 (H)
<A/20

This cm value is of interest to a design engineer, because by rearranging the formula and utilising published tables, the
resistance of the earth electrode required can be calculated:
p = 2 AR ( cm)

therefore electrode resistance R = p / 2 A

Earth system resistance

It is important to remember why earth resistance testing is being


undertaken and why a low resistance value is normally required.
In essence, the earth is provided to either enable protective
devices to operate, reduce ground potential rises or to provide a
safe passage to earth for lightning strikes and static charges etc.
Different applications will call for different maximum permissible
earth resistance values and there are numerous variables that
will contribute to this. Published standards or specific design

criteria will dictate what values are necessary and these should
be referred to in all cases.
Earthing systems fall within 2 categories: Simple or Complex.
Simple systems consist of either a single or small number of
electrodes driven in to the ground, whereas a complex system
will have multiple earthing points.
So what makes up an earth electrode resistance value? There are
3 main components involved:
1. Resistance of the electrode itself (dependent on material)
and the connections to it
2. Contact resistance between the electrode and the soil it
is driven into
3. Resistance of the surrounding body of soil
1 - Electrode resistance will vary slightly due to the type of
material used. Copper is the preferred material for earth rods
and mats, but it is not uncommon to find steel or iron used. The
resistance value between the materials is measurable but not
normally significant. Contact resistance between connections is
where issues may arise primarily down to incorrect termination
techniques or corrosion.
2 - Contact resistance is often thought of as one of the main
contributors to high earth resistance readings, but provided the
electrode is free from paint and grease and the earth is packed
firmly, the value is negligible
3 - Finally, an electrode driven in to the earth of uniform
resistivity will radiate current in all directions. By envisaging the
electrode surrounded by shells of earth of equal thickness, it is
easy to realise that the nearest shell will have the smallest
surface area, but as you move further away the surface area of
each shell is somewhat larger and offers less resistance. Finally, a
distance from the electrode will be reached where additional

shells will not add significantly to the resistance of the earth


surrounding the electrode. It is this critical volume of soil that
determines the effectiveness of the electrode.
In most cases, the greatest influence on the earth resistance
value will be the depth of the electrode. Doubling the depth can
see a reduction of up to 40% in the measured value. If multiple
rods are required, as a rule of thumb, the spacing of the rods
needs to be at least equal to the driven depth.

Effect of temperature
C

Resistivity (Ohm-cm)

20
10
0 (water)
0 (ice)
-5
-15

7,200
9,900
13,800
30,000
79,000
330,000

Resistivity of different soil types


Resistivity (Ohm-cm)
Surface soils, loam, etc.
Clay
Sand and gravel
Surface limestone
Shale
Sandstone
Granites, basalts, etc.
Slates, etc.

100 - 5,000
200 - 10,000
5,000 - 100,000
10,000 - 1,000,000
500 - 10,000
2,000 - 200,000
100,000
1,000 - 10,000

Earth system resistance test methods

2-pole or direct measurement (Dead Earth)


Although the simplest form of resistance testing, this method is
generally used as a last resort as it requires using unknown
factors and involves making certain assumptions.
In essence, a measurement of two electrodes in series is made
with one of the electrodes being an existing earth i.e. a water
pipe. For the reading of the electrode under test to be accurate,
an extremely low resistance value would be needed from the
existing earth but this cannot be proven. Although an extensive
metallic water pipe system may indeed have a low resistance
value, there would be no guarantee that non-metallic couplings
have been used and without comprehensive schematics, the
electrode under test could be placed firmly within the sphere of
influence created by the existing earth.

C1 (E)
P1 (ES)

Imeas

Emeas

Earth electrode
under test

P2 (S)
C2 (H)

Fall of potential method


This is the classic method for measuring resistance of a single
electrode, or a system of electrodes, to Earth. Two auxiliary
spikes are driven into the ground in line with the electrode/s
under test. Current is generated by the instrument between the
electrode/s under test and the auxiliary C spike. The resultant
potential across the soil resistance is then measured between the
electrode under test and the auxiliary P spike. However to
measure the true resistance of the electrode/s under test, the
auxiliary C spike must be far enough away from the electrode/s
under test for the spheres of influence not to interfere with each
other. This is determined by moving the P spike in steps between
the electrode/s under test and the C spike and plotting the
resistance curve caused by the fall of potential. The plotted
curve must have a flat, see diagram, and the true resistance of
the electrode/s is measured here. If there is no flat the distance
between the electrodes under test and the C spike must be
increased until there is.
Ground
Electrode
Under
Test (X)

Current
Probe (C)

Ground
Electrode
Under
Test (X)

Potential
Probe (P)
Position

Current
Probe (C)

Resistance in Ohms

Resistance in Ohms

True system
resistance
measured
here

X
Ground
Electrode
Position

Distance of Potential Probe from X (dp)

Current
Probe
Position

Ground
Electrode
Position

Distance of Potential Probe from X (dp)

C
Current
Probe
Position

When testing a single earth electrode the C spike can usually be


placed 15 m away from the electrode under test, with the P spike
placed 9m away. With a small grid of two electrodes, C can be
placed about 100 m from the electrodes under test; P spike about
62 m away. Larger earth systems consisting of several rods or
plates in parallel required the distance for C to be increased to
possibly 200 m and P to some 125 m.

Lazy spike method


Megger earth testers can operate with high temporary spike
resistances and still give accurate, reliable results. This means
auxiliary spikes do not have to be inserted too far into the
ground. However another advantage is that in urban concrete
locations where driving in spikes is impossible the spikes may be
laid flat on a wet patch of concrete and a measurement made.
However, structural steelwork and buried metal piping could
affect readings and should be taken into account.

61.8% rule
Assuming the C spike is far enough away from the electrode
under test, the soil mass is homogenous, and there are no buried
objects the correct P spike position will always be at 61.8% of the
distance from the electrode/s under test and the C spike.
This is definitely a rule to be treated with great care.

10

ART Attached rod technique


Based on the Fall of Potential method, instruments with ART
capability use the ICLAMP to measure only the instruments test
current flowing down the electrode under test, negating the
requirement to disconnect the electrode under test.
X
Connection

Building earth
connection/s

I Total

I System

Ie

Ie

Ie 2

Ie test Test

Potential Probe (P)

Current
Probe (C)

Ground
Electrodes

Ie Test > I Total


20

Earth system leakage and current range


Instruments equipped with ART and ICLAMP also have a current
measurement range. This is an important feature; it enables the
operator to check if there is current flowing, should an
electrode have to be disconnected from a system, ensuring his
safety

11

The slope method


When testing very large earth systems, such as that encountered
on large substations, it may be impractical to get the required
auxiliary P and C spike distances. The result is that the plotted
resistance curve would not have a flat area, remain a slope. In
this method three measurements are taken, inserted into a
formula and a value calculated. This value can then be looked up
in a table to find the correct P spike distance required to measure
the true resistance of the system under test.

Imeas

=(R3-R2)/(R2-R1)
Emeas

R = Emeas/Imeas

P1 (ES)

C2 (H)

C1 (E)

0.2B

R1= 9.3 ohm


R1
B

Imeas

=(R3-R2)/(R2-R1)
E meas

R = Emeas/Imeas

P1 (ES)

C2 (H)

C1 (E)

R1= 9.3 ohm


R2= 16 ohm

0.4B

Earth
electrode
under test

R2
B

Imeas

=(R3-R2)/(R2-R1)
Emeas

= (19.2 16) / (16 9.3)

R = Emeas/Imeas

P1 (ES)

C2 (H)

C1 (E)

0.6B

R1= 9.3 ohm


R2= 16 ohm
R3= 19.2 ohm

R3

12

Imeas

=(R3-R2)/(R2-R1)
Emeas

= (19.2 16) / (16 9.3)

R = Emeas/Imeas

P1 (ES)
C1 (E)

C2 (H)

P2 (S)
0.2B
0.4B

R1

R2

0.6B

R3

=0.478

Auxiliary test
electrodes

The resulting value of u (which in this example = 0.478) is then


looked up in the table shown below. In this example the correct
earth system resistance would be measured with the P spike at
0.632, or 63.2% of the C spike distance from the electrode under
test.

Chart for use with the Slope Method


Values of Pt / dc for Values of

Pt / dc
Pt / dc
0.4
0.643
0.8
0.58
0.41
0.642
0.81
0.579
0.42
0.64
0.82
0.577
0.43
0.639
0.83
0.575
0.44
0.637
0.84
0.573
0.45
0.636
0.85
0.571
0.46
0.635
0.86
0.569
0.47
0.633
0.87
0.567
0.48
0.632
0.88
0.566
0.49
0.63
0.89
0.564
0.5
0.51
0.52
0.53
0.54
0.55
0.56
0.57
0.58
0.59

0.629
0.627
0.626
0.624
0.623
0.621
0.62
0.618
0.617
0.615

0.9
0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99

0.562
0.56
0.558
0.556
0.554
0.552
0.55
0.548
0.546
0.544

1.2
1.21
1.22
1.23
1.24
1.25
1.26
1.27
1.28
1.29

Pt / dc
0.494
0.491
0.488
0.486
0.483
0.48
0.477
0.474
0.471
0.468

1.3
1.31
1.32
1.33
1.34
1.35
1.36
1.37
1.38
1.39

0.465
0.462
0.458
0.455
0.452
0.448
0.445
0.441
0.438
0.434

Values of Pt / dc for Values of

Pt / dc

13

0.6
0.61
0.62
0.63
0.64
0.65
0.66
0.67
0.68
0.69

0.614
0.612
0.61
0.609
0.607
0.606
0.604
0.602
0.601
0.599

1
1.01
1.02
1.03
1.04
1.05
1.06
1.07
1.08
1.09

Pt / dc
0.542
0.539
0.537
0.535
0.533
0.531
0.528
0.526
0.524
0.522

1.4
1.41
1.42
1.43
1.44
1.45
1.46
1.47
1.48
1.49

Pt / dc
0.431
0.427
0.423
0.418
0.414
0.41
0.406
0.401
0.397
0.393

0.7
0.71
0.72
0.73
0.74
0.75
0.76
0.77
0.78
0.79

0.5797
0.596
0.594
0.592
0.591
0.589
0.587
0.585
0.584
0.582

1.1
1.11
1.12
1.13
1.14
1.15
1.16
1.17
1.18
1.19

0.519
0.517
0.514
0.512
0.509
0.507
0.504
0.502
0.499
0.497

1.5
1.51
1.52
1.53
1.54
1.55
1.56
1.57
1.58
1.59

0.389
0.384
0.379
0.374
0.369
0.364
0.358
0.352
0.347
0.341

SAFETY NOTES
There is always the possibility that a fault in a power system will
cause high current to flow into the ground system while the test
is in progress. This may cause unexpected high voltages to
appear at the current and voltage probes and also at the
terminals of the instrument. The person responsible for the tests,
taking into account potential fault current and expected step
and touch potentials, must evaluate this risk, take suitable
precautions, and observe safe systems of work.

The clamp on or stakeless method

ICLAMP

Building earth
connection/s
VCLAMP

Ground
Electrode
Under
Test

ICLAMP

R Meas.
VCLAMP

R4
25 Ohms

R3
22 Ohms

R2
19 Ohms

R1
25 Ohms

R test
45 Ohms

R Meas. = R test + 1 / (1/R1 + 1/R2 + 1/R3 + 1/R4)

14

= 50.6 Ohms

This method measures the resistance of the loop including all


connections and cables and is ideal for many applications,
including lightning protection. The readings taken are ideal for
comparative condition monitoring testing.

Intersecting curves, star delta and four potential methods


These 3 methods are either very complex, time consuming or
both! Details of their specific applications, advantages and
disadvantages along with their operational procedures - can be
found in the Megger publication Getting Down To Earth,
available as a free PDF download from
http://bit.ly/earthtestingguide

Intersecting Curves

Imeas

E meas

R = Emeas/Imeas

P1 (ES)
R1

C1 (E)

R2

R3

R4

R5

R6

P2 (S)

C2 (H)

Earth electrode
under test
0.2B

Auxiliary test
electrodes
0.4B
0.5B
0.6B
0.7B
0.8B
B

15

Selecting Earth System / Electrode Test Method Chart


Method

Best
Application

Advantages

Limitations

Small electrode
systems;
Complex
system if full
resistance
curve is plotted.
2. Simplified
Small and
Fall of
medium
Potential
electrode
systems
3. 61.8% Rule Small and
medium electrode
systems

Extremely reliable;
conforms to IEEE 81;
ART (with clamp) no
requirement to
disconnect electrode.

Requires long distances


(and long test leads) on
medium and large
systems; time
consuming.

Easier than Fall of


Potential; much faster.

4. Slope

Knowledge of electrical
centre not required.
Long distance to
probes not required
Quick and simple to
perform
Knowledge of electrical
centre not required.
Long distance to
probes not required
Long distances for test
probe positioning not
necessary

Ineffective if the electrical


centre unknown. Less
accurate than Fall of
Potential.
Assumes perfect
conditions; ineffective if
electrical centre is
unknown; soil must be
homogeneous; less
accurate
Susceptible to nonhomogeneous soil; less
accurate; requires maths

1. Fall of
Potential

Large systems
like substations

5. Dead Earth
(2 pole)
6. Intersecting
Curves

Not
recommended
Large systems
like substations

7. Star Delta

Ground
systems
located in
urban areas
and/or rocky
terrain
Medium to
large ground
systems
Simple ground
system with
existing return
path through
multiple
grounds

8. Four
Potential
9. Clamp-on /
Stakeless

Simplest to carry out;


minimal calculation;
fewest number of test
probe moves

Problems with resistance


overlap.
Numerous calculations
and drawing of curves

Resistance areas should


not overlap; a number of
calculations required

Knowledge of electrical
centre not required

Long distances to test probes is s


required; a number of calculations

Quick, easy; includes


bonding and overall
connection resistance

Effective only in
situations with multiple
grounds in parallel

16

Earth loop impedance testing

When looking at making measurements of Earth loop


Impedance, or Prospective Fault Current (PFC) for that matter, it
is always worth remembering why the reading is being taken. All
too often time is lost on site because the principle of what the
test is expected to prove is lost.
Loop testing could be described as a Dark Art it is the most
difficult measurement taken by the electrical contractor on his
day to day business. By difficult, it should be clarified that the
difficulty remains in the method of obtaining the elusive, stable,
repeatable reading we all look for, not the application of the
test itself. When you look at and compare the principles of
continuity, insulation, loop or RCD testing, loop tests should not
cause the level of consternation that they do. It is a simple test.
What is the resistance that a fault between live and earth will be
subjected to? Earth loop testing has been carried out for
decades, so why do we still get fluctuating readings on certain
circuits or worse still, readings that on the face of it would
condemn an installation?
Test equipment manufacturers continue to search for the Holy
Grail of earth loop test techniques one test that can be used on
any circuit, at any location, on any voltage, that will give us the
stable accurate reading we desire. With each technological
advance in testing, circuits and their components change,
throwing obstacles in to the path of the poor loop impedance
tester! What we hope this booklet will do is give you an insight
into the different techniques that are available on the market
today and arm you with the knowledge to go about your daily
routine, confident in the readings being taken and recorded.

17

What is the loop and why do we test it?


If a fault occurs in an electrical system, we must prove that the
over-current device will operate within the prescribed time by
ensuring that the circuit impedance is low enough to allow
sufficient current to flow. The required values of impedance and
time will change dependent upon the type of installation (TN/TT
etc.) and the type of protection, whether it be a miniature circuit
breaker (MCB), cartridge fuse or re-wireable fuse for example.
The fault current can either be in the Line-Neutral or Line-Earth
circuit, so there is a need to confirm the loop impedance of each.

18

Earth fault loop return path TNC-S installation

The testing of the Line-Neutral loop impedance does not throw


up many issues as the circuit has no earth leakage protection and
a straight forward high current test returns repeatable, stable
readings.

Loop impedance tests methods


As it stands today, most contractors will use one of 5 different
test techniques when loop impedance testing:

2-wire high current test


2-wire No-Trip d.c. saturation test (Obsolete)
3-wire No-Trip test
2-wire No-Trip test
4-wire grid impedance test

Determining which test to use will depend upon a number of


factors, not least being which one is available on the test meter
being used! The following information will hopefully go some

19

way to explain some of the applications and limitations of these


different options when in the field.

2-wire high current test


This is the traditional loop impedance test. Using a test current of
up to 20 A and a simple 2 wire connection, it is by and large the
fastest, most accurate test available on a day to day basis. Most
standard loop impedance testers will incorporate this type of
test. Because of the relatively high test current, the readings are
not generally influenced by external factors and will return
repeatable, stable readings in most scenarios.
Unfortunately, it does have its limitations. When first conceived,
earth leakage monitoring RCDs and RCBOs were not part of the
electrical installation and because it relies on a short between
Line-Earth for the earth loop test, albeit only for 2 cycles (or 40
ms) of the AC waveform, the test will cause the RCD/RCBO to
operate. In addition, some early instruments whose test time was
not so tightly restricted had cause to operate some of the low
current MCBs as well. Where earth leakage protection was in
place, the contractor was left with no option but to bypass it to
allow for the test to be undertaken a time consuming and
rather un-safe practice as it left the system unprotected for the
duration of the test.
That said, this test still has its place in a contactors toolkit and
should be the go to solution wherever possible. When carrying
out a Ze measurement of an installation or taking a Zs reading
on an unprotected circuit, this is still the most accurate, easiest
test to use.

20

2-wire No-Trip d.c. saturation test


To overcome the problems caused by the introduction of earth
leakage protection, a test technique was developed whereby a
DC test current was injected in to the circuit prior to carrying out
a standard 2 wire high current test. The aim of this DC test was
to saturate the monitoring coil within the RCD, allowing enough
time for the high current AC test to be carried out. This
anesthetising effect proved very effective. At the time, there
were claims that the saturation left the coil in a potentially
unresponsive state, but this was never substantiated.
However, due to the increase in electronic RCDs, this method
now has limited applications with some newer RCDs and RCBOs
specifically monitoring for DC voltage being present on the
system. This technique is no longer incorporated within the
current range of instruments on the market.

3-wire No-Trip test


The 3 wire method of no-trip loop testing has become the norm
over the past 20 years. This test method overcame the need to
by-pass even the new electronic protection devices by utilising a
low current Line-Earth test current, whilst still returning a degree
of accuracy. Not having to by-pass the RCD/RCBO obviously
introduced a time saving factor. In addition, by having the
requirement of connecting to Line, Neutral and Earth, the testers
were now able to confirm the presence of all three as well as
indicate if there was a reverse polarity at the test point and, due
to the limited test current, there was no issue with tripping the
MCB.
There remain limitations with the 3-wire test however. Due to
the lower test current, readings became more susceptible to

21

external factors (much more on these later) introducing


instability on certain circuits and a reduction in consistency. In
some circumstances the internal impedance of the RCD can be
seen or existing system earth leakage can combine with the test
signal to cause the protective device to operate.

2-wire No Trip test


The 2 wire no-trip option has come and gone in various guises
over the years. Some testers opted for a low current test, but this
affected accuracy on the low end, where as other techniques
never proved accurate and were dropped as soon as they were
launched.
The latest 2-wire no-trip units have a much improved technique
offering far better repeatability, but still suffer from limitations.
Obviously, they will allow for testing most RCDs and RCBOs
without having to bypass them. With no neutral connection
required, they maintain a true 2-handed operation, but will no
longer indicate reverse polarity or warn of a missing neutral. The
test current does not combine with existing leakage, so there
is no accumulation effect, as suffered by the 3 wire test.
Although the physical test time is similar to that of the 3-wire
method, the time saving of not having to bypass the RCD still
makes for a more efficient test. External factors can again affect
the reading taken, but the simplicity of 2 handed testing can
outweigh this limitation in a lot of cases.
The Megger range of loop and multifunction testers also
incorporate an Auto-Start feature, whereby once the probes
are connected and the voltage verified, the test will
automatically start alleviating the need to clip one of the leads
to free up a hand to press the test button

22

4-wire grid impedance test


This new method of testing will only be undertaken in certain
circumstances. The test uses a 4 wire Kelvin connection, negating
internal lead and contact resistance; such is the accuracy of the
test. With test currents up to 1000 A, measurements down as low
as 10 mOhm can be accurately made. Consequently, there is no
No-Trip option with this test method. With specific
applications being measurement in sub-station/switch room
environments, this tester gives the test engineer the ability to
take accurate readings when sited next to the main transformer
something that has caused problems for many years when
trying to sign off jobs with readings based on design engineers
calculations down as low as 0.001 Ohm!
As stated, this test set will have a limited market,
notwithstanding the size and cost of the unit, but also the safety
aspect of working in HV environments.

23

Test instrument accuracy


Having an understanding of the published accuracy and
uncertainties for the test equipment you use is paramount. Test
equipment manufacturers have an obligation to stamp on the
instrument the accuracy the operator can expect on any given
range and interpreting this can alleviate a number of queries
raised when deducing results.
BS EN61557-3 requires that loop testers measure no worse than
30% accuracy across a stated range, in the presence of
operational uncertainties. Achieving this is no great feat, but
manufacturers realise that this would fall far short of the
repeatability in readings required to instil confidence when using
their instruments. As such, the accuracy statements you see will
far exceed this requirement.
It should be noted, however, that accuracy will normally be
shown across a measuring range so, for example, on the Megger
MFT1700 series multifunction tester, for a high current loop test
the accuracy is claimed for the range 0.1 to 1000 , compared
to 1 to 1000 for non-trip testing.
Guidance Note 3 Inspection & Testing talks about basic
measurement accuracy of 5%. Here, the discrepancy between
basic and operational accuracy is introduced. To clarify, basic
accuracy can be deemed to be achieved within controlled
laboratory type conditions, whereas operational accuracy looks
at real world, field readings. It goes on to state that operational
accuracy is always worse than basic accuracy.
The Electrical Safety Council publication back up this
measurement discrepancy in their published Best Practice Guide
No.7 Test Instruments for Electrical Installations: Accuracy and
Consistency where they state that readings on a high current
test will be susceptible to errors once readings below 0.2 are

24

being made, whereas on the no-trip test ranges, anything below


1.0 will be subject to significant errors. They recommend taking
multiple readings if there is any concern about the result of a
test.

Real world example


Accuracy needs to be looked at and understood. Here are 2
examples:
Example A: Range: 0.1 to 1000 Accuracy: 5% +/- 0.05 digits
Example B: Range: 0.1 to 1000 Accuracy: 3% +/- 0.1 digits
In this example, we have a known clean loop impedance value of
0.5
Example A:

5% +/- 0.05 digits

5% accuracy = 0.03 add the 5 Digits = +/- 0.08


Therefore, before any external influence, any reading between
0.42 & 0.58 is acceptable! (Variation 0.16 )
Example B:

3% +/- 0.1 digits

3% accuracy = 0.015 add the 0.1 Digits = +/- 0.115


Therefore, before any external influence, any reading between
0.385 & 0.62 is acceptable! (Variation 0.23 )

What this goes to prove is the acceptable range that an


instrument can be deemed to be accurate and just as
importantly, a claimed 3% accuracy against 5%, pales in to
insignificance when you take account of the +/- digits.

25

External factors influence measured values


When making a loop impedance measurement, there are
numerous challenges that the test signal has to overcome. Some
are physical and some are man-made. Having an understanding
of the limitations of the various tests that are available goes
some way in overcoming some of these obstacles.
Just as importantly, knowing the significance of the desired value
(usually stipulated by regulation) and an appreciation of the
measured value in the real world will help to maintain
confidence in the recorded value. Below are a number of factors
that will directly influence the readings being taken on a day to
day basis, and the challenge is appreciating these and the fact
that some are unavoidable and outside of your or the test
equipments control.

Line waveform distortion In the UK we rely on the 50Hz


supply being a smooth sinusoidal waveform. Unfortunately, due
to the explosion of switch mode power supplies, power factor
correction equipment and inverter drives, this is no longer the
case. Clipped or distorted waveforms can have a significant
influence on the test signal. Repeat testing can usually average
out any issues arising from waveform issues.

26

Harmonic disturbance This has now earned the right of a


section within the 17th Edition and the problems severe
harmonics can cause are being formally documented to a far
greater extent. The detrimental effect on a loop test signal can
be significant, but repeat testing, again, can often overcome this.

Line noise Somewhat different to harmonic disturbance, line


noise can be a general background signal, superimposed over the
normal 50Hz supply. Again this can play havoc with a test signal
especially the no-trip techniques. Testing at different times is
probably the best solution, as noise will often fluctuate
throughout a 24hr period.

27

Proximity of transformer As stated earlier in this booklet, we


are not looking to venture into the physics of the testing, but
suffice to say, when in close proximity of a transformer, the
hand-held units available on the market today will struggle to
return repeatable readings, when the calculated value is in the
realms of milliohms and well below the stated range of the
instrument. A work around is shown a bit later in this booklet.

Ambient temperature Probably the most overlooked factor


that can influence a reading. The changes due to ambient
temperature may not be huge, but when making comparative
readings, it is always worth bearing in mind when the original
values were obtained.

Line transients and spikes These do not have to be massive


over voltages. More often than not they may well be recorded as
sags and swells by line monitoring equipment. Most are manmade and are due to switching either at the substation or from
larger industrial complexes running from the same grid. Again,
repeat testing will help to alleviate any issues with readings.

28

Test lead resistance The one part of any manufacturers test


equipment that will be slated more than anything else is
ordinarily the test leads. They are the one mechanical component
that will be subject to wear and tear, over and above any other
component of the test kit. Regular checks should be carried out,
especially against known values, as deterioration of lead contact
resistance is rarely picked up as it is a gradual phenomenon.
Some operators will replace their leads 2 or 3 times a year,
whereas some look to change them only when a major issue
arises. Regular inspection and checks should overcome any
problems the leads may end up giving.

Contact resistance This may be a subjective issue, but can be


proven on most installations. Whether the resistance is
generated by accessibility to the test point, or due to wear on a
socket, it is easily rectified. Firm, constant pressure is required
across the contact points and even applying a test probe to the
centre of a screw as opposed to the outer edge can have a
significant affect. With regards to a double socket, always look
to test on both as it may be that one is favoured by the usual
operator (the cleaner using 1 socket daily, for example). Other
examples may be RCD internal resistance due to oxidisation.
Testing and resetting can often overcome this factor.

Inductance and capacitance These can often be unknown


quantities when testing. Capacitance can be seen to be charged
by the test signal, therefore directly affecting the reading taken.
Inductance would not ordinarily affect a standard test (it is
primarily associated with coils of cable) but when testing a third
party installation it is a factor that could influence the result if
found to be present. Repeat testing at various points on a circuit
can usually alleviate the discrepancy seen.

29

When some of the issues faced when taking a simple loop


impedance test are listed out, you start to get a better
understanding of how these can easily influence the reading
being taken. Added to this, the variation that the instrument can
show whilst still be working within design /accuracy standards, it
is easy to see why the loop test causes more head scratching than
any of the other readings being taken.
The digital age has been our undoing in all this. If we return to
the 1970s when we had our traditional analogue balanced
moving iron coils, if the reading swung anywhere below 1 or 2
ohms we were happy.

30

Testing at source simple work-around


One technique that goes someway to obtaining a more stable,
repeatable reading when taking measurements close to the
source of supply is to add additional resistance to the circuit
being measured. Notwithstanding the stated accuracy of the
instrument range, if a known resistive value is placed in series
with the test circuit, by deducting this away from the measured
value a reading for the circuit can be obtained. In some
instances, the additional resistance need not be great, for
instance, a long test lead set with a known value of 0.15 may be
sufficient. The 2 wire high current test must be used and
numerous readings taken to give an average.

31

PFC and PSCC testing


Prospective fault current and prospective short circuit testing are
measurements that are made to calculate the current that will
flow in the event of a fault. Too little current and protective
devices may fail to operate in time (if at all) and too much
current will cause damage to equipment, may cause fire or
prevent the breaker from operating.
Interestingly, the calculation should be made using the nominal
supply voltage value and not the measured voltage.

Loop impedance, either earth loop or line-neutral, will have a


greater influence on the PFC/PSCC value the smaller they get,
causing issues when taking measurements below the stated
range of an instrument. Any PFC measurement should be taken
using the high current option no-trip test ranges should only be

32

used for verification. If a critical measurement is being made, it


should always be confirmed by calculation against design
specifications.

PFC v Earth Resistance (230 V Supply)


@ 50 ohms to earth
PFC = 230/50 = 4.6 A (0.0046 kA
@ 0.5 ohms to earth
PFC = 230/0.5 = 460 A (0.46 kA
@ 0.1 ohms to earth
PFC = 230/0.1 = 2300 A (2.3 kA)
@ 0.05 ohms to earth
PFC = 230/0.05 = 4600 A (4.6 kA)

33

Loop testing summary


This booklet started out by saying that when loop impedance
testing, you should not lose sight of why the test is being carried
out. All too often a fluctuating reading or a reading higher or
lower than you would have expected causes additional time to
be spent on site, when in essence; the difference can be seen as
negligible. Again, this harks back to the digital age our brains
process 0.39 to be VASTLY different to 0.51 as a reading, yet
in essence, with a difference of 0.12 this could be explained as
an accuracy fluctuation.
It is worth remembering the requirements laid out in
BS7671:2008

Typical 32A Circuit with BS EN 60898 Breaker


Type B Zs < 1.16 (Domestic)
Type C Zs < 0.58 (Inductive/Resistive Loads)

Typical 6A Circuit with BS EN 60898 Breaker


Type B Zs < 6.16 (Domestic)
Type C Zs < 3.09 (Inductive/Resistive Loads)
Values from GN3 Table B4 (80% Rule Applied)

34

And remember

Maximum Zs to Ensure (Non-Delayed) RCD


operation to BS EN 61008-1 & BS EN 61009-1 for
final circuits not exceeding 32 Amp
30mA on 230V circuit < 1667 *
100mA on 230V circuit < 500 *
300mA on 230V circuit < 167
(based on a touch voltage limit of 50 V)
*A value exceeding 200 may not be stable.
I hope this booklet has proved interesting and perhaps useful in
clarifying some of the issues faced day to day when undertaking
earth and loop measurements. If you need more information on
any of the subjects, a quick visit to the internet using your
favourite search engine will return plenty of additional technical
papers, delving in to the physics of what we have brushed upon
today.

35

If I can ask you to take one thing away from reading this
booklet, that I believe will make your life easier when out
testing, it would be the following:
When testing use the best available test in the following order of
preference

2 Wire High Current Test


3 Wire No-Trip Test
2 Wire No-Trip Test

One final statement.

Where the possibility of accidentally tripping an RCD


is NOT ACCEPTABLE, loop impedance testing should
not be performed, as it is impossible to absolutely
guarantee an RCD will not trip during a loop
impedance test.

36

37

38

39

Archcliffe Road
Dover
CT17 9EN
E: [email protected]

40

You might also like