Earth Electrode and Loop Booklet V2
Earth Electrode and Loop Booklet V2
Earth Electrode and Loop Booklet V2
and
earth loop impedance testing
Theory and applications
Contents
Introduction
Resistivity v resistance
17
18
19
24
26
31
32
34
Introduction
As two of the most common testing subjects debated amongst
electricians - as well as generating the highest percentage of calls
to the Megger Technical Support desk - this series of
presentations and supporting booklet hope to clarify some of the
obstacles faced by an electrical contractor, or test and inspection
engineer, out testing today.
The intention is not to delve in to the physics of the tests, but
rather look at the practical issues relating to the measurements.
We will also clarify the different test techniques, detail some of
the reasons why fluctuating values will be seen and hopefully
instil a greater confidence in the day to day results obtained
when testing in the field.
This booklet, although designed to be read in isolation, is in no
way a definitive guide. There have been written a plethora of
articles and application notes and it is recommended that should
further information be required, a quick search of the internet
will return a wealth of additional material, from basic How To
guides, to complete scientific papers on the subjects.
Resistivity v resistance
When talking about earth electrode testing, there are two basic
test types: earth resistivity and earth system resistance. In a
nutshell, resistivity testing is used when looking to site a new
earthing system and system resistance testing is used to check an
existing resistance is low enough for a desired application.
Resistivity
Resistivity testing is primarily used when surveying an area, prior
to sinking rods, mesh, mats etc. Soil resistivity can vary across a
site by significant amounts and the cost implications involved
make surveys invaluable in identifying the optimal location to
locate the new installation. There are numerous factors that will
influence the resistance readings obtained the soil composition,
the moisture level and temperature as well as geographic
features within the ground.
In addition, when surveying, the variables of moisture content,
water table level and temperature have to be accounted for as
these will change dependent upon the season. Fairly obviously,
as the moisture content of the soil increases, the resistance value
decreases, so an allowance would have to be made for readings
taken in mid-winter as opposed to a reading taken through the
summer months.
The most popular method for earth resistivity surveys is the
4-pole (Wenner method), utilised with the standard formula for
average earth resistivity:
p = 2 AR
Where:
is average earth resistivity to depth A in ohm-cm
A is the distance between the spikes
R is the resistance read from the earth tester
Imeas
Emeas
C1 (E)
P1 (ES)
P2 (S)
C2 (H)
<A/20
This cm value is of interest to a design engineer, because by rearranging the formula and utilising published tables, the
resistance of the earth electrode required can be calculated:
p = 2 AR ( cm)
criteria will dictate what values are necessary and these should
be referred to in all cases.
Earthing systems fall within 2 categories: Simple or Complex.
Simple systems consist of either a single or small number of
electrodes driven in to the ground, whereas a complex system
will have multiple earthing points.
So what makes up an earth electrode resistance value? There are
3 main components involved:
1. Resistance of the electrode itself (dependent on material)
and the connections to it
2. Contact resistance between the electrode and the soil it
is driven into
3. Resistance of the surrounding body of soil
1 - Electrode resistance will vary slightly due to the type of
material used. Copper is the preferred material for earth rods
and mats, but it is not uncommon to find steel or iron used. The
resistance value between the materials is measurable but not
normally significant. Contact resistance between connections is
where issues may arise primarily down to incorrect termination
techniques or corrosion.
2 - Contact resistance is often thought of as one of the main
contributors to high earth resistance readings, but provided the
electrode is free from paint and grease and the earth is packed
firmly, the value is negligible
3 - Finally, an electrode driven in to the earth of uniform
resistivity will radiate current in all directions. By envisaging the
electrode surrounded by shells of earth of equal thickness, it is
easy to realise that the nearest shell will have the smallest
surface area, but as you move further away the surface area of
each shell is somewhat larger and offers less resistance. Finally, a
distance from the electrode will be reached where additional
Effect of temperature
C
Resistivity (Ohm-cm)
20
10
0 (water)
0 (ice)
-5
-15
7,200
9,900
13,800
30,000
79,000
330,000
100 - 5,000
200 - 10,000
5,000 - 100,000
10,000 - 1,000,000
500 - 10,000
2,000 - 200,000
100,000
1,000 - 10,000
C1 (E)
P1 (ES)
Imeas
Emeas
Earth electrode
under test
P2 (S)
C2 (H)
Current
Probe (C)
Ground
Electrode
Under
Test (X)
Potential
Probe (P)
Position
Current
Probe (C)
Resistance in Ohms
Resistance in Ohms
True system
resistance
measured
here
X
Ground
Electrode
Position
Current
Probe
Position
Ground
Electrode
Position
C
Current
Probe
Position
61.8% rule
Assuming the C spike is far enough away from the electrode
under test, the soil mass is homogenous, and there are no buried
objects the correct P spike position will always be at 61.8% of the
distance from the electrode/s under test and the C spike.
This is definitely a rule to be treated with great care.
10
Building earth
connection/s
I Total
I System
Ie
Ie
Ie 2
Ie test Test
Current
Probe (C)
Ground
Electrodes
11
Imeas
=(R3-R2)/(R2-R1)
Emeas
R = Emeas/Imeas
P1 (ES)
C2 (H)
C1 (E)
0.2B
Imeas
=(R3-R2)/(R2-R1)
E meas
R = Emeas/Imeas
P1 (ES)
C2 (H)
C1 (E)
0.4B
Earth
electrode
under test
R2
B
Imeas
=(R3-R2)/(R2-R1)
Emeas
R = Emeas/Imeas
P1 (ES)
C2 (H)
C1 (E)
0.6B
R3
12
Imeas
=(R3-R2)/(R2-R1)
Emeas
R = Emeas/Imeas
P1 (ES)
C1 (E)
C2 (H)
P2 (S)
0.2B
0.4B
R1
R2
0.6B
R3
=0.478
Auxiliary test
electrodes
Pt / dc
Pt / dc
0.4
0.643
0.8
0.58
0.41
0.642
0.81
0.579
0.42
0.64
0.82
0.577
0.43
0.639
0.83
0.575
0.44
0.637
0.84
0.573
0.45
0.636
0.85
0.571
0.46
0.635
0.86
0.569
0.47
0.633
0.87
0.567
0.48
0.632
0.88
0.566
0.49
0.63
0.89
0.564
0.5
0.51
0.52
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.629
0.627
0.626
0.624
0.623
0.621
0.62
0.618
0.617
0.615
0.9
0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
0.562
0.56
0.558
0.556
0.554
0.552
0.55
0.548
0.546
0.544
1.2
1.21
1.22
1.23
1.24
1.25
1.26
1.27
1.28
1.29
Pt / dc
0.494
0.491
0.488
0.486
0.483
0.48
0.477
0.474
0.471
0.468
1.3
1.31
1.32
1.33
1.34
1.35
1.36
1.37
1.38
1.39
0.465
0.462
0.458
0.455
0.452
0.448
0.445
0.441
0.438
0.434
Pt / dc
13
0.6
0.61
0.62
0.63
0.64
0.65
0.66
0.67
0.68
0.69
0.614
0.612
0.61
0.609
0.607
0.606
0.604
0.602
0.601
0.599
1
1.01
1.02
1.03
1.04
1.05
1.06
1.07
1.08
1.09
Pt / dc
0.542
0.539
0.537
0.535
0.533
0.531
0.528
0.526
0.524
0.522
1.4
1.41
1.42
1.43
1.44
1.45
1.46
1.47
1.48
1.49
Pt / dc
0.431
0.427
0.423
0.418
0.414
0.41
0.406
0.401
0.397
0.393
0.7
0.71
0.72
0.73
0.74
0.75
0.76
0.77
0.78
0.79
0.5797
0.596
0.594
0.592
0.591
0.589
0.587
0.585
0.584
0.582
1.1
1.11
1.12
1.13
1.14
1.15
1.16
1.17
1.18
1.19
0.519
0.517
0.514
0.512
0.509
0.507
0.504
0.502
0.499
0.497
1.5
1.51
1.52
1.53
1.54
1.55
1.56
1.57
1.58
1.59
0.389
0.384
0.379
0.374
0.369
0.364
0.358
0.352
0.347
0.341
SAFETY NOTES
There is always the possibility that a fault in a power system will
cause high current to flow into the ground system while the test
is in progress. This may cause unexpected high voltages to
appear at the current and voltage probes and also at the
terminals of the instrument. The person responsible for the tests,
taking into account potential fault current and expected step
and touch potentials, must evaluate this risk, take suitable
precautions, and observe safe systems of work.
ICLAMP
Building earth
connection/s
VCLAMP
Ground
Electrode
Under
Test
ICLAMP
R Meas.
VCLAMP
R4
25 Ohms
R3
22 Ohms
R2
19 Ohms
R1
25 Ohms
R test
45 Ohms
14
= 50.6 Ohms
Intersecting Curves
Imeas
E meas
R = Emeas/Imeas
P1 (ES)
R1
C1 (E)
R2
R3
R4
R5
R6
P2 (S)
C2 (H)
Earth electrode
under test
0.2B
Auxiliary test
electrodes
0.4B
0.5B
0.6B
0.7B
0.8B
B
15
Best
Application
Advantages
Limitations
Small electrode
systems;
Complex
system if full
resistance
curve is plotted.
2. Simplified
Small and
Fall of
medium
Potential
electrode
systems
3. 61.8% Rule Small and
medium electrode
systems
Extremely reliable;
conforms to IEEE 81;
ART (with clamp) no
requirement to
disconnect electrode.
4. Slope
Knowledge of electrical
centre not required.
Long distance to
probes not required
Quick and simple to
perform
Knowledge of electrical
centre not required.
Long distance to
probes not required
Long distances for test
probe positioning not
necessary
1. Fall of
Potential
Large systems
like substations
5. Dead Earth
(2 pole)
6. Intersecting
Curves
Not
recommended
Large systems
like substations
7. Star Delta
Ground
systems
located in
urban areas
and/or rocky
terrain
Medium to
large ground
systems
Simple ground
system with
existing return
path through
multiple
grounds
8. Four
Potential
9. Clamp-on /
Stakeless
Knowledge of electrical
centre not required
Effective only in
situations with multiple
grounds in parallel
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
And remember
35
If I can ask you to take one thing away from reading this
booklet, that I believe will make your life easier when out
testing, it would be the following:
When testing use the best available test in the following order of
preference
36
37
38
39
Archcliffe Road
Dover
CT17 9EN
E: [email protected]
40