SPECIFICATION
N
ECG-UG-00-001
DATE
06/12/00
USER'S GUIDE
TITLE: PRO-DIALOG CONTROL 4 FOR AIR & WATER COOLED
CHILLERS SERIES 30 GX & HXC VERSION 2
REV: original
ORIGINATOR
COPY #
1
ECG-UG-02-002
Rev: original
Ba-Tung PHAM
NAME
Carrier Service
COMPANY
Carrier
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page: /98
ECG-UG-02-002
Rev: original
Page:2 /98
CONTENTS
1 - INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 - About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 - Manual Structure and contents . . . . . . . . . . . . . . . . . . 4
2 - GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 - Generalities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 - Software Reference Number . . . . . . . . . . . . . . . . . . . .
2.3 - Abbreviations Used . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
4
7
7
3 - HARDWARE DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 - Produc Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1.1 - Basic Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1.2 - CCN/Clock Option Board . . . . . . . . . . . . . . . . . 10
3.1.3 - Screw Compressor Protection Module . . . . . 11
3.1.3.1 - Screw Compressor Module Layout 11
3.1.3.2 - Compressor Part Number/MTA Header
Configuration . . . . . . . . . . . . . . . . . . . . 12
3.1.4 - 4 xDO Board . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.4.1 - General . . . . . . . . . . . . . . . . . . . . . . . .
3.1.4..2 - Terminal J4 Description . . . . . . . .
3.1.5 - AUX Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.5.1 - General . . . . . . . . . . . . . . . . . . . . . . . .
3.1.6 - EXV Driver Board . . . . . . . . . . . . . . . . . . . . . . . .
3.1.7 - 4 x AI - 2 x AO Board . . . . . . . . . . . . . . . . . . . .
3.1.8 - Aquasnap Basic Board . . . . . . . . . . . . . . . . . .
12
12
12
13
13
14
14
16
4 - CONTROL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . 20
32
32
33
Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1 - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.2 - Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.2.1 - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.2.2 - Main Interface Configuration sub menu
structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.2.3 - Factory Configuration . . . . . . . . . . . . . . . . . . . 21
4.2.3.1 - Factory configuration from Service
Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2.3.2 - Factory configuration from Main
Interface . . . . . . . . . . . . . . . . . . . . . . . . 23
4.2.3.3 - Economizer TQ valve Feedback
Signal Wiring . . . . . . . . . . . . . . . . . . . . 24
32
32
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: original
CONTENTS
6 - CCN COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7 - PRO_DIALOG 4 DOWNLOADER ADDENDUM
INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Appendix A - CCN DIPSLAY, SETPOINT, MAINTENANCE,
CONFIGURATION TABLE SCREENS . . . . . . . 61
Appendix B - CCN Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Appendix C - Wiring Schemes . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Appendix D - JBUS memory with GX& HX
default configuration . . . . . . . . . . . . . . . . . . . . . . . . 96
Appendix E - SAM Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Appendix F - CCN Network Example . . . . . . . . . . . . . . . . . . . . . 98
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page:3 /98
ECG-UG-02-002
Rev: original
Page: 4/98
1 - INTRODUCTION
1.1 - ABOUT THIS MANUAL
This manual is intended to be used as an additional guide for using and configuring the Pro-Dialog control for
the 30GX & HX chillers. The use of this document does not substitute the IOM.
This manual is intended for use by Service organizations inside the Carrier corporation. It is delivered on
the express condition that it is not to be disclosed, reproduced in whole or in part, or used for
manufacture by anyone other than Carrier Corporation.
2 - GENERAL DESCRIPTION
2.1 - GENERALITIES
PRO-DIALOG is a system for controlling units which use screw compressors:
w Dual circuits
w Air cooled and water cooled chillers
w Non reversible heat machines
PRO-DIALOG controls compressors and loaders needed to maintain the desired leaving or entering water
control point. It automatically sets the position of the electronic expansion valve to maintain a correct refrigerant
flow in the cooler. For air cooled units it controls the operation of the fans to maintain the correct condensing
pressure in each circuit.
Safety circuits in the unit are constantly monitored by PRO-DIALOG to ensure its safe operation. PRO-DIALOG
also gives access to a Quick Test program covering all inputs and outputs excepted compressors outputs.
The control features of the 30GX&HX Pro-Dialog Plus are divided into standard features and options
(additional board needed):
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: original
Standard features:
w
Local control
CCN control
Compressor & loader sequence control (up to 4 compressors - two loaders per compressor)
Ramp loading
Delay at startup
Temperature reset
Diagnostics function
Alarm POC
Varifan control
Reclaim sensors
Page: 5/98
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
FUNCTIONS
HARDWARE
OPTION
FACTORY
CONFIG
Chiller Type
Air Cooled
Water Cooled
Heat Machine
SERVICE
CONFIG
Page: 6/98
USER
CONFIG
No configuration required
Refrigerant R134
Heat Reclaim Option
x
x
Economizer Select
x
No configuration required
Fans
2 Separate Circuits with 1 to 8 fans per circuit
x**
x**
x**
x**
x**
Loading Sequence
Equal
Staged
No configuration required
Delay at startup
Condenser Sensors
x
No configuration required
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
FUNCTIONS
HARDWARE
OPTION
FACTORY
CONFIG
ECG-UG-02-002
Rev: original
SERVICE
CONFIG
Page: 7/98
USER
CONFIG
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: original
3 - HARDWARE DESCRIPTION
3.1 - PRODUCT COMPONENT
This control shall employ the following electronic modules:
Basic Board
NRCP Board
CCN and RTC Board
4 x DO Board (087)
4xAI - 2xAO Board
8 x DO Board (Auxiliary 2)
8xDO - 4xAI - 2xAO Board (Auxiliary 1)
EXV Board
Screw Compressor Protection Module
Local Interface Device 30GX dual circuits
Local Interface Device 30HX dual circuits
Local Interface Device 30GX single circuit
Local Interface Device 30HX single circuit
32 GB 500 182 EE
32 GB 500 052 EE
32 GB 500 062 EE
OP 12AS 004 EE
OP 12AS 005 EE
32 GB 500 312 EE
32 GB 500 322 EE
32 GB 500 192 EE
32 GB 500 232 EE
32 GB 500 092 EE
32 GB 500 112 EE
32 GB 500 082 EE
32 GB 500 102 EE
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page: 8/98
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 9/98
COMPONENT USAGE
UNIT TYPE : WATER COOLED
NUMBER OF COMPRESSORS
COMPONENTS
2[2]
2[2]
2[2]
4 x AI-2xAO BOARD
1[1]
1[1]
1[1]
1[1]
AUX 1 BOARD
1[1]
1[1]
1[1]
1[1]
2[2]
2[2]
2[2]
2[3]
1[3]
1[3]
1[3]
1[3]
1[3]
1[3]
1[3]
1[4]
1[4]
1[4]
1[4]
4 x AI-2xAO BOARD
1[1]
1[1]
1[1]
1[1]
AUX 1 BOARD
1[1]
2[1]
2[1]
2[1]
UNIT TYPE : AIR COOLED - MORE THAN 2 FAN STAGES (if no AUX board) or MORE
THAN 4 FAN STAGES (AUX BOARD) PER CIRCUIT
NUMBER OF COMPRESSORS
COMPONENTS
2[2]
2[2]
2[2]
4x DO BOARD
2[3]
2[3]
2[3]
2[3]
1[3]
1[3]
1[3]
1[3]
1[4]
1[4]
1[4]
4 x AI-2xAO BOARD
1[1]
1[1]
1[1]
1[1]
AUX 1 BOARD
1[1]
1[1]
1[1]
1[1]
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: original
Page: 10/98
CHANNEL
J6
All
J6
All
J6
Master/Slave
J6
Outside Temperature
Air cooled
J6
J6
J7A
All
J7B
All
J7C
All
J7D
All
J8
10
J4
11
All
J4
12
All
J4
13
Heat machine
J4
13
J4
14
All
J4 & J5
J5
FUNCTION
UNIT TYPE
All
J5
17
J5
18
All
J2
19
Cooler Pump #1
All
J2
20
Cooler Pump #2
All
J2
21
Condenser Pump
J2
22
Air cooled
J2
23
Air cooled
J3
24
Alarm Circuit A
All
J3
25
Alarm Circuit B
All
J3
26
All
ECG-UG-02-002
Rev: original
Page: 11/98
N.B :Only Y dip switch of the 4 is used to configure start-delta startup procedure (when in ON
position), the 3 others shall remain OFF ! If not, MTA header configuration alarm will occur.
Connector AI #* Channel#
J9
1
1
J9
2
2
J10A
3
3
J10B
4
4
Type
5K thermistor
5K thermistor
0-5V pressure transducer
0-5V pressure transducer
Usual Functions
Compressor temperature
Discharge Gas Temperature
Economizer pressure
Oil pressure
Connector CT #* Channel#
J8
1
J8
2
J8
3
Connector DI #* Channel#
J7
1
5
J6
2
6
Type
Current sensor 1
Current sensor 2
Current sensor 3
Type
Dry contact
Dry contact
Usual Functions
Current Phase #1
Current Phase #2
Current Phase #3
Main Functions
High Pressure
Oil level
Connector DO #*
Channel#
J3
J3
J4
J2
J2
J2
1
2
3
4
5
6
7
8
9
12
13
14
J2
J2
7
8
10
11
Type
Load max
(Voltage,power)
Relay/Triac 115VAC, 250VA
Relay/TRiac 115VAC, 70VA,
115VAC,145VA,Triac
24VAC ,10VA
Triac
24VAC, 26 VA
Triac
24VAC, 10VA
Triac
Triac
Triac
24VAC, 10VA
24VAC, 10VA
Main Functions
Compressor output D
Compressor output Y
Oil pump
Oil solenoid
Motor cooling #1
Motor cooling #2 or economizer valve for
circuit which has 2 compressors
Loader #1
Loader #2
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: original
Page: 12/98
Tons
MTA
(for 400V)
06NA2300S5E
80
298
01111100
06NA2300S5N
80
240
01011111
06NA2250S7N
66
204
01001101
06NW2300S5E
80
218
01010100
06NA2209S7N
56
170
00111100
06NA2174S7N
46
142
00101110
06NW2250S7N
66
164
00111001
06NA2146S7N
39
114
00100000
06NW2300S7N
80
198
01001010
06NW2209S7N
56
136
00101011
06NW2174S7N
46
112
00011111
06NW2146S7N
39
92
00010101
DO #1
TO CONTACTOR # 2
DO #2
DO #3
TO OTHER CONTACTORS
DO #4
11 12 12
TERMINAL J4
24 VAC DO
POWER SUPPLY
TRIAC
TRIAC
TRIAC
TRIAC
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 13/98
------
J9
R S V
CH14
75 mm
(2.95
in)
J7
J2
CH13
J5
CH13
J4
J3
J8
T
P
V
T
P
V
R S V
-- G +
3 2 1
SIO
-- G +
3 2 1
J1
24VAC
12 11
CH14
CH -- CH -- CH -- CH -1
2
3
4
CH -- CH -- CH -- CH -5
6
7
8
CH
9
--
CH
10
--
CH
11
--
CH
12
--
J6
------
Connector
J2
AUX1
&
AUX2
DO #
Channel#
Main Functions
Fan 1 - circuit A or circuit B/ Pumpdown valve A
J3
All are standard 24 VAC/10%. All 24Vac common ground must be connected together on board and to 24Vac
ground pin of J1. All DOs total consomption = 115VA
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: original
Page: 14/98
AI
#*
Type
Usual Functions
J3 (TH A)
J3 (TH B)
1
Coil 1
2
Coil 2
BRIDGE
POSITION
FUNCTION
PINS
T,C
unused
1-R
Pressure transducer
(remote discharge
pressure circuit A)
V-1-R
T,C
unused
1-R
Pressure transducer
(remote discharge
pressure circuit B)
V-1-R
AI #1
AI #2
REMARKS
unused
V: Transducers 5 Volts power supply
1: Signal
R: -
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: original
J2
ANALOG
INPUT
AI #3
AI #4
BRIDGE
POSITION
FUNCTION
PINS
REMARKS
Reclaim leaving
thermistor
1-R
not used
V-1-R
unused
1-R
1: +
R: -
Reclaim entering
thermistor
1-R
not used
V-1-R
unused
1-R
Each output can be independently configured with a bridge allowing to close 2 pair of pins named C or V.
J1
ANALOG
OUTPUT
BRIDGE
POSITION
FUNCTION
PINS
REMARKS
5-R
5: +
R: -
4 - 20 mA Varifan
circuit A or water valve
5-R
5: +
R: -
6-R
6: +
R: -
4 - 20 mA Varifan
circuit B
6-R
6: +
R: -
AO #1
AO #2
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page: 15/98
ECG-UG-02-002
Rev: original
Page: 16/98
Channel Number
I/O
01
AI_1
Type
FUNCTION
Thermistor 5K or 10K
02
AI 2
Thermistor 5K or 10K
03, 04
AI 3
Thermistor 5K or 10K
unused
05
AI_5
06
AI 6
07
AO_1
0 - 10 Vdc
08 to 15
DIs
Relay input
unused
DO_13
Triac
17
DO_24
Triac
18
DO 3
Triac
unused
19
DO 4
Triac
20
DO_5
Triac
21
DO 6
Triac
22
DO_7
Triac
unused
23
DO 8
Triac
24
DO_9
Relay output
25
DO_10
Relay output
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 17/98
Suction pressure
Economizer pressure
Oil pressure
Economizer pressure on first compressor and also in the second compressor if unit is not equipped
with economizer
They are electronic sensors which linearise the output signal and deliver a 0 to 5 Vdc to either the basic board or
to an analog board. Three types of sensors are used.
3.2.1 - High pressure side sensors
They are used to measure discharge pressure and oil pressures when large band oil pressure transducer is not
selected. Carrier part: OP12DA039
5
Voltage (VDC)
50
345
100
689
150
1034
200
1379
300
250
2068
1724
Pressure
350
2414
400
2758
450
3103
500
3447
PSI
kPa
Voltage (VDC)
-6.6
-45
50
345
100
689
155
1068
215
276
1904
1484
Pressure
327
2252
387
2670
420
2895
500
3447
PSI
kPa
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 18/98
Voltage (VDC)
20
40
60
80
138
276
414
552
120
100
689
828
Pressure
140
160
965
1103
180
1241
200
1379
PSI
kPa
3.3 - THERMISTORS
All thermistor, excepted the reset sensor, have similar characteristics (see next page).
They have Carrier Part No. HH 79 NZ 047
3.3.1 - Discharge gas temperature
This is installed on the discharge pipe of each compressor. It is used to control the discharge superheat. The
discharge gas temperature (lowest discharge compressor temperature or average discharge temperature of both
compressors) is subtracted to the saturated condensing temperature to determine the discharge superheat.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 19/98
Resistanc
e
(OHMS)
100 049,0
97 006,4
94 060,8
91 209,3
88 449,0
85 777,0
83 190,7
80 687,1
78 263,9
75 918,3
73 648,0
71 450,6
69 323,7
67 265,0
65 272,4
63 343,7
61 476,9
59 670,0
57 920,9
56 227,9
54 589,1
53 002,7
51 467,0
49 980,4
48 541,1
47 147,7
45 798,6
44 492,4
43 227,6
42 002,9
40 816,9
39 668,3
38 555,9
37 478,4
36 434,7
35 423,7
34 444,2
33 495,2
32 575,6
31 684,6
30 821,0
29 984,0
29 172,7
28 386,3
27 623,8
26 884,4
26 167,5
25 472,2
24 797,8
24 143,6
23 509,0
22 893,2
22 295,6
21 715,7
21 152,6
20 606,4
20 075,9
Temp.
(C)
-3,5
-3,5
-3,0
-2,5
-2,0
-1,5
-1,0
-0,5
0,0
0,5
1,0
1.5
2,0
2.5
3.0
3,5
4,0
4.5
5,0
5,5
6,0
6.5
7.0
7,5
8,0
8,5
9.0
9.5
10,0
10,5
11,0
11,5
12,0
12,5
13,0
13,5
14,0
14,5
15,0
15,5
16,0
16,5
17,0
17,5
18,0
18,5
19,0
19,5
20,0
20,5
21,0
21,5
22,0
22,5
23,0
23,5
24,0
Resistanc
e
(OHMS)
20 075,9
19 560,8
19 060,6
18 574,8
18 102,9
17 644,5
17 199,1
16 766,3
16 345,7
15 936,9
15 539,5
15 153,1
14 777,5
14 412,2
14 056,9
13 711,4
13 375,3
13 048,3
12 730,1
12 420,5
12 119,2
11 826,0
11 540,5
11 262,7
10 992,1
10 728,8
10 472,3
10 222,6
9979.3
9742.5
9 511,7
9287.0
9068.0
8854.7
8 469,9
8 444,5
8 247,2
8 055,0
7 867,7
7 685,1
7 507,2
7 333,9
7164.9
7 000,3
6 839,8
6 683,4
6 530,9
6 382,3
6 237,5
6 096,3
5 958,7
5 824,6
5 693,9
5 566,4
5 442,2
5 321,2
5 203,2
Temp.
(C)
24,0
24,5
25,0
25,5
26,0
26,5
27,0
27,5
28,0
28,5
29,0
29,5
30,0
30,5
31,0
31,5
32,0
32,5
33,0
33,5
34,0
34,5
35,0
35,5
36,0
36,5
37,0
37,5
38,0
38,5
39,0
39,5
40,0
40,5
41,0
41,5
42,0
42,5
43,0
43,5
44,0
44,5
45,0
45,5
46,0
46,5
47,0
47,5
48,0
48,5
49,0
49,5
50,0
50,5
51,0
51,5
52,0
Resistanc
e
(OHMS)
5 203,2
5 088,1
4 976,0
4 866,8
4 760,2
4 656,4
4 555,2
4 456,6
4 630,4
4 266,7
4 175,4
4 086,3
3 999,6
3 915,0
3 832,5
3 752,1
3 673,7
3 597,3
3 522,9
3 450,2
3 379,4
3 310,4
3 243,1
3 177,5
3 113,4
3 051,0
2 990,1
2 930,7
2 872,8
2 816,2
2 761,1
2 707,2
2 654,7
2 603,4
2 553,3
2 504,4
2 456,6
2 410,0
2 364,4
2 319,9
2 276,3
2 233,8
2 192,2
2 151,5
2 111,7
2 072,8
2 034,7
1 997,4
1 960,9
1 925,1
1 890,1
1 855,7
1 822,1
1 789,1
1 756,8
1 725,1
1 694,0
Temp.
(C)
52,0
52,5
53,0
53,5
54,0
54,5
55,0
55,5
56,0
56,5
57,0
57,5
58,0
58,5
59,0
59,5
60,0
60,5
61,0
61,5
62,0
62,5
63,0
63,5
64,0
64,5
65,0
65,5
66,0
66,5
67,0
67,5
68,0
68,5
69,0
69,5
70,0
70,5
71,0
71,5
72,0
72,5
73,0
73,5
74,0
74,5
75,0
75,5
76,0
76,5
77,0
77,5
78,0
78,5
79,0
79,5
80,0
Resistanc
e
(OHMS)
1 694,0
1 663,5
1 633,5
1 604,1
1 575,2
1 546,9
1 519,0
1 491,6
1 464,7
1 438,3
1 412,3
1 386,8
1 361,6
1 336,9
1 312,6
1 288,7
1 265,2
1 242,1
1 219,3
1 196,9
1 174,8
1 153,2
1 131,8
1 110,9
1 090,2
1 069,9
1 050,0
1 030,3
1 011,0
992,1
973,4
955,1
937,1
919,4
902,1
885,1
868,4
952,0
836,0
820,2
804,8
789,8
775,0
760,6
746,5
732,6
719,2
706,1
693,3
680,8
668,6
656,8
645,2
634,0
623,2
612,6
602,4
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Temp.
(C)
80,0
80,5
81,0
81,5
82,0
82,5
83,0
83,5
84,0
84,5
85,0
85,5
86,0
86,5
87,0
87,5
88,0
88,5
89,0
89,5
90,0
90,5
91,0
91,5
92,0
92,5
93,0
93,5
94,0
94,5
95,0
95,5
96,0
96,5
97,0
97,5
98,0
98,5
99,0
99,5
100,0
100,5
101,0
101,5
102,0
102,5
103,0
103,5
104,0
104,5
105,0
105,5
106,0
106,5
107,0
Resistanc
e
(OHMS)
602,4
592,4
582,8
573,4
564,4
555,7
547,2
539,1
531,2
523,6
516,2
509,2
502,3
495,7
489,4
483,2
477,4
571,6
466,1
460,8
455,6
450,6
445,7
440,9
436,3
431,8
427,4
423,0
418,8
414,5
410,3
406,0
401,8
397,6
393,3
389,0
384,7
380,3
375,8
371,1
366,5
361,6
356,7
351,5
346,3
341,1
335,3
329,7
323,8
317,9
311,6
305,3
298,6
292,1
285,2
ECG - UG - 02 - 02
Rev: Original
Page: 20 /98
4.2 - CONFIGURATION
4.2.1 - General
Four types of configuration are available:
w The factory configuration. It describes the "hardware" structure of the unit (e.g. the number of compressors,
valve...). This configuration is accessible through the Main Interface Factory menu Menus or the Network
Service Tool and can be done by Carrier factory or service only.
w The Service configuration. It allows to modify operating parameters. This configuration is accessible
through the Main Interface Service Menus or the Network Service Tool and can be done by Carrier
factory or service only.
w The User configuration. It allows to modify a limited number of simple parameters (i.e. loading sequence,
start-up delay, cooler pumps control, reset select...). This configuration can be done through the Main
Interface or through the Network Service Tool. This configuration can be modified by the customer.
w The network configuration. It allows to modify parameters used by network functions (i.e. Alarm POC,
Broadcast ...). This is accessible through the Building Supervisor or the Network Service Tool.
4.2.2 -Main interface configuration sub menu tree structure
CONFIGURATION SUB MENUS
USER
I
T
E
M
S
SERVICE
FACTORY
USEr MEnu
SErViCE MEnu
"FACtorY MEnu"
USEr 1
SErViCE 1
"FACtorY 1 MEnu"
USEr 2
SErViCE 2
"FACtorY 2 MEnu"
dAtE
SErViCE 3
SCHEduLE 1
MAStEr SLAvE
SCHEduLE 2
HoLidAY
broAdCASt
I
T
E
M
S
"FACtorY1 MEnu"
10
11
12
13
14
15
16
17
18
19
FACTORY 2
"FACtorY2 MEnu"
fac_pass
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 21 /98
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
DESCRIPTION
STATUS
DEFAULT UNITS
POINT
Chiller Type
Circuit A Fan Stages Num
Circuit B Fan Stages Num
Varifan or W. Valves Sel
Economizer Select
Large Bd Oil Transducers
Comp A1 Must Trip Amps
Comp A2 Must Trip Amps
Comp B1 Must Trip Amps
Comp B2 Must Trip Amps
Reclaim Sensor Select
Air Cooled Reclaim Sel
Evaporator Number Pass
Cooler LWT On Circuit A
Cooler Heater Select
Factory Password
EXV A Maximum Steps Numb
EXV B Maximum Steps Numb
Motor Cool. TQ Feedback
PD4 Aux Boards Select
1,2,31
0 to 82
0 to 82
0/1/2/3/4
Yes/No3
Yes/No4
0 to 5605
0 to 5605
0 to 5605
0 to 5605
Yes/No6
Yes/No7
1 to 38
Yes/No9
Yes/No10
0 to 15011
1500/1500012
1500/1500012
Yes/No13
Yes/No14
1
0
0
0
No
No
0
0
0
0
No
No
3
Yes
No
113
1500
1500
No
No
unit_typ
nb_fan_a
nb_fan_b
hd_selec
econ_sel
oil_sel
mta_cpa1
mta_cpa2
mta_cpb1
mta_cpb2
hr_tmp
recl_opt
evap_pas
cira_lwt
heat_sel
fac_pass
exva_max
exvb_max
TQ_r_fbk
pd4_aux
Parameters from 1 to 16 in version 1.x are the same than those in the new version 2.X.
For Retrofit from verson 1.x to the new 2.x, it is better to write down in a paper, configuration items
from 1 to 16. Use Service Tool to upload all the configuration from version 1 (example address 1).
Then use address search function to change the address to 2 before downloading the new software
version 2.x. Use Service Tool to add a new controller with a different addresse (example address 1 for
version 1 and address 2 for version 2). Once Upload configuration is done, fill factory configuration in
FACTORY table and then download this.
1.
2.
ECG - UG - 02 - 02
Rev: Original
Page: 22 /98
13.
Yes = Use Pro_dialog 4 auxiliary boards instead of old 4xAO-2xAO board and 4xDO board
No = Use old 4xAO-2xAO board & 4x DO board (shall be set to no for version 1 retrofit)
3.
When this item is selected, both compressor use the common economizer transducer in the economizer.
Otherwise, each compressor uses it own economizer transducer, located in the refrigerant injection pipe
line, near the motor cooling valve. Economizer pressure represents the intermediary pressure between
high pressure and low pressure. It is used to determine the oil differential pressure (oil pressure economizer pressure).
4.
The use of large band oil pressure transducer is required for low ambient application and is only applied on
oil pressure transducers since high pressure range transducer can not read pressure lower than 2.4 bars,
Calibration is automatically determined each time the control is in OFF mode and both suction and
discharge pressures are equalized. Differences between oil pressures and suction pressure are then
stored as offset (if less than 0.4 bar).
5.
MTA configuration is required for capacity calculation, motor current measurement and protection. This
value shall match the one read from MTA header configuration on screw compressor board, if not an alarm
will be generated.
6.
If only reclaim sensor is selected and reclaim option is not, an 4xAI-2xAO board is required, and reclaim
temperature sensor are used for information only.
Reclaim option requires an Aquasnap Basic board for reclaim entering and leaving temperatures,
solenoids, an analogue output to control the reclaim condenser water valve, 2 transducers for reclaim
pumpdown injection pressure.
This items indicates the number of pass the cooler fluid goes through the cooler. For example, if cooler
enters from circuit A and goes out by circuit A and only 1 time, then a number of 2 shall be entered. This
item is used for exv control when caculating cooler pinch.
This items indicates if cooler leaving temperature sensor is in the circuit A or not. If cooler leaving pipe line
is on side A, then Yes shall be entered, otherwise, no shall be required. This item is used for exv control
when caculating cooler pinch.
Cooler heater option requires an Aquasnap Basic board for refrigerant isolation solenoids and heater
output.
Factory password is required when accessing the main interface factory menu. Factory password can be
used to access to service and user configuration sub menus.
7.
8.
9.
10.
11.
12.
1500 = For Muller valve, Unipolar, 1500 steps, 33 steps/s (1500 steps shall be kept !!!)
15000 = For Muller valve phase 3, Bipolar, 15300 steps, 300 steps/s (for future use,)
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 23 /98
VARIABLE
FORMAT
UNITS
COMMENTS
"FACTORY
MEnu"
unit typ
1/2,3,4
2[1]
nb fan a
0 to 8
3[1]
nb fan b
0 to 8
hd_selec
0,1,2,3,4
econ_sel
yes/no
Economizer select
oil sel
yes/no
cpa1 mta
0 to 560
8[1]
cpa2 mta
0 to 560
9[1]
cpb1 mta
0 to 560
10[1]
cpb2_mta
0 to 560
11[1]
hr_temp
yes/no
12[1]
recl opt
yes/no
13
evap pas
1 to 3
14
cira lwt
yes/no
15[1]
heat sel
yes/no
16
exva_max
1500 to 15000
17
exva_max
1500 to 15000
18
pd4 aux
yes/no
19
tq r fbk
yes/no
ITEM #
VARIABLE
FORMAT
UNITS
COMMENTS
"FACTORY 2
MEnu"
fac_pass
0 to 150
Factory password
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 24 /98
SCPM A1
TQ output (done)
THA
EXV BOARD
TQ output (done)
SCPM B1
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 25 /98
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
DESCRIPTION
STATUS
DEFAULT
1/2/31
10 to 1202
3.8 to 223
-20.0 to 20.04
-5.0 to 5.04
-20.0 to 20.04
8.3 to 225
8.3 to 225
0.5 to 2.66
0.5 to 2.66
48.8 to 71.17
5.5 to 117
50 to 858
5 to 208
Dsable/Enable9
4 to 610
1.0 to 6.011
Yes/No12
1
90
5
1.0
1.0
1.0
11
11
1.0
1.0
68
6.7
80
10
Dsable
6
6.0
No
UNITS
sec
^C
^C
^C
^C
^C
C
^C
%
%
-
POINT
flui_typ
head_tim
head_dif
hd_pg
hd_ig
hd_dg
dsh_sp_a
dsh_sp_b
pinc_p_a
pinc_p_b
mct_sp
mct_diff
curr_max
curr_dif
cls_ctrl
zm_spt
hc_zm
ewt_opt
Note: this table canl be downloadable at any time. However, modified value shall not be used by tasks until the
unit is in off state . This shall not apply to the Varifan/water valves gains that shall be modified at any time and
used immediately by the head pressure control tasks even if the unit is in operation.
1. >
1 = Water
2 = Brine
3 = Low Brine
Used to set fan cycling. Decreasing this value will increase fan cycling. This timer can be reduced since the
unit is fitted with an important number of fan stages, as to increase the condensing control accuracy. But in
certain cases, notably on units with few fan stages, at too small value can causes superheat hunting
problems.
3.
Used to set fan cycling. Default value is 5 ^C, 11.1^C or higher value are recommanded if unit has varifan.
This value can be increased on units with few fan stages to avoid superheat hunting problems.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 26 /98
This configuration applies to varifan or water valve upon unit type. It is used to adjust the head pressure
control PID loop. Normally this decision has not to be modified for Varifan. For water valve it can be
adjusted upon water valve type and installation.
PDI GAINS
hd_sp_pg
2.7
hd_sp_ig
0.4
hd_sp_dg
0.4
PDI GAINS
Recommanded for
water cooled
hd_sp_pg
2.0
hd_sp_ig
0.2
hd_sp_dg
2.0
5.
6.
This setpoint is used by the EXV control in order to maintain an optimal cooIer exchange delta temperature
between leaving temperature and saturated suction temperature. This is done in compensation with
discharge superheat temperature which has higher priority.
7.
8.
9.
The Global chillers use compressors which have better performance at full load than at part load.
Therefore the loading sequence strategy will be different from the one for flotronic II or pro-dialog 30 G & H
control. When compressor is on, it will try to avoid the compressor operate at low capacity (no loader ON).
If this item is enable, the control will use any stage of capacity in order to keep the exchanger leaving
temperature as closed at possible to the control point what ever the compressor performance. When the
circuit is in capacity override (compressor status LEDs in the synopsis are blinking), the control will force
the close control capacity variable to enable until the circuit is no more in override.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 27 /98
10.
This decision allows to set the setpoint which is used for auto Z Multiplier calculation. The Z Multiplier
calculation tries to maintain, for each compressor, a maximum number of starts per hour equal to [zm_spt].
Thus, decreasing the setpoint shall increase the reactivity of the auto Z Multiplier to compressors cycling.
11.
The Z Multiplier parameter allows to adjust the on/off time delay between compressors staging. It doesn't
affect loaders staging. Increasing this value shall increase the on/off time delay but shall reduce the
accuracy on the leaving temperature control.
w Tthe current Z Multiplier is the result of calculation based on the number of starts of compressors.
However, the maximum Z multiplier calculation will be limited to the value entered in this decision.
12.
This item allows the entering fluid control. Default is leaving fluid control. Entering fluid control can be used
for small charge.
VARIABLE
COMMENTS
flui_typ
2 [2]
head_tim
3[2]
head_dif
4 [2]
hd_sp_pg
Setpoint head pressure control - Proportional gain for Varifan or water valve control. Masked if
hd_sp_ig
Setpoint head pressure control - Integral gain for Varifan or water valve control. Masked if the
Varifan or the water valve is not selected (hd_selec = 0).
6 [2]
hd_sp_dg
Setpoint head pressure control - Derivative gain for Varifan or water valve control. Masked if the
Varifan or the water valve is not selected (hd_selec = 0).
dsh_sp_a
8 [2]
dsh_sp_b
pinc_p_a
10 [2]
pinc_p_b
Cooler pinch T setpoint Circuit B (lwt - sst setpoint displayed only if cap_b1 > 0).
11
mct_sp
12
mct diff
13
curr max
14
curr dif
15
cls ctrl
16
zm_spt
17
hc_zm
18
ewt opt
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 28 /98
1
2
3
4
5
6
7
8
9
10
11
12
10
11
12
13
14
15
16
DESCRIPTION
STATUS
DEFAULT
0/1/21
1/2/32
- 20 to 1013
0.6 to 3.34
Enable/Disable5
Enable/Disable6
RECLAIM PARAMETERS
Reclaim to Reclaim Delay
Heat Reclaim Deadband
Recl Valve Min Position
Recl Valve Max Position
Cir A SCT Ctrl Pt Coef a
Cir B SCT Ctrl Pt Coef a
Cir A SCT Ctrl Pt Offs b
Cir B SCT Ctrl Pt Offs b
5 to 207
2.7 to 11.18
0 to 509
20 to 10010
1.1 to 11.111
1.1 to 11.111
0 .0to 5.512
0.0 to 5.512
User Password
Service Password
0 to 15013
0 to 15013
1
14
1.1
Enable
Disable
UNITS
11
88
cond_ctr
cond_typ
low_setp
heatersp
ccnclock
auto_sm
mn
^F
%%
^C
^C
^C
^C
recl_del
recl_db
min_3w
max_3w
rsp_a_a
rsp_a_b
rsp_b_a
rsp_b_b
^F
^C
-
15
4.4
20
100
4.4
4.4
1.7
1.7
-
POINT
use_pass
ser_pass
1.
2.
3.
This decision allows to limit the setpoint of the customer (control point shall be higher than this value). It is
mostly used for brine application, as freezing condition depends on ratio on glycol and water.
4.
Used for cooler heater operation, this item is applied to outside temperature to determine the freeze
conditions (see cooler heater operation section).
5.
This item allows to use capabilities and functions based on CCN and clock..
6.
If enable, when chiller looses communication with the System Manager, it shall force the its CHIL_S_S
variable to enable and auto all other variables. Chiller restarts in stand alone mode with default setpoint .
7.
This decision allows to enter the entering temperature dead band for reclaim operation mode. See reclaim
operation description.
8.
This decision allows to enter the delay between two air cooled to reclaim injection sessions. See reclaim
operation description.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 29 /98
9.
This decision allows to set the minimum position in percent of the reclaim condenser water valve. See
reclaim operation description.
10.
This decision allows to set the maximum position in percent of the reclaim condenser water valve. See
reclaim operation. See reclaim operation description.
11.
coefficient A in delta F / percent for circuit. This decision allows to set the coefficient A of the saturated
condensing temperature control point determination (rsp_a, for circuit A or rsp_b for circuit B) for each
circuit when reclaim operation is active. See the items description below and reclaim operation description.
12.
offset B in delta F. This decision allows to set the offset B of the saturated condensing temperature control
point determination (rsp_a, for circuit A or rsp_b for circuit B) for each circuit when reclaim operation is
active.
ITEM #
VARIABLE
UNITS
cond_ctr
COMMENTS
When selected this item shall allow to return to main menu.
Condenser control type.
cond typ
5[1]
heatersp
^C
4[1]
low setp
5[1]
ccnclock
Clock capabilities select. Not displayed if the control is not fitted with the optional
CCN/clock board (RTC_CHIP_PRESENT = no). Always displayed when ccnclock =
yes.
6[1]
auto_sm
Auto restart when loss of communication with SM. Not dislayed if the control is not
fitted with the optional CCN/clock board (ccnclock = yes).
use_pass
User password.
Service password.
ser pass
9[2]
hr deadb
^C
10[2]
recl_del
minute
11[2]
min_3w
12[2]
max_3w
13[2]
rsp_a_a
^C%
14[2]
rsp a b
^C%
15[2]
rsp b a
^C
16[2]
rsp b b
^C
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 30 /98
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
STATUS
DEFAULT
UNITS
POINT
Servicing Alert
Enable/Disable
Disable
s_alert
Enable/Disable
Enable/Disable
Enable/Disable
Disable
Disable
Disable
charge_c
wloop_c
aexch_c
MAINTENANCE CONFIG
0 to 1000
0 to 1000
0 to 1000
0 to 1000
0 to 1000
0 to 1000
0 to 1000
0 to 1000
0
0
0
0
0
0
0
0
cpump1_c
cpump2_c
hpump_c
wfilte_c
ofila1_c
ofila2_c
ofilb1_c
ofilb2_c
VARIABLE
UNITS
COMMENTS
When selected this item shall allow to return to the main menu.
s reset
2[1]
charge m
3[1]
wloop m
4[1]
aexch m
5[1]
cpump1_m
Cooler water pump #1 next service in days (displayed only if pump_seq > 0)
6[1]
cpump2_m
Cooler water pump #2 next service in days (displayed only if pump_seq > 1)
7[1]
hpump_m
Condenser water pump next service in days, (displayed only if recl_opt = yes or
unit typ = 2 or 3 and cond tr > 0)
8[1]
wfilte m
9[1]
ofila1 m
10[1]
ofila2_m
11[1]
ofilb1_m
12[1]
ofilb2 m
This table is used for service maintenance alert and not available today.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 31 /98
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
STATUS
UNITS
POINT
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
hours
hours
hours
hours
hours
hours
hours
hours
hr_mach
st_mach
hr_cp_a1
hr_cp_a2
st_cp_a1
st_cp_a2
hr_cp_b1
hr_cp_b2
st_cp_b1
st_cp_b2
hr_cpum1
hr_cpum2
hr_hpump
Note: this table shall be used for purposes of transplanting the devices on time or starts number in the event of a
module hardware failure or software upgrade via downloading. It shall be usable only if all items are still nul.
Afterwards, its access shall be denied.
4.2.4.8 - Service 4 configuration table from main interface, runtime sub menu
The main interface allows to view and modify the service configuration table UPDTHOUR. Unit shalld be stopped
and service password or factory password are required.
ITEM #
VARIABLE
UNITS
COMMENTS
hr mach
hrs/10 or 100
hr cp a1
hrs/10 or 100
3 [1]
hr_cp_a2
hrs/10 or 100
4 [1]
hr_cp_b1
hrs/10 or 100
5 [1]
hr cp b2
hrs/10 or 100
st mach
-/10 or 100
Machine starts
st cp a1
-/10 or 100
Compressor A1 starts
8 [1]
st cp a2
-/10 or 100
9 [1]
st_cp_b1
-/10 or 100
10 [1]
st_cp_b2
-/10 or 100
11
st cp mx
12
st_cp_av
13 [1]
hr cpum1
hrs/10 or 100
14 [1]
hr_cpum2
hrs/10 or 100
15 [1]
hr_hpump
hrs/10 or 100
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 32 /98
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 33 /98
1
2
3
4
5
DESCRIPTION
STATUS
DEFAULT
POINT
0-11111111
0-7
1 - 240 min
1 - 255 min
8 chars
00000000
4
10
30
PD4_GXHX
ALRM_CNT
EQP_TYP
RETRY_TM
RE_ALARM
ALRM_NAM
Dataport 2
Autodial Gateway(s)
Local Building
Supervisor(s)
00000000
Note: If the CCN network does not contain a Building Supervisor, Autodial Gateway, or Dataport 2 to
serve as an alarm acknowledger, all digits in this decision shall be set to 0 in order to prevent
unnecessary activity on the CCN communication bus.
Allowable Entries
0 = Disabled
1 = Enabled
Default
00000000
0 to 7 (priority numbers)
Default
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 34 /98
This decision specifies the amount of time that will be allowed to elapse between alarm retries. Retries occur
when an alarm is not acknowledged by a network alarm acknowledger, which may be either a Building
Supervisor, an Autodial Gateway, or a Dataport 2. If the acknowledgement is not received, the alarm will be
retransmitted after the number of minutes specified in this decision.
Allowable Entries
1 to 240 minutes
Default
10 minutes
REALARM TIME
This decision specifies the amount of time that will be allowed to elapse between re-alarms. A re-alarm
occurs when the condition that caused the initial alarm continues to persist for the number of minutes
specified in this decision. Re-alarming will continue to occur at the specified interval until the condition
causing the alarm is corrected.
Allowable Entries
1 to 254 minutes
Default
30 minutes
Up to 8 alphanumeric characters
Default
PRO_30GX
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG - UG - 02 - 02
Rev: Original
Page: 35 /98
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
STATUS
DEFAULT
UNITS
POINT
0/1/21
ms_sel
1/2/3
ms_ctrl
1 to 236
2 to 302
Yes/No3
40 to 4004
0/1
1
10
No
168
0
0 to 605
MASTER/SLAVE CONTROL
Master/Slave Select:
0 = Disable
1 = Master
2 = Slave
Master Control Type:
1 = Local Control
2 = Remote Control
3 = CCN Control
Slave Address
Lag Start Timer
Lead/Lag Balance
Lead/Lag Balance Delta
Lag Unit Pump Control
0 = Stop if Unit Stops
1 = Run if Unit Stops
Lead Pulldown Time
min
hours
minutes
slv_addr
lstr_tim
ll_bal
ll_bal_d
lag_pump
lead_pul
Decisions description:
1.
This decision allows the unit to operate as master or a slave in a two chillers master/slave. The master
chiller monitors all external commands as start/stop, demand limiting, setpoint select or reset via CCN bus.
Control of the slave chiller is done through commands (start/stop, demand limit, setpoint, heat cool)
emitted by the master chiller. The slave will not be allowed to operate as a slave if its CHIL_S_S,
CTRL_PNT or DEM_LIM, HC_SEL variables has a force priority higher than a control force.
2.
This timer is started when all conditions to start the lag chiller are satisfied. Lag chiller shall not be started
until this timer is elapsed. To be set in the master unit table only.
3.
This decision allows to activate two chillers lead/lag balance function. It is used for master/slave chiller
running time equalization. When this function is active, once per day or each time the master chiller is
switched from the off to the on state the control determines the lead chiller based on both chillers run hours
delta. When the run hours delta is greater than the configured lead/lag balance delta then a changeover
will occur and the unit with the smallest operating hours value will become the lead. This function cannot
operate if the master chiller demand limit is less than 100%. In that case, the master chiller will always be
the lead. To be set in the master unit table only.
4.
This function allows to set the lead/lag balance delta used for master/slave chiller running time
equalization. Lead/lag changeover occurs when the lead/lag operating time delta overlaps the configured
balance value and provided that master unit is not under demand limit control.
5.
This decision allows to set the lead chiller pull down duration before the lag chiller starts.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 36/98
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 37/98
plate exchanger
Condenser
compressor 1
cpx1_mc2
compressor 2
sub-cooling
cpx2_mc2
Evaporator
EXV
(refer to factory configuration and wiring for retrofit, pages, 21, 23 and 24)
Tq valve opening position depends on the heat (resistor is the image) on the TQ valve and also the equalisation pressure located at plate exchanger (in our application, quite the same than economiser pressure).
With the same economiser pressure, the higher heating signal is commanded (CPA1_PUL, or
CPB1_PUL), the lower is the resistor and the more the valve is opened.
With same heating signal value, if the economiser pressure increases, the valve will tend to close. And
vice versa
Based on this relation, if the feedback signal is enabled, the control will check all the time the relation TQ
position = F (economiser pressure/TQ resistor) and shall make a kind of override (absolutely required at
the start-up, resistor is very high)
When a value of 200 is sent on CPA1_PUL or CPB1_PUL (hardware SIO variable) some time, that means
resistor value is a little above the minimum position, preheat is sent.
This value is sent also when loading capacity.
When the economiser pressure is steady, and TQ resistor is near to the pre-opening position, regular
control (PID) is used.
TQ resistor sensor is connected to the EXV board. The value read is in K Ohms MTQ_RESA (for circuit
A), MTQ_RESB (for circuit B). During regular operation, value read shall be from 0.7 k Ohm to 4 k
Ohms.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 38/98
The control calculates the SMZ: load/unload factor. It is compared to the z_multiplier to determine when to add or
remove stage:
w If (sum/z) > +z_multiplier -> stage = +1 (add a compressor)
w If (sum/z) > +0.6 and if a loader is available (loader is OFF) -> stage = +1 (add a loader)
w If (sum/z) < - z_multiplier -> stage = -1 (remove one compressor)
w If sum/z) < -0.6 and loader is avaialble (loader is ON) -> stage = -1 (turn off one loader)
Note: z_multiplier doesn't apply to loaders.
4.8.1.3 - Overrides
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 39/98
sum/z ratio will be overridden if any one of the following conditions is satisfied.
1
2,3
4
5,6
7, 8
9
10
11
12
13
14
15
16, 17
18,19
20, 21
22,23,24,25
28
26, 27
29,30
31,32
33,34
35
Note : When overrides 2,3 , 5, 6, 16, 17, 18, 19, 20, 21 are active, the variable close control (cls_ctrl) shall be
enabled whatever the configuration to allow unloading the last loader in the circuit.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 40/98
A compressor will not be started until all other running compressors are 100% loaded.
2.
On units with 3 compressors, both circuits cannot have their loaders off at the same time once 3 or
more of the compressors in the unit are on. Where possible, the circuit which is starting a
compressor will be the one which is to be unloaded.
3.
Any time a lag compressor in a circuit is starting, the loaders in the circuit shall be turned off
(unloading all compressors in the circuit). This shall be done 15 seconds prior to starting the new
compressor. 15 seconds after the new compressor has started, the loaders shall be set to their
desired state. When a lead compressor is starting, all loaders shall be turned off when the
compressor relay is turned on (+/- 2 seconds), and shall be set to their desired state 15 seconds
after the compressor has been started.
4.
There shall be a configuration decision for "close control", which (when selected) will cause the
control to utilize all of the loading devices to achieve better leaving water temperature control.
5.
Whenever any compressor in a circuit is going to be stopped normally, the circuit shall be fully
unloaded for 15 seconds prior to shutting down the compressor. This shall not apply when the
reason for a shutdown is due to an alarm condition.
7.
For any shutdown, all compressors and loaders will be shut down at the same time.
For more than 2 compressors, two types of sequencing are available and configurable by the user through either the
Main Interface or through the CCN network:
w Equal circuit loading: The control shall attempt to maintain equal capacity between the circuits as the machine
loads and unloads.
w Staged circuit loading: The control shall load the lead circuit completely before the lag circuit is started. When
the load is decreasing the lag circuit shall be unloaded first.
Circuit compressors sequence select shall try to equalize the compressor starts number. That means any
compressor in the circuit can become the lead compressor if it has the lowest starts number, however, this shall be
balanced with the operating hours.
Loaders in the same circuit are commanded simultaneously. Thus one loader variable is displayed.
When a circuit is overridden (compressor status are blinking in the synopsis) because of low suction
temperature, low or high discharge temperature or high condensing temperature (high pressure), or high
current then no capacity increase shall be allowed on the affected circuit. This circuit is selected to unload
capacity first when unloading capacity condition is required.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
LEAD CIRCUIT
LAG CIRCUIT
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
LAG CIRCUIT
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page: 41/98
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
LEAD CIRCUIT
LAG CIRCUIT
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
LAG CIRCUIT
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
ON
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page: 42/98
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
4.9.7 - Equal Loading Decreasing Capacity Logic
with close_control = NO
LEAD CIRCUIT
LAG CIRCUIT
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
LAG CIRCUIT
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page: 43/98
ECG-UG-02-002
Rev: Original
LEAD CIRCUIT
LAG CIRCUIT
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
NUMBER OF
COMPRESSORS
LOADER
1
LOADER
2
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page: 44/98
ECG-UG-02-002
Rev: Original
Page: 45/98
4.10.2 - Overrides
over_exv
1
2
3
4
5
6
7
8
9
10,11
12,13, 14
15
16,17
18, 20
19
21,26
22
23
24, 25
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 46/98
55C (13F1)
SC
T
+ 1 fan
co
nt
ro
lp
oin
t
SCT Diff
40C (104F)
35C (95F)
35C (95F)
- 1 fan
0c
20c
68F
32F
OAT
4.12.1 - Air Cooled Condensing Pressure Control - Fan staging with Aux board
Each DO shall support only one fan. The first DO is not used if varifan is present to standardize the way
of making connection and to avoid wiring mistake.
4.12.2 - Air Cooled Condensing Pressure Control - Fan staging
The combination described here below is for 4 fans configured maximum, each DO commands 1 fan
stage
DO_1
DO_2
DO_3
DO_4
0
1
2
3
4
off
on
on
on
on
off
off
on
on
on
off
off
off
on
on
off
off
off
off
on
fans controlled
0
fan_1
fan_1 + fan_2
fan_1 + fan_2+ fan_3
fan_1 + fan_2 + fan_3 + fan_4
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
total
fans
0
1
2
3
4
ECG-UG-02-002
Rev: Original
Page: 47/98
The following combinations are used for a circuit with more than 4 fans configured
stage
DO_1
DO_2
DO_3
DO_4
0
1
2
3
4
5
off
on
on
on
on
on
off
off
on
off
on
on
off
off
off
on
on
on
off
off
off
off
off
on
stage
DO_1
DO_2
DO_3
DO_4
0
1
2
3
4
5
6
off
on
on
on
on
on
on
off
off
on
off
on
off
on
off
off
off
on
on
on
on
off
off
off
off
off
on
on
stage
DO_1
DO_2
DO_3
DO_4
0
1
2
3
4
5
6
7
off
on
on
on
on
on
on
on
off
off
on
off
on
on
off
on
off
off
off
on
on
off
on
on
off
off
off
off
off
on
on
on
stage
DO_1
DO_2
DO_3
DO_4
0
1
2
3
4
5
6
7
8
off
on
on
on
on
on
on
on
on
off
off
on
off
on
off
on
off
on
off
off
off
on
on
off
off
on
on
off
off
off
off
off
on
on
on
on
fans controlled
0
fan_1
fan_1 + fan_2
fan_1 + + fan_3 + fan_4
fan_1 + fan_2 + fan_3 + fan_4
fan_1 + fan_2 + fan_3 + fan_4 + fan_5
fans controlled
fan_1
fan_1+ fan_2
fan_1+ + fan_3 + fan_4
fan_1+ fan_2 + fan_3 + fan_4
fan_1+ - + fan_3 + fan_4+ fan_5 + fan_6
fan_1+ fan_2 + fan_3 + fan_4 + fan_5 + fan_6
fans controlled
fan_1
fan_1 + fan_2
fan_1 + + fan_3 + fan_4
fan_1 + fan_2 + fan_3 + fan_4
fan_1 + fan_2 + - + - + fan_5 + fan_6 + fan_7
fan_1 + - + fan_3 + fan_4 + fan_5 + fan_6 + fan_7
fan_1 + fan_2 + fan_3 + fan_4 + fan_5 + fan_6 + fan_7
fans controlled
fan_1
fan_1 + fan_2
fan_1 + + fan_3 + fan_4
fan_1 + fan_2 + fan_3 + fan_4
fan_1 + + - + - + fan_5 + fan_6 + fan_7 + fan_8
fan_1 + fan_2 + - + - + fan_5 + fan_6 + fan_7 + fan_8
fan_1 + - + fan_3 + fan_4 + fan_5 + fan_6 + fan_7 + fan_8
fan_1 + fan_2 + fan_3 + fan_4 + fan_5 + fan_6 + fan_7 + fan_8
total
fans
0
1
2
3
4
5
total
fans
0
1
2
3
4
5
6
total
fans
0
1
2
3
4
5
6
7
total
fans
0
1
2
3
4
5
6
7
8
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 48/98
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 49/98
< 240
> 350
70
86
104
DP - SP (kpa)
< 861
> 1137
0.63645* (DP - SP) + 35
* DP = Discharge Pressure
* SP = Suction pressure
DOP: Differential Oil Pressure for the appropriate compressor. DOP = Oil pressure - Economizer pressure.
Economizer pressure is the common (econ_sel = YES) Economizer Pressure transducer reading for the
circuit involved or the appropriate economizer pressure transducer (econ_sel = NO) associated to the
compressor.
A. Compressor has started with Normal Ambient (oat > 10 C) or or condenser temperature (temp > 18C)
1.
If the compressor has been running for less than 5 seconds then ignore the alarm.
2.
If the compressor has been running for more than 5 seconds but less than 30 seconds and
DOP < (Oil Setpoint1/30)*(Comp. Running Time [in seconds])
for 3 continuous readings, then the alarm shall be tripped.
3.
If the compressor has been running for 30 seconds or more, then if:
a). DOP < Oil pressure setpoint1 for 15 continuous seconds,
OR
b). (Poil - Psuction) < Oil pressure setpoint2 for 15 continuous seconds,
then the alarm shall be tripped
B. Compressor has started with Low Ambient (oat < 10 C) or low condenser temperature (temp < 18C)
1.
If the compressor has been running for less than 90 seconds then ignore the alarm.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 50/98
2.
If the compressor has been running for more than 90 seconds but less than 180 seconds and
DOP < (Oil Setpoint1/90)*(Comp. Running Time [in seconds] - 90)
for 3 continuous readings, then the alarm shall be tripped.
3.
If the compressor has been running for 180 seconds or more, then if:
a). DOP < Oil pressure setpoint1 for 15 continuous seconds,
OR
b). (Poil - Psuction) < Oil pressure setpoint2 for 15 continuous seconds,
then the alarm shall be tripped.
Action To Be Taken
1.
If the alarm is tripped then the affected compressor shall be stopped. The other compressors shall
continue to run.
oil setpoint1
15 s delay
15 s delay
3 continued
reading values
3 continued
reading values
0
5s
30s
180s
90s
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 51/98
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 52/98
reclaim operation
indicator
Status description
*note : in case of reclaim operation failure (alarm # 83 for circuit A, alarm # 84 for circuit B), hr_status will not be
initialized until the manual reset on main interface is done.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 53/98
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 54/98
The lead pulldown time tells how long after starting the lead chiller (one time after the master chiller status has been
manually started) before checking whether to start an additional chiller. This time delay gives the lead chiller a
chance to pull down the loop temperature before starting another chiller.
If a communication failure is detected between the master and the slave then, all master/slave functions shall be
disabled and chillers shall return to standalone operations until communication is reestablished.
Note: to ensure that no compressor is started before the flow rate is correctly established then, the water flow control
is absolutely required on the lag chiller for master slave operations.
The figures below illustrate master/slave application for the most common plant layouts. Those figures are not
exhaustive.
COOL_LWT
MASTER
SLAVE
COOL_LWT
COOL_EWT
LOAD
COOL_EWT
MASTER PUMP
SLAVE PUMP
COOL_LWT
COOL_EWT
MASTER
SLAVE
COOL_LWT
LOAD
COOL_EWT
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 55/98
COOL_LWT
MASTER
SLAVE
COOL_LWT
COOL_EWT
LOAD
COOL_EWT
MASTER PUMP
SLAVE PUMP
MASTER
SLAVE
COOL_LWT
COOL_EWT
LOAD
COOL_EWT
COOL_LWT
COOL_LWT
COOL_EWT
MASTER
SLAVE
LOAD
BYPASS (controlled by chillers)
VALVES
PUMP (not controlled by chillers)
ECG-UG-02-002
Rev: Original
Page: 56/98
Master/Slave Error
The following error shall be updated in the M_MSTSLV Maintenance table (priority order):
Master/Slave alarm code
Error
code
0
1
Master
2
3
4
5
x
x
x
x
9
10
11
x
x
x
x
x
12
13
x
x
x
x
Slave
x
x
Description
Normal
The master or slave water pump is not configured while the control of the lag unit pump is
required (lag_pump = 1)
Master and slave units have the same network address.
There is no slave configured at the slave address
Slave pump_seq incorrect configuration
There is a conflict between the master and the slave lwt option: the master is configured for
ewt control while the slave is configured for lwt control.
There is a conflict between the master and the slave lwt option: the master is configured for
lwt control while the slave is configured for ewt control.
There is a conflict between the master and the slave pump option: the master is configured
for lag pump control while the slave is not configured for lag pump control.
There is a conflict between the master and the slave pump option: the master is not
configured for lag pump control while the slave is configured for lag pump control.
The slave chiller is in local or remote control (chilstat = 3)
The slave chiller is down due to fault (chilstat = 5)
The master chiller operating type is not Master: master_oper_typ master
No communication with slave.
master and slave heatcool status are not the same.
Note
Master/slave sequence can be controlled through the Network Service Tool or PCDCT tools (see appendix,
M_MSTSLV Maintenance Table)
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 57/98
Alarm 13
Alarm 14
Alarm 15
Alarm 16
Alarm 17
Alarm 18
Alarm 19
Alarm 20
Alarm 21
Alarm 22
Alarm 23
Alarm 24
Alarm 25
Alarm 26
Alarm 26
Alarm 27
Alarm 28
Alarm 29
Alarm 30
Alarm 31
Alarm 32
Alarm 33
Alarm 34
Alarm 35
Alarm 36
Alarm 37
Alarm 38
Alarm 39
Alarm 40
Alarm 41
Alarm 42
Alarm 43
Alarm 44
Alarm 45
Alarm 46
ECG-UG-02-002
Rev: Original
Alarms compressor
Alarm 101
Compressor
Alarm 102
Compressor
Alarm 103
Compressor
Alarm 104
Compressor
Alarm 105
Compressor
Alarm 106
Compressor
Alarm 107
Compressor
Alarm 108
Compressor
Alarm 109
Compressor
Alarm 110
Compressor
Alarm 111
Compressor
Alarm 112
Compressor
Alarm 113
Compressor
Alarm 114
Compressor
Alarm 115
Compressor
Alarm 116
Compressor
Alarm 117
Compressor
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page: 58/98
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Alarm 301
Alarm 302
Alarm 303
Alarm 304
Alarm 305
Alarm 306
Alarm 307
Alarm 308
Alarm 309
Alarm 310
Alarm 311
Alarm 312
Alarm 313
Alarm 314
Alarm 315
Alarm 316
Alarm 317
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Alarm 401
Alarm 402
Alarm 403
Alarm 404
Alarm 405
Alarm 406
Alarm 407
Alarm 408
Alarm 409
Alarm 410
Alarm 411
Alarm 412
Alarm 413
Alarm 414
Alarm 415
Alarm 416
Alarm 417
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
Compressor
ECG-UG-02-002
Rev: Original
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Page: 59/98
ECG-UG-02-002
Rev: Original
Page: 60/98
6 - CCN COMPATIBILITY
30GX&HX Pro-Dialog 4 Control is compatible with:
wThe Building Supervisor
wThe Network Service Tool
30GX&HX Pro-Dialog 4 Control is compatible with the following POCs:
wAlarm POC II
wAutodial Gateway II
wData Transfer/Collection History
wDataport 1
wDataport 2
wSAM
wNDS
wCCN/JBUS Gateway
wFlotronic System Manager
wChiller SYstem Manager III
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 61/98
DISPLAY SCREEN
TABLE NAME: GENUNIT
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
STATUS
UNITS
POINTS FORCEABLE
GENERAL PARAMETERS
Control Type
Run Status
CCN Chiller Start/Stop
Chiller Occupied?
Minutes Left for Start
Heat/Cool Select
Heat Reclaim Select
Local/CCN/Remote1
running/Off/Stopping/Delay2
Enable/Dsable3
Yes/No4
0-15
Heat/Cool5
Yes/No10
Alarm State
Current Alarm 1
Current Alarm 2
Current Alarm 3
Current Alarm 4
Current Alarm 5
Normal6
nnn
nnn
nnn
nnn
nnn
nnn
nnn7
nnn
nnn.n
Yes/No4
nnn.n8
nnn.n
nnn.n
%
%
%
F
F
F
F
Emergency Stop
Enable/Emstop9
min
-
ctr_type
status
CHIL_S_S
CHIL_OCC
MIN_LEFT
HC_SEL
RECL_SEL
N
N
Y
Y
N
Y
Y
ALM
alarm_1
alarm_2
alarm_3
alarm_4
alarm_5
N
N
N
N
N
N
CAP_T
DEM_LIM
LAG_LIM
SP
SP_OCC
CTRL_PNT
CTRL_WT
OAT
N
Y
N
N
Y
Y
N
N
EMSTOP
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 62/98
6 : Alarm status
wNormal (no alarm)
wPartial (alarm but unit is not down)
wShutdown (unit is down)
7: Active Demand Limit Value. This item can be forced. If the unit is in CCN mode, the forced value shall be used
whatever the status of the external limit switch contact and whatever the value of the demand limit switch setpoint.
If the unit is not in CCN mode the forced value shall be unused. Forced value and force code shall appear in the
GENUNIT Points Display table only if the unit is under CCN control.
8: Control Point. This item can be forced. If the unit is in CCN mode, the forced value shall be used instead of the
real control point calculation. If the unit is not in CCN mode the forced value shall be unused. Forced value and
force code shall appear in the GENUNIT Points Display table only if the unit is under CCN control.
9 : Active all the time even if the unit is not in CCN control type.
10: Heat Reclaim Select. This item can be forced. If the unit is in CCN mode, the forced value shall be used
whatever the status of the remote reclaim switch. Forced value and force code shall appear in the GENUNIT
Points Display table only if the unit is under CCN control.
DISPLAY SCREEN
TABLE NAME: CIRCA_AN
DESCRIPTION
1
2.
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
STATUS
UNITS
POINTS
0 - 100
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
0 - 100
0 - 100
n.n
nn.n
nnn
%
psi
psi
psi
psi
psi
psi
psi
psi
F
F
F
F
F
F
F
AMPS
AMPS
%
%
^F
CAPA_T
DP_A
SP_A
CPA1_OP
CPA2_OP
DOP_A1
DOP_A2
CPA1_ECP
CPA2_ECP
SCT_A
SST_A
CPA1_DGT
CPA2_DGT
dt_a
CPA1_TMP
CPA2_TMP
CPA1_CUR
CPA2_CUR
EXV_A
hd_pos_a
PINCH_A
MTQ_RESA
CPA1_PUL
FORCEABLE
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 63/98
DISPLAY SCREEN
TABLE NAME: CIRCA_D
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
STATUS
UNITS
POINTS
FORCIBLE
Compressor 1 Output
Cp1 Mtr Cool Solenoid 1
Cp1 Mtr Cool Solenoid 2
Cp1, Oil Solenoid Out
Compressor 2 Output
Cp2 Mtr Cool Solenoid 1
Cp2 Mtr Cool Solenoid 2
Cp2, Oil Solenoid Out
Cir A, Loader 1 Output
Cir A, Loader 2 Output
Cir A, Oil Heater Output
Cir A, Oil Level Input
Cir A, Oil Pump Output
Cir A Refrig Isolate Out
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
Low/High
On/Off
On/Off
CP_A1
cpa1_mc1
cpa1_mc2
cpa1_ols
CP_A2
cpa2_mc1
cpa2_mc2
cpa2_ols
ldr_1_a
ldr_2_a
oil_h_a
oil_l_a
oilpmp_a
refa_iso
N
N
N
N
N
N
N
N
N
N
N
N
N
N
FANS OUTPUT
Fan Output DO # 1
Fan Output DO # 2
Fan Output DO # 3
Fan Output DO # 4
Fan Output DO # 5
Fan Output DO # 6
Fan Output DO # 7
Fan Output DO # 8
Fan Staging Number
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0-8
fan_a1
fan_a2
fan_a3
fan_a4
fan_a5
fan_a6
fan_a7
fan_a8
FAN_ST_A
N
N
N
N
N
N
N
N
N
STATUS
UNITS
POINTS
0 - 100
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
%
psi
psi
psi
psi
psi
psi
psi
psi
F
F
CAPB_T
DP_B
SP_B
CPB1_OP
CPB2_OP
DOP_B1
DOP_B2
CPB1_ECP
CPB2_ECP
SCT_B
SST_B
CIRCUIT A DISCRETE
DISPLAY SCREEN
TABLE NAME: CIRCB_AN
DESCRIPTION
1
2.
3
4
5
6
7
8
9
10
11
12
13
FORCEABLE
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
N
N
N
N
N
N
N
N
N
N
N
Page: 64/98
F
F
F
F
F
AMPS
AMPS
%
%
^F
CPB1_DGT
CPB2_DGT
dt_b
CPB1_TMP
CPB2_TMP
CPB1_CUR
CPB2_CUR
EXV_B
hd_pos_b
PINCH_B
MTQ_RESB
CPB1_PUL
N
N
N
N
N
N
N
N
N
N
N
N
STATUS
UNITS
POINTS
Compressor 1 Output
Cp1 Mtr Cool Solenoid 1
Cp1 Mtr Cool Solenoid 2
Cp1, Oil Solenoid Out
Compressor 2 Output
Cp2 Mtr Cool Solenoid 1
Cp2 Mtr Cool Solenoid 2
Cp2, Oil Solenoid Out
Cir B, Loader 1 Output
Cir B, Loader 2 Output
Cir B, Oil Heater Output
Cir B, Oil Level Input
Cir B, Oil Pump Output
Cir B Refrig Isolate Out
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
Low/High
On/Off
On/Off
CP_B1
cpb1_mc1
cpb1_mc2
cpb1_ols
CP_B2
cpb2_mc1
cpb2_mc2
cpb2_ols
ldr_1_b
ldr_2_b
oil_h_b
oil_l_b
oilpmp_b
refb_iso
N
N
N
N
N
N
N
N
N
N
N
N
N
N
FANS OUTPUT
Fan Output DO # 1
Fan Output DO # 2
Fan Output DO # 3
Fan Output DO # 4
Fan Output DO # 5
Fan Output DO # 6
Fan Output DO # 7
Fan Output DO # 8
Fan Staging Number
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0-8
fan_b1
fan_b2
fan_b3
fan_b4
fan_b5
fan_b6
fan_b7
fan_b8
FAN_ST_B
N
N
N
N
N
N
N
N
N
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
14
15
16
17
18
19
20
21
22
23
24
25
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
0 - 100
0 - 100
n.n
nn.n
nnn
DISPLAY SCREEN
TABLE NAME: CIRCB_D
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
FORCEABLE
CIRCUIT B DISCRETE
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 65/98
DISPLAY SCREEN
TABLE NAME: OPTIONS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
DESCRIPTION
STATUS
UNITS
POINTS
UNIT DISCRETE IN
Remote On/Off Switch
Remote Heat/Cool Switch
Remote Reclaim Switch
Remote Setpoint Switch
Limit Switch Status
Interlock Status
Pump Run status
Condenser Flow Status
Electrical Box Thermostat
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
On/Off
Open/Close
Open/Close4
onoff_sw
hc_sw
recl_sw
setp_sw
limit_sw
lock_1
pump_def
condflow
elec_box
N
N
N
N
N
N
N
N
N
On/Off1
On/Off1
Yes/No1
On/Off3
On/Off
On/Off5
CLPUMP_1
CLPUMP_2
ROT_PUMP
COND_PMP
coolheat
SAFE_ALM
Y
Y
Y
Y
N
N
UNIT ANALOG
Cooler Entering Fluid
Cooler Leaving Fluid
Condenser Entering Fluid
Condenser Leaving Fluid
CHWS Temperature
External 0-10Vdc Signal
Current Cond Setpoint
Chiller Total Current
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nn.n
nnn.n2
nnn.n
F
F
F
F
F
Volts
F
amps
COOL_EWT
COOL_LWT
COND_EWT
COND_LWT
CHWSTEMP
EXT_VDC
COND_SP
tot_curr
N
N
N
N
N
N
Y
N
FORCEABLE
1: Cooler pump control. This item can be forced On or Off if the unit is in CCN mode and if the CHIL_S_S is
disabled. If the unit is not in CCN mode the forced value shall be unused and the regular calculation shall be
used. Forced value and force code shall appear in the OPTIONS Points Display table only if the unit is under CCN
control and if CHIL_S_S is disabled.
If PUMP#1 is forced, no force shall be allowed on PUMP_2 and vice versa.
2: Condensing Setpoint. This item can be forced. If the unit is in CCN mode, the forced value shall be used instead
of the real control point calculation. If the unit is not in CCN mode the forced value shall be unused and the
regular calculation shall be used. Forced value and force code shall appear in the OPTIONS Points Display table
only if the unit is under CCN control.
3: Condenser pumpcontrol. This item can be forced On but not Off. If the unit is in CCN mode, the forced value shall
be used instead of regular pump control point. If the unit is not in CCN mode the forced value shall be unused and
the regular calculation shall be used. Forced value and force code shall appear in the OPTIONS Points Display
table only if the unit is under CCN control.
4: Electrical box Thermostat. This item indicates the electrical box thermostat and network power reverse phase
detection status (wired internally in series 16a and 16b on PD4-BASIC BOARD). These contacts, when opened
will prevent the unit from starting.
5: This output is energized when a contact failure is reported by any SCPM board
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 66/98
DISPLAY SCREEN
TABLE NAME: RECLAIM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DESCRIPTION
STATUS
UNITS
POINTS
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
F
F
F
F
F
psi
psi
F
F
%
HR_EWT
HR_LWT
hr_sp
sct_a_sp
sct_b_sp
pmpd_p_a
pmpd_p_b
pd_sat_a
pd_sat_b
hr_v_pos
N
N
N
N
N
N
N
N
N
N
Yes/No
Open/Close
On/Off
On/Off
On/Off
On/Off
n
n
On/Off
RECL_SEL
condflow
hr_val_a
hr_val_b
pd_val_a
pd_val_b
hrstat_a
hrstat_b
cond_htr
N
N
N
N
N
N
N
N
N
N
No
-
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
FORCEABLE
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Page: 67/98
DESCRIPTION
STATUS
OPERATING MODES
Startup Delay in Effect
Second Setpoint in Use
Reset in Effect
Demand Limit Active
Ramp Loading Active
Low Source Protection
Low Cooler Suction Cir A
Low Cooler Suction Cir B
Low Dis Superheat Cir A
Low Dis Superheat Cir B
High Pres Override Cir A
High Pres Override Cir B
High Current Over Cir A
High Current Over Cir B
Reclaim Active?
Cooler Heater Active?
Cooler Pumps Rotation?
Pump Periodic Start?
Night Capacity Active?
System Manager Active?
Master Slave Active?
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
UNITS
-
POINTS
Mode[07]
Mode[08]
Mode[09]
Mode[10]
Mode[11]
Mode[12]
Mode[13]
Mode[14]
Mode[15]
Mode[16]
Mode[17]
Mode[18]
Mode[19]
Mode[20]
Mode[21]
Mode[22]
Mode[23]
Mode[24]
Mode[25]
Mode[26]
Mode[27]
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
FORCEABLE
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
ECG-UG-02-002
Rev: Original
Page: 68/98
CONFIGURATION SCREEN
TABLE NAME: USER
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
STATUS
DEFAULT
0/1/2
UNITS
POINT
USER CONFIGURATION
Circuit Loading Sequence
0 = Auto
1 = Circuit A First
2 = Circuit B First
Loading Sequence
0/1
Yes/No
No
1 to 15
lead_cir
seq_typ
ramp_sel
min
off_on_d
0/1/2/3/4
pump_seq
24 to 3000
Yes/No
48
No
hours
-
pump_del
pump_per
0 to 3
res_sel
0 to 2
lim_sel
0
10
volts
volts
lim_mx
lim_ze
0 to 10
0 to 10
Night Control
Start Hour
End Hour
Capacity Limit
Capacity Limit
00:00 to 24:00
00:00 to 24:00
0 to 100
0 to 100
00:00
00:00
100
100
%
%
90 to 15001
Yes/No
Yes/No
1500
Yes
No
amps
-
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
nh_start
nh_end
nh_limit
nh_limit
curr_lim
menu_des
all_pass
ECG-UG-02-002
Rev: Original
Page: 69/98
DESCRIPTION
STATUS
DEFAULT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Activate
Yes/No
No
ccnbroad
OAT Broadcast
Bus #
Element #
0 to 239
0 to 239
0
0
oatbusnm
oatlocad
1 to 12
1 to 31
00:00 to 24:00
0 to 1440
4
15
02:00
60
startmon
startday
starttim
min_add
1 to 12
1 to 31
00:00 to 24:00
0 to 1440
10
15
02:00
60
stopmon
stopday
stoptim
min_sub
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
UNITS
POINT
ECG-UG-02-002
Rev: Original
Page: 70/98
CONFIGURATION SCREEN
TABLE NAME: OCCDEFCS / OCCPC01S and OCCPC02S
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
DESCRIPTION
STATUS
DEFAULT
0-4
0/1
0:00-24:00
0:00-24:00
0/1
0:00-24:00
0:00-24:00
0/1
0:00-24:00
0:00-24:00
0/1
0:00-24:00
0:00-24:00
0/1
0:00-24:00
0:00-24:00
0/1
0:00-24:00
0:00-24:00
0/1
0:00-24:00
0:00-24:00
0/1
0:00-24:00
0:00-24:00
0
11111111
0:00
24:00
00000000
0:00
24:00
00000000
0:00
24:00
00000000
0:00
24:00
00000000
0:00
24:00
00000000
0:00
24:00
00000000
0:00
24:00
00000000
0:00
24:00
UNITS
-
POINT
ovr_ext
dow1
occtod1
unoctod1
dow2
occtod2
unoctod2
dow3
occtod3
unoctod3
dow4
occtod4
unoctod4
dow5
occtod5
unoctod5
dow6
occtod6
unoctod6
dow7
occtod7
unoctod7
dow8
occtod8
unoctod8
DESCRIPTION
STATUS
DEFAULT
0-12
0-31
0-99
0
0
0
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
UNITS
-
POINT
HOL_MON
HOL_DAY
HOL_LEN
ECG-UG-02-002
Rev: Original
Page: 71/98
SETPOINT SCREEN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
DESCRIPTION
STATUS
COOLING
Cooling Setpoint 1
Cooling Setpoint 2
Voltage No Reset Value
Voltage Full Reset Value
Delta T No Reset Value
Delta T Full Reset Value
OAT No Reset Value
OAT Full Reset Value
Cooling Reset Deg. Value
Cooling Ramp Loading
- 20 to 101
- 20 to 101
0 to 10
0 to 10
0 to 25
0 to 25
14 to 125
14 to 125
-30 to 30
0.2 to 2.0
HEATING
Heating Setpoint
Voltage No Reset Value
Voltage Full Reset Value
Delta T No Reset Value
Delta T Full Reset Value
Heating Reset Deg. Value
Heating Ramp Loading
DEFAULT
UNITS
POINT
44.0
44.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.0
F
F
volts
volts
^F
^F
F
F
^F
^F
csp1
csp2
v_cr_no
v_cr_fu
dt_cr_no
dt_cr_fu
oatcr_no
oatcr_fu
cr_deg
cramp_sp
80 to 153
0 to 10
0 to 10
0 to 25
0 to 25
-30 to 30
0.2 to 2.0
100.0
0.0
0.0
0.0
0.0
0.0
1.0
F
volts
volts
^F
^F
^F
^F
hsp
v_hr_no
v_hr_fu
dt_hr_no
dt_hr_fu
hr_deg
hramp_sp
HEAD PRESSURE
Sat Cond Temp Setpoint
Reclaim Setpoint
95 to 1401
95 to 140
104.0
122.0
F
F
headsp
rsp
DEMAND LIMIT
Switch Demand Limit Setp
0 to 100
100
lim_sp
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 72/98
MAINTENANCE SCREEN
TABLE NAME: LOADFACT
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
POINT
CAPACITY CONTROL
Average Ctrl Water Temp
Differential Water Temp
Water Delta T
Control Point
Reset Amount
Controlled Temp Error
Actual Capacity
Actual Capacity Limit
Current Z Multiplier Val
Load/Unload Factor
Active Capacity Override
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn
nnn
n.n
nnn.n
nn
nnn.n
nnn.n
n.n
n.n
n.n
nn
%
%
^F
F
^F
-
EXV_A
exvlim_a
PINCH_A
DSH_A
offset_a
ov_exv_a
nnn.n
nnn.n
n.n
n.n
n.n
nn
%
%
^F
F
^F
-
EXV_B
exvlim_b
PINCH_B
DSH_B
offset_b
ov_exv_b
F
F
^F
F
^F
^F
%
%
ctrl_avg
diff_wt
delta_t
CTRL_PNT
reset
tp_error
cap_t
cap_lim
zm
smz
over_cap
PowerDown 1:day-mon-year
PowerDown 1:hour-minute
Power On 2: day-mon-year
Power On 2: hour-minute
PowerDown 2:day-mon-year
PowerDown 2:hour-minute
Power On 2: day-mon-year
Power On 2: hour-minute
PowerDown 3:day-mon-year
PowerDown 3:hour-minute
Power On 3: day-mon-year
Power On 3: hour-minute
PowerDown 4:day-mon-year
PowerDown 4:hour-minute
Power On 4: day-mon-year
Power On 4: hour-minute
PowerDown 5:day-mon-year
PowerDown 5:hour-minute
Power On 5: day-mon-year
Power On 5: hour-minute
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
nnnnnn
nnnn
ddmmyy
hhmm
ddmmyy
hhmm
ddmmyy
hhmm
ddmmyy
hhmm
ddmmyy
hhmm
ddmmyy
hhmm
ddmmyy
hhmm
ddmmyy
hhmm
ddmmyy
hhmm
ddmmyy
hhmm
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
date_of1
time_of1
date_on1
time_on1
date_of2
time_of2
date_on2
time_on2
date_of3
time_of3
date_on3
time_on3
date_of4
time_of4
date_on4
time_on4
date_of5
time_of5
date_on5
time_on5
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 73/98
MAINTENANCE SCREEN
TABLE NAME: M_MSTSLV
1
2
3
4
5
6
7
8
9
10
11
12
13
DESCRIPTION
STATUS
UNITS
POINT
MASTER/SLAVE CONTROL
Unit is Master or Slave
Master Control Type
Master/Slave Ctrl Active
Lead Unit is the:
Slave Chiller State
Slave Chiller Total Cap
Lag Start Delay
Lead/Lag Hours Delta
Lead/Lag Changeover?
Lead Pulldown?
Master/Slave Error
Max Available Capacity ?
Disable/Master/Slave
Local/Remote/CCN3
True/False
Master/Slave
0/1/2/3/4/51
0-100
1 to 302
nnnnn3
Yes/No4
Yes/No4
nn
True/False5
%
minutes
hours
-
mstslv
ms_ctrl
ms_activ
lead_sel
slv_stat
slv_capt
l_strt_d
ll_hr_d
ll_chang
ll_pull
ms_error
cap_max
1
2
3
4
5
6
7
8
10
11
12
13
14
15
16
17
18
19
DESCRIPTION
STATUS
nn
UNITS
POINT
FORCEABLE
S_RESET
OPERATION WARNINGS
1 - Refrigerant Charge
2 - Water Loop Size
3 - Air Exchanger
Normal/Low
Normal/Low
Normal/Dirty
charge_m
wloop_m
aexch_m
N
N
N
0 to 1000/Alert
0 to 1000/Alert
0 to 1000/Alert
0 to 1000/Alert
0 to 1000/Alert
0 to 1000/Alert
0 to 1000/Alert
0 to 1000/Alert
cpump1_m
cpump2_m
hpump_m
wfilte_m
ofila1_m
ofila2_m
ofilb1_m
ofilb2_m
N
N
N
N
N
N
N
N
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 74/98
MAINTENANCE SCREEN
TABLE NAME: STRTHOUR
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
DESCRIPTION
STATUS
MACHINE
Total Operating Hours
Starts Number
Compressor A1 Hours
Compressor A2 Hours
Compressor A1 Starts
Compressor A2 Starts
Compressor B1 Hours
Compressor B2 Hours
Compressor B1 Starts
Compressor B2 Starts
Starts Max During 1 Hour
Starts/hr From Last 24 h
Cooler Pump #1 Hours
Cooler Pump #2 Hours
Condenser Pump Hours
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nn
nn
nnnnn
nnnnn
nnnnn
UNITS
hours
hours
hours
hours
hours
hours
hours
hours
POINT
HR_MACH
st_mach
HR_CP_A1
HR_CP_A2
st_cp_a1
st_cp_a2
HR_CP_B1
HR_CP_B2
st_cp_b1
st_cp_b2
st_cp_mx
st_cp_av
hr_cpum1
hr_cpum2
hr_hpump
1
2
3
4
5
6
7
8
9
10
DESCRIPTION
STATUS
DEFAULTUNITS
POINT
0 to 560
0 to 560
0 to 560
0 to 560
0
0
0
0
Amps
Amps
Amps
Amps
cpa1_mta
cpa2_mta
cpb1_mta
cpb2_mta
Scheme Number
SCPM A1 Software Version
SCPM A2 Software Version
SCPM B1 Software Version
SCPM B2 Software Version
0 to 5
nnn.nn
nnn.nn
nnn.nn
nnn.nn
3
0
0
0
0
scheme
cpa1_ver
cpa2_ver
cpb1_ver
cpb2_ver
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
1
2
3
4
5
6
7
8
9
10
11
12
Page: 75/98
DESCRIPTION
STATUS
0/1
1 to 8
Yes/No
0 to 4
00:00 to 23:59
00:00 to 23:59
Mon to Sun
00:00 to 23:59
Mon to Sun
00:00 to 23:59
Mon to Sun
00:00 to 23:59
UNITS
hours
-
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
POINT
MODE
PER_NO
OVERLAST
OVR_HRS
STRTTIME
ENDTIME
NXTOCDAY
NXTOCTIM
NXTUNDAY
NXTUNTIM
PRVUNDAY
PRVUNTIM
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page: 76/98
APPENDIX B
CCN Variables
The following variables can be used for trace functions (Network Service Tool-Trace, Data Collection).
DESCRIPTIONS
UNITS
TYPE
CONFIGURATION
ALARM_A
H-DO
all
ALARM_B
H-DO
cpb1_mta > 0
H-AI
All
H-AI
unit_typ = 2 or 3
COND_LWT
H-AI
unit_typ = 2 or 3
COOL_EWT
H-AI
all
COOL_LWT
H-AI
all
CPUMP_1
H-DO
pump_seq > 0
CPUMP_2
H-DO
pump_seq > 1
H-DO
All
H-DO
all
CPA1_MUX
H-DO
All
CPA1_PUL
H-AO
econ_sel = 1
CPA1_CUR
Amps
H-AI
all
CPA1_OP
psi
H-AI
all
CPA1_ECP
psi
H-AI
all
CPA1_DGT
H-AI
all
CPA1_TMP
H-AI
all
CPA1_STA
H-AI
all
CP_A2
H-DO
cpa2 _mta> 0
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
POINT
NAMES
DESCRIPTIONS
Page: 77/98
UNITS
TYPE
CONFIGURATION
H-DO
cpa2_mta > 0
Amps
H-AI
cpa2_mta > 0
CPA2_MUX
CPA2_CUR
CPA2_OP
psi
H-AI
cpa2_mta> 0
CPA2_ECP
psi
H-AI
CPA2_DGT
H-AI
cpa2_mta> 0
CPA2_TMP
H-AI
cpa2_mta> 0
CPA2_STA
H-AI
cpa2_mta> 0
CP_B1
H-DO
cpb1_mta> 0
CPB1_MUX
H-DO
cpb1_mta > 0
CPB1_PUL
H-AO
cpb1_mta> 0 and
econ_sel = 1
CPB1_CUR
Amps
H-AI
cpb1_mta > 0
CPB1_OP
psi
H-AI
cpb1_mta > 0
CPB1_ECP
psi
H-AI
cpb1_mta > 0
CPB1_DGT
H-AI
cpb1_mta> 0
CPB1_TMP
H-AI
cpb1_mta > 0
H-AI
cpb1_mta> 0
CP_B2
H-DO
cpb2_mta> 0
CPB2_MUX
H-DO
cb2_mta > 0
CPB2_CUR
Amps
H-AI
cb2_mta> 0
CPB2_OP
psi
H-AI
cb2_mta> 0
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
POINT
NAMES
DESCRIPTIONS
Page: 78/98
UNITS
TYPE
CONFIGURATION
CPB2_ECP
psi
H-AI
CPB2_DGT
H-AI
cb2_mta> 0
CPB2_TMP
H-AI
cb2_mta> 0
CPB2_STA
H-AI
cb2_mta> 0
EXV_ST_A
H-AO
all
EXV_ST_B
H-AO
cb2_mta > 0
EXT_VDC
volts
H-AI
all
DP_A
psi
H-AI
all
DP_B
psi
H-AI
cb2_mta> 0
HD_A
4 - 20
mA
010Vdc
H-AO
hd_selec > 0
HD_B
4 - 20
mA
010Vdc
H-AO
hd_selec > 0
HR_EWT
H-AI
hr_tmp = 1
HR_LWT
H-AI
hr_tmp = 1
HR_WTRVL
010Vdc
H-AO
recl_opt = 1
MTQ_RESA
H-AI
MTQ_RESB
H-AI
MUX_DI
H-DIM
all
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
(all)
(all)
(unit_typ = 3)
(unit_typ = 1 or 4)
(all)
(all)
(all)
(all)
(uni_typ = 1 or 4)
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
POINT
NAMES
MUX_FAN1
DESCRIPTIONS
Fan 4xDO board #1, multiplexed DO's
b4b3b2b1b0
b0:
fan_a1
Fan output 1, circuit A
b1:
fan_a2
Fan output 2, circuit A
b2:
fan_b1
Fan output 1, circuit B
b3:
fan_b2
Fan output 2, circuit B
b0:
b1:
b2:
b3:
fan_a1
fan_a2
fan_a3
fan_a4
UNITS
TYPE
CONFIGURATION
H-DO
unit_typ = 1
MUX_FAN2
Page: 79/98
H-DO
unit_typ = 1
nb_fan_a> 0
b4:
b5:
b6:
b7:
fan_a5
fan_a6
fan_a7
fan_a8
b4
b5
b6
b7
fan_b1
fan_b2
fan_b3
fan_b4
H-DO
H-DO
unit_typ = 1
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
nb_fan_b> 0
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
POINT
NAMES
DESCRIPTIONS
OIL_HTRA
Page: 80/98
UNITS
TYPE
CONFIGURATION
H-DOM
heat_sel = yes or
recl_opt = yes
recl_opt = yes
recl_opt = yes
recl_opt = yes
recl_opt = yes
recl_opt = yes
(heat_sel = yes)
(heat_sel = yes)
(heat_sel = yes)
H-AI
unit_typ = 1 or 4
H-DO
unit_typ = 1 or 4
OIL_HTRB
H-DO
unit_typ = 1 or 4 and
cpb1_mta > 0
PD_P_A
PSI
H-AI
recl_opt = yes
PD_P_B
PSI
H-AI
SP_A
PSI
H-AI
all
SP_B
PSI
H-AI
all
SAFE_ALM
H-DO
alll
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
ECG-UG-02-002
Rev: Original
Page: 81/98
POINT NAMES
DESCRIPTIONS
UNITS
TYPE
S-AI
ALM
CAPA_T
Percent
S-A
CAPB_T
Percent
S-A
CAP_T
Percent
S-A
CAP_T_AV
Percent
S-A
CHILSTAT
S-D
CHIL_OCC
S-D
CHIL_S_S
S-D
CL_PUMP1
S-D
CL_PUMP2
S-D
COND_PMP
S-D
COND_SP
Consensing Setpoint
S-A
COOLHEAT
S-D
CTRL_PNT
S-A
CTRL_WT
S-A
DEM_LIM
Percent
S-A
DSH_A
^F
S-A
DSH_B
^F
S-A
DOP_A1
psi
S-A
DOP_A2
psi
S-A
DOP_B1
psi
S-A
DOP_B2
psi
S-A
EMSTOP
S-D
EWT
S-A
EXV_A
S-A
EXV_B
S-A
FAN_ST_A
S-A
FAN_ST_B
S-A
HC_SEL
HR_MACH
S-A
Hours
S-A
HR_CP_A1
Hours
S-A
HR_CP_A2
Hours
S-A
HR_CP_B1
Hours
S-A
HR_CP_B2
Hours
S-A
LAG_LIM
S-A
LCW_STPT
S-A
LWT
S-A
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
POINT NAMES
ECG-UG-02-002
Rev: Original
DESCRIPTIONS
Page: 82/98
UNITS
TYPE
MIN_LEFT
min
S-A
PINCH_A
^F
S-A
PINCH_B
^F
S-A
RECL_SEL
Reclaim Select
S-D
S-D
ROT PUMP
S RESET
SCT_A
S-D
S-A
SCT_B
S-A
SMZ
S-A
SP_OCC
S-D
SST_A
S-A
SST_B
S-A
STATE
S-A
S-A
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
COOL LWT
COOL EWT
CHWSTEMP
COND LWT
COND EWT
DP A
SP A
EXT VDC
MUX DI 1
onoff sw
spt sw
hc sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
CONDPUMP
ALARM A
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
SAFE ALM
EXV BOARD #1
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
AI
AI
Page: 83 / 98
SCPM BOARD #1
Address =84
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Channel 93
Channel 94
ECG-UG-02-002
Rev: Original
EXV ST A
-MTQ RESA
-
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
AUXILIARY BOARD # 1
Address = 49
Channel 49
Ch 49 bit-0
Ch 49 bit-1
Ch 49 bit-2
Ch 49 bit-3
Ch 49 bit-4
Ch 49 bit-5
Ch 49 bit-6
Ch 49 bit-7
Channel 50
Channel 51
Channel 52
Channel 53
Channel 54
Channel 55
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
AI
AI
AI
HD A
-
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
EXV BOARD # 1
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
AI
AI
EXV
EXV
MTQ
MTQ
ST A
ST B
RESA
RESB
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Channel 93
Channel 94
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
SCPM BOARD #2
Address = 95
Channel 95
Channel 96
96 - bit 0
96 - bit 1
96 - bit 2
96 - bit 3
96 - bit 4
96 - bit 5
Channel 97
Channel 98
Channel 99
Channel 100
Channel 101
Channel 102
Channel 103
Channel 104
Channel 105
Page: 84 / 98
SCPM BOARD #1
Address =84
COOL LWT
COOL EWT
CHWSTEMP
COND LWT
COND EWT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
hc sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
CONDPUMP
ALARM A
ALARM B
SAFE ALM
ECG-UG-02-002
Rev: Original
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A2
CPA2 MUX
cpa2 mc1
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
SCPM BOARD #3
Address =106
Channel 106
Channel 107
107 - bit 0
107 - bit 1
107 - bit 2
107 - bit 3
107 - bit 4
107 - bit 5
Channel 108
Channel 109
Channel 110
Channel 111
Channel 112
Channel 113
Channel 114
Channel 115
Channel 116
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1 TMP
CPB1 STA
-
SCPM BOARD #4
Address = 117
Channel 117
Channel 118
118 - bit 0
118 - bit 1
118 - bit 2
118 - bit 3
118 - bit 4
118 - bit 5
Channel 119
Channel 120
Channel 121
Channel 122
Channel 123
Channel 124
Channel 125
Channel 126
Channel 127
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B2
CPB2 MUX
cpb2 mc1
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
AUXILIARY BOARD # 1
Address = 49
Channel 49
Ch 49 bit-0
Ch 49 bit-1
Ch 49 bit-2
Ch 49 bit-3
Ch 49 bit-4
Ch 49 bit-5
Ch 49 bit-6
Ch 49 bit-7
Channel 50
Channel 51
Channel 52
Channel 53
Channel 54
Channel 55
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
AI
AI
AI
HD A
HD B
-
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
EXV BOARD # 1
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
AI
AI
EXV
EXV
MTQ
MTQ
ST A
ST B
RESA
RESB
47
48
49
50
51
52
AI
AI
AI
AI
AO
AO
SCPM BOARD
Address = 84
COOL LWT
COOL EWT
CHWSTEMP
COND LWT
COND EWT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
hc sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
CONDPUMP
ALARM A
ALARM B
SAFE ALM
HD A
HD B
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Chan 93-94
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
SCPM BOARD
Address = 40
Channel 95
Channel 96
96 - bit 0
96 - bit 1
96 - bit 2
96 - bit 3
96 - bit 4
96 - bit 5
Channel 97
Channel 98
Channel 99
Channel 100
Channel 101
Channel 102
Channel 103
Chan104-105
ECG-UG-02-002
Rev: Original
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
CP A2
CPA2 MUX
cpa2 mc1
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
SCPM BOARD
Address = 106
Channel 106
Channel 107
107 - bit 0
107 - bit 1
107 - bit 2
107 - bit 3
107 - bit 4
107 - bit 5
Channel 108
Channel 109
Channel 110
Channel 111
Channel 112
Channel 113
Channel 114
Chan 115-16
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1 TMP
CPB1 STA
-
SCPM BOARD
Address = 117
Channel 117
Channel 118
118 - bit 0
118 - bit 1
118 - bit 2
118 - bit 3
118 - bit 4
118 - bit 5
Channel 119
Channel 120
Channel 121
Channel 122
Channel 123
Channel 124
Channel 125
Chan126-127
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
CP B2
CPB2 MUX
cpb2 mc1
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
Page: 85 / 98
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
EXT VDC
MUX DI 1
onoff sw
spt sw
hc sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Channel 93
Channel 94
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
OIL HTRA
COOL HTR
ALARM A
REFA ISO
SAFE ALM
EXV ST A
AI
AI
Page: 86 / 98
EXV BOARD
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
ECG-UG-02-002
Rev: Original
MTQ RESA
-
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
AUXILIARY BOARD # 1
Address = 49
Channel 49
Ch 49 bit-0
Ch 49 bit-1
Ch 49 bit-2
Ch 49 bit-3
Ch 49 bit-4
Ch 49 bit-5
Ch 49 bit-6
Ch 49 bit-7
Channel 50
Channel 51
Channel 52
Channel 53
Channel 54
Channel 55
MUX FAN1
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
AI
AI
AI
fan
fan
fan
fan
HD
-
a1
a2
a3
a4
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
EXT VDC
MUX DI 1
onoff sw
spt sw
hc sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Channel 93
Channel 94
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
OIL HTRA
COOL HTR
ALARM A
REFA ISO
SAFE ALM
EXV ST A
AI
AI
Page: 87 / 98
EXV BOARD
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
ECG-UG-02-002
Rev: Original
MTQ RESA
-
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
AUXILIARY BOARD # 1
Address = 49
Channel 49
Ch 49 bit-0
Ch 49 bit-1
Ch 49 bit-2
Ch 49 bit-3
Ch 49 bit-4
Ch 49 bit-5
Ch 49 bit-6
Ch 49 bit-7
DO
DO
DO
DO
DO
DO
DO
DO
MUX FAN1
fan a1
fan a2
fan a3
fan a4
-
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
SCPM BOARD #1
Address =84
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
recl sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
OIL HTRA
OIL HTRB
ALARM A
ALARM B
SAFE ALM
EXV BOARD
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
AI
AI
EXV
EXV
MTQ
MTQ
ST A
ST B
RESA
RESB
47
48
49
50
51
52
AI
AI
AI
AI
AO
AO
HR LWT
HR EWT
HD A
HD_B
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Channel 93
Channel 94
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
SCPM BOARD #2
Address = 95
Channel 95
Channel 96
96 - bit 0
96 - bit 1
96 - bit 2
96 - bit 3
96 - bit 4
96 - bit 5
Channel 97
Channel 98
Channel 99
Channel 100
Channel 101
Channel 102
Channel 103
Channel 104
Channel 105
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A2
CPA2 MUX
cpa2 mc1
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
ECG-UG-02-002
Rev: Original
Page: 88 / 98
2 to 4 compressors,
No Aux Board
SCPM BOARD #3
Address =106
Channel 106
Channel 107
107 - bit 0
107 - bit 1
107 - bit 2
107 - bit 3
107 - bit 4
107 - bit 5
Channel 108
Channel 109
Channel 110
Channel 111
Channel 112
Channel 113
Channel 114
Channel 115
Channel 116
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1 TMP
CPB1 STA
-
SCPM BOARD #4
Address = 117
Channel 117
Channel 118
118 - bit 0
118 - bit 1
118 - bit 2
118 - bit 3
118 - bit 4
118 - bit 5
Channel 119
Channel 120
Channel 121
Channel 122
Channel 123
Channel 124
Channel 125
Channel 126
Channel 127
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B2
CPB2 MUX
cpb2 mc1
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
Channel 39
39 - bit 0
39 - bit 1
39 - bit 2
39 - bit 3
MUX FAN1
fan a1
fan a2
fan b1
fan b2
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
SCPM BOARD #1
Address =84
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
recl sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
CONDPUMP
OIL HTRA
OIL HTRB
ALARM A
ALARM B
SAFE ALM
EXV BOARD
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
AI
AI
EXV
EXV
MTQ
MTQ
ST A
ST B
RESA
RESB
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Channel 93
Channel 94
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
SCPM BOARD #2
Address = 95
Channel 95
Channel 96
96 - bit 0
96 - bit 1
96 - bit 2
96 - bit 3
96 - bit 4
96 - bit 5
Channel 97
Channel 98
Channel 99
Channel 100
Channel 101
Channel 102
Channel 103
Channel 104
Channel 105
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A2
CPA2 MUX
cpa2 mc1
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
ECG-UG-02-002
Rev: Original
Page: 89 / 98
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1 TMP
CPB1 STA
-
Channel 49
Ch 49 bit-0
Ch 49 bit-1
Ch 49 bit-2
Ch 49 bit-3
Ch 49 bit-4
Ch 49 bit-5
Ch 49 bit-6
Ch 49 bit-7
DO
DO
DO
DO
DO
DO
DO
DO
MUX FAN1
fan a1
fan a2
fan a3
fan a4
fan b1
fan b2
fan b3
fan b4
SCPM BOARD #4
Address = 117
Channel 117
Channel 118
118 - bit 0
118 - bit 1
118 - bit 2
118 - bit 3
118 - bit 4
118 - bit 5
Channel 119
Channel 120
Channel 121
Channel 122
Channel 123
Channel 124
Channel 125
Channel 126
Channel 127
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B2
CPB2 MUX
cpb2 mc1
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
AI
AI
AI
MUX HRDO
pd val a
hr val a
refa iso
pd val b
hr val b
refb iso
cond htr
cool htr
HR LWT
HR EWT
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
SCPM BOARD #1
Address =84
DI
DI
DI
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
recl_sw
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
11 - bit 3
11 - bit 4
11 - bit 5
11 - bit 6
11 - bit 7
Channel 19
Channel 20
Channel 21
Channel 22
Channel 23
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
CONDPUMP
OIL HTRA
OIL_HTRB
Channel 92
Channel 93
Channel 94
Channel 24
Channel 25
Channel 26
DO
DO
DO
ALARM A
ALARM B
SAFE ALM
EXV BOARD
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
AI
AI
EXV ST A
EXV ST B
-
DO
ECG-UG-02-002
Rev: Original
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1_TMP
Channel 106
Channel 107
107 - bit 0
107 - bit 1
107 - bit 2
107 - bit 3
107 - bit 4
107 - bit 5
Channel 108
Channel 109
Channel 110
Channel 111
Channel 112
Channel 113
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1_TMP
AI
AI
AI
CPA1 STA
-
Channel 114
Channel 115
Channel 116
AI
AI
AI
CPB1 STA
-
SCPM BOARD #2
Address = 95
Channel 95
Channel 96
96 - bit 0
DO
96 - bit 1
96 - bit 2
96 - bit 3
96 - bit 4
96 - bit 5
Channel 97
Channel 98
Channel 99
Channel 100
Channel 101
Channel 102
Channel 103
Channel 104
Channel 105
DO
SCPM BOARD #4
Address = 117
Channel 117
Channel 118
118 - bit 0
DO
DO
CP A2
CPA2 MUX
cpa2_mc1
DO
CP B2
CPB2 MUX
cpb2_mc1
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
118 - bit 1
118 - bit 2
118 - bit 3
118 - bit 4
118 - bit 5
Channel 119
Channel 120
Channel 121
Channel 122
Channel 123
Channel 124
Channel 125
Channel 126
Channel 127
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
Page: 90 / 98
Channel 49
Ch 49 bit-0
Ch 49 bit-1
Ch 49 bit-2
Ch 49 bit-3
Ch 49 bit-4
Ch 49 bit-5
Ch 49 bit-6
Ch 49 bit-7
DO
DO
DO
DO
DO
DO
DO
DO
MUX FAN1
fan a1
fan a2
fan a3
fan a4
fan a5
fan a6
fan a7
fan a8
DO
DO
DO
DO
DO
DO
DO
DO
MUX FAN2
fan b1
fan b2
fan b3
fan b4
fan b5
fan b6
fan b7
fan b8
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
AI
AI
AI
MUX HRDO
pd val a
hr val a
refa iso
pd val b
hr val b
refb iso
cond htr
cool htr
HR LWT
HR EWT
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
recl sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
CONDPUMP
OIL HTRA
OIL HTRB
ALARM A
ALARM B
SAFE ALM
AI
AI
EXV
EXV
MTQ
MTQ
ST B
ST B
RESARESB
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A2
CPA2 MUX
cpa2 mc1
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
ECG-UG-02-002
Rev: Original
2 to 4 compressors
SCPM BOARD #3 Address =106
Channel 106
Channel 107
107 - bit 0
107 - bit 1
107 - bit 2
107 - bit 3
107 - bit 4
107 - bit 5
Channel 108
Channel 109
Channel 110
Channel 111
Channel 112
Channel 113
Channel 114
Channel 115
Channel 116
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1 TMP
CPB1 STA
-
Page: 91 / 98
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
MUX FAN1
fan a1
fan a2
fan a3
fan b1
fan b2
fan b3
HD A
HD B
-
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B2
CPB2 MUX
cpb2 mc1
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
AI
AI
AI
MUX HRDO
pd val a
hr val a
refa iso
pd val b
hr val b
refb iso
cond htr
cool htr
HR WTRVL
HR LWT
HR EWT
PD P A
PD_P_B
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
recl sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
CONDPUMP
OIL HTRA
OIL HTRB
ALARM A
ALARM B
SAFE ALM
AI
AI
EXV
EXV
MTQ
MTQ
ST B
ST B
RESA
RESB
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A2
CPA2 MUX
cpa2 mc1
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
ECG-UG-02-002
Rev: Original
2 to 4 Compressors
SCPM BOARD #3 Address =106
Channel 106
Channel 107
107 - bit 0
107 - bit 1
107 - bit 2
107 - bit 3
107 - bit 4
107 - bit 5
Channel 108
Channel 109
Channel 110
Channel 111
Channel 112
Channel 113
Channel 114
Channel 115
Channel 116
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1 TMP
CPB1 STA
-
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B2
CPB2 MUX
cpb2 mc1
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
Page: 92 / 98
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
MUX FAN1
ffan a1
fan a2
fan a3
fan a4
fan a5
fan a6
fan a7
HD A
-
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
MUX FAN1
fan b1
fan b2
fan b3
fan b4
fan b5
fan b6
fan b7
HD B
-
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AI
AI
AI
AI
MUX HRDO
pd val a
hr val a
refa iso
pd val b
hr val b
refb iso
cond htr
cool htr
HR WTRVL
HR LWT
HR EWT
PD P A
PD_P_B
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
OIL HTRA
OIL HTRB
ALARM A
ALARM B
unused
EXV BOARD
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
AI
AI
EXV
EXV
MTQ
MTQ
ST A
ST B
RESA
RESB
47
48
49
50
51
52
AI
AI
AI
AI
AO
AO
HR
HR
HD
HD
LWT
EWT
A
B
Page: 93 / 98
>2 separate fan stages, 2 to 4 Compressors, Cooler heater = NO, Reclaim option = no,
SCPM BOARD #1
Address =84
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
recl sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
ECG-UG-02-002
Rev: Original
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Channel 93
Channel 94
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
SCPM BOARD #2
Address = 95
Channel 95
Channel 96
96 - bit 0
96 - bit 1
96 - bit 2
96 - bit 3
96 - bit 4
96 - bit 5
Channel 97
Channel 98
Channel 99
Channel 100
Channel 101
Channel 102
Channel 103
Channel 104
Channel 105
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A2
CPA2 MUX
cpa2 mc1
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
Channel 26 : DO unused
Channel 27-28: virtual
Channel 80 - 83 : free
SCPM BOARD #3
Address =106
Channel 106
Channel 107
107 - bit 0
107 - bit 1
107 - bit 2
107 - bit 3
107 - bit 4
107 - bit 5
Channel 108
Channel 109
Channel 110
Channel 111
Channel 112
Channel 113
Channel 114
Channel 115
Channel 116
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1 TMP
CPB1 STA
-
SCPM BOARD #4
Address = 117
Channel 117
Channel 118
118 - bit 0
118 - bit 1
118 - bit 2
118 - bit 3
118 - bit 4
118 - bit 5
Channel 119
Channel 120
Channel 121
Channel 122
Channel 123
Channel 124
Channel 125
Channel 126
Channel 127
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B2
CPB2 MUX
cpb2 mc1
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
4xDO BOARD #1
Address = 39
Channel 39
39 - bit 0
39 - bit 1
39 - bit 2
39 - bit 3
MUX FAN1
fan a1
fan a2
fan a3
fan a4
4xDO BOARD #2
Address = 43
Channel 43
43 - bit 0
43 - bit 1
43 - bit 2
43 - bit 3
MUX FAN2
fan b1
fan b2
fan b3
fan b4
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
SCPM BOARD #1
Address =84
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
recl sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
HPUMP
OIL HTRA
OIL HTRB
ALARM A
ALARM B
unused
EXV BOARD
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
AI
AI
EXV
EXV
MTQ
MTQ
ST A
ST B
RESA
RESB
47
48
49
50
51
52
AI
AI
AI
AI
AO
AO
HD A
HD B
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Channel 93
Channel 94
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
SCPM BOARD #2
Address = 95
Channel 95
Channel 96
96 - bit 0
96 - bit 1
96 - bit 2
96 - bit 3
96 - bit 4
96 - bit 5
Channel 97
Channel 98
Channel 99
Channel 100
Channel 101
Channel 102
Channel 103
Channel 104
Channel 105
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A2
CPA2 MUX
cpa2 mc1
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
Channel 26 : DO unused
Channel 27-28: virtual
Channel 80 - 83 : free
ECG-UG-02-002
Rev: Original
Page: 94 / 98
Channel 106
Channel 107
107 - bit 0
107 - bit 1
107 - bit 2
107 - bit 3
107 - bit 4
107 - bit 5
Channel 108
Channel 109
Channel 110
Channel 111
Channel 112
Channel 113
Channel 114
Channel 115
Channel 116
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1 TMP
CPB1 STA
-
SCPM BOARD #4
Address = 117
Channel 117
Channel 118
118 - bit 0
118 - bit 1
118 - bit 2
118 - bit 3
118 - bit 4
118 - bit 5
Channel 119
Channel 120
Channel 121
Channel 122
Channel 123
Channel 124
Channel 125
Channel 126
Channel 127
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B2
CPB2 MUX
cpb2 mc1
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
AI
AI
AI
AI
AI
AI
AO
DI
DI
DI
DI
DI
DI
DI
DI
MUX
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
HR LWT
HR EWT
PD P A
PD P B
HR WTRVL
MUX NRCP
hr val a
hr val b
cond htr
pd val a
pd val b
cool htr
refa iso
refb iso
virtual-unused
4xDO BOARD #1
Address = 39
Channel 39
39 - bit 0
39 - bit 1
39 - bit 2
39 - bit 3
MUX FAN1
fan a1
fan a2
fan b1
fan b2
CARRIER SA
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
DI
DI
DI
DI
DI
DO
DO
DO
DO
DO
DO
DO
DO
SCPM BOARD #1
Address =84
COOL LWT
COOL EWT
CHWSTEMP
OAT
DP A
SP A
DP B
SP B
EXT VDC
MUX DI 1
onoff sw
spt sw
recl sw
lim sw
lock 1
elec box
cond_flow
pump_def
CPUMP 1
CPUMP 2
CONDPUMP
OIL HTRA
OIL HTRB
ALARM A
ALARM B
unused
EXV BOARD
Address = 29
Channel 29
Channel 33
Channel 37
Channel 38
AI
AI
EXV
EXV
MTQ
MTQ
ST A
ST B
RESA
RESB
47
48
49
50
51
52
AI
AI
AI
AI
AO
AO
HD A
HD B
Channel 84
Channel 85
85 - bit 0
85 - bit 1
85 - bit 2
85 - bit 3
85 - bit 4
85 - bit 5
Channel 86
Channel 87
Channel 88
Channel 89
Channel 90
Channel 91
Channel 92
Channel 93
Channel 94
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A1
CPA1 MUX
cpa1 mc1
cpa1 mc2
cpa1 ols
a1 ldr 1
a1 ldr 2
oilpmp a
CPA1 PUL
CPA1 CUR
CPA1 OP
CPA1 ECP
CPA1 DGT
CPA1 TMP
CPA1 STA
-
SCPM BOARD #2
Address = 95
Channel 95
Channel 96
96 - bit 0
96 - bit 1
96 - bit 2
96 - bit 3
96 - bit 4
96 - bit 5
Channel 97
Channel 98
Channel 99
Channel 100
Channel 101
Channel 102
Channel 103
Channel 104
Channel 105
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP A2
CPA2 MUX
cpa2 mc1
cpa2 mc2
cpa2 ols
a2 ldr 1
a2 ldr 2
CPA2 CUR
CPA2 OP
CPA2 ECP
CPA2 DGT
CPA2 TMP
CPA2 STA
-
Channel 26 : DO unused
Channel 27-28: virtual
Channel 80 - 83 : free
ECG-UG-02-002
Rev: Original
Page: 95 / 98
Channel 106
Channel 107
107 - bit 0
107 - bit 1
107 - bit 2
107 - bit 3
107 - bit 4
107 - bit 5
Channel 108
Channel 109
Channel 110
Channel 111
Channel 112
Channel 113
Channel 114
Channel 115
Channel 116
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B1
CPB1 MUX
cpb1 mc1
cpb1 mc2
cpb1 ols
b1 ldr 1
b1 ldr 2
oilpmp b
CPB1 PUL
CPB1 CUR
CPB1 OP
CPB1 ECP
CPB1 DGT
CPB1 TMP
CPB1 STA
-
SCPM BOARD #4
Address = 117
Channel 117
Channel 118
118 - bit 0
118 - bit 1
118 - bit 2
118 - bit 3
118 - bit 4
118 - bit 5
Channel 119
Channel 120
Channel 121
Channel 122
Channel 123
Channel 124
Channel 125
Channel 126
Channel 127
DO
DO
DO
DO
DO
DO
DO
DO
AI
AI
AI
AI
AI
AI
AI
AI
CP B2
CPB2 MUX
cpb2 mc1
cpb2 mc2
cpb2 ols
b2 ldr 1
b2 ldr 2
CPB2 CUR
CPB2 OP
CPB2 ECP
CPB2 DGT
CPB2 TMP
CPB2 STA
-
AI
AI
AI
AI
AI
AI
AO
DI
DI
DI
DI
DI
DI
DI
DI
MUX
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
HR LWT
HR EWT
PD P A
PD P B
HR WTRVL
MUX NRCP
hr val a
hr val b
cond htr
pd val a
pd val b
cool htr
refa iso
refb iso
virtual-unused
4xDO BOARD #1
Address = 39
Channel 39
39 - bit 0
39 - bit 1
39 - bit 2
39 - bit 3
MUX FAN1
fan a1
fan a2
fan a3
fan a4
4xDO BOARD #2
Address = 43
Channel 43
43 - bit 0
43 - bit 1
43 - bit 2
43 - bit 3
MUX FAN2
fan b1
fan b2
fan b3
fan b4
CARRIER SA
ECG-UG-02-002
Rev: Original
Page: 96 / 98
CARRIER SA
ECG-UG-02-002
Rev : Original
Page: 96 / 98
JBUS
ACCESS
CONTENT
TYPE**
0 [h00]
1 [h01]
2 [h02]
3 [h03]
4 [h04]
Control Point
5 [h05]
6 [h06]
Demand Limit
7 [h07]
Chiller State
8 [h08]
Alarm State
9 [h09]
INT
REMARK**
FLOAT
0 = cool, 1 = heat
10 [h0A]
11 [h0B]
12 [h0C]
13 [h0D]
Compressor A1 Hours
14 [h0E]
Compressor A2 Hours
15 [h0F]
Compressor B1 Hours
16 [h10]
Compressor B2 Hours
---
40 [h28]
41 [h29]
Active alarm 1*
42 [h2A]
Active alarm 2*
43 [h2B]
Active alarm 3*
44 [h2C]
Active alarm 4*
45 [h2D]
Active alarm 5*
61 [h3D]
66 [h42]
97 [h61]
R/W
Cooling Setpoint 1
98 [h62]
R/W
Cooling Setpoint 2
99 [h62]
R/W
Heating Setpoint
107 [6Bh]
R/W
108 [h6C]
R/W
Control Point
109 [h6D]
R/W
112 [70h]
R/W
Default = 9600
113 [71h]
R/W
JBUS address
Default = 1
114 [72h]
R/W
X
X
Provide the code of up to 5 active alarms. These
are stored in arrival order.
Alarms read from CCN/JBUS are alarm index but
not alarms codes as follows
from iom, alarm codes 101 to 117 , index = 88
(code 101) to 104 ( code 117)
from iom, alarm codes 201 to 217 , index = 105
(code 201) to 121 (code 217)
-------from iom, alarm codes 401 to 417 , index = 139
(code 401) to 155 (code 417)
2 = CCN communication failure
0 = Off 1 = On
X
X
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
PRO-DIALOG 30DQ
PRO-DIALOG 30GH
CCN/JBUS
GATEWAY
J-BUS/RS-485
TO
BMS
ASCII/RS-232
TO
BMS
ASCII/RS-232
TO
BMS
DATAPORT II
DATAPORT I
Page:97 / 98
COMFORT
NETWORK
FLOTRONIC II
BUILDING
AUTODIAL
GATEWAY
SUPERVISOR
FSM
REPEATER
MODEM
39 L
LOCAL BUILDING SUPERVISOR
FLOTRONIC I
GW
TSM
NETW
ORK
S E RV
ICE
TOOL
19XL
39 L
SER
WSM
39 L
CSM
AIR TERMINAL
35
DATA COLLECTION
DATA TRANSFERT
VIC
EW
IND
OW
2
MODEM
AIR TERMINAL
37
SAM
NDS BRIDGE
AUTODIAL
GATEWAY
SECONDARY
BUS
BUILDING
SUPERVISOR
3200 MP
GW
REPEATER
FLOTRONIC I
GW
PRIMARY CCN BUS
RS-485
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
Page:98 / 98
CARRIER
NORMAL
PARTIAL: ALARM XX
SHUTDOWN: ALARM XX
CONFORT
NETWORK
ON - COOLING
NORMAL
ENTERING
05-20-94
15:00
255 hours
LEAVING
OUTDOOR
12.5
6.7
12
CAPACITY
HEATCOOL
PUMP
50
CTRL PNT
CTRL WT
LIMIT
6.0
6.7
100
CCN
LOCAL
LOCAL
REMOTE
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
MENU