AISI Code of Standard Practice 2006

Download as pdf or txt
Download as pdf or txt
You are on page 1of 31
At a glance
Powered by AI
The key takeaways are that this document outlines standards and best practices for cold-formed steel structural framing design, fabrication, and installation.

The purpose of this document is to address trade practices for design, fabrication and installation of cold-formed steel structural framing products.

This document is endorsed by the Association of the Wall and Ceiling Industries, Steel Framing Alliance, and Steel Stud Manufacturers Association.

practice guide

1140 Connecticut NW
Suite 705
Washington DC 20036
www.steel.org

803 West Broad Street


Suite 600
Falls Church, VA 22046
www.awci.org

National Housing Center


1201 15th Street NW
Suite 320
Washington DC 20005
www.steelframingalliance.com

8 S. Michigan Avenue
Suite 1000
Chicago IL 60603
www.ssma.com

TM

CF06-1-COSP-2006-0906-1K-AP

Code of Standard Practice for


Cold-Formed Steel Structural Framing
Committee on Framing Standards

2006 EDITION
with Commentary

Endorsed by Association of the Wall and


Ceiling Industries, Steel Framing Alliance,
and Steel Stud Manufacturers Association

Code of Standard Practice


for Cold-Formed Steel Structural Framing

September 2006
Practice Guide CF06-1

Committee on Framing Standards


American Iron and Steel Institute
1140 Connecticut Avenue, NW
Washington, DC 20036

ii

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

DISCLAIMER
The material contained herein has been developed by the American Iron and Steel Institute
Committee on Framing Standards. The Committee has made a diligent effort to present
accurate, reliable, and useful information on trade practices for fabrication and installation of
cold-formed steel structural framing. The Committee acknowledges and is grateful for the
contributions of the numerous engineers, manufacturers, contractors and others who have
contributed to the body of knowledge on the subject. Specific references are included in the Code
of Standard Practice document.
With anticipated improvements in understanding of the behavior of cold-formed steel
framing and the continuing development of new technology, this material will become dated. It
is anticipated that AISI will publish updates of this material as new information becomes
available, but this cannot be guaranteed.
No conflict between this Code of Standard Practice and any legal building regulation is
intended. This Code of Standard Practice is intended only to supplement and amplify such legal
building regulations and laws.
The materials set forth herein are for general purposes only. They are not a substitute for
competent professional advice. Application of this information to a specific project, particularly
if included as part of a contract, should be reviewed by competent legal counsel. Anyone
making use of the information set forth herein does so at their own risk and assumes any and all
liability arising there from.

1st Printing September 2006


Copyright American Iron and Steel Institute 2006

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

iii

PREFACE
The American Iron and Steel Institute Committee on Framing Standards has developed this
Code of Standard Practice for Cold-Formed Steel Structural Framing [Code of Standard Practice] to
address trade practices for design, fabrication and installation of cold-formed steel structural
framing products.
This Code of Standard Practice, as revised to date, defines and sets forth accepted norms of
good practice and has been developed and reviewed by a peer committee of the cold-formed steel
structural framing industry. The practices defined in this Code of Standard Practice are the
commonly accepted standards of custom and usage for cold-formed steel structural framing
fabrication and installation. This voluntary document is intended to be used by owners
representatives, design professionals, contractors, construction managers, suppliers, manufacturers,
installers and others on individual projects that utilize cold-formed steel structural framing.
This Code of Standard Practice is not applicable to non-structural members, including but not
limited to interior drywall framing, which is addressed by ASTM C645 and C754, or structural
steel, structural steel joists, steel deck, metal building systems or rack structures, which are
addressed by AISC, SJI, SDI, MBMA and RMI, respectively.
The Committee acknowledges and is grateful for the numerous engineers, manufacturers,
contractors and others who have contributed to the body of knowledge on the subject. The
Committee wishes to also express their appreciation for the support of the Association of the
Wall and Ceiling Industries (AWCI) International, Steel Framing Alliance (SFA) and Steel Stud
Manufacturers Association (SSMA).
The first edition of this Code of Standard Practice was published in 2005. This 2006 Edition
includes new provisions on revisions, the RFI process, contract price adjustment and scheduling.
A non-mandatory commentary, shown in gray boxes throughout the document, is also added to
provide background and further explanation for the corresponding provisions.

iv

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

AISI COMMITTEE ON FRAMING STANDARDS


Richard Haws, Chairman

NUCONSTEEL

Steve Fox, Vice Chairman

Canadian Sheet Steel Building Institute

Jay Larson, Secretary

American Iron and Steel Institute

Don Allen

Steel Stud Manufacturers Association

Bill Babich

Alpine Engineered Products

John Butts

John F. Butts & Associates

Brad Cameron

Keymark Engineering

Nader Elhajj

NAHB Research Center

Jeff Ellis

Simpson Strong-Tie

Ray Frobosilo

Super Stud Building Products

Michael Gardner

Gypsum Association

Stephen Gatto

Compass International

Greg Greenlee

USP Structural Connectors

John Heydon

Heydon Building Systems

Jeff Klaiman

ADTEK Engineers

Roger LaBoube

University of Missouri-Rolla

John Matsen

Matsen Ford Design Associates

Michael Meek

Allied Studco

Kenneth Pagano

Scosta Corporation

Mike Pellock

Aegis Metal Framing

Nabil Rahman

The Steel Network

Greg Ralph

Dietrich Industries

Gary Rolih

Consultant

Ben Schafer

Johns Hopkins University

Reynaud Serrette

Santa Clara University

Fernando Sesma

California Expanded Metal Products

Sutton Stephens

Kansas State University

Tom Trestain

T.W.J. Trestain Structural Engineering

Steven Walker

Steven H. Walker, P.Eng.

Lei Xu

University of Waterloo

Rahim Zadeh

Marino\Ware

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

CODE OF STANDARD PRACTICE SUBCOMMITTEE


Jeff Klaiman, Chairman

ADTEK Engineers

Jay Larson, Secretary

American Iron and Steel Institute

Don Allen

Steel Stud Manufacturers Association

Bill Babich

Alpine Engineered Products

Nader Elhajj

NAHB Research Center

Kirk Grundahl

WTCAs Cold-Formed Steel Council

Richard Layding

NUCONSTEEL

Kenneth Pagano

Scosta Corporation

Wei Pei

Wei Pei Structural Engineers

Mike Pellock

Aegis Metal Framing

Nabil Rahman

The Steel Network

Greg Ralph

Dietrich Industries

Fernando Sesma

California Expanded Metal Products

Steven Walker

Steven H. Walker, P.Eng.

Rahim Zadeh

Marino\Ware

AISI also acknowledges the following individuals who helped develop this document.
Brent Allen

South Texas Drywall

John Carpenter

Alpine Engineered Products (retired)

vi

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

TABLE OF CONTENTS
CODE OF STANDARD PRACTICE
FOR
COLD-FORMED STEEL STRUCTURAL FRAMING
DISCLAIMER ............................................................................................................................................. ii
PREFACE..................................................................................................................................................iii
AISI COMMITTEE ON FRAMING STANDARDS ....................................................................................... iv
CODE OF STANDARD PRACTICE SUBCOMMITTEE................................................................................ v
A. GENERAL ............................................................................................................................................1
A1 Scope ............................................................................................................................................. 1
A2 Definitions .................................................................................................................................... 1
A3 Referenced Documents............................................................................................................... 5
A4 Responsibility for Design ........................................................................................................... 6
B. CLASSIFICATION OF MATERIALS .....................................................................................................8
B1 Definition of Cold-Formed Steel Structural Framing............................................................. 8
B2 Other Items................................................................................................................................... 8
C. CONTRACT DOCUMENTS................................................................................................................ 10
C1 Responsibilities .......................................................................................................................... 10
C2 Limit of Responsibility ............................................................................................................. 11
C3 Jurisdiction ................................................................................................................................. 11
C4 Discrepancies ............................................................................................................................. 11
C5 Revisions..................................................................................................................................... 11
D. INSTALLATION DRAWINGS............................................................................................................. 13
D1 Owners Responsibility.............................................................................................................. 13
D2 Component Manufacturer and/or Installer Responsibility ................................................ 13
D3 Review Process .......................................................................................................................... 14
D4 Responsibility............................................................................................................................. 14
E. MATERIALS ..................................................................................................................................... 16
E1 Structural Members................................................................................................................... 16
E2 Fasteners and Connection Hardware ..................................................................................... 16
E3 Preparation of Material............................................................................................................. 16
E4 Member Identification .............................................................................................................. 16
E5 Special Marking ......................................................................................................................... 16
E6 Camber........................................................................................................................................ 16
F. INSTALLATION ................................................................................................................................. 17
F1 Scope ........................................................................................................................................... 17
F2 Site Conditions........................................................................................................................... 17
F3 Delivery, Handling and Storage of Materials........................................................................ 17
F4 Field Modifications and Repairs ............................................................................................. 18
F5 Installation Tolerances .............................................................................................................. 18
G. QUALITY CONTROL.......................................................................................................................... 19
G1 General........................................................................................................................................ 19
G2 Material Inspection.................................................................................................................... 19
G3 Workmanship ............................................................................................................................ 19

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

vii

H. CONTRACTUAL RELATIONS............................................................................................................ 20
H1 Presentation of Proposals ......................................................................................................... 20
H2 Acceptance of Proposals........................................................................................................... 20
H3 Terms of Payment ..................................................................................................................... 20
H4 The RFI Process.......................................................................................................................... 20
H5 Revisions to the Contract Documents .................................................................................... 21
H6 Change Orders........................................................................................................................... 21
H7 Contract Price Adjustment....................................................................................................... 21
H8 Scheduling .................................................................................................................................. 21

viii

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

This Page Intentionally Left Blank

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

CODE OF STANDARD PRACTICE


FOR
COLD-FORMED STEEL STRUCTURAL FRAMING
A. GENERAL
A1 Scope
In the absence of specific instructions to the contrary in the contract documents, the trade
practices that are defined in this Code of Standard Practice shall govern the design, fabrication
and installation of cold-formed steel structural framing.
Commentary:
The practices defined in this Code of Standard Practice are the commonly accepted standards
of custom and usage for the fabrication and installation of cold-formed steel structural framing,
which generally represent the most efficient approach. This Code of Standard Practice is not
intended to define a professional standard of care for the owners representatives or change the
duties and responsibilities of the owner, contractor, design professionals (i.e., architect or
structural engineer-of record) from those set forth in the contract documents. Nor does it assign
to the owner or design professionals any duty or authority to undertake responsibility
inconsistent with the provisions of the contract documents.
Commentary:
This Code of Standard Practice is not applicable to non-structural members, including but not
limited to interior drywall framing, which is addressed by ASTM C645 and C754, or
structural steel, structural steel joists, steel deck, metal building systems or rack structures,
which are addressed by AISC, SJI, SDI, MBMA and RMI, respectively. An extended list of
non-applicable items is given in Section B2.
A2 Definitions
Where the following terms appear in this Code of Standard Practice in italics they shall have
the meaning herein indicated. Where terms are not included, such terms shall have ordinary
accepted meaning in the context for which they are intended.
AISC. American Institute of Steel Construction.
AISI. American Iron and Steel Institute.
Applicable Building Code. Building code under which the building is designed.
Approved. Approved by a building official or design professional.
Base Steel Thickness. The thickness of bare steel exclusive of all coatings.
Blocking. C-shaped track, break shape, or flat strap material attached to structural members, flat
strap or sheathing panels to transfer shear forces.
Bracing. Structural elements that are installed to provide restraint or support (or both) to other
framing members so that the complete assembly forms a stable structure.
CASE. Council of American Structural Engineers.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

Clarification. An interpretation of the contract documents that have been released for construction,
providing an explanation that neither revises the information that has been released for
construction nor alters the cost or schedule of performance of the work.
Cold-Formed Sheet Steel. Sheet steel or strip steel that is manufactured by (1) press braking blanks
sheared from sheets or cut length of coils or plates, or by (2) continuous roll forming of cold- or
hot-rolled coils of sheet steel; both forming operations are performed at ambient room
temperature, that is, without any addition of heat such as would be required for hot forming.
Cold-Formed Steel. See Cold-Formed Sheet Steel.
Cold-Formed Steel Structural Framing. The elements of the structural frame, as given in Section B1
of this Code of Standard Practice.
Component Assembly. A fabricated assemblage of cold-formed steel structural members that is
manufactured by the component manufacturer, which may also include structural steel framing,
sheathing, insulation or other products.
Component Design Drawing. The written, graphic and pictorial definition of an individual
component assembly, which includes engineering design data.
Component Designer. The individual or organization responsible for the engineering design of
component assemblies. Also referred to as truss designer on projects involving trusses, but
hereinafter will be referred to as Component Designer.
Component Manufacturer. The individual or organization responsible for the manufacturing of
component assemblies for the project. Also referred to as truss manufacturer on projects involving
trusses, but hereinafter will be referred to as Component Manufacturer.
Component Placement Diagram. The illustration supplied by the component manufacturer
identifying the location assumed for each of the component assemblies which references each
individually designated component design drawing.
Construction Manager. The individual or organization designated by the owner to issue contracts
for the construction of the project and to purchase products.
Contract Documents. The documents, including, but not limited to, plans and specifications, which
define the responsibilities of the parties involved in bidding, purchasing, designing, supplying,
and installing cold-formed steel framing.
Contractor. The individual or organization that is contracted to assume full responsibility for the
construction of the structure.
Design Load. Applied load determined in accordance with either LRFD load combinations or ASD
load combinations, whichever is applicable.
Design Professional. An individual who is registered or licensed to practice their respective
design profession as defined by the statutory requirements of the state, province or territory in
which the project is to be constructed.
Discrepancy. Any conflicts or omissions within the contract documents, or conflicts between the
contract documents and applicable building codes, standards of good engineering or industry
practice.
Drawings. See Plans and Installation Drawings.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

Embedded Anchor. A structural anchor or device (bolt, strap, plate, etc.) intended for fastening
cold-formed steel structural framing to masonry or concrete that is installed prior to hardening of
the grout or concrete.
Framing Contractor. See installer.
Framing Material. Steel products, including but not limited to structural members and prefabricated
structural assemblies, ordered expressly for the requirements of the project.
General Contractor. See Contractor.
Installation Drawings. Drawings that show the location and installation of the cold-formed steel
structural framing.
Installer. Party responsible for the installation of cold-formed steel products.
Commentary:
While this Code of Standard Practice was patterned after a similar document by the AISC, care
was taken to use terminology to avoid confusion between material suppliers, fabricators and
trades. Therefore, the term installer is used in reference to cold-formed steel structural framing
versus the term erector typically used in reference to structural steel.
Lateral Force Resisting System. The structural elements and connections required to resist racking
and overturning due to wind and/or seismic forces imposed upon the structure in accordance
with the applicable building code.
Material Supplier. An individual or entity responsible for furnishing framing materials for the
project.
MBMA. Metal Building Manufacturers Association.
Metal Building System. A complete integrated set of mutually dependent components and
assemblies that form a building. As defined by the MBMA, a metal building system includes the
primary and secondary framing, covering, and accessories, all of which are manufactured to
permit inspection on site prior to assembly or installation.
Non-Structural Member. A member in a steel framed assembly which is limited to a transverse
(out-of-plane) load of not more than 10 lb/ft2 (480 Pa), a superimposed axial load, exclusive of
sheathing materials, of not more than 100 lb/ft (1460 N/m), or a superimposed axial load of not
more than 200 lbs (890 N).
Owner. The individual or entity organizing and financing the design and construction of the
project.
Owners Representative. The owner or individual designated contractually to act for the owner.
Owners Representative for Construction. The owner or the entity that is responsible to the owner for
the overall construction of the project, including its planning, quality and completion. This is
usually the contractor, construction manager or similar authority at the job site.
Owners Representative for Design. The owner or the entity that is responsible to the owner for the
overall structural design of the project. Also referred to as building designer, but hereinafter will
be referred to as Owners Representative for Design. This is usually the Structural Engineer-ofRecord.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

Plans. Drawings prepared by the design professional for the owner of the project. These drawings
include but are not limited to floor plans, framing plans, elevations, sections, details and
schedules as necessary to define the desired construction.
Post-installed Anchor. A structural anchor or device (bolt, clip, angle, bracket, etc.) intended for
fastening cold-formed steel structural framing to hardened masonry or concrete. For anchorage to
concrete, these anchors are installed after the concrete has achieved sufficient stiffness to be
sawn or drilled.
Receiving Entity. The individual or entity responsible to the owners representative for construction
for accepting or rejecting furnished framing materials, and proper storage of received framing
materials on the job site.
Release for Construction. The release by the owners representative, permitting the component
manufacturer and/or installer to commence work under the contract, including ordering framing
material and preparing installation drawings.
Revision. An instruction or directive providing information that differs from information that
has been released for construction. A revision may, but does not always, impact the cost or
schedule of performance of the work.
RFI. Request for Information. A written request for information or clarification generated during
the bidding, design or construction phases of the project.
RMI. Rack Manufacturers Institute.
SDI. Steel Deck Institute.
Specialty Designer. The design professional, individual or organization having responsibility for
the design of the specialty items. This responsibility shall be in accordance with the states,
provinces or territorys statues and regulations governing the professional registration and
certification of architects or engineers. Also referred to as component designer, specialty engineer,
delegated engineer, design engineer, registered engineer, and engineer, but hereinafter will be
referred to as Specialty Designer. The requirement for a Specialty Designer is typically called out
on architectural specifications or structural general notes. The Specialty Designer is typically not
the Structural Engineer-of-Record.
Shop Drawings. Drawings for the production of individual component assemblies for the project.
Specifications. Written instructions, which, with the plans, define the materials, standards, design
of the products, and workmanship expected on a construction project.
SJI. Steel Joist Institute.
SSMA. Steel Stud Manufacturers Association.
Standard Cold-Formed Steel Structural Shapes. Cold-formed steel structural members that meet the
requirements of the SSMA Product Technical Information or AISI North American Standard for ColdFormed Steel Framing Product Data.
Commentary:
The AISI North American Standard for Cold-Formed Steel Framing Product Data was
introduced in 2006. While the industry is encouraged to migrate to this new document, it is
recognized that the SSMA document is also applicable and has widespread acceptance.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

Structural Engineer-of-Record. The design professional who is responsible for sealing the contract
documents, which indicates that he or she has performed or supervised the analysis, design and
document preparation for the structure and has knowledge of the requirements for the loadcarrying structural system.
Structural Member. A member that resists design loads, as required by the applicable building code,
except when defined as a non-structural member.
Structural Steel. The elements of the structural frame defined as structural steel by AISC in the
Code of Standard Practice for Steel Buildings and Bridges.
Sub-Contractor. The individual or organization with whom a contractor has contracted to furnish,
install and/or install a portion of the project.
Submittals. Items required by the contract documents to be submitted by the contractor or subcontractor. These include but are not limited to component design drawings, component placement
diagrams and/or installation drawings. Submittals are usually not a part of the contract documents
but are a work effort requirement of the documents.
Truss. A coplanar system of structural members joined together at their ends usually to construct
a series of triangles that form a stable beam-like framework. See component assembly.
Truss Designer. Also referred to as truss engineer, design engineer and registered engineer, but
hereinafter referred to as truss designer, is an individual or organization responsible for the
design of cold formed steel trusses.
Truss Manufacturer. An individual or organization engaged in the manufacturing of site-built or
in-plant trusses.
A3 Referenced Documents
The following documents or portions thereof are referenced within this Code of Standard
Practice and shall be considered part of the requirements of this document.
1. AIA 201, General Conditions of the Contract for Construction (1997), American Institute of
Architects, Washington, DC.
2. AISI GP-2004, Standard for Cold-Formed Steel Framing General Provisions, American Iron and
Steel Institute, Washington, DC.
3. AISI TRUSS-2004, Standard for Cold-Formed Steel Framing Truss Design, American Iron and
Steel Institute, Washington, DC.
4. AISI PRODUCT-2006, North American Standard for Cold-Formed Steel Framing Product Data,
American Iron and Steel Institute, Washington, DC.
5. ASTM A1003/A1003M-05, Standard Specification for Sheet Steel, Carbon, Metallic and NonMetallic Coated for Cold-Formed Framing Members, ASTM International, West Conshohocken,
PA.
6. ASTM A780-01, Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip
Galvanized Coatings, ASTM International, West Conshohocken, PA.
7. ASTM C645-06, Standard Specification for Nonstructural Steel Framing Members, ASTM
International, West Conshohocken, PA.
8. ASTM C754-04, Standard Specification for Installation of Steel Framing Members to Receive ScrewAttached Gypsum Panel Products, ASTM International, West Conshohocken, PA.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

9. ASTM C955-06, Standard Specification for Load-Bearing (Transverse and Axial) Steel Studs,
Runners (Tracks), and Bracing or Bridging for Screw Application of Gypsum Panel Products and
Metal Plaster Bases, ASTM International, West Conshohocken, PA.
10. SSMA, Product Technical Information, 2001 Edition, Steel Stud Manufacturers Association,
Chicago, IL.
A4 Responsibility for Design
Commentary:
Prior to this Code of Standard Practice, design responsibilities for component assemblies were
defined in several overlapping industry documents, which included the AISI Standard for
Cold-Formed Steel Framing Truss Design, LGSEA Council Technical Note 551f on Specifying
Trusses, and STCA Standard Practices and Recommended Guidelines on Responsibilities for
Construction using Cold-Formed Steel Trusses and Components. Where the AISI Standard for ColdFormed Steel Framing Truss Design is referenced by the applicable building code, those
responsibilities would be legally binding unless modified. However, design responsibilities
for other types of cold-formed steel structural framing were only partially defined in several
CASE documents, which included the National Practice Guidelines for Structural Engineer of
Record and National Practice Guidelines for Specialty Structural Engineers.
Commentary:
A key point of this Code of Standard Practice and the documents used in its development is
that although design may be delegated, the structural engineer-of-record is responsible for the
overall structural integrity of the system when completed.
A4.1 The design professionals are responsible for the suitability and adequacy of all aspects of
design. The design professionals and/or the owner shall have a right to solicit designs, plans,
specifications and/or data from the component manufacturer, installer and/or specialty designer,
but the responsibility for the safety of the structure, property and conformance to applicable
building codes and standards remains with the design professionals of record.
A4.2 If the contract documents require that the installer and/or specialty designer prepare
designs, plans and/or specifications, the contract documents shall state clearly and precisely the
exact requirements, including all applicable building codes and design requirements and all
other regulatory requirements. The design professional of record assumes the responsibility for
these designs. The design professionals of record shall confirm that the effect of the specialty
designer's work conforms to the intent of the structural engineer of record on the overall project.
The design professional of record shall coordinate the work of all the specialty designers with the
design professionals work and/or that of other specialty designers to ensure compatibility and
integrate the connection and conformity of the components designed by the different
specialty designers. This coordination includes, but is not limited to, addressing the forces and
reactions as identified by the specialty designer that are transmitted to those elements of the
structure that are not designed by the specialty designer.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

A4.3 If the contract documents specify trusses, the design responsibilities defined in the AISI
Standard for Cold-Formed Steel Framing - Truss Design shall apply. If the contract documents
specify component assemblies other than trusses, the contract documents shall define the
responsibility for design of the component assemblies. If the contract documents require that the
component manufacturer be responsible for the design of the component assemblies, the contract
documents shall state clearly and precisely the exact requirements, including all applicable
building codes and design requirements and all other regulatory requirements. The owner's
representative for design assumes the responsibility for these designs.
Commentary:
For lateral force resisting systems, the design responsibilities of the structural engineer-ofrecord include but are not limited to design of roof/floor diaphragms, lateral load
transferring elements (sometimes referred to as shear transfer bracing), main lateral force
resisting elements and foundations, as well as compliance of the overall structure with
applicable building codes.
When the design of lateral load transferring elements is to be performed by a specialty
designer or component designer, the structural engineer-of-record must specify the following:
(1) magnitude of lateral load to be transferred;
(2) load path (i.e., where loads originate and where they are to be transferred);
(3) bearing material and conditions; and
(4) any special requirements for the design of the transferring elements.
The structural engineer-of-record must also provide for the following in the design and
detailing of the building:
(1) horizontal, vertical or other deflection due to lateral loads; and
(2) support and anchorage accommodating horizontal and vertical reactions due to
lateral loads.
A4.4 If the owner chooses not to hire a design professional, the owner is responsible for the
suitability, adequacy and legality of all aspects of design in the plans and specifications. In this
case, the owner is responsible for the review and approval of submittals.
A4.5 The contactor or sub-contractor shall not be required to provide professional services
which constitute the practice of architecture or engineering unless such services are
specifically required by the contract documents for a portion of the work or unless the
contractor or sub-contractor needs to provide such services in order to carry out the contractors
or sub-contractors responsibilities for construction means, methods, techniques, sequences
and procedures.
Commentary:
The provisions of Section A4.5 were based AIA 201 Section 2.12.10; however, references to
the contractor were expanded to include both the contractor and sub-contractor.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

B. CLASSIFICATION OF MATERIALS
B1 Definition of Cold-Formed Steel Structural Framing
Cold-formed steel structural framing shall consist of the elements of the structural frame that
are shown in the contract documents, essential to support the design loads and described as:

Cold-formed steel structural members.


Cold-formed steel component assemblies.
Bracing and blocking necessary for the cold-formed steel structural framing or to
provide stability for cold-formed steel structural members.
Connection methods, hardware (fasteners, connectors, and post-installed anchors)
and processes necessary for the installation of cold-formed steel structural framing.
Lateral force resisting system.
Welding materials and processes related to the fabrication or installation of coldformed steel structural framing.

Commentary:
The items listed in Section B1 are normally fabricated and/or installed by the component
manufacturer or installer, and thereby defines the scope of this Code of Standard Practice.
B2 Other Items
Cold-formed steel structural framing shall not include other items that are not generally
described in Section B1, even where such items are shown in the structural plans or are attached
to the cold-formed steel structural framing unless specifically identified by item in the contract
documents. Other items include but are not limited to:

Awnings.
Blocking for other attachments, such as door, window, cabinet, handrail,
plumbing, awnings, storefront, glazing and other systems.
Building cleaning equipment and equipment anchor support.
Cables for permanent bracing or suspension systems.
Cold-formed steel concrete form decking.
Cold-formed steel floor decking.
Cold-formed steel non-structural framing.
Cold-formed steel roof decking.
Cold-formed steel wall sheathing, except as part of a lateral force resisting system.
Chimney support framing.
Concrete slab edge forms.
Drywall and plaster trims and accessories.
Eave struts deployed as a component of a metal building system.
Edge angles, plates, embeds and structural steel supports necessary for the
support of suspended cold-formed steel structural framing.
Embedded anchors.
Expansion and control joints.
Fastening systems for ceiling, wall, floor and roof sheathing materials.
Fire, smoke and draft stopping.
Flagpole support framing.
Girts deployed as a component of a metal building system.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

Handrails and handrail support members.


Insulation products.
Interior drywall (non-structural) framing.
Mechanical equipment support framing.
Metal building systems.
Metal panels deployed as a component of a metal building system.
Miscellaneous metal.
Opening framing, if made from other than standard cold-formed steel structural
shapes.
Open-web steel joists.
Plaster lathing, except where included with a prefabricated structural assembly.
Purlins deployed as a component of a metal building system.
Sheathing, unless part of a prefabricated structural assembly.
Stairs, stair landings and stair railings.
Stair component support framing.
Structural steel framing.
Structural steel lintels, if job-site installed.
Structural steel plate.
Support framing for cables.
Support framing for sign structures.
Suspended ceiling systems, proprietary or pre-engineered.
Window washing supports.

Commentary:
The items listed in Section B2 are normally not fabricated and/or installed by the component
manufacturer or installer. When such items are contracted to be provided by the component
manufacturer or installer, coordination will normally be required between the component
manufacturer or installer and other material suppliers and trades.

10

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

C. CONTRACT DOCUMENTS
Commentary:
Contract documents vary greatly in complexity and completeness. Nonetheless, the component
manufacturer and/or installer must be able to rely upon the accuracy and completeness of the
contract documents. This allows the component manufacturer and/or installer to provide the
owner with bids that are adequate and complete.
Commentary:
One of the owners responsibilities is to ensure proper communication of all facts throughout
the planning and construction phases of the project between all parties involved. The contract
documents (i.e., architectural plans, structural plans, specifications and structural notes) are the
primary method of communication. It is the owners responsibility to properly define the
scope of work. When the owner releases plans or specifications for construction, the component
manufacturer and/or installer rely on the fact that these are the owners requirements for his
project.
Commentary:
Critical requirements that are necessary to protect the owners interest, that affect the integrity
of the structure or that are necessary for the component manufacturer and/or installer to
proceed with their work must be included in the contract documents. In some cases, however,
the owner can benefit when reasonable latitude is allowed in the contract documents for
alternatives that can reduce cost without compromising quality.
C1 Responsibilities
C1.1 The owners representative shall furnish to the component manufacturer and/or installer a
set of contract documents of current issue including addenda showing the type of support
supplied, method of attachment, correct dimensions, and required size and spacing.
C1.2 If contract documents are not available, the owners representative shall provide complete
information as specified in Section A4.2.
C1.3 The contract documents may require the component manufacturer and/or installer to
submit a complete design for approval prior to the commencement of construction. In the
process of this submittal, the component manufacturer and/or installer shall bring to the
attention of the owner's representative, any conflicts within the construction documents. The
owner's representative, must present clear instructions to the component manufacturer and/or
installer on how to resolve each conflict. Changes resulting from such conflicts shall be
handled in accordance with Section H6.
C1.4 Architectural plans shall be legible, shall indicate the design intent of cold-formed steel
structural framing, and shall include at a minimum the location of cold-formed steel structural
framing, constraints on member size (e.g., web depth), wall and other assembly types, nonstandard spacing and location requirements.
C1.5 Structural plans shall show the structural member locations, sizes, reinforcing and
connections in sufficient scale and detail to enable the construction of the building in a
reasonable sequence by a competent contractor experienced in the techniques of construction
for the specified materials. Structural plans may refer to architectural plans for dimensions,
where appropriate. Elevations, sections and details should be of appropriate scale, number

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

11

and extent to portray clearly the relationship of members to each other and their
interconnection(s). Care should be taken to determine that details noted typical are
applicable to the project or condition being portrayed.
C2 Limit of Responsibility
The owner's construction documents are assumed to be correct in all details, and the
component manufacturers and/or installers responsibility is limited to furnishing products in
accordance with these documents and this Code of Standard Practice. Any change to these contract
documents must be authorized in writing by the owners representative.
Commentary:
It should not be the responsibility of the component manufacturer or the installer to compare
the contract documents (i.e., architectural plans, structural plans, specifications and structural
notes) against each other in order to verify consistency. This is the responsibility of the owner
or the owners representative(s).
C3 Jurisdiction
Where state and local boards or other regulatory agencies have jurisdiction, the owner is to
indicate such information in the contract documents.
C4 Discrepancies
When a discrepancy is discovered in the contract documents in the course of work by the
contractor, component manufacturer, installer and/or any other parties involved with the
construction, the entity finding the discrepancy shall promptly notify the owners representative
for construction so that the discrepancy can be resolved by the owners representative for design.
Such resolutions shall be timely so as not to affect the work of the component manufacturer
and/or installer. Changes resulting from such discrepancies shall be handled in accordance with
Section H6.
Commentary:
While it is the responsibility of the component manufacturer and/or installer to report any
discrepancies that are discovered in the contract documents, it is not the responsibility of the
component manufacturer and/or installer to discover discrepancies, including those that are
associated with the coordination of the various disciplines. The quality of the contract
documents is the responsibility of the entities that produce those documents.
C5 Revisions
Revisions to the contract documents shall be made either by issuing new contract documents or
by reissuing the existing contract documents. In either case, all revisions, including revisions that
are communicated through responses to RFIs (see Section H4) or the review process (see Section
D3), shall be clearly and individually indicated in the contract documents. If new contract
documents are issued due to revisions, the parties issuing the new contract documents shall submit
them to the owner or the owners representative for distribution. The contract documents shall be
dated and identified by revision number. Revised contract documents shall be identified by the
same number throughout the duration of the project, regardless of the revision. See also Section
H6.

12

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

Commentary:
Revisions to the contract documents can be made by issuing sketches and supplemental
information separate from the contract documents. These sketches and supplemental
information become amendments to the contract documents and are considered new contract
documents. All sketches and supplemental information must be uniquely identified with a
number and date as the latest instructions until such time as they may be superseded by new
information. When revisions are made by revising and re-issuing the existing contract
documents, a unique revision number and date must be added to those documents to identify
that information as the latest instructions until such time as they may be superseded by new
information. The same unique drawing number must identify each drawing throughout the
duration of the project so that revisions can be properly tracked, thus avoiding confusion and
miscommunication among the various entities involved in the project. When revisions are
communicated through the annotation of submittals, such changes must be confirmed in
writing by one of the aforementioned methods. This written confirmation is imperative to
maintain control of the cost and schedule of a project and to avoid potential errors in
fabrication and installation.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

13

D. INSTALLATION DRAWINGS
D1 Owners Responsibility
D1.1 When the project is released for construction, the owner's representative shall provide
complete contract documents and relevant information, including addenda and other related
drawings such as window shop drawings and architectural metal panel drawings, in a
timely manner for the installation of cold-formed steel structural framing and, if required,
preparation of component design drawings and installation drawings. A scope of work for items
required, having been agreed upon at the time of the contract, shall also be incorporated with
these documents. This scope shall include and indicate all items that are to be fabricated and
installed.
D1.2 If the owners representative requests that submittals be prepared before the timely
submittal of any other required documents, such as window shop drawings or architectural
metal panel drawings, any changes required due to the differences between these drawings
and the assumptions made in preparation of the submittals will be the responsibility of the
owners representative. Delays in obtaining required information can extend the schedule
agreed to at time of contract.
D2 Component Manufacturer and/or Installer Responsibility
D2.1 The component manufacturer and/or installer shall submit submittals, with supporting
calculations, when required by and per the contract documents, on a schedule formulated and
agreed to at time of contract.
Commentary:
The component manufacturer and/or installer should be permitted to use the services of a
specialty designer or independent detailer to produce shop drawings and/or installation
drawings and to perform other support services.
Commentary:
When the component manufacturer and/or installer provides a schedule for submittals, it
must be recognized that this schedule may be affected by revisions, response time to RFI(s)
and resolution of discrepancies.
D2.2 Requests for supplemental structural support elements, such as miscellaneous
structural steel and/or embedded items, shall be submitted by the component manufacturer
and/or installer and handled in accordance with Section H6. Delays in obtaining
confirmation of such requests can extend the schedule agreed to at time of contract.

14

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

D3 Review Process
Commentary:
Upon receipt of shop drawings from different trades, the owners representative must review
each submittal, or delegate such review in order to assure continuity and completeness. The
different trade submittals shall be reviewed in conjunction with all the submittals to insure
conformity and identify conflicts or gray areas not covered by any trade but necessary to
integrate the different trades.
D3.1 The owner's representative shall return to the component manufacturer and/or installer one
set of the submittals indicating one of the following: approved (no exception taken), approved
as noted (re-submittal not required), revise and resubmit or rejected.
D3.2 If modifications are required, the component manufacturer and/or installer and specialty
designer, if retained by the component manufacturer and/or installer, shall have at least fourteen
(14) calendar days for incorporating the required changes.
D3.3 If modifications with re-submittal are required, the submittals shall be resubmitted to
the owners representative for review after all required modifications and/or corrections have
been executed.
Commentary:
If such modifications involve a single item or minor changes, only those items need be
revised and resubmitted. These revisions may be appended to the original submittals. For
example, if one component assembly design among several designs is incorrect, that design
should be revised and resubmitted. However, if the design criteria have to be revised, all
the component assembly designs based on that criteria must be revised and resubmitted.
Revisions to the component design drawings can be made by issuing sketches and
supplemental information separate from the component design drawings.
D3.4 Should modifications be required which were not part of the agreed to scope of work,
the component manufacturer and/or installer shall submit in writing the extra costs for this
additional work (including but not limited to engineering, material, labor, overhead and
profit), for approval by the owner's representative.
D3.5 The component manufacturer and/or installer shall not proceed with any work until all
drawings, modifications and extra charges are resolved, except those portions of the work
where all parties have agreed to the completeness and correctness of all drawings,
modifications, and any extra charges.
Commentary:
The intent of this section is to protect all parties from potential risks and costs associated
with proceeding prior to the resolution of issues.
D3.6 It is the responsibility of the owners representative, to assure that the above approval
process is coordinated with the proper sequence for submittal and project schedule.
D4 Responsibility
D4.1 Approval by the owner's representative of submittals prepared by the component
manufacturer and/or installer indicates that the component manufacturer and/or installer has
correctly interpreted the contract requirements and is released to start fabrication and

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

15

installation. The owners representative is responsible for adequacy of designs, structural


configurations, material and code requirements. The above approval constitutes the owner's
acceptance of this responsibility.
D4.2 Approval by the owner's representative of submittals does not relieve the component
manufacturer and/or installer of the responsibility for accuracy of dimensions on submittals,
nor the general fit-up of parts to be assembled in the field, nor for providing acceptable
workmanship.
Commentary:
When the component manufacturer and/or installer intends to make a submission of an
alternate to what is shown in the contract documents, the component manufacturer and/or
installer must notify the owner or owners representative in advance. This will allow the
parties involved to schedule the review of the alternate for impact on cost, schedule and
benefits. This evaluation by the owner or owners representative may result in the rejection of
the alternate. However, if alternate submittals are approved, this constitutes acceptance by
the owner of materials, criteria or designs that may differ from those required by the
contract documents.

16

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

E. MATERIALS
E1 Structural Members
E1.1 Structural members shall be of the grade, base steel thickness and coating specified by the
approved design. However, steel of a higher grade, base steel thickness, or coating may be
substituted for the grade, base steel thickness, or coating as specified, unless specifically
prohibited in the contract documents.
E1.2 Structural members shall be of the size and shape specified by the approved design.
Changes in size and/or shape shall require the approval of the owners representative for
design.
E1.3 Structural members shall comply with the manufacturing tolerances listed in ASTM
C955.
E1.4 Component assemblies shall have structural members that are cut and assembled in
accordance with the tolerances prescribed in the AISI Standard for Cold-Formed Steel Framing
General Provisions. Trusses shall have structural members that are cut and assembled in
accordance with the additional requirements of the AISI Standard for Cold-Formed Steel
Framing - Truss Design.
E2 Fasteners and Connection Hardware
E2.1 Fasteners shall be at minimum the type and size specified by the approved design. Use
of a larger than specified fastener shall be permitted, providing that the minimum spacing
and edge distance requirements of the larger fastener are met and the strength requirements
of the specified fastener are met.
E2.2 Connection hardware (i.e., connectors and post-installed anchors) shall be as specified in
the approved design, except for substitutions approved by the owners representative for design.
E3 Preparation of Material
E3.1 Cutting shall be by sawing, abrasive cutting, shearing, plasma cutting or other approved
methods. Proper methods of cutting are to be selected by the installer, unless otherwise
specified in the contract documents.
E3.2 In the manufacture and/or fabrication of structural members and connection hardware,
mechanical braking, bending or forming is permitted.
E4 Member Identification
Structural members shall be identified in accordance with the product identification
requirements for framing members defined in the AISI Standard for Cold-Formed Steel Framing General Provisions.
E5 Special Marking
Component assemblies shall be marked, as necessary, to document such items as proper
orientation, special bearing conditions and permanent bracing requirements. Alternatively, it
shall be acceptable for the specialty designer to provide this information to the installer by means
of indications on the component placement diagrams.
E6 Camber
Component assemblies will only be provided with camber if specified by the specialty designer.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

17

F. INSTALLATION
F1 Scope
Items of cold-formed steel to be installed shall be enumerated in the contract documents.
F2 Site Conditions
Commentary:
This section is deemed important for the safety and efficiency of the installer and the
installers crew, as well as for the protection of the people, property, etc., which may be
present at the site at the time of installation.
F2.1 The installer shall be permitted to use the most efficient and economical method and
sequence of installation or assembly available consistent with the contract documents. When
the owner contracts separately with a component manufacturer and installer, the owner is
responsible for coordinating work between contractors.
F2.2 The installer shall examine areas and conditions under which framing materials are to be
installed. Work shall not proceed until unsatisfactory conditions have been corrected by
those responsible.
F2.3 The owners representative for construction shall provide and maintain adequate access
necessary for equipment and framing materials to be installed. The owners representative for
construction shall provide the installer level, convenient, and adequate space to safely use the
necessary equipment and install the framing materials.
F2.4 The contractor shall coordinate installation drawings, resolution of dimensional
problems, compatibility of various trades and/or installation.
F3 Delivery, Handling and Storage of Materials
F3.1 It is the receiving entitys responsibility to verify that framing materials arrive in good
condition. If framing materials arrive at a destination in a damaged condition, the receiving
entity shall promptly notify the material supplier or component manufacturer prior to unloading
the framing material, or promptly upon discovery and prior to installation.
F3.2 It is the contractors and/or the installers responsibility to verify the framing material is
not damaged and meets the project specifications and/or approved submittals before
installation. The material supplier or component manufacturer shall be responsible solely for the
replacement of damaged material or material that does not meet the project specifications
and/or approved submittals. If the contractor and/or the installer installs damaged material
then the contractor and/or the installer assumes the cost of repairing or installing new
materials. At no time will the consequential costs to be assumed by the material supplier or
component manufacturer exceed the selling price of the particular material in question.
F3.3 Damage caused by improper storage or handling of framing materials on the job site is
not the responsibility of the material supplier or component manufacturer.
F3.4 Proper storage of framing materials on the job site is the responsibility of the receiving
entity, and requires that framing materials not be in direct contact with the ground and are
protected from the elements. Adequate drainage and ventilation shall be provided to
minimize the formation of wet storage stain or white rust.

18

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

F3.5 Proper handling of framing materials on the job site is the responsibility of the contractor
and installer, and requires that care be exercised to not cause significant damage to the
metallic coating. Bare steel exposed at minor scuffs and scratches is generally protected by
the zincs ability to provide cathodic protection and does not require any repair; however,
significant damage to the metallic coating, such as is caused by field welding, must be
repaired in accordance with Section F4.
F4 Field Modifications and Repairs
F4.1 If the contractor, sub-contractor or any others modify or damage framing materials, that
party is responsible for all costs necessary to analyze and, when necessary, correct the
situation.
F4.2 Installation of holes in the webs of structural members is limited to the size,
configuration, and location as specified in the approved design or recognized design standard.
Any webs of structural members with holes violating the above requirements must be
evaluated by the design professional.
F4.3 Field repairs to damaged structural members shall be made in accordance with the
design professionals recommendation. The design professional may request that the specialty
designer provide recommendations on field repairs, with final approval by the design
professional.
F4.4 Repairs to the metallic coating, when required, shall be in accordance with ASTM
A780.
F4.5 Changes orders resulting from such approved field modifications or repairs shall be
handled in accordance with Section H6.
F5 Installation Tolerances
F5.1 Structural members and component assemblies shall be installed in accordance with the
tolerances prescribed in the AISI Standard for Cold-Formed Steel Framing General Provisions.
F5.2 Trusses shall be installed in accordance with the additional requirements of the AISI
Standard for Cold-Formed Steel Framing Truss Standard.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

19

G. QUALITY CONTROL
G1 General
G1.1 Material suppliers and component manufacturers shall maintain a properly documented
quality control program to assure that their work is performed in accordance with this Code
of Standard Practice and relevant ASTM and AISI standards.
Commentary:
If the component manufacturer and/or installer produce structural members using on-site
mechanical braking, bending, or forming, they have in effect assumed the role of the
material supplier and these provisions would apply.
G1.2 The contractor shall maintain a quality control program so that the work performed by
the installer can be completed in accordance with this Code of Standard Practice and the
contract documents, and submittals.
Commentary:
Items under the contractors quality control that may affect the installers performance
include but are not limited to the following:
Tolerances and quality of work by other trades that precede the installers work
Placement of embedded anchors and/or bearing plates
Clean and unobstructed work areas
Timeliness and completeness of work by other trades
G1.3 The installer shall maintain a quality control program so that their work is performed in
accordance with this Code of Standard Practice and the contract documents. The installer shall be
capable of performing the necessary installation or assembly and provide the equipment,
personnel and management for the scope, magnitude and required quality of each project.
The installer shall employee sufficient qualified personnel to properly complete the work
required by the contract documents.
G2 Material Inspection
G2.1 The receiving entity shall verify that the framing materials delivered meet the
requirements of the contract documents.
G2.2 The receiving entity shall check the framing materials to verify that the framing materials
have been properly labeled as required by Section E4.
G3 Workmanship
The quality of workmanship expected for the cold-formed steel structural framing product
shall be specified in the contract documents.

20

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

H. CONTRACTUAL RELATIONS
H1 Presentation of Proposals
All proposals for furnishing framing material shall be made on a sales contract form. After
acceptance by the owner, these proposals must be accepted or executed by a qualified official of
the component manufacturer and/or installer. Upon such acceptance, the proposal becomes a
contract.
H2 Acceptance of Proposals
All proposals shall have a specified term of acceptance. If the proposal is not accepted
within this term the proposal becomes invalid.
H3 Terms of Payment
The terms of payment for the work to be completed shall be specified in the contract
documents.
H4 The RFI Process
When RFIs are issued, the process shall include the maintenance of a written record of
inquiries and responses related to interpretation and implementation of the contract documents,
including the clarifications and/or revisions to the contract documents that result, if any. RFIs shall
not be used for the incremental release for construction of contract documents. When RFIs involve
discrepancies or revisions, see Sections C4 and C5.
Commentary:
The RFI process is most commonly used during the detailing process, but can also be used to
forward inquiries by the component manufacturer and/or installer or to inform the owners
representatives in the event of a component manufacturer and/or installer error and to develop
corrective measures to resolve such errors. The RFI process is intended to provide a written
record of inquiries and associated responses but not to replace all verbal communication
between the parties on the project. RFIs should be prepared and responded to in a timely
fashion so as not to delay the work of the component manufacturer and/or installer. Discussion
of the RFI issues and possible solutions between the component manufacturer and/or installer
and owners representatives often can facilitate timely and practical resolution. Unlike shop
drawing and installation drawing submittals in Section D2, RFI response time can vary
depending on the urgency of the issue, the amount of work required by the owners
representatives to develop a complete response, and other circumstances such as building
official approval. RFIs should be prepared in a standardized format, including RFI number
and date, identity of the author, reference to a specific drawing number (and specific detail as
applicable) or specification section, the needed response date, a description of a suggested
solution (graphic depictions are recommended for more complex issues), and an indication
of possible schedule and cost impacts. RFIs should be limited to one question each (unless
multiple questions are interrelated to the same issue) to facilitate the resolution and
minimize response time. Questions and proposed solutions presented in RFIs should be clear
and complete. RFI responses should be equally clear and complete in the depictions of the
solutions, and signed and dated by the responding party.

Code of Standard Practice for Cold-Formed Steel Structural Framing - 2006

21

Commentary:
Unless otherwise noted, the component manufacturer and/or installer can assume that a
response to an RFI constitutes a release for construction.
H5 Revisions to the Contract Documents
Revisions to the contract documents shall be confirmed by change order, in accordance with
Section H6. Unless otherwise noted, the issuance of a revision to the contract documents shall
constitute authorization by the owner that the revision is released for construction.
H6 Change Orders
The owners representative for construction shall review the change order within fourteen (14)
days, or sooner if the decision delays the project schedule, and issue a formal response. The
owners representative for constructions compensation of the component manufacturer and/or
installer for conflicts, discrepancies and approved field modifications and repairs shall not be
delayed due to the owners representative for constructions negotiations with the contractor
determined to be at fault.
Commentary:
These change orders may be necessitated by any conflicts, in accordance with Section C1;
discrepancies, in accordance with Section C4; revisions, in accordance with Section C5;
delivery, handling and storage of materials, in accordance with Section F3; or field
modifications and repairs, in accordance with Section F4.
H7 Contract Price Adjustment
When the scope of work and responsibilities of the component manufacturer and/or installer
are changed from those previously established in the contract documents, an appropriate
modification of the contract price shall be made. In computing the contract price adjustment, the
component manufacturer and/or installer shall consider the quantity of work that is added or
deleted, the modifications in the character of the work and the timeliness of the change with
respect to the status of material ordering, detailing, fabrication and installation operations.
Requests for contract price adjustments shall be presented by the component manufacturer
and/or installer in a timely manner and shall be accompanied by a description of the change
that is sufficient to permit evaluation and timely approval by the owner.
H8 Scheduling
The contract schedule shall state:

When the contract documents will be released for construction

When the job site will be ready, free from obstructions and accessible to the installer,
so that installation can start at the designated time and continue without
interference or delay caused by the owner's representative for construction or other
trades.

The component manufacturer and/or installer shall advise the owner, owner's representatives for
design or owner's representatives for construction, in a timely manner, of the effect any revision has
on the contract schedule.
If the fabrication or installation is significantly delayed due to revisions to the requirements
of the contract, or for other reasons that are the responsibility of others, the component
manufacturer and/or installer shall be compensated for the additional costs incurred.

practice guide

1140 Connecticut NW
Suite 705
Washington DC 20036
www.steel.org

803 West Broad Street


Suite 600
Falls Church, VA 22046
www.awci.org

National Housing Center


1201 15th Street NW
Suite 320
Washington DC 20005
www.steelframingalliance.com

8 S. Michigan Avenue
Suite 1000
Chicago IL 60603
www.ssma.com

TM

CF06-1-COSP-2006-0906-1K-AP

Code of Standard Practice for


Cold-Formed Steel Structural Framing
Committee on Framing Standards

2006 EDITION
with Commentary