3. Abnormal overcurrent flow with a value more than 10 times the normal
current flow is known as short-circuit or fault current flow
OCPDs
Fuses
Circuit Breakers
Circuit Breakers contain a resettable latch which acts like an ON-OFF switch
for the normal current flow. When abnormal current flows through the circuit
breaker, the latch trips, and the indicator on the outside of the circuit breaker
moves into the OFF position. Once the overcurrent problem has been
corrected, the indicator lever can be reset into the ON position, which
simultaneously resets the latch inside the circuit breaker.
Panel Boards
OCPD location
Locate OCPDs so you prevent exposure to physical damage. But also make
the OCPDs readily accessible, Readily accessible means located so a person
can reach the OCPD quickly without having to climb over or remove
obstacles. Supplementary OCPDs, which are often used for luminaires,
appliances, or for internal circuits and components of equipment, don't need
to be readily accessible. OCPDs located next to the equipment they supply
can be accessible by portable means.
Each occupant must have ready access to all OCPDs that protect the
conductors that supply that occupancy, with a few exceptions.
Service and feeder OCPDs need not be accessible to occupants of multipleoccupancy buildings or guest rooms of hotels and motels if electric
maintenance is provided under continuous building management, and
branch-circuit OCPDs need not be accessible to occupants of guest rooms of
However, there are two location restrictions. Don't locate OCPDs near easily
ignitable material. For example, keep them out of clothes closets. Don't
locate them in the bathrooms of dwelling units or guest rooms of hotels or
motels. Note that prohibits locating the service disconnect in any bathroom.