02645s01 Fire Hydrant Requirements
02645s01 Fire Hydrant Requirements
02645s01 Fire Hydrant Requirements
Specifications.
Minimum Water Main Size
Minimum Dead End Main
Hydrant Type
Direction of Opening
New Hydrants
Existing Hydrants
Depth of Bury
Main Valve Opening
Type of Inlet
Type of Caps
Operating Nut Size
Center of Outlets to Ground
1.7.
8 inch
8 inch
Dry Barrel
Right (clockwise)
(2) 4 Openings
Min. of (1) 4 Opening
3-6 Minimum
5 Minimum
6 inch
15/16 inch square nut with chains
15/16 inch square
18 inches
All hydrants shall be painted with red barrels. The caps shall be painted per the Classification
of Hydrants below.
Classification of Hydrants
Class AA Rated capacity of 1500 gpm or greater
Class A Rated capacity of 1000-1499 gpm
Class B Rated capacity of 500-999 gpm
Class C Rated capacity of less than 500 gpm
1.8.
Where fire hydrants are installed along a roadway, parking within 15 feet is prohibited. All curbs
within 15 feet of a hydrant shall be painted fire lane red.
1.9
When fire hydrants are installed in parking areas, parking shall be designed and maintained to
allow 10 feet clear access to the hose connection side of the hydrant, and a four foot minimum
clear radius around the hydrant
1 of 2
2.1.5
2.1.6
Signs shall be made from 16 wide x 10 tall 0.0624 thick aluminum plate.
Plate shall be painted white.
Plate shall have a 0.01875 RED border offset 0.250 from the edges of the
plate.
Lettering shall be 1 tall using all capital letters. Wording shall be:
FIRE DEPARTMENT CONNECTION
FOR
(NAME OF BUILDING))
Signs shall be mounted on the pipe with two, adjustable stainless steel
airplane clamps at the top and bottom. Wall mounted signs shall be secured to
the building wall with two 3/8 stainless steel expansion anchors.
Should there be two (2) fire department connections for a particular building,
each fire department connection shall be identified as to the areas of the
building it serves and identified as being a wet or dry connection.
2.2. All post indicator valves (PIV's) shall be equipped with provisions to mount an internal electric
switch and shall have an internal conduit (1/2" min.) from this switch mounting location to the
base of the post for connection of status monitoring equipment provided by the Fire Alarm
System installer. Switch shall be covered with a splash proof cover and wiring and switch must
be accessible without removal of any part of the PIV. Conduit shall have provision at base of
post to exit immediately above grade and directly under the post. Conduit connections to the
post shall be 1/2" NPT or larger.