ELSSG12
ELSSG12
April 2012
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
COMPLETE REVISION
April 2012
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
Table of Contents
1. Introduction
1.1 Purpose
1.2 Scope 2
2. References
2
2
3. Definitions
4. Requirements 3
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
Service Conditions
Base 3
Walls and Roof4
Doors 5
Screens and Filters
Electrical Accessories
Grounding
7
Nameplates 7
Coatings
9
Inspection and Testing
Shipping
10
Documentation11
6
6
10
Page 1 of 12
1.
Introduction
1.1
Purpose
This Practice provides requirements for design and fabrication of outdoor enclosures
that are provided as an integral part of enclosed equipment.
1.2
2.
Scope
1.2.1
1.2.2
1.2.3
References
Applicable parts of the following Practices, industry codes and standards, and references
should be considered an integral part of this Practice. The edition in effect on the date of
contract award should be used, except as otherwise noted. Short titles are used herein when
appropriate.
2.1
2.2
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
COMPLETE REVISION
April 2012
3.
Definitions
owner: The party that owns the facility where the equipment will be used or installed
purchaser: The party who awards the contract to the supplier. The purchaser may be the
owner or the owners authorized agent.
supplier: The party responsible for furnishing the enclosure
4.
Requirements
4.1
Service Conditions
Unless otherwise specified on the purchasers PIP ELSSG12D Data Sheet, equipment
shall be designed to perform satisfactorily under the following ambient conditions:
a. Ambient condition within the limits of -30C (-18F) and 40C (104F)
b. Altitude of installation does not exceed 3300 feet (1000 m)
c. Humidity within the limits of 0 - 95% non-condensing, over a 24 hour period and
0 90% non-condensing, over a 1 month period
d. For seismic and wind and snow loading requirements, see PIP CVC01017 and
PIP STC01015 and ASCE7.
4.2
Base
4.2.1
4.2.2
Where bottom entry is used, removable floor plates shall be provided in rear
cable compartment.
4.2.3
The design shall meet all load combinations for enclosure, equipment, and
contents.
Page 3 of 12
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
COMPLETE REVISION
April 2012
4.2.4
The structural steel base shall be designed to withstand all shipping and
erection loads in addition to normal dead and live loads.
4.2.5
Structural steel for the base of the power center shall be in accordance with
ASTM A36.
4.2.6
Structural steel members shall be rigidly braced with structural steel crossmembers for installation on a concrete slab or piers by others.
4.2.7
Suitable lifting lugs rated for the load and lift of enclosure and contents shall
be furnished by supplier.
4.2.8
4.3
4.2.8.2
4.2.8.3
4.3.2
4.3.3
Joints in the outer steel housing shall be designed and fabricated to prevent
the entry of dust and moisture. All gaskets shall be continuous and held in
metal retainers (channel, etc.).
4.3.4
Locations of incoming and outgoing bus duct and cable shall be coordinated
with equipment to be enclosed.
Page 4 of 12
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
4.4
COMPLETE REVISION
April 2012
4.3.5
The roof shall be sealed and sloped to provide drainage in a direction away
from personnel doors and any front access doors.
4.3.6
Side paneling shall stop at a minimum of 3 inches (76 mm) above bottom of
base.
Doors
4.4.1
4.4.2
Enclosures more than 72 inches (1.8 m) wide shall have a door at each end.
The door width shall be large enough to remove the largest controller or
breaker element. The doors shall swing outward and be equipped with panic
bars or other devices that are normally latched and designed to open under
simple pressure. The door shall have provisions for padlocking or for the
purchasers lockset as specified on the purchasers PIP ELSSG12D Data
Sheet. If specified on the purchasers PIP ELSSG12D Data Sheet, personnel
doors shall be equipped with windows.
4.4.3
Door stops on personnel doors and equipment access doors shall be provided
to maintain doors in the open position.
4.4.4
Equipment access doors on the front of the enclosure shall be equipped with
gasketed, hinged doors with a 3-point latching mechanism.
4.4.4.1 Latching mechanisms for rear access doors shall be as specified on
the purchasers PIP ELSSG12D Data Sheet and may be 3-point latch,
three sides bolted, or both.
4.4.4.2 Latches on equipment access doors shall engage the steel frame at
three points (top, bottom, and side) to latch the door closed and shall
have a rolling or smooth sliding action when engaging the frame to
aid in operating the latches.
4.4.4.3 All doors shall be suitable for pad locking.
4.4.4.4 All outdoor handles and hardware shall be Series 300 stainless steel.
4.4.4.5 Where bolts are used to secure equipment access doors, removal of
bolts shall be by tool only.
4.4.4.6 Dust sealing on all doors shall be achieved by the use of a
compression type neoprene strip. The use of foam rubber or foam
plastic as a dust sealing strip will not be accepted.
4.5
Enclosures shall have louvered ventilation openings at the top and bottom.
4.5.2
4.5.3
Page 5 of 12
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
4.6
COMPLETE REVISION
April 2012
Electrical Accessories
4.6.1
Panelboards
Supplier shall provide a circuit breaker panel with main circuit breaker and
minimum of six branch circuit breakers. These branch circuits will serve
equipment space heaters, lighting, receptacles, fans, personnel space heaters,
etc. Power supply voltage shall be as specified on the purchasers
PIP ELSSG12D Data Sheet.
4.6.2
Heaters
If specified on the purchasers PIP ELSSG12D Data Sheet, walk-in enclosure
shall include personnel space heaters with hand-off-auto switches and
thermostats to activate at preset temperatures. One form C contact shall be
provided for use as a remote alarm to indicate over- or under-temperature
conditions inside the enclosure.
4.6.3
Fans
If specified on the purchasers PIP ELSSG12D Data Sheet, walk-in enclosure
shall include ventilation fans with hand-off-auto switches and thermostats to
activate at a preset temperature. One form C contact shall be provided for use
as a remote alarm to indicate over-temperature.
4.6.4
Lighting
4.6.4.1 Lighting shall be provided in all walk-in enclosures.
4.6.4.2 Minimum illumination shall be 30 foot candles on the vertical
panels, 42 inches (1.1 m) above the floor.
4.6.4.3 Light switches shall be identified with engraved nameplates
indicating the power source and shall be located on the non-hinged
side of the door(s).
4.6.4.4 In walk-in enclosures, three-way switches for lighting shall be
installed and located beside each door.
4.6.4.5 Unless otherwise specified on the purchasers PIP ELSSG12D Data
Sheet, lighting fixtures shall be fluorescent.
4.6.4.6 Bottom of lighting fixtures shall be a minimum of 6 feet 8 inches
(2.03 m) above the floor in walk-in enclosures.
4.6.4.7 Lighting fixtures shall have guards and lights shall be suitable for
service conditions listed on the purchasers PIP ELSSG12D Data
Sheet.
4.6.4.8 Supplier shall furnish emergency lights, lighted exit signs, and
external lighting near doors if specified on the purchasers
PIP ELSSG12D Data Sheet.
4.6.5
Receptacles
If specified on the purchasers PIP ELSSG12D Data Sheet, walk-in enclosure
shall include a 120-volt GFCI-type receptacle outlet located near each
personnel door.
Page 6 of 12
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
4.6.6
COMPLETE REVISION
April 2012
Wiring Methods
Wiring methods, including raceways, cable systems, grounding, and bonding,
shall comply with NFPA 70.
4.6.7
Fire Safety
4.6.7.1 If specified on the purchasers PIP ELSSG12D Data Sheet, a
minimum of one fire extinguisher shall be provided by each exit door
of a walk-in enclosure. Additional fire extinguishers shall be
provided as indicated on purchasers PIP ELSSG12D Data Sheet.
4.6.7.2 Fire extinguishers shall be carbon dioxide Type C for energized
electrical equipment, 10 pound capacity, hand carry with hanging
bracket, hose, hose nozzle, and hand squeeze valve control.
4.6.7.3 If specified on purchasers PIP ELSSG12D Data Sheet, a fire
detection system shall be supplied.
4.7
Grounding
A NEMA standard 4-hole stainless steel ground pad shall be located on diagonally
opposite corners of the enclosure skid (total of 2 ground pads). Supplier shall connect
equipment ground bus to the ground pads.
4.8
Nameplates
4.8.1
General
4.8.1.1 Nameplates, safety signs, and labels shall be in accordance with
NFPA 70 and ANSI Z535.4.
4.8.1.2 Permanent engraved lamacoid nameplates shall be provided
identifying each instrument and device, including transformers,
circuit breakers, and auxiliary compartments.
4.8.1.3 Equipment and terminal blocks within the compartments shall be
suitably identified.
4.8.1.4 Except as specified in Section 4.8.2.3, all nameplates, internal and
external, shall be made of laminated plastic at least 3/32 inch (2.4
mm) thick.
4.8.1.5 Nameplates shall be attached as specified on the purchasers
PIP ELSSGS12D Data Sheet.
4.8.1.6 Nameplates shall be of following background color and engraving:
a. Identification nameplates White background with black
engraving
b. Caution nameplates Yellow background with black engraving
c. Warning nameplates Red background with white engraving
4.8.1.7 Unless otherwise specified on the purchasers PIP ELSGS12D Data
Sheet, all lettering shall be inch (6.4 mm) high.
4.8.1.8 All vertical section rear compartments shall have a nameplate
indicating section number and service description.
Page 7 of 12
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
4.8.2
COMPLETE REVISION
April 2012
Manufacturers Nameplate
4.8.2.1
4.8.3
4.8.2.2
4.8.2.3
4.8.3.2 The tag number and description shall be in accordance with the
purchasers nameplate schedule.
4.8.3.3 Lettering on the EIN shall be 1 inch (25.4 mm) high.
4.8.4
Device Nameplate
4.8.4.1 A device nameplate (DN) shall be provided for each front mounted
device. Examples of front mounted devices are relays, meters, and
switches.
4.9
4.8.4.2
4.8.4.3
Coatings
4.9.1
All structural framing members shall be cleaned to near white metal. The use
of chemical or solvent cleaning of structural steel shall not be permitted.
Following cleaning, one shop coat of epoxy primer (3.0 mils minimum dry
thickness) shall be applied.
4.9.2
4.9.3
All seams outside the enclosure shall be sealed with 25-year silicone sealant
to preclude crevice corrosion and assure the environmental integrity of the
enclosure against blowing rain, dust, dirt, or sand.
4.9.4
All interior and exterior exposed metal surfaces shall receive factory paint
that meets or exceeds the requirements of a 2000-hour salt spray test as
defined by ASTM B 117 and evaluated in accordance with ASTM D 1654 and
ASTM D 714.
Page 8 of 12
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
4.9.5
COMPLETE REVISION
April 2012
Interior and exterior color coating design shall meet the following
performance standards after 10 years continuous exposure in normal
atmospheric conditions:
a. Panels shall show no evidence of blistering, peeling, or chipping.
b. Panels shall show no surface chalking.
c. Panels, after cleaning, shall show no color change in excess of seven (7)
units when measured in accordance with the ASTM D 2244 standard.
4.9.6
4.9.7
All structural members under the flooring shall be coated with an additional
20-25 mils of bitumastic or equal undercoating to eliminate base rusting and
subsequent corrosion.
4.9.8
Unless specified otherwise on the purchasers PIP ELSSG12D Data Sheet, all
exterior exposed bolting shall be corrosion resistant or stainless steel.
4.9.9
Two (2) 1-quart (0.94L) cans of touch-up paint shall be supplied per
equipment assembly for each color used.
Page 9 of 12
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
4.10
COMPLETE REVISION
April 2012
4.11
Shipping
4.11.1 Preparation for shipment shall be in accordance with suppliers standards
unless otherwise noted in the job specifications.
4.11.2 The supplier shall be solely responsible for the preparation for shipment.
4.11.3 Loose equipment, such as auxiliary test devices, charts, replacement parts,
manual operating handles, packing devices, etc., shall be appropriately
packaged, tagged for easy identification, and secured for shipment inside the
power center.
4.11.4 Moving parts shall be securely blocked and braced in relays, contactors, and
other components in which these moving parts might be damaged during
shipment. Blocking shall be identified (tagged) for removal.
4.11.5 Additional shipping and handling requirements that appear in the individual
equipment specifications shall be strictly followed, if applicable.
4.11.6 If the enclosure is shipped in more than one section, each open shipping split
shall be protected with plywood or other purchaser approved method.
Page 10 of 12
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
4.12
COMPLETE REVISION
April 2012
Documentation
4.12.1 Documentation Content
4.12.1.1 Drawings and data requirements shall be as shown in Table 1, and
purchasers PIP ELSSG12D Data Sheet.
4.12.1.2 All engineering data provided for the equipment shall represent the
actual equipment specified and ordered.
4.12.1.3 Generic drawings shall not be acceptable unless the drawings are
revised to show only the equipment being furnished.
4.12.1.4 Approval drawings (documents listed in column B of Table 1) shall
be provided and approved by purchaser before start of
manufacturing.
4.12.1.5 Final factory drawings and data (as listed in column D of Table 1),
completed to owners satisfaction, shall be provided no later than
2 weeks after shipment of equipment.
4.12.1.6 The following drawings and details for building and support
facilities shall be provided:
a. Structural drawings shall include the following:
(1) Complete dimensions
(2) Arrangement
(3) Plan and elevation views
(4) Support locations and weight on each support
(5) Other details as required for civil/structural design for
installation of the enclosure
(6) Conduit and bus duct entrance locations
(7) Lifting and jacking provisions
(8) Grounding connections
(9) Estimated weight of each piece of equipment
(10) Total weight of enclosure and included equipment,
including layout of floor beams
b. Electrical drawings shall include schematics for lighting and
power circuits.
Page 11 of 12
COMPLETE REVISION
PIP ELSSG12
Design and Fabrication of Outdoor Enclosures for
Motor Controllers and Switchgear
April 2012
Description
X(1)
Notes:
A. These documents shall be provided with proposal.
B. These documents shall be provided for purchasers review and
authorization to proceed before fabrication.
C. These documents shall be provided as part of the final certified document
submittal.
(1) Equipment shall be shipped with one set of installation, operation, and
maintenance manuals.
D. Final as-built drawings shall be provided within 2 weeks after shipment.
Page 12 of 12