Elc-Copbdp Instruction Sheet: ELC PA/PB/PC/PH Controllers Profibus/DP Slave Adapter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

IL05003018E.

pdf
2006-02-10

FUNCTION SPECIFICATIONS

2
Item

5011640000-DP00

ELC-COPBDP

Instruction Sheet

ELC PA/PB/PC/PH Controllers


Profibus/DP Slave Adapter

WARNING
This Instruction Sheet only provides descriptions for electrical specifications, general specifications,

DP Connections
Interface

DB9 9 pin connector

Transfer method

High speed RS485

Transfer cable

2-wire twisted shielded cable

Electrical isolation

500V DC

Communications
Message types

DPV0, Cyclical data exchange process

Device ID

09B9 HEX

GSD file

EATN09B9.GSD

Model Name

ELC-COPBDP
9.6K bps
19.2K bps

This is an OPEN TYPE Controller. The ELC-COPBDP should be kept in an enclosure away from

93.75K bps

airborne dust, humidity, electric shock risk and vibration.

501-10(B)(1) of the National Electrical Code.

Baud rates
(Auto detected)

500K bps
1.5M bps

Suitable for use in Class 1, Division 2, Groups A, B, C, D or Non-Hazardous locations only.

3M bps
6M bps

Warning Explosion hazard - Substitution of components may impair suitability for Class 1, Division 2.
Warning Explosion hazard - Do not disconnect equipment unless power has been switched off or the area
is known to be Non-Hazardous.

Use a screwdriver to lift and unfasten the fixing clip.

187.5K bps

Power, input and output (I/O) wiring must be in accordance with Class 1, Div. 2 wiring methods - Article

OVERVIEW

12M bps
Environmental specifications

Noise Immunity

ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge


EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, Analog &
Communication I/O: 1KV
RS(IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m

Environment

Operation: 0 ~55
Storage: -25 ~70

ELC-COPBDP: Profibus/DP Slave Module for ELC Series Controllers

(Temperature), 50~95% (Humidity), Pollution degree 2;


(Temperature), 5~95% (Humidity)

Vibration / Shock Resistance

POWER
NET

Address switch

UL1604, Class1,Div2

Agency Approvals

Operating temperature code: T5

European community EMC Directive 89/336/EEC and Low Voltage Directive

x16

73/23/EEC

ELC-COPBDP

Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)


IEC61131-2 & IEC 68-2-27 (TEST Ea)
UL508

x16

Extension port

Open the extension cover with a screwdriver.

Specification

installation and wiring.

Power LED
Net LED

Installing the ELC-COPBDP with the ELC controller

INSTALLATION AND CONFIGURATION

Connect the ELC-COPBDP to extension port of ELC controller and fasten the fixing clip.

Dimensions
Dimensions are in millimeter and [inch]

Profibus connector

POWER
POWER

ss

RUN

NET

ERROR
1

x16

BAT.LOW

X0

POWER
NET

X1

x16

X2
0

x16

X3

Support the SYNC and FREEZE for data synchronization between master and slaves.

Support Auto Baud rate detection.

Support 12MHz baud rate in DP network.

Cyclical data size is fixed to 4bytes input and 4bytes output.

Support GSD file configures by using configuration tools.

Y0
C1
Y1
C2
Y2
Y3

ELC-CDPBDP

63.4 [2.50]

Cyclical data exchange process.

X7
C0

RS-232
RS-485

STOP

60 [2.36]

x16

X6

ELC-PC12NNDR

Function

X4
X5

ELC-COPBDP

90 [3.54]

RUN

IL05003018E.pdf
Plug the PROFIBUS connector to the socket of ELC-COPBDP, and tighten screw to secure the connector.

Configure ELC-COPBDP to Profibus-DP


LED Status

Indication

Corrective Actions

Red ON

No connection to PROFIBUS

Verify that DP network installation is OK.


Verify that PLC is working.
Verify that switch address setting match with
configuration in DP master.

Green blinking

Reserved
Cyclic data exchange in
progress and OK

No action.

LED Status

Indication

Corrective Actions

Green ON

Power on

No action needed.

OFF

No power

Verify that ELC Controller is powered on.

Connecting example as follow:

PC with master card

Green ON
Profibus network

No action.

Power LED
ELC-PS01
ELC-PC12NNDR
ELC-COPBDP

POWER

RUN
X0

ERROR

POWER
NET

X1

BAT.LOW

x16

X2
X3
RUN

X4

APPENDIX PROFIBUS-DP

x16

X5
X6
X7

ELC-PC12NNDR

STOP

The Maximum cable length in a segment depends on the transmission speed. PROFIBUS-DP communicates at

Y1

Y2
Y3

ELC-COPBDP

Y0
C1

C2

PROFIBUS is an international, vendor- independent, opening filed bus standard for a wide range of applications in

RS-232
RS-485

Limitation of Cable length vs. Baudrate

PROFIBUS

C0

the fields of manufacturing, production, process and building automation, and other automation control field.

speeds from 9.6 Kbps to 12 Mbps over distances from 100 to 1,200 meters.
The PROFIBUS family comprises three types of protocol, PROFIBUS-DP, PROFIBUS-PA and PROFIBUS-FMS,
Baud Rate (bps)

9.6K

19.2K

93.75K

187.5K

500K

1.5M

3M

6M

12M

Length (m)

1200

1200

1200

1000

400

200

100

100

100

ELC-COPBDP provides fixed 4bytes input data and 4bytes output data to user in Profibus-DP system. 4bytes input

each of them is used for different tasks:

data are transmitted from ELC-COPBDP module to Profibus-DP Master, it are mapping to Y20-Y57 in ELC

And check the extension I/O by ELC software:


Connecting to ELC controller

Once connection is successful, software will check


if 32 inputs/outputs is detected.

controller when ELC-COPBDP is the first extension unit of ELC. 4bytes output data are transmitted from

PROFIBUS-DP (Decentralized Periphery): PROFIBUS-DP is a rapid and low cost communication connection

Profibus-DP Master, and it are also mapping to X20-X57 in ELC controller.

mainly designed for high-speed modem. PROFIBUS-DP has widespread usage for such items as remote I/O
systems, motor control centers, and variable speed drives. It is designed and optimized especially for

And the data mapping as follow:

communication between automation systems and decentralized peripheral devices.

4 bytes output

X20~X57

From DP Master
PROFIBUS-PA (Process Automation): PROFIBUS-PA is the PROFIBUS solution for process automation, typically

ELC-Pxxxxxxx

ELC-COPBDP

Y20~Y57

4 bytes input

with MBP-IS transmission technology. Based upon PROFIBUS-DP, PROFIBUS-PA is an extension of the
PROFIBUS-DP protocol for data transmission. It is designed to support intrinsically safe applications and can be

To DP Master

used within hazardous areas, with high explosion risk using intrinsic safe MBP-IS interface. PROFIBUS-PA is used
to connect sensor and controller to the bus.

One example ladder program as follow:

PROFIBUS-FMS (Fieldbus Message Specification): PROFIBUS-FMS is multiple master communications designed


for communication at the cell level. It is designed for acyclic or cyclic data transfers at medium speed between

M1000
DP Connector Assignment
Pin

Designation

Content

--

NC

--

NC

RxD/TxD-P

Data receiving/sending P (B)

--

NC

DGND

Data reference potential (C)

VP

Positive voltage

--

NC

RxD/TxD-N

Data receiving/sending N (A)

--

NC

MOV

K4X20

D10

MOV

K4X40

D11

MOV

D20

K4Y20

MOV

D21

K4Y40

This program example copies the 4 bytes data from X20-X57 that transmitted by DP master to D10 and D11
registers in ELC controller. And, ELC controller will write 4 bytes data in D20 and D21 registers to Y20-Y57, these 4
bytes data will send to ELC-COPBDP, and ELC-COPBDP will send these data to DP master.

TROUBLESHOOTING

NET LED
MAC ID setting for ELC-COPBDP module
Address

Content

LED Status

Indication

Corrective Actions

OFF

No power supply
Invalid PROFIBUS address
setting via switch

Verify ELC-COPBDP is powered on.


Check whether the switch setting is valid. Setting range
of slave: 1-125. Set the valid value and re-power.

Communication link to
PROFIBUS, and No cyclical
data exchanged

No action.

x16

1 .. 0x7D

Valid PROFIBUS Address.

Red blinking (rapidly)

0 or
Invalid PROFIBUS Address. NET LED will rapidly
0x7E .. 0xFF blink with RED when node address is at 0, 0x7E~
0xFF.

x16

Red blinking

control equipment and cell-level controllers. FMS services open up a wide range of applications and offer a wide
range of functionality and flexibility.