Elc-Copbdp Instruction Sheet: ELC PA/PB/PC/PH Controllers Profibus/DP Slave Adapter
Elc-Copbdp Instruction Sheet: ELC PA/PB/PC/PH Controllers Profibus/DP Slave Adapter
Elc-Copbdp Instruction Sheet: ELC PA/PB/PC/PH Controllers Profibus/DP Slave Adapter
pdf
2006-02-10
FUNCTION SPECIFICATIONS
2
Item
5011640000-DP00
ELC-COPBDP
Instruction Sheet
WARNING
This Instruction Sheet only provides descriptions for electrical specifications, general specifications,
DP Connections
Interface
Transfer method
Transfer cable
Electrical isolation
500V DC
Communications
Message types
Device ID
09B9 HEX
GSD file
EATN09B9.GSD
Model Name
ELC-COPBDP
9.6K bps
19.2K bps
This is an OPEN TYPE Controller. The ELC-COPBDP should be kept in an enclosure away from
93.75K bps
Baud rates
(Auto detected)
500K bps
1.5M bps
3M bps
6M bps
Warning Explosion hazard - Substitution of components may impair suitability for Class 1, Division 2.
Warning Explosion hazard - Do not disconnect equipment unless power has been switched off or the area
is known to be Non-Hazardous.
187.5K bps
Power, input and output (I/O) wiring must be in accordance with Class 1, Div. 2 wiring methods - Article
OVERVIEW
12M bps
Environmental specifications
Noise Immunity
Environment
Operation: 0 ~55
Storage: -25 ~70
POWER
NET
Address switch
UL1604, Class1,Div2
Agency Approvals
x16
73/23/EEC
ELC-COPBDP
x16
Extension port
Specification
Power LED
Net LED
Connect the ELC-COPBDP to extension port of ELC controller and fasten the fixing clip.
Dimensions
Dimensions are in millimeter and [inch]
Profibus connector
POWER
POWER
ss
RUN
NET
ERROR
1
x16
BAT.LOW
X0
POWER
NET
X1
x16
X2
0
x16
X3
Support the SYNC and FREEZE for data synchronization between master and slaves.
Y0
C1
Y1
C2
Y2
Y3
ELC-CDPBDP
63.4 [2.50]
X7
C0
RS-232
RS-485
STOP
60 [2.36]
x16
X6
ELC-PC12NNDR
Function
X4
X5
ELC-COPBDP
90 [3.54]
RUN
IL05003018E.pdf
Plug the PROFIBUS connector to the socket of ELC-COPBDP, and tighten screw to secure the connector.
Indication
Corrective Actions
Red ON
No connection to PROFIBUS
Green blinking
Reserved
Cyclic data exchange in
progress and OK
No action.
LED Status
Indication
Corrective Actions
Green ON
Power on
No action needed.
OFF
No power
Green ON
Profibus network
No action.
Power LED
ELC-PS01
ELC-PC12NNDR
ELC-COPBDP
POWER
RUN
X0
ERROR
POWER
NET
X1
BAT.LOW
x16
X2
X3
RUN
X4
APPENDIX PROFIBUS-DP
x16
X5
X6
X7
ELC-PC12NNDR
STOP
The Maximum cable length in a segment depends on the transmission speed. PROFIBUS-DP communicates at
Y1
Y2
Y3
ELC-COPBDP
Y0
C1
C2
PROFIBUS is an international, vendor- independent, opening filed bus standard for a wide range of applications in
RS-232
RS-485
PROFIBUS
C0
the fields of manufacturing, production, process and building automation, and other automation control field.
speeds from 9.6 Kbps to 12 Mbps over distances from 100 to 1,200 meters.
The PROFIBUS family comprises three types of protocol, PROFIBUS-DP, PROFIBUS-PA and PROFIBUS-FMS,
Baud Rate (bps)
9.6K
19.2K
93.75K
187.5K
500K
1.5M
3M
6M
12M
Length (m)
1200
1200
1200
1000
400
200
100
100
100
ELC-COPBDP provides fixed 4bytes input data and 4bytes output data to user in Profibus-DP system. 4bytes input
data are transmitted from ELC-COPBDP module to Profibus-DP Master, it are mapping to Y20-Y57 in ELC
controller when ELC-COPBDP is the first extension unit of ELC. 4bytes output data are transmitted from
PROFIBUS-DP (Decentralized Periphery): PROFIBUS-DP is a rapid and low cost communication connection
mainly designed for high-speed modem. PROFIBUS-DP has widespread usage for such items as remote I/O
systems, motor control centers, and variable speed drives. It is designed and optimized especially for
4 bytes output
X20~X57
From DP Master
PROFIBUS-PA (Process Automation): PROFIBUS-PA is the PROFIBUS solution for process automation, typically
ELC-Pxxxxxxx
ELC-COPBDP
Y20~Y57
4 bytes input
with MBP-IS transmission technology. Based upon PROFIBUS-DP, PROFIBUS-PA is an extension of the
PROFIBUS-DP protocol for data transmission. It is designed to support intrinsically safe applications and can be
To DP Master
used within hazardous areas, with high explosion risk using intrinsic safe MBP-IS interface. PROFIBUS-PA is used
to connect sensor and controller to the bus.
M1000
DP Connector Assignment
Pin
Designation
Content
--
NC
--
NC
RxD/TxD-P
--
NC
DGND
VP
Positive voltage
--
NC
RxD/TxD-N
--
NC
MOV
K4X20
D10
MOV
K4X40
D11
MOV
D20
K4Y20
MOV
D21
K4Y40
This program example copies the 4 bytes data from X20-X57 that transmitted by DP master to D10 and D11
registers in ELC controller. And, ELC controller will write 4 bytes data in D20 and D21 registers to Y20-Y57, these 4
bytes data will send to ELC-COPBDP, and ELC-COPBDP will send these data to DP master.
TROUBLESHOOTING
NET LED
MAC ID setting for ELC-COPBDP module
Address
Content
LED Status
Indication
Corrective Actions
OFF
No power supply
Invalid PROFIBUS address
setting via switch
Communication link to
PROFIBUS, and No cyclical
data exchanged
No action.
x16
1 .. 0x7D
0 or
Invalid PROFIBUS Address. NET LED will rapidly
0x7E .. 0xFF blink with RED when node address is at 0, 0x7E~
0xFF.
x16
Red blinking
control equipment and cell-level controllers. FMS services open up a wide range of applications and offer a wide
range of functionality and flexibility.