FAPN102
FAPN102
FAPN102
D -F-13001
FA P N 10 2 -R -10 L
FEATURES
Very small enclosure
10-zone capacity only
Conventional type
Switch-lock protection for operation
Easy-to-see front panel guidance
Alarm verification type
Name plate display for alarmed zones
Ni-Cd stand-by battery built in
Telephone handset built in for maintenance
Programmable function on front panel
Automatic self-checking
Various test facilities for maintenance
Surge arrestor built in for power lines
WALL MOUNTING TYPE
DESCRIPTION
The FAPN102-R-10L fire alarm panel was developed to
provide a cost- and space-saving conventional fire alarm
panel together with more user-oriented functions.
The size of the fire alarm panel is approximately 17%
smaller than that of our FAP129N series 10-zone fire alarm
panel.
The cabinet is made of ABS resin non-flammability to UL94V2.
The fire alarm panel equips with the function to lock the
operation of its front panel. That is useful to prevent the
unauthorized persons from operating the front panel.
<Alarm Inputs>
Conventional fire detectors and manual alarm boxes are
connected to alarm input circuits to give visual and audible
alarm at the panel and to actuate alarm bells. The
FAPN102-R-10L fire alarm panel has 10 alarm input circuits
(zones).
<Auxiliary input>
An auxiliary input signal can be connected to an auxiliary
input circuit to be displayed on the panel. It may be used for
a non-alarm input signal.
<Signal Outputs>
2 representative alarm signals are available.
10 voltage-free contacts are available for signal output when
an optional unit is used.
A group of output signal for an annunciator panel is
available when an optional unit is used.
<Alarm bell activation>
There are 2 modes to activate alarm bells. One is to actuate
all alarm bells at the same time, called general alarm. The
other is to actuate a group of alarm bells depending on the
location of a fire, called localized alarm.
CAT. NO.
D -F-13001
(A)
NUMBER of WIRESBASIC
Location lamp
(B)
(PL)
n6 wires
Annunciator ()
220VAC
50/60Hz
SPECIFICATIONS
Model no.
TYPE
POWER SUPPLY
AUXILIARY POWER SUPPLY
CIRCUITS VOLTAGE
POWER CONSUMPTION
NOMINAL ALARM VERIFICATION TIME
MAXIMUM NUMBER OF APPARATUS
TO BE CONNECTED
AMBIENT TEMPERATURE
LOOP RESISTANCE OF ALARM INPUT CIRCUIT
END-OF-LINE RESISTOR
TERMINAL BLOCK
MATERIALSENCLOSURE
COLOR
DIMENSIONS
WEIGHT
FAPN102-R-10L
Wall-mounting type
220VAC 50/60Hz
Ni-cd battery24VDC, 0.45Ah
5, 24, 48VDC, 24VAC
Approx. 30VA for monitoring
Approx. 60VA for alarming
60sec.
Spot type smoke detectors : 30/zoneMax.100/panel
Projected beam type smoke detectors : 2/zone
Alarm bells : 2024VDC, 10mA/bell
Location Lamps : 730V, 2W/lamp2024VDC, 21mA/lamp
0 to 40
Less than 50/loop
10k, 1/2W
Insert type terminals suitable for solid conductors with a diameter of 0.8 to 1.6 mm
Use pin type solderless contacts for stranded conductors.
ABS resin with non-flammability to 94V2UL
Light gray : Nearly to Munsell no. 5.0Y 8.5/1.0
435mm
H
310mm
W
73mm
D
Approx. 4kg
ORDERING INFORMATION
10-zone fire alarm panel
FAPN102-R-10L
These
instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in connection
with installation, operation and maintenance.
Specifications are subject to change without notice. Contact Nohmi before relying on above specifications.
Actual performance is based on proper application of the product by a qualified professional.
Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser's purposes, the matter should be
referred to Nohmi or a distributer in your region.
051020 D -F-13001YO1