Basic Drive Modules to 315 kW
The inside front cover contains a fold-out Quick Look-Up Selection Chart with page references. This will lead you
from a basic drive configuration through to the selection of options for a more sophisticated application.
To assist with listing the equipment you need for each application, the Appendix includes an Equipment List and
Price Fill-In Sheet which may be photocopied as required. Please refer to your ALSTOM Power Conversion Sales
Office or Representative for Price Lists in your local currency.
A Recommended Spares Lists plus a full list of all documentation is also included for convenience.
HELP! Should you have any problems whatsoever in specifying the necessary items, we have included at the end
of this buyers guide an enquiry sheet which you can fill in and send to us. Fill in as many of the spaces as possible
and fax the sheet in to your local ALSTOM Power Conversion Sales Office or representative. You will then be advised
of all the items you need.
RELATED DOCUMENTS
ALSPA MV3000 DELTA Buyers Guide For inverter drives between 150 to 3600 kW. The ALSPA MV3000
DELTA based inverters are available in both air and liquid cooled versions. This is available from your ALSTOM
Power Conversion Sales Office or Representative.
Variable Speed Drives Price List This is available from your ALSTOM Power Conversion Sales Office or
Representative.
ALSPA MV3000
CONTENTS
1.
1.1
1.2
Introduction.....................................................................................1-1
The MicroCubicleTM ........................................................................... 1-3
The DELTA Concept .......................................................................... 1-4
2.
2.1
2.2
2.3
2.4
2.5
2.6
3.
3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.1.6
3.1.7
3.1.8
4.
4.1
4.1.1
4.1.2
4.1.3
4.1.4
4.1.5
4.1.6
4.1.7
4.1.8
4.2
4.3
4.4
4.5
4.5.1
4.5.2
4.6
4.6.1
4.6.2
4.6.3
4.7
4.7.1
4.7.2
4.7.3
5.
5.1
5.2
5.3
Technical Data.................................................................................5-1
Weights & Dimensions MicroCubicleTM............................................. 5-1
Weights & Dimensions Line Filters ................................................... 5-2
Weights & Dimensions DC Link Chokes........................................... 5-3
Issue (08/00)
Page v
ALSPA MV3000
5.4
5.5
5.6
5.7
5.7.1
5.7.2
5.8
5.9
5.10
6.
6.1
6.2
7.
8.
8.1
8.2
Appendix.........................................................................................8-1
Documentation .................................................................................8-1
Equipment List and Price Fill-In Sheet..................................................8-3
Issue (08/00)
Page vi
ALSPA MV3000
1. Introduction
1. Introduction
FORM
MicroCubicle
TM
DESCRIPTION
Fully self-contained inverter drive unit also available fully packaged
MicroCubicleTM
Ratings up to 315 kW
Issue (08/00)
DELTA Modules
Inverter building blocks
Page 1-1
1. Introduction
ALSPA MV3000
All inverters are available in three AC supply voltage ranges as indicated in the following table.
VOLTS
DELTA Modules Liquid Cooled
575 690
380 440
10
100
1000
4000 kW
This Buyers Guide covers only the ALSPA MV3000 MicroCubicle range of inverters up to 315 kW.
Please refer to ALSTOM or the ALSPA MV3000 DELTA Buyers Guide for details of higher rated inverters.
Page 1-2
Issue (08/00)
ALSPA MV3000
1. Introduction
The MicroCubicleTM
1.1
The ALSPA MV3000 MicroCubicleTM combines innovations in design, compactness, power to weight ratio,
ease of use and speed of maintenance previously unknown in an AC inverter drive.
A mixture of wide power and voltage supply range, increased functionality and improved usability allow the
ALSPA MV3000 to be applied in virtually all types of applications in all corners of the globe.
MicroCubicleTM Overview
-
Mechanical Outline
-
Bookcase format
High packing density
Space saving
Dimensions to fit standard cubicles
Expandability
-
Built-in Reliability
-
Further Features
-
Issue (08/00)
Page 1-3
1. Introduction
1.2
ALSPA MV3000
The Concept:
For drive ratings above 315 kW ALSPA MV3000 is designed to be fully packaged. To provide flexibility of
construction and commonality of components over a wide power range, the DELTA concept was conceived.
It is a modular approach to the construction of AC inverter drives where the major drive components have
been built into conveniently sized building blocks called DELTA Modules. A complete inverter drive is
constructed using a number of these modules. Further, parallel capability allows higher ratings to be achieved
using the same modules.
The Modules:
Parallel Capability:
Inverter drives spanning a wide power range can take advantage of common building blocks providing
benefits in drive construction, minimisation of spares holding and identical set-up procedure.
COOLING
RECTIFIER
MODULES
INVERTER
MODULES
CONTROLLER
DC CHOKE
Page 1-4
Issue (08/00)
ALSPA MV3000
2. Product Overview
2. Product Overview
2.1
Supply Voltage
Voltage Variation
10% long term, 15% for 0.5 to 30 cycles with loss of performance but no trip.
Voltage Imbalance
Frequency
50 Hz, 60 Hz as selected.
Freq. Variation
Network Type
With earthed/grounded neutral (i.e. TN or TT) or isolated neutral (i.e. IT network). For IT networks, transient
suppression (e.g. to UL 1449) and earth fault protection must be provided external to the drive.
Output
Overload
Constant Torque: 150% full load current for 60s, giving up to 160% related motor torque at breakaway.
Variable Torque: 110% full load current for 60s where selected (see rating tables)
Voltage
3 Phase, compensated to give maximum voltage level equal to the supply voltage
Frequency
3 Modes available: Variable Voltage Variable Frequency, Flux Vector without encoder, Flux vector with encoder
Switching Frequency
Enclosure protection
Operating - Temperature
Storage
- Altitude
- Humidity
- Vibration
- Temperature
-25C to 55C
- Humidity
Transport - Temperature
Cooling
-25C to 70C
- Humidity
- Vibration
- Method
- Air Quality
Clean, free from dust, condensation and conductive vapours (i.e. pollution degree 2 according to IEC 60664-1 and
UL840). If optional dirty air kit is fitted, the power devices can use unfiltered air that does not contain corrosive,
conductive or explosive dust or gases.
EMC
CE
CE marked to comply with the European Union Low Voltage Directive 73/23/EEC.
Control sources
Optional Drive Data Manager - mounts on drive module, cubicle, or is hand held. Control terminals for remote
control (analogue and digital) wiring. Control via Serial Link.
Languages
Serial communications
RS485, RS232, with MODBUS ASCII/RTU, GEM80 ESP. Drive to drive link. Opt: WorldFIP, PROFIBUS, DeviceNet.
Analogue inputs
Analogue outputs
Digital inputs
Digital outputs
1 x RS422 Programmable as: Frequency input for speed reference or Frequency output of motor speed
Encoder Feedback
4 channel differential line receiver for interface to incremental encoder (A, A*, B, B*, Z, Z*). Max 1 MHz
Performance
Issue (08/00)
Page 2-1
2. Product Overview
2.2
ALSPA MV3000
Model
Motor Rating
Frame
Size
Nominal
Power
(1.1/1.5)
kW
Nominal
Power
(1.1/1.5)
HP
Continuous
Current
(1.1)
(1.5)
A
A
Model Number
(All models shown are 50 Hz)
Rating (1.1/1.5)
380 440 V
MV3ACL030A4 / MV3ACL022A4
MV3058A4A1
30/22
40/29
58
44
MV3071A4A1
37/30
50/40
71
58
MV3ACL037A4 / MV3ACL030A4
MV3086A4A1
45/37
60/50
86
71
MV3ACL045A4 / MV3ACL037A4
MV3105A4A1
55/45
74/60
105
86
MV3ACL055A4 / MV3ACL045A4
MV3140A4A1
75/55
101/74
140
105
MV3ACL075A4 / MV3ACL055A4
MV3168A4A1
90/75
121/101
168
140
MV3ACL090A4 / MV3ACL075A4
MV3204A4A1
110/90
147/121
204
168
MV3ACL110A4 / MV3ACL090A4
MV3244A4A1
132/110
177/147
244
204
MV3ACL132A4 / MV3ACL110A4
MV3ACL160A4 / MV3ACL132A4
MV3292A4A1
160/132
214/177
292
244
MV3364A4A1
200/160
268/214
364
292
MV3ACL200A4 / MV3ACL160A4
MV3449A4A1
250/200
335/268
449
364
MV3ACL250A4 / MV3ACL200A4
MV3503A4A1
280/250
375/335
503
449
MV3ACL280A4 / MV3ACL250A4
690 V
MV3062A6A1
55/45
74/60
61
50
MV3ACL055A7 / MV3ACL045A7
MV3077A6A1
75/55
101/74
82
61
MV3ACL075A7 / MV3ACL055A7
MV3099A6A1
90/75
121/101
98
82
MV3ACL090A7 / MV3ACL075A7
MV3125A6A1
110/90
147/121
119
98
MV3ACL110A7 / MV3ACL090A7
MV3144A6A1
132/110
177/147
142
119
MV3ACL132A7 / MV3ACL110A7
MV3192A6A1
160/132
214/177
170
142
MV3ACL160A7 / MV3ACL132A7
MV3242A6A1
200/160
268/214
211
170
MV3ACL200A7 / MV3ACL160A7
MV3289A6A1
250/200
335/268
260
211
MV3ACL250A7 / MV3ACL200A7
MV3336A6A1
280/250
375/335
291
260
MV3ACL280A7 / MV3ACL250A7
MV3382A6A1
315/280
422/375
327
292
MV3ACL315A7 / MV3ACL280A7
Page 2-2
Issue (08/00)
ALSPA MV3000
Drive
Model
2. Product Overview
IEC Rated
Fuse
(1.1/1.5)
A
Losses
UL Rated
Fuse
(1.1/1.5)
A
Total Drive
Approx. Losses
(Maximum)
kW
Ventilation
Fan Fuses
Typical
Drive Airflow
Rating
m3/h
cu ft/min
380 440 V
MV3058A4A1
59/44
63/50
80/60
1.1
140
85
N/A
MV3071A4A1
73/59
80/63
100/80
1.3
140
85
N/A
MV3086A4A1
88/73
100/80
100/100
1.6
255
150
MV3105A4A1
107/88
125/100
150/110
1.8
255
150
MV3140A4A1
145/107
160/125
200/150
2.4
255
150
MV3168A4A1
173/145
200/160
225/200
3.0
680
400
MV3204A4A1
210/173
250/200
300/225
3.4
680
400
MV3244A4A1
251/210
315/250
350/300
4.0
680
400
MV3292A4A1
304/251
315/315
400/350
4.4
680
400
MV3364A4A1
379/304
400/315
500/400
5.6
680
400
MV3449A4A1
473/379
500/400
600/500
6.5
850
500
MV3503A4A1
529/473
630/500
700/600
7.5
850
500
690 V
MV3062A6A1
62/51
63/63
1.6
255
150
MV3077A6A1
84/62
100/63
2.0
255
150
MV3099A6A1
100/84
100/100
2.4
255
150
MV3125A6A1
122/100
125/100
3.0
680
400
MV3144A6A1
146/122
160/125
3.4
680
400
MV3192A6A1
176/146
200/160
4.1
680
400
4
4
MV3242A6A1
220/176
250/200
4.6
680
400
MV3289A6A1
274/220
315/250
5.4
850
500
MV3336A6A1
307/274
315/315
6.2
850
500
MV3382A6A1
345/307
400/315
7.1
850
500
Issue (08/00)
Page 2-3
2. Product Overview
2.3
ALSPA MV3000
Model
Motor Rating
Frame
Size
Nominal
Power
(1.1/1.5)
kW
Nominal
Power
(1.1/1.5)
HP
Continuous
Current
(1.1)
(1.5)
A
A
Model Number
(All models shown are 60 Hz)
Rating (1.1/1.5)
460 525 V
MV3052A5A1
30/22
40/30
52
40
MV3ACL040B5 / MV3ACL030B5
MV3065A5A1
37/30
50/40
65
52
MV3ACL050B5 / MV3ACL040B5
MV3077A5A1
45/37
60/50
77
65
MV3ACL060B5 / MV3ACL050B5
MV3096A5A1
56/45
75/60
96
77
MV3ACL075B5 / MV3ACL060B5
MV3124A5A1
75/56
100/75
124
96
MV3ACL100B5 / MV3ACL075B5
MV3156A5A1
93/75
125/100
156
124
MV3ACL125B5 / MV3ACL100B5
MV3180A5A1
112/93
150/125
180
156
MV3ACL150B5 / MV3ACL125B5
MV3240A5A1
149/112
200/150
240
180
MV3ACL200B5 / MV3ACL150B5
MV3302A5A1
187/149
250/200
302
240
MV3ACL250B5 / MV3ACL200B5
MV3361A5A1
224/187
300/250
361
302
MV3ACL300B5 / MV3ACL250B5
MV3414A5A1
261/224
350/300
414
361
MV3ACL350B5 / MV3ACL300B5
MV3477A5A1
298/261
400/350
477
414
MV3ACL400B5 / MV3ACL350B5
MV3062A6A1
45/37
60/50
62
52
MV3ACL060B6 / MV3ACL050B6
MV3077A6A1
56/45
75/60
77
62
MV3ACL075B6 / MV3ACL060B6
MV3099A6A1
75/56
100/75
99
77
MV3ACL100B6 / MV3ACL075B6
MV3125A6A1
93/75
125/100
125
99
MV3ACL125B6 / MV3ACL100B6
600 V
MV3144A6A1
112/93
150/125
144
125
MV3ACL150B6 / MV3ACL125B6
MV3192A6A1
149/112
200/150
192
144
MV3ACL200B6 / MV3ACL150B6
MV3242A6A1
187/149
250/200
242
192
MV3ACL250B6 / MV3ACL200B6
MV3289A6A1
224/187
300/250
289
242
MV3ACL300B6 / MV3ACL250B6
MV3336A6A1
261/224
350/300
336
289
MV3ACL350B6 / MV3ACL300B6
Page 2-4
Issue (08/00)
ALSPA MV3000
Drive
Model
2. Product Overview
IEC Rated
Fuse
(1.1/1.5)
A
Losses
UL Rated
Fuse
(1.1/1.5)
A
Total Drive
Approx. Losses
(Maximum)
kW
Ventilation
Fan Fuses
Typical
Drive Airflow
Rating
m3/h
cu ft/min
460 - 525 V
MV3052A5A1
53/40
63/40
70/50
1.0
140
85
N/A
MV3065A5A1
66/53
80/63
90/70
1.2
140
85
N/A
MV3077A5A1
79/66
80/80
100/90
1.5
255
150
MV3096A5A1
98/79
100/80
125/100
1.7
255
150
MV3124A5A1
130/98
160/100
175/125
2.2
255
150
MV3156A5A1
162/130
200/160
225/175
2.9
680
400
MV3180A5A1
194/162
200/200
250/225
3.1
680
400
MV3240A5A1
258/194
315/200
350/250
4.0
680
400
MV3302A5A1
321/258
400/315
450/350
4.7
680
400
MV3361A5A1
385/321
400/400
500/450
5.6
850
500
MV3414A5A1
448/385
500/400
600/500
6.4
850
500
MV3477A5A1
512/448
630/500
650/600
7.6
850
500
64/53
80/63
80/70
1.6
255
150
600 V
MV3062A6A1
MV3077A6A1
79/64
80/80
100/80
1.8
255
150
MV3099A6A1
105/79
125/80
150/100
2.4
255
150
MV3125A6A1
130/105
160/125
175/150
3.1
680
400
MV3144A6A1
156/130
160/160
200/175
3.3
680
400
MV3192A6A1
207/156
250/160
300/200
4.4
680
400
MV3242A6A1
258/207
315/250
350/300
5.0
680
400
MV3289A6A1
309/258
315/315
400/350
6.0
850
500
MV3336A6A1
359/309
400/315
450/400
7.0
850
500
Issue (08/00)
Page 2-5
2. Product Overview
2.4
ALSPA MV3000
The following table lists the main features and parameters available as standard within ALSPA MV3000.
Parameters are grouped in 50 functional menus for ease of use. It is possible to hide and reveal menus in
order to customise the complexity of the user interface.
CONTROL PANEL FUNCTIONS
CONTROL FEATURES
Frequency Control
Speed Control
Torque Control open & closed loop
Open Loop (Encoderless) Flux Vector Control
Position Control
Rotary
Linear
Position Shaper
Tacho Feedback
Encoder Feedback
Slip Compensation
Fwd/Rev Separate Ramps
Volt Free Output Relays
Start Modes:
Normal Ramp Start
Synchronous starting
Synchro Start only after a trip
D.O.L. Motor Start
Stop Modes:
Coast Stop
Normal Ramp Stop
Saturation Braking (High Trq Stop)
DC Injection Braking
PID Controller
Alpha-numeric Display
Numeric Keypad Entry
PC Software
Frequency Skipping
Multi-Level Password Authorisation
Separate Auxiliary Supply
Reference Sequencer
Reference Shaper
Multiple Reference Sources
Master/Slave Operation
Local/Remote Operation
Motor Parameter Identification
Energy Saving Economy Mode
Analogue I/O
Digital I/O
High Speed Digital I/O
Control and Status Flags
General Purpose Logic Blocks
Speed Droop
Motorised Potentiometer
MONITORING/DISPLAY
AC Supply Voltage
Motor Voltage
DC Link Voltage
Current
Frequency
Motor Power
Motor Speed rpm
Motor Speed m/s
Motor Thermal State
Speed Reach
Torque
Hours Run
Days Run
Hours Energised
Days Energised
kWhrs
MWhrs
Warning Fault
Trip Fault
History Record
- Set-Up
- Monitor
- Playback
- Trigger Source
- Printing
Trip Log
Time Since Last Trip
Drive Status Word
Output Bridge Temperature
Control Electronics Temperature
Dynamic Braking Unit Temperature
Interlock
PROTECTION FEATURES
PROGRAMMABLE ADJUSTMENTS
I2t Overload
Current Limit
Current Clipping
Instantaneous Short Circuit
Earth Fault
Phase Loss
Overvoltage
Undervoltage
Heatsink Overtemperature
Ambient Overtemperature
Motor Modelling
Motor Thermistor
Motor Stall
Microprocessor Fault
Keypad Fault
Page 2-6
Issue (08/00)
ALSPA MV3000
2.5
2. Product Overview
Standards of Compliance
EC Directives
CE Marked: complies with EN50178 LVD. Complies with EN61800-3 EMC when used and installed as directed.
BS 7671:1992
Requirements for electrical installations. IEE Wiring Regulations. Sixteenth edition. (Related to IEC 60364)
NFPA 70 - 1999
IEC 60038:1983
IEC 60417-1:1998
IEC 60417-2:1998
IEC 60664-1:1992
Insulation co-ordination for equipment within low voltage systems - Part 1: Principles, requirements and tests
IEC 60664-3:1992
Insulation co-ordination for equipment within low voltage systems - Part 3: Use of coatings to achieve insulation coordination of printed circuit assemblies
(BS) EN 50178:1998
(BS) EN 50082-2:1995
(BS) EN 55011:1998
CISPR 11:1999
Industrial, scientific and medical (ISM) radio-frequency equipment - Electromagnetic disturbance characteristics - Limits
and methods of measurement
IEC 60065:1998
(BS) EN 60068-2-6:1996
IEC 60068-2-6:1995
(BS) EN 60073:1997
IEC 60073:1996
Basic and safety principles for man-machine interface, marking and identification - Coding principles for indication
devices and actuators
(BS) EN 60146-1-1:1993
IEC 60146-1-1:1991
Semiconductor convertors - General requirements and line commutated convertors - Part 1-1: Specifications of basic
requirements
(BS) EN 60204-1:1998
IEC 60204-1:1997
(BS) EN 60529:1992
IEC 60529:1989
(BS) EN 60721-3-2:1997
IEC 60721-3-2:1997
Classification of environmental conditions - Part 3: Classification of groups of environmental parameters and their
severities - Section 2: Transportation
(BS) EN 60721-3-3:1995
IEC 60721-3-3:1994
Classification of environmental conditions - Part 3: Classification of groups of environmental parameters and their
severities - Section 3: Stationary use at weather protected locations
IEC 60950:1999
IEC 61000-2-2:1990
Electromagnetic compatibility (EMC) - Part 2: Environment - Section 2: Compatibility levels for low-frequency
conducted disturbances and signalling in public low-voltage power supply systems
(BS) EN 61000-2-4:1995
IEC 61000-2-4:1994
Electromagnetic compatibility (EMC) - Part 2: Environment - Section 4: Compatibility levels in industrial plants for lowfrequency conducted disturbances
(BS) EN 61000-4-2:1995
IEC 61000-4-2:1995
Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 2: Electrostatic discharge
immunity test. Basic EMC Publication
(BS) EN 61000-4-3:1997
IEC 61000-4-3:1995
Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 3: Radiated, radiofrequency, electromagnetic field immunity test
(BS) EN 61000-4-4:1995
IEC 61000-4-4:1995
Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 4: Electrical fast
transient/burst immunity test. Basic EMC Publication
(BS) EN 61000-4-5:1995
IEC 61000-4-5:1995
Electromagnetic compatibility (EMC) - Part 4: Testing and measurement techniques - Section 5: Surge immunity test
(BS) EN 61136-1:1998
IEC 61136-1:1992
Semiconductor power convertors - Adjustable speed electric drive systems - General requirements - Part 1: Rating
specifications, particularly for D.C. motor drives
(BS) EN 61800-1:1998
IEC 61800-1:1997
Adjustable speed electrical power drive systems - Part 1: General requirements - Rating specifications for low voltage
adjustable speed D.C. power drive systems
(BS) EN 61800-2:1998
IEC 61800-2:1998
Adjustable speed electrical power drive systems - Part 2: General requirements - Rating specifications for low voltage
adjustable frequency AC power drive systems
(BS) EN 61800-3:1997
IEC 61800-3:1996
Adjustable speed electrical power drive systems - Part 3: EMC product standard including specific test methods
ANSI/UL 508C
UL 840
CAN/CSA C22.2-14:1995
Issue (08/00)
Page 2-7
2. Product Overview
2.6
ALSPA MV3000
Speed
Resolution
0.01%
Control accuracy
0.1%
Resolution
0.01%
Accuracy (absolute)
0.01%
VVVF
ENCODERLESS
FLUX VECTOR
FLUX VECTOR
WITH ENCODER
50 : 1
50 : 1
>1000 : 1
N/A
20 Rad/s
100 Rad/s
< 1 Rad/s
10 %
10 %
5%
1%
0.5 %
0.02 %
Page 2-8
Issue (08/00)
ALSPA MV3000
In order to match the right inverter to the application, one first needs to establish basic data about the mains
electricity supply and also the motor nameplate details.
Mains Electricity Supply
Mains Supply Voltage:
Volts
Motor Nameplate Details
Volts
Hz
Amps
Motor Power:
kW
r/min
The next step is to categorise the application in order to choose an inverter with
the right overload duty to match the application requirements.
In general we distinguish between two types of applications:
1)
2)
Constant Torque Applications: for all other types of loads (150% overload)
Mains Supply
Line
Filter
ALSPA MV3000
Inverter Drive
Drive
Data
Manager
To Motor
Application
Centrifugal Pump or Fan ?
No (1.5 O/L)
Go To Page
Go To Page
380 440 V AC 50 Hz
3-2
3-6
575 - 690 V AC 50 Hz
3-3
3-7
460 - 525 V AC 60 Hz
3-4
3-8
575 690 V AC 60 Hz
3-5
3-9
* All drives are suitable for 50 and 60 Hz supplies. Typical territorial voltage/frequency ranges shown.
Issue (08/00)
Page 3-1
ALSPA MV3000
Variable torque loads generally comprise centrifugal pump and fan applications where 110% of full load
current overload is sufficient. Fan fluxing (square law) and economy modes are included to assist with energy
saving.
Mains Supply
Line
Filter
ALSPA MV3000
Inverter Drive
Drive
Data
Manager
To Motor
Line Filter
Order Codes
kW
HP
Amps
MicroCubicleTM
Line Filter VT
30
40
58
MV3058A4A1
MV3ACL030A4
37
50
71
MV3071A4A1
MV3ACL037A4
45
60
86
MV3086A4A1
MV3ACL045A4
55
74
105
MV3105A4A1
MV3ACL055A4
75
101
140
MV3140A4A1
MV3ACL075A4
90
121
168
MV3168A4A1
MV3ACL090A4
110
147
204
MV3204A4A1
MV3ACL110A4
132
177
244
MV3244A4A1
MV3ACL132A4
160
214
292
MV3292A4A1
MV3ACL160A4
200
268
364
MV3364A4A1
MV3ACL200A4
250
335
449
MV3449A4A1
MV3ACL250A4
280
375
503
MV3503A4A1
MV3ACL280A4
MVS3000-4001
Special Note: If the drive is to be used in a 12 Pulse configuration, then the Input Line Filter is not required if
it is supplied from its own dedicated 12 Pulse Supply Transformer. Where a number of drives are supplied
from a common 12 pulse transformer, then each drive must have its own Input Line Filter.
Page 3-2
Issue (08/00)
ALSPA MV3000
3.1.2
Variable torque loads generally comprise centrifugal pump and fan applications where 110% of full load
current overload is sufficient. Fan fluxing (square law) and economy modes are included to assist with energy
saving.
Mains Supply
Line
Filter
ALSPA MV3000
Inverter Drive
Drive
Data
Manager
To Motor
Line Filter
Order Codes
TM
kW
HP
Amps
MicroCubicle
Line Filter VT
55
74
61
MV3062A6A1
MV3ACL055A7
75
101
82
MV3077A6A1
MV3ACL075A7
90
121
98
MV3099A6A1
MV3ACL090A7
110
147
119
MV3125A6A1
MV3ACL110A7
132
177
142
MV3144A6A1
MV3ACL132A7
160
214
170
MV3192A6A1
MV3ACL160A7
200
268
211
MV3242A6A1
MV3ACL200A7
250
335
260
MV3289A6A1
MV3ACL250A7
280
375
291
MV3336A6A1
MV3ACL280A7
315
422
327
MV3382A6A1
MV3ACL315A7
MVS3000-4001
Special Note: If the drive is to be used in a 12 Pulse configuration, then the Input Line Filter is not required if
it is supplied from its own dedicated 12 Pulse Supply Transformer. Where a number of drives are supplied
from a common 12 pulse transformer, then each drive must have its own Input Line Filter.
Issue (08/00)
Page 3-3
ALSPA MV3000
Variable torque loads generally comprise centrifugal pump and fan applications where 110% of full load
current overload is sufficient. Fan fluxing (square law) and economy modes are included to assist with energy
saving.
Mains Supply
Line
Filter
ALSPA MV3000
Inverter Drive
Drive
Data
Manager
To Motor
Line Filter
Order Codes
TM
kW
HP
Amps
MicroCubicle
Line Filter VT
30
40
52
MV3052A5A1
MV3ACL040B5
37
50
65
MV3065A5A1
MV3ACL050B5
45
60
77
MV3077A5A1
MV3ACL060B5
56
75
96
MV3096A5A1
MV3ACL075B5
75
100
124
MV3124A5A1
MV3ACL100B5
93
125
156
MV3156A5A1
MV3ACL125B5
112
150
180
MV3180A5A1
MV3ACL150B5
149
200
240
MV3240A5A1
MV3ACL200B5
187
250
302
MV3302A5A1
MV3ACL250B5
224
300
361
MV3361A5A1
MV3ACL300B5
261
350
414
MV3414A5A1
MV3ACL350B5
298
400
477
MV3477A5A1
MV3ACL400B5
MVS3000-4001
Special Note: If the drive is to be used in a 12 Pulse configuration, then the Input Line Filter is not required if
it is supplied from its own dedicated 12 Pulse Supply Transformer. Where a number of drives are supplied
from a common 12 pulse transformer, then each drive must have its own Input Line Filter.
Page 3-4
Issue (08/00)
ALSPA MV3000
3.1.4
Variable torque loads generally comprise centrifugal pump and fan applications where 110% of full load
current overload is sufficient. Fan fluxing (square law) and economy modes are included to assist with energy
saving.
Mains Supply
Line
Filter
ALSPA MV3000
Inverter Drive
Drive
Data
Manager
To Motor
Line Filter
Order Codes
TM
kW
HP
Amps
MicroCubicle
Line Filter VT
45
60
62
MV3062A6A1
MV3ACL060B6
56
75
77
MV3077A6A1
MV3ACL075B6
75
100
99
MV3099A6A1
MV3ACL100B6
93
125
125
MV3125A6A1
MV3ACL125B6
112
150
144
MV3144A6A1
MV3ACL150B6
149
200
192
MV3192A6A1
MV3ACL200B6
187
250
242
MV3242A6A1
MV3ACL250B6
224
300
289
MV3289A6A1
MV3ACL300B6
261
350
336
MV3336A6A1
MV3ACL350B6
MVS3000-4001
Special Note: If the drive is to be used in a 12 Pulse configuration, then the Input Line Filter is not required if
it is supplied from its own dedicated 12 Pulse Supply Transformer. Where a number of drives are supplied
from a common 12 pulse transformer, then each drive must have its own Input Line Filter.
Issue (08/00)
Page 3-5
ALSPA MV3000
With the exception of centrifugal pump and fan loads, all types of applications, in all industries, may be
classified as constant torque loads. These have a requirement for up to 150% of full load current overload.
Mains Supply
Line
Filter
ALSPA MV3000
Inverter Drive
Drive
Data
Manager
To Motor
Line Filter
Order Codes
TM
kW
HP
Amps
MicroCubicle
Line Filter CT
22
29
44
MV3058A4A1
MV3ACL022A4
30
40
58
MV3071A4A1
MV3ACL030A4
37
50
71
MV3086A4A1
MV3ACL037A4
45
60
86
MV3105A4A1
MV3ACL045A4
55
74
105
MV3140A4A1
MV3ACL055A4
75
101
140
MV3168A4A1
MV3ACL075A4
90
121
168
MV3204A4A1
MV3ACL090A4
110
147
204
MV3244A4A1
MV3ACL110A4
132
177
244
MV3292A4A1
MV3ACL132A4
160
214
292
MV3364A4A1
MV3ACL160A4
200
268
364
MV3449A4A1
MV3ACL200A4
250
355
449
MV3503A4A1
MV3ACL250A4
MVS3000-4001
Special Note: If the drive is to be used in a 12 Pulse configuration, then the Input Line Filter is not required if
it is supplied from its own dedicated 12 Pulse Supply Transformer. Where a number of drives are supplied
from a common 12 pulse transformer, then each drive must have its own Input Line Filter.
Page 3-6
Issue (08/00)
ALSPA MV3000
3.1.6
With the exception of centrifugal pump and fan loads, all types of applications, in all industries, may be
classified as constant torque loads. These have a requirement for up to 150% of full load current overload.
Mains Supply
Line
Filter
ALSPA MV3000
Inverter Drive
Drive
Data
Manager
To Motor
Line Filter
Order Codes
TM
kW
HP
Amps
MicroCubicle
Line Filter CT
45
60
50
MV3062A6A1
MV3ACL045A7
55
74
61
MV3077A6A1
MV3ACL055A7
75
101
82
MV3099A6A1
MV3ACL075A7
90
121
98
MV3125A6A1
MV3ACL090A7
110
147
119
MV3144A6A1
MV3ACL110A7
132
177
142
MV3192A6A1
MV3ACL132A7
160
214
170
MV3242A6A1
MV3ACL160A7
200
268
211
MV3289A6A1
MV3ACL200A7
250
335
260
MV3336A6A1
MV3ACL250A7
280
375
292
MV3382A6A1
MV3ACL280A7
MVS3000-4001
Special Note: If the drive is to be used in a 12 Pulse configuration, then the Input Line Filter is not required if
it is supplied from its own dedicated 12 Pulse Supply Transformer. Where a number of drives are supplied
from a common 12 pulse transformer, then each drive must have its own Input Line Filter.
Issue (08/00)
Page 3-7
ALSPA MV3000
With the exception of centrifugal pump and fan loads, all types of applications, in all industries, may be
classified as constant torque loads. These have a requirement for up to 150% of full load current overload.
Mains Supply
Line
Filter
ALSPA MV3000
Inverter Drive
Drive
Data
Manager
To Motor
Line Filter
Order Codes
TM
kW
HP
Amps
MicroCubicle
Line Filter CT
22
30
40
MV3052A5A1
MV3ACL030B5
30
40
52
MV3065A5A1
MV3ACL040B5
37
50
65
MV3077A5A1
MV3ACL050B5
45
60
77
MV3096A5A1
MV3ACL060B5
56
75
96
MV3124A5A1
MV3ACL075B5
75
100
124
MV3156A5A1
MV3ACL100B5
93
125
156
MV3180A5A1
MV3ACL125B5
112
150
180
MV3240A5A1
MV3ACL150B5
149
200
240
MV3302A5A1
MV3ACL200B5
187
250
302
MV3361A5A1
MV3ACL250B5
224
300
361
MV3414A5A1
MV3ACL300B5
261
350
414
MV3477A5A1
MV3ACL350B5
MVS3000-4001
Special Note: If the drive is to be used in a 12 Pulse configuration, then the Input Line Filter is not required if
it is supplied from its own dedicated 12 Pulse Supply Transformer. Where a number of drives are supplied
from a common 12 pulse transformer, then each drive must have its own Input Line Filter.
Page 3-8
Issue (08/00)
ALSPA MV3000
3.1.8
With the exception of centrifugal pump and fan loads, all types of applications, in all industries, may be
classified as constant torque loads. These have a requirement for up to 150% of full load current overload.
Mains Supply
Line
Filter
ALSPA MV3000
Inverter Drive
Drive
Data
Manager
To Motor
Line Filter
Order Codes
TM
kW
HP
Amps
MicroCubicle
Line Filter CT
37
50
52
MV3062A6A1
MV3ACL050B6
45
60
62
MV3077A6A1
MV3ACL060B6
56
75
77
MV3099A6A1
MV3ACL075B6
75
100
99
MV3125A6A1
MV3ACL100B6
93
125
125
MV3144A6A1
MV3ACL125B6
112
150
144
MV3192A6A1
MV3ACL150B6
149
200
192
MV3242A6A1
MV3ACL200B6
187
250
242
MV3289A6A1
MV3ACL250B6
224
300
289
MV3336A6A1
MV3ACL300B6
MVS3000-4001
Special Note: If the drive is to be used in a 12 Pulse configuration, then the Input Line Filter is not required if
it is supplied from its own dedicated 12 Pulse Supply Transformer. Where a number of drives are supplied
from a common 12 pulse transformer, then each drive must have its own Input Line Filter.
Issue (08/00)
Page 3-9
ALSPA MV3000
Page 3-10
Issue (08/00)
ALSPA MV3000
4. Extended Applications
4. Extended Applications
Some applications may require the addition of further components to meet the needs of local regulations,
system integration, or performance.
The following chart lists situations when further components may be necessary and indicates where the
selection rules are to be located.
REQUIREMENT
GO TO
Pump & Fan
Other Applications
Other Applications
Page 4-12
Communication Fieldbus
Page 4-22
Page 6-1
Page 7-1
Documentation List.
Issue (08/00)
Page 4-1
4. Extended Applications
ALSPA MV3000
Page 4-2
Issue (08/00)
ALSPA MV3000
4.1
4. Extended Applications
Low Harmonics
Various configurations are available to progressively reduce harmonic levels to meet site requirements or
local regulations. The following table shows harmonic levels for three configurations, beginning with the
standard 6 pulse configuration and two other configurations with improved harmonic levels. Note: these
levels will be affected by existing supply harmonic levels, supply imbalance and supply impedance.
PROGRESSIVELY LOWER HARMONICS
6 Pulse - Standard
6 Pulse
Harmonic
6 Pulse - Enhanced
6 Pulse
Harmonic
12 Pulse
12 Pulse
Order
% of Fund.
Order
% of Fund.
Harmonic
Order
100
100
100
44.69
28.00
1.00
20.11
10.40
0.69
11
7.26
11
7.90
11
8.35
13
4.13
13
4.70
13
4.52
17
3.35
17
4.00
17
0.29
19
1.96
19
2.85
19
0.26
23
1.84
23
2.30
23
1.99
25
1.23
25
1.90
25
1.69
29
1.12
29
1.40
29
0.17
31
0.89
31
1.20
31
0.16
THD (Current)
49.9 %
THD (Current)
31.8 %
THD (Current)
9.9 %
Mains Supply
ALSPA
MV3000
Inverter
Drive
Data
Manager
To Motor
Mains Supply
Mains Supply
Line
Filter
Line
Filter
12 Pulse
Transformer
Drive
Data
Manager
ALSPA
MV3000
Inverter
Drive
Data
Manager
To Motor
% of Fund.
DC Link
Choke
12
Pulse
Unit
Interbridge
Transformer
ALSPA
MV3000
Inverter
To Motor
Application
Torque
Variable
Go to
Page
3-2 3-5
Application
Torque
Variable
Go to
Page
4-4, 4-8
Application
Torque
Variable
Go to
Page
4-6, 4-10
Constant
3-6 3-9
Constant
4-5, 4-9
Constant
4-7, 4-11
Issue (08/00)
Page 4-3
4. Extended Applications
4.1.1
ALSPA MV3000
For 6 Pulse Enhanced configuration, the addition of a DC Link Choke will be required to meet the harmonic
level indicated on Page 4-3.
Amps
MicroCubicleTM
380 - 440 V
Line Filter
Variable Torque
DC Link Choke
Variable Torque
58
71
MV3058A4A1
MV3071A4A1
MV3ACL030A4
MV3ACL037A4
MV3DCL030A4
MV3DCL037A4
60
86
MV3086A4A1
MV3ACL045A4
MV3DCL045A4
74
105
MV3105A4A1
MV3ACL055A4
MV3DCL055A4
75
101
140
MV3140A4A1
MV3ACL075A4
MV3DCL075A4
90
121
168
MV3168A4A1
MV3ACL090A4
MV3DCL090A4
110
147
204
MV3204A4A1
MV3ACL110A4
MV3DCL110A4
132
177
244
MV3244A4A1
MV3ACL132A4
MV3DCL132A4
160
214
292
MV3292A4A1
MV3ACL160A4
MV3DCL160A4
200
268
364
MV3364A4A1
MV3ACL200A4
MV3DCL200A4
250
335
449
MV3449A4A1
MV3ACL250A4
MV3DCL250A4
280
375
503
MV3503A4A1
MV3ACL280A4
MV3DCL280A4
kW
Rating at 400 V
HP
30
37
40
50
45
55
Rating at 690 V
kW
HP
Amps
575 - 690 V
55
74
61
MV3062A6A1
MV3ACL055A7
MV3DCL055A7
75
101
82
MV3077A6A1
MV3ACL075A7
MV3DCL075A7
90
121
98
MV3099A6A1
MV3ACL090A7
MV3DCL090A7
110
147
119
MV3125A6A1
MV3ACL110A7
MV3DCL110A7
132
177
142
MV3144A6A1
MV3ACL132A7
MV3DCL132A7
160
214
170
MV3192A6A1
MV3ACL160A7
MV3DCL160A7
200
268
211
MV3242A6A1
MV3ACL200A7
MV3DCL200A7
250
335
260
MV3289A6A1
MV3ACL250A7
MV3DCL250A7
280
375
291
MV3336A6A1
MV3ACL280A7
MV3DCL280A7
315
422
327
MV3382A6A1
MV3ACL315A7
MV3DCL315A7
Page 4-4
Issue (08/00)
ALSPA MV3000
4.1.2
4. Extended Applications
For 6 Pulse Enhanced configuration, the addition of a DC Link Choke will be required to meet the harmonic
level indicated on Page 4-3.
Amps
MicroCubicleTM
380 - 440 V
Line Filter
Const Torque
DC Link Choke
Const Torque
29
40
44
58
MV3058A4A1
MV3071A4A1
MV3ACL022A4
MV3ACL030A4
MV3DCL022A4
MV3DCL030A4
37
50
71
MV3086A4A1
MV3ACL037A4
MV3DCL037A4
45
60
86
MV3105A4A1
MV3ACL045A4
MV3DCL045A4
55
74
105
MV3140A4A1
MV3ACL055A4
MV3DCL055A4
75
101
140
MV3168A4A1
MV3ACL075A4
MV3DCL075A4
kW
Rating at 400 V
HP
22
30
90
121
168
MV3204A4A1
MV3ACL090A4
MV3DCL090A4
110
147
204
MV3244A4A1
MV3ACL110A4
MV3DCL110A4
132
177
244
MV3292A4A1
MV3ACL132A4
MV3DCL132A4
160
214
292
MV3364A4A1
MV3ACL160A4
MV3DCL160A4
200
268
364
MV3449A4A1
MV3ACL200A4
MV3DCL200A4
250
355
449
MV3503A4A1
MV3ACL250A4
MV3DCL250A4
Rating at 690 V
kW
HP
Amps
575 - 690 V
45
60
50
MV3062A6A1
MV3ACL045A7
MV3DCL045A7
55
74
61
MV3077A6A1
MV3ACL055A7
MV3DCL055A7
75
101
82
MV3099A6A1
MV3ACL075A7
MV3DCL075A7
90
121
98
MV3125A6A1
MV3ACL090A7
MV3DCL090A7
110
147
119
MV3144A6A1
MV3ACL110A7
MV3DCL110A7
132
177
142
MV3192A6A1
MV3ACL132A7
MV3DCL132A7
160
214
170
MV3242A6A1
MV3ACL160A7
MV3DCL160A7
200
268
211
MV3289A6A1
MV3ACL200A7
MV3DCL200A7
250
335
260
MV3336A6A1
MV3ACL250A7
MV3DCL250A7
280
375
292
MV3382A6A1
MV3ACL280A7
MV3DCL280A7
Issue (08/00)
Page 4-5
4. Extended Applications
4.1.3
ALSPA MV3000
For a 12 Pulse configuration, additional items will be required to meet the harmonic level indicated on Page
4-3.
Rating at 400 V
kW
HP
Amps
MicroCubicleTM
380 - 440 V
12 Pulse Unit
Interbridge Tformer
Variable Torque
12 P Transformer*
Variable Torque
30
37
40
50
58
71
MV3058A4A1
MV3071A4A1
N/A
N/A
N/A
N/A
N/A
N/A
45
60
86
MV3086A4A1
MV3R140A6A1
MV3IBTA045A4
MV3TPT045zppp/aaa
55
74
105
MV3105A4A1
MV3R140A6A1
MV3IBTA055A4
MV3TPT055zppp/aaa
75
101
140
MV3140A4A1
MV3R140A6A1
MV3IBTA075A4
MV3TPT075zppp/aaa
90
121
168
MV3168A4A1
MV3R364A6A1
MV3IBTA090A4
MV3TPT090zppp/aaa
110
147
204
MV3204A4A1
MV3R364A6A1
MV3IBTA110A4
MV3TPT110zppp/aaa
132
177
244
MV3244A4A1
MV3R364A6A1
MV3IBTA132A4
MV3TPT132zppp/aaa
160
214
292
MV3292A4A1
MV3R364A6A1
MV3IBTA160A4
MV3TPT160zppp/aaa
200
268
364
MV3364A4A1
MV3R364A6A1
MV3IBTA200A4
MV3TPT200zppp/aaa
250
335
449
MV3449A4A1
TBA
MV3IBTA250A4
MV3TPT250zppp/aaa
280
375
503
MV3503A4A1
TBA
MV3IBTA280A4
MV3TPT280zppp/aaa
Rating at 690 V
kW
HP
Amps
575 - 690 V
55
74
61
MV3062A6A1
MV3R140A6A1
MV3IBTA055A7
MV3TPT055zttt/ddd
75
101
82
MV3077A6A1
MV3R140A6A1
MV3IBTA075A7
MV3TPT075zttt/ddd
90
121
98
MV3099A6A1
MV3R140A6A1
MV3IBTA090A7
MV3TPT090zttt/ddd
110
147
119
MV3125A6A1
MV3R364A6A1
MV3IBTA110A7
MV3TPT110zttt/ddd
132
177
142
MV3144A6A1
MV3R364A6A1
MV3IBTA132A7
MV3TPT132zttt/ddd
160
214
170
MV3192A6A1
MV3R364A6A1
MV3IBTA160A7
MV3TPT160zttt/ddd
200
268
211
MV3242A6A1
MV3R364A6A1
MV3IBTA200A7
MV3TPT200zttt/ddd
250
335
260
MV3289A6A1
TBA
MV3IBTA250A7
MV3TPT250zttt/ddd
280
375
291
MV3336A6A1
TBA
MV3IBTA280A7
MV3TPT280zttt/ddd
315
422
327
MV3382A6A1
TBA
MV3IBTA315A7
MV3TPT315zttt/ddd
Transformer
Enclosure Type
Notes:
1.
Input Line Filter is not required if the drive is supplied from a dedicated 12 Pulse Supply Transformer.
2.
Where a number of drives are supplied from one common 12 pulse transformer, then each drive must
have a line filter. Since there are two input bridges in this configuration, two line filters are required. To
allow for imbalance, each filter should be rated at 55% of the total drive rating.
Page 4-6
Issue (08/00)
ALSPA MV3000
4.1.4
4. Extended Applications
For a 12 Pulse configuration, additional items will be required to meet the harmonic level indicated on Page
4-3.
Rating at 400 V
MicroCubicleTM
12 Pulse Unit
Interbridge Tformer
12 P Transformer*
Const Torque
Const Torque
N/A
N/A
kW
HP
Amps
380 - 440 V
22
29
44
MV3058A4A1
30
40
58
MV3071A4A1
N/A
N/A
N/A
37
50
71
MV3086A4A1
MV3R140A6A1
MV3IBTA037A4
MV3TPT037zppp/aaa
45
60
86
MV3105A4A1
MV3R140A6A1
MV3IBTA045A4
MV3TPT045zppp/aaa
55
74
105
MV3140A4A1
MV3R140A6A1
MV3IBTA055A4
MV3TPT055zppp/aaa
75
101
140
MV3168A4A1
MV3R364A6A1
MV3IBTA075A4
MV3TPT075zppp/aaa
90
121
168
MV3204A4A1
MV3R364A6A1
MV3IBTA090A4
MV3TPT090zppp/aaa
110
147
204
MV3244A4A1
MV3R364A6A1
MV3IBTA110A4
MV3TPT110zppp/aaa
132
177
244
MV3292A4A1
MV3R364A6A1
MV3IBTA132A4
MV3TPT132zppp/aaa
160
214
292
MV3364A4A1
MV3R364A6A1
MV3IBTA160A4
MV3TPT160zppp/aaa
200
268
364
MV3449A4A1
TBA
MV3IBTA200A4
MV3TPT200zppp/aaa
250
355
449
MV3503A4A1
TBA
MV3IBTA250A4
MV3TPT250zppp/aaa
N/A
Rating at 690 V
kW
HP
Amps
575 - 690 V
45
60
50
MV3062A6A1
MV3R140A6A1
MV3IBTA045A7
MV3TPT045zttt/ddd
55
74
61
MV3077A6A1
MV3R140A6A1
MV3IBTA055A7
MV3TPT055zttt/ddd
75
101
82
MV3099A6A1
MV3R140A6A1
MV3IBTA075A7
MV3TPT075zttt/ddd
90
121
98
MV3125A6A1
MV3R364A6A1
MV3IBTA090A7
MV3TPT090zttt/ddd
110
147
119
MV3144A6A1
MV3R364A6A1
MV3IBTA110A7
MV3TPT110zttt/ddd
132
177
142
MV3192A6A1
MV3R364A6A1
MV3IBTA132A7
MV3TPT132zttt/ddd
160
214
170
MV3242A6A1
MV3R364A6A1
MV3IBTA160A7
MV3TPT160zttt/ddd
200
268
211
MV3289A6A1
TBA
MV3IBTA200A7
MV3TPT200zttt/ddd
250
335
260
MV3336A6A1
TBA
MV3IBTA250A7
MV3TPT250zttt/ddd
280
375
292
MV3382A6A1
TBA
MV3IBTA280A7
MV3TPT280zttt/ddd
Transformer
Enclosure Type
Notes:
1.
Input Line Filter is not required if the drive is supplied from a dedicated 12 Pulse Supply Transformer.
2.
Where a number of drives are supplied from one common 12 pulse transformer, then each drive must
have a line filter. Since there are two input bridges in this configuration, two line filters are required. To
allow for imbalance, each filter should be rated at 55% of the total drive rating.
Issue (08/00)
Page 4-7
4. Extended Applications
4.1.5
ALSPA MV3000
For 6 Pulse Enhanced configuration, the addition of a DC Link Choke will be required to meet the harmonic
level indicated on Page 4-3.
Amps
MicroCubicleTM
460 - 525 V
Line Filter
Variable Torque
DC Link Choke
Variable Torque
40
50
52
65
MV3052A5A1
MV3065A5A1
MV3ACL040B5
MV3ACL050B5
MV3DCL040B5
MV3DCL050B5
45
60
77
MV3077A5A1
MV3ACL060B5
MV3DCL060B5
56
75
96
MV3096A5A1
MV3ACL075B5
MV3DCL075B5
75
100
124
MV3124A5A1
MV3ACL100B5
MV3DCL100B5
93
125
156
MV3156A5A1
MV3ACL125B5
MV3DCL125B5
112
150
180
MV3180A5A1
MV3ACL150B5
MV3DCL150B5
149
200
240
MV3240A5A1
MV3ACL200B5
MV3DCL200B5
187
250
302
MV3302A5A1
MV3ACL250B5
MV3DCL250B5
224
300
361
MV3361A5A1
MV3ACL300B5
MV3DCL300B5
261
350
414
MV3414A5A1
MV3ACL350B5
MV3DCL350B5
298
400
477
MV3477A5A1
MV3ACL400B5
MV3DCL400B5
kW
Rating at 480 V
HP
30
37
Rating at 600 V
kW
HP
Amps
575 - 690 V
45
60
62
MV3062A6A1
MV3ACL060B6
MV3DCL060B6
56
75
77
MV3077A6A1
MV3ACL075B6
MV3DCL075B6
75
100
99
MV3099A6A1
MV3ACL100B6
MV3DCL100B6
93
125
125
MV3125A6A1
MV3ACL125B6
MV3DCL125B6
112
150
144
MV3144A6A1
MV3ACL150B6
MV3DCL150B6
149
200
192
MV3192A6A1
MV3ACL200B6
MV3DCL200B6
187
250
242
MV3242A6A1
MV3ACL250B6
MV3DCL250B6
224
300
289
MV3289A6A1
MV3ACL300B6
MV3DCL300B6
261
350
336
MV3336A6A1
MV3ACL350B6
MV3DCL350B6
298
400
382
MV3382A6A1
MV3ACL400B6
MV3DCL400B6
Page 4-8
Issue (08/00)
ALSPA MV3000
4.1.6
4. Extended Applications
For 6 Pulse Enhanced configuration, the addition of a DC Link Choke will be required to meet the harmonic
level indicated on Page 4-3.
Amps
MicroCubicleTM
460 - 525 V
Line Filter
Const Torque
DC Link Choke
Const Torque
30
40
40
52
MV3052A5A1
MV3065A5A1
MV3ACL030B5
MV3ACL040B5
MV3DCL030B5
MV3DCL040B5
37
50
65
MV3077A5A1
MV3ACL050B5
MV3DCL050B5
45
60
77
MV3096A5A1
MV3ACL060B5
MV3DCL060B5
kW
Rating at 480 V
HP
22
30
56
75
96
MV3124A5A1
MV3ACL075B5
MV3DCL075B5
75
100
124
MV3156A5A1
MV3ACL100B5
MV3DCL100B5
93
125
156
MV3180A5A1
MV3ACL125B5
MV3DCL125B5
112
150
180
MV3240A5A1
MV3ACL150B5
MV3DCL150B5
149
200
240
MV3302A5A1
MV3ACL200B5
MV3DCL200B5
187
250
302
MV3361A5A1
MV3ACL250B5
MV3DCL250B5
224
300
361
MV3414A5A1
MV3ACL300B5
MV3DCL300B5
261
350
414
MV3477A5A1
MV3ACL350B5
MV3DCL350B5
Rating at 600 V
kW
HP
Amps
575 - 690 V
37
50
52
MV3062A6A1
MV3ACL050B6
MV3DCL050B6
45
60
62
MV3077A6A1
MV3ACL060B6
MV3DCL060B6
56
75
77
MV3099A6A1
MV3ACL075B6
MV3DCL075B6
75
100
99
MV3125A6A1
MV3ACL100B6
MV3DCL100B6
93
125
125
MV3144A6A1
MV3ACL125B6
MV3DCL125B6
112
150
144
MV3192A6A1
MV3ACL150B6
MV3DCL150B6
149
200
192
MV3242A6A1
MV3ACL200B6
MV3DCL200B6
187
250
242
MV3289A6A1
MV3ACL250B6
MV3DCL250B6
224
300
289
MV3336A6A1
MV3ACL300B6
MV3DCL300B6
Issue (08/00)
Page 4-9
4. Extended Applications
4.1.7
ALSPA MV3000
For a 12 Pulse configuration, additional items will be required to meet the harmonic level indicated on Page
4-3.
Rating at 480 V
kW
HP
Amps
MicroCubicleTM
460 - 525 V
12 Pulse Unit
Interbridge Tformer
Variable Torque
12 P Transformer*
Variable Torque
30
37
40
50
52
65
MV3052A5A1
MV3065A5A1
N/A
N/A
N/A
N/A
N/A
N/A
45
60
77
MV3077A5A1
MV3R140A6A1
MV3IBTA060A5
MV3TPT060zqqq/bbb
56
75
96
MV3096A5A1
MV3R140A6A1
MV3IBTA075A5
MV3TPT075zqqq/bbb
75
100
124
MV3124A5A1
MV3R140A6A1
MV3IBTA100A5
MV3TPT100zqqq/bbb
93
125
156
MV3156A5A1
MV3R364A6A1
MV3IBTA125A5
MV3TPT125zqqq/bbb
112
150
180
MV3180A5A1
MV3R364A6A1
MV3IBTA150A5
MV3TPT150zqqq/bbb
149
200
240
MV3240A5A1
MV3R364A6A1
MV3IBTA200A5
MV3TPT200zqqq/bbb
187
250
302
MV3302A5A1
MV3R364A6A1
MV3IBTA250A5
MV3TPT250zqqq/bbb
224
300
361
MV3361A5A1
TBA
MV3IBTA300A5
MV3TPT300zqqq/bbb
261
350
414
MV3414A5A1
TBA
MV3IBTA350A5
MV3TPT350zqqq/bbb
298
400
477
MV3477A5A1
TBA
MV3IBTA400A5
MV3TPT400zqqq/bbb
Rating at 600 V
kW
HP
Amps
575 - 690 V
45
60
62
MV3062A6A1
MV3R140A6A1
MV3IBTA060A6
MV3TPT060zrrr/ccc
56
75
77
MV3077A6A1
MV3R140A6A1
MV3IBTA075A6
MV3TPT075zrrr/ccc
75
100
99
MV3099A6A1
MV3R140A6A1
MV3IBTA100A6
MV3TPT100zrrr/ccc
93
125
125
MV3125A6A1
MV3R364A6A1
MV3IBTA125A6
MV3TPT125zrrr/ccc
112
150
144
MV3144A6A1
MV3R364A6A1
MV3IBTA150A6
MV3TPT150zrrr/ccc
149
200
192
MV3192A6A1
MV3R364A6A1
MV3IBTA200A6
MV3TPT200zrrr/ccc
187
250
242
MV3242A6A1
MV3R364A6A1
MV3IBTA250A6
MV3TPT250zrrr/ccc
224
300
289
MV3289A6A1
TBA
MV3IBTA300A6
MV3TPT300zrrr/ccc
261
350
336
MV3336A6A1
TBA
MV3IBTA350A6
MV3TPT350zrrr/ccc
Transformer
Enclosure Type
Notes:
1.
Input Line Filter is not required if the drive is supplied from a dedicated 12 Pulse Supply Transformer.
2.
Where a number of drives are supplied from one common 12 pulse transformer, then each drive must
have a line filter. Since there are two input bridges in this configuration, two line filters are required. To
allow for imbalance, each filter should be rated at 55% of the total drive rating.
Page 4-10
Issue (08/00)
ALSPA MV3000
4.1.8
4. Extended Applications
For a 12 Pulse configuration, additional items will be required to meet the harmonic level indicated on Page
4-3.
Rating at 480 V
MicroCubicleTM
Interbridge Tformer
12 P Transformer
Const Torque
Const Torque
N/A
N/A
N/A
MV3065A5A1
N/A
N/A
N/A
65
MV3077A5A1
MV3R140A6A1
MV3IBTA050A5
MV3TPT050zqqq/bbb
77
MV3096A5A1
MV3R140A6A1
MV3IBTA060A5
MV3TPT060zqqq/bbb
75
96
MV3124A5A1
MV3R140A6A1
MV3IBTA075A5
MV3TPT075zqqq/bbb
75
100
124
MV3156A5A1
MV3R364A6A1
MV3IBTA100A5
MV3TPT100zqqq/bbb
93
125
156
MV3180A5A1
MV3R364A6A1
MV3IBTA125A5
MV3TPT125zqqq/bbb
112
150
180
MV3240A5A1
MV3R364A6A1
MV3IBTA150A5
MV3TPT150zqqq/bbb
149
200
240
MV3302A5A1
MV3R364A6A1
MV3IBTA200A5
MV3TPT200zqqq/bbb
187
250
302
MV3361A5A1
TBA
MV3IBTA250A5
MV3TPT250zqqq/bbb
224
300
361
MV3414A5A1
TBA
MV3IBTA300A5
MV3TPT300zqqq/bbb
261
350
414
MV3477A5A1
TBA
MV3IBTA350A5
MV3TPT350zqqq/bbb
kW
HP
Amps
460 - 525 V
22
30
40
MV3052A5A1
30
40
52
37
50
45
60
56
12 Pulse Unit
Rating at 600 V
kW
HP
Amps
575 - 690 V
37
50
52
MV3062A6A1
MV3R140A6A1
MV3IBTA050A6
MV3TPT050zrrr/ccc
45
60
62
MV3077A6A1
MV3R140A6A1
MV3IBTA060A6
MV3TPT060zrrr/ccc
56
75
77
MV3099A6A1
MV3R140A6A1
MV3IBTA075A6
MV3TPT075zrrr/ccc
75
100
99
MV3125A6A1
MV3R364A6A1
MV3IBTA100A6
MV3TPT100zrrr/ccc
93
125
125
MV3144A6A1
MV3R364A6A1
MV3IBTA125A6
MV3TPT125zrrr/ccc
112
150
144
MV3192A6A1
MV3R364A6A1
MV3IBTA150A6
MV3TPT150zrrr/ccc
149
200
192
MV3242A6A1
MV3R364A6A1
MV3IBTA200A6
MV3TPT200zrrr/ccc
187
250
242
MV3289A6A1
TBA
MV3IBTA250A6
MV3TPT250zrrr/ccc
224
300
289
MV3336A6A1
TBA
MV3IBTA300A6
MV3TPT300zrrr/ccc
Transformer
Enclosure Type
Notes:
1.
Input Line Filter is not required if the drive is supplied from a dedicated 12 Pulse Supply Transformer.
2.
Where a number of drives are supplied from one common 12 pulse transformer, then each drive must
have a line filter. Since there are two input bridges in this configuration, two line filters are required. To
allow for imbalance, each filter should be rated at 55% of the total drive rating.
Issue (08/00)
Page 4-11
4. Extended Applications
4.2
ALSPA MV3000
Dynamic Braking
A Dynamic Braking Unit is used in conjunction with an externally mounted braking resistor to dissipate surplus
kinetic energy regenerated back into the inverter during deceleration or overhauling.
ALSPA MV3000
DB Unit
Nominal
Voltage
Order Code
MV3DB045S5
Insert DB unit.
Nominal Power
18 seconds
Nominal
ON time
Current
Minimum
Maximum
DB resistor
Volts
Amps
kW
Ohms
Ohms
Order Code
Ohms
400
45
28.1
13.61
16.6
MV3DBR045S4
13.6
MV3DB092S5
400
92
57
6.77
8.21
MV3DBR092S4
6.8
MV3DB247S5
400
247
153.3
1.58
3.05
MV3DBR247S4
2.6
TBA
400
TBA
TBA
TBA
TBA
TBA
TBA
MV3DB045S5
480
38
28.3
15.31
23.6
MV3DBR038S5
15.3
MV3DB092S5
480
76
56.7
7.62
11.8
MV3DBR076S5
7.6
MV3DB247S5
480
231
171.7
1.78
3.89
MV3DBR231S5
3.3
TBA
480
TBA
TBA
TBA
TBA
TBA
TBA
MV3DB061S6
600/690
61
56.7
11
20.3
MV3DBR061S6
11.0
MV3DB185S6
600/690
185
171.7
3.7
6.71
MV3DBR185S6
5.2
TBA
600/690
TBA
TBA
TBA
TBA
TBA
TBA
18
18
18
MV3DB045S
MV3DB045S
16
MV3DB092S5
14
MV3DB247S5
12
10
8
6
4
400V operation
400 V Operation
2
0
16
MV3DB092S5
14
MV3DB247S5
12
10
8
6
4
480 V Operation
480V operation
2
0
25
50
75
100
125
150
2
175
200
16
MV3DB061S6
14
MV3DB185S6
12
10
8
6
4
690V operation
690 V Operation
2
0
25
50
75
100
125
150
175
200
25
50
75
100
125
150
175
Stopping times from 1500 r/min at various supply voltages using standard braking resistors tabled
Page 4-12
Issue (08/00)
200
ALSPA MV3000
4. Extended Applications
Frame
Size
DB Unit
DB Resistor
(Maximum Duty)
Resistance
Ohms
MV3058A4A1
MV3DB045S5
MV3DBR045S4
13.6
MV3071A4A1
MV3DB045S5
MV3DBR045S4
13.6
MV3086A4A1
MV3DB092S5
MV3DBR092S4
6.8
MV3105A4A1
MV3DB092S5
MV3DBR092S4
6.8
MV3140A4A1
MV3DB092S5
MV3DBR092S4
6.8
MV3168A4A1
MV3DB247S5
MV3DBR247S4
2.6
MV3204A4A1
MV3DB247S5
MV3DBR247S4
2.6
MV3244A4A1
MV3DB247S5
MV3DBR247S4
2.6
MV3292A4A1
MV3DB247S5
MV3DBR247S4
2.6
MV3364A4A1
MV3DB247S5
MV3DBR247S4
2.6
MV3449A4A1
TBA
TBA
TBA
MV3503A4A1
TBA
TBA
TBA
MV3052A5A1
MV3DB045S5
MV3DBR038S5
15.3
MV3065A5A1
MV3DB045S5
MV3DBR038S5
15.3
MV3077A5A1
MV3DB092S5
MV3DBR076S5
7.6
MV3096A5A1
MV3DB092S5
MV3DBR076S5
7.6
MV3124A5A1
MV3DB092S5
MV3DBR076S5
7.6
MV3156A5A1
MV3DB247S5
MV3DBR231S5
3.3
MV3180A5A1
MV3DB247S5
MV3DBR231S5
3.3
MV3240A5A1
MV3DB247S5
MV3DBR231S5
3.3
MV3302A5A1
MV3DB247S5
MV3DBR231S5
3.3
MV3361A5A1
TBA
TBA
TBA
MV3414A5A1
TBA
TBA
TBA
MV3477A5A1
600/690 V
TBA
TBA
TBA
MV3062A6A1
MV3DB061S6
MV3DBR061S6
11.0
MV3077A6A1
MV3DB061S6
MV3DBR061S6
11.0
MV3099A6A1
MV3DB061S6
MV3DBR061S6
11.0
MV3125A6A1
MV3DB185S6
MV3DBR185S6
5.2
MV3144A6A1
MV3DB185S6
MV3DBR185S6
5.2
MV3192A6A1
MV3DB185S6
MV3DBR185S6
5.2
MV3242A6A1
MV3DB185S6
MV3DBR185S6
5.2
MV3289A6A1
TBA
TBA
TBA
MV3336A6A1
TBA
TBA
TBA
MV3382A6A1
TBA
TBA
TBA
400 V
480 V
Issue (08/00)
Page 4-13
4. Extended Applications
ALSPA MV3000
PP
Where
AC Voltage
VD B
400
480
600/690
732
846
1118
V DB = DB Operating Voltage
PP = Peak pow er during braking
Alternatively a lower value of resistor may be used, but not below the specified minimum value.
91.2V 2DBt1
JN2(N2 - N1)
=
=
=
=
=
V DB
J
t1
N1
N2
DB Operating Voltage
system inertia (kgm 2)
braking tim e (seconds)
initial speed r/m in
final speed r/m in
JN2(N2 - N1)
91.2 t 1
P eak
R e ge nerativ e
P ow er
R e pe at
Ave rag e
R e ge nerativ e
P ow er
t1
Derating factor
0.8
0.6
0.4
t2
0.2
20
40
60
80
100
120
140
160
180
200
Duration of braking, t1
The calculated resistor value should have a peak power capability equal to the power during braking and be
able to withstand this power for the braking time t1. The calculated resistor value should also have an
average power capability given by:
Long term average power = Average power during braking x t1 / t3
The dynamic braking unit has a 10% duty factor, which corresponds to an 18 second ON time in any 180
second period. If the braking ON time is longer than 18 seconds, the Peak Power must be derated by
applying the derating factor indicated by the curve above.
Page 4-14
Issue (08/00)
ALSPA MV3000
4.3
4. Extended Applications
EMC filters and ferrites will assist the inverter installation to meet EMC emission requirements. This generally
applies when operating in non-industrial environments or when the inverter is installed in the proximity of
sensitive equipment.
For 6 Pulse configurations, one EMC filter plus one motor cable ferrite ring will be required to meet EMC
emission requirements.
MicroCubicleTM
EMC Filter
EMC Ferrite
380 - 440 V
Mains Supply
MV3058A4A1
MV3FLT083A4A1
MV3FLT140B6A1
MV3071A4A1
MV3FLT083A4A1
MV3FLT140B6A1
MV3086A4A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3105A4A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3140A4A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3168A4A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3204A4A1
MV3FLT250A5X1
MV3FLT566B6A1
MV3244A4A1
MV3FLT250A5X1
MV3FLT566B6A1
MV3292A4A1
MV3FLT400A5X1
MV3FLT566B6A1
MV3364A4A1
MV3FLT400A5X1
EMC
Filter
Line
Filter
MV3FLT566B6A1
MV3449A4A1
MV3FLT566B6A1
MV3503A4A1
MV3FLT566B6A1
Drive
Data
Manager
ALSPA
MV3000
Inverter
440 - 525 V
MV3052A5A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3065A5A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3077A5A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3096A5A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3124A5A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3156A5A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3180A5A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3240A5A1
MV3FLT250A6X1
MV3FLT566B6A1
MV3302A5A1
MV3FLT320A6X1
MV3FLT566B6A1
Ferrite Ring
MV3361A5A1
MV3FLT566B6A1
MV3414A5A1
MV3FLT566B6A1
MV3477A5A1
MV3FLT566B6A1
Ferrite
Ring
To Motor
6 Pulse
575 - 690 V
MV3062A6A1
MV3FLT150A6X1
MV3FLT140B6A1
MV3077A6A1
MV3FLT150A6X1
MV3FLT140B6A1
MV3099A6A1
MV3FLT150A6X1
MV3FLT140B6A1
MV3125A6A1
MV3FLT150A6X1
MV3FLT566B6A1
MV3144A6A1
MV3FLT150A6X1
MV3FLT566B6A1
MV3192A6A1
MV3FLT250A6X1
MV3FLT566B6A1
MV3242A6A1
MV3FLT250A6X1
MV3FLT566B6A1
MV3289A6A1
MV3FLT320A6X1
MV3FLT566B6A1
MV3289A6A1
MV3FLT566B6A1
MV3336A6A1
MV3FLT566B6A1
MV3382A6A1
MV3FLT566B6A1
Issue (08/00)
Page 4-15
4. Extended Applications
4.4
ALSPA MV3000
EMC filters and ferrites will assist the inverter installation to meet EMC emission requirements. This generally
applies when operating in non-industrial environments or when the inverter is installed in the proximity of
sensitive equipment.
For 12 Pulse drive configurations, two x EMC filters (one per input rectifier) plus one motor cable ferrite ring
will be required to meet EMC emission requirements.
MicroCubicleTM
EMC Filter
EMC Ferrite
Qty Reqd = 2
380 - 440 V
MV3058A4A1
N/A
N/A
MV3071A4A1
N/A
N/A
MV3086A4A1
MV3FLT083A4A1
MV3FLT140B6A1
MV3105A4A1
MV3FLT083A4A1
MV3FLT140B6A1
MV3140A4A1
MV3FLT083A4A1
MV3FLT140B6A1
MV3168A4A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3204A4A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3244A4A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3292A4A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3364A4A1
MV3FLT250A5X1
MV3FLT566B6A1
MV3449A4A1
MV3FLT250A5X1
MV3FLT566B6A1
MV3503A4A1
MV3FLT400A5X1
MV3FLT566B6A1
MV3052A5A1
N/A
N/A
MV3065A5A1
N/A
N/A
MV3077A5A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3096A5A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3124A5A1
MV3FLT180A5A1
MV3FLT140B6A1
MV3156A5A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3180A5A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3240A5A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3302A5A1
MV3FLT180A5A1
MV3FLT566B6A1
MV3361A5A1
MV3FLT250A6X1
MV3FLT566B6A1
MV3414A5A1
MV3FLT250A6X1
MV3FLT566B6A1
MV3477A5A1
MV3FLT320A6X1
MV3FLT566B6A1
MV3062A6A1
MV3FLT150A6X1
MV3FLT140B6A1
MV3077A6A1
MV3FLT150A6X1
MV3FLT140B6A1
440 - 525 V
Mains Supply
12 Pulse
Transformer
EMC
Filters
Drive
Data
Manager
12
Pulse
Unit
ALSPA
MV3000
Inverter
Interbridge
Reactor
Ferrite
Ring
To Motor
575 - 690 V
MV3099A6A1
MV3FLT150A6X1
MV3FLT140B6A1
MV3125A6A1
MV3FLT150A6X1
MV3FLT566B6A1
Ferrite Ring
MV3144A6A1
MV3FLT150A6X1
MV3FLT566B6A1
MV3192A6A1
MV3FLT150A6X1
MV3FLT566B6A1
MV3242A6A1
MV3FLT150A6X1
MV3FLT566B6A1
MV3289A6A1
MV3FLT250A6X1
MV3FLT566B6A1
MV3289A6A1
MV3FLT250A6X1
MV3FLT566B6A1
MV3336A6A1
MV3FLT250A6X1
MV3FLT566B6A1
MV3382A6A1
MV3FLT250A6X1
MV3FLT566B6A1
Page 4-16
12 Pulse
Issue (08/00)
ALSPA MV3000
4. Extended Applications
4.5
Fieldbus Communication
4.5.1
WorldFIP Fieldbus
The WorldFIP Fieldbus board may be retrofitted on all ALSPA MV3000 inverter drives. Boards providing a
dual redundant WorldFIP Fieldbus are available for 1 Mbit/s and 2.5 Mbit/s operation.
FIP bus arbiter functionality is not supported, and must be provided by another device on the FIP network.
The FIP board is parameterised and controlled using the same parameter interface as for the host drive unit.
The board may be configured over the drives serial link, but not over the FIP link itself.
SPECIFICATION
Fieldbus
Dual redundant FIP Fieldbus: Options
- 1 Mbit/s
- 2.5 Mbit/s
Protocol
WorldFIP Profile A, IEC 1158-2 and FIP, NFC 46-603/4
Data Refresh Rate
Two drive data refresh rates
- fast scan : 10 mS
- slow scan : 100 mS
Environment
Storage
Issue (08/00)
Page 4-17
4. Extended Applications
4.5.2
ALSPA MV3000
PROFIBUS Fieldbus
The PROFIBUS Fieldbus Coupler may be retrofitted on all ALSPA MV3000 inverter drives and allows
connection to a PROFIBUS-DP network.
The PROFIBUS board is parameterised and controlled using the same parameter interface as for the host
drive unit. The board may be configured over the drives serial link, but not over the PROFIBUS link itself.
SPECIFICATION
Fieldbus communication rates:
- 9.6K, 19.2K, 93.75K, 187.5K, 500K, 1.5M bit/s
Protocol
PROFIBUS-DP Field bus protocol to DIN 19245
Data Refresh Rate
10 mS
Data Volume
Cyclic Channel Receive:
Power Supply
Internal 5V supply. Current consumption : 315 mA.
Environment
Storage
Page 4-18
Issue (08/00)
ALSPA MV3000
4. Extended Applications
4.6
Programming
4.6.1
!"#$
The Drive Data ManagerTM is the keypad programming tool for ALSPA MV3000.
The ergonomically designed unit features:
parameter editing
4 line backlit display
wide angle, magnified view
multilingual text display
telephone style navigation key
- menu and parameter access
numeric keys for fast data entry and shortcut parameter access
versatile to use:
- mounts directly on drive unit
- mounted on enclosure
- handheld
parameter storage for faster multi-drive commissioning
- upload/download to/from drive
on-line HELP key for extra parameter information
diagnostic help and history record viewing
optional cable and IP65 seal for enclosure door mounting
Order Codes:
MVS3000-4001
MVS3001-4001
Issue (08/00)
Page 4-19
4. Extended Applications
4.6.2
ALSPA MV3000
ALSPA Drive Coach is a PC based programming tool providing a superior programming and diagnostic
viewing environment.
Facilities include:
Order Codes:
MVS3004-4001
GDS1009-4001
PC Programming Lead 3m
Page 4-20
Issue (08/00)
ALSPA MV3000
4.6.3
4. Extended Applications
Demonstration Briefcase
A self-contained demonstration briefcase simulating the complete functionality of the ALSPA MV3000.
Comprising:
Fault simulation
Diagnostics
The unit allows training of engineering staff and machine operators before actual equipment hands-on.
Further, the unit allows development of plant programs or SCADA simulations in a safe development
environment.
Order Codes
MV3000 CASE DEMO/E
MV3000 CASE DEMO/F
MV3000 CASE DEMO/D
Issue (08/00)
Page 4-21
4. Extended Applications
ALSPA MV3000
4.7
4.7.1
Motor Cables
To avoid EMC problems, the motor cable should be screened (e.g. NYCWY according to VDE 0271 or steel
wire armoured) or fully enclosed in metallic trunking. The screen or metallic trunking must be continuous
throughout its length and be connected directly to both the drive cabinet and motor.
Outside the drive cabinet the motor cable must be segregated from other cables by at least 300mm (12in)
4.7.2
Motor Insulation
Motors with Insulation Peak Voltage Withstand ratings of 1200 V (400V motors), 1500 V (500V motors) and
2250 V (690 V motors) can be operated with ALSPA MV3000 without risk to the motor winding insulation, for
cable lengths up to 500m (1640 ft). Such motors are available from reputable manufacturers, as standard
motors up to 500 V and with an enhanced insulation system for voltages greater than 500 V up to 690 V.
For motor cable lengths greater than 500 metres, please refer to ALSTOM.
4.7.3
Encoders
When operating in closed loop flux vector control or position control, encoder feedback is required. Only
RS422A type encoders can be used with ALSPA MV3000. A marker pulse is only required when in position
control mode.
The MV3000 is equipped with power supplies suitable for two types of encoders:
1) Encoders requiring +5 V supply and producing an RS422 output
2) Encoders requiring +24 V supply and producing an RS422 output
Note: 24V differential outputs are not compatible. The pulse train must be RS422.
Encoder Resolution
For accurate speed control, a resolution not less than 1024 pulse/revolution is suggested.
The drive will allow a maximum of 64,000 pulse/revolution, however since the frequency of pulses is affected
by the maximum motor speed, the frequency of pulses must not exceed 1.5 MHz. Therefore the encoder
resolution must not exceed:
90 x 106
Required top speed (r/min)
Page 4-22
Issue (08/00)
ALSPA MV3000
5. Technical Data
5. Technical Data
5.1
TOP
VIEW
140O
max
310O
max
F
20 mm
DRAWING
NOT TO SCALE
FRONT
VIEW
Dimensions mm (in)
Weight
Size*
F (max)
Kg (lb)
170 (6.7)
350 (13.8)
600 (23.7)
60 (2.37)
110 (4.33)
156 (6.1)
27.0 (59.4)
255 (10.0)
370 (14.6)
789 (31.2)
145 (5.7)
110 (4.33)
210 (8.3)
45 (99)
430 (17.0)
420 (16.6)
873 (34.4)
320 (12.6)
110 (4.33)
355 (14)
100.5 (221.1)
485 (19.1)
450 (17.8)
1155 (45.5)
372 (14.7)
110 (4.33)
355 (13.8)
156 (344.0)
* Please refer to Section 2.2 Rating and Protection Data for correspondences between Frame Size and actual
MicroCubicleTM unit.
Issue (08/00)
Page 5-1
5. Technical Data
5.2
ALSPA MV3000
Height
mm/in
Dimensions
Width
mm/in
Depth
mm/in
400 V
MV3ACL022A4
195/7.68
180/7.09
MV3ACL030A4
195/7.68
MV3ACL037A4
Line Filter
Weight
Frame
kg/lb
Size
166/6.54
12/26.4
180/7.09
166/6.54
12/26.4
195/7.68
180/7.09
166/6.54
12/26.4
3/4
MV3ACL045A4
250/9.84
240/9.45
170/6.69
17/37.4
MV3ACL055A4
260/10.24
280/11.02
170/6.69
14/30.8
MV3ACL075A4
260/10.24
280/11.02
190/6.69
18/39.6
4/6
MV3ACL090A4
320/12.6
346/13.62
225/8.86
25/55
MV3ACL110A4
320/12.6
346/13.62
235/9.25
30/66
MV3ACL132A4
320/12.6
346/13.62
245/9.65
35/77
MV3ACL160A4
320/12.6
346/13.62
245/9.65
35/77
MV3ACL200A4
320/12.6
346/13.62
255/10.04
45/99
MV3ACL250A4
372/14.64
430/16.93
275/10.83
50/110
MV3ACL280A4
372/14.64
430/16.93
290/11.42
56/123.2
MV3ACL315A4
373/14.7
430/16.93
300/11.81
70/154
690 V
MV3ACL045A7
250/9.84
240/9.45
170/6.69
16/35.2
MV3ACL055A7
250/9.84
240/9.45
170/6.69
16/35.2
MV3ACL075A7
250/9.84
240/9.45
190/7.48
19/41.8
MV3ACL090A7
250/9.84
240/9.45
190/7.48
21/46.2
4/6
MV3ACL110A7
320/12.6
346/13.62
235/9.25
35/77
MV3ACL132A7
320/12.6
346/13.62
245/9.65
35/77
MV3ACL160A7
320/12.6
346/13.62
235/9.25
35/77
MV3ACL200A7
320/12.6
346/13.62
255/10.04
50/110
MV3ACL250A7
372/14.65
430/16.93
275/10.83
50/110
MV3ACL280A7
372/14.65
430/16.93
290/11.42
56/123.2
MV3ACL315A7
375/14.8
430/16.93
300/11.81
70/154
Part No.
Depth
Height
Width
Page 5-2
Issue (08/00)
ALSPA MV3000
5.3
5. Technical Data
DC Link Choke
Part No.
Dimensions
Weight
Losses
kg / lb
Watts
Height
Width
Depth
mm/in
mm/in
mm/in
MV3DCL022A4
148/5.8
137/5.4
150/5.9
9/19.8
40
MV3DCL030A4
180/7.1
170/6.7
150/5.9
12.5/27.5
50
MV3DCL037A4
180/7.1
170/6.7
175/6.9
16/35.2
55
MV3DCL045A4
220/8.7
220/8.7
145/5.7
17/37.4
70
MV3DCL055A4
220/8.7
220/8.7
215/8.5
20/44
80
MV3DCL075A4
220/8.7
220/8.7
230/9.1
24/52.8
95
MV3DCL090A4
230/9.1
220/8.7
230/9.1
24.5/53.9
110
MV3DCL110A4
245/9.6
240/9.4
265/10.4
34.5/75.9
120
MV3DCL132A4
245/9.6
240/9.4
290/11.4
43/94.6
125
MV3DCL160A4
290/11.4
286/11.3
285/11.2
51/112
140
MV3DCL200A4
290/11.4
286/11.3
310/12.2
60/132
160
MV3DCL250A4
300/11.8
286/11.3
320/12.6
68/150
180
MV3DCL280A4
420/16.5
280/11.0
320/12.6
60/132
300
MV3DCL315A4
420/16.5
280/11.0
330/13.0
66/145
320
MV3DCL045A7
220/8.7
220/8.7
145/5.7
16.5/36.3
75
MV3DCL055A7
220/8.7
216/8.5
170/6.7
20/44
80
MV3DCL075A7
220/8.7
220/8.7
180/7.0
24.5/53.9
100
MV3DCL090A7
220/8.7
220/8.7
230/9.1
25/55
105
MV3DCL110A7
245/9.6
240/9.4
265/10.4
35/77
120
MV3DCL132A7
245/9.6
240/9.4
290/11.4
43/94.6
125
MV3DCL160A7
290/11.4
286/11.3
285/11.2
51/112
150
MV3DCL200A7
290/11.4
286/11.3
310/12.2
61/134
165
MV3DCL250A7
300/11.8
286/11.3
320/12.6
70/154
175
MV3DCL280A7
420/16.5
280/11.0
320/12.6
60/132
300
MV3DCL315A7
420/16.5
280/11.0
330/13.0
67/147
300
400 V
690 V
Issue (08/00)
Page 5-3
5. Technical Data
5.4
ALSPA MV3000
12 Pulse Unit
Part No.
Weight
Losses
Watts
@ FLC
Airflow
16/35.2
190
100.0
26/57.2
490
100.0
Height
mm/in
Width
mm/in
Depth
mm/in
kg/lb
MV3R140A6A1
378/14.9
218/8.6
370/14.6
MV3R364A6A1
480/18.9
248/9.8
420/16.6
cfm
380 - 690 V
FS 7 - TBA
Page 5-4
Issue (08/00)
ALSPA MV3000
5.5
5. Technical Data
Height
mm/in
Dimensions
Width
mm/in
Depth
mm/in
MV3IBTA037A4
240/9.4
140/5.5
MV3IBTA045A4
240/9.4
MV3IBTA055A4
240/9.4
MV3IBTA075A4
MV3IBTA090A4
Interbridge
Transformer
Weight
Losses
Kg/lb
Watts
250/9.8
19/41.8
90
155/6.1
250/9.8
21/46.2
100
155/6.1
250/9.8
25/55.0
100
260/10.2
195/7.7
270/10.6
36/79.2
130
250/9.8
290/11.4
240/9.4
45/99.0
150
MV3IBTA110A4
290/11.4
280/11.0
290/11.4
50/110
170
MV3IBTA132A4
290/11.4
290/11.4
290/11.4
55/121
190
MV3IBTA160A4
290/11.4
300/11.8
290/11.4
60/132
230
MV3IBTA200A4
300/11.8
310/12.2
290/11.4
68/149.6
250
MV3IBTA250A4
420/16.5
330/13.0
280/11.0
70/154
320
MV3IBTA280A4
420/16.5
350/13.8
280/11.0
75/165
350
MV3IBTA315A4
420/16.5
370/14.6
280/11.0
83/182.6
390
MV3IBTA037A7
240/9.4
140/5.5
250/9.8
19/41.8
90
MV3IBTA045A7
240/9.4
155/6.1
250/9.8
21/46.2
100
MV3IBTA055A7
240/9.4
155/6.1
250/9.8
25/55.0
100
MV3IBTA075A7
260/10.2
195/7.7
270/10.6
38/83.6
130
MV3IBTA090A7
250/9.8
280/11.0
240/9.4
45/99.0
150
MV3IBTA110A7
290/11.4
280/11.0
290/11.4
50/110
170
MV3IBTA132A7
290/11.4
290/11.4
290/11.4
55/121
190
MV3IBTA160A7
290/11.4
300/11.8
290/11.4
60/132
230
MV3IBTA200A7
300/11.8
310/12.2
290/11.4
68/149.6
250
MV3IBTA250A7
420/16.5
330/13.0
280/11.0
70/154
320
MV3IBTA280A7
420/16.5
350/13.8
280/11.0
75/165
350
MV3IBTA315A7
420/16.5
370/14.6
280/11.0
83/182.6
390
Part No.
380 - 440 V
690 V
Issue (08/00)
Page 5-5
5. Technical Data
5.6
ALSPA MV3000
Height
mm/in
Dimensions
Width
mm/in
Depth
mm/in
MV3IBTA050A5
240/9.4
140/5.5
MV3IBTA060A5
240/9.4
MV3IBTA075A5
240/9.4
MV3IBTA100A5
MV3IBTA125A5
Interbridge
Transformer
Weight
Losses
Kg/lb
Watts
250/9.8
19/41.8
90
155/6.1
250/9.8
21/46.2
100
155/6.1
250/9.8
36/79.2
100
260/10.2
195/7.7
270/10.6
38/83.6
130
250/9.8
290/11.4
240/9.4
45/99
150
MV3IBTA150A5
290/11.4
290/11.4
290/11.4
55/121
190
MV3IBTA200A5
290/11.4
300/11.8
290/11.4
60/132
230
MV3IBTA250A5
300/11.8
310/12.2
290/11.4
68/149.6
250
MV3IBTA300A5
420/16.5
330/13.0
280/11.0
70/154
320
MV3IBTA350A5
420/16.5
350/13.8
280/11.0
75/165
350
MV3IBTA400A5
420/16.5
370/14.6
280/11.0
83/182.6
390
MV3IBTA050A6
240/9.4
140/5.5
250/9.8
19/41.8
90
MV3IBTA060A6
240/9.4
155/6.1
250/9.8
21/46.2
100
MV3IBTA075A6
240/9.4
165/6.5
250/9.8
36/79.2
130
MV3IBTA100A6
260/10.2
195/7.7
270/10.6
38/83.6
130
MV3IBTA125A6
250/9.8
290/11.4
240/9.4
45/99
150
MV3IBTA150A6
290/11.4
290/11.4
290/11.4
55/121
190
MV3IBTA200A6
290/11.4
300/11.8
290/11.4
60/132
230
MV3IBTA250A6
300/11.8
310/12.2
290/11.4
68/149.6
250
MV3IBTA300A6
420/16.5
330/13.0
280/11.0
70/154
320
MV3IBTA350A6
420/16.5
350/13.8
280/11.0
75/165
350
MV3IBTA400A6
420/16.5
370/14.6
280/11.0
83/182.6
390
Part No.
460 525 V
600 V
Page 5-6
Issue (08/00)
ALSPA MV3000
5.7
5. Technical Data
Operating Temperature
0 - 40C
Secondary 1
Star
Storage/Transport Temp
-25 to +55/70C
Secondary 2
Delta
Ventilation
Naturally ventilated
Frequency
50 Hz
Relative Humidity
0 - 95 % non-condensing
Overload
Altitude
Type
Isolated
Accessories
T-type thermistors
5.7.1
12 Pulse Supply
Transformer
Part No. Prefix
MV3TPT037
MV3TPT045
MV3TPT055
Height
mm/in
Dimensions
Width
mm/in
Depth
mm/in
45
54
700/27.6
750/29.5
350/13.8
400/15.7
66
750/29.5
420/16.5
Primary
kVA
Weight
Losses
Kg/lb
Watts
650/25.6
650/25.6
290/638
350/770
1700
2000
650/25.6
400/880
2300
MV3TPT090
90
760/29.9
375/14.8
1020/40.2
515/1133
3200
MV3TPT090
107
760/29.9
400/15.7
1020/40.2
550/1210
3600
MV3TPT110
130
800/31.5
450/17.7
1100/43.3
615/1353
3800
MV3TPT132
156
900/35.4
450/17.7
1100/43.3
690/1518
4300
MV3TPT160
188
1000/39.4
500/19.7
1150/45.3
750/1650
4500
MV3TPT200
235
1000/39.4
550/21.7
1200/47.2
850/1870
5900
MV3TPT250
293
1100/43.3
550/21.7
1250/49.2
1100/2420
6200
MV3TPT280
328
1100/43.3
550/21.7
1300/51.2
1200/2640
6750
MV3TPT315
369
1100/43.3
650/25.6
1350/53.1
1250/2750
7500
Weight
Losses
Kg/lb
Watts
5.7.2
Dimensions
Width
mm/in
Depth
mm/in
45
54
1100/43.3
1100/43.3
600/23.6
600/23.6
1050/41.3
1050/41.3
340/748
410/902
1700
2000
66
1100/43.3
600/23.6
1050/41.3
460/1012
2300
MV3TPT090
90
1250/49.2
800/31.5
1200/47.2
575/1265
3200
MV3TPT090
107
1250/49.2
800/31.5
1200/47.2
625/1375
3600
MV3TPT110
130
1250/49.2
800/31.5
1200/47.2
690/1518
3800
MV3TPT132
156
1250/49.2
800/31.5
1200/47.2
765/1683
4300
MV3TPT160
188
1250/49.2
800/31.5
1300/51.2
825/1815
4500
MV3TPT200
235
1550/61
900/35.4
1400/55.1
1000/2200
5900
MV3TPT250
293
1550/61
900/35.4
1400/55.1
1250/2750
6200
MV3TPT280
328
1550/61
900/35.4
1500/59.1
1350/2970
6750
MV3TPT315
369
1550/61
1000/39.4
1500/59.1
1450/3190
7500
12 Pulse Supply
Transformer
Part No. Prefix
MV3TPT037
MV3TPT045
MV3TPT055
Issue (08/00)
Primary
kVA
Page 5-7
5. Technical Data
5.8
ALSPA MV3000
Height
Dimensions
Width
Depth
mm/in
mm/in
mm/in
MV3FLT083A4A1
220/8.66
329/12.9
80/3.2
4/8.8
MV3FLT150A6X1
300/11.8
160/6.3
120/4.7
6.5/14.3
MV3FLT180A5A1
300/11.8
210/8.3
120/4.7
6.5/14.3
MV3FLT250A5X1
300/11.8
230/9.1
125/4.9
7/15.4
MV3FLT250A6X1
300/11.8
230/9.1
125/4.9
7/15.4
MV3FLT320A6X1
386/15.2
260/10.2
115/4.5
10.5/23.1
MV3FLT400A5X1
386/15.2
260/10.2
115/4.5
10.5/23.1
5.9
Weight
Kg/lb
Part No:
MV3FLT140B6A1
Weight:
0.91 kg / 2 lb
52 9 (2 1")
4 9 54 7 ( 15
86.9 (3.4")
67.0 (2.6")
98.0 (3.9")
13.0 (0.51")
120.0 (4.7")
Part No:
MV3FLT566B6A1
203.0 (7.99")
226.0 (8.90")
Weight:
5.11 kg / 11.24 lb
30.0 (1.18")
84.0 (3.31")
156.8 (6.17")
144.0 (5.67")
Page 5-8
Issue (08/00)
ALSPA MV3000
5. Technical Data
5.10
63
66
76
80
* Please refer to Section 2.2 Rating and Protection Data for correspondences between Frame Size and actual
MicroCubicleTM unit.
Issue (08/00)
Page 5-9
5. Technical Data
ALSPA MV3000
Page 5-10
Issue (08/00)
ALSPA MV3000
MicroCubicleTM Spares
The following spares are available for ALSPA MV3000 MicroCubicles. Spares for DELTA based inverters
comprise complete module replacement. Please refer to the ALSPA MV3000 DELTA Buyers Guide for
details.
F
r
MicroCubicle
Control Module
Fan
Rectifier
Module
Transistor Transistor
Module
RectifierTransistor
Module
SMPS (Switch
Mode Power
Supply)
(3 off Reqd)
Precharge
Fuses
400 V
MV3058A4A1
S41Y7784/40
S41Y7786/10
S41Y7782/10
S20X4320/10
S82028/220
MV3071A4A1
S41Y7784/40
S41Y7786/10
S41Y7782/20
S20X4320/10
S82028/220
MV3086A4A1
S41Y7784/40
S98101/153
S41Y8008/30
S20X4320/10
S82028/260
MV3105A4A1
S41Y7784/40
S98101/153
S41Y8008/20
S20X4320/10
S82028/260
MV3140A4A1
S41Y7784/40
S98101/153
S41Y8008/10
S20X4320/10
S82028/260
MV3168A4A1
S41Y7784/40
SMV98101/151
S41Y7770/40
S41Y7771/30
S20X4321/20
S82028/280
MV3204A4A1
S41Y7784/40
SMV98101/151
S41Y7770/40
S41Y7771/30
S20X4321/20
S82028/280
MV3244A4A1
S41Y7784/40
SMV98101/151
S41Y7770/40
S41Y7771/20
S20X4321/20
S82028/280
MV3292A4A1
S41Y7784/40
SMV98101/151
S41Y7770/30
S41Y7771/10
S20X4321/20
S82028/280
MV3364A4A1
S41Y7784/40
SMV98101/151
S41Y7770/10
S41Y7771/70
S20X4321/20
S82028/280
MV3449A4A1
S41Y7784/40
SMV98101/151
S41Y8081/10
S41Y8082/10
S20X4321/20
S82028/280
MV3503A4A1
S41Y7784/40
SMV98101/151
S41Y8081/20
S41Y8082/20
MV3566A4A1
S82028/280
480 V
MV3052A5A1
S41Y7784/40
S41Y7786/10
S41Y7782/30
S20X4320/20
S82030/366
MV3065A5A1
S41Y7784/40
S41Y7786/10
S41Y7782/30
S20X4320/20
S82030/366
MV3077A5A1
S41Y7784/40
S98101/153
S41Y8008/40
S20X4320/20
S82028/240
MV3096A5A1
S41Y7784/40
S98101/153
S41Y8008/40
S20X4320/20
S82028/240
MV3124A5A1
S41Y7784/40
S98101/153
S41Y8008/50
S20X4320/20
S82028/240
MV3156A5A1
S41Y7784/40
SMV98101/151
S41Y7770/80
S41Y7771/50
S20X4320/20
S82028/240
MV3180A5A1
S41Y7784/40
SMV98101/151
S41Y7770/80
S41Y7771/50
S20X4321/30
S82028/240
MV3240A5A1
S41Y7784/40
SMV98101/151
S41Y7770/80
S41Y7771/60
S20X4321/30
S82028/240
MV3302A5A1
S41Y7784/40
SMV98101/151
S41Y7770/20
S41Y7771/40
S20X4321/30
S82028/240
MV3361A5A1
S41Y7784/40
SMV98101/151
S41Y8081/40
S41Y8082/30
S20X4321/30
S82028/270
MV3414A5A1
S41Y7784/40
SMV98101/151
S41Y8081/50
S41Y8082/30
S20X4321/30
S82028/270
MV3477A5A1
S41Y7784/40
SMV98101/151
S41Y8081/60
S41Y8082/40
S20X4321/30
S82028/270
Issue (08/00)
Page 6-1
ALSPA MV3000
F
r
MicroCubicle
Control Module
Fan
Rectifier
Module
Transistor Transistor
Module
RectifierTransistor
Module
SMPS (Switch
Mode Power
Supply)
(3 off Reqd)
Precharge
Fuses
600/690 V
MV3062A6A1
S41Y7784/40
S98101/153
S41Y8008/60
S20X4321/10
S82028/240
MV3077A6A1
S41Y7784/40
S98101/153
S41Y8008/60
S20X4321/10
S82028/240
MV3099A6A1
S41Y7784/40
S98101/153
S41Y8008/60
S20X4321/10
S82028/240
MV3125A6A1
S41Y7784/40
SMV98101/151
S41Y8036/40
S41Y8045/40
S20X4321/10
S82028/260
MV3144A6A1
S41Y7784/40
SMV98101/151
S41Y8036/40
S41Y8045/30
S20X4321/10
S82028/260
MV3192A6A1
S41Y7784/40
SMV98101/151
S41Y8036/30
S41Y8045/20
S20X4321/10
S82028/260
MV3242A6A1
S41Y7784/40
SMV98101/151
S41Y8036/10
S41Y8036/10
S20X4321/10
S82028/260
MV3289A6A1
S41Y7784/40
SMV98101/151
S41Y8081/70
S41Y8082/50
S20X4321/10
S82028/270
MV3336A6A1
S41Y7784/40
SMV98101/151
S41Y8081/70
S41Y8082/60
S20X4321/10
S82028/270
MV3382A6A1
S41Y7784/40
SMV98101/151
S41Y8081/80
S41Y8082/60
S20X4321/10
S82028/270
6.2
Precharge Fuses
Data for precharge fuses is shown below. The data is given here in addition to the part numbers shown in
Section 6.1 to allow local purchase of fuses, which may be helpful during commissioning. Replacing these
fuses with another rating or type will invalidate safety approvals.
Frame size
Fuse rating
A
Fuse type
(Qty. 3)
Bussmann KTK-2
Bussmann KTK-4
Bussmann KTK-6
Bussmann KTK-6
Littelfuse KLKD002.T
Bussmann KTK-3
Bussmann KTK-3
Bussmann KTK-5
Bussmann KTK-3
Bussmann KTK-4
Bussmann KTK-5
400 V
480 V
600/690 V
Page 6-2
Issue (08/00)
ALSPA MV3000
Issue (08/00)
Page 7-1
ALSPA MV3000
Fax: ______________________________
Page 1 of ______
Phone:
Fax:
Email Address:
Supply Frequency
Application
Centrifugal Pump or Fan?
If No: describe
Overload Magnitude/Duration
V AC
Yes/No
%/
sec
Environmental Details
Is the drive installed in a normal industrial environment?
- If No: describe
Ambient Conditions
Maximum Ambient Temperature
Air Quality e.g. contaminants, humidity
rpm
A
Hz
m
Hz
rpm
Yes/No
ppr
Yes/No
Altitude
Acoustic Noise Limit
dBA @ 1m
If yes, Protocol:
Other Requirements
Please list any other information, which you may consider relevant. Add further sheets as necessary.
Page 7-2
Issue (08/00)
ALSPA MV3000
8. Appendix
8. Appendix
8.1
Documentation
T1676
T1676DE
T1676EN
T1676FR
T1679DE
T1679EN
T1679FR
T1684DE
T1684EN
T1684FR
T1686DE
T1686EN
T1686FR
T1689
T1691
T1692
T1692EN
T1693
T1694DE
T1694EN
T1694FR
T1698
T1698EN
T1699EN
T1915DE
T1915EN
T1915FR
T1916DE
T1916EN
T1916FR
T1917DE
T1917EN
T1917FR
T1921DE
T1921EN
T1921FR
T1922DE
Issue (08/00)
Page 8-1
8. Appendix
ALSPA MV3000
T1922EN
T1922FR
T1923DE
T1923EN
T1923FR
T1924DE
T1924EN
T1924FR
T1925
T1926
T1927
T1928
T1929
T1930
T1930DE
T1930EN
T1930FR
Page 8-2
Issue (08/00)
ALSPA MV3000
8.2
8. Appendix
Enquiry Number:
Customer:
Project:
ITEM NUMBER
Drive Reference:
GENERIC DESCRIPTION
PRICE
Basic Configuration
ALSPA MV3000 MicroCubicleTM Inverter Drive
Line Filter
Drive Data ManagerTM
Fan Fuses
Extended Requirements and Options
DC Link Choke
12 Pulse Adapter Unit
Interbridge Transformer
12 Pulse Transformer
Dynamic Braking Unit
Dynamic Braking Resistor
EMC Filter
EMC Ferrite
FIP Fieldbus Module
FIP Fieldbus Cable
FIP Link AC Earth Connector
Profibus Module
Drive Data ManagerTM Lead and Door Mounting Kit
ALSPA Drive Coach PC Programming Tool
PC Programming Lead
Recommended Spares
Control Module
Fan
Rectifier Module
Transistor Transistor Module
Rectifier Transistor Module
Switch Mode Power Supply
Precharge Fuses
Other Items
TOTAL
Issue (08/00)
Page 8-3
8. Appendix
ALSPA MV3000
!"#$
Page 8-4
Issue (08/00)
PLANT INTERLOCK
STOP
RUN
REVERSE
KEYPAD/REMOTE
(open = Keypad)
ANALOGUE REF1/2
(open = Ref. 1)
TRIP RESET
From
Encoder
and
PTC
REF1: +/-10V
20K
REF2:
4 - 20 mA
LOOP
METERS
Speed Feedback
Current
Feedback
TB3
10 +24V O/P
R/L1
INTERLOCK
DIGIN 1
DIGIN 2
DIGIN 3
DIGIN 4
DIGIN 5
3
2
1
DIGIN 6
+24 V O/P
0 Volts (digital)
RECT+
RECT-
HSIO HSIO +
CAN LO
CAN HI
GND
RS485 RxRS485 Rx+
RS485 TxRS485 Tx+
TB5
12
11
10
9
8
7
6
5
4
3
2
1
A+
AB+
BZ+
Z+24V
FB+
+5V
0V
FBM_PTC
9
8
7
6
5
4
3
2
1
20 mA
4
3
2
1
S/L2
T/L3
TB4
9
8
7
6
5
4
3
2
1
TB6
DC Link
Inductor
(optional)
DCDC+
Internal
Dynamic
Braking
Unit
(Optional)
Cabinet Boundary
U
V
W
U V W
Connect PTC
between:
TB5/1 and TB5/3
PTC
Motor Thermistor
To TB5
10 V
AN
AN
AN
AN
Externally fitted
DB Resistor
(Optional)
BR
+10V
AN I/P 1+
AN I/P 1 AN I/P 2 +
AN I/P 2 -10V
AN GND
AN O/P 1
AN O/P 2
D
C
B
C
Fuses
TB2
2
1
EARTH/GROUND
DIGOUT 3
EMC Filter
(optional)
0V
Isolator
DIGOUT 2
GLAND
AT SPEED
DIGOUT 1
Line Reactor
OUTPUT
RUNNING
AC LINE INPUT
Ferrite Rings
(optional)
HEALTHY
TB1
9
8
7
6
5
4
3
2
1
ALSPA MV3000
24V
Lamps on
cabinet door
Note: a motor
thermostat can be
accommodated by
re-programming a
digital input
FB+
+5 V
E
OPTIONAL
ENCODER
0V
FB-