MRCT

Megger Relay and Current Transformer Test Set

MRCT

Megger Relay and Current Transformer Test Set

DESCRIPTION
The Megger MRCT is a light weight, robust, portable unit
used to perform demagnetization, ratio, saturation, winding
resistance, polarity, phase deviation, and insulation tests on
current transformers. The MRCT automatically calculates ratio
errors, saturation curves, and knee points. The MRCT provides a
microprocessor-controlled variable voltage and current output and
precision instrumentation for automatically testing single and multi
ratio CTs, reducing testing time and increasing productivity. The
MRCT will directly connect to multi ratio CTs and perform all tests
saturation, ratio and polarity, winding resistance and insulation on
all taps with the push of a button and without changing leads.
The MRCT can be controlled
via Meggers Smart Touch
View Interface (STVI)
controller. The STVI controller
is a full color, high resolution,
LCD touch screen which
allows the user to perform
manual and automatic testing
quickly and easily using the
manual test screen, as well
as using pre-constructed
test routines. The large color
display permits the user to easily read all pertinent data while the
test is being performed and provides the ability to view the current
transformers saturation curve. The unit can also be configured to
come without a Megger STVI and can be controlled via a laptop
with Meggers PowerDB software.

nn

Industry leading test duration using patented


simultaneous multi-tap measurements
reduces testing time by 20% on multi-tap CTs

nn

Accuracy to support testing of metering and


protection class CT

nn

Smallest and lightest 2 kV AC secondary


voltage injection unit on the market

nn

Optional DC excitation technique for testing


CTs with kneepoints up to 30 kV

nn

Integrated single phase relay test system

nn

Integrated VT/CVT test system

nn

Grouped testing: demagnetization, knee


points, ratios, saturation curves, and more

nn

Measure all ratios and saturation curves on


multi-tap CTs with one lead connection

nn

Built-in insulation resistance testing

Current transformers can be tested in their equipment


configuration, such as being mounted in transformers, oil circuit
breakers or switchgear. It is necessary for the equipment to be
completely isolated from the electrical system prior to testing.

APPLICATIONS
Saturation Test
With the single push
of a button, the
MRCT performs a
CT saturation test
and calculates the
rated knee point. The
saturation test can be
performed at frequency
of 50 or 60 Hz up to
2,000 volts as required
by IEC regulations.
In addition the MRCT can be configured to test kneepoints up to
30 kV using an alternative DC technique. This allows testing the
majority of CTs using line frequency while still being able to test
larger generation class CT with a portable instrument.
The MRCT will calculate the rated knee point in compliance with
either IEEE C57.13.1, IEC 60044-1, IEC 60044-6 or IEC 61869
on both standards as well as of specialized CTs such as PX, TPS,
TPX, TPY and TPZ. While the saturation test is being performed,
the MCRT will plot the CT saturation curve on the STVI display
and automatically provide the user with the rated knee point per
the desired IEEE or IEC standard. Many substations CTs include a
multi-ratio secondary; therefore the MRCT has the ability to plot and
simultaneously display up to 10 CT saturation curves.

MRCT
Megger Relay and Current Transformer Test Set
Ratio, Polarity Test
Ratio testing can be performed by using the MRCT. The method
used by the MRCT compares a voltage applied to the secondary
winding to the resulting voltage produced on the primary winding.
For example, if 1 volt per turn is applied to the secondary winding,
the voltage present on the primary winding would be 1 volt. More
specifically, if 120 volts were applied to the secondary of a 600:5
current transformer (120:1 ratio), 1 volt would be present on the
primary winding.
Winding Resistance Test
Measures CT winding resistance with the injection of a test
voltage, measuring the DC current and calculating temperature
compensated resistance.

The MRCT is available in 2 onboard display/enclosure options.

Demagnetization
Normal operating conditions and typical winding resistance
measurements can cause a CT to become magnetized. The MRCT
has the ability to automatically demagnetize the CT under test. This
automatic demagnetization routine is useful to ensure that the CT
saturation test yield correct results. Prior to testing demagnetization
is recommended per both ANSI and IEC standards.

nn Automated Test Plans with CT Saturation, Ratio and

Polarity, Winding Resistance and Insulation Testing - The


microprocessor controlled output fully automates testing of CTs.
The MRCT will directly connect to multi ratio CTs and perform
all tests saturation, ratio and polarity, winding resistance, and
insulation on all taps with the push of a button and without
changing leads.

CT Burden
The MRCT measures the connected CT burden load with direct
injection of secondary current to a load that is disconnected from
the CT. The MRCT measures the secondary voltage in magnitude
and angle of the connected burden in VA and power factor.

nn Direct Connection to Multi Ratio CTs - The MRCT will directly

connect to all taps on multi ratio CTs to eliminate lead changes


required to test all inner-winding CT ratios, saturation curves and
knee points. The MRCT will test all programmed taps with the
push of one button.

Insulation Resistance Test


In order to ensure that the CT secondary wiring is properly insulated,
the MRCT system includes a 500 V, 1,000 V insulation resistance
test system. This test ensures that the CT secondary winding and
secondary wiring is properly insulated per both ANSI and IEC
standards.

nn Full Color, High Resolution, LCD Touch Screen - Menu screens

and touch screen function buttons are provided to quickly and


easily select the desired test function. Tests results can be saved
to the unit for download to a memory stick to transfer or print
test reports.
nn CT Saturation, Ratio and Polarity, Winding Resistance, and

The MRCT will also automatically switch the test leads to perform all
required insulation test. These test include H-L, H-G, L-G.

Insulation Automated Testing - The microprocessor-controlled


output fully automates testing of CTs. This automated testing
simplifies CT testing and reduces testing time. Automated testing
is accomplished directly on the Meggers STVI or via PowerDB
Lite.

Note: Disconnect all electronic loads before performing this test.


Data Storage and Printing
The MRCT test system not only permits accurate and automated CT
testing, but also catalogs and stores test results within the STVI for
simple retrieval by software at a later date. All cataloged test results
can be uploaded to Meggers PowerDBTM Lite for report generation
and saturation curve plotting on a computer or STVI. PowerDB
Lite also has the ability to operate the MRCT with no operator
intervention, thus providing a completely computer controlled
automated test system.

nn CT Demagnetization - During operation and routine

DC winding resistance testing, it is possible for a CT to


become magnetized. The MRCT includes an automated CT
demagnetization function, which allows determination of
accurate knee point and ratios thus providing stable, repeatable
test results, and reduces test time.
nn Insulation Test - The MRCT includes a 500/1,000 V insulation

Upgradeability
The MRCT includes the ability to upgrade testing capability. With
various configurations and accessories the MRCT system can be
upgraded as new testing needs are developed.

test system to verify the CT secondary winding and secondary


wiring. This insures that the secondary insulation has not
degraded and will continue to perform its function during high
current faults.

FEATURES AND BENEFITS

nn Test Result Report - The MRCT offers storage of complete test

files in an easy-to-use, versatile format that permits upload to


PowerDB Lite, or printing test results using the optional external
printer. These options provide a simple, complete, easy way to
store over 200 test results and saturation curves. All test results
can be cataloged and stored in the MRCT.

nn Industry leading test duration using patented simultaneous

multi tap measurements - The MRCT system can provide


concurrent measurement of voltages on all taps during CT
saturation, and ratio and polarity testing. This allows the MRCT
system to calculate the knee points and ratios of all windings at
the same time thus eliminating the need for multiple tests on a
CT. This will drastically reduce testing time.

MRCT
Megger Relay and Current Transformer Test Set
SPECIFICATIONS
Input

Accuracy
100 to 132 V or 200 to 264 V, 1, 50 or 60 Hz,
15 A max.

Ratio Test

Output
Voltage

3 minuntes typical
6 minutes maximum

Secondary Voltage Injection Method


Continuously variable in three ranges:
0 to 30 V at 5.0 A max
(15 minute on, 5 minute off)
0 to 300 V at 1.0 A max
(15 minute on, 5 minute off)
300 to 2000 V at 1.0 A max
(5 minute on, 5 minute off)

Range

Current
Output Current

Power Max V/Duty Cycle

30 Amperes

200 VA (282 peak) 6.67 V rms


(15 minutes on, 5 minutes off)

60 Amperes

600 VA 90 cycles

Accuracy

0.8 to 2000

0.02% typical
0.05% maximum

2000 to 5000

0.03% typical
0.1% maximum

5000 to 20000

0.05% typical
0.2% maximum

Winding Resistance Test


Measuring Range

0 30

Accuracy

(at 20 C) 1%, 0 30

Instrumentation

Insulation Test

Voltmeters

Test Voltage

1000 VDC, 500 VDC

Output

Measuring Range

20 G, 10 G

Resolution

0.0000 to 1.9999/19.999/199.99/1999.9

Short Circuit Current

1.5 mA nominal

Ranges

0 to 2/20/200/2000 V

Test Current on Load

1 mA at min. pass values of insulation

Accuracy

0.5% of reading typical


1.0% of reading typical
max

Accuracy

1000 volts 3% 2 digits 0.2% per G


500 volts 3% 2 digits 0.4% per G

Communication
Interfaces

Ethernet

(as specified in BS7671, HD 384 and IEC 364)

Input
Primary Voltage
Measurement
Ranges

0 to 0.35/2.0/20.0/200.0/600.0 V

Resolution

0.0001 to 1.9999/19.999/199.9/600 V

Accuracy

0.02% of reading and .02% range typical

Environment
Humidity

Relative humidity 5%...95% not condensing

Operating

-10 C to 50 C

Storage

-30 C to 70 C

Secondary Voltage Measurement

Enclosure

The unit is housed in a rugged enclosure suitable


for use in outdoor substations.

Ranges

0 to 2/20.0/200.0/2000.0 V

Standards

IEC 61010, CSA 22.2, CE

Resolution

0.0000 to 19.999/199.9/1999.9 V

100 to 240 V (10%) AC, 50/60 Hz

Accuracy

0 to 999.9 V
0.02% of reading and .02% range typical
0.05% of reading and .05% range maximum
1000 to 2000 V
0.08% of reading and .08% range typical
0.2% of reading and 0.2% range maximum

Input Power
Dimensions

14 H X 7.5 W X 12 D
(36 H X 19.3 W X 30.5 D cm)

Weight

36.7 lb (16.7 kg)

CE Marking

Low voltage directive

2006/95/EC

Electronmagnetic
Compatibility Directive

2004/108/EC

0.05% of reading and 05% range maximum

Ammeter
Output
Ranges

0.0 to 1.0/10.0/60.0 A

Resolution

.001/.01

Conformance
Standards

Input
Excitation curve testing
Range

0.0000 to 0.1/1.0/8.0 A

Accuracy

0.08% of reading .08% range typical


0.2% of reading 0.2% range maximum

EMC
EN 61326-1
EN 61326-2-1

Phase Angle Measurement


3 digits
Range

0 to 360 degrees

Resolution

1 minute

Safety
EN 61010-1
EN 61010-2-030
EN 61010-031
EN 61010 +A1

2010
2010
2002

2006
2006

MRCT
Megger Relay and Current Transformer Test Set
DESCRIPTIONS OF HARDWARE OPTIONS AND

AC Voltage Output Outputs are rated with the following


Ranges:

ACCESSORIES

Output volts power max I


30 volts 150 VA 5 amps

CURRENT TRANSFORMER TESTING (CT) USING DC


VOLTAGE OPTION

150 volts 150 VA (see Power V)


300 volts 150 VA 0.5 amps
DC 150 watts
Duty Cycle: Continuous

DESCRIPTION

Metering

The MRCT can be configured to include the functionality to perform


the excitation test on current transformers using DC voltage. With
this configuration the MRCT can measure knee points on current
transformers up to 30 kV

AC Voltage Amplitude

APPLICATIONS
As part of a regular maintenance program to verify factory readings
and locate the presence of defects in current transformers, the
MRCT can accurately perform the excitation test on CTs and
measure the knee point up to 2 kV using AC voltage. For CTs that
have a knee point higher than 2 kV the MRCT can be configured to
utilize DC voltage to saturate the CT and accurately measure the
knee point up to 30 kV.

Outputs
Output Voltage
Output Current
Output Power

Output power ratings are specified in


AC rms values and peak power ratings.

Output Current Power


Max V / Duty Cycle

1 ampere 15 VA 15.0 V rms continuous

Resolution

.01

Measurements

AC RMS

Ranges

30, 150, 300V

Accuracy

0.05% reading + 0.02% range typical,


0.15% reading + 0.05% range maximum

Resolution

.001/.01

Measurements

AC RMS

Ranges

30, 60A

Accuracy

0.1% range typical, 0.25% range maximum

Resolution

.01

Measurements

RMS

Ranges

30, 150, 300V

DC Current Amplitude

All outputs are independent from sudden


changes in line voltage and frequency. This
provides stable outputs not affected by
sudden changes in the power source. All
outputs are regulated so changes in load
impedance do not affect the output.

Output Current

0.05% reading + 0.02% range typical,


0.15% reading + 0.05% range maximum

DC Voltage Amplitude

0 to 300 V DC
0 to 1 A eff
300VA

RELAY OPTION SPECIFICATIONS


Outputs

Accuracy

AC Current Amplitude

DC VOLTAGE TESTING OPTION SPECIFICATIONS


CT Testing Using
DC Voltage

Measured output quantities such as AC


amperes, AC Volts, DC volts or DC amperes,
and time may be simultaneously displayed
on the large, color TFT LCD, optional STVI
touch screen. The AC and DC outputs
display the approximate voltage/current
output prior to initiation of the outputs.

4 amperes 200 VA (282 peak)


50.0 V rms continuous
15 amperes 200 VA (282 peak)
13.4 V rms continuous
30 amperes 200 VA (282 peak)
6.67 V rms continuous
75 amperes 300 VA (424 peak)
5.00 V rms 90 cycles
DC 200 Watts

Accuracy

0.05 % reading + 0.02 % range typical,


0.15 % reading + 0.05 % range
maximum

Resolution

.001/.01

Measurements

RMS

Ranges

30A

MRCT
Megger Relay and Current Transformer Test Set
DESCRIPTIONS OF HARDWARE OPTIONS
AND ACCESSORIES

VT/CVT OPTION SPECIFICATIONS


Inductive VT Testing
Outputs

VOLTAGE TRANSFORMER TESTING (VT) & COUPLING


CAPACITOR VOLTAGE TRANSFORMER (CCVT) OPTION

Output Voltage
Output Current
Output Power

0 to 300 V AC
0 to 1 A eff
300VA

Ratio Measurement
Voltage ratio

1 to 350 >350 to 1100 >1100 to 2450

Voltage Level

.6 kV to 35 kV >35 kV to 110 kV
>110 kV to 245 kV

DESCRIPTION

Accuracy

The MRCT can be configured to include the functionality to test


voltage transformers. With this configuration the MRCT can
measure ratio errors and phase angles as well as the secondary
winding resistance of inductive voltage transformers.

0.03% typical 0.2% maximum,


0.05% typical 0.3% maximum,
0.05% typical 0.5% maximum.

Phase Angle Measurement

VOLTAGE TRANSFORMER (VT) TESTING OPTION

Voltage ratio

1 to 350 >350 to 1100 >1100 to 2450

Voltage Level

.6 kV to 35 kV >35 kV to 110 kV
>110 kV to 245 kV

APPLICATIONS

Accuracy

As part of a regular maintenance program to verify factory


readings and locate the presence of defects in voltage
transformers, the MRCT can accurately measure the ratio, phase
displacement, and secondary winding resistance. The MRCT
utilizes up to 300V to accurately measure the ratio and phase
angle of inductive voltage transformers.

3 min typical 6 min maximum,


3 min typical 6 min maximum,
3 min typical 6 min maximum.

Winding resistance measurement


Resolution

1m

Guaranteed Accuracy

(at 20 C) 0.2% + 1m,

Capacitive VT Testing
COUPLING CAPACITOR VOLTAGE TRANSFORMER
(CCVT) TESTING OPTION
DESCRIPTION

Outputs

Stand Alone

W/ 4 kV booster

Output Voltage

0 to 2000 V AC

0 to 4000 V AC

Output Current

0 to 1 A

0 to 1 A

Output Power

2000 VA

4000 VA

Ratio Measurement

With the VT & CCVT testing option enabled the MRCT can
measure the CCVT ratio and phase error. With an output of up
to 2 kV the MRCT can measure a CCVT ratio error and phase
error of low to medium voltage capacitive coupled voltage
transformers up to 245 kV.

Voltage ratio

300 to 2450

Voltage Level

>30 kV to 245 kV

Accuracy

0.1% typical 0.3% maximum

Phase Angle Measurement


Voltage ratio

300 to 2450

APPLICATIONS

Voltage Level

>30 kV to 245 kV

The MRCT has ability to measure CCVT ratio and phase thus
ensuring that the CCVT is working properly and can be returned
to service. The MRCT the capability to supply up to 2000V to
measure the ratio of low to medium voltage capacitive voltage
transformers up to 245 kV.

Accuracy

6 min typical 15 min maximum

Winding resistance measurement

Resolution

1m

Guaranteed Accuracy

(at 20 C) 0.2% + 1m,

MRCT
Megger Relay and Current Transformer Test Set

ORDERING INFORMATION
Style Number Identification

Model MRCT -

M
Test Leads Option
N = Without leads
S = Standard leads
K = Kelvin leads

Reserved for future use


Testing Method
S= Standard Method 2 kV AC
D=Standard Method and DC
Technique for knee points
up to 30 kV

Bluetooth Options
1 = With Bluetooth
0 = Without Bluetooth

Multi Function Testing Option


C = CT testing only
R = Relay testing and CT testing
V = VT testing and CT testing
T = CT, VT, and Relay testing

Reserved for future use


Onboard Display/Enclosure
0 = No onboard display w/small enclosure
2 = Onboard display w/long enclosure

IEC 61850 Option


1 = With IEC 61850 GOOSE
0 = Without

Power Cord Option


A = North American power cord
I = International power cord
E = Continental Europe power cord
U = United Kingdom

Integrated Insulation Test


N = No integrated insulation resistance test
R = Integrated insulation resistance test
Overlay Option
1 = ANSI
3 = IEC

DESCRIPTIONS OF HARDWARE OPTIONS

Testing Method
Customer can choose which method the MRCT will use to perform the excitation test. Enter the letter S for the unit to be configured to
perform the excitation test using only AC voltage. Enter the letter D for the unit to perform the test up to 2 kv using AC and above 2 kV
using DC voltage
Multi Function Testing Option
Customers can choose which type of testing functionality they want the MRCT unit to come with. Enter the letter C for the unit to come
with the current transformer testing capability only, or enter the letter R for the unit to also have relay testing functionality. Enter V for the
unti to be configured to test both Ct and VT or enter the letter T for the unit to be configured to test CT; Relays, and VTs
IEC 61850 Option
If the MRCT is configured to test relays, Megger GOOSE Configurator software may be used in the testing or commissioning of IEC 61850
compliant devices. In order for the MRCT to be able to subscribe as well as publish GOOSE messages, the MRCT must be configured to test
relays and the IEC 61850 feature needs to be enabled. Enter the number 1 for the unit to come with the IEC 61850 option enabled. Enter 0
for the unit without IEC 61850 enabled.
Integrated Insulation Test
Enter R for the unit to come with an integrated insulation resistance test capability. Enter N for the unit without an integrated insulation test.
Bluetooth Option
For customers who wish to have a wireless control of the SMRT unit, enter the number 1 for the unit to come with the Bluetooth option
installed. Enter 0 for without.
Power Cord Option
Customers can choose which type of power cord they want the unit to come with.
A option NEMA 5-15 to IEC60310 C13 connectors, UL & CSA approved for countries with NEMA outlets.
I option International color coded wires (light blue, brown and green with yellow stripe) insulation jacket stripped ready for male
connector with IEC 60320 C13 connector. CE marked.
E option CEE 7/7 Schuko plug to IEC 60320 C13 connector. CE marked.
U option United Kingdom power cord with IEC 60320 C13 connector, and 13 amp fuse. CE marked.
Test Leads Option
Enter the letter N for the unit without test leads. Enter the letter S for the unit to come with set of standard test leads. Enter the letter K for
the unit to come with both standard and Kelvin test leads.
Test Leads and Accessories
All units come with a power cord (see power cord option), and Ethernet communication cable, and instruction manual CD. All other
accessories vary depending on the options selected, see table of optional accessories

MRCT
Megger Relay and Current Transformer Test Set
TEST LEADS AND ACCESSORIES
All units come with a power cord, an Ethernet communication cable, and instruction manual. All other accessories varies depending on the features selected, see
Table of Accessories.

Included Standard Accessories


Description

Part Number
90015-267

Power Cord - Depending on the style number, the unit will


come with one of the following,
Line cord, North American

90015-267

Line cord, Continental Europe


with CEE 7/7 Schuko Plug

90015-268

Line cord, International color coded wire

90015-269

Line cord, United Kingdom

90015-270

Ethernet cable for interconnection to PC,


210cm (7 ft.) long (Qty. 1 ea)

90015-268

90003-594

Instruction manual

81757

90015-270

TABLE OF ACCESSORIES
Accessories are supplied with the selection of the various features depending upon the option selected . Test Leads and Accessories can also
be ordered individually, see below for accessories included with option and part numbers.

STANDARD LEADS

684004
Cable/Spade lug adapter (small, 5 each)

Accessories included in standard set of test leads.

Small lug fit most new relay small terminal


blocks. Lug adapter, red, 4.1 mm, rated up
to 1000 V/ 20 Amps CAT II

2003-725
Accessory Carry Case (1 each)

Use to carry power cord, Ethernet cable,


Optional STVI and test leads.

684005
Cable/Spade lug adapter (small, 5 each)

Small lug fit most new relay small terminal


blocks. Lug adapter, black, 4.1 mm, rated
up to 1000 V/ 20 Amps CAT II

1005-466
Set of primary test leads (1 each)

5 Tap ( X1, X2, X3, X4, X5) Test Leads,


20ft (6.096m)

9005-599
Screw in banana test jack (5 each)

1005-774
Set of secondary test leads (1 each)

5 Tap ( X1, X2, X3, X4, X5) Test Leads,


20ft (6.096m)

830029
USB memory stick (1 each)

2003-724
Ground lead (1 each)

640266

green with yellow, with large


ground clip, 20 ft

red, 40mm opening

Large test clip (1 each)

640267
Large test clip (1 each)

9004-427
Alligator clip (5 each)

black, 40mm opening

Black, 4.1mm

MRCT
Megger Relay and Current Transformer Test Set

KELVIN LEADS
Accessories included in Kelvin set of test leads.
2005-477
Clips (1 each)

1004-424
Kelvin test leads (1 each)

Black

black, 20ft
substituted for standard secondary
test lead 1005-774

2005-478
Clips (1 each)

Red

RELAY OPTION
Accessories included with relay option
2008-539
Sleeved Pair of Test Leads:

684004
Cable/Spade lug adapter (small, 5 each)

Small lug fit most new relay small terminal


blocks. Lug adapter, red, 4.1 mm, rated up
to 1000 V/ 20 Amps CAT II

Keeps the test leads in pairs and from


getting entangled. Sleeved Test Leads, one
red, one black, 200 cm (78.7) long, 600 V,
32 Amperes CAT II

2001-573
Jumper lead

Used to common returns together on units


with floating ground returns, or parallel of
current channels. Jumper lead, black,
12.5 cm (5) long, use with voltage /
current outputs, 600 V, 32 Amps CAT II

OPTIONAL ACCESSORIES
1006-492

STVI-1

Hard-Sided transit case w/integrated display

Smart Touch View Interface

1003-884

The Smart Touch View Interface (STVI)


is Meggers handheld controller for the
MRCT, the SMRT and the older MPRT
relay test systems. The STVI, with its large,
full color, new high resolution, and high
definition TFT LCD touch screen allows
the user to easily control the MRCT
using built in MRCT test screens, as well
manual routines for current transformers.
Ergonomically designed for either right
or left hand operation using the rubber
cushion grips, the centrally located control
knob, and the touch screen, the STVI is
extremely easy to use. Use the new builtin stand for single-handed operation. The
STVI uses a standard Ethernet cable, and
Power Over Ethernet (POE) operation. The
STVI includes non-volatile built-in data
storage for saving tests and test results. A
USB port is provided for transferring test
results to your PC.

Hard-Sided transit case w/o integrated display

Includes custom designed foam inserts


for the MRCT unit and accessory case.
Transit case includes retractable handle,
polyurethane wheels with stainless steel
bearings, double-throw latches, fold down
handles, and stainless steel
hardware and padlock protection, with
O-ring seal making the case water-tight,
with an IP 67 rating. Tested and certified
to US Department of Defense Standards
for impact, vibration, and low/high storage
temperatures. The case is small, and weighs
only 25 pounds (11.25 kg).

MRCT
Megger Relay and Current Transformer Test Set

UK
Archcliffe Road Dover
CT17 9EN England
T +44 (0) 1304 502101
F +44 (0) 1304 207342
[email protected]

UNITED STATES
4271 Bronze Way
Dallas TX 75237-1019 USA
T 800 723 2861 (USA only)
T +1 214 333 3201
F +1 214 331 7399
[email protected]

OTHER TECHNICAL SALES OFFICES


Valley Forge USA, College Station USA,
Sydney AUSTRALIA, Tby SWEDEN, Ontario
CANADA, Trappes FRANCE, Oberursel
GERMANY, Aargau SWITZERLAND, Kingdom
of BAHRAIN, Mumbai INDIA, Johannesburg
SOUTH AFRICA, Chonburi THAILAND

CERTIFICATION ISO
Registered to ISO 9001:2000 Cert. no. Q 09290
Registered to ISO 14001-1996 Cert. no. EMS 61597

MRCT_DS_EN_V08
www.megger.com

Megger is a registered trademark