Large Grilles Multiple Sections
Large Grilles Multiple Sections
Large Grilles Multiple Sections
P. No.
Safety considerations
Introduction
General description
Installation
2-11
Pre start up
11-14
16-25
28-42
Warranty
43-45
5-6
15
24-25
26-27
32-35
36-39
REVISION A
40
UPDATED ON 28/08/2012
SAFETY CONSIDERATIONS
Installation, start-up and servicing of the equipment can be hazardous due to system pressures,
electrical components and locations of equipment (roofs etc.).
Only trained, qualified installers and service mechanics should install start-up and service this
equipment. Trained service personnel should perform all operations except basic maintenance.
When working on the equipment, follow all safety codes. Use proper tools, tackles and necessary
instruments. Use safety glasses, gloves, boots, valves and regulators etc. Be sure power to the
equipment is off before performing maintenance or service.
INTRODUCTION
These instructions cover installation, start-up and service of 40LC-010DS /38LH-102DS Air Cooled
DIGITAL DUCTED air-conditioning units.
GENERAL DESCRIPTION
The Air Cooled DIGITAL DUCTED system is composed of two units, one installed outside and the
other inside, which are interconnected after positioning. The outdoor unit is the condensing unit
incorporating condenser coil, fan and fan motor & Digital Scroll compressor, Electrical panel. Where as
indoor unit contains filter drier, evaporator coil, electronic expansion valve, distributor, air filter, blower
& blower motor & Handset controller.
INSTALLATION
PRE-DELIVERY INSPECTION
This applies to the condensing and indoor units both.
1. Open packing carefully ensuring unit in upright position.
2. Check the unit thoroughly for dents, paint discrepancies, fins damage, pinching of tubes etc. Check
coil / copper tubes for any dents, pinching or cuts, especially near tube sheets. Ensure all parts /
components, electrical wiring and connections are visibly in order.
3. Rotate fan / blower for any bearing or touching noise.
4. Check and test fans / blower as per the rated supply for Indoor and Outdoor if possible.
5. Check coil and piping for leaks.
6. If any damage is found, rectify / take the necessary action and repack the unit in upright position.
RIGGING
These units are designed to be handled by forklift trucks. Use the unit skid for placing on the forks of
the lift-truck.
PLACEMENT
Out door Units are shipped mounted on wooden members & Indoor unit packed in carton box. These
should be removed only when the unit is in its final position.
The unit may be lifted, dragged or rolled into place while the wooden supports are still in place. When
rolling, use a minimum of three rollers and pull / push the wooden members not the unit frame.
Once the unit is in place, lift and remove pad or roller, unbolt wooden supports and lower to ground.
REVISION A
UPDATED ON 28/08/2012
3
LOCATION AND MOUNTING
A. CONDENSING UNIT
Location
Locate the unit so that airflow through the condenser coil is unrestricted. Provide clearance for wiring
and piping. There should be ample space for service requirements.
Install the outdoor unit in well-ventilated space. Avoid wet locations to prevent water entry. The unit
should be placed preferably in shaded areas, and places exposed to direct sunlight should be avoided.
The unit should be installed in a location so as to minimize refrigerant and drain pipe length.
Mounting
The unit should be mounted to prevent corrosion of sheet steel base on
(a) Prefabricated angle iron frame, or
(b) 3 raised concrete platform.
These should be designed to take care of vibratory operating loads.
Placement area must be level and strong enough to support operating weight of the unit. Check that
the unit is mounted level to ensure proper oil return to compressor.
Units mounted on walls must be provided with a platform having space for service (if otherwise not
easily accessible for service).
B) INDOOR UNIT
Location
These units are designed specially for applications where piping is fully concealed.
Locate unit ensuring adequate space for supply / return air, service purposes and connections.
The location of the unit should be such that there is no ingress of fresh air as this would cause
condensation / sweating. Location should be near a drain point for easy drainage, and in a location to
simplify refrigerant piping.
REVISION A
UPDATED ON 28/08/2012
4
Digital Ducted 11HP
Model
INDOOR UNIT
OUTDOOR UNIT
40LC-010DS
38LH-102DS
8.5 TR
Nominal Cooling
Capacity*
Btu/hr
102000
Kcal/hr
25500
No. of units
Nominal Air
Quantity
CFM
3400
CMH
5780
Type
Propeller
Qty.
Discharge
Horizontal
Horizontal
Type
Fan
Fan Motor
Speed RPM
Qty.
Power HP
(watt)
Hi
(450)
1/6 (124)
1350
1050
Med
1300
1000
Lo
1250
950
Control Type
1720
1200
Height
Depth
Depth
345
730
-
1055
654
602
Width
1200
Type
Digital Scroll
Make
Emerson
Qty.
Model
ZPD-103KCE
110
200
Refrigerant
R410a
Expansion Device
Overall dimensions
(mm)
Cabinet
Compressor
Net Weight
REVISION A
Kg
UPDATED ON 28/08/2012
REVISION A
UPDATED ON 28/08/2012
REVISION A
UPDATED ON 28/08/2012
7
Air distribution
Install the air distribution system complete with ductwork, supply and return air grilles / diffusers, etc.
following recommended good practice.
Connect the supply air duct with double canvas cloth at the mouth of the unit for eliminating vibrations
and duct alignment problems, and as per recommended ducting practice.
I. Ducting system design
Design of ducts for normal applications may be done using the equal friction method. The method
employs the same friction loss per foot of length for the entire system. The procedure is outlined
below:
1) Sketch the air distribution layout complete with duct run lengths, location of supply registers and
return grilles, air quantities through each outlet and in each circuit, & fan location and static.
2) Knowing initial velocity and air quantity (CFM) of the machine, find friction rate using a Friction
Chart.
3) Select equivalent round duct area corresponding to this point from the Friction Chart. Use the
following relation to obtain rectangular duct dimensions.
[By substituting D, and a value of a or b in the relation to find the value of other side (depth /
width of duct)].
Equivalent Diameter D = 1.3 x (a x b) 0.623 / (a + b) 0.23
4) To determine the total friction loss the fan must overcome; calculate total equivalent length of the
circuit run having the longest length plus fittings equivalent length (largest friction drop). TOTAL
EQUIVALENT LENGTH may be roughly assumed as CIRCUIT STRAIGHT LENGTH + 50% OF
STRAIGHT LENGTH.
Find total pressure loss using the following relation:
TOTAL PRESSURE LOSS = TOTAL EQUIVALENT LENGTH X FRICTION RATE/100
5) Total pressures loss calculated must be less than fan static. If not, select a different initial velocity
and repeat from step 2.
6) Now, for each circuit part or air outlet, find out equivalent round duct area and rectangular duct
dimensions using Friction Chart and the relation given in step 4. Use a constant value of friction
rate (from step 3), and air quantity through the duct length (= original CFM - CFM delivered
through the outlet) to enter in Friction Chart to find duct dimensions.
II. Fabrication and installation of ducting
Refer Table 1 for ducting specifications for ducts of different sizes. Follow recommended ducting
principles.
All the angles iron flanges should be welded electrically and holes drilled. All the angle iron flanges
should be connected to the GSS duct by rivets at 4 centers.
All the flanged joints should have thick felt / foam gasket or sealed with silicon sealant. Felt should
be stuck with varnish and the hole in packing should be burnt through.
The GSS duct should be lapped across the flange.
REVISION A
UPDATED ON 28/08/2012
8
The duct should be supported by supports at a distance not exceeding 8 Feet. 24-G duct should be
supported by MS rod with 1 x 3/16 angle on which the ducts will be rested. felt / foam should
be provided between the duct bottom and support face of the angle. All support rods and angles should
be painted with red oxide primer.
For all branches, guide vanes / splitters / dampers should be provided. Provide straightening vanes for
collars and smooth bends. Interconnection of ducts between two units should have individual dampers
of opposed blades / sliding type.
Provide acoustic lining for the first 5 feet of ducting after fan outlet with 12 mm fiberglass rigid board
with RP tissue paper / 26 G perforated aluminum sheets.
In case plenums are used, the velocity in plenum should not exceed 300 FPM and the plenum should
be lined for acoustic purpose. If two branches are to be taken from the same plenum, the same should
be provided with dampers. These should be taken on the same side but opposite to the incoming duct
connection.
Provide for suitable fresh air arrangement.
Provide a straight duct length of at least 2D after the fan outlet for streamlining airflow; D is the
equivalent round duct diameter. This is VERY IMPORTANT.
III. Return and supply air grille sizing
Return air at the inlet of the indoor unit should not exceed 300 FPM. Return air path should be
designed for a maximum velocity of 1000 FPM.
Supply air grilles / diffusers should be sized as per manufacturers specification. A quick selection chart
for the purpose is given in Table 2.
Maximum side
Thickness (G)
(for GSS duct)
1.
UPTO 30"
24
2.
32" to 40"
22
3.
41" to 60"
4.
5.
Type of connection
Bracing
Cross bracing
22
Cross bracing
61" to 90"
20
18
REVISION A
UPDATED ON 28/08/2012
9
TABLE 2 : QUICK SELECTION CHART FOR GRILLES/DIFFUSERS
S.NO.
Description
Size
CFM
Throw
300
450
750
11
1050
13
20"x6"
270
16
24"x6"
325
18
30"x6"
400
19
36"x6"
500
19
24"x8"
480
26
30"x8"
580
27
36"x8"
700
27
24"x10"
600
30
30"x10"
750
32
36"x10"
900
33
24"x12"
740
25
30"x12"
925
31
36"x12"
1115
39
(feet)
1.
Round Type/square
type (Flat type)
(Terminal velocity
100FPM and jet
velocity 1250 FPM)
2.
Double deflection
type grilles
(Outlet velocity 500
FPM straight vane
type)
Refrigerant Piping
Piping
Since in the Unit Both Compressor & Suction Line are in outdoor. It fully complies general guideline of
Suction line. The cross-section of horizontal suction lines shall be such that the resulting gas velocity is
at least 4 m/s. Suction lines are insulated to limit suction gas superheat.
Indoor & Outdoor Unit are connected by Suction & Liquid Line Piping. Special Attention is required to
insulate Suction line whose temperature remain 5-20 deg. It is required to do insulation of proper grade
& thickness.
Do not run any Wiring with Suction or Liquid line.
Routing
REVISION A
UPDATED ON 28/08/2012
10
The pipes should run as straight as possible, avoiding unnecessary turns and bends. The piping length
between indoor & outdoor
utdoor unit should not exceed 50 meter & vertical pipe length between indoor &
outdoor should not exceed 12 meter
meter. Also number of bends should be adhered to the possible extent. In
case if the piping length exceeds 50 meter
meter, contact Carrier Air conditioning & Refrigeration Limited
for other length, pipe sizes and extra refrigerant charge for extra pipe length. If brazing is done to
connect two tube lengths, it should be carried out using proper flux and brazing rod (7.25% Phosphorus,
rest copper) with a constant purge of nitrogen through the piping to maintain a clear system.
All connections must be leak tight.
Note: - Provide the oil trap in vertical length if ODU is placed above the indoor unit (after every 4
meter).see figure below
11
Clamping
Clamping is necessary to prevent vibrations from being transmitted. When passing the pipes through
walls, opening should be sealed to minimize vibration transmission. Some slack in pipes between
structure & unit should be left.
Insulation
Insulate Suction & liquid line properly. This is necessary safety. Use tubular foam of 5/8 ID for liquid
line and 1 1/8 for Suction line.
PRE-START UP
Note: Do not mix the tools & equipments used with other refrigerants & also ensure that the tools &
equipments meet the requirement of R410A refrigerant.
Outdoor unit is factory charge with R410A Refrigerant (Charging Amount-7.6 Kg.)
PRE-PRESSURE TEST
Carry out a pressure test of the Indoor unit and interconnecting pipes at 300 PSIG by using dry nitrogen
through the adaptor which is being placed on the suction pipe. Hold this pressure for sometime to
ensure that there is no leakage in the system.
However, in case of leaks in the refrigerant circuit or breaking of joints etc., the valves have to be back
seated and the entire system of indoor and outdoor units with piping has to be pressure tested,
evacuated and charged.
After pressurizing the system, do the following:
SOAP TEST
Apply soap solution at all flare connections and brazing point. If bubbles appear at some points, then
tighten the flare nut or braze the leaking points (after releasing the gas from the system). No bubbles
should finally appear.
REVISION A
UPDATED ON 28/08/2012
12
After soap test, note the pressure and leave the system pressurized for 30 minutes. Note the pressure
again. There should be no pressure decay, recheck for leaks, remove them and do the pressure decay
test again.
EVACUATION
Vacuum pump
REVISION A
UPDATED ON 28/08/2012
13
A two-stage vacuum pump with gas ballast (0.04 mbar standing vacuum) shall be used with a capacity
consistent with the system volume. It is recommended to use connecting hoses with a large diameter to
avoid excessive pressure losses.
Warning
Do not use a manometer or apply power to the compressor while it is under vacuum. This may cause
motor winding damage. Never run the compressor under vacuum as it may cause compressor motor
burnout.
Note: - You are requested to use Electronic Vacuum Gauge.
OPENING OF VALVES / CHARGING
Open (backseat) the suction and liquid valve to allow refrigerant to flow through the system. The unit is
ready to be test started.
In case a leak has occurred the refrigerant system has to be repaired, pressure tested and evacuated,
recharging of R410a will have to be done. For this, connect the refrigerant cylinder to the suction valve
and the gauge manifold to the liquid valve. Make sure to purge air from charging line prior to tightening
the connections.
Connect the cylinder to allow vapor refrigerant to flow.
Open the all shut-off valves and charge the correct amount of refrigerant through adaptor on suction
line as per any of the following indicators:
a) Charge the correct amount of refrigerant by maintaining superheat of 10 deg at Suction line.
b) Charge Amount by Weighting Machine
8.5TR
Refrigerant Charge
Amount
7.6 Kg Per Circuit
8.5TR
Extra Refrigerant
Charge Amount per
meter
140 gms
Do not charge using the indication of sweating suction line or by only measuring the amperes drawn by
the machine as these may lead to incorrect charge amount along with the associated problems.
Charging by weight should be done as far as possible, as charging i.e. one of the most important factors
governing system performance. Purging of air before tightening connections is necessary.
REVISION A
UPDATED ON 28/08/2012
14
REVISION A
UPDATED ON 28/08/2012
15
REVISION A
UPDATED ON 28/08/2012
16
Wire
Specification
Label
Comment
5 Core / 6 mm
R/Y/B/N/E
CDU Power
3 Core / 2.5 mm
P/N/E
Data Cable
4 Core / 1.5 mm
+12V/RX/TX/GND
Shielded cable
Caution: Data cable and power cable should not tied together
Unbalanced 3-phase supply voltage
Never operate unit when supply voltage unbalance is more than 2%.
% Voltage unbalance = (Max. voltage deviation from avg. voltage) / (avg. voltage) x 100
REVISION A
UPDATED ON 28/08/2012
17
WARNING
1. Turn OFF the main power of the unit before performing services or maintenance on system.
Electrical shock can cause personal injuries.
2. Apply specified voltage only otherwise it will damage the unit or install a voltage stabilizer.
3. Check the power cord, it should not be damaged and should be plugged in properly. Otherwise
electrical shocks may occur.
4. Do not use power cord to turn off the unit.
5. Do not use flammable sprays near the unit. Benzene, thinners, insecticides and other chemical
agents can damage unit.
6. Use only correct MCB/fuses of proper amperage. If rewritable fuse is in use then using only correct
fuse wire otherwise fire and electrical
ctrical accident may occur.
7. While unplugging the power plug, don't pull it by power cord, this may damage the cord and cause
electrical shocks.
8. Never splash the unit with water, this will cause serious electrical shocks.
9. Do not obstruct the front of the discharge grill. This will block air flow, reduce the cooling effect and
may result in unit malfunction.
10. Set comfortable temperature. Extreme low temperature set can increase power consumption.
11. Avoid direct sunlight from heating the room. Us
Use
e Curtains and blinds or keep windows doors
closed, to keep the room cool for longer and save power.
12. Clean the filter once every fortnight or more often. Clogged filters reduce air supply, cooling and
can damage the unit. Service your unit regularly.
13.
3. A blocked Condenser will, for example, reduce cooling, increase power consumption and in
extreme cases even damage the unit.
14. Operate in FAN mode if you just want to circulate the room air.
15. Please carefully go through this handbook before o
operatin
INSTALLATION:
LCD REMOTE (WIRED)
Step 1: Open the front cover using screwdriver and unlock the cover at the bottom.
Step 2: Insert the wire thru a small hole on the back cover.
18
Step 3: Insert the back cover into 2x 4 box or attach the back cover to the wall using screw.
screw
Step 4: Connect the wire to back cover. Be careful; do not do wrong connection or interchange wires on
both ends. (RED +Ve & BLACK -Ve)
Step 5: Close the front cover by aligning the back cover lock
Step 6: Connect the 2 core wire (diameter 0.65 mm.) at P31 (2 pin connector) on PCB of indoor
controller at fan coil unit, from the display unit. Connect one end of the wire to the FCU PCB as shown in
the picture.. Be sure to match the color ((RED +Ve & BLACK -Ve)) at both ends.
ends
19
USERS FEATURES
The following features can be operated by the buttons on the Display unit.
1.1 Power on/off
button to turn on/off the air conditioner. When turn on, it will operate according to the setting
Press
shown on the display unit.
1.2 Fan
20
Press FAN button to select the fan speed (low, medium, high or auto).
Fan:
Cool:
The system will operate as the fan only. In this mode the temperature setting and Sleep
function cannot be operate.
The system will operate as the cooling unit. The compressor will
Operate if
Troom
Tset +1
Stop if
Troom
Tset
Dry:
or TEMP
REVISION A
UPDATED ON 28/08/2012
21
1.6 Sleep
Moving the cursor to SLEEP position and then press MENU button. The Display shows
For Cool operating mode, the setting temperature will be automatically raised up 1C after one hour.
Note:
During
the
Sleep mode if the system
syste is
turned off or stopped by power failure, it will exit from the Sleep mode.
2.
The following features can be operated by the buttons on the Remote unit.
2.1 Power
Press
2.2 Mode
Press MODE button to change the mode of operation in the following sequence.
22
2.4 Fan
Press
2.5 Sleep
Press SLEEP button to activate the Sleep function which will raise up/reduce the setting temperature 1C for
Cool/Heat mode respectively.
Press
Press
is blinking.
Press
Press
Remark
To cancel is to press
23
SYSTEM DIAGNOSES:
View system parameters on wired LCD display/Control.
Press and hold MENU and MODE button, for 5 seconds, the Display shows P0.
Use
or
View index
Value
Description
P0
0-500
P1
0-100
P2
0-20
P3
-9-60
P4
-9-60
P5
-9-60
P6
-9-60
P7
0-140
P8
0-140
P9
P10
F1-F3
P11
PWM modulation
0-100
P12
Status zone
P13
Current sensor1
0-30
P14
Current sensor2
0-30
P15
0-30
P16
0-30
P17
KP
0-255
P18
TD
P19
TI
0-255
REVISION A
-3 TO 5
S Y G R
UPDATED ON 28/08/2012
24
ERROR CODE:
The error message is shown at the OUTDOOR UNIT CONTROLLER as following table:
Error Message
Events
E0
E1
E2
E3
E4
[E
KP
LP
Over current
0[
D0
D1
D2
Evacuation process
F2
Pump down
F1
Test mode
F0
Oil balancing
OB
Oil recovery
OR
HP or LP system off
F3
Note: If there are 2 or more errors at the same time, the display will show the upper line
event as the priority.
REVISION A
UPDATED ON 28/08/2012
25
The error message is shown at the INDOOR UNIT CONTROLLER as following table:
EVENTS
Error Message
Remark
IN
: E0
IN
:E1
IN
:E2
IN
:E3
IN
: FR
OD
: E0
OD
: E1
OD
: E2
OD
: E3
OD
: E4
OD
: KP
OD
: LP
Over current
OD
: 0[
OD
: CO
OD
: [E
OD
: F3
Note: if there are 2 or more errors at the same time, the display will show the upper line
event as the priority.
REVISION A
UPDATED ON 28/08/2012
26
Temperature
sensor
Scanner
Contactor
MCB
Main incoming power
supply (400V, 3PH, 50Hz)
EXV Wire
Temperature
sensor
Incoming Power
Supply from cdu
Power supply to
motor
27
SCANNER DETAIL
FRONT VIEW
REAR VIEW
SCANNER SPECIFICATION
Voltage Sacnner
Indications (LED):
1
2
Supply health
Voltage High
3
4
5
Voltage Low
Single Phase or Voltage unbalanced
Reverse Phase Sequence
Technical Specifications
Mechanical details
Mounting
Weight
Dimension
Required Panel Cut out for mounting
Connecting terminals
Door Mounting
470 Gms.
96 (W) X 96 (L) X 53 (D) mm.
92 (L) x 92 (W) mm.
Terminals are from backward.
Electrical details
Supply Voltage Range
Contact Type
Contact Rating
Frequency
Auxillary supply
Unbalance Trip Setting
Tolerance
Under Volt trip setting
Tolerance
Over Volt Trip setting
Tolerance
Trip Time Delay
Fault Reset
28
REVISION A
UPDATED ON 28/08/2012
29
REVISION A
UPDATED ON 28/08/2012
30
3. Remove the nuts from service panel safely and handle the service panel along with motor and
blowers.
4. Remove the ventures of the housing assemble and loose the Grub screw of damaged impeller by
Ellen key then remove it safely.
5. Replace the impeller then tight the side ventures check the impeller curves direction it should be in
forward position check the rotation and positioning of the impeller. Tight the grub screws by seeing
proper alignment of the impeller.
6. Reassemble the unit.
Collect the refrigerant in CDU and close service valves (Suction 1 1/8 & liquid 5/8).
REVISION A
UPDATED ON 28/08/2012
31
REVISION A
UPDATED ON 28/08/2012
32
REVISION A
UPDATED ON 28/08/2012
33
REVISION A
SAP Code
1022437
1022438
1022432
1022428
1020797
1014252
1509427
1509554
1509555
1021466
1509556
1509557
1022699
1022700
1509558
1001689
1021478
1020721
1000050
1020720
1015038
1020566
1003315
1003271
1004697
1003332
1003370
1004696
1003305
1017365
1022298
1001844
1005614
1021957
1004406
Part Name
ASSY. BASE PAN
COMPRESSOR ASSY. (DIGITAL SCROLL)
SUCTION ACCUMULATORS
CONTROL BOX ASSY.
PCB ASSY. ODU, 11HP, 2AP5-60-402-1
CT PCB (2AL5-40-402-2)
SIDE PANEL RIGHT
TOP & BOTTOM PAD, COND. COIL
ASSY. BARE COIL CONDENSER
HEADER ASSY. (DISCHARGE)
HEADER ASSY. (LIQUID)
TUBE LIQUID
ASSY. TUBE SUCTION 'A'
TUBE SUCTION 'B'
INSULATION, SUCTION TUBE 'A' - 1680LONG
INSULATION, SUCTION TUBE 'B' - 970LONG
TUBE DISCHARGE ASSY.
SERVICE VALVE 1-1/8"
SERVICE VALVE 5/8" (R410A)
L P SWITCH, HS200 (HS200-13-0112) - WILSPEC
VALVE CORE ( 02AX5-02-326 )
H P SWITCH, HS200 (HS200-13-0113) - WILSPEC
RETAINER
CORNER POST LEFT
CENTER POST
REFRIGERANT R-410A
FAN DECK ASSY.
MOTOR MOUNTING BRACKET
M8 X 16 FLANGE BOLT IN M.S.NICKEL PLATED
M8 NYLOK NUT IN NICKEL PLATING YELLOW
PLAIN WASHER M8 (BIG OD)
HEX. HD BOLT M6 x 15 (HIGH TENSILE)
HEX. NUT M6 (HIGH TENSILE)
PLAIN WASHER M6 (BIG OD)[5002-00-006]
SPRING WASHER M6
FAN PROPELLER (19.5") Plastic
MOTOR 1/6 HP (PICL)
RUBBER WASHER
GRILLE COND. BACK
GRILLE COND. SIDE
FAN GUARD
TOP COVER
PANEL ACCESS
STICKER AIR DIRECTION
STICKER DIGITAL R410-A
STICKER CARRIER
Qty.
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
2
1
7.6 Kg.
1
2
8
8
8
8
8
8
8
2
2
8
2
2
2
1
1
1
1
1
UPDATED ON 28/08/2012
34
REVISION A
UPDATED ON 28/08/2012
35
REVISION A
SAP CODE
1021769
1003339
1003280
1018406
1018405
1018404
1021758
1003315
1003371
1004697
1509419
1509551
1509552
1014556
1003303
1000050
1021683
1019457
1004517
1004515
1022433
1022430
1020798
1022697
1018411
1004406
1004451
1015038
1021957
Part Name
ASSY. DRAIN PAN (PAINTED)
BOTTOM PANEL (PAINTED)
ASSY. SIDE PANEL LEFT (PAINTED)
ASSY. SIDE PANEL RIGHT (PAINTED)
HANGER BRACKET (PAINTED)
HANGER STICKER (3ASP5-00-152)
HEX. HD. BOLT M8 x 25mm (HIGH TENSILE)
PLAIN WASHER M8 (SMALL OD)
ASSY. FAN DECK (PAINTED)
ASSY.BLOWER HOUSING
BLOWER (DIA 8" X 10"W)
MOTOR 3/4 HP -1300 RPM (PICL)-DOUBLE SHAFT
MOTOR 3/4 HP -1300 RPM (PICL)-SINGLE SHAFT
M8 x 16 FLANGE BOLT
HEX. NUT M8 (HIGH TENSILE)
PLAIN WASHER M8 (BIG OD)
BRACKET COIL LEFT (PAINTED)
BRACKET COIL RIGHT (PAINTED)
ASSY.BARE COIL EVAPORATOR
ASSY. LIQUID TUBE
ASSY. SUCTION HEADER
TUBE SENSOR
SCREW METRIC PAN HEAD
VALVE CORE ( 02AX5-02-326 )
ASSY. TUBE LIQUID 'B'
FILTER DRIER DCL-165
DEAD NUT 5/8"
RUBBER WASHER 5/8"
CLAMP FILTER DRIER (PAINTED)
CONTROL PANEL ASSY.-IDU, 11HP, 3BP5-60-300
PCB ASSY. IDU, 11 HP, 3BP5-60-402
WIRED REMOTE LCD DISPLAY (3BL5-50-306)
ASSY. TOP PANEL (PAINTED)
DRAIN PAN PILLER-A (PAINTED)
FILTER COMP.
GROMMET (DIA.-50)
STICKER 'CARRIER' LOGO
GROMMET
RETAINER
STICKER DIGITAL R410-A
UPDATED ON 28/08/2012
QTY
1
1
1
1
4
2
12
12
1
3
3
1
1
8
8
8
1
1
1
01
01
2
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
3
1
1
36
TABLE 4: TROUBLESHOOTING CHART
SYMPTOMS
CAUSE
REMEDY
Tripping
Shaft
MECHANICAL :
service instruction
Compressor seized
Replace compressor
Tripping
evacuate, charge
Replace compressor
Compressor
Noise and vibration
loose bracket
Fan motor bearing worn out
Undersized
Piping vibration
Overcharged refrigerant
Loosening of compressor
Replace compressor
Components / parts
Compressor motor rotates in
Backward direction
Terminal
REVISION A
UPDATED ON 28/08/2012
37
ELECTRICAL
Unit not operating
Replace
- Loose connection
Tighten connection
place
Contactor stuck open
Replace contactor
Replace compressor
Current
Fan motor speed low / motor
Defective
Condenser fan tripping
Replace Contactor
Loose connections
Add refrigerant
Open it totally
REVISION A
UPDATED ON 28/08/2012
38
valve
Procedure
Rectify
Applicable
incorrect installation
Overcharging of refrigerant
Compressor runs
to warm place
cut
Defective control box
SYSTEM
Unit does not cool
Refrigerant leak
adequately
Evacuate, charge.
Compressor motor rotates in
backward direction
compressor terminal
Refrigerant undercharged
REVISION A
Replace or repair
quantity
installation
UPDATED ON 28/08/2012
39
Overcharged system
Refrigerant contaminated
Open it totally
line
refrigerant
REVISION A
UPDATED ON 28/08/2012
40
TABLE 6 : START-UP CHECKLIST
Equipment sold by:
Installed by:
Site address:
Deg. C / F
Deg. C / F
Supply voltage:
Phase 1 -
Phase 2 -
V Phase 3 -
Phase unbalance:
Phase 1 -
Phase 2 -
V Phase 3 -
Main:
Phase 1 -
Phase 2 -
A Phase 3 -
Compressor:
Phase 1 -
Phase 2 -
A Phase 3 -
Phase 1 -
Phase 2 -
A Phase 3 -
Phase 1 -
Phase 2 -
A Phase 3 -
Current drawn:
Suction pressure 1:
kPa / psig,
Discharge pressure 1:
kPa / psig
Suction pressure 2:
kPa / psig,
Discharge pressure 2:
kPa / psig
Room temperature:
Dry bulb:
Wet bulb:
Deg C / F
Dry bulb:
Wet bulb:
Deg C / F
Dry bulb:
Wet bulb:
Deg C / F
Dry bulb:
1
Wet bulb:
Deg C / F
2
Deg C / F
REVISION A
UPDATED ON 28/08/2012
41
TIPS
FOR MAXIMUM COMFORT AND POWER CONSUMPTION, FOLLOW THESE HELPFUL TIPS:
Avoid direct sunlight in room. Use curtains and cover at windows and doors
but avoid obstacles. Dont cover the A/C.
Close seal all opening /crevices in conditioned space. Install outdoor in well
ventilated space to avoid short cycling of hot condenser air. Install unit with
minimum recommended clearances and within specified distance between
indoor/outdoor unit for optimum performance.
For exhaust purpose, switch ON only the FAN with doors /windows open for
ventilation. Do not run in COOL mode.
SELF SERVICE: Before calling to the Carrier Service, there are certain things you can check by yourself.
Refer to the Table.1
Problem
Unit does not start
Possible cause
Solution
Blown fuse.
Re plug properly.
Filter dirty.
Clean filter.
Filter dirty.
Clean filter.
REVISION A
UPDATED ON 28/08/2012
42
CARRIER SERVICE
REST ASSURED
Certain normal sounds made by the unit
Dripping noise
The sound of liquid refrigerant passing through the system
Humming noise
Motor noise when unit is in operation or when fan is working and the
fluctuation in voltage /frequency is more than normal .
All these sounds signify that the unit is working normally and room temperature is being monitored
as required. If ever your unit fails to operate properly, contact the Carrier Authorized Dealer. If you are still
dissatisfied, get in touch with the Carrier Service Center.
REVISION A
UPDATED ON 28/08/2012
43
CARRIER AIR CONDITIONING & REFRIGERATION LTD.
Date of purchase:
Invoice No:
Name & Address of the Dealer:
Signature of the Dealer with Seal.
Clauses on next page will form the terms and conditions for this warranty.
TERMS & CONDITIONS
The Warranty will be applicable only for the specified period indicated above, irrespective of whether the air
conditioner has been in use for any reason whatsoever, including any break down, time taken for repairs
/replacements and transmit time etc. The warranties will automatically expire/terminate on completion of the
period indicated above and no notice whatsoever will be given to this effect.
All parts failing due to faulty material or defective workmanship pertaining to the above DUCTED airconditioner will be repaired /replaced within the warranty period by Carrier Air Conditioning & Refrigeration
Ltd. (C.A.R.L) or by the authorized Dealer as intimated by C.A.R.L.
During the period of warranty it will be obligatory on the part of customer that the air conditioning machine is
serviced /repaired /attended to/installed /reinstalled only by the authorized Dealer of C.A.R.L and in case the
unit is attended to by any other agency, the warranty stands automatically terminated.
For units installed beyond the Municipal limits of the jurisdiction of the authorized Dealer of C.A.R.L all
expenses incurred in collecting the unit or parts there of from the Service Station of the Dealer of C.A.R.L as
expenses incurred in connection with deputing of Service Personnel /technician towards to &fro travel,
conveyance and other incidentals etc., will be borne by the customer and payable in advance.
The guarantee extended here is in lieu of all implied conditions and warranties under the law and is
confirmed to the repair or replacement of defective parts and does not cover any consequential or resulting
liability damage or loss arising from such defects. Furthermore, the guarantee, in no case, shall extend to
the payment of any monetary consideration whatsoever, or the replacement or return of the AC as a whole.
It is obligatory on the part of the customer that in case there is any change in the location of the unit and /or
change in the ownership, he should immediately intimate in writing to C.A.R.L or its servicing Authorized
Dealer, at least a week before such change takes place. In such case, the warranty period will be reckoned
REVISION A
UPDATED ON 28/08/2012
44
on pro-rate basis for the new location/ownership from the date of such changes as the case may be.
Failure to do so will totally absolve C.A.R.L /authorized dealer of their obligation under this warranty.
Further, for continuation of this warranty at the new location and /or new ownership, fresh installation
charges and inspection fee for the units as well as the cost of rectification of any damage in transit due to
mishandling shall be added to the customers account and shall be paid in advance .In case, for any reason,
the customer/owner does not want to carry the repairs after the inspection of the unit, the inspection fees will
not be refunded to the customer.
The decision of C.A.R.L /Authorized Dealer will be final as to whether to affect the repair or replace parts at
the new site /location.
Any loss of refrigerant due to sabotage, man handling, wrong installation by the user or damage caused due
to accidents, fires, floods or earthquakes etc. or for any other reason or any corrosive action on refrigerant
pipes, fitting, valves etc. are not covered under warranty free of cost replenishment of such refrigerant or
pipes, fitting & valves.
This warranty is applicable only when the purchaser has paid all money in relation to the purchase and
installation of this product to C.A.R.L. or to its channel partners.
REVISION A
UPDATED ON 28/08/2012
45
1800 30 111111
REVISION A
UPDATED ON 28/08/2012
46
REVISION A
UPDATED ON 28/08/2012