PROJECT: WAREHOUSE BUILDING

PLANNED COMPLETION DATE SUMMARY OF MDB -01,02 & 3

(SHEET 1 OF 1)
RATING AMPS

DB NO.

TP

ISO

MCCB

PLOT NO.

CONSULTANT : M/S. YAGHMOUR ENGINEERING CONSULTANTS

AREA

PVC/

DUTY

XLPE

KA

SWA/

2/4 X

PVC

IC mm2

F/S
SP

OWNER : M/S. MAG ME REAL ESTATE LLC.

FAULT

CIRCUIT
FEEDER

LOCATION OF MDB'S : ELECTRICAL ROOM

DETAILS OF CONNECTED LOAD/MAX. DEMAND

MCB

CABLE SIZE

ECC

CONNECTED LOAD KW

: 365-3907

: AL QUOZ IND. SECOND

PROPOSED KWH METERING

REMARKS

SIZE

R-PH

Y-PH

B-PH

I-PH

3-PH

3-PH

CT

2/3/4C

IC

KW

KW

KW

(1)

(2)

(3)

(4)

mm2

mm2

162.97

163.54

163.49

TOTAL .

2NO 300/5A&1NO 400/5A 0.2S C.T.


METER

2x1C,95

55.00

55.00

55.00

165.00

STORAGE-01

ACB

INCOMER

TP

SUMMARY

MCCB

OUTGOING

MDB - 01

TP

300

35

BY DEWA

MDB - 02

TP

300

35

BY DEWA

2x1C,95

55.06

54.97

54.97

165.00

STORAGE-02

MDB - 03

TP

400

45

BY DEWA

2X1C,150

52.91

53.57

53.52

160.00

ELECTRICAL ROOM

TOTAL=490KW

MDB'S CONNECTED TO : DEWA Trasformer

162.97
MAX DEMAND 3 (PH)457. KW AT 1/0.90DIVERSITY

163.54

TOTAL CONNECTED LOAD 3 ( PH)........

163.49

490.00 KW

CONTRACTOR : FUJAIRAH NATIONAL CONSTRUCTION

PROVIDE CT-METER WHEN MAX.DEMAND - 100 KW

P. O. BOX : 16269 - DUBAI , TEL . NO : 04 - 3938888

(1) 20-80A (2) 30-90/120A (3) 100-200A (4) ../5A

1 OF 4

PROJECT: WAREHOUSE BUILDING

LOCATION OF MDB - 01 : STORAGE-01

DETAILS OF CONNECTED LOAD/MAX. DEMAND

PLANNED COMPLETION DATE -

OWNER : M/S. MAG ME REAL ESTATE LLC.

PLOT NO.

MDB - 01

CONSULTANT : M/S. YAGHMOUR ENGINEERING CONSULTANTS

AREA

(SHEET 1 OF 1)
RATING AMPS

FAULT

PVC/

DUTY

XLPE

KA

SWA/

2/4 X

PVC

IC mm2

CIRCUIT
FEEDER
DB NO.

F/S
SP

TP

ISO

MCCB

MCB

CABLE SIZE

ECC

CONNECTED LOAD KW

: 365-3907

: AL QUOZ IND. SECOND

PROPOSED KWH METERING

REMARKS

SIZE

R-PH

Y-PH

B-PH

I-PH

3-PH

3-PH

CT

2/3/4C

IC

KW

KW

KW

(1)

(2)

(3)

(4)

mm2

mm2

ACB

INCOMER

TP

300
MCCB

TP

100

OUTGOING

DB -01

300/5A 0.2S C.T. METER


2x1C,95
35
BY DEWA
55.00
55.00
55.00
TOTAL

1
TO 300A TP ISOLATOR AT MDB - 01 - 1x4C,185sq.mm XLPE/SWA/PVC. CU + 1C,95 sq.mm CU/Y/G PVC(ECC) FROM CT METER- 01

25

XLPE/SWA/PVC

4C,35

1C,16

16.00

16.00

16.00

48.00

STORAGE- 01

SPARE

TP

80

25

13.00

13.00

13.00

39.00

FOR FUTURE LOAD

SPARE

TP

80

25

13.00

13.00

13.00

39.00

FOR FUTURE LOAD

13.00

13.00

13.00

39.00

FOR FUTURE LOAD

XLPE/SWA/PVC

4C,35

1C,16

SPARE

TP

80

25

CAPACITOR BANK-01

TP

100

25

ELECTRICAL ROOM

4 STEPS 45 KVAR CAPACITOR BANK ( 5+10+10+20)

SPARE LOAD WILL BE FOR FUTURE LIGHTING AND SMALL POWER LOAD ONLY.

ASSUMING A P.F 0.78 FOR 165 KW, TO ACHIEVE 0.9 P.F LAGGING WE REQUIRE 165 x 0.31 = 51.15 KVAR
WE PROPOSED 4 STEPS (5+10+10+20) 45 KVAR AUTOMATIC CAPACITOR BANK

MDB - 01 CONNECTED TO : DEWA Trasformer


DB'S CONNECTED TO MDB - 01

MAX DEMAND 3 (PH). 148.5 KW AT 0.9DIVERSITY

55.00

55.00

TOTAL CONNECTED LOAD 3 ( PH)........

55.00

TOTAL=165KW

165.00 KW

CONTRACTOR : FUJAIRAH NATIONAL CONSTRUCTION

PROVIDE CT-METER WHEN MAX.DEMAND - 100 KW

P. O. BOX : 16269 - DUBAI , TEL . NO : 04 - 3938888

(1) 20-80A (2) 30-90/120A (3) 100-200A (4) ../5A

2 OF 4

PROJECT: WAREHOUSE BUILDING

LOCATION OF MDB - 02 : STORAGE-02

DETAILS OF CONNECTED LOAD/MAX. DEMAND

PLANNED COMPLETION DATE -

OWNER : M/S. MAG ME REAL ESTATE LLC.

PLOT NO.

MDB - 02

CONSULTANT : M/S. YAGHMOUR ENGINEERING CONSULTANTS

AREA

(SHEET 1 OF 1)
RATING AMPS

FAULT

PVC/

DUTY

XLPE

KA

SWA/

2/4 X

PVC

IC mm2

CIRCUIT
FEEDER
DB NO.

F/S
SP

TP

ISO

MCCB

MCB

CABLE SIZE

ECC

CONNECTED LOAD KW

: 365-3907

: AL QUOZ IND. SECOND

PROPOSED KWH METERING

REMARKS

SIZE

R-PH

Y-PH

B-PH

I-PH

3-PH

3-PH

CT

2/3/4C

IC

KW

KW

KW

(1)

(2)

(3)

(4)

mm2

mm2

ACB

INCOMER

TP

300
MCCB

TP

80

OUTGOING

DB -02

300/5A 0.2S C.T. METER


2x1C,95
35
BY DEWA
55.06
54.97
54.97
TOTAL

1
TO 300A TP ISOLATOR AT MDB - 02 - 1x4C,185sq.mm XLPE/SWA/PVC. CU + 1C,95 sq.mm CU/Y/G PVC(ECC) FROM CT METER- 02

25

XLPE/SWA/PVC

4C,35

1C,16

13.40

13.30

13.30

40.00

STORAGE- 02

SPARE

TP

100

25

15.00

15.00

15.00

45.00

FOR FUTURE LOAD

SPARE

TP

100

25

15.00

15.00

15.00

45.00

FOR FUTURE LOAD

11.66

11.67

11.67

35.00

FOR FUTURE LOAD

XLPE/SWA/PVC

4C,35

1C,16

SPARE

TP

80

25

CAPACITOR BANK-02

TP

100

25

ELECTRICAL ROOM

4 STEPS 45 KVAR CAPACITOR BANK ( 5+10+10+20)

SPARE LOAD WILL BE FOR FUTURE LIGHTING AND SMALL POWER LOAD ONLY.

ASSUMING A P.F 0.78 FOR 165 KW, TO ACHIEVE 0.9 P.F LAGGING WE REQUIRE 165 x 0.31 = 51.15 KVAR
WE PROPOSED 4 STEPS (5+10+10+20) 45 KVAR AUTOMATIC CAPACITOR BANK

MDB - 02 CONNECTED TO : DEWA Trasformer


DB'S CONNECTED TO MDB - 02

MAX DEMAND 3 (PH). 148.5 KW AT 0.9DIVERSITY

55.06

54.97

TOTAL CONNECTED LOAD 3 ( PH)........

54.97

TOTAL=165KW

165.00 KW

CONTRACTOR : FUJAIRAH NATIONAL CONSTRUCTION

PROVIDE CT-METER WHEN MAX.DEMAND - 100 KW

P. O. BOX : 16269 - DUBAI , TEL . NO : 04 - 3938888

(1) 20-80A (2) 30-90/120A (3) 100-200A (4) ../5A

3 OF 4

PROJECT: WAREHOUSE BUILDING

LOCATION OF MDB - 03 : ELECTRICAL ROOM

DETAILS OF CONNECTED LOAD/MAX. DEMAND

PLANNED COMPLETION DATE -

OWNER : M/S. MAG ME REAL ESTATE LLC.

PLOT NO.

MDB - 03

CONSULTANT : M/S. YAGHMOUR ENGINEERING CONSULTANTS

AREA

(SHEET 1 OF 1)
RATING AMPS

CIRCUIT
FEEDER
DB NO.

F/S
SP

TP

ISO

MCCB

FAULT

PVC/

DUTY

XLPE

KA

SWA/

2/4 X

PVC

IC mm2

MCB

CABLE SIZE

ECC

CONNECTED LOAD KW

: 365-3907

: AL QUOZ IND. SECOND

PROPOSED KWH METERING

REMARKS

SIZE

R-PH

Y-PH

B-PH

I-PH

3-PH

3-PH

CT

2/3/4C

IC

KW

KW

KW

(1)

(2)

(3)

(4)

mm2

mm2

ACB
400/5A 0.2S C.T MAIN METER
2x1C,150
45
BY DEWA
52.91
53.57
53.52
TOTAL

1
TO 400A TP ISOLATOR AT MDB - 03 - 1x4C,300sq.mm XLPE/SWA/PVC. CU + 1C,150 sq.mm Y/G PVC CU. AS ECC FROM METER BOX - 03

TP

400
MCCB

FIRE PUMP

TP

300

35

XLPE/SWA/PVC

4C, 185

1C,95

36.66

36.67

36.67

110.00

DB - PR

TP

40

25

XLPE/SWA/PVC

4C,10

1C,10

5.65

5.70

5.65

17.00

DB - TR

TP

40

25

XLPE/SWA/PVC

4C,10

1C,10

5.10

5.70

5.70

16.50

TELEPHONE ROOM

DB - EL

TP

40

25

XLPE/SWA/PVC

4C,10

1C,10

5.50

5.50

5.50

16.50

ELECTRICAL ROOM

CAPACITOR BANK-03

TP

160

35

XLPE/SWA/PVC

4C,70

1C,35

5 STEPS 65 KVAR CAPACITOR BANK ( 5+10+10+20+20)

INCOMER
OUTGOING

100mA ELS+ALARM
INSIDE OF PUMP ISO

300A TP ISOLATOR FOR FIRE


PUMP

PUMP ROOM

ELECTRICAL ROOM

ASSUMING A P.F 0.78 FOR 160 KW, TO ACHIEVE 0.9 P.F LAGGING WE REQUIRE 160 x 0.31 = 49.6 KVAR
WE PROPOSED 5 STEPS (5+10+10+20+20) 65 KVAR AUTOMATIC CAPACITOR BANK

MDB - 03 CONNECTED TO : DEWA Trasformer


FIRE PUMP CONNECTED TO MDB - 03

MAX DEMAND 3 (PH). 160 KW AT 1DIVERSITY

52.91

53.57

TOTAL CONNECTED LOAD 3 ( PH)........

53.52

TOTAL=160KW

160.00 KW

P. O. BOX : 16269 - DUBAI , TEL . NO : 04 - 3938888

PROVIDE CT-METER WHEN MAX.DEMAND - 100 KW

PROJECT: WAREHOUSE BUILDING

(1) 20-80A (2) 30-90/120A (3) 100-200A (4) ../5A

P. O. BOX : 16269 - DUBAI , TEL . NO : 04 - 3938888

(1) 20-80A (2) 30-90/120A (3) 100-200A (4) ../5A

4 OF 4