C&R Panel (Without Automation) - Aug, 2016
C&R Panel (Without Automation) - Aug, 2016
CHIEF ENGINEER/MM,
DESIGN DIRECTORATE, HVPNL,
SHAKTI BHAWAN, Basement,
SEC-6, PANCHKULA 134109
(HARYANA)
Tel./Fax No. 0172-2583724
CONTENTS
-------------------------------------------------------------------------------CLAUSE NO.
TITLE
PAGE NO.
--------------------------------------------------------------------------------1.0
2.0
3.0
4.0
5.0
6.0
7.0
SCOPE
STANDARDS
SERVICE CONDITION
PRINCIPAL PARAMETERS
GENERAL TECHNICAL REQUIREMENTS
TESTS
DOCUMENTATION
3
3
4
5
5
24
25
ANNEXURES
A.
B.
C.
D.
E.
F.
G.
H.
I.
SCHEDULE OF REQUIREMENTS
GUARANTEED TECHNICAL PARTICULARS
TECHNICAL PARTICULARS OF CTs, PTs, CVTs AND NCTs
TRANSMISSION LINE DATA
SCHEDULE OF DEVIATIONS FROM THE SPECIFICATION
LINE PARAMETERS
ANNUNCIATION DETAILS
DETAILS OF CARRIER EQUIPMENTS
PANELS MOUNTING DETAILS
27
28
37
56
57
58
59
63
64
---------------------------------------------------------------------------------
1.0
1.1
1.2
1.3
1.4
14.1
14.2
SCOPE:
This specification covers the design, engineering, manufacture, inspection & testing at
manufacturer's work before despatch, packing, forwarding and delivery at discretion of
purchaser of control & relay boards for 220kV, 132kV & 66kV S/Stns. listed in the
schedule of requirement at Annexure 'A'.
Unless specifically excluded from the offer, all fittings and accessories, not specifically
stated in this specification but which are necessary for satisfactory operation of the
scheme or to complete the work in a good workman like manner shall be deemed to have
been included in the scope of supply of the Bidder.
CO-ORDINATION :
Circuit Breakers, CT's, PT's/CVT's & Isolating Switches, etc. are being purchased against
separate specification. The particulars of CTs, PTs and CVTs existing/ to be arranged are
listed at Annexure 'C'. The Supplier of control & relay boards shall be responsible for
preparing complete wiring diagram of 33kV,66kV,132 kV & 220 kV C&R panel boards and
shall also undertake to mount & wire any equipment received from other supplier. The
schematic of breakers & isolators are required to be incorporated in the panel schematic.
EXPERIENCE:
For 400kV & 220kV C&R Panels:
The supplier of C&R panels shall be manufacturer of relays and all the main relays on the
C&R panels shall be of his make only. However, one of the distance protection schemes
on each 220 kV feeder C&R panel can be of different make in view of the fact that both
the distance protection scheme (Main-I & Main-II) should have different measuring
techniques.
For 132kV, 66kV & 33kV C&R Panels:
The supplier of C&R panels shall be manufacturer of relays and all the main relays on the
C&R panels shall be of his make only. The suppliers own make relay includes the relays
manufactured by their Principals/Associates and they have their service centre with them.
2.0
2.1
STANDARDS:
The equipment offered shall conform to latest relevant Indian Standards listed hereunder
or equivalent IEC: Sr. No.
Standard
Title
1.
IS: 5
Colour for ready mix paints.
2.
IS: 375
Marking & arrangements for switchgear, bus bars, main
connections & auxiliary wiring.
3.
IS: 694
PVC insulated cable for working voltage upto and including
1100 V.
4.
IS: 722
AC Electricity meters.
5.
IS: 1248
Direct acting indicating analogue electrical measuring
Part-I& IV
instruments & their accessories.
6.
IS: 2419
Dimensions for panel mounted indicating & recording
electrical instruments.
7.
IS :3231
Electrical relays for power system protection.
8.
IS :8686
Static protective relays.
9.
IS :2147
Degree of protection provided by enclosures for low voltage
switchgear & control gear.
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
3.0
3.1
In addition to meeting the specific requirement called for in the Technical Specification,
the equipment shall also conform to the general requirement of the relevant standards
and shall form an integral part of Specification.
The Bidder shall note that standards mentioned in the specification are not mutually
exclusive or complete in themselves, but intended to compliment each other.
The Contractor shall also note that list of standards presented in this specification is not
complete. Whenever necessary the list of standards shall be considered in conjunction
with specific IS/IEC.
When the specific requirements stipulated in the specification exceed or differ than those
required by the applicable standards, the stipulation of the specification shall take
precedence.
Other internationally accepted standards which ensure equivalent or better performance
than that specified in the standard referred shall also be accepted.
In case governing standards for the equipment is different from IS or IEC, the salient
points of difference shall be clearly brought out alongwith English language version of
standard or relevant extract of the same. The equipment conforming to standards other
than IS/IEC shall be subject to Employer's approval.
The bidder shall clearly indicate in his bid the specific standards in accordance with which
the works will be conformed.
SERVICE CONDITIONS:
Equipment to be supplied against this specification shall be suitable for satisfactory
continuous operation under the following tropical conditions:i)
Location
IN THE STATE OF HARYANA
ii)
Max. ambient air temp (C)
50
iii)
Min. ambient air temp (C)
-2.5
iv)
Maximum Relative humidity (%)
100
v)
Minimum Relative humidity (%)
26
vi)
Average annual rainfall (mm)
900
vii)
Max. wind pressure (kg/sq. m.)
195
viii)
Max. altitude above mean sea level (meters).
1000
ix)
Isoceraunic level (days/Year)
50
x)
Seismic level (horizontal acceleration)
0.3 g
xi)
Average number of dust storm
35
(days per annum)
Note:i)
Moderately hot and humid tropical climate conducive to rust and fungus growth. The
climatic conditions are also prone to wide variations in ambient conditions.
ii)
Air conditioning or any special arrangement for making the control room dust proof shall
not be provided in any of the S/Stn.
3.2
All control wiring, equipment & accessories shall be protected against fungus growth,
condensation, vermin & other harmful effects due to tropical environments.
3.3 AUX. POWER SUPPLY :
i)
A.C. Supply
:
415/240 Volts, 3-phase, 4-wire, 50 Hz
Voltage variation
:
10%
Frequency variation :
3%
ii)
D C Supply
:
220 Volts, 2 wire available from S/Stn.
battery(insulated)
Variation
:
10%.
3.4.1.1 220 kV, 132 kV, 66 kV & 33 kV voltages will be three phase having normal frequency of
50 Hz subject to a variation of 3%. Neutrals of the Power Transformers at the S/Stn.
covered in this specification are solidly earthed.
4.0
4.1
PRINCIPAL PARAMETERS:
The panel shall have the principal dimensions as detailed below:= 610
mm
i. Depth of panels
ii. a) Height of switchboard above base frame
b) Height of base frame
iii. Width of corridor in case of duplex panels
=
=
=
2210 mm
102 mm
762
mm
v. TYPE OF PANEL :
a) Simplex control & relay panels for all 33 kV, 66kV, & 132 kV circuits.
b) Duplex control & Relay panels for all 220 kV circuits.
Note:- The offer of the bidder not conforming to above requirement shall be out rightly rejected.
4.2.1
MIMIC DISPOSITION:
The mimic disposition on control panel should be matching to our standard drawings; the
details of which will be supplied to successful Bidders.
4.2.2 MIMIC SCHEME:
Mimic diagram shall be of overlaid strip type and shall be made up of metal sheet
or plastic (width 10 mm for horizontal and 7 mm for vertical and thickness of both
3 mm) fixed on the control and relay boards with help of screws covered by the
specification. Placement of the mimic diagram shall be 75 mm from top of the panel
with a spacing of 60 mm between the buses. Automatic semaphores for indicating
'open' and 'close' position of circuit breakers, isolators & earth switches shall be suitable
incorporated in the mimic diagram. The colour scheme for all the S/Stn. specified herein
shall, however, be as under;--------------------------------------------------------------------------------------------------------------------------------Voltage Level
Colour
Shade No. (According to IS:5 or Equivalent
IEC)
--------------------------------------------------------------------------------------------------------------------------------220 kV
Dark brown
412
132 kV
Black
66 kV
Golden brown
414
33 kV
Brilliant-green
221
11 kV
Signal red
537
--------------------------------------------------------------------------------------------------------------------------------4.3
ARRANGEMENT OF PANELS:
The panels shall be fabricated so that even if the serial of panels is changed no difficulty
will be faced in the placement of panels and cabling etc. The sequence of various panels
in a panel board at a S/Stn. shall be supplied to successful bidder.
5.0
5.1
5.2
5.3
5.4.
5.5
5.6
5.7
in his tender and submit such full information, drawings and specifications as will enable
the merit of his proposal to be appreciated.
In the event of contractor drawings, specification and tables etc. disagreeing with this
specification during the execution of the contract this specification shall be held binding
unless the departures have been fully recorded as required above.
PAINTING:
All unfinished surfaces of steel panels and frame works shall be sand blasted to remove
rust scale, foreign adhering matter & grease. A suitable rust resistance primer shall be
applied on the interior & exterior of steel which will be followed by application of an under
coat suitable to serve as base for finishing coat. The finishing coat shall be as under: Exterior
Stove enameled light grey as per shade No.631 of IS: 5/IEC.
Interior
stove enameled white.
Base frame Stove enameled glossy black.
TESTING EQUIPMENT AND TESTING FACILITIES ON THE RELAYS:
The tenderer shall recommend suitable testing equipment (alongwith quantity) required
for field testing of protective schemes and other relays offered against this specification.
The actual quantity to be ordered shall be determined by the Purchaser.
Also adequate testing facilities should be provided on the relay so as to test them without
the necessity of their removal or making any extra connections. The Bidder will clearly
indicate the testing procedure to be followed in respect of relays offered.
The transmission lines shall be either in form of overhead conductor or
combination of overhead conductor & underground cable. The tentative transmission
line data in respect of 220kV, 132kV & 66 kV lines covered in this specification is given at
Annexure-D.
The standard chart providing the details of per unit values of Z1, Z2 & Z0 on 100 MVA base
per 100 km of line for calculating these values for full lengths of lines are enclosed at
Annexure-F.
The tentative details of carrier equipment are enclosed at Annexure-H.
The suitability of distance scheme offered with reference to the above parameters may be
seen.
Guaranteed test sheets as per Annexure B shall be submitted by the tenderer. Relevant
literature shall be supplied along with the bid for proper appreciation of the offered
equipment.
SUPERVISORY SERVICES:
The tenderer may offer supervisory services, panel wise testing & commissioning of
220kV, 132 kV, 66 kV & 33 kV panel included in the specification. The tenderer may quote
their rates on diem basis category-wise with their terms & conditions. The rates quoted
should be valid for at least three years form the date of receipt of equipment by us.
TRANINING OF PERSONNEL:
The contractor will provide free facilities for training the purchaser's technicians /Engineers
at his works, design office and HVPNL's site. He will intimate in advance the schedule of
completion of designs and manufacture of equipment against the contract (of this
specification) or similar equipment to be manufactured at the works so that the purchaser
may depute upto 3 technicians & 3 engineers for training at the manufacture assembly,
testing, operation and commissioning etc. including testing and commissioning of
protective relays, covering training in detecting faults in static relays complete explanation
of the schematic wiring and wiring schedule of the relays/scheme together with full
understanding regarding the functional modules of the relays/scheme shall be given to the
Engineer / technicians. The topics of CTs & PTs towards relay application shall also be
kept under the scope of training. The training shall be arranged by the contractor at the
works in such a way that the persons under training shall be freely acquainted with the
equipment. The engineers / technicians shall also be provided with relay/scheme
guides/instruction manuals covering drawings of functional modules of relays/schemes.
The period of training will be not exceeding 15 days and all expenses shall be borne by
the purchaser.
5.8
GENERAL DESCRIPTION:
5.8.1. DUPLEX C&R PANEL BOARDS:
The panel shall comprise of cubicles placed in juxta position to form continuous board. At
each Substation the relay boards shall be mounted back to back with the control board
and so arranged as to have a corridor carrier in between to provide access to internal
wiring. Hinged lockable access doors shall be fitted at both ends of the corridor and
switch boards interior shall be automatically lit by the opening of these doors.
The C&R panels tendered for Cl. No. 4.1(v) (b) above may match in the following
respects: i)
Height-wise and depth-wise matching including the matching in respect of corridor
width.
ii)
Size & disposition of mimic diagram matching.
The offered C&R panels shall be complete with side covers for each circuit, end access
doors with concealed hinges having a swing of not less than 105O in fully open position of
the doors.
The control and relay cubicles shall be made of sheet steel of thickness not less than 10
SWG for the base frame, door frame, front and rear portions of cubicle and not less than
14 SWG for doors, side, top & bottom portions.
The bottom of the cubicle frame shall be suitable for erection on flush concrete floor. The
trench, carrying the control cables, shall run at the back of erected C&R panel boards in
the switch house building. Evenly spaced grout bolts projecting through the base channel
forming members of the frame shall be used for securing cubicles to the floor.
The front panels of all cubicles shall be detachable and all inter-connections from the
control panel to the relay panel & vice -versa shall be through terminal connectors. The
inter-connections shall preferably run underneath the top cover.
The control & relay boards shall be completely dust & vermin proof. The enclosure shall
provide degree of protection not less than IP-54 in accordance with IS: 2147 and shall be
suitable for tropical use. All holes and extension windows in the panels shall be blanked
and access doors shall be lined with compressible liners at the edges.
NOTE:- For testing purpose a small opening with a cap to close the same is
required to be provided to extend the testing leads on front side of the relay
panel.
5.8.2. SIMPLEX C&R PANEL BOARDS:
The panel board for the substations mentioned at Cl. No. 4.1(v) (a) above shall be of
`simplex' type & consisting of separate cubicles (for each circuit complete with side
covers) made of sheet steel of thickness not less than 10 SWG for the base frame, door
frame and front portions of the cubicles and not less than 14 SWG for door, side, top &
bottom portion having provision for extension at both ends with internal wiring, illumination
with door operated off & on switch. The cubicle shall be suitable for floor mounting with
its bottom open. Each cubicle shall be fitted with flush mounted steel hinged door & lock
at the back & all the equipments will be mounted in front. The supply shall include
suitable grouting bolts and nuts etc. All holes and extension windows shall be blanked
and access doors shall be provided with compressible liners at the edges.
These simplex panels offered may, therefore, match in following respects:i)
Height-wise and depth-wise matching.
ii)
Size & disposition of mimic diagram matching.
The control & relay boards shall be completely dust & vermin proof. The enclosure shall
provide degree of protection not less than IP-54 in accordance with IS: 2147 and shall be
suitable for tropical use.
NOTE:- For testing purpose a small opening with a cap to close the same is
required to be provided to extend the testing leads on front side of the relay
panel.
5.9
SUPERVISION SCHEME:
SEMAPHORE INDICATORS:
5.9.3.2.
The annunciation ways for various 220 kV, 132 kV, 66 kV & 33 kV C&R panels shall be
provided as under:Description
220 kV
132 kV
66 kV
33 kV
Transformer
panel
Feeder
panel
Capacitor
panel
28
28
28
24
10
10
10
28
12
24
4
10
-
10
4
8
-
10
6
The detail of annunciations on all these panels is attached at Annexure G. All the 33kV,
66kV,132kV & 220 kV panels have trip as well as non trip annunciations, as such the
facia must have two buses; one for trip alarm and another for non trip alarm. All trip facia
shall have red colour and all non trip facia shall have white/Yellow colour.
5.9.4
5.9.4.1
ALARMS:
Alarm scheme for trip alarms:
Trip commands due to operation of protective relays will trip the breaker and light the
relevant annunciation window. Auxiliary contact of circuit breaker and trip bus of
annunciator will actuate bell (common to a panel board at a S/Stn.) & will be cancelled by
the circuit breaker control handle & Accept button of annunciator in case of all the panels
against this specification. Auto trip lamp will glow on the concerned panel & there will be
flag indication on the concerned protective relays/auxiliary relay of the panel.
5.9.4.2 Alarm scheme for non-trip alarms:
Non-trip commands will light the relevant annunciation window. Non- trip bus of
annunciator will actuate hooter (common to a panel board at a S/Stn.) & will be cancelled
by the Accept button of annunciator in case of all the panels against this specification.
5.10 METERING SCHEME :
5.10.1. All indicating and integrating instruments shall be of switch-board type back connected
suitable for flush mounting and provided with dust and vermin proof cases and finished in
egg shell bright black colour and shall be calibrated to read directly the primary quantities.
All fixing screws, nuts and threaded parts shall be designed to relevant Indian Standards.
All the instruments (i.e. Voltmeters, frequency meters & Wattmeters) shall be in square
pattern case and shall conform to the provisions of the latest edition of IS: 1248 & IS:
2419 or relevant I.E.C. standards. The nominal sizes of these indicating instruments shall
be 144 mm2. Energy meters shall conform to provisions of IS: 13779 amended up-to date
or relevant I.E.C. standards.
5.10.2 AMMETERS:
Ammeter shall be suitably scaled (additional dials, if any, required to cover all the taps of
the CT's shall be included at the time of tendering) and provided with a selector switch
facilitating the measurements of phase currents as well as the unbalance current. The coil
of the ammeter shall be rated for 5Amp. for 33kV, 1 Amp. for 66 kV, 132kV & 220 kV
levels . The instruments shall be of digital type of industrial grade `A' classification with
accuracy class 1.0 or better.
5.10.3 VOLTMETERS :
Voltmeter shall be suitably scaled and provided with selector switch (wherever asked for)
to facilitate the measurement of phase-to-phase and phase- to-neutral voltage of all the
three phases one by one. The coil of the voltmeter shall be rated for 110 volts (phase-tophase) wherever asked with selector switch and 110/3 volts if asked without selector
switch. The instrument shall be digital type of industrial grade `A' classification with
accuracy class of 1.0 or better.
10
5.11.3
5.11.3.1 Synchronizing switches shall be provided on each of the 220 kV feeder & bus coupler
panels to facilitate checking of various parameters with the instruments mounted on the
synchronizing panel.
5.11.3.2 Suitable interlock shall be provided in the closing circuits of C.B. so that the C.B. could be
closed only after the synchronizing (of the supplies) has been checked.
5.12
5.13
5.14
5.15
11
12
5.17
PROTECTION SCHEME:
Note:- 1. The Protection Scheme shall be suitable for 5A current (instead of 1A) in case of
33kV Level.
2. Overcurrent & Earth Fault relay for 11kV T/F panel has to be provide on LV side
i.e. 11kV VCB panel as per latest VCB panel specification of HVPNL.
5.17.1 PROTECTION SCHEME FOR POWER TRANSFORMERS.
A)
13
Xii)
B)
C)
D)
8No. auxiliary relays for various transformer trip functions (Main Buch. Trip, OLTC
Oil Temp. Trip, Winding Temperature Trip, Oil Temp Trip, Pressure Relief Trip, Surge
Relay Trip and two no. spare) shall be provided.
E)
Note:- The over fluxing relay in built with the numerical differential protection relay is
acceptable provided it meets the above specification.
F)
Note:- The over load alarm relay in built with the numerical differential protection relay or
Over current & Earth Fault Protection Relay is acceptable provided it meets the
above specification.
14
15
a3)
a4)
a5)
xx)
a1)
a2)
a3)
a4)
xxi)
xxii)
xxiii)
xxiv)
a)
b)
c)
16
B)
C)
17
a1)
a2)
a3)
a4)
a5)
xix)
a1)
a2)
a3)
a4)
xx)
xxi)
D)
i)
ii)
iii)
iv)
v)
vi)
i)
ii)
iii)
iv)
v)
vi)
E)
Note:-
The Feeder over Load Alarm Relay in-built with numerical distance
protection relay or Over current & Earth Fault Protection Relay is acceptable
provided it meets the above specification.
18
5.17.3
5.17.4
i.
ii.
iii.
iv.
v.
vi.
vii.
viii.
ix.
x.
xi.
xii.
xiii
xiv.
xv.
xvi.
xvii.
xviii.
xix
5.17.3.1
One bus bar protection scheme shall be provided for each main bus for 220kV
having double bus arrangement. Bus bar protection scheme shall:be of numerical, low impedance type and modular in construction. The scheme
shall be complete in all respects to cater the need of at-least 14 feeders/ bays.
have an operating time up-to trip impulse to trip relay for all types of faults less
than or equal to 15 milli seconds at 5 times setting value.
operate selectively for each bus bar.
give hundred percent security up-to 40 kA fault level.
incorporate check feature.
incorporate continuous supervision for CT secondaries against any possible open
circuit and if it occurs, shall tender the relevant zone of protection inoperative and
initiate an alarm.
not give false operation during normal load flow in bus bars.
incorporate clear zone indication.
be of phase segregated, triple pole type and provide independent zones of
protection for each bus.
include necessary auxiliary relays for each circuit as required for the scheme.
shall be biased differential type and shall have operate and restraint
characteristics.
be transient free in operation.
include continuous DC supply supervision for alarm and trip circuits separately
and provide separately non-trip alarm for B/B protection alarm circuit DC fail & B/B
protection trip circuit DC fail conditions.
shall include necessary multi-tap auxiliary CTs for each bay.
include protection 'in/out' switch for each zone.
include necessary CT switching relays. Also provide indication to monitor
`Operate' status of the CT switching relays with a common push button and shall
have CT selection incomplete alarm with adequate time delay when proper CT
switching has not taken place. CT switching relay should have adequate contacts
for selection of trip bus instead of direct isolator contact.
bus bar protection scheme should cover the blind zone on account of single CT
on B/C circuit.
Include high speed tripping relays for each bay.
The Scheme shall have in-built features of disturbance recorder and event logger.
The disturbance recorder should record the disturbance data bay-wise (all bays
phase and neutral current).
LOCAL BREAKER BACK UP PROTECTION SCHEME:
The relay shall be provided to take care of stuck breaker conditions. The local
breaker back up protection scheme will under such conditions, immediately after
the operation of primary / back up protection, transmit the tripping impulse to all
the circuit breakers connected to that bus zone of which the circuit breaker forms
19
part. The scheme shall be supplemented with a timer suitable for station DC
supply and continuously adjustable setting of .05 to .5 sec. on pick up.
The relay shall :
i)
be triple pole type with a setting range of 20% -80% of rated current.
ii)
have an operating time less than or equal to 15 m-sec.
iii)
have a resetting time less than or equal to 15 m-sec.
iv)
be of numerical type.
v)
have a continuous thermal with stand of two times rated current irrespective of
setting.
Note:- The LBB protection scheme in built with numerical bus bar protection scheme is
acceptable provided it meets the above specification.
B)
TIME DELAY RELAY:A time delay relay must be included with adjustable setting range of 0-5 minutes to
provide a time lag before which the bank shall not be again switched on (to avoid closing
of the circuit breaker on a trapped charge).
C)
UNDER VOLTAGE PROTECTION :One inverse time under voltage relay having setting range of 50% to 90% of 110/3 volt
(Phase-to-neutral) shall be provided to disconnect the capacitor bank under low voltage
conditions.
D)
OVER VOLTAGE PROTECTION :One inverse time over voltage relay suitable for operation with 110/3 volt AC supply
(Phase to neutral) with setting range of 100% to 130% shall be provided.
E)
UNBALANCE PROTECTION :The unbalance protection shall be provided through current unbalance relay connected to
the NCT in neutral of capacitor bank connected in double star. Two such relays, one
each for alarm & trip are required. The setting of the relay shall be 10% to 40% of the CT
secondary (i.e. 1A for 132 kV& 66kV voltage levels and 5A for 33 kV voltage levels)
followed by a time delay through a timer of 0.1 sec. for transient free operation of the
protection. The relays shall be numerical type.
The relay should not operate for healthy state spill current in neutral. Number of units of
failure on which alarm shall come and tripping is initiated, be clearly mentioned for proper
setting of the relays.
Note:- The under voltage Relay and over voltage relay in-built with numerical unbalance
protection relay is acceptable provided it meets the above specification.
5.17.7 TRIPPING RELAY:
High speed tripping relay shall
i)
be instantaneous ( operating time not to exceed 10milli-seconds.)
ii)
reset within 20milli-seconds.
iii)
Be 220 Volt DC operated.
iv)
have adequate contacts to meet the scheme requirement
v)
Be provided with operation indicators for each element/coil.
20
Synchronising check relay with necessary auxiliary equipments shall be provided which
shall permit breakers to close after checking the requirements of synchronising of
incoming and running supply. The phase angle setting shall be less than or equal to 35
degree and have voltage difference setting less than or equal to 10%. This relay shall
have a response time of less than 200 milliseconds when the two system conditions are
met within preset limits and with the timer disconnected. The relay shall have a
continuously adjustable time setting range of 0.5-3secs. A guard relay shall be provided
to prevent the closing attempt by means of synchronising check relay when control
switch is kept in closed position long before the two systems are in synchronism
5.19.
RELAY SETTINGS :
The successful bidder will be responsible for calculating the relay setting of the protection
schemes included in the bid and obtain HVPN's M&P wing clearance before their
adoption. Any data\ information in regard to the power system required by the supplier for
this purpose shall be supplied by HVPN.
5.20
ii)
iii)
iv)
v)
vi)
vii)
viii)
21
IRIG-B
RS232C
ix)
5.21.
5.22.
The equipment shall have a periodic time correction facility of one second
periodicity.
x)
Time synchronisation equipment shall be suitable to operate from 220V DC as
available at Substation.
xi)
Equipment shall have real time digital display in hour, minute, second (24 hour
mode) & have a separate time display unit to be mounted on the top of control
panels having display size of approx. 100 mm height.
SMALL WIRING :
a)
All wiring shall be of switch board type consisting of stranded /single annealed
copper conductor insulated with polyvinyl chloride insulation suitable for 650 volts
service and in accordance with IS : 694.
b)
The wiring of the following circuits shall not be less than the size specified below:
CTs, PTs & CVTs circuits
:
2.5
mm2
Control, alarm & supervision circuits etc.
:
1.5
mm2
c)
All wires will be continuous from one terminal to the other and also will have no tee
- junction en-route. The connections shall be securely made with the help of
connecting lugs to ensure non-oxidation of the bare copper conductor. At the
terminal connections, washers shall be interposed between stud type terminals
and holding nuts. All holding nuts shall be secured by locking nuts. The connection
studs shall project at least 6 mm from the lock nut surface.
d)
Bus wires shall be fully insulated and run separately. MCBs shall be provided to
enable all the circuits in a panel to be isolated from the bus wire. Wherever
practicable, all circuits in which the voltage exceeds 125 volts shall be kept
physically separated from the remaining wiring. The function of each circuit shall
be marked on the associated terminal boards.
e)
All wiring diagrams for the control and relay boards shall be drawn as viewed from
the back of the cubicle and shall be in accordance with IS:375 or equivalent IEC.
Multi core cable tails shall be so bound to its cable that each wire may be traced
without difficulty.
f)
All potential bus wiring, non-trip and trip alarm bus wiring, AC & DC control supply,
panel lighting bus wires and such other wiring which runs from panel to panel
within a C&R panel board shall be laid out in gutters and shall be suitably
screened. In case of `simplex' type C&R boards these common wires will run
through bus wire holes.
TERMINAL BOARDS, TEST BLOCKS & SPARE CONTACTS:
a)
Terminal block connectors built from cells of moulded dielectric and brass stud
inserts shall be provided for terminating the outgoing ends of the panel wiring and
the corresponding tail ends of control cables. Insulating barriers shall be provided
between adjacent connections. The height of the barriers and the spacing
between terminals shall be such as to give adequate protection while allowing
easy access to terminals. Provision shall be made on each pillar for holding 10%
extra connectors.
b)
The terminal blocks shall be suitable for 650 Volts service and for connection with
both copper and aluminum wires.
c)
Terminal boards shall be mounted in such a manner as to afford easy access to
terminations and to enable ferrule numbers to be read without difficulty. Wire ends
shall be so connected at the terminals that no wire terminal gets marked due to
succeeding connections. Terminal board rows shall be adequately spaced and
shall not be less than 100 mm apart so as to permit convenient access to wires
and terminations. Labels in the form of engraved plastic plates shall be provided
on the fixed portion of terminal boards. No live metal parts shall be exposed at the
back of terminal boards.
22
d)
e)
f)
Switch board type back connected test block with contacts shall be provided with
links or other devices for shorting terminals of CT leads before interrupting the
normal circuit for injection from an external source or for inserting testing
instruments in the circuit without causing open circuit of the CT. The potential
testing studs shall preferably be housed in narrow recesses of the block, wherever
required, shall be placed as close to the equipments as possible. Test blocks shall
be of flush mounting pattern and the number of test blocks being provided on each
control and relay panel shall be stated in the tender.
The purpose of all the relays (including the auxiliary relays) switches, lamps &
push buttons etc. is required to be indicated just below the respective equipment
through engraving or painting.
Spare contacts of relays are required to be brought on T.B's and shall be indicated
on the drawings.
5.23.
BUS WIRES:
The VT, DC, AC, trip alarm , non-trip alarm & DC fail etc. inter panel bus wire terminals
shall be brought on Bus T.B's as well as on T.B's so that any panel specified herein can
be used separately at the Substation specified in this specification. The said bus wires for
the panels specified in case of existing substations shall be matched with the bus wires of
the C&R panels already available at site, the drawing for matching purposes for which
shall be supplied to the successful bidder. The bus wire terminals shall be indicated on
the panel schematic drawings as well. The bus wire diagram shall also be supplied
alongwith the schematic drawings for each panel.
5.24.
FERRULES :
Wire No. shall be indicated on panel schematic and wiring diagrams and accordingly
engraved ferrules with the same numbers and letters as indicated in the said diagrams
shall be provided on the terminal ends of all wires for easy identification of circuits for
inspection and maintenance. Ferrules shall be of strong & flexible insulating material with
glossy finish to prevent adhesion. These shall be engraved and marked clearly and shall
not be affected by dampness. Ferrule numbering shall be in accordance with IS: 375. The
same ferrule number shall not be used on wires in different circuits on a panel. At those
points of interconnection between the wiring carried for equipments of different suppliers
where a change of number cannot be avoided double ferrules shall be provided on each
wire with the appropriate connection diagram of the equipment.
5.25.
SPACE HEATERS:
Tubular space heaters suitable for connection to the single phase 220 Volts AC supply
complete with switches located at convenient positions shall be provided at the bottom of
each control and relay panel to prevent condensation of moisture. The watt loss per unit
surface of heater shall be low enough to keep surface temperature well below visible
heat.
5.26.
ILLUMINATION:
The C&R panel shall be provided with 220/240 Volts AC interior lighting. The lamp shall
be free from hand shadows. A door operated button switch shall be provided in each
simplex panel. Each simplex panel shall be provided with one no. illumination lamp with
door switch.
5.27
POWER SOCKET :
Single phase 240 volt AC, 5-Pin, 5/15A power socket with power on/off switch shall be
provided in each simplex panel.
5.28
SAFETY EARTHING:
Earthing of current free metallic parts or metallic bodies of the equipment mounted on the
switch boards shall be done with bare copper conductor. Copper bus of size 25 mm x 6
23
mm extending through entire length of a control and relay board shall be provided. The
earthing conductor shall be connected by Rose Courtney terminals and clamp junctions.
The neutral point of star connected secondary windings of instrument transformers and
one corner of the open delta connected LV side of potential transformer, if used shall be
similarly earthed with the main earth bar of the switch board earthing system. Multiple
earthing of any instrument transformer shall be avoided. An electrostatic discharge point
shall be provided in each panel connected to earth bus via 1 Mega Ohm resistor.
5.29.
NAME PLATE:
An easily accessible engraved or painted panel name plate shall be provided inside each
panel. It must include G.A. drawing No., purchase order No., Contractor's reference No.,
name of S/Stn. as per purchase order and name of circuit. In addition to this, an engraved
plate indicating the purchase order no. alongwith name of S/Stn. is required to be affixed
on the panel at appropriate height so that it is readable while standing in front of the
panel. These are required to be indicated on the G.A. drawings also. An engraved label
indicating the purpose of all the relays & switches shall also be provided.
5.29
6.0
TESTS :
6.1
TYPE TESTS :
The equipment offered should be type tested. Type test report of similar equipment
should not be more than seven years old, reckoned from the date of bid opening, in
respect of the following tests, carried out in accordance with ISS-3231(1965)/equivalent
IEC from Govt./ Govt. approved test house & shall be submitted along with bid:
a)
Insulation tests as per IEC 60255-5
b)
High frequency disturbance test as per IEC 60255-22-1(applicable for all type of
numerical relays).
c)
Fast transient test as per IEC 1000-4, Level-III (not applicable for
electromechanical relays)
d)
Relay characteristics, performance and accuracy test as per IEC 60255.
e)
Tests for thermal and mechanical requirements as per IEC 60255-6
f)
Tests for rated burden as per IEC 60255-6
g)
Contact performance test as per IEC 60255-0-20
h)
Conformance tests as per IEC 61850
The above tests shall be supplied for distance protection, over current and earth fault
protection, restricted earth fault protection, Bus bar protection and transformer differential
protection as per the applicability of the relay alongwith bid.
The remaining type test reports of above relays & all the type test reports of remaining
relays and type test reports of meters shall be submitted by the successful bidder within
three months of placement of order. These type test reports will also be from Govt./
Govt. approved test house & should not be more than seven years old, reckoned from
the date of placement of order. The failure to do so will be considered as a breach of
contract.
24
6.2
6.2.1
ROUTINE TESTS:
All equipment shall be subject to routine tests according to the relevant standards /
Quality Assurance Program (QAP) and to such other tests as may be required to ensure
that all equipment is satisfactory and in accordance with this specification. The
Purchaser reserves the right to witness all the tests, unless dispensed with in writing by
the Purchaser.
6.3
6.3.1
ACCEPTANCE TESTS:
The Supplier shall give sufficient advance intimation (at least 15 days notice for Indian
Supplier and 30 days notice for Foreign Supplier) to the Purchaser to enable him to
depute his representative for witnessing the tests. Following tests shall be carried out at
the manufacturer's works after complete assembly:i)
Checking wiring of circuits and their continuity.
ii)
One minute high voltage test.
iii)
Insulation resistance of complete wiring, circuit by circuit with all equipment
mounted on the panel.
iv)
Checking the operation of protection schemes.
7.0
7.1
DOCUMENTATION:
All drawings shall conform to international standards organization (ISO) `A' series of
drawing sheet/Indian Standards Specification IS: 11065. All drawings shall be in ink and
suitable for microfilming. If drawings are computerized than all drawings shall be nicely
printed. All dimensions and data shall be in S.I.Units.
The successful Supplier shall submit four sets of G.A. and schematic drawings for
Purchaser's approval within two weeks of the date of placement of order.
The Purchaser shall communicate his comments/approval on the drawings to the
Supplier within four weeks of the date of receipt of above drawings. The Supplier shall, if
necessary, modify the drawings and resubmit four copies of the modified drawings for
Purchaser's approval within two weeks from the date of Purchaser's comments. After
receipt of Purchaser's approval, the Supplier shall submit 10 prints of final drawings for
each Item/Circuit and one good quality soft copy (CD) of the following drawings and
instruction manuals :i)
Board-wise arrangement drawing (applicable for the panel board at a Substation
having more than one panel).
ii)
G.A. drawing alongwith G.A. legend and foundation details.
iii)
Schematic drawings alongwith legend & internal wiring details of main relays like
transformer differential relay, REF relay, and local breaker back up schemes,
distance protection scheme, bus-bar protection scheme, voltage selection
scheme etc.
iv)
Equipment-wise & wire-wise wiring diagrams.
Each set of drawings shall be bound separately. The final documents shall be supplied
before despatch of equipment.
The manufacturing of the equipment shall be strictly in accordance with approved
drawings and no deviation shall be permitted without the written approval of the
Purchaser. All manufacturing & fabrication work in connection with the equipment prior
to the approval of the drawings shall be at the Supplier's risk.
The Supplier shall furnish specified no. of nicely printed and bound volumes of the
instruction manuals in English language, prior to the despatch of the equipment. The
instruction manual shall contain step by step instructions for all operational &
maintenance requirements for all the protective and aux. relays, switches, instruments
etc. mounted on the panel and shall include the following aspects.
i)
Storage for prolonged duration.
ii)
Unpacking.
iii)
Erection.
7.2
7.3
7.4
25
iv)
v)
vi)
vii)
viii)
ix)
x)
Handling at site.
Pre commissioning tests.
Operating procedures.
Maintenance procedure.
Precautions to be taken during operation & maintenance work.
Catalogue numbers of all the components liable to be replaced during the life of
the panels.
Internal wiring diagrams of all the relays.
7.5
Ten (10) copies of instruction manuals for each Circuit/Item shall be supplied free of cost
before despatch of equipment. Each set of instruction manuals shall be bound
separately. One master set for all the Circuits/Items shall be supplied with in a
week of placement of order to the Design Directorate to facilitate the checking and
approval of drawings.
7.6
Approval of drawings by Purchaser shall not relieve the Supplier of his responsibility and
liability for ensuring correctness & correct interpretation of the latest revision of
applicable standards, rules & codes of practices. The equipment shall conform in all
respects to high standards of engineering, design, workmanship and latest revisions of
relevant standards at the time of ordering.
NOTE:- In case the equipment offered by the Supplier does not meet with the
requirements of technical specification, the offer of the firm shall not be
considered.
26
ANNEXURE-A
SCHEDULE OF REQUIREMENT
(Tender Enquiry No. QDP- )
I.
Sr.
No.
C&R PANELS
Description of
Equipment
1.
2.
3.
4.
5.
Capacitor panel
II.
Qty. of Panel
220 kV
For
220/132
kV T/F
For 220/66
kV T/F
132 kV
For
For
132/33 132/11
kV T/F kV T/F
66 kV
For 66/33
kV T/F
For
For 33/11
66/11 kV kV T/F
T/F
With Bus
bar
protection
33 kV
For
132/33
kV T/F
With out
bus bar
protection
LOOSE RELAYS
27
For
66/33
kV T/F
ANNEXURE -B
GUARANTED TECHNICAL PARTICULARS
CONTROL AND RELAY PANELS
I.
1.
PANELS.
Dimension of the C&R panels.
i)
Depth
ii)
Overall height
iii)
Width
2.
3.
4.
II.
1.
2.
3.
4.
5.
III.
i.
ii.
iii.
iv.
v.
vi.
vii.
viii.
ix.
x.
xi.
xii.
xiii.
xiv.
xv.
xvi.
xvii.
xviii.
xix.
xx.
xxi.
xxii.
xxiii.
Insulation of wiring.
Material of wiring conductor.
Size of wiring conductor for:
C.T. Circuits.
i)
C.V.T./P.T. Circuits.
ii) D.C. supply circuits.
iii) A.C. Supply Circuit.
iv) Other circuits.
Size of earthing bar for safety earthing.
Type of terminals used in wiring the
panel.
INDICATING AND INTEGRATING INSTRUMENTS (AMMETER, VOLTMETER, MW METER,
MVAR METER AND KWH METER TO BE FILLED IN SEPARATELY FOR EACH ITEM).
Makers Name
Type and Model of Instruments
Size
Whether magnetically Shielded
Limits of Errors in The effective range
Maximum scale length
Total deflection angle
Class of Accuracy
Whether tropicalized
Auxiliary Supply
Short Time overload
VA burden
i) Current coil
ii) Potential coil
Power consumption
i) Current coil
ii) Potential coil
Continuous over load rating of Current coil.
Continuous over load rating of Potential coil.
Short time over voltage rating of Potential coil.
Short time over voltage rating of Current coil.
Temperature at which calibrated( degree C ).
Range of temp. for Correct operations.
Accuracy at 125%, 25% and 10% of rated value
i) Active energy measured
ii) Reactive energy measured
Other details, if any.
Type of mounting.
Ref. no. of descriptive leaflet, submitted.
28
xxiv.
IV.
1.
2.
3.
4.
5.
selector
Type
No. of position
8.
9.
10.
11.
12.
Interface protocol
6.
7.
8.
9.
V.
1.
2.
3.
4.
5.
6.
7.
VI.
1.
2.
3.
4.
5.
6.
VII.
1.
2.
3.
4.
5.
6.
7.
29
VIII.
1.
2.
3.
4.
5.
6.
7.
8.
IX.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
X.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
AUXILIARY RELAYS.
Make.
Type.
Capacity of contacts:
i) Continuously.
ii) for 3 seconds.
Operating coil VA burden.
Voltage operated or current operated.
No. of Normally closed & Normally open
contacts sufficient for scheme requirements
(Yes / No).
Contacts hard or soft reset type
Descriptive leaflet number submitted.
FACIA ANNUNCIATOR.
Make and model
Type
Size
No. of windows of the standard facia
No. of additional windows that can be added to
the standard facia
Provision of `Accept', `Reset', and `Lamp test',
push buttons in the facia.
Mode of inscription on the fascia window.
Operating voltage.
Description of leaflet submitted.
Minimum duration of impulse for initiating
contacts not more than 10milisec.
Auxiliary supply voltage
(i) For DC fail annunciation (AC Volt)
(ii) For other than DC fail annunciation (DC
Volt)
(iii) Permissible voltage variation for both
supply + / - %
TRANSFORMER DIFFERENTIAL RELAY.
Make
Type and designation/model
Whether comply to Principle Technical
Parameters
Whether Numerical measurement.
Whether continuous self monitoring and
diagnostic feature is available
Current circuit rating
Operating principle
Number of poles
Max. V.A burden
i) Operating circuit
ii) Restraining circuit
Min. Operating current
Is the slope setting variable.
Setting ranges available
Power consumption
i) Operating circuit
ii) Restraining circuit
2nd and 5th harmonic restrain provided or not.
Whether internal angle and ratio correction is
available.
Operating time
i) at 2 x In
ii) At 10 x In
30
17.
XII.
1.
2.
Interface protocols.
3.
4.
5.
6.
7.
8.
9.
18.
19.
20.
21.
22.
23.
24.
25.
26.
XI.
1.
2.
3.
4.
5.
6.
7.
XIII
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Reset time.
31
XIV.
1.
2.
3.
4.
5.
6.
7.
8.
XV.
1.
2.
3.
4.
5.
6.
XVI.
1.
2.
3.
4.
5.
6.
7.
XVII.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
PROTECTION IN/OUT
32
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
XVIII.
1.
2.
3.
4.
33
5.
6.
7.
XIX.
1.
2.
3.
4.
5.
6.
7.
8.
9.
XX.
1.
2.
3.
4.
5.
6.
XXI.
1.
2.
3.
4.
5.
6.
7.
34
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
XXII
i.
ii.
iii.
iv.
v.
vi.
vii.
(x)
No. of I/P per bay unit
(xi) No. of I/P for central unit:
(xii) Pickup current for I/P:
(xiii) Operating Time for I/P:
Auxiliary Supply:
(i)
Input Voltage:
(ii)
Load:
(a) (Bay Unit)
(b) (Central Unit)
(iii)
Front plate Signal
(iv)
Switch
(v)
Redundant power Supply: Optional
Optical Interface:
(i)
Number of Cores
(ii)
Core/ sheath diameter
(iii)
Max permissible attenuation
(iv)
Connector
Event Recorder:
It shall have event recording facility for
minimum last50 Operational/ fault events.
Disturbance Recorder:
(i)
Independent setting for pre-fault and
post- fault period
(ii)
Format
Local & Remote communication:
(i)
Serial interface for connecting a PC,
either Directly or via a modem
(ii)
System interface for connecting to a
control system via IEC 61850
(iii)
System interfaces via IEC 61850
protocol for interbay bus supports.
(iv)
Time synchronization
Maximum fault current for which 100% stability
can be achieved.
Impedance type and operating characteristic
Continuous supervision of CT secondary
against open circuit
Architecture & Interconnection of Central unit
and bay unit panel.
Principle of CT ratio error matching
Measuring and tripping criterion
HMI details
Self supervision and diagnostic facility.
Measurements available
Whether bus bar image for each bay is formed
and displayed in HMI
Redundant hardware available
Standard functions available
Optional functions available
Reset through a single push button
TRIPPING RELAYS
Make
Type designation/model
Rating
Operating principal
Literature write up enclosed
Operating time at rated voltage.
Relay suitable
for
being
continuously
monitored.
35
viii.
ix.
x.
xi.
36
Annexure - C
COREWISE DETAILS OF 420 kV CTs
(2000-1000-500/1-1-1-1-1A)
NUMBER OF CORES 5
Core
No.
Application
Current
ratio
Output
burden
(VA)
Accuracy
class
Min. knee
Pt. Voltage
Vk
Max. CT sec.
wdg.
Resistance
(ohms)
Max. Excitation
current at Vk
(in mA)
BUS
MAIN
DIFF
20001000 /1
PS
2000/1000
10/5
BUS
CHECK
DIFF
20001000/1
PS
2000/1000
10/5
METERING
20001000500/1
10
0.2S
ISF<5 for
500/1A,
ISF<10 for
1000/1A,
ISF<20 for
2000/1A
TRANS.
BACKUP/
LINE PROTN.
20001000500/1
PS
4000/2000/1
000
10/5/2.5
TRANS. DIFF/
LINE PROTN.
20001000500/1
PS
4000/2000/1
000
10/5/2.5
30 on 2000/1
Tap;
60
on
1000/1 Tap
30 on 2000/1
Tap;
60
on
1000/1 Tap
-
30 on 2000/1
Tap;60
on
1000/1 Tap; 120
on 500/1 Tap
30 on 2000/1
Tap;60
on
1000/1 Tap; 120
on 500/1 Tap
1
1
2
3
4
Application
Current
Ratio (A)
2
DIFFERENTIAL
PROTECTION
REF PROTECTION
Output
burden
(VA)
Accuracy
class
as per
IEC 185
Maximum
Exciting
Current
(mA)
I.S.F./
A.L.F
450-300/
0.577
450-300/1
PS
40 (RCT+2)
30 @Vk/4
PS
14 (RCT+2)
30 @Vk/2
OVER CURRENT
450-300/1
PROTECTION / BUS BAR
PROTECTION
BUSBAR PROTECTION (FOR 450-300/1
LOW IMPEDANCE SCHEME)
PS
40 (RCT+4)
30 @Vk/2
PS
40 (RCT+4)
30 @Vk/2
10
0.2S
<5
METERING
450-300/1
NOTE : 4th core for bus bar protection has been kept in view of general design being followed in
HVPNL. In case this CT is used on a sub station having high impedance bus bar protection scheme or no
bus bar protection scheme then this core shall be short-circuited at site.
37
Application
1
1.
2.
3.
4.
5.
2
MAINI
DISTANCE
PROTECTION
MAINII
DISTANCE
PROTECTION
BUS
DIFFERENTIAL
MAIN
BUS
DIFFERENTIAL
CHECK
METERING
NOTE :
1.
Current
Ratio (A)
Output Accuracy
burden class
(VA)
as per
IEC 185
Maximum Instrument
Exciting
Security
Current
factor
(mA)
7
1200-800400/1
PS
80(RCT+9)
80 @ Vk
1200-800400/1
PS
80(RCT+9)
80 @ Vk
1200-800400/1
PS
100(RCT+4)
30 @ Vk/2
1200-800400/1
PS
100(RCT+4)
30 @ Vk/2
1200-800400/1
10
0.2S
ISF<5 for
ratio 400/1,
ISF<10 for
ratio 800/1,
ISF<20 for
ratio 1200/1
5 cores of 245kV line CT have been kept in view of general design being followed in
HVPNL.
2.
In case this CT is used exclusively for bus bar protection purpose on a transformer
circuit at sub station having high impedance bus bar protection scheme then core no
1, 2 & 5 shall be short circuited at site.
3.
In case this CT is used for feeder circuit on a sub station having low impedance bus
bar protection scheme then core no. 4 shall be short circuited at site and where there
is no bus bar protection scheme core no. 3 & 4 shall be short circuited at site.
38
Application
Current
Ratio (A)
1.
MAINI
DISTANCE
PROTECTION
MAINII
DISTANCE
PROTECTION
BUS
DIFFERENTIAL
MAIN
BUS
DIFFERENTIAL
CHECK
METERING
2.
3.
4.
5.
Output Accuracy
burden class
(VA)
as per
IEC 185
Formula for
minimum knee point
voltage At CT
Secondary resistance
at 750C at 1000A tap
(Volt)
6
Maximum
Exciting
Current
(mA)
Instrument
Security
Factor/
A.L.F
20001000/1
PS
1600
20-40
20001000/1
PS
1600
20-40
20001000/1
PS
1600
20-40
20001000/1
PS
1600
20-40
20001000/1
10
0.2S
ISF<5 for
ratio 1000/1,
ISF<10 for
ratio 2000/1,
NOTE :
1.
5 cores of 245kV line CT have been kept in view of general design being followed in HVPNL.
2.
In case this CT is used exclusively for bus bar protection purpose on a transformer circuit at sub
station having high impedance bus bar protection scheme then core no 1, 2 & 5 shall be short
circuited at site.
3.
In case this CT is used for feeder circuit on a sub station having low impedance bus bar protection
scheme then core no. 4 shall be short circuited at site and where there is no bus bar protection
scheme core no. 3 & 4 shall be short circuited at site.
COREWISE DETAILS OF 245 kV BUS COUPLER CTs FOR 400KV S/STNS.
(2400-1200/1-1-1-1A)
NUMBER OF CORES - 4
Core
No.
1
1.
2.
3.
4.
Application
Current
Ratio (A)
Output
burden
(VA)
Accuracy
class
as per
IEC 185
Formula for
minimum knee
point voltage
At CT
Secondary
resistance at
750C at
2400Atap (Volt)
6
Maximum
Exciting
Current
(mA)
ALF/ISF
O/C
&
E/F
PROTECTION
2400-1200/
1
15
5P
10
BUS
DIFFERENTIAL
BUS
DIFFERENTIAL
CHECK
METERING
2400-1200/
1
2400-1200/
1
PS
100(RCT+4)
30 @ Vk/2
PS
100(RCT+4)
30 @ Vk/2
2400-1200/
1
10
1.0
ISF<5
39
1
1
2
3
4
Current
Ratio (A)
Output
burden
(VA)
Accuracy
class
as per
IEC 185
Formula for
minimum
knee-point
voltage
At CT
Secondary
resistance
at 750C at
900Atap
(Volt)
Maximum
Exciting
Current
(mA)
I.S.F./
A.L.F
6
40 (RCT+2)
7
30 @Vk/4
8
-
10
2
DIFFERENTIAL
PROTECTION
OVER
CURRENT
&
EARTH
FAULT
PROTECTION
METERING
BUSBAR PROTECTION
MAIN DIFF.
3
900-600-300/1
5
PS
900-600-300/1
15
5P
900-600-300/1
900-600-300/1
10
-
0.2S
PS
40 (RCT+4)
30 @Vk/2
<5
-
BUSBAR PROTECTION
CHECK DIFF.
900-600-300/1
PS
40 (RCT+4)
30 @Vk/2
Current
Ratio (A)
Accuracy
class
as per
IEC 185
REF PROTECTION
450-300/1
Maximum
Exciting
Current
(mA)
PS
Minimum
Insulation
Voltage
(kV)
14(RCT+2)
30 @ VK/2
33
1
1.
2.
3.
4.
Application
Current
Ratio (A)
Output
burden
(VA)
PS
PS
15
10
DIFFERENTIAL
750-500/
PROTECTION
0.577
REF
750-500/1
PROTECTION
OVER
750-500/1
CURRENT AND
EARTH FAULT
PROTECTION
METERING
750-500/1
Accuracy
Class
as per
IEC 185
Maximum
Exciting
Current
(mA)
I.S.F./
A.L.F.
40 (RCT+2)
30 @ Vk/4
90 (RCT+2)
37.5 @ Vk/2
5P
ALF10
0.2S
ISF<5
40
1
1.
2.
3.
4.
Application
Current
Ratio (A)
2
DIFFERENTIAL
PROTECTION
REF
PROTECTION
OVER
CURRENT
PROTECTION
METERING
3
250-150100/0.577
250-150100/1
250-150100/1
Output
burden
(VA)
Accuracy
class as
per IEC
185
250-150100/1
Maximum
Exciting
Current
(mA)
A.L.F.
PS
6
40 (RCT+1)
7
30 @ Vk/4
8
-
PS
20 (RCT+1)
30 @ Vk/2
15
5P
10
0.2S
ISF<5
10
COREWISE DETAILS OF 145kV LINE CT AND 145kV BUS COUPLER CT for 132kV
S/STNS.
(600-300-150/1-1-1A)
No. OF CORES = 3
Core Application
No.
1
1
2
Current
Ratio (A)
Output Accurac
burden y class
(VA)
as per
IEC 185
DISTANCE
PROTECTION
OVER-CURRENT
& EARTH FAULT
PROTECTION
METERING
Formula
for
minimum
kneepoint voltage
At CT Secondary
resistance at 750C
at 300Atap (Volt)
6
Maximum
Exciting
Current
(mA)
A.L.F./
I.S.F.
600-300-150/1
PS
120 (RCT+4.5)
80 @ VKP
600-300-150/1
15
5P
ALF 10
600-300-150/1
10
0.2S
ISF<5 for
ratio 150/1,
ISF<10 for
ratio 300/1,
ISF<20 for
ratio 600/1
1
1
Application
2
REF
PROTECTION
Current
Ratio (A)
3
250-150-100/1
Output
burden
(VA)
Accuracy
class
as per
IEC 185
PS
Formula
for
minimum
kneepoint voltage
At CT Secondary
resistance at 750C
at
100A tap (Volt)
6
20 (RCT+1)
Maximum
Exciting
Current
(mA)
Minimum
Insulation
Voltage
(kV)
30 @ VK/2
15
41
Current
Ratio (A)
2
A.L.F./
I.S.F.
8
750-500/1
15
5P
ALF 10
750-500/1
10
1.0
ISF<5
1
1
2
3
Application
Current
Ratio (A)
Output
burden
(VA)
Accuracy
class
as per
IEC 185
5
Maximum
Exciting
Current
(mA)
A.L.F./
I.S.F.
DIFFERENTIA
L
PROTECTION
REF
PROTECTION
OVER
CURRENT &
EARTH
FAULT
PROTECTION
1500-1000/0.577
PS
40 (RCT+2)
30 @ VK/4
1500-1000/1
PS
14 (RCT+2)
30 @ VK/2
1500-1000/1
15
5P
ALF 10
METERING
1500-1000/1
10
0.2S
ISF <5
1
1
2
3
Current
Ratio (A)
Output Accuracy
burden class
(VA)
as per
IEC 185
Formula
for
minimum
kneepoint voltage At CT
Secondary
resistance at 750C
at 300A tap (Volt)
6
Maximum A.L.F
Exciting
Current
(mA)
DIFFERENTIAL
PROTECTION
REF PROTECTION
300-200-150/0.577
PS
40(RCT+4)
30 @ VK/2
300-200-150/1
PS
40(RCT+4)
30 @ VK/2
OVER CURRENT
PROTECTION
300-200-150/1
15
5P
10
42
COREWISE DETAILS OF 72.5kV LINE CT AND 72.5kV BUS COUPLER CT for 66kV
S/STNS.
(600-300-150/1-1-1A)
No. OF CORES = 3
Core Application
No.
1
1
2
Current
Ratio (A)
Output Accuracy
burden class
(VA)
as per
IEC 185
DISTANCE
PROTECTION
OVER
CURRENT &
EARTH FAULT
PROTECTION
METERING
Maximum A.L.F./
Exciting
I.S.F.
Current
(mA)
600-300-150/1
PS
80(RCT+4)
40 @VK/2
600-300-150/1
15
5P
ALF 10
0.2S
600-300-150/1
10
1
1
Current
Ratio (A)
2
REF PROTECTION
Output
burden
(VA)
3
1500-1000/1
Accuracy
class
as per
IEC 185
PS
Maximum
Exciting
Current
(mA)
Minimum
Insulation
Voltage
(kV)
14
(RCT+2)
30 @ VK/2
15
Application
Current
Ratio (A)
Output
burden
(VA)
Accuracy
class as
per
IEC
185
1.
REF
PROTECTION
300-200150/1
Maximum
exciting
current
(mA)
Minimum
Insulation
voltage
(kV)
Formula
for
minimum knee
point voltage at
CT
secondary
resistance at 750
at
300A
tap
(Volt)
6
PS
20 (RCT+1)
30 @ Vk/2
15
43
Current
Ratio (A)
2
Output
burden
(VA)
4
Accuracy class
as per
IEC 185
5
A.L.F./
I.S.F.
8
1500-1000/1
15
5P
ALF 10
1500-1000/1
10
1.0
ISF<5
1
1
2
3
Application
2
DIFFERENTIAL
PROTECTION
REF
PROTECTION
OVER CURRENT
&
EARTH
FAULT
PROTECTION
MAIN
METERING
Current
Ratio (A)
Output Accuracy
burden class as
(VA)
Per IEC
185
1000-600-400/0.577
Formula
for
minimum
knee
point voltage At
CT
Secondary
resistance at 750C
at
400A tap (Volt)
6
Maximum
Exciting
Current
(ma)
A.L.F./
I.S.F.
PS
40 (RCT+1)
30@VK/4
1000-600-400/5
PS
100(RCT+1)
75@VK/2
1000-600-400/5
15
5P
10
1000-600-400/1
10
0.2S
<5 for
ratio
300/1
<10 for
ratio
400/1
<20 for
ratio
600/1
44
Current
Ratio (A)
DIFFERENTIAL
PROTECTION
REF. PROT.
OVER
CURRENT
&
EARTH
FAULT
PROT.
MAIN
METERING
2
3
Output
Burden
(VA)
Accuracy
class
as per
IEC 185
Formula for
minimum kneepoint voltage At CT
Secondary
resistance at 750C at
2000A tap (Volt)
6
Maximum
Exciting
Current
(mA)
A.L.F.
/ ISF
2000-1000/
0.577
2000-1000/ 5
2000-1000/5
PS
40 (RCT+1)
30@ V K/4
15
PS
5P
100 (RCT+1)
-
75@ V K/2
-
10
2000-1000/1
10
0.2S
For
ratio
1000/1
ISF<5.
For
ratio
2000/1
ISF<1
0.
COREWISE DETAILS OF 36kV LINE CUM CAPACITOR CT for 33kV LINE BAY AND
FOR 20MVAR & 10MVAR CAPACITOR BANKS ON 220/33KV T/F & 40/50MVA
132/33kV T/F WITH 26.3KA STC
(400-300/5-1)
No. OF CORES = 2
Core
No.
1.
2.
3.
4.
Accuracy
Class
as
per IEC
185
5.
1.
400-300/5
15
5P
10
400-300/1
10
0.2S
75
2.
Application
Current Ratio
(A) (VA)
Output
Burden
A.L.F.
6.
1
1
Application
2
REF
PROTECTION
Current
Ratio (A)
3
1000-600-400/5
Output
burden
(VA)
Accuracy
class as
Per IEC
185
PS
Formula
for
minimum knee
point voltage
At
CT
Secondary
resistance
at
0
75 C at
400A tap (Volt)
6
100 (RCT+1)
Maximum
Exciting
Current
(mA)
Minimum
Insulation
Voltage
(kV)
7
75@ VK/2
8
15
45
1
1
Current
Ratio (A)
Output
Burden
(VA)
REF PROTECTION2000-1000
/5
Accuracy
class
as per
IEC 185
PS
Maximum
Exciting
Current
(mA)
100 (RCT+1)
Minimum
Insulation
Voltage
(kV)
75@ VK/2
15
COREWISE DETAILS OF 36kV BUS COUPLER CT FOR 220/33KV WITH 26.3KA STC
(2000-1000/5A)
No. OF CORES = 1
Core
No.
Application
1
1
Current
Ratio (A)
Output
Burden
(VA)
4
OVER CURRENT
& EARTH FAULT
PROTECTION
2000-1000/
5A
A.L.F.
15
5P
10
Application
Current
Ratio (A)
REF
PROTECTION
OVER
CURRENT
PROTECTION
Output
burden
(VA)
Accuracy
class as
Per IEC
185
Formula
for
minimum
knee
point voltage
At CT Secondary
resistance at 750C
at
100A tap (Volt)
6
100-50/5
PS
100 (RCT+1)
100-50/5
15
5P
Maximum
Exciting
Current
(mA)
Minimum
Insulation
Voltage
(kV)
75@ VK/2
10
1
1
2
REF
PROTECTION
Current
Ratio (A)
Accuracy
class
as per
IEC 185
4
Maximum
Exciting
Current
(mA)
6
Minimum
Insulation
Voltage
(kV)
7
PS
100 (RCT+1)
75@ VK/2
15
100-50/5
46
Application
Current
Ratio (A)
Accuracy
class
as
per
IEC
185
Maximum
exciting
current
(mA)
Minimum
Insulation
voltage
(kV)
Formula
for
minimum knee point
voltage
at
CT
secondary
resistance at 750 at
1800A tap (Volt)
5
1.
REF
PROTECTION
1800900/5
PS
95 (RCT+1)
75@ Vk/2
8.66
COREWISE DETAILS OF 12kV NEUTRAL CT FOR 12.5/16 MVA & 16/20 MVA T/F
(1200-900/5)
No. OF CORE = 1
Core Application
No.
1
1
2
REF
PROTECTION
Current
Ratio (A)
3
1200-900/5
Accuracy
class
as per
IEC 185
4
Maximum
Exciting
Current
(mA)
6
Minimum
Insulation
Voltage
(kV)
7
PS
95 (RCT+1)
75@ VK/2
8.66
1
1
2
REF
PROTECTION
Current
Ratio (A)
3
300-150/5
Accuracy
class
as per
IEC 185
4
Maximum
Exciting
Current
(mA)
6
Minimum
Insulation
Voltage
(kV)
7
PS
95 (RCT+1)
75@ VK/2
8.66
47
Sl.
No.
Requirement
Particulars
400/3kV
1.
2.
Type
3.
No. of Secondaries
4.
5.
Capacitance (minimum)
6.
7.
Application
8.
Accuracy
9.
10.
Note:-
Single phase
Secondary-II
110/3
Protection
Secondary-III
110/3
Metering
3P
0.2
100
50
50
As per ISS/IEC
48
Sl.
No.
1.
2.
Type
3.
No. of Secondaries
4.
5.
Capacitance (minimum)
6.
7.
Requirement
Application
Particulars
220/3kV
Single phase
Secondary-II
Secondary-III
110/3
110/3
110/3
Protection &
Protection
Metering
Measurement
8.
Accuracy
1/3P
3P
0.2
9.
100
50
10
10.
Note:-
As per ISS/IEC
49
Sl.
No.
1.
2.
Type
3.
No. of Secondaries
4.
5.
6.
Particulars
Requirement
220/3kV
Single phase
Application
Secondary-I
Secondary-II
110/3
110/3
Protection &
Protection
Measurement
7.
Accuracy
1/3P
3P
8.
150
50
9.
As per ISS/IEC
respective
specified
accuracy classes.
Note:-
50
2.
Type
3.
No. of Secondaries
4.
5.
Capacitance (minimum)
6.
7.
Requirement
Particulars
1323kV
Single phase
Application
Secondary-II
Secondary-III
110/3
110/3
110/3
Protection &
Protection
Metering
1/3P
3P
0.2
50
25
10
Measurement
8.
Accuracy
9.
10.
As per ISS/IEC
respective
specified
accuracy classes.
Note:-
51
Sl.
No.
1.
2.
Type
3.
No. of Secondaries
4.
5.
6.
Particulars
Requirement
132/3kV
Single phase
Application
Secondary-I
Secondary-II
Secondary-III
110/3
110/3
110/3
Protection &
Protection
METERING
Measurement
7.
Accuracy
1/3P
3P
0.2
8.
250
25
20
9.
As per ISS/IEC
respective
specified
accuracy classes.
Note:-
52
2.
Type
3.
No. of Secondaries
4.
5.
Capacitance (minimum)
6.
7.
Requirement
Particulars
66/3kV
Single phase
Application
Secondary-II
110/3
110/3
Protection &
Metering
Measurement
8.
Accuracy
9.
10.
1/3P
0.2
50
10
As per ISS/IEC
respective
specified
accuracy classes.
Note:-
53
Sl.
No.
1.
Particulars
Requirement
2.
Type
3.
No. of Secondaries
4.
5.
Secondary-I
66/3kV
Single phase
Secondary-II 110/3
110/3
6.
Application
Protection &
Protection
Measurement
7.
Accuracy
1/3P
3P
8.
250
25
9.
As per ISS/IEC
respective
specified
accuracy classes.
Note:-
54
Particulars
2.
Type
Single phase
3.
No. of Secondaries
4.
5.
33/3kV
Secondary-I
Secondary-II
110/3
110/3
Main metering
6.
Application
7.
Accuracy
0.2
1/3P
8.
10
50
9.
As per ISS/IEC
displacement
for
respective
55
ANNEXURE-D
TRANSMISSION LINE DATA (TENTATIVE)
-----------------------------------------------------------------------------------------------------------------------------------Sr.
Name of Circuit
Line
Conductor size
No.
length
Sq. inch ACSR
in KM. Copper equivalent
---------------------------------------------------------------------------------------------------------------------------------
--------------------------------------------------------------------------------------------------------------------------------* The line lengths and conductor size shall be supplied to successful Bidder.
56
ANNEXURE-E
Clause No.
----------
57
ANNEXURE-F
LINE PARAMETERS (per UNIT)/100 MVA BASE/100 km
WITH CONDUCTOR SIZE & POWER CAPACITY
Volt
age
(kV)
No.of Conduc
Ckt. tor
size
(inch2)
Resistan
ce
R
Reactan
ce
X
Suscepta
nce
Y
Resistan
ce
R0
Reactanc
e
X0
Line
Capacity
(MW )
400
D/C
0.50
0.00093
0.01038
1.11000
0.00000
0.06458
1000*
400
S/C
0.50
0.00186
0.02075
0.55500
0.01013
0.07749
500*
220
D/C
0.40
0.0088
0.0443
0.2700
0.05109
0.21666
300
220
S/C
0.40
0.0176
0.0886
0.1350
0.05951
0.26180
150
132
D/C
0.20
0.0445
0.1167
0.0970
0.15648
0.64289
112
132
S/C
0.20
0.0890
0.2335
0.0485
0.19776
0.76814
56
66
D/C
0.15
0.2347
0.4637
0.0272
0.71210
2.70857
50
66
S/C
0.15
0.4695
0.9275
0.0136
0.93744
3.20761
25
* - Tentative
Remarks:
1. Size of Earth wire for:400kV =
7/3.66 mm
220 kV =
7/3.15 mm
132 kV =
7/2.5 mm
66 kV
7/2.5 mm
2. Resistance of conductor at 20 C.
3. Resistivity of Earth Assumed = 100.
58
ANNUNCIATION DETAILS
ANNEXURE-G
(C&R PANELS)
I.
220 kV TRANSFORMER C&R PANELS.
Sr. No.
Description
1.
T/F Magnetic oil level low.
2.
T/F Bucholz alarm.
3.
T/F winding temp. high alarm.
4.
T/F oil temp. high alarm.
5.
Spare for T/F function.
6.
Spare for T/F function.
7.
CB motor single phasing/over load alarm.
8.
CB low air Pr. Alarm.
9.
CB low air pressure lockout alarm
10.
CB Low SF-6 Gas Pressure alarm.
11.
CB Low SF-6 Gas Pressure alarm.
12.
CB Low SF-6 Gas Pressure alarm.
13.
CB Low SF-6 Gas Pressure Locked alarm.
14.
CB DC fail.
15.
Spare for CB.
16.
Spare for CB.
17.
Over load alarm.
18.
LBB Protection operated.
19.
Over flux alarm
20.
Trip circuit-1 faulty.
21.
Trip circuit-2 faulty.
22.
Spare.
23.
Spare.
24
Spare
25
Spare
26
Spare
27
Spare
28
Spare
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
II.
220 kV FEEDER C&R PANELS.
Sr. No.
Description
1.
Main-I Protection operated.
2.
Carrier received Channel-I.
3.
Main-I VT fuse fail.
4.
Main-I equipment faulty
5.
Main-II Protection operated.
6.
Carrier received Channel-II.
7.
Main-II VT fuse fail.
8.
Main-II equipment faulty
9.
Carrier Channel-I/II faulty
10.
Auto re-close operated
11.
Auto re-close lockout
12.
LBB Protection operated.
13.
CB Pole discrepancy operated.
14.
CB DC fail.
15.
CB motor single phasing/over load alarm.
16.
CB low air Pr. Alarm.
17.
CB Low SF-6 Gas Pressure alarm.
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
59
18.
19.
20.
21.
22.
23.
24
25
26
27
28
III.
220 kV BUSCOUPLER CUM BUSBAR PROTECTION
Sr. No.
Description
1.
Trip circuit-1 faulty.
2.
Trip circuit-2 faulty.
3.
O/C & E/F Protection operated
4.
LBB Protection operated.
5.
Spare
6.
Spare
7.
CB Pole discrepancy operated.
8.
CB DC fail.
9.
CB motor single phasing/over load alarm.
10. CB low air Pr. Alarm.
11. CB Low SF-6 Gas Pressure alarm.
12. CB Low SF-6 Gas Pressure alarm.
13. CB Low SF-6 Gas Pressure alarm.
14. CB low air/ gas pressure lockout
15. Spare for CB.
16. Spare for CB.
17. Busbar Protection Zone I operated
18. Busbar Protection Zone II operated
19. Zone I CT circuit faulty
20. Zone II CT circuit faulty
21. B/B Protection alarm circuit DC fail
22. B/B Protection trip circuit DC fail
23. Spare
24. Spare
IV.
Sr. No.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
C&R PANELS.
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
60
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
V.
LV REF trip.
O/C and E/F operated.
CB DC Fail trip.
OLTC surge relay alarm
Buchholz trip
PRV trip
HV WTI trip
LV WTI trip
OTI trip
OLTC PRV trip
OLTC surge relay trip
Differential relay trip.
HV REF trip.
Spare.
Spare.
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
VI.
132 kV & 66 kV FEEDER C&R PANELS.
Sr. No.
DESCRIPTION
Broken conductor alarm
1.
VT fuse fail (Protection) alarm
2.
VT fuse fail (Metering) alarm
3.
Trip Circuit-1 faulty alarm
4.
Trip Circuit-II faulty alarm
5.
CB SF-6 low gas pressure alarm.
6.
Main AC supply fail alarm
7.
Trip Circuit-1 faulty alarm
8.
Trip Circuit-II faulty alarm
9.
10. Feeder overload alarm
11. Distance Relay faulty
12. O/C+ E/F relay faulty
13. Distance Protection Relay operated.
14. CB SF-6 gas pressure lockout.
15. CB DC Fail trip.
16. Directional O/C + E/F operated
17. SOTF trip
18. Spare
19. Spare
20. Spare
21. Spare
22. Spare
23. Spare
24. Spare
VII. 132 kV & 66 kV Bus Coupler C&R PANELS.
Sr. No.
DESCRIPTION
1.
TRIP CIRCUIT- 1 Faulty
2.
TRIP CIRCUIT- 2Faulty
3.
O/C & E/F Protection operated
4.
Spare
5.
CB DC fail alarm
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
61
6.
7.
8.
9.
10.
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
IX.
33 kV FEEDER & 33 kV I/C T/F C&R Panels.
Sr. No.
Description
1.
CB DC Fail alarm
2.
Trip Circuit faulty
3.
VT fuse fail (Protection) alarm
4.
VT fuse fail (metering) alarm
-1
-1
-1
-1
X.
33 kV T/F C&R Panels.
Sr. No. DESCRIPTION
1.
T/F magnetic oil level low alarm.
2.
T/F Bucholz alarm.
3.
T/F oil temp. high alarm.
4.
T/F winding temp. high alarm.
5.
CB DC fail alarm.
6.
Trip circuit faulty
7.
Spare.
8.
Spare.
9.
Spare.
10.
Spare.
11.
Spare.
12.
Spare.
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
XI
33 kV Capacitor C&R panels.
Sr. No.
DESCRIPTION
1.
Trip circuit faulty.
2.
CB D.C.fail alarm.
3.
Neutral unbalance alarm.
4.
Neutral unbalance trip.
5.
Over voltage/under voltage trip.
6.
O/C and E/F protection trip.
-1
-1
-1
-1
-1
-1
62
ANNEXURE-H
DETAILS OF CARRIER EQUIPMENT
The carrier terminals available in carrier equipment for feeders are as under:-
CARRIER BOOST
CARRIER SEND
(MAIN-I)
CARRIER SEND
(MAIN-II)
+ VE
+ VE
- VE
DIRECT TRIP
(SEND)
+ VE
- VE
CARRIER HEALTHY
(MAIN-I)
CARRIER HEALTHY
(MAIN-II)
CARRIER SIGNAL
RECEIVE
(MAIN-I)
CARRIER SIGNAL
RECEIVE
(MAIN-II)
DIRECT TRIP
(RECEIVE)
63
ANNEXURE-I
MOUNTING DETAILS OF C&R PANELS.
i)
220 KV TRANSFORMER C&R PANELS FOR 100 MVA, 220/132KV & 220/66 kV
TRANSFORMERS.
Each of these panels will be equipped with the followings:Control panel:
1.
Black PVC circuit label.
1
2.
Mimic diagram section.
1
3.
Indication lamps for CB open, close, spring charge and auto
4
trip indications.
4.
Semaphore indicators for isolator position indication.
2
5.
Semaphore indicator for CB position indication.
1
6.
Ammeter suitably scaled.
1
7.
Ammeter selector switch.
1
8.
Spring return to neutral CB control switch with sequence
1
device, lost motion device and 2 pairs of bell alarm contacts.
9.
Spring return to neutral isolator control switches.
2
10.
24 ways static facia annunciator complete with accept,
1
reset and lamps test push buttons.
11.
Trip circuit supervision relays.
6
12.
Set of Trip Ckt. DC supply supervision scheme including one No.
1
push button each for DC fail test and DC fail accept and one
No. indicating lamp (amber) for DC fail visual indication.
To be mounted inside :1.
Set of illumination lamps with on/off switches.
2.
Space heater with switch.
3.
Power socket with on/off switch.
4.
Set of corridor illumination lamps with door switches at both ends
of the corridor.
Relay Panel :1.
Black PVC circuit label.
2.
Transformer differential relay.
3.
REF relay for HV side
4.
REF relay for LV side for 220/66kV T/F or ICT of 1/0.6 A for REF
(for 220/132kV T/F) having adequate knee point voltage to meet the
Relay requirement and should be compatible with main CT.
5.
Set of 3 non directional over current relays and 1 non directional
earth fault relay with high set.
6.
Transformer over load alarm relay.
7.
Over fluxing relay.
8.
High speed tripping relay.
9.
Aux. relay for Transformer buch., OLTC oil temp., winding 8
temp., oil temp., pressure relief, surge relay trip
functions and 2 nos. spare.
10.
Voltage selection relay for double bus arrangements
11.
Set of relays for local breaker back up protection.
12.
High speed tripping relay for bus bar protection.
To be mounted Inside :1.
Set of illumination lamps with on/off switches.
2.
Space heater with switch.
3.
Power socket with on/off switch.
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
64
ii)
1
1
4
1
3
1
1
1
1
1
1
1
1
2
1
1
3
2
1
1
1
6
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
65
14.
Set of 3 directional over current relays and 1 directional earth fault relay
High speed tripping relay.
15.
1
2
1
1
1
iii)
1
1
3.
10
11
12
13
14
15
1.
1
1
1
1
5.
6.
7.
2.
3.
4.
66
Relay Panel
1.
2.
3.
5.
To be mounted inside:
1.
2.
3.
iv)
2.
3.
Indicating lamps for CB open , close, spring charge and auto trip
indications
4.
5.
6.
7.
8.
9.
10.
Frequency meters
11.
12.
13.
Synchronising selector switch along with push button for dead Bus
closing.
14.
15.
16.
17.
67
18.
19.
To be mounted inside
1.
2.
3.
4.
5.
6.
7.
Relay Panel:
1.
2.
3.
4.
5.
6.
Bus bar protection scheme as per the detail given at Cl. No. 5.17.4 1
To be mounted inside:
1.
2.
3.
v)
SYNCHRONISING PANEL:
The swing door type synchronising panel shall be equipped as detailed at Cl. No. 5.18 above.
(vi)
132 KV & 66 kV TRANSFORMER (INCOMING) C&R PANELS FOR 132 KV& 66KV
SIDE OF 100 MVA, 220/132 KV & 220/66 kV TRANSFORMERS.
Each of the panels shall be equipped with the followings:On the front:
1.
Black PVC circuit label.
1
2.
Mimic diagram.
1
3.
Indication lamps for CB open, close & auto trip indications.
3
4.
Spring charge indication lamp.
1
5.
Semaphore indicators for isolator position indication for
double bus arrangements respectively.
2
6.
Semaphore indicator for CB position indication.
1
7.
Voltmeter.( to be fed from CVT for AVR)
1
8.
Ammeter suitably scaled.
1
9.
Ammeter selector switch.
1
10.
Spring return to neutral CB control switch with sequence
1
device, lost motion device & two pairs of bell alarm contracts.
68
11.
12.
13.
14.
15.
16.
2
1
2
1
2
1
1
1
1
(vii)
1
1
3
1
3
1
1
1
1
1
1
1
1
1
3
1
2
1
1
2
1
1
1
1
1
1
1
1
Note:- Protection & Metering will be fed from 132KV line CVTs in case of 132KV feeder
panels and from 66KV bus PTs in case of 66KV feeder panels.
69
viii)
132kV & 66 kV BUS COUPLER C&R PANEL.
The panel shall be equipped with the followings :1.
Black PVC circuit label.
2.
Mimic diagram.
3.
Indicating lamps for circuit breaker
open, close & auto trip indications.
4.
Spring charge indication lamp.
5.
Semaphore indicator for isolator position indication.
6.
Semaphore indicator for circuit breaker position indication.
7.
Ammeter suitably scaled for double bus arrangement only.
8.
Ammeter selector switch for double bus arrangement only.
9.
Voltmeter suitably scaled for double bus arrangement only.
10.
Voltmeter selector switch for double bus arrangement only.
11.
Spring return to neutral breaker control switch with
sequence device, lost motion device & two pairs of
bell alarm contacts.
12.
8 ways /10 ways static annunciator facia complete with accept,
reset and lamp test push buttons for main and transfer bus
arrangement and double bus arrangement respectively.
13.
Trip circuit supervision relays.
14.
Set of 3 non directional over current relays and 1 non directional
earth fault relay with high set.
15.
Set of Trip Ckt. DC supervision scheme including one no. push
button each for DC fail test and accept with one no.
indication lamp (amber) for DC fail visual indication.
16.
Synchronising switch along with push button for dead Bus closing
17.
High speed trip relay
18.
Spring return to neutral isolator control switches.
1
1
3
1
2
1
1
1
2
2
1
2
1
1
1
1
2
MOUNTED INSIDE
1.
2.
3.
4.
5.
6.
1
1
1
1
1
1
ix)
132 KV & 66 kV TRANSFORMER C&R PANEL FOR 132/33 kV, 66/33 kV,
132/11 KV & 66 /11 kV TRANSFORMER.
The C&R panel shall be equipped with the followings:-
1
1
3
1
2
1
1
1
1
1
70
11.
12.
13.
14.
2
1
1
1
1.
2.
3.
4.
a.
b.
c.
1
1
1
2
8
1
1
1
1
2
1
1
1
1
x)
1
1
3
1
3
1
1
1
1
1
1
1
1
1
1
1
2
2*
71
MOUNTED INSIDE
1.
Illumination lamp with door switch.
2.
Space heater with on/off switch.
3.
Power socket with on/off switch.
1
1
1
xi)
33 kV TRANSFORMER INCOMER C&R PANELS FOR 132/33KV T/Fs AND 66/33KV T/Fs
Each of these panels shall be equipped with the followings:-
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
MOUNTED INSIDE
1.
Illumination lamp with door switch.
2.
Space heater with on/off switch.
3.
Power socket with on/off switch.
4.
AC buzzer for DC fail alarm.
5.
DC bell for trip alarm.
6.
DC hooter for non trip alarm.
(xii)
1
1
3
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
TO BE MOUNTED ON FRONT:1.
Circuit label.
2.
Mimic diagram section.
3.
Semaphore indicator for isolator/earth switch.
4.
Semaphore indicator for C.B.
5.
Indicating lamps for C.B. open, close, auto, trip
and spring charge.
6.
Trip circuit supervision relay.
7.
Spring return to neutral breaker control switch with lost motion
device with two pairs of bell alarm contact and sequence device.
8.
Ammeter suitably scaled.
9.
Ammeter selector switch.
10.
Time delay relay for closing of breaker with time
1
1
3
1
4
1
1
1
1
1
72
17.
18.
19.
20.
1
1
1
2
1.
2.
3.
4.
1
1
1
1
11.
12.
13
14.
15.
16.
1
1
2
1
1
1
(xiii)
33KV TRANSFORMER C&R PANEL FOR 4 MVA 33/11 kV TRANSFORMER.
The C&R panel shall be equipped with the followings:On the front :1.
2.
3.
4.
5.
6.
7.
8.
9.
1
1
3
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
73