Testing Synchrophasor Data
Testing Synchrophasor Data
D. H. Wilson, PhD
K. Hay, PhD
T. Cumming
D. Cole
Psymetrix
Edinburgh, UK
Psymetrix
Edinburgh, UK
Psymetrix
Edinburgh, UK
Scottish Power
Glasgow, UK
Qualitrol
Belfast, UK
tom.cumming@
sppowersystems.com
The present IEEE C37.118-2005 standard for synchrophasor measurement [1] defines the steady state
performance of PMUs, but dynamic performance is not
covered. Nevertheless, different approaches for phasor
estimation and requirements under transient and dynamic conditions can be found in the literature [2, 3, 4].
Also, some steady-state requirements can be more stringent than the C37.118 requirements.
While PMU performance testing has been addressed
in literature [5, 6], it is generally not related to the specific requirements of the applications using the data. In
this paper, the testing exercise reported is related directly to the requirements of the applications, and the focus
of the testing was to qualify a specific PMU model for
use in the intended applications.
There are other sources of error, in particular because
of the accuracy of the instrumentation channels including the current and voltage transducers. It is known
those errors can be larger than the PMU itself [7]. The
instrumentation channels are important for applications
requiring accurate results, such as the line parameter
estimation. However, it is generally less significant for
dynamics application. This paper does not address instrumentation channels issues, but rather focuses on
testing and qualification of the PMU.
2
The main drivers for implementing a WAMS system
were to do with increasing the utilization of the transmission while maintaining system security. This is increasingly challenging in view of the renewable generation targets in Scotland.
The performance of the PMUs was tested for the following application requirements:
Oscillatory stability monitoring, requiring knowledge
of gain and phase, and good attenuation of aliased
components
Transient detection and reporting, requiring fast response to disturbances
Line parameter estimation, requiring high steady-state
accuracy
In this paper, the testing methodology for each of these application areas is described, and test results reported. It was concluded that the PMU was suitable for the
areas of application that were intended, within certain
boundaries, which were clearly understood through the
testing exercise.
2
APPLICATION REQUIREMENTS
1.14
Start Time
Overshoot
1.12
Settling Time
1%
Delay Time
1.1
Value (pu)
1.08
1.06
Rise Time
1.04
1.02
1
0.98
-0.1
-0.05
0.05
0.1
0.15
Time (sec)
0.2
0.25
0.3
4
necessary to configure the line parameter estimation to
provide results in value ranges where the measurements
are sufficiently accurate to yield results. Also, an assessment of the measurement accuracy is of interest for
the use of the measurements in post-event analysis.
Imbalanced test signals were applied to ensure that
there was no inter-dependence between the measurements of each phase. The steady-state tests were also run
at different frequencies to ensure that the results were
not influenced by frequency deviation from the nominal.
The phase angle tests are evaluated based on the absolute reference phase, where the 0 angle is defined at
the second transition provided by PPS clock [1]. Given
that the signal generator output was triggered by PPS,
the angle values reported by the PMU should corresponds exactly to the signal generator output.
TEST RESULTS
Occurencies [%]
0.9
0.8
0.5
V 0.5pu
V 1.0pu
0
Voltage (1.0pu)
Voltage (0.7pu)
Current (1.0pu)
Current (0.3pu)
0.005
0.01
0.015
0.02
0.025
0.03
Voltage Mag. Abs. Error Variation [%]
0.035
Occurencies [%]
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.5
I 0.5pu
I 1.0pu
0
0.01
0.02
0.03
0.04
Current Mag. Abs. Error Variation [%]
0.05
10
20
30
40
50
60
70
Window Length (samples)
80
90
100
6
ripple. This response is as good as can be achieved with
a PMU. Similar responses were achieved for all phases,
for upward and downward steps.
The V&I step response of angle to a large angle step
(15), illustrated in Figure 10, shows a similarly short
fast rise time and delay time, which is less than one
sample. However, there is a small 1-sample ripple that
does not overshoot the target value, and the value takes
100ms to reach the 1% limit for the settling time. Similar results are obtained for voltage steps.
A smaller angle step (3, Figure 11) shows similar
performance to the 15 angle step, but with a smaller
overshoot value.
V Attenuation (dB)
-5
-10
-15
-20
-25
-30
10
15
20
25
30
35
40
45
50
The phasor outputs are composed by the voltage and current phasors. In addition, the bus frequency signal is reported
by the PMU in the same data frame [1]. Frequency is generally calculated from the voltage waveform and is independent of
the phasor calculation.
100
V mag
Amplitude Modulation
V angle
Phase Angle Modulation
V Phase (deg)
50
-50
10
-1
0
-5
-2
-3
-4
-10
-5
-15
-6
-20
-25
-30
-35
-40
-45
10
15
20
25
30
35
40
45
50
70
60
50
40
30
20
10
0
5 DISCUSSION
From the testing carried out, it is concluded that the
PMU under test is suitable for use in the three contrasting applications considered. In particular, it may be
noted that:
The PMU steady-state accuracy in normal situations
is significantly better than the requirement for 1%
TVE specified in the C37.118 standard. This is important for line parameter estimation.
The transient response to a change in signal level is
very fast. The rise time is short, with negligible delay
and very little settling time.
For analysing oscillations, there is very little attenuation in the band 0-10Hz for V&I measurements, however to achieve sufficient attenuation of aliased components, a bandwidth of 0-4Hz is used. This is sufficient to cover electromechanical and frequency control modes.
There is a trade-off to be made between the transient
performance of the PMU and the oscillation performance. Filtering with a sharper roll-off would improve
oscillation performance with greater attenuation of high
frequency components while providing good in-band
performance. However, such filtering would also tend to
slow the transient performance and increase the overshoot and ripple. Some further work would be of value
to investigate whether further high frequency attenuation
is possible without a significant influence on the transient
performance, so that the bandwidth 0-10Hz can be
6
used. The extended frequency range would be useful, for
example, for generator control system tuning.
The extended bandwidth could also be used if there
are no significant components of frequency in the range
40-46Hz. It is thought that such components are unusual
in the power system. Since the PMU device is also a
disturbance recorder, it would be possible to cross-check
using waveform data if observations of frequency at 410Hz were correctly represented, or were aliased components.
The testing process has shown that the V&I phasor
data is more reliable for oscillation analysis than the
frequency output. The frequency output is restricted to a
narrow bandwidth, and cannot be used directly if the
relative phase of oscillations is important. However, it is
relatively straightforward to derive a frequency signal
from voltage angle data, and this should provide a more
useful representation of dynamic frequency.
The testing process has proved to be valuable in gaining experience in configuring and using the information.
It was found, for example, that the application requirements were better served using the high resolution configuration of the PMU, rather than the option of an extended measurement range. The high resolution setting
is necessary for any PMUs used for line parameter estimation, and is strongly recommended for at least some,
if not all of the oscillation monitoring points. There may
be some locations where the extended range may be
necessary for the disturbance monitoring functions, but
where possible, the high resolution setting is preferred
for wide-area monitoring applications.
8
This paper addresses the accuracy of the PMU itself.
As mentioned previously, the instrumentation channels
are important for applications requiring accurate results,
such as line parameter estimation. The influence of the
measurement chain is reported [7] and is the subject of
further research.
The testing that has been done has focused on the use
of the PMUs as part of a monitoring system, and not for
control. Depending on the specific requirements of control applications, there may be further testing to be done
on the continuity of data and the latency between a system change and the change being reported.
6 CONCLUSIONS
The testing process has proven the capability of the
PMU to be used for three applications that serve as
examples of applications requiring:
High steady-state accuracy;
Fast response;
Accurate representation of oscillations.
It has been proven that the tested PMU satisfies the
main requirements of all three applications. This paper
relates the process and results of PMU testing to the
needs of applications, and shows how the PMU performance enables and also bounds the information that can
be derived from synchrophasors. The testing process
and results can also be applied to requirements for future
applications.
REFERENCES
[1] IEEE C37.118. "Standard for Synchrophasors for
Power Systems", 2005.
[2] Phadke, A. G.; Kasztenny, B. "Synchronized Phasor and Frequency Measurement Under Transient
Conditions". IEEE Transactions on Power Delivery.
2009.
[3] Premerlani, W.; Kasztenny, B.; Adamiak, M. "Development and Implementation of a Synchrophasor
Estimator Capable of Measurements Under Dynamic
Conditions". IEEE Transactions on Power Delivery.
2008.
[4] "PMU System Testing and Calibration Guide".
North American Synchrophasor Iniciative (NASPI),
Performance and Standart Task team. 2007.
[5] Steinhauser F. Test and Calibration of Phasor
Measurement Units, International Protection Testing Symposium, 2008.
[6] Huang, Z.; Hauer, J. F.; Martin, K. E. "Evaluation of
PMU Dynamic Performance in Both Lab Environments and under Field Operating Conditions". 2007.
[7] Lira, R., "Influence of Instrumentation Channels
Accuracy in Synchronised Phasor Measurement" (in
Portuguese), Master's Thesis, Federal University of
Santa Catarina, Brazil, 2010.
[8] Wilson D.H., Hay K., Maclaren R. F. B., Hawkins
D.J., Dunn A., Middleton A. J., Carter A., Hung W.
Control Centre Applications of Integrated WAMS-
based Dynamics Monitoring and Energy Management Systems. Cigre Session, Paris, 2008
[9] OMICRON High Precision Relay test set and universal calibrator CMC 256 plus (http://
www.omicron.at /en/products/pro/secondary-testingcalibration/cmc-256plus/).
AUTHOR'S BIOGRAPHIES
Ricardo Lira received his MSc in 2010 from Federal
University of Santa Catarina, Brazil, focusing on synchrophasor measurement accuracy. He joined Psymetrix
Ltd (now part of the Alstom Group) as a Power System
Engineer in the same year. Currently working on developments in WAMS applications such as data quality and
line parameter estimation.
Dr Douglas Wilson is Chief Technology Officer for
Psymetrix Ltd. He has worked with Psymetrix since
1998, and is involved in synchrophasor measurement
systems and applications, dynamics analysis and control
and renewable generation connection. He graduated
B.Eng(Hons) and PhD from the University of Edinburgh
and MSc from the University of Manchester. He is involved in R&D, consulting and in commercial application of synchrophasor technology.
Dr Karine Hay received her PhD degree in signal
processing from University of Rennes I in 1997. She is a
senior engineer with Psymetrix Ltd, having worked in
the company since 1998. She is involved in signal processing for online power system stability measurement
and analysis.
Thomas Cumming MSc Power Systems and High
Voltage Engineering. System Monitoring Engineer for
Scottish Power, part of Iberdrola Group Responsible for
all aspects of fault recording, system monitoring, fault
analysis and location, plant condition monitoring, PD
and DGA systems. The development and application of
new technologies including PMU's and IEC61850. 35
years experience in the Power Industry.
David Cole BSc Hons - Product Manager at Qualitrol for Fault and System Disturbances responsible for
the development and subsequent sales of on-line travelling wave based fault locators and multi function disturbance recorders that include power quality and PMU.
Past experience includes testing of HV circuit breakers,
research on locating partial discharge sites in drum
lengths of polymeric cable and time with a UK Distribution company.