Tutorial2 Solution
Tutorial2 Solution
Figure 1:
Solution: Generator reactance on its own base is 0.15 p.u.
Transformer T1s p.u. reactance on new base MVA and kV is
2
100
32
T1
Xp.u = 0.08
= 0.06838p.u.
110
33
Base Voltage on secondary of transformer T1 is
33
110
= 113.43kV
32
32
= 33kV
110
= 0.5509p.u.
30
33
100
M3 : 0.2
50
100
M2 : 0.2
20
30
33
2
= 0.3305p.u.
30
33
2
= 0.8264p.u.
Figure 2:
Solution:
(a) p.u. reactance of generator on its own base is 0.18 p.u.
p.u. reactance of T1 is
T1
Xpu
80
= 0.12
20
11
11
2
= 0.48p.u.
50 80
= 0.0826p.u.
2202
p.u. reactance of T2 is
80
= 0.1
20
11
11
2
= 0.4p.u.
80
= 0.08
20
11
11
2
= 0.32p.u.
T2
Xpu
p.u. reactance of T3 is
T3
Xpu
60 80
= 0.3966p.u.
1102
p.u. reactance of T4 is
T4
Xpu
80
= 0.06
20
11
11
2
= 0.24p.u.
2
= 0.289p.u.
p.u. reactance of M1 is
M1
Xpu
80
= 0.15
40
10.8
11
(b)
112
= 1.5125
80
112
=
= 4.84 + 3.63i
16 12i
Zp.u. = 3.2 + 2.4i
Zbase =
Zactual
3. A 100 MVA, 13.8 kV, 3 phase generator has reactance of 20 %. The generator is connected to a 3 phase transformer (T1) rated 100 MVA, 12.5 kV/110 kV with 10 %
reactance. The HV side of the transformer is connected to a transmission line of reactance 100 . The far end of the line is connected to a step-down transformer T2 made
of 3 single phase transformers, connected in Y - , each rated 30 MVA, 66 kV/10 kV
with 10 % reactance. The generators supply two motors connected on the LV side of
T2. The motors are rated at 25 MVA and 50 MVA both at 10 kV with 15 % reactance.
Draw the reactance diagram showing all the values in p.u. Take generator rating as
T1
line
T2
M1
base.
[Xp.u
= 0.0820p.u., Xp.u
= 0.6780p.u., Xp.u
= 0.0985p.u., Xp.u
= 0.5319p.u.,
M2
Xp.u = 0.2659p.u. ]
Solution: Generator reactance on its base is 0.2 p.u.
p.u. reactance of T1 is
2
100
12.5
T1
Xpu = 0.1
= 0.0820p.u.
100
13.8
Vbase on the secondary side of T1=13.8
110
= 121.44kV
12.5
100 100
= 0.6780p.u.
121.442
121.44
on the secondary side of T2=10
= 10.62kV
3 66
2
100
10
T2
Xpu = 0.1
= 0.0985p.u.
90
10.62
M1
Xpu
100
= 0.15
25
10
10.62
2
= 0.5319p.u.
M2
Xpu
100
= 0.15
50
10
10.62
2
= 0.2659p.u.
4. A 3 bus system is given in Figure 3. The ratings of various components are listed below.
G1: 50 MVA, 13.8 kV, X=0.15 p.u.; G2: 40 MVA, 13.2 kV, X=0.2 p.u.; G3: 30 MVA,
11 kV, X=0.25 p.u.; T1: 45 MVA, 11 kV / 110 kV, X=0.1 p.u.; T2: 25 MVA, 12.5 kV
/ 115 kV, X=0.15 p.u.; T3: 40 MVA, 12.5 kV / 115 kV, X=0.1 p.u.
The line impedances are as shown in figure. Determine the reactance diagram based on
T1
50 MVA and 13.8 kV as base quantities in Generator 1.
[Xp.u
= 0.0705p.u.,
line12
line23
T2
G2
T3
Xp.u = 0.1312p.u., Xp.u = 0.0656p.u., Xp.u = 0.2083p.u., Xp.u = 0.1936p.u., Xp.u
=
0.0868p.u]
Figure 3:
Solution:
T1
Xpu
G1
Xpu
= 0.15p.u.
2
50
11
= 0.1
= 0.0705p.u.
45
13.8
110
= 138kV
11
50 50
= 0.1312p.u.
1382
25 50
line23
= Xpu
=
= 0.0656p.u.
1382
line12
Xpu
=
line13
Xpu
12.5
= 15kV
115
2
50
12.5
= 0.15
= 0.2083p.u.
25
15
G2
Xpu
50
= 0.2
40
13.2
15
2
= 0.1936p.u.
12.5
= 15kV
115
2
50
12.5
= 0.1
= 0.0868p.u.
40
15
[Xp.u. = 0.5p.u.]
Consider base quantities as 5 kVA and 200 V on the low voltage side of the transformer.
Solution: The per-unit value of reactance referred to primary side is
4 0.005
= 0.5p.u
0.22
The ohmic value of reactance referred to secondary side is
2
400
= 16
4
200
The per-unit value of reactance referred to secondary side is
16 0.005
= 0.5p.u
0.42
300
2 6 = 4.9589p.u.
11 3
6
= 18
11 3
Vbase on secondary is 33 kV.
Secondary
Xp.u.
=
300
18 = 4.9589p.u.
332