Atv600 Profibus DP Manual
Atv600 Profibus DP Manual
EAV64329 08/2015
EAV64329.01
08/2015
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific user
applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
2015 Schneider Electric. All rights reserved.
EAV64329 08/2015
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hardware Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Common Additional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identification and Maintenance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I&M Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 PROFIdrive Parameters Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROFIdrive Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROFIdrive Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PROFIdrive Parameter Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EAV64329 08/2015
5
9
11
12
13
15
16
16
17
18
19
20
21
22
24
25
27
28
29
30
31
33
35
36
37
38
39
40
41
42
43
44
45
46
47
49
50
51
52
53
54
55
56
59
61
64
65
66
67
Telegram 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
State Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Command Word and Operating State Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Fieldbus Integration Tutorial. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fieldbus Integration Tutorial. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Operating States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Communication Error Response. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the Control Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration of the Drive for Operation in I/O Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode. . . . . . . . .
Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode. . . . . . . . . .
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71
72
73
76
77
77
81
82
82
83
84
85
86
87
89
90
91
92
93
95
97
99
EAV64329 08/2015
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, or maintain it. The following special messages may appear throughout this
documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.
Qualification Of Personnel
Only appropriately trained persons who are familiar with and understand the contents of this manual and
all other pertinent product documentation are authorized to work on and with this product. In addition, these
persons must have received safety training to recognize and avoid hazards involved. These persons must
have sufficient technical training, knowledge and experience and be able to foresee and detect potential
hazards that may be caused by using the product, by changing the settings and by the mechanical,
electrical and electronic equipment of the entire system in which the product is used. All persons working
on and with the product must be fully familiar with all applicable standards, directives, and accident
prevention regulations when performing such work.
EAV64329 08/2015
Intended Use
This product is a drive for three-phase synchronous and asynchronous motors and intended for industrial
use according to this manual.The product may only be used in compliance with all applicable safety
regulations and directives, the specified requirements and the technical data.Prior to using the product, you
must perform a risk assessment in view of the planned application. Based on the results, the appropriate
safety measures must be implemented.Since the product is used as a component in an entire system, you
must ensure the safety of persons by means of the design of this entire system (for example, machine
design). Any use other than the use explicitly permitted is prohibited and can result in hazards. Electrical
equipment should be installed, operated, serviced, and maintained only by qualified personnel.
Product Related Information
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
z
z
z
z
z
z
z
z
Only appropriately trained persons who are familiar with and understand the contents of this manual
and all other pertinent product documentation and who have received safety training to recognize and
avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment,
repair and maintenance must be performed by qualified personnel.
The system integrator is responsible for compliance with all local and national electrical code
requirements as well as all other applicable regulations with respect to grounding of all equipment.
Many components of the product, including the printed circuit boards, operate with mains voltage. Do
not touch. Use only electrically insulated tools.
Do not touch unshielded components or terminals with voltage present.
Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the
drive system, block the motor shaft to prevent rotation.
AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused
conductors of the motor cable.
Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
Before performing work on the drive system:
z Disconnect all power, including external control power that may be present.
z Place a Do Not Turn On label on all power switches.
z Lock all power switches in the open position.
z Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator
of the absence of DC bus voltage that can exceed 800 Vdc.
Measure the voltage on the DC bus between the DC bus terminals (PA/+, PC/-) using a properly
rated voltmeter to verify that the voltage is <42 Vdc
z If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative. Do not repair or operate the product.
Install and close all covers before applying voltage.
WARNING
UNEXPECTED MOVEMENT
Drive systems may perform unexpected movements because of incorrect wiring, incorrect settings,
incorrect data or other errors.
z Carefully install the wiring in accordance with the EMC requirements.
z Do not operate the product with unknown or unsuitable settings or data.
z Perform a comprehensive commissioning test.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Damaged products or accessories may cause electric shock or unanticipated equipment operation.
EAV64329 08/2015
DANGER
ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION
Do not use damaged products or accessories.
Failure to follow these instructions will result in death or serious injury.
Contact your local Schneider Electric sales office if you detect any damage whatsoever.
WARNING
LOSS OF CONTROL
z
z
z
z
z
The designer of any control scheme must consider the potential failure modes of control paths and,
for critical control functions, provide a means to achieve a safe state during and after a path failure.
Examples of critical control functions are emergency stop, overtravel stop, power outage and restart.
Separate or redundant control paths must be provided for critical control functions.
System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
Observe all accident prevention regulations and local safety guidelines (1).
Each implementation of the product must be individually and thoroughly tested for proper operation
before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
(1) For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition),
Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed
Drive Systems.
NOTICE
DESTRUCTION DUE TO INCORRECT MAINS VOLTAGE
Before switching on and configuring the product, verify that it is approved for the mains voltage
Failure to follow these instructions can result in equipment damage.
EAV64329 08/2015
EAV64329 08/2015
Action
In the Search box type the reference of a product or the name of a product range.
z Do not include blank spaces in the model number/product range.
z To get information on grouping similar modules, use asterisks (*).
If you entered a reference, go to the Product Datasheets search results and click on the reference that
interests you.
If you entered the name of a product range, go to the Product Ranges search results and click on the
product range that interests you.
If more than one reference appears in the Products search results, click on the reference that interests
you.
Depending on the size of your screen, you may need to scroll down to see the data sheet.
To save or print a data sheet as a .pdf file, click Download XXX product datasheet.
The characteristics that are presented in this manual should be the same as those characteristics that
appear online. In line with our policy of constant improvement, we may revise content over time to improve
clarity and accuracy. If you see a difference between the manual and online information, use the online
information as your reference.
EAV64329 08/2015
Related Documents
Use your tablet or your PC to quickly access detailed and comprehensive information on all our products
on www.schneider-electric.com
The internet site provides the information you need for products and solutions
z The whole catalog for detailed characteristics and selection guides
z The CAD files to help design your installation, available in over 20 different file formats
z All software and firmware to maintain your installation up to date
z A large quantity of White Papers, Environment documents, Application solutions, Specifications... to
gain a better understanding of our electrical systems and equipment or automation
z And finally all the User Guides related to your drive, listed below:
Title of Documentation
Reference Number
EAV64300 (English)
EAV64325 (English)
EAV64327 (English)
EAV64328 (English)
EAV64329 (English)
EAV64330 (English)
EAV64331 (English)
EAV64333 (English)
EAV64332 (English)
EAV64334 (English)
You can download these technical publications and other technical information from our website at
http://download.schneider-electric.com
Terminology
The technical terms, terminology, and the corresponding descriptions in this manual normally use the
terms or definitions in the relevant standards.
In the area of drive systems this includes, but is not limited to, terms such as error, error message, failure,
fault, fault reset, protection, safe state, safety function, warning, warning message, and so on.
Among others, these standards include:
z IEC 61800 series: Adjustable speed electrical power drive systems
z IEC 61508 Ed.2 series: Functional safety of electrical/electronic/programmable electronic safety-related
z EN 954-1 Safety of machinery - Safety related parts of control systems
z EN ISO 13849-1 & 2 Safety of machinery - Safety related parts of control systems.
z IEC 61158 series: Industrial communication networks - Fieldbus specifications
z IEC 61784 series: Industrial communication networks - Profiles
z IEC 60204-1: Safety of machinery - Electrical equipment of machines Part 1: General requirements
In addition, the term zone of operation is used in conjunction with the description of specific hazards, and
is defined as it is for a hazard zone or danger zone in the EC Machinery Directive (2006/42/EC) and in
ISO 12100-1.
Also see the glossary at the end of this manual.
10
EAV64329 08/2015
Presentation
Chapter 1
Presentation
EAV64329 08/2015
Page
Hardware Overview
12
Software Overview
13
11
Presentation
Hardware Overview
General
The VW3A3607 is a PROFIBUS DP fieldbus module that can be used in a PROFIBUS DP industrial
fieldbus. The module has a 9-pin female Sub-D connector for connection to the PROFIBUS DP network.
The figure shows the hardware presentation of the VW3A3607 PROFIBUS DP fieldbus module:
12
EAV64329 08/2015
Presentation
Software Overview
Compatibility
The VW3A3607 communication module enables the integration of a variable speed drive into a PROFIBUS
DP fieldbus. This module offers the possibility to control its host drive in native profile or with the
PROFIdrive profile.
Profile
Telegrams
100,101,102,106,107
I/O profile
100,101,102,106,107
PROFIdrive
EAV64329 08/2015
13
Presentation
14
EAV64329 08/2015
Basics
Chapter 2
Basics
EAV64329 08/2015
Topic
Page
Introduction
16
2.2
17
2.3
20
15
Basics
Introduction
Section 2.1
Introduction
Introduction
PROFIBUS
PROFIBUS DP is the fast PROFIBUS version which is specially designed for communication in production
processes and for building automation. Features of PROFIBUS DP includes simple connection of new
devices in the bus and high transmission rates.
Device Identification
A master device uses the Ident number to identify the device class of the connected slave. The Ident
number is a unique number assigned to each device class by the PNO.
Slave Address
Each device on the network must be assigned a unique address from 1 to 126.
The master (normally address 0 ... 2) can communicate with each slave via this address.
PROFIBUS DP V1 Communication
PROFIBUS DP-V1 allows cyclic and acyclic communication between master and slave. Acyclic
communication is slower than cyclic communication, however it enables the modification of parameters
during operation.
The product supports acyclic communication as per PROFIBUS specification for MS0 communication.
The product supports acyclic communication for DP-V1 as per PROFIBUS specification for MS1 and MS2
communication.
The following services are available for acyclic communication:
16
Service
Master Class 1
Master Class 2
READ
WRITE
INITIATE
Connect to master C2
ABORT
EAV64329 08/2015
Basics
Common Additional Features
Section 2.2
Common Additional Features
EAV64329 08/2015
Page
18
I&M Record
19
17
Basics
18
EAV64329 08/2015
Basics
I&M Record
Description
The table provides the details of I&M record:
EAV64329 08/2015
Champ
Number of
Bytes
Value
Description
HEADER_MANUF_SPEC
MANUFACTURER_ID
10 bytes
(string)
Manufacturer-specific field
2 bytes
01 hex, 29 hex
ORDER_ID
SERIAL_NUMBER
20 bytes
Identification object ID 1
16 bytes
Serial number
HARDWARE_REVISION
2 bytes
10 hex, 00 hex
SOFTWARE_REVISION
4 bytes
V, A, B, C
REVISION_COUNTER
2 bytes
xx hex, yy hex
Rev xy
PROFILE_ID
2 bytes
PROFILE_SPECIFIC_TYPE
2 bytes
IM_VERSION
2 bytes
01 hex, 02 hex
IM_SUPPORTED
2 bytes
00 hex, 01 hex
19
Basics
PROFIdrive Parameters Channel
Section 2.3
PROFIdrive Parameters Channel
20
Page
PROFIdrive Profile
21
Parameter Structure
22
PROFIdrive Parameters
24
25
EAV64329 08/2015
Basics
PROFIdrive Profile
Overview
When operated with the PROFIdrive profile, the drive parameters are organized as defined by PNU
numbering and addressing modes. However, for people who are familiar with the Altivar parameters, this
addressing mode keeps the native structure of the device (based on Modbus addressing). PNU is
numbered from 0...65535 and each PNU represents a parameter (from single type as words to complex
data structure or arrays). PROFIdrive parameters from PNU 900 ...PNU 999 are standardized, they are
described below. All others PNUs are manufacturer-specific.
In the case of this drive, parameters can be separated in two groups:
Standardized PNUs (900...999)
z Drive parameters which are gathered in a single PNU entry point: PNU1000 and Modbus address as
subindex. It is also possible to access the parameters using the Modbus address as PNU for each
parameter (1001...59999) and 0 as subindex.
z
EAV64329 08/2015
21
Basics
Parameter Structure
PROFIdrive Telegram
The table describes the PROFIdrive header:
DU
Byte Nr
Request
Function code
Slot_num
0: global parameters
Index
Length
Data
4...5
10 hex
PWE
+ Sub index
20 hex
PBE
+ Sub index
30 hex
Text
+ Sub index
22
EAV64329 08/2015
Basics
Drive Parameters
Each drive parameter can be represented according to the PNU standard structure. Drive parameters are
part of the PNU 1000 or can be accessed using the Modbus address as PNU number.
The table provides the possible values of a parameter according to the PNU properties:
EAV64329 08/2015
Parameter Property
Drive Implementation
Example
PNU number
1000
Sub index
Modbus address
PWE
PBE
Constant
Text
Drive parameter
23
Basics
PROFIdrive Parameters
PROFIdrive Standard Parameters
Parameters 900 to 999 are defined in accordance with the PROFIdrive profile.
The table describes the required parameters:
PNU
Sub -ID
Definition
Data Type
R/W
Comments
900
Control telegram.
Image of PZD
907
Controller < DO
PNU900 contains the
cyclical frame if supervisor
handles the DO
Status telegram.
Image of PZD
922
Telegram selection
UINT
1,100,101,102,106,107
927
Operation priority
UINT
R/W
Enables control
928
Control priority
UINT
=1
930
Operating mode
UINT
=1
944
UINT
947
Error number
UINT
963
UNIT
964
Manufacturer ID
Drive unit
String
Version (drive)
INT
24
965
Profile identification
number
UINT
980...989
UINT
EAV64329 08/2015
Basics
Request data
Byte n+1
Byte n
Request reference = 01
Request ID = 01
Axis = 01 hex
Number of parameters = 01
Attribute = 10 hex *
Number of elements = 01
Response
Byte n+1
Response header
Response data
Byte n
Request reference = 01
Request ID = 01
Axis = 01 hex
Number of parameters = 01
Format = 42 hex *
Number of elements = 01
NOTE: byte 41 hex, word 42 hex, standard integer 03 hex, double word 43 hex.
Parameter Writing
Request
Byte n+1
Byte n
Request header
Request reference = 01
Request ID = 02
Axis = 01 hex
Number of parameters = 01
Parameter number
Attribute = 10 hex *
Number of elements = 01
Format = 42 hex
Amount values = 01
Response
Byte n+1
Response header
EAV64329 08/2015
Byte n
Request reference = 01
Request ID = 02
Axis = 01 hex
Number of parameters = 01
25
Basics
Byte n
Request reference = 01
Request ID = 82*
Axis = 01 hex
Number of parameters = 01
Parameter number
Number of values
Value
With the sub index in addition to the detected error value, the total length of the answer is 10 bytes.
26
EAV64329 08/2015
Hardware Setup
Chapter 3
Hardware Setup
EAV64329 08/2015
Page
Hardware Presentation
28
29
30
Electrical Installation
31
33
27
Hardware Setup
Hardware Presentation
PROFIBUS DP Fieldbus Module
The figure shows the PROFIBUS DP fieldbus module equipped with a Sub-D 9 connector:
28
Sub-D 9 connector
EAV64329 08/2015
Hardware Setup
EAV64329 08/2015
29
Hardware Setup
DANGER
ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION
Do not use damaged products or accessories.
Failure to follow these instructions will result in death or serious injury.
Insertion of the Fieldbus Module
The table provides the procedure for insertion of the PROFIBUS DP fieldbus module in the drive:
Step
Action
Locate the fieldbus module slot (A) on the bottom of the control part.
Add the corresponding sticker on the LED front panel of the drive.
Check that the module is correctly inserted and locked mechanically in the drive.
Slot A
30
Action
EAV64329 08/2015
Hardware Setup
Electrical Installation
Pin Layout
The VW3A3607 fieldbus module is equipped with a sub-D 9 female connector for the PROFIBUS DP
connection.
Use only validated PROFIBUS connectors. The PROFIBUS connectors are suitable for connecting the
fieldbus signal.
z Connect the PROFIBUS signals.
z If the device is at the end of the network, use a PROFIBUS connector with a terminating resistor.
z Fasten the cables to the cable guide. The cable guide is not a strain relief.
The table provides the pin out details of the sub-D 9 connector:
Pin
Signal
Meaning
Shield
Not connected
RxD/TxD-P
Receive/Transmit-data-P
CNTR-P
Control-P
DGND
Data ground
VP
Voltage plus
Not connected
RxD/TxD-N
Receive/Transmit-Data-N
Not connected
Cable Specification
Cable specifications are as follows:
Use equipotential bonding conductors.
z Use pre-assembled cables to reduce the wiring mistakes.
z Shield: both end grounded.
z Twisted-pair cable.
z Verify that wiring, cables, and connected interfaces meet the PELV requirements.
z The maximum cable length depends on the baud rate and the signal propagation delay, that is, shorter
bus cable for higher baud rate.
z
EAV64329 08/2015
9.6
19.2
93.75
187.5
500
1500
3000
6000
12000
Distance m (ft.)
1200
(4000)
1200
(4000)
1200
(4000)
1000
(3300)
400
(1300)
200
(650)
100
(330)
100
(330)
100
(330)
31
Hardware Setup
Terminating Resistor
Both ends of the entire PROFIBUS DP network must be terminated with a terminating resistor. Use
PROFIBUS connectors with integrated terminating resistors at both ends of the network.
The schematic diagram shows the terminating resistor combination:
32
EAV64329 08/2015
Hardware Setup
EAV64329 08/2015
33
Hardware Setup
34
EAV64329 08/2015
Software Setup
Chapter 4
Software Setup
EAV64329 08/2015
Topic
Page
Basic Settings
36
4.2
Communication Profile
42
4.3
77
35
Software Setup
Basic Settings
Section 4.1
Basic Settings
36
Page
Introduction
37
[Address] ( AdrC)
38
39
40
41
EAV64329 08/2015
Software Setup
Introduction
Overview
The parameters are described according to the graphic display terminal. These settings are also possible
from commissioning software.
EAV64329 08/2015
37
Software Setup
[Address] ( AdrC)
About This Parameter
This parameter defines the PROFIBUS DP slave address.
Access
The parameter is accessible in the [Communication] ( COM) /[Comm Parameters] ( CMP) , [Profibus]
( PbC-) menu.
The parameter number is 6601
Possible Settings
38
Settings
Code
Value
Description
[2...126]
2...126
2...126
PROFIBUS address
Factory setting: 126
EAV64329 08/2015
Software Setup
EAV64329 08/2015
Settings
Code
Value
Description
[Automatic]]
[9600 bps]
[10 Kbps]
[19200 bps]
[45.45 Kbps]
[93.75 Kbps]
[187.5 Kbps ]
[500 Kbps]
[1.5 Mbps ]
[3 Mbps]
[6 Mbps]
[12 Mbps]
AUtO
9K6
10K
19K2
45K4
93K7
187K
500
1M5
3M
6M
12M
4
28
30
32
37
42
54
68
80
82
83
88
39
Software Setup
40
Settings
Code
Value
Description
[UnCG]
[1]
[100]
[101]
[102]
[106]
[107]
unCG
1
100
101
102
106
107
0
1
100
101
102
106
107
UNCFG
Profidrive
Device specific
Device specific
Device specific
Device specific
Device specific
Factory setting: 0
EAV64329 08/2015
Software Setup
EAV64329 08/2015
Settings
Code
Value
Description
[MCL1]]
[MCL2]
1
2
1
2
Active master
Factory settings: 1
41
Software Setup
Communication Profile
Section 4.2
Communication Profile
42
Page
Definition of a Profile
43
44
Functional Description
45
46
47
Summary
49
50
Stop Commands
51
52
53
Starting Sequence
54
55
56
59
61
64
65
66
Parameters Management with the Telegram 100, 101, 102, 106, 107
67
Telegram 1
71
State Diagram
72
73
Reference Frequency
76
EAV64329 08/2015
Software Setup
Definition of a Profile
Types of Profiles
There are 3 types of profile:
z Communication profiles
z Functional profiles
z Application profiles
Communication Profile
A communication profile describes the characteristics of a bus or network:
z Cables
z Connectors
z Electrical characteristics
z Access protocol
z Addressing system
z Periodic exchange service
z Messaging service
z ...
A communication profile is unique to a type of fieldbus (such as Modbus, PROFIBUS DP, and so on) and
is used by different types of devices.
Functional Profile
A functional profile describes the behavior of a type of device:
z Functions
z Parameters (such as name, format, unit, type, and so on.)
z Periodic I/O variables
z State chart
z ...
A functional profile is common to all members of a device family (such as variable speed drives, encoders,
I/O modules, displays, and so on).
They can feature common or similar parts. The standardized (IEC 61800-7) functional profiles of variable
speed drives are:
z CiA402
z PROFIDRIVE
z CIP
DRIVECOM has been available since 1991.
CiA402 device profile for drives and motion control represents the next stage of this standard development
and is now part of the IEC 61800-7 standard.
Some protocols also support the Open DeviceNet Vendor Association profile (ODVA).
Application Profile
Application profile defines the services to be provided by the devices on a machine. For example, CiA DSP
417-2 V 1.01 part 2: CANopen application profile for lift control systems - virtual device definitions.
Interchangeability
The aim of communication and functional profiles is to achieve interchangeability of the devices connected
via the fieldbus.
EAV64329 08/2015
43
Software Setup
44
EAV64329 08/2015
Software Setup
Functional Description
Introduction
Drive operation involves two main functions, which are illustrated in the diagrams below.
CiA402
The main parameters are shown with their CiA402 name and their CiA402/Drivecom index (the values in
brackets are the CANopen addresses of the parameter).
The following figure shows the control diagram for drive operation:
Altivar Drive
These diagrams translate as follows for the Altivar drive.
The following figure shows the control diagram for drive operation:
EAV64329 08/2015
45
Software Setup
46
EAV64329 08/2015
Software Setup
Description
2 - Switch on disabled
3 - Ready to switch on
The power stage is ready to switch on and awaiting power stage supply mains.
For a separate control stage, it is not necessary to supply the power stage, but the
system expects it in order to change to state 4 - Switched on.
For a separate control stage with mains contactor, the contactor is not closed.
The drive is locked, no power is supplied to the motor.
The configuration and adjustment parameters can be modified.
4 - Switched on
5 - Operation enabled
EAV64329 08/2015
47
Software Setup
48
Operating State
Description
The drive performs a fast stop and remains locked in the operating state 6-Quick
stop active. Before restarting the motor, it is required to go to the operating state
2-switch on disabled.
During fast stop, the drive is unlocked and power is supplied to the motor.
The configuration parameters cannot be modified.
The condition for transition 12 to state 2 - Switch on disabled depends on the
value of the parameter
Quick stop mode (QStd):
If the Quick stop mode parameter has the value FST2, the drive stops according
to the fast stop ramp and then changes to state 2 - Switch on disabled .
If the Quick stop mode parameter has the value FST6, the drive stops according
to the fast stop ramp and then remains in state 6 - Quick stop active until:
z A Disable voltage command is received or
z The STOP key is pressed or
z A freewheel stop command via the digital input of the terminal.
7 - Fault reaction
active
Transient state during which the drive performs an action corresponding to the
selected error response.
8 - Fault
EAV64329 08/2015
Software Setup
Summary
Device Status Summary
EAV64329 08/2015
Operating State
Power Supplied to
Motor
Modification of Configuration
Parameters
1 - Not ready to
switch on
Not required
No
Yes
2 - Switch on
disabled
Not required
No
Yes
3 - Ready to
switch on
Not required
No
Yes
4 - Switched on
Required
No
5 - Operation
enabled
Required
Yes
No
6 - Quick stop
active
Required
No
7 - Fault reaction
active
Depends on error
response configuration
8 - Fault
Not required
No
Yes
49
Software Setup
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Fault reset
Reserved
(=0)
Reserved
(=0)
Reserved
(=0)
Enable
operation
Quick stop
Enable
voltage
Switch on
1 = Run
command
0 = Quick
stop active
Authorization
to supply AC
power
Mains
contactor
control
0 to 1
transition =
Error is
reset (after
cause of
error is no
longer
active)
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Manufacturer
specific
assignable
Manufacturer
specific
assignable
Manufacturer
specific
assignable
Manufacturer
specific
assignable
Manufacturer
specific
Reserved
(=0)
Reserved
(=0)
Halt
Command
State
Transition
Final
Operating
State
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Fault
Reset
Enable
Operation
Quick
Stop
Enable
Voltage
Switch
On
Shutdown
2, 6, 8
3 - Ready
to switch
on
0006 hex
Switch on
4 Switched
on
0007 hex
Enable
operation
5 Operation
enabled
000F hex
Disable
operation
4 Switched
on
0007 hex
Disable
voltage
7, 9, 10, 12
2 - Switch
on
disabled
0000 hex
6 - Quick
stop
active
0002 hex
01
0080 hex
Quick stop 11
Fault
reset
7, 10
2 - Switch
on
disabled
15
2 - Switch
on
disabled
Halt
0 = Forward
direction
asked
1= Reverse
direction
asked
Example
Value
50
EAV64329 08/2015
Software Setup
Stop Commands
Halt Command
The Halt command enables movement to be interrupted without having to leave the 5 - Operation
enabled state. The stop is performed in accordance with the [Type of stop] ( Stt) parameter.
If the Halt command is active, no power is supplied to the motor and no torque is applied.
Regardless of the assignment of the [Type of stop] ( Stt) parameter [Fast stop Assign] ( FSt) ,
[Ramp stop] ( rMP) , [Freewheel Stop] ( nSt) , or [DC Injection Assign] ( dCI) , the drive remains
in the 5 - Operation enabled state.
Fast Stop Command
A Fast Stop command at the terminals or using a bit of the control word assigned to Fast Stop causes
a change to the 4 - Switched on
Freewheel Command
A Freewheel Stop command using a digital input of the terminal or a bit of the control word assigned
to Freewheel Stop causes a change to operating state 2 - Switch on disabled.
EAV64329 08/2015
51
Software Setup
Fieldbus Module
Bit 11
C311
Bit 12
C312
Bit 13
C313
Bit 14
C314
Bit 15
C315
For example, to assign the DC injection braking to bit13 of the fieldbus module, simply configure the [DC
Injection Assign] ( dCI) parameter with the [C313] ( C313) value.
Bit 11 is assigned by default to the operating direction command [Reverse Assign] ( rrS) .
52
EAV64329 08/2015
Software Setup
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Warning
Switch on
disabled
Quick stop
Voltage
enabled
Fault
Operation
enabled
Switched on
Ready to
switch on
Error
detected
Running
Ready
1 = Awaiting
power
Stage
supply
0 = Quick
Power stage
stop is active supply
present
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Manufacturer
-specific
Direction of
rotation
Manufacturerspecific Stop
via STOP key
Reserved
(=0)
Reserved
(=0)
Internal limit
active
Target
reached
Remote
Reserved (=0)
Reference
value outside
limits
Reference
value
reached
Command
or reference
value via
fieldbus
Operating
State
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Switch On
Disabled
Quick
Stop
Voltage
Enabled
Fault
Operation
Enabled
Switched
On
Ready to
Switch On
1 -Not
ready to
switch on
2 -Switch
on
disabled
0040 hex
3 -Ready
to switch
on
0021 hex
4 Switched
on
0023 hex
5 Operation
enabled
11
0027 hex
6 -Quick
stop
active
0007 hex
7 -Fault
reaction
active
8 -Fault
0008 hex(2)..
.0028 hex
(1)
ETA
Masked by
006F H (1)
This mask can be used by the PLC program to test the diagram state.
(2)
EAV64329 08/2015
53
Software Setup
Starting Sequence
Description
The command sequence in the state diagram depends on how power is being supplied to the drive.
There are 3 possible scenarios:
Power stage
supply
Direct
Direct
Control stage
supply
Separate
Separate
(1)
54
EAV64329 08/2015
Software Setup
Step 2
z
z
z
Check that the drive is in the operating state 3 - Ready to switch on.
Then apply the 4 - Enable operation command.
The motor can be controlled (send a reference value not equal to zero).
NOTE: It is possible, but not necessary to apply the 3 - Switch on command followed by the 4 Enable Operation command to switch successively into the operating states 3 - Ready to Switch
on, 4 - Switched on and then 5 - Operation Enabled. The 4 - Enable operation command
is sufficient.
EAV64329 08/2015
55
Software Setup
56
EAV64329 08/2015
Software Setup
Step 2
z
z
Check that the drive is in the operating state 3 - Ready to switch on.
Check that the power stage supply is present (Voltage enabled of the status word).
Status Word
Absent
nLP
21 hex
Present
rdY
31 hex
EAV64329 08/2015
Terminal Display
57
Software Setup
Step 3
z
z
z
z
58
EAV64329 08/2015
Software Setup
EAV64329 08/2015
The power stage supply is not present as the mains contactor is not being controlled.
Apply the 2 - Shutdown command.
59
Software Setup
Step 2
z
z
60
Check that the drive is in the operating state 3 - Ready to switch on.
Apply the 3 - Switch on command, which closes the mains contactor and switch on the power stage
supply.
EAV64329 08/2015
Software Setup
The native mode of the PROFIBUS DP VW3A3607 is used when telegram 100 is used.
The PKW area of telegram 100, which is used for a simple parameter management, is compliant with the
PKW mechanism used with the PROFIBUS DP fieldbus module of the Altivar 32, 61, 71.
NOTE: After switching from one telegram to another, the drive shall be restarted to validate the new
configuration.
The following diagram shows the native modes for telegram 101, 106, 107:
EAV64329 08/2015
61
Software Setup
The following diagram shows the native modes for telegram 102:
Periodic Exchanges
The following table provides the details of telegram 100, 101, and 102
Telegram 100
Telegram 101
Telegram 102
PLC>VSD
VSD>PLC
PLC>VSD
VSD>PLC
PLC>VSD
PKW 1
PKE
PKE
PKE
PKE
VSD>PLC
PKW 2
R/W
R/W
R/W
R/W
PKW 3
PWE
PWE
PWE
PWE
PKW 4
PWE
PWE
PWE
PWE
Cyclic data 1
OCA1 address OMA1 address OCA1 address OMA1 address OCA1 address OMA1 address
of ETA =3201*
of ETA =3201* of CMD
of ETA =3201* of CMD
of CMD
=8501*
=8501*
=8501*
Cyclic data 2
OCA2 address OMA2 address OCA2 address OMA2 address OCA2 address OMA2 address
of RFRD
of LFRD
of RFRD
of LFRD
of RFRD
of LFRD
=8604*
=8602*
=8604*
=8602*
=8604*
=8602*
Cyclic data 3
OCA3 default
=0
OMA3 default
=0
OCA3 default
=0
OMA3 default
=0
Cyclic data 4
OCA4 default
=0
OMA4 default
=0
OCA4 default
=0
OMA4 default
=0
Cyclic data 5
OCA5 default
=0
OMA5 default
=0
OCA5 default
=0
OMA5 default
=0
Cyclic data 6
OCA6 default
=0
OMA6 default
=0
OCA6 default
=0
OMA6 default
=0
62
EAV64329 08/2015
Software Setup
The following table provides the details of telegram 106 and 107
Telegram 106
Telegram 107
PLC>VSD
VSD>PLC
PLC>VSD
VSD>PLC
PKW 1
PKE
PKE
PKE
PKE
PKW 2
R/W
R/W
R/W
R/W
PKW 3
PWE
PWE
PWE
PWE
PKW 4
PWE
PWE
PWE
PWE
Cyclic data 1
OCA1 address of
CMD =8501*
OMA1 address of
ETA =3201*
OCA1 address of
CMD =8501*
OMA1 address of
ETA =3201*
Cyclic data 2
OCA2 address of
LFRD =8602*
OMA2 address of
RFRD =8604*
OCA2 address of
LFRD =8602*
OMA2 address of
RFRD =8604*
Cyclic data 3
OCA3 default =0
OMA3 default =0
OCA3 default =0
OMA3 default =0
Cyclic data 4
OCA4 default =0
OMA4 default =0
OCA4 default =0
OMA4 default =0
Cyclic data 5
OCA5 default =0
OMA5 default =0
OCA5 default =0
OMA5 default =0
Cyclic data 6
OCA6 default =0
OMA6 default =0
OCA6 default =0
OMA6 default =0
Cyclic data 7
OCA7 default =0
OMA7 default =0
OCA7 default =0
OCA7 default =0
Cyclic data 8
OCA8 default =0
OMA8 default =0
OCA8 default =0
OCA8 default =0
Cyclic data 9
OCA9 default =0
OCA9 default =0
Cyclic data 10
OCA10 default =0
OCA10 default =0
Cyclic data 11
OCA11 default =0
OCA11 default =0
Cyclic data 12
OCA12 default =0
OCA12 default =0
Cyclic data 13
OCA13 default =0
OCA13 default =0
Cyclic data 14
OCA14 default =0
OCA14 default =0
Cyclic data 15
OCA15 default =0
OCA15 default =0
Cyclic data 16
OCA16 default =0
OCA16 default =0
The configuration of the cyclic data is made with the PROFIBUS DP master configuration tool. The Modbus
address of the parameter linked to each cyclic data must be defined as in the following example with the
HW configuration software:
Input cyclic data 1/2 and output cyclic data 1/2 are already preconfigured to (CMd) (8501) and (LFrd)
(8602); (EtA) (3201) and (rFrd) (8604).
If a null address Modbus is entered, no link between the related cyclic data and the drive is established. In
any case, the 6 cyclic data are not disabled and the 6 cyclic data takes place in the I/O memory image of
the controller.
1
2
EAV64329 08/2015
63
Software Setup
64
EAV64329 08/2015
Software Setup
Define the addresses of the cyclic data and PKW data in the PLC periphery:
By default, the process data are linked to (CMd), (LFrd), (EtA) and (rFrd) (native CiA 402 profile
of the drive).
You can check that the exchanges are working properly with the Monitor/Modify function of the
configuration tool:
EAV64329 08/2015
65
Software Setup
1
2
New parameters are added or modified by entering the drive Modbus address.
For example: (OMA3) is configured to read the value of (ACC), which Modbus address is 9001.
66
EAV64329 08/2015
Software Setup
Parameters Management with the Telegram 100, 101, 102, 106, 107
Description
In native modes several accesses to the drive parameters are possible:
z The standard acyclic requests from PROFIdrive, for more information see PROFIdrive Parameters
Channel (see page 20).
z PKW mechanisms consistent with Altivar 32,61, and 71 for 16-bit data.
Parameter Management Through the PKW Area
With telegram 100, 101, 106, 107 you can read or write any drive parameter by using this PKW area. (This
addressing format is identical to the PKW mechanism of the Altivar 32,61, and 71).
NOTE: The management of the parameters (compatibility with series 1 product) is Schneider Electric
specific. Actually, previous versions of PROFIdrive also specified parameter management thought PKW,
are not compatible with Schneider Electric method. In recent versions, parameters are managed with
acyclic messages, and the PNO PKW method is obsolete.
The PKW area is made of four input words and four output words.
The table lists the controller-to-drive parameters in the input PKW area:
PKW Number
PKE Name
Description
PKW1
PKE
PKW2
R/W
Request code:
0: no request
1: read
2: write (16 bit)
3: write (32 bit)
PKW3
PWE
PKW4
PWE
The table lists the drive-to-controller parameters in the output PKW area:
EAV64329 08/2015
PKW Number
PKE Name
Description
PKW1
PKE
PKW2
R/W
Response code:
0: no request
1: read done (16 bit)
2: write done (16 bit)
3: request in progress
4: read done (32 bit)
5: write done (32 bit)
7: read or write error
PKW3
PWE
PKW4
PWE
67
Software Setup
Byte - nr
Function code
Slot_num
Index
Length
Data
4-5
Bytes
Request
Positive answer
Negative answer
Function code
5E hex (read)
5F hex (write)
5E hex (read)
5F hex (write)
DF hex (read)
DE hex (write)
Slot_num
80 hex
Index
E9 hex
E9 hex
Length
Data
4-5
68
Step 2:
DU
Bytes
Request
Positive answer
Negative answer
Function code
5E hex (read)
5F hex (write)
5E hex (read)
5F hex (write)
DF hex (read)
DE hex (write)
Slot_num
80 hex
Index
EA hex
E9 hex
Length
Data
4-5
EAV64329 08/2015
Software Setup
EAV64329 08/2015
69
Software Setup
70
EAV64329 08/2015
Software Setup
Telegram 1
Overview
The following diagram shows the operating modes:
The following section describes how the VW3A3607 is operated when configured in PROFIdrive mode
(telegram 1).
The selection of this mode is done while configuring the slave device with the PROFIBUS DP network
configuration tool. It is out of the scope of this document to describe how to use such tool. However, you
can find in the examples (see Configuring the Drive With a Siemens S7-300 ) how to configure the
module for the Schneider PLCs and for the SIMATIC S7 PLCs.
Periodic Exchanges
The periodic exchanges, with PROFIdrive application class 1 profile consists of:
z 16-bit command word (STW1) and 16-bit reference word (NSOLL_A),
z 16-bit operating state word (ZSW1) and 16-bit actual velocity word (NIST_A).
The mapping of these words is automatically done when you select telegram 1 during the configuration of
the device.
NOTE: After switching from one telegram to another, restart the controller to validate the new
configuration.
EAV64329 08/2015
71
Software Setup
State Diagram
Description
The following state diagram shows the PROFIdrive state machine for the application class 1. The diagram
also describes the command word and operating state word.
72
EAV64329 08/2015
Software Setup
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Fault reset
Enable
operation
Quick stop
Coast stop
ON/OFF
Bit 9
Bit 8
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Control and
reference by
PLC
The table lists the status from PROFIdrive application profile class 1:
ZSW1
EAV64329 08/2015
Bit 7
Bit 6
Bit 5
Warning
Switching
inhibited
Bit 15
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Quick stop
Coast stop
Error
not activated not activated detected
Operation
enabled
Ready to
operate
Ready to
switch ON
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Reserved
Reserved
Reserved
Reserved
F or n
reached or
exceeded
Control
requested
Speed error
found within
tolerance
range
73
Software Setup
Bit 1
Bit 2
Bit 3
ON
OFF
(OFF 1)
The drive is ramped-down along the ramp (RFG) or along the current limit or
along the voltage limit of the d.c. Link if standstill is detected and power is
disabled when deceleration bit 1 of ZSW1 is still set.
An OFF command is interruptible (the drive returns to the
ready for switching on operating state).
No coast stop
No quick stop
Quick stop; if required, withdraw the operating enable, the drive is decelerated
as fast as possible. For example, along the current limit or at the voltage limit
of the d.c. Link, at n / f = 0; if the rectifier pulses are disabled, the power
voltage is disabled (the contact is opened) and the drive goes into the
Switching On Inhibited operating state.
A Quick Stop command is not interruptible.
Enable operation
Disable operation
The fault reset function is active with a positive edge; the drive error response
depends on the type of detected error. If the error response has isolated the
voltage, the drive then goes into the Switching On Inhibited operating
state.
Channel for the reference frequency and the command from the bus are
active.
Bit 4
Reserved
Bit 5
Reserved
Bit 6
Not used
Bit 7
Fault reset
Bit 8
Not used
Bit 9
Not used
Bit 10
Control by fieldbus
No control by fieldbus 0
74
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Channel for the reference frequency and the command from the bus are not
active.
EAV64329 08/2015
Software Setup
Ready to switch ON
Mains power supply is switched on, electronics are initialized, pulses are
inhibited.
Bit 1
Ready to operate
Bit 2
Operation enabled
Operation disabled
Either the power stage is disabled or the drive does not follow the reference
frequency.
Error detected
An error has been detected. The drive error response depends on the type of
detected error. The Fault Reset function may only be successfully used if the
detected error cause has disappeared or has been removed. If the detected
error response has disabled the power stage, the drive goes into the
Switching On Inhibited operating state, otherwise the drive returns to
Operation operating state.
No error detected
Switching inhibited
Switching not
inhibited
Warning present
No warning
Speed feedback
within tolerance
range
Control requested
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
EAV64329 08/2015
No control requested 0
Control by the automation system is not possible, only possible at the device
level, by another interface or the drive is controlled from a supervisor (Master
class 2).
Reference frequency 1
reached or exceeded
Actual output frequency reference frequency which may be set via the
parameter number.
Reference frequency 0
not reached
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
75
Software Setup
Reference Frequency
Channel for Reference Frequency
The reference frequency, written in NSOLL_A is defined by the following formula:
Reference frequency in Hz = (NSOLL_A x [Max Frequency] (tFr)) /4000 HEX
Reference Frequency Range
The table lists the different values for the reference frequency and the correspondence for the drive:
Value
0x0000
0x4000
0xC000
76
EAV64329 08/2015
Software Setup
Fieldbus Integration Tutorial
Section 4.3
Fieldbus Integration Tutorial
EAV64329 08/2015
77
Software Setup
78
EAV64329 08/2015
Software Setup
EAV64329 08/2015
79
Software Setup
80
EAV64329 08/2015
Operation
Chapter 5
Operation
EAV64329 08/2015
Topic
Page
5.1
Operating States
82
5.2
Operating Modes
83
81
Operation
Operating States
Section 5.1
Operating States
Meaning
Stop on ramp
Fast stop
DC injection stop
The values of the () parameter, which does not trigger a transition to the operating state fault are:
Value
Meaning
[Ignore] (nO)
The drive maintains the speed at the time the detected error occurred, as long
as the detected error persists, and the run command has not been removed
The fallback speed can be configured in the [Complete settings] (CSt-), [Error/Warning handling]
(CSWM-) menu, [Fallback speed] ( LFF-) submenu, using the [FallbackSpeed] (LFF) parameter.
WARNING
LOSS OF CONTROL
If this parameter is set to nO, fieldbus communication monitoring is disabled.
z Only use this setting after a thorough risk assessment in compliance with all regulations and standards
that apply to the device and to the application.
z Only use this setting for tests during commissioning.
z Verify that communication monitoring has been re-enabled before completing the commissioning
procedure and performing the final commissioning test.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
82
EAV64329 08/2015
Operation
Operating Modes
Section 5.2
Operating Modes
EAV64329 08/2015
Page
84
85
Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode
86
Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode
87
83
Operation
84
EAV64329 08/2015
Operation
[HMI] (HMI)
[I/O profile] IO
Default
[CD01] (Cd01)
In the [Error/Warning handling] ( CSWM-) menu, [Fault reset] ( rSt-) submenu, configure:
[Fault Reset Assign] (rSF)
EAV64329 08/2015
[CD07] (Cd07)
85
Operation
Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode
Description
This section describes how to configure the settings of the drive if it is controlled in CiA 402 mode. The
example focuses on the not separate mode. Additional modes are detailed in the drive programming
manual.
In the [Complete settings] (CSt-) menu, [Command and Reference] (CrP-) submenu:
z [Ref Freq 1 Config] (Fr1): is set on according to the communication source you can choose in the
following table:
Origin of the Control
PROFIBUS DP
z
z
[Freq Switch Assign] (rFC) is set to default value ([Ref Freq 1 Config] (Fr1)).
[Control Mode] (CHCF): defines if the drive operates in combined mode (reference and command
from the same channel).
For the current example, [Control Mode] (CHCF) is adjusted to [Not separ.] (SIM) as reference and
control are originated from the communication network:
86
Profile
[Separate] (SEp)
I/O profile
EAV64329 08/2015
Operation
Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode
Description
Alternate combinations are possible, see the drive programming manual for the list of possible settings.
For example:
The drive is controlled from the fieldbus (PROFIBUS DP) but the reference value is adjusted on the
controller terminal. The control word comes from the controller and is written according to CiA 402 profile.
The settings are as shown in the table:
EAV64329 08/2015
[AI1] (AI1)
[Separate] (SEp)
Factory setting
87
Operation
88
EAV64329 08/2015
Chapter 6
Diagnostic and Troubleshooting
EAV64329 08/2015
Page
90
91
92
Communication Interruption
93
95
Control-Signal Diagnostics
97
89
LED Description
Item
LED
Description
RUN
Module status
BF
Module Status
This LED indicates the module status:
Color & Status
Description
OFF
Green ON
90
Description
OFF
Red ON
Red flashing
Incorrect configuration
EAV64329 08/2015
EAV64329 08/2015
91
92
EAV64329 08/2015
Communication Interruption
Description
The drive triggers an error [Internal Link Error] (ILF) when the following events occur:
z Hardware error is detected on the PROFIBUS DP module
z Communication interruption between the PROFIBUS DP module and the drive
The response of the drive in the event of an [Internal Link Error] (ILF) error cannot be configured, and
the drive stops in freewheel. This detected error requires a power reset.
The diagnostic parameter can be used to obtain more detailed information about the origin of the [Internal
Link Error] (ILF) ([InterCom Error1] (ILF1) if the detected error has occurred on fieldbus module in
slot A).
The [InterCom Error1] (ILF1) parameter can be accessed on the graphic display terminal in the
[Communication map] (CMM-) menu, [PROFIBUS DIAG] (pRb-) submenu.
Value
No error detected
EEPROM
Flash memory
RAM memory
NVRAM memory
101
Unknown module
102
103
EAV64329 08/2015
Description
1...6
Reserved
Ext_Diag_Data
10
11
12
93
Enabling Diagnostics
By default, extended diagnostics are disabled. They can be activated during the configuration phase as
shown below:
94
EAV64329 08/2015
Parameter Code
Taken Into Account Modbus
by the Drive
Serial
CANopen
Control word
( CMd)
( CMd1)
( CMd2)
( CMd3)
( CMd5)
Extended control
word
( CMI)
( CMI1)
( CMI2)
( CMI3)
( CMI5)
Reference speed
(rpm)
( LFd)
( LFd1)
( LFd2)
( LFd3)
( LFd5)
Reference frequency
(0.1 Hz)
( LFr)
( LFr1)
( LFr2)
( LFr3)
( LFr5)
( LTR)
( LTR1)
( LTR2)
( LTR3)
( LTR5)
Reference value
supplied by PI
controller
( PISP)
( PIr1)
( PIr2)
( PIr3)
( PIr5)
Reference value
supplied by analog
multiplier function
( MFr)
( MFr1)
( MFr2)
( MFr3)
( MFr5)
torque)(1)
(1):
If available
Criteria
PROFIBUS module
Error Code
[Fieldbus Com Interrupt] ( CnF)
EAV64329 08/2015
95
96
The drive copies the run commands, the direction, and the forced local reference value to the active
channel (maintained).
Monitoring of the active command and reference value channels resumes following a time delay [Timeout forc. local] ( FLOt) .
Drive control only takes effect once the drive has received the reference value and the command from
the active channel.
EAV64329 08/2015
Control-Signal Diagnostics
Introduction
On the display terminal, the [Display] ( MON-) , [Communication map] ( CMM-) submenu can be
used to display control-signal diagnostic information between the drive and the controller:
z Active command channel [Command Channel] ( CMdC)
z Value of the control word [Cmd Register] ( CMd) from the active command channel [Command
Channel] ( CMdC)
z Active reference frequency channel [Ref Freq Channel] ( rFCC)
z Value of the reference frequency [Pre-Ramp Ref Freq] ( FrH) from the active target channel [Ref
Freq Channel] ( rFCC)
z Value of the operating state word [CIA402 State Reg] ( EtA)
z Specific data for all available fieldbus are in dedicated submenus.
z In the [Command word image] ( CWI-) submenu: control words from all channels
z In the [Freq. ref. word map] ( rWI-) submenu: reference frequency values produced by all channels
Control Word Display
The [Command Channel] ( CMdC) parameter indicates the active command channel.
The [Cmd Register] ( CMd) parameter indicates the hexadecimal value of the control word (CMD) used
to control the drive.
The [Command word image] ( CWI-) submenu ([COM. Module cmd.] ( CMd3) ) parameter is used
to display the hexadecimal value of the control word from the fieldbus module.
Reference Frequency Display
The [Ref Freq Channel] ( rFCC) parameter indicates the active channel for reference frequency.
The [Ref Frequency] ( LFr) parameter indicates the value (in 0.1 Hz units) of the reference frequency
used to control the drive.
The [Freq. ref. word map] ( rWI-) submenu ([Com Module Ref Freq] ( LFr3) parameter is used
to display the value (in 0.1 Hz units) of the reference frequency from the fieldbus.
Operating State Word Display
The [CIA402 State Reg] ( EtA) parameter gives the value of the operating state word (ETA).
The table provides the bit details of ETA parameter:
EAV64329 08/2015
Bit
Description
DRIVECOM
Status word
Bit0 = 1
Ready to switch on
Bit1 = 1
Switched on
Bit2 = 1
Operation enabled
Bit3 = 1
Bit4 = 1
Bit5 = 0
Quick stop
Bit6 = 1
Switch on disabled
Bit7 = 1
Warning
Bit8 = 1
Drivecom reserved
Bit9 = 0
Bit10 = 1
Bit11 = 1
Bit12
Reserved
Bit13
Reserved
Bit14 = 1
Bit15 = 0
97
98
EAV64329 08/2015
Glossary
A
Abbreviations
Req. = Required
Opt. = Optional
D
Display terminal
The display terminal menus are shown in square brackets.
For example: [Communication]
The codes are shown in round brackets.
For example: (COM-)
Parameter names are displayed on the display terminal in square brackets.
For example: [Fallback Speed]
Parameter codes are displayed in round brackets.
For example: (LFF)
DP
Decentralized Periphery
E
Error
Discrepancy between a detected (computed, measured, or signaled) value or condition and the specified
or theoretically correct value or condition.
F
Factory setting
Factory settings when the product is shipped
Fault
Fault is an operating state. If the monitoring functions detect an error, a transition to this operating state is
triggered, depending on the error class. A "Fault reset" is required to exit this operating state after the
cause of the detected error has been removed. Further information can be found in the pertinent standards
such as IEC 61800-7, ODVA Common Industrial Protocol (CIP).
Fault Reset
A function used to restore the drive to an operational state after a detected error is cleared by removing
the cause of the error so that the error is no longer active.
M
Monitoring function
Monitoring functions acquire a value continuously or cyclically (for example, by measuring) in order to
check whether it is within permissible limits. Monitoring functions are used for error detection.
MS0, MS1
Number of a master in the network.
P
Parameter
Device data and values that can be read and set (to a certain extent) by the user.
EAV64329 08/2015
99
Glossary
PELV
Protective Extra Low Voltage, low voltage with isolation. For more information: IEC 60364-4-41
PLC
Programmable logic controller
PNO
PROFIBUS Nutzerorganisation e.V. (PROFIBUS User organization).
Power stage
The power stage controls the motor. The power stage generates current for controlling the motor.
Q
Quick Stop
The quick Stop function can be used for fast deceleration of a movement as a response to a detected error
or via a command.
W
Warning
If the term is used outside the context of safety instructions, a warning alerts to a potential problem that
was detected by a monitoring function. A warning does not cause a transition of the operating state.
Z
Zone of operation
This term is used in conjunction with the description of specific hazards, and is defined as it is for a hazard
zone or danger zone in the EC Machinery Directive (2006/42/EC) and in ISO 12100-1.
100
EAV64329 08/2015
Altivar_Process_600_Profibus_DP_Manual_EN_EAV64329_01
08/2015