FACTs Controllers Notes
FACTs Controllers Notes
FACTs Controllers Notes
From the above figure it is clear that between the sending and the receiving end, voltages magnitude
variation as well as a phase difference is created and the most significant part of the voltage drop in the
line reactance is due to the reactive component of the load current. In order to maintain the voltages in
the network nearly to desired the rated value two compensation methods are being used and are:
1. Load compensation
2. System compensation
1.3.1 Load Compensation
It is possible to compensate for the reactive current of the load by adding a parallel capacitive
load so that Ic = Ix and the effective power factor to become unity.
In the figure the absence of Ix eliminates the voltage drop V1 bringing Vr closer in magnitude to
Vs, this condition is called load compensation and actually by charging extra for supplying the
reactive power, a power utility company makes it advantageous for customers to use load
compensation on their premises.
Loads compensated to the unity power factor reduce the line drop but do not eliminate it. They
still experience a drop of V2 from jIrX1.
When the voltage magnitudes at the two ends of a line are equal that is Vs = Vr =V and the line is
said to be symmetrical because power networks operate as voltage sources attempts are made to
hold almost all node voltages at nearly rated values. Therefore a symmetrical line presents a
realistic situation.
Active and Reactive powers of a transmission line are frequently normalized by choosing the
Surge-Impedance Load (SIL) as the base.
1.3.5 Midpoint Conditions of a Symmetrical Line
The magnitude of the midpoint voltage depends on the power transfer and this voltage influences the line
insulation. For a symmetrical line where the end voltages are held at nominal values the midpoint voltage
shows the highest magnitude variation.
Performance of uncompensated lines:
1. The dynamic regulation of voltage at the receiving (load) end of the line by using a controllable reactive
source, improves power transfer and voltage profile along the line.
2. However, even with symmetrical lines (with voltages maintained at both ends), the power transfer
capability is decreased as the line length increases. Assuming that a line is operated with max = 30o, the
maximum power transfer reduces below SIL for line lengths > 30o (approximately 500 km long line in
systems operating at 50 Hz).
3. The problems of voltage control and charging reactive power (at no load) become severe as line length
increases. For a symmetric line, the voltage variation is maximum at the mid point of the line.
compensator mitigates the undesirable effects of the circuit parameters of a given line and the objectives
of line compensation are invariably
1. To increase the power-transmission capacity of the line.
2. To keep the voltage profile of the line along its length within acceptable bounds to ensure the
quality of supply to the connected customers, to minimize the line insulation costs.
1.4.1 Distributed Compensation
Let us consider distributed series compensation (capacitive) whose effect, in steady state, is to counteract
the effect of the distributed series inductance of the line. Similarly, by providing distributed shunt
(inductive) compensation, the effect of line capacitance is reduced.
1. The distributed shunt compensation reduces the no load voltage and charging reactive power, but
has little effect on the maximum power flow in the line.
2. The distributed series compensation reduces the no load voltage and increases the power transfer
capacity, but less little effect on the no load charging reactive power.
1.4.2 Discrete Passive Compensation
It is not practical to provide distributed compensation. Here, we will consider discrete series and shunt
compensation.
Types of passive compensations:
1. Shunt Compensation
2. Series Compensation
1.4.2.1 Shunt Compensation
In a weak system, voltage control can be implemented by parallel compensation using a Static
Var Compensator (SVC) for fast control of shunt connected capacitors and reactors. It also helps
in improve the power quality and as well as improvement of the voltage profile for different
system and load conditions.
Shunt compensation can also be employed as a local remedy against voltage collapse which can
occur when large induction machines are connected to the system.
After system faults the machines load the power system heavily with high reactive power
consumption and the remedy for such fault is strong capacitive power injection for example by
using an either SVC or STATCOM or just switched capacitors.
The reactive current is injected into the line to maintain voltage magnitude and transmittable
active power (P) is increased but more reactive power (Q) is to be provided.
2V 2
P
sin
X
2
2V 2
Q
X
cos
V2
P
sin
X X C
V2
1 cos
Q
X X C
Typically an SVC comprises one or more banks of fixed or switched shunt capacitors or reactors of
which at-least one bank is switched by thyristors.
The elements which may be used to make an SVC typically include:
Thyristor Controlled Reactor (TCR) where the reactor may be air or iron cored.
Thyristor Switched Capacitor (TSC).
Harmonic filter(s).
Mechanically switched capacitors or reactors.
Connection:
Generally SVC is not done at line voltage; a bank of transformers steps the transmission voltage
down to a much lower level. This reduces the size and number of components needed in the SVC
although the conductors must be very large to handle high currents associated with the lower
voltage.
In some SVC for industrial applications such as electric arc furnaces where there may be an
existing medium-voltage bus bar present the SVC may be directly connected in order to save the
cost of the transformer.
The dynamic nature of the SVC lies in the use of thyristors connected in series and inverseparallel forming thyristor valves and the disc-shaped semiconductors usually several inches in
diameter are usually located indoors in a valve house.
Advantages:
Near instantaneous response to changes in the system voltage. For this reason they are often
operated at close to their zero-point in order to maximize the reactive power correction they can
rapidly provide when required.
In general, cheaper, higher-capacity, faster and more reliable than dynamic compensation schemes
such as synchronous condensers.
The UPFC is the most versatile member of FACTS family using power electronics to control
power flow on power grids.
The UPFC uses a combination of a shunt controller (STATCOM) and a series controller (SSSC)
interconnected through a common DC bus.
This FACTS topology provides much more flexibility than the SSSC for controlling the line
active and reactive power because active power can now be transferred from the shunt converter
to the series converter through the DC bus.
The system impedance Xs indeed corresponds to the short circuit MVA at the SVC bus and is obtained
as
Xs
Vb MVAb
Sc
in p.u.
Where, Sc is the 3 phase short circuit MVA at the SVC bus, Vb is the base line-line voltage and MVAb is
the base MVA
The SVC bus voltage is given by
Vs = VSVC + ISVC . Xs
The SVC current thus results in a voltage drop of ISVC . Xs in phase with the system voltage Vs.
The SVC bus voltage decreases with the inductive SVC current and increases with the capacitive current.
The intersection of the SVC dynamic characteristic and the system load line provides the quiescent
operating of the SVC as illustrated in the below figure.
VSVC
1
1 X T .BSVC
VH
VH
BSVC
VH
XS
VH
XT
VSVC
BSVC
The initial operating point in the uncompensated and compensated systems are indicated by rotor
angles 1 and c1. These points correspond to the intersection between the respective power-angle
curves with the mechanical input line PM, which is same for both the cases.
In the event of a 3-phase-to-ground fault at the generator terminals, even though the short-circuit
current increases enormously, the active-power output from the generator reduces to zero.
Because the mechanical input remains unchanged, the generator accelerates until fault clearing,
by which time the rotor angle has reached values 2 and c2 and the accelerating energy, A1 and
AC1, has been accumulated in the uncompensated and compensated system, respectively.
When the fault is isolated, the electrical power exceeds the mechanical input power, and the
generator starts decelerating.
The rotor angle, however, continues to increase until 3 and c3 from the stored kinetic energy in
the rotor.
The decline in the rotor angle commences only when the decelerating energies represented by A2
and AC2 in the two cases, respectively, become equal to the accelerating energies A1 and AC1.
The power system in each case returns to stable operation if the post-fault angular swing, denoted
by d3 and dC3, does not exceed the maximum limit of dmax and dcmax, respectively. Should these
limits be exceeded, the rotor will not decelerate.
The farther the angular overswing from its maximum limit, the more transient stability in the
system.
An index of the transient stability is the available decelerating energy, termed the transientstability margin, and is denoted by areas Amargin and Acmargin in the two cases, respectively.
Clearly, as Acmargin significantly exceeds Amargin, the system-transient stability is greatly enhanced
by the installation of an SVC. The increase in transient stability is thus obtained by the
enhancement of the steady-state power-transfer limit provided by the voltage-control operation of
the midline SVC.
2.4.2.2 Synchronizing Torque
The synchronous generator is assumed to be driven with a mechanical-power input, PM. The
transmission line is further assumed to be lossless; hence the electrical power output of the generator, PE,
and the power received by the infinite bus are same. The swing equation of the system can be written as
d 2
M 2 PM PE
dt
d 2
M
PM PE
dt 2
The mechanical-input power is assumed to be constant during the time of analysis; hence PM =0. The
linearized-swing equation then becomes
d 2
M
PE
dt 2
d 2
1
dt 2
M
(or)
KS
PE
d 2 K S
0
dt 2
M
The characteristic equation of the differential equation provides two roots:
1 , 2
KS
M
If the synchronizing torque KS is positive, the resulting system is oscillatory with imaginary roots:
1 , 2 js
where
KS
M
On the other hand, if the synchronizing torque KS is negative, the roots are real. A positive real root
characterizes instability. The synchronizing-torque coefficient is now determined for both the
uncompensated and SVC-compensated systems.
2.4.3 Steady State Power Transfer Capacity
An SVC can be used to enhance the power-transfer capacity of a transmission line, which is also
characterized as the steady-state power limit. Consider a single-machine infinite-bus (SMIB) system with
an interconnecting lossless tie line having reactance X shown in Fig.
Let the voltages of the synchronous generator and infinite bus be V1/ and V2/, respectively. The
power transferred from the synchronous machine to the infinite bus is expressed as
The power thus varies as a sinusoidal function of the angular difference of the voltages at the
synchronous machine and infinite bus, as depicted in Fig. The maximum steady-state power that can be
transferred across the uncompensated line without SVC corresponds at = 90o; it is given by
Let the transmission line be compensated at its midpoint by an ideal SVC. The term ideal corresponds to
an SVC with an unlimited reactive-power rating that can maintain the magnitude of the midpoint voltage
constant for all real power flows across the transmission line. The SVC bus voltage is then given by
VM/(/ 2).The electrical power flow across the half-line section connecting the generator and the SVC is
expressed as
which is twice the maximum power transmitted in the uncompensated case and occurs at /2 =90 o. If the
transmission line is divided into n equal sections, with an ideal SVC at each junction of these sections
maintaining a constant-voltage magnitude (V), then the power transfer (PC) of this line can be expressed
theoretically by
The maximum power, Pcmax, that can be transmitted along this line is nV2/X. In other words, with n
sections the power transfer can be increased n times that of the uncompensated line. It may be
understood that this is only a theoretical limit, as the actual maximum power flow is restricted by the
thermal limit of the transmission line. It can be shown that the reactive-power requirement, QSVC, of the
midpoint SVC for the voltage stabilization is given by
This curve is based on the corresponding equivalent reactance between the synchronous generator and
the infinite bus. If an SVC incorporating a limited-rating capacitor as in the preceding text (QSVC -2Pmax)
is connected at the line midpoint, it ensures voltage regulation until its capacitive output reaches its limit.
In case the system voltage declines further, the SVC cannot provide any voltage support, and behaves as
a fixed capacitor. Curve (d) represents the power-angle curve that shows this fixed-capacitor behavior
and demonstrates that the realistic maximum power transfer will be much lower than the theoretical limit
of 2Pmax if the SVC has a limited reactive-power rating.
2.4.4 Enhancement of Power System Damping
The power-transfer capacity along a transmission corridor is limited by several factors; for example, the
thermal limit, the steady-state stability limit, the transient-stability limit, and system damping. In certain
situations, a power system may have inadequateeven negativedamping; therefore, a strong need
arises to enhance the electrical damping of power systems to ensure stable, oscillation-free power
transfer.
A typical scenario of the magnitude of various limits, especially where damping plays a
determining role, is depicted graphically in Fig. Oscillations in power systems are caused by
various disturbances.
If the system is not series-compensated, the typical range of oscillation frequencies extends from
several tenths of 1 Hz to nearly 2 Hz.
Several modes of oscillation may exist in a complex, interconnected power system.
The behavior of generator oscillations is determined by the two torque components: the
synchronizing torque and damping torque.
The synchronizing torque ensures that the rotor angles of different generators do not drift away
following a large disturbance.
In addition, the magnitude of the synchronizing torque determines the frequency of oscillation.
Meanwhile, damping torque influences the decay time of oscillations.
Even if a power system is stable, the oscillations may be sustained for a long period without
adequate damping torque.