Protection Coordination Report: Renew Saur Urja PVT LTD
Protection Coordination Report: Renew Saur Urja PVT LTD
Protection Coordination Report: Renew Saur Urja PVT LTD
GURGAON,HARYANA
00
Initial Submission
18/12/2016
Revision
Revision Particulars
Date
RC
CBR
CBR
Approve
Reviewed Checked
d
CLIENT
PROJECT
CONTRACTOR
CONSULTANT
DOCUMENT ID
No. of Pages
REPORT NO 08/2016-17
(INCLUDING THIS FRONT PAGE)
REVISION:
00
Contents
Sl.No
1
2
3
4
5
6
7
8
9
10
11
Descriptiion
Executive Summary
Reference Documents
Device Details
Single line diagram
Short Circuit Current Details
Transformer Relay Setting Calculations
Setting Details for Line Control Panel
Setting Details for Transformer Control Panel
Setting Details for Feeder Control Panel
Setting Details for 33 kV Switch Board
Time Current Characteristic Curves
Page No
3
4
5
6
8
18
20
26
31
38
48
Introduction
Project:
Owner:
Electrical Contractor:
ElectricalDistribution System
Power System Data
Max Source Fault level (assumed)
Tools used:
Protection Coordination
Input Data
Conclusion
Executive Summary
30MWp SPV Project at Malkanoor,Telangana
Renew Saur Urja Pvt Ltd
L&T, Navi,Mumbai
132kV,33 kV,0.380 kV Power Distribution System
25kA for 1 secs at 33 kV
Paladin Design Base 5- an Electrical Design software
Selectivity of relays were worked out based on the rating of
transformers,cable size and flow of short circuit currents.
Time current characterstic curves are generated for every path and
verified .
The SLD,Control and Relay panel drawings,Transformer Data sheets
Settings for each device,short circuit currents at every busbars,detailed
calculations for the settings are given in the following pages.
Details
132kV Switchyard SLD
33kV ICOG Panel
33kV SwitchBoard
33kV Feeder -1&2 Control & Protection Panel
132/33kV,25/30MVA Power Transformer Control & Protection Panel
ACSLD
30 MVA,Transformer Data sheets
132kV Switchyard Single line Diagram
132kV Line Control & Protection Panel
Technical Specification of Grid Connected PhotoVoltaic Inverter
Rated Specification of the Inverter (PVL-L1000E)
File reference
SLD_Mulkanoor.pdf
Drawing-400-29.08.16.pdf
Drawing-200-29.08.16.pdf
33KV TWIN FEEDER 1 & 2_REV-B_17.11.2016.pdf
132_33KV,25_30MVA TRANSFORMER CONTROL & PROTECTION PANEL_REVACSLD FOR FOR 30MW MULKANOOR PROJECT_TELANGANA 31 08 2016-Model.pdf
GTP-T-05516-4.pdf
RP-5212-DWG-ELE-AC-002-R2-132kV Switchyard SLD.DWG
132KV LINE CONTROL & PROTECTION PANEL_REV-B_17.11.2016.pdf
PVL-L1000E_INVERTER-TECHNICAL.pdf
TMEIC INVERTER-1000KW-DATA SHEET.pdf
Device Details
Transformers
Details of Equipment
kVA rating
High
Low voltage Percentage
Voltage
side
Impedance
side
30000
132000
33000
4400
2200
33000 V 380
33000 V 380
Low winding
High winding
Grounding Mode
Vector
Group
Type of
Cooling
12.49
Star
Star
Direct
YNyn0
ONAN/ONAF
3.20
3.20
Delta
Delta
Star
Star
Direct
Direct
YND
YND
AN
AN
GRID
APTRANSCO
50
51
LINE RELAYS
132bus_Grid
132 kV Bus
50
51
TR1_RELAYS_HV
TR_HT-132 BUS
TR1
CAB_TR1_LV
50
51
TR1_RELAYS_LV
33kV BUS-TRafo LV
33 kV Main SWBD (100)
FCP_IC1
508
50
51
511
50
51
512
50
51
50
51
363
132
362
86
CAB_IC1
OG000_SWBD1
OG000_SWBD2
50
51
50
51
UPS
7_INVR2
7 PV3
UPS
7 INV4
10_PV4-INVR4
10_PV3-INVR3
10_PV2-INVR2
7_PV2
7 INV3
10_INVR4-TR
10_INVR3-TR
10_INVR2-TR
7_PV1
491
400
6_PV4
492
6_PV3
10_PV1-INVR1
6_PV2
UPS
7_INVR1
354
353
352
344
6_PV1
UPS
480
477
10_INVR1-TR
351
UPS
6_INVR4
318
317
5_PV4
399
358
UPS
6_INVR3
372
367
350
UPS
6_INVR2
33kV
PNL5(400)
50
51
IC0G0_PNL5
ICR7_TR
334
331
349
UPS
6_INVR1
357
345
315
314
UPS
356
328
323
5_INVR4
5_PV3
IC0G0_PNL4
355
321
5_PV2
322
5_PV1
UPS
5_INVR3
316
308
176
4_PV4
UPS
5_INVR2
33kV
PNL4(400)
50
51
ICR6_TR
298
295
313
UPS
5_INVR1
9_TR1-BUS
8_TR1-BUS
309
UPS
320
319
173
4_PV3
292
287
4_INVR4
175
4_PV2
180
UPS
4_INVR3
174
166
208
4_PV1
8PV21
UPS
4_INVR2
7_TR4
172
UPS
4_INVR1
8_INVR2
7_TR3
171
UPS
8_INVR1
8_PV11
167
UPS
206
3_PV4
7_TR2
7_TR1
CAB_8INVR2
3_PV3
3_INVR4
204
3_PV2
UPS
3_INVR3
202
200
198
3_PV1
UPS
3_INVR2
233
CAB_8INVR1
UPS
3_INVR1
232
CAB:3_INVR4
UPS
243
CAB:3_INVR3
CAB:3_INVR2
2_PV4
242
IC0G0_PNL3
ICR5_TR
179
241
CAB:3_INVR1
2_PV3
2_INVR4
196
2_PV2
UPS
2_INVR3
194
192
2_PV1
UPS
2_INVR2
240
CAB:2_INVR4
UPS
2_INVR1
249
CAB:2_INVR3
1_PV4
UPS
190
1_PV3
1_INVR4
188
186
184
182
1_PV2
UPS
1_INVR3
248
CAB:2_INVR2
UPS
1_INVR2
247
CAB:2_INVR1
CAB_1INVR4
UPS
1_INVR1
1_PV1
CAB_1INVR3
CAB_1INVR2
CAB_1INVR1
UPS
246
253
7_TR1-BUS
252
ICR4_TR
ICR8_TR
178
251
ICR3_TR
58
33kV
PNL3(400)
50
51
91
177
250
ICR2_TR
497
33kV
PNL2(400)
50
51
IC0G0_PNL2
IC0G0_PNL1
510
50
51
506
CAB_IC3
ICR1-swbd1
33kV PNL1
(400)
50
51
ICR1_TR
icr3-33kv bd
icr2-33 kv bd
IC003_SWBD2
4_TR1-BUS
IC003_SWBD1
50
51
7 PV4
REV. DATE
EC O#
DWN APP
DES CR IPTIO N
DWG No.:
ENG. APP./DATE:
MFG. APP./DATE:
SCALE:
PART No.:
DWG SIZE:
REV.
GRID
APTRANSCO
LINE RELAYS
50
51
132bus_Grid
132 kV Bus
50
51
TR1_RELAYS_HV
TR_HT-132 BUS
TR1
CAB_TR1_LV
50
51
TR1_RELAYS_LV
33kV BUS-TRafo LV
33 kV Main SWBD (100)
50
51
FCP_IC1
50
51
508
50
51
511
50
51
512
363
132
362
86
CAB_IC1
50
51
OG000_SWBD1
50
51
OG000_SWBD2
icr3-33kv bd
icr2-33 kv bd
UPS
7_INVR2
7 PV3
UPS
7 INV4
10_PV4-INVR4
10_PV3-INVR3
10_PV2-INVR2
7_PV2
7 INV3
10_INVR4-TR
10_INVR3-TR
10_INVR2-TR
7_PV1
480
477
UPS
491
400
6_PV4
492
6_PV3
10_PV1-INVR1
6_PV2
UPS
7_INVR1
354
353
352
344
6_PV1
10_INVR1-TR
351
UPS
6_INVR4
318
317
5_PV4
399
358
UPS
6_INVR3
372
367
350
UPS
6_INVR2
33kV
PNL5(400)
50
51
IC0G0_PNL5
ICR7_TR
334
331
349
UPS
6_INVR1
357
345
315
314
UPS
356
328
323
5_INVR4
5_PV3
IC0G0_PNL4
355
321
5_PV2
322
5_PV1
UPS
5_INVR3
316
308
176
4_PV4
UPS
5_INVR2
33kV
PNL4(400)
50
51
ICR6_TR
298
295
313
UPS
5_INVR1
9_TR1-BUS
8_TR1-BUS
309
UPS
320
319
173
4_PV3
292
287
4_INVR4
175
4_PV2
180
UPS
4_INVR3
174
166
208
4_PV1
8PV21
UPS
4_INVR2
7_TR4
172
UPS
4_INVR1
8_INVR2
7_TR3
171
UPS
8_INVR1
8_PV11
167
UPS
206
3_PV4
7_TR2
7_TR1
CAB_8INVR2
3_PV3
3_INVR4
204
3_PV2
UPS
3_INVR3
202
200
198
3_PV1
UPS
3_INVR2
233
CAB_8INVR1
UPS
3_INVR1
232
CAB:3_INVR4
UPS
243
CAB:3_INVR3
CAB:3_INVR2
2_PV4
242
179
241
CAB:3_INVR1
2_PV3
2_INVR4
196
2_PV2
UPS
2_INVR3
194
192
2_PV1
UPS
2_INVR2
240
CAB:2_INVR4
UPS
2_INVR1
249
CAB:2_INVR3
1_PV4
UPS
190
1_PV3
1_INVR4
188
186
184
182
1_PV2
UPS
1_INVR3
248
CAB:2_INVR2
UPS
1_INVR2
247
CAB:2_INVR1
CAB_1INVR4
UPS
1_INVR1
1_PV1
CAB_1INVR3
CAB_1INVR2
CAB_1INVR1
UPS
246
253
7_TR1-BUS
252
33kV
PNL3(400)
IC0G0_PNL3
ICR5_TR
178
251
ICR4_TR
ICR8_TR
177
250
510
50
51
91
ICR3_TR
58
IC003_SWBD2
497
33kV
PNL2(400)
50
51
IC0G0_PNL2
IC0G0_PNL1
ICR2_TR
50
51
506
CAB_IC3
ICR1-swbd1
33kV PNL1
(400)
50
51
ICR1_TR
50
51
7 PV4
REV. DATE
EC O#
DWN APP
DES CR IPTIO N
DRAWN BY/DATE:
DWG No.:
ENG. APP./DATE:
MFG. APP./DATE:
SCALE:
PART No.:
DWG SIZE:
REV.
APTRANSCO
System Volt:
Fault Type :
Bus R RMS ( A ):
Bus Y RMS ( A ):
Bus B RMS ( A ):
Steady State flow of Current
BRANCH NAME
PRE
3 PHASE
FAULT
FAULT
VOLTAGE
GRID - 132KV BUS
132000
132000
33000
33000
33000
33000
33000
SWBD1(200) - ICR1_TR
33000
SWBD1(200) - ICR2_TR
33000
SWBD1(200) - ICR3_TR
33000
SWBD2(200) - ICR4_TR
33000
10
L-G
L-L-G
409
0
0
0
336
453
275
275
275
275
275
275
1098
1098
1098
439
439
439
73
73
73
439
439
439
146
146
146
146
146
146
146
146
146
146
146
146
146
146
146
0
251
251
0
251
251
0
1005
1005
0
402
402
0
67
67
0
402
402
0
134
134
0
134
134
0
134
134
0
134
134
0
134
134
409
0
0
409
0
0
1635
0
0
654
0
0
109
0
0
654
0
0
218
0
0
218
0
0
218
0
0
218
0
0
218
0
0
0
336
453
0
336
453
0
1344
1813
0
538
726
0
90
121
0
538
726
0
179
242
0
179
242
0
179
242
0
179
242
0
179
242
33000
SWBD2(200) - ICR6_TR
33000
ICR1_TR - 1_INV1
380
ICR1_TR - 1_INV2
380
ICR1_TR - 1_INV3
380
ICR1_TR - 1_INV4
380
ICR2_TR - 2_INV1
380
ICR2_TR - 2_INV2
380
ICR2_TR - 2_INV3
380
ICR2_TR - 2_INV4
380
ICR3_TR - 3_INV1
380
ICR3_TR - 3_INV2
380
ICR3_TR - 3_INV3
380
ICR3_TR - 3_INV4
380
ICR8_TR - 8_INV1
380
11
146
146
146
146
146
146
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
0
134
134
0
134
134
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
218
0
0
218
0
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
0
179
242
0
179
242
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
380
ICR4_TR - 4_INV1
380
ICR4_TR - 4_INV2
380
ICR4_TR - 4_INV3
380
ICR4_TR - 4_INV4
380
ICR5_TR - 5_INV1
380
ICR5_TR - 5_INV2
380
ICR5_TR - 5_INV3
380
ICR5_TR - 5_INV4
380
ICR6_TR - 6_INV1
380
ICR6_TR - 6_INV2
380
ICR6_TR - 6_INV3
380
ICR6_TR - 6_INV4
380
ICR7_TR - 7_INV1
380
12
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
380
ICR7_TR - 7_INV3
380
ICR7_TR - 7_INV4
380
1_INV1 - 1_PV1
1_INV2 - 1_PV2
1_INV3 - 1_PV3
1_INV4 - 1_PV4
2_INV1 - 2_PV1
2_INV2 - 2_PV2
2_INV3 - 2_PV3
2_INV4 - 2_PV4
3_INV1 - 3_PV1
3_INV2 - 3_PV2
3_INV3 - 3_PV3
3_INV4 - 3_PV4
4_INV1 - 4_PV1
4_INV2 - 4_PV2
4_INV3 - 4_PV3
4_INV4 - 4_PV4
5_INV1 - 5_PV1
5_INV2 - 5_PV2
5_INV3 - 5_PV3
5_INV4 - 5_PV4
6_INV1 - 6_PV1
6_INV2 - 6_PV2
6_INV3 - 6_PV3
6_INV4 - 6_PV4
7_INV1 - 7_PV1
7_INV2 - 7_PV2
7_INV3 - 7_PV3
7_INV4 - 7_PV4
8_INV1 - 8_PV1
8_INV2 - 8_PV2
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
13
3179
3179
3179
3179
3179
3179
3179
3179
3179
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1679
1679
3358
1679
1679
3358
1679
1679
3358
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
2732
2732
0
2732
2732
0
2732
2732
0
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
3030
2246
3239
3030
2246
3239
3030
2246
3239
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
3 Phase Fault
Bus Name
APTRANSCO
132 kV Bus
33 kV Main SWBD (100)
33kV SWBD1 (200)
33kV SWBD2 (200)
1_INVR1
1_INVR2
1_INVR3
1_INVR4
2_INVR1
2_INVR2
2_INVR3
2_INVR4
3_INVR1
3_INVR2
3_INVR3
3_INVR4
4_INVR1
4_INVR2
4_INVR3
4_INVR4
5_INVR1
5_INVR2
5_INVR3
5_INVR4
6_INVR1
6_INVR2
6_INVR3
6_INVR4
7_INVR1
7_INVR2
7_INVR3
7_INVR4
8_INVR1
8_INVR2
14
LL Fault
Bus Name
APTRANSCO
132 kV Bus
33 kV Main SWBD (100)
33kV SWBD1 (200)
33kV SWBD2 (200)
1_INVR1
1_INVR2
1_INVR3
1_INVR4
2_INVR1
2_INVR2
2_INVR3
2_INVR4
3_INVR1
3_INVR2
3_INVR3
3_INVR4
4_INVR1
4_INVR2
4_INVR3
4_INVR4
5_INVR1
5_INVR2
5_INVR3
5_INVR4
6_INVR1
6_INVR2
6_INVR3
6_INVR4
7_INVR1
7_INVR2
7_INVR3
7_INVR4
8_INVR1
8_INVR2
15
LGFault
Bus Name
APTRANSCO
132 kV Bus
33 kV Main SWBD (100)
33kV SWBD1 (200)
33kV SWBD2 (200)
1_INVR1
1_INVR2
1_INVR3
1_INVR4
2_INVR1
2_INVR2
2_INVR3
2_INVR4
3_INVR1
3_INVR2
3_INVR3
3_INVR4
4_INVR1
4_INVR2
4_INVR3
4_INVR4
5_INVR1
5_INVR2
5_INVR3
5_INVR4
6_INVR1
6_INVR2
6_INVR3
6_INVR4
7_INVR1
7_INVR2
7_INVR3
7_INVR4
8_INVR1
8_INVR2
16
LLGFault
Bus Name
APTRANSCO
132 kV Bus
33 kV Main SWBD (100)
33kV SWBD1 (200)
33kV SWBD2 (200)
1_INVR1
1_INVR2
1_INVR3
1_INVR4
2_INVR1
2_INVR2
2_INVR3
2_INVR4
3_INVR1
3_INVR2
3_INVR3
3_INVR4
4_INVR1
4_INVR2
4_INVR3
4_INVR4
5_INVR1
5_INVR2
5_INVR3
5_INVR4
6_INVR1
6_INVR2
6_INVR3
6_INVR4
7_INVR1
7_INVR2
7_INVR3
7_INVR4
8_INVR1
8_INVR2
17
CTHV:200/1
30 MVA
CT LV:600/1 A
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 33 kV Bus (Grid operation)
Fault current at 132kV Bus as per report (Grid operation)
Transformer Full Load HV side Primary Current at 0% tapping
33kV
PT
Vp
Vs
CTR1
CTR2
Z
Ipfl
Isfl
Isfl
18
30000
kVA
132
kV
33
kV
200/1
200
600/1
600
12.50%
9274
A
35502
A
30000X 1000 )/ (1.732 Amps
X132x1000x1)
131.22
Amps
0.95
1.05 x HV Currrent/ Drop off ratio
=1.05x 131.21/0.95
145.03
0.73
0.7
0.7
Normal Inverse
30000X 1000 )/ (1.732 Amps
X33x1000x1)
524.88
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 437.40/0.95
607.75
1.01
1
1
Normal Inverse
33kV
0.380kV
CTHV:100/1
4.4MVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer HV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 0.380 kV Bus (Grid operation)
Fault current at 33 kV Bus as per report (Grid operation)
Transformer Full Load HV side Primary Current at 0% tapping
PT
Vp
Vs
CTR1
CTR2
Z
Ipfl
Isfl
19
4400
kVA
33
kV
0.38
kV
80/1
80
600/1
600
3.20%
9274
A
35502
A
4400X 1000 )/ (1.732 Amps
X33x1000x1)
76.98
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 76.98/0.95
89.14
1.10
1.1
1.1
Normal Inverse
20
Setting
Enabled
Function
Value (Range)
Diff.Prot
Differential Current Monitoring
Pick up value of differential current
T I-diff> time delay
Pick up value of High set trip
T I-diff>> time delay
Slope 1 of tripping charecterstic
Base point for slope1 of charecterstic
Slope 2 of tripping charecterstic
Base point for slope2 of charecterstic
Pick up for add on stablisation
Duration for add on stablisation
I-Diff> Mon
I-diff>
T I-diff>
I-diff>>
T I-diff>>
Slope 1
Base point 1
Slope 2
Base point 2
I Add on stab
T Add on stab
ON/OFF
ON/OFF
0.05..2 I/InO
0.00..60.00 s
0.5..35 I/InO
0.00..60.00 s
0.1..0.5
0.00..2 I/InO
0.25..0.95
0.00..10 I/InO
2..15 I/InO
2..250 Cycles
21
Set Value
ON
ON
0.2
0
8
0
0.2
0
0.7
4.5
4
15
sec
sec
Distance Protection 21
Parameter
Unit
kV
V
A
A
Parameter
Unom PRIMARY in kV
Unom Secondary in Volts
CT Primary in Amps
CT Secondary in Amps
SystemStarpoint
Uph / Udelta
Rated Frequency
Phase Seq
ZL1 mag
ZL1 ang
ZL0 mag
ZL0 ang
KZ0 mag
KZ0 ang
Z1mag
Z1ang
Z2mag
Z2ang
Z3mag
Z3ang
Z4mag
Z4ang
R1 Ph max
R1 Ph min
R1ph
R2ph
TZ1
TZ2
R1G
R2G
Zone 1
Zone 2
Zone 3
Zone 4
Range
1.0 .. 1200.0 kV
80..125
10~5000
1A/5A
Solid Earthed
Peterson-Coil Isolated
0.10 .. 9.99
50/60 Hz
L1 L2 L3
L1 L3 L2
km/Miles
1.0~1200
10~5000
10~89 deg
Not reversed
Reversed
kV
A
deg
Distance Unit
Full scale volt
Full scale Current
Line Angle
P,Q sign
ohms/km
ohms/km
mfd / km
km
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
Ohms
sec
sec
sec
sec
Ohms
Ohms
Z1
Z0
Z1
Z0
Z1
Z0
Z1
Z0
R
x1
0.0050~9.5
c'
0.0~100
Line length
0.1~1000
Line Positive Sequence impedance (mag)
Line Positive Sequence impedance (Phase angle )
Line Zero Sequence impedance (mag)
Line Zero Sequence impedance (Phase angle )
Default residual compensation factor (mag)
Default residual compensation factor (Phase angle)
Zone 1 reach impedance setting (mag)
Zone 1 reach impedance setting (Phase angle)
Zone 2 reach impedance setting (mag)
Zone 2 reach impedance setting (Phase angle)
Zone 3 reach impedance setting (mag)
Zone 3 reach impedance setting (Phase angle)
Zone 4 reach impedance setting (mag)
Zone 4 reach impedance setting (Phase angle)
Phase fault resistive reach value
Phase fault resistive reach value
Time delay Zone 1
Time delay Zone 2
Time delay Zone 3
Time delay Zone 4
Ground fault resistive reach value zone 1
Ground fault resistive reach value zone 2
0.605+J0.878
0.900+j2.592
0.907+J1.318
1.35+j3.88
1.512+J2.196
2.25+j6.48
0.151+J0.220
0.225+j0.648
22
Settings
132
110
300
1
Solid
Earthed
1.73
50 Hz
L1 L2 L3
km
132
300
55.45
not
reversed
0.168
0.44
0.0081
18
5.33
55.45
13.719
70.8
0.543
24.77
1.06
55.45
1.599
55.45
2.66
55.49
0.266
55.45
0.7
2.1
0
0.4
0.8
0.25
4
5.3
Setting
Enabled
Units
Stage 1
Delay stage 1
Stage 2
Delay stage 1
Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)
Setting
1.5
0.15
0.45
NA
0.05
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
450
Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)
Setting
1
0.3
0.08
NA
0.07
Standard Inverse
unit
x In
s
x In
s
Prim Value
200
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)
Setting
1.5
0.15
0.45
NA
0.05
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
450
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)
Setting
1
0.3
0.08
NA
0.07
Standard Inverse
unit
x In
s
x In
s
Prim Value
200
Range
5-200 V
0-599
5-200 V
0-599
Setting
unit
Volts
sec
Volts
sec
Prim Value
145.2
23
121
2
126.5
0.5
135
16
135
16
151.8
Mulkanoor SS
CTR =
300 /
PTR =
132000 /
Protected Line parameters:
Per kilometer
Line
Z1 =
Zero seq
Line distance
APTRANSCO SS
18 km
300
1200
1
110
0.168 + j
Z0 =
Mulkanoor SS to
APTRANSCO SS
0.25 + j
18 km
0.244
= 0.29624
55.45
per km
0.72
= 0.76217
70.85
per km
4.392
= 5.33238
55.45
12.96
70.85
MULKANOOR SS to APTRANSCO SS
Line parameters
Z1
Z0
18 x(0.168+j0.244)
3.024 + j
18 x(0.25+j0.72)
4.5 + j
Zone 1 reach =
Zone 2 reach =
Zone 3 reach =
Zone 4 reach =
Ratio of Secondary to Primary Impedance
Zone 1 Phase Reach Settings
Required Zone 1 reach =
13.719
80 % of protected line
120 % of protected line
200 % of protected line
20 % of protected line
=CTR/PTR =
0.250
55.45
70.85
55.45
70.85
55.45
70.85
24
131.22
132
580.7992
145.1998
25
= 0.26662
25
1 A CT
1
55.45
70.85
26
Setting Details for 132/33 kV ,25/30 MVA Power Transformer -Control & Protection Panel
Transformer Feeder protection for Power Transformer
Relay settings for relays located in the Protection Panel +1TR1A
Differential Protection Relay-87T/64R
Relay Located in Protection Panel +1TR1A MiCOM P643 Multi Function Relay
SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 87
Function 64R
Function 99-LV
Other functions are disabled
Power System Data 1
Setting
Enabled
Units
Range
Setting
0.10 Iref - 2.50 Iref
0.10 Iref
2.5 Iref-30.0 Iref
4.0 Iref
Blocked/ 2.5 Iref - 30.0 Iref
0.10 - 1.50
0.30
0.10 - 1.50
0.8
1.5 Iref - 10.0 Iref
4.0 Iref
0.00 s -100.00 s
0.00 s
Enabled
Enabled
Range
1.0~1.2
0~60 sec
1.0~1.4
0~1000 sec
Adaption Factors
0.5~2.0
27
unit
x Iref
x Iref
4 x Iref
x Iref
sec
1 x Iref
4 x Iref
4 I ref
10 %
20 %
0.1 x In
0
Setting
ON
Enabled
IDMT
2.53V/Hz
Prim Value
unit
1.1 V/Hz
1 sec
V/Hz
0.1
0 sec
200 sec
45
1
20
Prim Value
Setting
Enabled
IN 1 > 1 TMS
Standby Earth Fault Protection 51N LV
IN 1 > 1 Current Set
IN 1 > 1 Function
IN 1 > 1 TMS
Over Flux Protection HV
Setting name
State of the Overflux Protection
Pick up Value Warning Stage U/f
Time delay for Warning Stage U/f
V/Hz >1 Status
V/Hz >1 Trip Func
V/Hz >1 Trip Set
V/Hz >1 Trip TMS
V/Hz >1 tReset
Tpre-Trip Alarm
Units
IEC Curve
IEC Curve
Units
Range
Setting
Blocked/ 0.08 In - 4.00 In
Definite Time IEC
Definite Time
Standard Inverse IEC
Very Inverse IEC Extr.
Inverse IEC Long Time
Inv. IEEE Moderately Inv.
IEEE Very Inverse IEEE
Extr. Inverse ANSI
Normally Inv. ANSI Short
Time Inv. ANSI Long
Time Inv. RI-Type
Inverse RXIDG-Type
Inverse 0.025 - 1.2
unit
0.1 x In
0.1 x In
Range
1.0~1.2
0~60 sec
1.0~1.4
0~1000 sec
Adaption Factors
0.5~2.0
28
Setting
ON
Enabled
IDMT
2.53V/Hz
Prim Value
20
1 sec
75
1 sec
unit
1.1 V/Hz
1 sec
V/Hz
0.1
0 sec
200 sec
45
1
Prim Value
Relay Located in Protection Panel +1TR1A MiCOM C264P Multi Function Relay
SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 50
Function 51
Function 50N
Function 51N
Function 50BF
Other functions are disabled
Power System Data 1
Setting
Enabled
Setting name
CB Fail 1 Status
CB Fail 1 Timer
I< Current Set
CB Fail 2 Status
CB Fail 2 Timer
I< Current Set
Units
Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
1.5
0.3
0.7
NA
0.06
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
300
Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
1
0.3
0.1
NA
0.13
Standard Inverse
unit
x In
s
x In
s
Prim Value
200
Range
Setting
unit
Prim Value
Enabled/Disabled
0-10
Enabled/Disabled
0-10
29
Enabled
Enabled
0.05 sec
5%
0.2 sec
10 %
140
20
Relay Located in Protection Panel +1TR1B MiCOM C264P Multi Function Relay
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
600A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
2.1
0.45
1
NA
0.07
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
1260
Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
1
0.45
0.1
NA
0.21
Standard Inverse
unit
x In
s
x In
s
Prim Value
600
CT rated primary
CT rated secondary
Non Directional Phase over current Protection: 51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve
30
600
60
31
Setting Range
Enabled/Disabled
Setting
Enabled
Range
Setting
10..50000 A
1A/5A
250A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
450
Setting
0.9
0.6
0.09
NA
0.3
Standard Inverse
unit
x In
s
x In
s
Prim Value
225
Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
450
32
225
22.5
225
Setting Range
Enabled/Disabled
Setting
Enabled
Range
Setting
10..50000 A
1A/5A
250A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse
unit
x In
s
x In
s
s
Setting
unit
50N-2 Pickup
50N-2 Delay
51N-1Pickup
51N-1Delay
Time dial
IEC Curve
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
0.9
0.6
0.09
NA
0.3
Standard Inverse
x In
s
x In
s
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse
unit
x In
s
x In
s
s
Ie>> >>
Te>>>>
Ie>
TIe>
Ie> TMS
33
Prim Value
450
225
Prim Value
225
22.5
Prim Value
450
225
Setting Range
Enabled/Disabled
Setting
Enabled
Range
Setting
10..50000 A
1A/5A
100A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
1.6
0.6
0.8
NA
0.09
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
160
Setting
0.8
0.6
0.08
NA
0.3
Standard Inverse
unit
x In
s
x In
s
Prim Value
80
Setting
1.6
0.6
0.8
NA
0.09
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
160
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
34
80
80
Setting Range
Enabled/Disabled
Setting
Enabled
Range
Setting
10..50000 A
1A/5A
50A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
1.6
0.6
0.8
NA
0.09
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
80
Setting
0.8
0.6
0.08
NA
0.3
Standard Inverse
unit
x In
s
x In
s
Prim Value
40
Setting
1.6
0.6
0.8
NA
0.09
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
80
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
35
40
40
Setting Range
Enabled/Disabled
Setting
Enabled
Range
Setting
10..50000 A
1A/5A
250A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
450
Setting
0.9
0.6
0.09
NA
0.3
Standard Inverse
unit
x In
s
x In
s
Prim Value
225
Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
450
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
36
225
22.5
225
Setting Range
Enabled/Disabled
Setting
Enabled
Range
Setting
10..50000 A
1A/5A
30A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Setting
0.8
0.6
0.04
NA
0.07
Standard Inverse
unit
x In
s
x In
s
s
Prim Value
24
Setting
0.1
0.1
0.01
0.07
DT
Standard Inverse
unit
x In
s
x In
s
Prim Value
37
1.2
0.3
38
Panel 1-IC003
Ie> TMS
Setting Range
Enabled/Disabled
Setting
Enabled
Range
Setting
10..50000 A
1A/5A
80A
1A
Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
Setting
2
0.9
1
NA
0.12
IEC NI
unit
x In
s
x In
s
s
Prim Value
160
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100
Setting
1
0.9
0.1
NA
IEC NI
unit
x In
s
x In
s
Prim Value
80
39
0.44
80
Panel 2-OG000
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
250A
1A
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
0.01,0.025..1.6,1.7,..100
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
Setting
1.8
0.75
1
NA
0.08
IEC NI
unit
x In
s
x In
s
s
Prim Value
450
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100
Setting
1
0.75
0.1
NA
IEC NI
unit
x In
s
x In
s
Prim Value
250
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve
Ie> TMS
40
0.36
250
25
Panel 1-IC003
Ie> TMS
Setting Range
Enabled/Disabled
Setting
Enabled
Range
Setting
10..50000 A
1A/5A
80A
1A
Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
Setting
2
0.9
1
NA
0.12
IEC NI
unit
x In
s
x In
s
s
Prim Value
160
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100
Setting
1
0.9
0.1
NA
IEC NI
unit
x In
s
x In
s
Prim Value
80
41
0.44
80
Panel 2-OG000
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
250A
1A
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
0.01,0.025..1.6,1.7,..100
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
Setting
1.8
0.75
1
NA
0.08
IEC NI
unit
x In
s
x In
s
s
Prim Value
450
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100
Setting
1
0.75
0.1
NA
IEC NI
unit
x In
s
x In
s
Prim Value
250
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial
Ie> TMS
42
0.36
250
25
Panel 1-IC0G0
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
CT rated primary
CT rated secondary
10..50000 A
1A/5A
80A
1A
Units
I> >
T I>>
I>
tI>
I> TMS
Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100
Setting
2
0.9
1
NA
0.12
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
IEC NI
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
0.01,0.025..1.6,1.7,..100
Setting
1
0.9
0.1
NA
IEC NI
0.44
IEC Curve
43
Panel 1-IC0G0
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
CT rated primary
CT rated secondary
10..50000 A
1A/5A
80A
1A
Units
I> >
T I>>
I>
tI>
I> TMS
Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100
Setting
2
0.9
1
NA
0.12
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
IEC NI
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100
Setting
1
0.9
0.1
NA
IEC NI
IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial
Ie> TMS
44
0.44
Panel 1-IC0G0
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
CT rated primary
CT rated secondary
10..50000 A
1A/5A
80A
1A
Units
I> >
T I>>
I>
tI>
I> TMS
Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100
Setting
2
0.9
1
NA
0.12
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
IEC NI
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100
Setting
1
0.9
0.1
NA
IEC NI
IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial
Ie> TMS
45
0.44
Panel 1-IC0G0
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
CT rated primary
CT rated secondary
10..50000 A
1A/5A
80A
1A
Units
I> >
T I>>
I>
tI>
I> TMS
Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100
Setting
2
0.9
1
NA
0.12
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
IEC NI
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100
Setting
1
0.9
0.1
NA
IEC NI
IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial
Ie> TMS
46
0.44
Panel 1-IC0G0
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
CT rated primary
CT rated secondary
10..50000 A
1A/5A
80A
1A
Units
I> >
T I>>
I>
tI>
I> TMS
Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100
Setting
2
0.9
1
NA
0.12
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
IEC NI
Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100
Setting
1
0.9
0.1
NA
IEC NI
IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial
Ie> TMS
47
0.44
48
10000
1000
100
ITR1
FEED_CP_IC1
33kV_OG
TR1_RELAYS_HV
Time in Seconds
10
TR1_RELAYS_LV
TR1
A 30000.0 KVA
Transformer
LINE RELAYS
.01
.1
.5
10
100
Current in Amperes X 10
Time-Current Characteristic Curves
1000
10000
12-18-2016
19:39:55
mulk_09112016
49
10000
1000
100
IC003_SWBD1
FCP_IC1
TR1_RELAYS_LV
TR1_RELAYS_HV
10
LINE RELAYS
.01
.1
Time in Seconds
OG000_SWBD1
.5
10
100
Current in Amperes X 10
Time-Current Characteristic Curves
1000
10000
12-18-2016
19:52:39
mulk_09112016
50