Protection Coordination Report: Renew Saur Urja PVT LTD

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 50

RENEW SAUR URJA PVT LTD

GURGAON,HARYANA

PROTECTION COORDINATION REPORT

00

Initial Submission

18/12/2016

Revision

Revision Particulars

Date

RC

CBR

CBR
Approve
Reviewed Checked
d

CLIENT

RENEW SAUR URJA PVT LTD

PROJECT

30MWp SPV PROJECT AT MALKANOOR,TELANGANA

CONTRACTOR

LARSEN & TOUBRO,NAVI,MUMBAI

CONSULTANT
DOCUMENT ID
No. of Pages

REPORT NO 08/2016-17
(INCLUDING THIS FRONT PAGE)

REVISION:

00

Contents
Sl.No
1
2
3
4
5
6
7
8
9
10
11

Descriptiion
Executive Summary
Reference Documents
Device Details
Single line diagram
Short Circuit Current Details
Transformer Relay Setting Calculations
Setting Details for Line Control Panel
Setting Details for Transformer Control Panel
Setting Details for Feeder Control Panel
Setting Details for 33 kV Switch Board
Time Current Characteristic Curves

Page No
3
4
5
6
8
18
20
26
31
38
48

Introduction
Project:
Owner:
Electrical Contractor:
ElectricalDistribution System
Power System Data
Max Source Fault level (assumed)
Tools used:
Protection Coordination

Input Data
Conclusion

Executive Summary
30MWp SPV Project at Malkanoor,Telangana
Renew Saur Urja Pvt Ltd
L&T, Navi,Mumbai
132kV,33 kV,0.380 kV Power Distribution System
25kA for 1 secs at 33 kV
Paladin Design Base 5- an Electrical Design software
Selectivity of relays were worked out based on the rating of
transformers,cable size and flow of short circuit currents.
Time current characterstic curves are generated for every path and
verified .
The SLD,Control and Relay panel drawings,Transformer Data sheets
Settings for each device,short circuit currents at every busbars,detailed
calculations for the settings are given in the following pages.

Reference Documents / Drawings


Sl.No
1
2
3
4
5
6
7
8
9
10
11

Details
132kV Switchyard SLD
33kV ICOG Panel
33kV SwitchBoard
33kV Feeder -1&2 Control & Protection Panel
132/33kV,25/30MVA Power Transformer Control & Protection Panel
ACSLD
30 MVA,Transformer Data sheets
132kV Switchyard Single line Diagram
132kV Line Control & Protection Panel
Technical Specification of Grid Connected PhotoVoltaic Inverter
Rated Specification of the Inverter (PVL-L1000E)

File reference
SLD_Mulkanoor.pdf
Drawing-400-29.08.16.pdf
Drawing-200-29.08.16.pdf
33KV TWIN FEEDER 1 & 2_REV-B_17.11.2016.pdf
132_33KV,25_30MVA TRANSFORMER CONTROL & PROTECTION PANEL_REVACSLD FOR FOR 30MW MULKANOOR PROJECT_TELANGANA 31 08 2016-Model.pdf
GTP-T-05516-4.pdf
RP-5212-DWG-ELE-AC-002-R2-132kV Switchyard SLD.DWG
132KV LINE CONTROL & PROTECTION PANEL_REV-B_17.11.2016.pdf
PVL-L1000E_INVERTER-TECHNICAL.pdf
TMEIC INVERTER-1000KW-DATA SHEET.pdf

Device Details
Transformers
Details of Equipment

Main Power Transformer


Transformer
Inverter Transformers
5 Winding Transformer
3 Winding Transformer

kVA rating

High
Low voltage Percentage
Voltage
side
Impedance
side

30000

132000

33000

4400
2200

33000 V 380
33000 V 380

Low winding

High winding

Grounding Mode

Vector
Group

Type of
Cooling

12.49

Star

Star

Direct

YNyn0

ONAN/ONAF

3.20
3.20

Delta
Delta

Star
Star

Direct
Direct

YND
YND

AN
AN

Supply Variation on Primary side

-25% to +5% in 24 steps

SINGLE LINE DIAGRAM

GRID

APTRANSCO

50
51

LINE RELAYS

132bus_Grid
132 kV Bus
50
51

TR1_RELAYS_HV

TR_HT-132 BUS

TR1

CAB_TR1_LV
50
51

TR1_RELAYS_LV

33kV BUS-TRafo LV
33 kV Main SWBD (100)
FCP_IC1

508

50
51

511

50
51

512

50
51

50
51

363
132
362

86

CAB_IC1
OG000_SWBD1

OG000_SWBD2

50
51

50
51

icr8-33kv main board


33kV SWBD1 (200)

UPS

7_INVR2

7 PV3

UPS
7 INV4
10_PV4-INVR4

10_PV3-INVR3

10_PV2-INVR2
7_PV2

7 INV3

10_INVR4-TR

10_INVR3-TR

10_INVR2-TR

7_PV1

491

400

6_PV4

492

6_PV3

10_PV1-INVR1

6_PV2

UPS

7_INVR1
354

353

352

344

6_PV1

UPS

480

477

10_INVR1-TR

351

UPS

6_INVR4

318

317

5_PV4

399

358

UPS

6_INVR3

372

367

350

UPS

6_INVR2

33kV
PNL5(400)

50
51

IC0G0_PNL5

ICR7_TR

334

331

349

UPS
6_INVR1

357

345

315

314

UPS

356
328

323

5_INVR4

5_PV3

IC0G0_PNL4

355

321

5_PV2

322

5_PV1

UPS

5_INVR3

316

308

176
4_PV4

UPS

5_INVR2

33kV
PNL4(400)

50
51

ICR6_TR

298

295

313

UPS
5_INVR1

9_TR1-BUS

8_TR1-BUS

309

UPS

320

319

173

4_PV3

292

287

4_INVR4

175

4_PV2

180

UPS

4_INVR3

174

166

208

4_PV1

8PV21

UPS

4_INVR2

7_TR4

172

UPS
4_INVR1

8_INVR2

7_TR3

171

UPS

8_INVR1

8_PV11

167

UPS

206

3_PV4

7_TR2

7_TR1

CAB_8INVR2

3_PV3

3_INVR4
204

3_PV2

UPS

3_INVR3
202

200

198
3_PV1

UPS

3_INVR2

233

CAB_8INVR1

UPS

3_INVR1

232

CAB:3_INVR4

UPS

243

CAB:3_INVR3

CAB:3_INVR2

2_PV4

242

IC0G0_PNL3

ICR5_TR
179

241

CAB:3_INVR1

2_PV3

2_INVR4
196

2_PV2

UPS

2_INVR3
194

192

2_PV1

UPS

2_INVR2

240

CAB:2_INVR4

UPS

2_INVR1

249

CAB:2_INVR3

1_PV4

UPS

190

1_PV3

1_INVR4
188

186

184

182

1_PV2

UPS

1_INVR3

248

CAB:2_INVR2

UPS

1_INVR2

247

CAB:2_INVR1

CAB_1INVR4

UPS

1_INVR1

1_PV1

CAB_1INVR3

CAB_1INVR2

CAB_1INVR1

UPS

246

253

7_TR1-BUS

252

ICR4_TR

ICR8_TR

178

251

ICR3_TR

58

33kV
PNL3(400)

50
51

91

177

250

ICR2_TR

497

33kV
PNL2(400)

50
51

IC0G0_PNL2

IC0G0_PNL1

510

50
51

506

CAB_IC3

ICR1-swbd1

33kV PNL1
(400)

50
51

ICR1_TR

33kV SWBD2 (200)

icr3-33kv bd

icr2-33 kv bd

IC003_SWBD2

4_TR1-BUS

IC003_SWBD1
50
51

7 PV4

REV. DATE

EC O#

DWN APP

DES CR IPTIO N

THIS DRAWING IS PROPRIETARY INFORMA TION

Your Company Name


Address
Address
Phone and web site

Electrical One-Line Diagram for


System Study
DRAWN BY/DATE:

DWG No.:

ENG. APP./DATE:
MFG. APP./DATE:
SCALE:

PART No.:
DWG SIZE:

REV.

SHORT CIRCUIT CURRENT DETAILS

GRID

APTRANSCO

LINE RELAYS

50
51

132bus_Grid
132 kV Bus
50
51

TR1_RELAYS_HV

TR_HT-132 BUS

TR1

CAB_TR1_LV
50
51

TR1_RELAYS_LV

33kV BUS-TRafo LV
33 kV Main SWBD (100)

50
51

FCP_IC1

50
51

508

50
51

511

50
51

512

363
132
362

86

CAB_IC1
50
51

OG000_SWBD1

50
51

OG000_SWBD2

icr8-33kv main board


33kV SWBD1 (200)
IC003_SWBD1

icr3-33kv bd

icr2-33 kv bd

UPS

7_INVR2

7 PV3

UPS
7 INV4
10_PV4-INVR4

10_PV3-INVR3

10_PV2-INVR2
7_PV2

7 INV3

10_INVR4-TR

10_INVR3-TR

10_INVR2-TR

7_PV1

480

477

UPS

491

400

6_PV4

492

6_PV3

10_PV1-INVR1

6_PV2

UPS

7_INVR1
354

353

352

344

6_PV1

10_INVR1-TR

351

UPS

6_INVR4

318

317

5_PV4

399

358

UPS

6_INVR3

372

367

350

UPS

6_INVR2

33kV
PNL5(400)

50
51

IC0G0_PNL5

ICR7_TR

334

331

349

UPS
6_INVR1

357

345

315

314

UPS

356
328

323

5_INVR4

5_PV3

IC0G0_PNL4

355

321

5_PV2

322

5_PV1

UPS

5_INVR3

316

308

176
4_PV4

UPS

5_INVR2

33kV
PNL4(400)

50
51

ICR6_TR

298

295

313

UPS
5_INVR1

9_TR1-BUS

8_TR1-BUS

309

UPS

320

319

173

4_PV3

292

287

4_INVR4

175

4_PV2

180

UPS

4_INVR3

174

166

208

4_PV1

8PV21

UPS

4_INVR2

7_TR4

172

UPS
4_INVR1

8_INVR2

7_TR3

171

UPS

8_INVR1

8_PV11

167

UPS

206

3_PV4

7_TR2

7_TR1

CAB_8INVR2

3_PV3

3_INVR4
204

3_PV2

UPS

3_INVR3
202

200

198
3_PV1

UPS

3_INVR2

233

CAB_8INVR1

UPS

3_INVR1

232

CAB:3_INVR4

UPS

243

CAB:3_INVR3

CAB:3_INVR2

2_PV4

242

179

241

CAB:3_INVR1

2_PV3

2_INVR4
196

2_PV2

UPS

2_INVR3
194

192

2_PV1

UPS

2_INVR2

240

CAB:2_INVR4

UPS

2_INVR1

249

CAB:2_INVR3

1_PV4

UPS

190

1_PV3

1_INVR4
188

186

184

182

1_PV2

UPS

1_INVR3

248

CAB:2_INVR2

UPS

1_INVR2

247

CAB:2_INVR1

CAB_1INVR4

UPS

1_INVR1

1_PV1

CAB_1INVR3

CAB_1INVR2

CAB_1INVR1

UPS

246

253

7_TR1-BUS

252

33kV
PNL3(400)

IC0G0_PNL3

ICR5_TR
178

251

ICR4_TR

ICR8_TR

177

250

510

50
51

91

ICR3_TR

58

IC003_SWBD2
497

33kV
PNL2(400)

50
51

IC0G0_PNL2

IC0G0_PNL1

ICR2_TR

50
51

506

CAB_IC3

ICR1-swbd1

33kV PNL1
(400)

50
51

ICR1_TR

33kV SWBD2 (200)


4_TR1-BUS

50
51

7 PV4

REV. DATE

EC O#

DWN APP

DES CR IPTIO N

THIS DRAWING IS PROPRIETARY INFORMA TION

Your Company Name


Address
Address
Phone and web site

Flow of Short Circuit Current

DRAWN BY/DATE:

DWG No.:

ENG. APP./DATE:
MFG. APP./DATE:
SCALE:

PART No.:
DWG SIZE:

REV.

Short Circuit Report


Bus Name :

APTRANSCO

Branch Flow ( A ) IEC60909 Method


APTRANSCO
Fault At Bus:

System Volt:
Fault Type :

132000 Base Volt:


132000 V
Pre Fault
3-phase
L-L
voltage
132000
275
0
132000
275
251
132000
275
251

Bus R RMS ( A ):
Bus Y RMS ( A ):
Bus B RMS ( A ):
Steady State flow of Current
BRANCH NAME
PRE
3 PHASE
FAULT
FAULT
VOLTAGE
GRID - 132KV BUS

132000

132kV BUS - TR_HV SIDE

132000

TR_LV SIDE - MAIN PNL

33000

MAIN PNL - SWBD1(200)

33000

MAIN PNL - ICR8_TR

33000

MAIN PNL - SWBD2(200)

33000

MAIN PNL - ICR7_TR

33000

SWBD1(200) - ICR1_TR

33000

SWBD1(200) - ICR2_TR

33000

SWBD1(200) - ICR3_TR

33000

SWBD2(200) - ICR4_TR

33000

10

L-G

L-L-G

409
0
0

0
336
453

LL FAULT LG FAULT LLG


FAULT

275
275
275
275
275
275
1098
1098
1098
439
439
439
73
73
73
439
439
439
146
146
146
146
146
146
146
146
146
146
146
146
146
146
146

0
251
251
0
251
251
0
1005
1005
0
402
402
0
67
67
0
402
402
0
134
134
0
134
134
0
134
134
0
134
134
0
134
134

409
0
0
409
0
0
1635
0
0
654
0
0
109
0
0
654
0
0
218
0
0
218
0
0
218
0
0
218
0
0
218
0
0

0
336
453
0
336
453
0
1344
1813
0
538
726
0
90
121
0
538
726
0
179
242
0
179
242
0
179
242
0
179
242
0
179
242

Steady State flow of Current


BRANCH NAME
PRE
3 PHASE
FAULT
FAULT
VOLTAGE
SWBD2(200) - ICR5_TR

33000

SWBD2(200) - ICR6_TR

33000

ICR1_TR - 1_INV1

380

ICR1_TR - 1_INV2

380

ICR1_TR - 1_INV3

380

ICR1_TR - 1_INV4

380

ICR2_TR - 2_INV1

380

ICR2_TR - 2_INV2

380

ICR2_TR - 2_INV3

380

ICR2_TR - 2_INV4

380

ICR3_TR - 3_INV1

380

ICR3_TR - 3_INV2

380

ICR3_TR - 3_INV3

380

ICR3_TR - 3_INV4

380

ICR8_TR - 8_INV1

380

11

LL FAULT LG FAULT LLG


FAULT

146
146
146
146
146
146
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179

0
134
134
0
134
134
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358

218
0
0
218
0
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0

0
179
242
0
179
242
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239

Steady State flow of Current


BRANCH NAME
PRE
3 PHASE
FAULT
FAULT
VOLTAGE
ICR8_TR - 8_INV2

380

ICR4_TR - 4_INV1

380

ICR4_TR - 4_INV2

380

ICR4_TR - 4_INV3

380

ICR4_TR - 4_INV4

380

ICR5_TR - 5_INV1

380

ICR5_TR - 5_INV2

380

ICR5_TR - 5_INV3

380

ICR5_TR - 5_INV4

380

ICR6_TR - 6_INV1

380

ICR6_TR - 6_INV2

380

ICR6_TR - 6_INV3

380

ICR6_TR - 6_INV4

380

ICR7_TR - 7_INV1

380

12

LL FAULT LG FAULT LLG


FAULT

3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179
3179

1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358
1679
1679
3358

2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0
2732
2732
0

3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239
3030
2246
3239

Steady State flow of Current


BRANCH NAME
PRE
3 PHASE
FAULT
FAULT
VOLTAGE
ICR7_TR - 7_INV2

380

ICR7_TR - 7_INV3

380

ICR7_TR - 7_INV4

380

1_INV1 - 1_PV1
1_INV2 - 1_PV2
1_INV3 - 1_PV3
1_INV4 - 1_PV4
2_INV1 - 2_PV1
2_INV2 - 2_PV2
2_INV3 - 2_PV3
2_INV4 - 2_PV4
3_INV1 - 3_PV1
3_INV2 - 3_PV2
3_INV3 - 3_PV3
3_INV4 - 3_PV4
4_INV1 - 4_PV1
4_INV2 - 4_PV2
4_INV3 - 4_PV3
4_INV4 - 4_PV4
5_INV1 - 5_PV1
5_INV2 - 5_PV2
5_INV3 - 5_PV3
5_INV4 - 5_PV4
6_INV1 - 6_PV1
6_INV2 - 6_PV2
6_INV3 - 6_PV3
6_INV4 - 6_PV4
7_INV1 - 7_PV1
7_INV2 - 7_PV2
7_INV3 - 7_PV3
7_INV4 - 7_PV4
8_INV1 - 8_PV1
8_INV2 - 8_PV2

380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380

13

LL FAULT LG FAULT LLG


FAULT

3179
3179
3179
3179
3179
3179
3179
3179
3179
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882
1882

1679
1679
3358
1679
1679
3358
1679
1679
3358
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859
1859

2732
2732
0
2732
2732
0
2732
2732
0
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517
1517

3030
2246
3239
3030
2246
3239
3030
2246
3239
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884

Residual Voltage Summary Results: 0.5 Cycle--Symmetrical


Fault At Bus : APTRANSCO

3 Phase Fault
Bus Name

APTRANSCO
132 kV Bus
33 kV Main SWBD (100)
33kV SWBD1 (200)
33kV SWBD2 (200)
1_INVR1
1_INVR2
1_INVR3
1_INVR4
2_INVR1
2_INVR2
2_INVR3
2_INVR4
3_INVR1
3_INVR2
3_INVR3
3_INVR4
4_INVR1
4_INVR2
4_INVR3
4_INVR4
5_INVR1
5_INVR2
5_INVR3
5_INVR4
6_INVR1
6_INVR2
6_INVR3
6_INVR4
7_INVR1
7_INVR2
7_INVR3
7_INVR4
8_INVR1
8_INVR2

Pre Fault voltage Residual voltage in


in Volts
Volts
132000
0
132000
0
33000
4684
33000
4685
33000
4686
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72
380
72

14

Residual Voltage Summary Results: 0.5 Cycle--Symmetrical


Fault At Bus : APTRANSCO

LL Fault
Bus Name

APTRANSCO
132 kV Bus
33 kV Main SWBD (100)
33kV SWBD1 (200)
33kV SWBD2 (200)
1_INVR1
1_INVR2
1_INVR3
1_INVR4
2_INVR1
2_INVR2
2_INVR3
2_INVR4
3_INVR1
3_INVR2
3_INVR3
3_INVR4
4_INVR1
4_INVR2
4_INVR3
4_INVR4
5_INVR1
5_INVR2
5_INVR3
5_INVR4
6_INVR1
6_INVR2
6_INVR3
6_INVR4
7_INVR1
7_INVR2
7_INVR3
7_INVR4
8_INVR1
8_INVR2

Pre Fault voltage Residual voltage in


in Volts
Volts
132000
71801
132000
71801
33000
17950
33000
17950
33000
17950
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211
380
211

15

Residual Voltage Summary Results: 0.5 Cycle--Symmetrical


Fault At Bus : APTRANSCO

LGFault
Bus Name

APTRANSCO
132 kV Bus
33 kV Main SWBD (100)
33kV SWBD1 (200)
33kV SWBD2 (200)
1_INVR1
1_INVR2
1_INVR3
1_INVR4
2_INVR1
2_INVR2
2_INVR3
2_INVR4
3_INVR1
3_INVR2
3_INVR3
3_INVR4
4_INVR1
4_INVR2
4_INVR3
4_INVR4
5_INVR1
5_INVR2
5_INVR3
5_INVR4
6_INVR1
6_INVR2
6_INVR3
6_INVR4
7_INVR1
7_INVR2
7_INVR3
7_INVR4
8_INVR1
8_INVR2

Pre Fault voltage Residual voltage in


in Volts
Volts
132000
0
132000
0
33000
5792
33000
5796
33000
5798
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68
380
68

16

Residual Voltage Summary Results: 0.5 Cycle--Symmetrical


Fault At Bus : APTRANSCO

LLGFault
Bus Name

APTRANSCO
132 kV Bus
33 kV Main SWBD (100)
33kV SWBD1 (200)
33kV SWBD2 (200)
1_INVR1
1_INVR2
1_INVR3
1_INVR4
2_INVR1
2_INVR2
2_INVR3
2_INVR4
3_INVR1
3_INVR2
3_INVR3
3_INVR4
4_INVR1
4_INVR2
4_INVR3
4_INVR4
5_INVR1
5_INVR2
5_INVR3
5_INVR4
6_INVR1
6_INVR2
6_INVR3
6_INVR4
7_INVR1
7_INVR2
7_INVR3
7_INVR4
8_INVR1
8_INVR2

Pre Fault voltage Residual voltage in


in Volts
Volts
132000
36974
132000
36974
33000
11122
33000
11120
33000
11120
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124
380
124

17

Transformers Relay Setting Calculations


Setting Calculation for Power Transformers
132kV

CTHV:200/1

30 MVA

CT LV:600/1 A

Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 33 kV Bus (Grid operation)
Fault current at 132kV Bus as per report (Grid operation)
Transformer Full Load HV side Primary Current at 0% tapping

33kV

PT
Vp
Vs
CTR1
CTR2
Z

Ipfl

Transformer HV side current as per name plate


Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 132 kV side
Setting proposed on HV side Ip
Curve
Transformer Full Load LV side Current at 0% tapping

Isfl

Transformer LV side Primary current as per name plate


Relay drop off Ratio
LV Pick up Current

Transformer LV side CT Secondary Pick up Current


IDMT setting at 33 kV side
Setting proposed on LV side Ip
Curve

Isfl

18

30000
kVA
132
kV
33
kV
200/1
200
600/1
600
12.50%
9274
A
35502
A
30000X 1000 )/ (1.732 Amps
X132x1000x1)
131.22
Amps
0.95
1.05 x HV Currrent/ Drop off ratio
=1.05x 131.21/0.95
145.03
0.73
0.7
0.7
Normal Inverse
30000X 1000 )/ (1.732 Amps
X33x1000x1)
524.88
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 437.40/0.95
607.75
1.01
1
1
Normal Inverse

Setting Calculation for Inverter Transformers

33kV

0.380kV

CTHV:100/1

4.4MVA
Transformer capacity
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer HV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 0.380 kV Bus (Grid operation)
Fault current at 33 kV Bus as per report (Grid operation)
Transformer Full Load HV side Primary Current at 0% tapping

PT
Vp
Vs
CTR1
CTR2
Z

Ipfl

Transformer HV side current as per name plate


Relay drop off Ratio
HV Pick up Current

Transformer HV side CT Secondary Pick up Current


IDMT setting at 33kV side
Setting proposed on HV side Ip
Curve

Isfl

19

4400
kVA
33
kV
0.38
kV
80/1
80
600/1
600
3.20%
9274
A
35502
A
4400X 1000 )/ (1.732 Amps
X33x1000x1)
76.98
Amps
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 76.98/0.95
89.14
1.10
1.1
1.1
Normal Inverse

SETTING DETAILS FOR LINE CONTROL PANEL

20

Setting Details for 132kV ,Line Control & Protection Panel


Line Protection
Relay settings for relays located in the Protection Panel

Relay Located in Protection Panel MiCOM P543 Multi Function Relay


SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 87
Function 21
Function 99-LV
Other functions are disabled
Power System Data 1

Setting
Enabled

CT Ratio on 132 kV side 300/1:In=300


PT Ratio 132 kV/ 3 : 110V/ 3
Line Differential Protection 87
Parameter

Function

Value (Range)

Diff.Prot
Differential Current Monitoring
Pick up value of differential current
T I-diff> time delay
Pick up value of High set trip
T I-diff>> time delay
Slope 1 of tripping charecterstic
Base point for slope1 of charecterstic
Slope 2 of tripping charecterstic
Base point for slope2 of charecterstic
Pick up for add on stablisation
Duration for add on stablisation

I-Diff> Mon
I-diff>
T I-diff>
I-diff>>
T I-diff>>
Slope 1
Base point 1
Slope 2
Base point 2
I Add on stab
T Add on stab

ON/OFF
ON/OFF
0.05..2 I/InO
0.00..60.00 s
0.5..35 I/InO
0.00..60.00 s
0.1..0.5
0.00..2 I/InO
0.25..0.95
0.00..10 I/InO
2..15 I/InO
2..250 Cycles

21

Set Value
ON
ON
0.2
0
8
0
0.2
0
0.7
4.5
4
15

Set unit Primary


Value

sec
sec

Distance Protection 21
Parameter

Unit
kV
V
A
A

Parameter
Unom PRIMARY in kV
Unom Secondary in Volts
CT Primary in Amps
CT Secondary in Amps
SystemStarpoint
Uph / Udelta
Rated Frequency
Phase Seq

ZL1 mag
ZL1 ang
ZL0 mag
ZL0 ang
KZ0 mag
KZ0 ang
Z1mag
Z1ang
Z2mag
Z2ang
Z3mag
Z3ang
Z4mag
Z4ang
R1 Ph max
R1 Ph min
R1ph
R2ph
TZ1
TZ2
R1G
R2G
Zone 1
Zone 2
Zone 3
Zone 4

Range
1.0 .. 1200.0 kV
80..125
10~5000
1A/5A
Solid Earthed
Peterson-Coil Isolated
0.10 .. 9.99
50/60 Hz
L1 L2 L3
L1 L3 L2
km/Miles
1.0~1200
10~5000
10~89 deg
Not reversed
Reversed

kV
A
deg

Distance Unit
Full scale volt
Full scale Current
Line Angle
P,Q sign

ohms/km
ohms/km
mfd / km
km
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
deg
Ohms
Ohms
sec
sec
sec
sec
Ohms
Ohms
Z1
Z0
Z1
Z0
Z1
Z0
Z1
Z0

R
x1
0.0050~9.5
c'
0.0~100
Line length
0.1~1000
Line Positive Sequence impedance (mag)
Line Positive Sequence impedance (Phase angle )
Line Zero Sequence impedance (mag)
Line Zero Sequence impedance (Phase angle )
Default residual compensation factor (mag)
Default residual compensation factor (Phase angle)
Zone 1 reach impedance setting (mag)
Zone 1 reach impedance setting (Phase angle)
Zone 2 reach impedance setting (mag)
Zone 2 reach impedance setting (Phase angle)
Zone 3 reach impedance setting (mag)
Zone 3 reach impedance setting (Phase angle)
Zone 4 reach impedance setting (mag)
Zone 4 reach impedance setting (Phase angle)
Phase fault resistive reach value
Phase fault resistive reach value
Time delay Zone 1
Time delay Zone 2
Time delay Zone 3
Time delay Zone 4
Ground fault resistive reach value zone 1
Ground fault resistive reach value zone 2
0.605+J0.878
0.900+j2.592
0.907+J1.318
1.35+j3.88
1.512+J2.196
2.25+j6.48
0.151+J0.220
0.225+j0.648

22

Settings
132
110
300
1
Solid
Earthed
1.73
50 Hz
L1 L2 L3
km
132
300
55.45
not
reversed
0.168
0.44
0.0081
18
5.33
55.45
13.719
70.8
0.543
24.77
1.06
55.45
1.599
55.45
2.66
55.49
0.266
55.45
0.7
2.1
0
0.4
0.8
0.25
4
5.3

Relay settings for relays located in the Protection Panel

Bay Control Unit

Relay Located in Protection Panel MiCOM C264P Multi Function Relay


SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 50
Function 51
Function 50N
Function 51N
Function 67
Function 67N
Function 59
Other functions are disabled
Power System Data 1

Setting
Enabled

CT Ratio on 132 kV side 300/1:In=300


PT Ratio 132 kV/ 3 : 110V/ 3

Non Directional Phase over current Protection: 51


Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Non Directional Ground over current Protection: 51 N


Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Time dial
Ie> TMS
IEC Curve

Directional Phase over current Protection: 67


Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Directional Ground over current Protection: 67 N


Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Time dial
Ie> TMS
IEC Curve

Over voltage Protction 59


Setting name
V>= Voltage set
tV> delay
V>>= Voltage set
tV>> delay

Units
Stage 1
Delay stage 1
Stage 2
Delay stage 1

Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)

Setting
1.5
0.15
0.45
NA
0.05
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
450

Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)

Setting
1
0.3
0.08
NA
0.07
Standard Inverse

unit
x In
s
x In
s

Prim Value
200

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)

Setting
1.5
0.15
0.45
NA
0.05
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
450

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI) ,Very
Inverse(VI) ,Extremely
Inverse(EI)

Setting
1
0.3
0.08
NA
0.07
Standard Inverse

unit
x In
s
x In
s

Prim Value
200

Range
5-200 V
0-599
5-200 V
0-599

Setting

unit
Volts
sec
Volts
sec

Prim Value
145.2

23

121
2
126.5
0.5

135

16

135

16

151.8

Distance Relay Setting Calculations

Name of Substation = 132 kV Mulkanoor SS S/S

Mulkanoor SS

CTR =
300 /
PTR =
132000 /
Protected Line parameters:
Per kilometer
Line
Z1 =
Zero seq
Line distance

APTRANSCO SS

18 km

300
1200

1
110

0.168 + j

Z0 =
Mulkanoor SS to
APTRANSCO SS

0.25 + j
18 km

0.244

= 0.29624

55.45

per km

0.72

= 0.76217

70.85

per km

4.392

= 5.33238

55.45

12.96

70.85

MULKANOOR SS to APTRANSCO SS

Line parameters

Z1

Z0

18 x(0.168+j0.244)
3.024 + j
18 x(0.25+j0.72)
4.5 + j

Zone 1 reach =
Zone 2 reach =
Zone 3 reach =
Zone 4 reach =
Ratio of Secondary to Primary Impedance
Zone 1 Phase Reach Settings
Required Zone 1 reach =

Zero seq Zone 1 reach

Required Zone2 reach =

Zero seq Zone 2 reach

Required Zone 3 reach =

Zero seq Zone3 reach

Required Zone4 reach =

13.719

80 % of protected line
120 % of protected line
200 % of protected line
20 % of protected line

=CTR/PTR =

0.250

80 % of Protected line length x Z1 x CTR/PTR


0.8 x(3.024+j4.392)x 0.250
= 1.06648
0.605 + j
0.878

55.45

80 % of Protected line length x Z0 x CTR/PTR


0.8 x(4.5+j12.96)x 0.250
= 2.7438
0.900 + j
2.592

70.85

120 % of Protected line length x Z1 x CTR/PTR


1.2 x(3.024+j4.392)x 0.250
= 1.59971
0.907 + j
1.318

55.45

120 % of Protected line length x Z0 x CTR/PTR


1.2 x(4.5+j12.96)x 0.250
= 4.11571
1.350 + j
3.8880

70.85

200 % of Protected line length x Z1 x CTR/PTR


2 x(3.024+j4.392)x 0.250
= 2.66619
1.512 + j
2.196

55.45

200 % of Protected line length x Z0 x CTR/PTR


2x(4.5+j12.96)x 0.250
= 6.85951
2.250 + j
6.480

70.85

20 % of Protected line length x Z1 x CTR/PTR

24

0.2 x(3.024+j4.392)x 0.250


0.151 + j
0.220
Zero seq Zone 4 reach

max load on line


system voltage
Z load
Z load Sec
angle
line

131.22
132
580.7992
145.1998
25

= 0.26662

20 % of Protected line length x Z0 x CTR/PTR


0.2 x(4.5+j12.96)x 0.104
= 0.68595
0.225 + j
0.648
Amps
kV
Ohms
deg

Resistive Reach Calculations


All distance elements must avoid the heaviest system loading. Taking the
secondary rating as a guide to the maximum load current, the minimum load impedance
presented to the relay would be:
Vn (phase-neutral) / In =
132 /3
= 76.21024
Typically, phase fault distance zones would avoid the minimum load impedance by a
margin of 40% if possible (bearing in mind that the power swing characteristic
surrounds the tripping zones), earth fault zones would use a 20% margin. This
allows maximum resistive reaches of
45.72614 for Phase faults
&
60.96819 for Earth faults
Taking a required primary resistive coverage of
7 for phase faults,
and assuming a typical earth fault coverage of
20 , for earth faults
the minimum secondary reaches become:
RPh (min) =
7 x
0.25
1.8 (secondary);
RG (min) =
20 x
0.25
5 (secondary).
RPh (max) =
46 x
0.25
11 (secondary);
RG (max) =
61 x
0.25
15 (secondary).
Resistive reaches could be chosen between the calculated values as shown in Table
The zone 2 elements satisfy R2Ph (R3Ph x 80%), and R2G (R3G 80%).

25

1 A CT
1

55.45

70.85

SETTING DETAILS FOR TRANSFORMER


CONTROL PANEL

26

Setting Details for 132/33 kV ,25/30 MVA Power Transformer -Control & Protection Panel
Transformer Feeder protection for Power Transformer
Relay settings for relays located in the Protection Panel +1TR1A
Differential Protection Relay-87T/64R

Relay Located in Protection Panel +1TR1A MiCOM P643 Multi Function Relay
SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 87
Function 64R
Function 99-LV
Other functions are disabled
Power System Data 1

Setting
Enabled

CT Ratio on 33 kV side 600/1:In=600


CT Ratio on 132 kV side 200/1:In=200
CT Ratio for LV NCT LV 750/1:In=750
CT Ratio for HV NCT HV 200/1:In=200
PT Ratio 33 kV/ 3 : 110V/ 3

Transformer Differential Protection 87


Setting name
DIFF: Idiff> SGx
DIFF: Idiff>> SGx 30.0 Iref 0.1 Iref
DIFF: Idiff>>> SGx
DIFF: m1 SGx
DIFF: m2 SGx
DIFF: IR, m2 SGx
DIFF: Op.del., trip sig. SGx
Is2
IS-HS1
IS-HS2
2nd harmonic Block
Ih(2)%>
5nd harmonic Block
Ih(5)%>
Restricted Earth fault Protection 64R
IREF > K1
t ref > Time delay
Over Flux Protection LV
Setting name
State of the Overflux Protection
Pick up Value Warning Stage U/f
Time delay for Warning Stage U/f
V/Hz >1 Status
V/Hz >1 Trip Func
V/Hz >1 Trip Set
V/Hz >1 Trip TMS
V/Hz >1 tReset
Tpre-Trip Alarm

Units

Range
Setting
0.10 Iref - 2.50 Iref
0.10 Iref
2.5 Iref-30.0 Iref
4.0 Iref
Blocked/ 2.5 Iref - 30.0 Iref
0.10 - 1.50
0.30
0.10 - 1.50
0.8
1.5 Iref - 10.0 Iref
4.0 Iref
0.00 s -100.00 s
0.00 s

Enabled
Enabled

Blocked/ 0.05 In -1.00 In


Blocked/ 0.00 s - 10.00 s
Units

Range
1.0~1.2
0~60 sec

Time for cooldown

1.0~1.4
0~1000 sec

Adaption Factors

0.5~2.0

27

unit
x Iref
x Iref
4 x Iref

x Iref
sec
1 x Iref
4 x Iref
4 I ref
10 %
20 %
0.1 x In
0

Setting
ON

Enabled
IDMT
2.53V/Hz

Prim Value

unit
1.1 V/Hz
1 sec

V/Hz
0.1
0 sec
200 sec
45
1

20

Prim Value

SEF & Over Fluxing Protection -99HV/51N


Relay Located in Protection Panel +1TR1A MiCOM P642 Multi Function Relay
SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 51N
Function 99-HV
Other functions are disabled
Power System Data 1

Setting
Enabled

CT Ratio for LV NCT LV 750/1:In=750


CT Ratio for HV NCT HV 200/1:In=200
PT Ratio 132 kV/ 3 : 110V/ 3

Standby Earth Fault Protection 51N HV


Setting name
IN 1 > 1 Current Set
IN 1 > 1 Function

IN 1 > 1 TMS
Standby Earth Fault Protection 51N LV
IN 1 > 1 Current Set
IN 1 > 1 Function

IN 1 > 1 TMS
Over Flux Protection HV
Setting name
State of the Overflux Protection
Pick up Value Warning Stage U/f
Time delay for Warning Stage U/f
V/Hz >1 Status
V/Hz >1 Trip Func
V/Hz >1 Trip Set
V/Hz >1 Trip TMS
V/Hz >1 tReset
Tpre-Trip Alarm

Units
IEC Curve

IEC Curve

Units

Range
Setting
Blocked/ 0.08 In - 4.00 In
Definite Time IEC
Definite Time
Standard Inverse IEC
Very Inverse IEC Extr.
Inverse IEC Long Time
Inv. IEEE Moderately Inv.
IEEE Very Inverse IEEE
Extr. Inverse ANSI
Normally Inv. ANSI Short
Time Inv. ANSI Long
Time Inv. RI-Type
Inverse RXIDG-Type
Inverse 0.025 - 1.2

unit
0.1 x In

Blocked/ 0.08 In - 4.00 In


Definite Time IEC
Definite Time
Standard Inverse IEC
Very Inverse IEC Extr.
Inverse IEC Long Time
Inv. IEEE Moderately Inv.
IEEE Very Inverse IEEE
Extr. Inverse ANSI
Normally Inv. ANSI Short
Time Inv. ANSI Long
Time Inv. RI-Type
Inverse RXIDG-Type
Inverse 0.025 - 1.2

0.1 x In

Range
1.0~1.2
0~60 sec

Time for cooldown

1.0~1.4
0~1000 sec

Adaption Factors

0.5~2.0

28

Setting
ON

Enabled
IDMT
2.53V/Hz

Prim Value
20

1 sec
75

1 sec
unit
1.1 V/Hz
1 sec

V/Hz
0.1
0 sec
200 sec
45
1

Prim Value

Relay settings for relays located in the Protection Panel +1TR1A


Bay Control Unit for HV -BCPU HV

Relay Located in Protection Panel +1TR1A MiCOM C264P Multi Function Relay
SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 50
Function 51
Function 50N
Function 51N
Function 50BF
Other functions are disabled
Power System Data 1

Setting
Enabled

CT Ratio on 132 kV side 200/1:In=200


PT Ratio 132 kV/ 3 : 110V/ 3

Non Directional Phase over current Protection: 51


Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Non Directional Ground over current Protection: 51 N


Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Time dial
Ie> TMS
IEC Curve

Breaker Failure Protectiion 50 BF

Setting name

CB Fail 1 Status
CB Fail 1 Timer
I< Current Set
CB Fail 2 Status
CB Fail 2 Timer
I< Current Set

Units

Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
1.5
0.3
0.7
NA
0.06
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
300

Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
1
0.3
0.1
NA
0.13
Standard Inverse

unit
x In
s
x In
s

Prim Value
200

Range

Setting

unit

Prim Value

Enabled/Disabled
0-10
Enabled/Disabled
0-10

29

Enabled
Enabled

0.05 sec
5%
0.2 sec
10 %

140

20

Relay settings for relays located in the Protection Panel +1TR1B


Bay Control Unit for LV -BCPU LV

Relay Located in Protection Panel +1TR1B MiCOM C264P Multi Function Relay

CT Ratio on 33kV side 600/1:In=600

33000V Outgoing to Transformer


Relay type: Schneider Electric C 264P
SCOPE OF FUNCTION
Address

Other functions are disabled


Power System Data 1
CTs

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

600A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
2.1
0.45
1
NA
0.07
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
1260

Range
0.1~40.00 A
0.00..150.00 s
0.01~8.00A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
1
0.45
0.1
NA
0.21
Standard Inverse

unit
x In
s
x In
s

Prim Value
600

CT rated primary
CT rated secondary
Non Directional Phase over current Protection: 51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Non Directional Ground over current Protection: 51 N


Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Time dial
Ie> TMS
IEC Curve

30

600

60

SETTING DETAILS FOR FEEDER


CONTROL PANEL

31

Setting Details for 33 kV ,Feeder 1 & 2-Control & Protection Panel


Incomer from Array Yard 1
CT Ratio on 33kV side 250/1:In=250

33000V Incomer 1 12 MW block


Relay type: Schneider Electric C 264P
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Non Directional Phase over current Protection: 51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

250A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
450

Setting
0.9
0.6
0.09
NA
0.3
Standard Inverse

unit
x In
s
x In
s

Prim Value
225

Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
450

Non Directional Ground over current Protection: 51 N


Setting name
Units
Range
50N-2 Pickup
Ie>> >>
0.1~40.00 A
50N-2 Delay
Te>>>>
0.00..150.00 s
51N-1Pickup
Ie>
0.1~40.00 A
51N-1Delay
TIe>
0.00..150.00 s
Time dial
Ie> TMS
0.02~1.5
IEC Curve
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Directional Phase over current Protection: 67
Setting name
Units
Range
50-2 pickup
I> >
0.1~40.00 A
50-2 Delay
T I>>
0.00..150.00 s
50-1Pickup
I>
0.01~8.00A
50-1Delay
tI>
0.00..150.00 s
Time dial
I> TMS
0.02~1.5
IEC Curve
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

32

225

22.5

225

Incomer from Array Yard 2


CT Ratio on 33kV side 250/1:In=250

33000V Incomer 2 12MW block


Relay type: Schneider Electric C 264P
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Non Directional Phase over current Protection: 51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

250A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse

unit
x In
s
x In
s
s

Non Directional Ground over current Protection: 51 N


Setting name
Units
Range

Setting

unit

50N-2 Pickup
50N-2 Delay
51N-1Pickup
51N-1Delay
Time dial
IEC Curve

0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

0.9
0.6
0.09
NA
0.3
Standard Inverse

x In
s
x In
s

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse

unit
x In
s
x In
s
s

Ie>> >>
Te>>>>
Ie>
TIe>
Ie> TMS

Directional Phase over current Protection: 67


Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
50-1Pickup
I>
50-1Delay
tI>
Time dial
I> TMS
IEC Curve

33

Prim Value
450
225

Prim Value
225
22.5

Prim Value
450
225

Setting Details for 33 kV ,Feeder 3 & 4-Control & Protection Panel


Incomer from ICR 7
CT Ratio on 33kV side 100/1:In=100

33000V Incomer 3 4 MW block


Relay type: Schneider Electric C 264P
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Non Directional Phase over current Protection: 51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

100A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
1.6
0.6
0.8
NA
0.09
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
160

Setting
0.8
0.6
0.08
NA
0.3
Standard Inverse

unit
x In
s
x In
s

Prim Value
80

Setting
1.6
0.6
0.8
NA
0.09
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
160

Non Directional Ground over current Protection: 51 N


Setting name
Units
Range
50N-2 Pickup
Ie>> >>
0.1~40.00 A
50N-2 Delay
Te>>>>
0.00..150.00 s
51N-1Pickup
Ie>
0.1~40.00 A
51N-1Delay
TIe>
0.00..150.00 s
Time dial
Ie> TMS
0.02~1.5
IEC Curve
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Directional Phase over current Protection: 67
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
50-1Pickup
I>
50-1Delay
tI>
Time dial
I> TMS
IEC Curve

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

34

80

80

Incomer from ICR 8


CT Ratio on 33kV side 50/1:In=50

33000V Incomer 4 2 MW block


Relay type: Schneider Electric C 264P
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Non Directional Phase over current Protection: 51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

50A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
1.6
0.6
0.8
NA
0.09
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
80

Setting
0.8
0.6
0.08
NA
0.3
Standard Inverse

unit
x In
s
x In
s

Prim Value
40

Setting
1.6
0.6
0.8
NA
0.09
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
80

Non Directional Ground over current Protection: 51 N


Setting name
Units
Range
50N-2 Pickup
Ie>> >>
0.1~40.00 A
50N-2 Delay
Te>>>>
0.00..150.00 s
51N-1Pickup
Ie>
0.1~40.00 A
51N-1Delay
TIe>
0.00..150.00 s
Time dial
Ie> TMS
0.02~1.5
IEC Curve
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Directional Phase over current Protection: 67
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
50-1Pickup
I>
50-1Delay
tI>
Time dial
I> TMS
IEC Curve

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

35

40

40

Setting Details for 33 kV ,Feeder 5 & 6-Control & Protection Panel


Spare
CT Ratio on 33kV side 250/1:In=250

33000V Incomer 1 12 MW block


Relay type: Schneider Electric C 264P
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Non Directional Phase over current Protection: 51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

250A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
450

Setting
0.9
0.6
0.09
NA
0.3
Standard Inverse

unit
x In
s
x In
s

Prim Value
225

Setting
1.8
0.6
0.9
NA
0.08
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
450

Non Directional Ground over current Protection: 51 N


Setting name
Units
Range
50N-2 Pickup
Ie>> >>
0.1~40.00 A
50N-2 Delay
Te>>>>
0.00..150.00 s
51N-1Pickup
Ie>
0.1~40.00 A
51N-1Delay
TIe>
0.00..150.00 s
Time dial
Ie> TMS
0.02~1.5
IEC Curve
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)
Directional Phase over current Protection: 67
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
50-1Pickup
I>
50-1Delay
tI>
Time dial
I> TMS
IEC Curve

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

36

225

22.5

225

Outgoing to Auxiliary Transformer


CT Ratio on 33kV side 30/1:In=30

33000V outgoing to 63 kVA Transformer


Relay type: Schneider Electric C 264P
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Non Directional Phase over current Protection: 51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

30A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

Setting
0.8
0.6
0.04
NA
0.07
Standard Inverse

unit
x In
s
x In
s
s

Prim Value
24

Setting
0.1
0.1
0.01
0.07
DT
Standard Inverse

unit
x In
s
x In
s

Prim Value

Non Directional Ground over current Protection: 51 N


Setting name
Units
Range
50N-2 Pickup
Ie>> >>
0.1~40.00 A
50N-2 Delay
Te>>>>
0.00..150.00 s
51N-1Pickup
Ie>
0.1~40.00 A
51N-1Delay
TIe>
0.00..150.00 s
Time dial
Ie> TMS
0.02~1.5
IEC Curve
Standard Inverse(SI)
,Very Inverse(VI)
,Extremely Inverse(EI)

37

1.2

0.3

SETTING DETAILS FOR 33kV SWITCHBOARD

38

33kV,630 A,26.3kA /3 sec, Switch Board 1 (Item No 200)


Incomer from Inverter Transformer ICR 1
Relay Located in Switch Board

Panel 1-IC003

CT Ratio on 33kV side 80/1:In=80

33000V Incomer ICR 4 MW block


Relay type: Siemens 7SR1003
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial

Ie> TMS

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

80A
1A

Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL

Setting
2
0.9
1
NA
0.12
IEC NI

unit
x In
s
x In
s
s

Prim Value
160

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100

Setting
1
0.9
0.1
NA
IEC NI

unit
x In
s
x In
s

Prim Value
80

39

0.44

80

Outgoing to 33 kV Switch Board


Relay Located in Switch Board

Panel 2-OG000

CT Ratio on 33kV side 250/1:In=250

Relay type: Siemens 7SR1003


SCOPE OF FUNCTION
Address

Other functions are disabled


Power System Data 1
CTs

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

250A
1A

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
0.01,0.025..1.6,1.7,..100
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL

Setting
1.8
0.75
1
NA
0.08
IEC NI

unit
x In
s
x In
s
s

Prim Value
450

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100

Setting
1
0.75
0.1
NA
IEC NI

unit
x In
s
x In
s

Prim Value
250

CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial

Ie> TMS

40

0.36

250

25

33kV,630 A,26.3kA /3 sec, Switch Board 2 (Item No 200)


Incomer from Inverter Transformer ICR 4
Relay Located in Switch Board

Panel 1-IC003

CT Ratio on 33kV side 80/1:In=80

33000V Incomer ICR 4 MW block


Relay type: Siemens 7SR1003
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Other functions are disabled
Power System Data 1
Title Setting
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial

Ie> TMS

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

80A
1A

Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL

Setting
2
0.9
1
NA
0.12
IEC NI

unit
x In
s
x In
s
s

Prim Value
160

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100

Setting
1
0.9
0.1
NA
IEC NI

unit
x In
s
x In
s

Prim Value
80

41

0.44

80

Outgoing to 33 kV Switch Board


Relay Located in Switch Board

Panel 2-OG000

CT Ratio on 33kV side 250/1:In=250

Relay type: Siemens 7SR1003


SCOPE OF FUNCTION
Address

Other functions are disabled


Power System Data 1
CTs

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

250A
1A

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
0.01,0.025..1.6,1.7,..100
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL

Setting
1.8
0.75
1
NA
0.08
IEC NI

unit
x In
s
x In
s
s

Prim Value
450

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100

Setting
1
0.75
0.1
NA
IEC NI

unit
x In
s
x In
s

Prim Value
250

CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-2 pickup
I> >
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial

Ie> TMS

42

0.36

250

25

33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR2


Incomer from Inverter Transformer

Relay Located in Switch Board

Panel 1-IC0G0

CT Ratio on 33kV side 80/1:In=80

33000V Incomer ICR2 4 MW block


Relay type: Siemens 7SR1003
SCOPE OF FUNCTION
Address

Other functions are disabled


Power System Data 1
CTs

Phase over current Protection: 50/51


Setting name
50-2 pickup
50-2 Delay
51-1Pickup
51-1Delay
Time dial

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary

10..50000 A
1A/5A

80A
1A

Units
I> >
T I>>
I>
tI>
I> TMS

Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100

Setting
2
0.9
1
NA
0.12

IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL

IEC NI

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
0.01,0.025..1.6,1.7,..100

Setting
1
0.9
0.1
NA
IEC NI
0.44

IEC Curve

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial
Ie> TMS

43

unit Prim Value


160
x In
s
80
x In
s
s

unit Prim Value


300
x In
s
30
x In
s

33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR3


Incomer from Inverter Transformer

Relay Located in Switch Board

Panel 1-IC0G0

CT Ratio on 33kV side 80/1:In=80

33000V Incomer ICR3 4 MW block


Relay type: Siemens 7SR1003
SCOPE OF FUNCTION
Address

Other functions are disabled


Power System Data 1
CTs

Phase over current Protection: 50/51


Setting name
50-2 pickup
50-2 Delay
51-1Pickup
51-1Delay
Time dial

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary

10..50000 A
1A/5A

80A
1A

Units
I> >
T I>>
I>
tI>
I> TMS

Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100

Setting
2
0.9
1
NA
0.12

IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL

IEC NI

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100

Setting
1
0.9
0.1
NA
IEC NI

IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial

Ie> TMS

44

0.44

unit Prim Value


160
x In
s
80
x In
s
s

unit Prim Value


300
x In
s
30
x In
s

33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR5


Incomer from Inverter Transformer

Relay Located in Switch Board

Panel 1-IC0G0

CT Ratio on 33kV side 80/1:In=80

33000V Incomer ICR5 4 MW block


Relay type: Siemens 7SR1003
SCOPE OF FUNCTION
Address

Other functions are disabled


Power System Data 1
CTs

Phase over current Protection: 50/51


Setting name
50-2 pickup
50-2 Delay
51-1Pickup
51-1Delay
Time dial

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary

10..50000 A
1A/5A

80A
1A

Units
I> >
T I>>
I>
tI>
I> TMS

Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100

Setting
2
0.9
1
NA
0.12

IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL

IEC NI

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100

Setting
1
0.9
0.1
NA
IEC NI

IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial

Ie> TMS

45

0.44

unit Prim Value


160
x In
s
80
x In
s
s

unit Prim Value


300
x In
s
30
x In
s

33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR6


Incomer from Inverter Transformer

Relay Located in Switch Board

Panel 1-IC0G0

CT Ratio on 33kV side 80/1:In=80

33000V Incomer ICR6 4 MW block


Relay type: Siemens 7SR1003
SCOPE OF FUNCTION
Address

Other functions are disabled


Power System Data 1
CTs

Phase over current Protection: 50/51


Setting name
50-2 pickup
50-2 Delay
51-1Pickup
51-1Delay
Time dial

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary

10..50000 A
1A/5A

80A
1A

Units
I> >
T I>>
I>
tI>
I> TMS

Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100

Setting
2
0.9
1
NA
0.12

IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL

IEC NI

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100

Setting
1
0.9
0.1
NA
IEC NI

IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial

Ie> TMS

46

0.44

unit Prim Value


160
x In
s
80
x In
s
s

unit Prim Value


300
x In
s
30
x In
s

33kV,800A,26.3 kA /3 sec, ICOG Panel (ItemNo 400) ICR7


Incomer from Inverter Transformer

Relay Located in Switch Board

Panel 1-IC0G0

CT Ratio on 33kV side 80/1:In=80

33000V Incomer ICR7 4 MW block


Relay type: Siemens 7SR1003
SCOPE OF FUNCTION
Address

Other functions are disabled


Power System Data 1
CTs

Phase over current Protection: 50/51


Setting name
50-2 pickup
50-2 Delay
51-1Pickup
51-1Delay
Time dial

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

CT rated primary
CT rated secondary

10..50000 A
1A/5A

80A
1A

Units
I> >
T I>>
I>
tI>
I> TMS

Range
0.005 to 5
0.00..14400 s
0.05,0.06,..4
0.00..14400 s
0.01,0.025..1.6,1.7,..100

Setting
2
0.9
1
NA
0.12

IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL

IEC NI

Range
0.005 to 5
0.00..14400s
0.05,0.06,..4
0.00..14400s
IEC NI,VI,EI,LTI,ANSI
MI,VI,EI, & DTL
0.01,0.025..1.6,1.7,..100

Setting
1
0.9
0.1
NA
IEC NI

IEC Curve
Ground over current Protection: 50N/51 N
Setting name
Units
50N-2 Pickup
Ie>> >>
50N-2 Delay
Te>>>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
IEC Curve
Time dial

Ie> TMS

47

0.44

unit Prim Value


160
x In
s
80
x In
s
s

unit Prim Value


80
x In
s
8
x In
s

TIME CURRENT CHARACTERSTIC CURVES

48

10000
1000
100

ITR1
FEED_CP_IC1
33kV_OG
TR1_RELAYS_HV

Time in Seconds

10

TR1_RELAYS_LV

TR1
A 30000.0 KVA
Transformer

LINE RELAYS

.01

.1

.5

33000 Volt Phase

10

100
Current in Amperes X 10
Time-Current Characteristic Curves

1 - Fault current Flow:ICR1-33kV SWBD-Power Trafo-Grid

1000

10000
12-18-2016
19:39:55
mulk_09112016

49

10000
1000
100

IC003_SWBD1
FCP_IC1
TR1_RELAYS_LV
TR1_RELAYS_HV

10

LINE RELAYS

.01

.1

Time in Seconds

OG000_SWBD1

.5

33000 Volt Ground

10

100
Current in Amperes X 10
Time-Current Characteristic Curves

1 - Fault current Flow:ICR1-33kV SWBD-Power Trafo-Grid

1000

10000
12-18-2016
19:52:39
mulk_09112016

50