Transformers
Transformers
Transformers
This has distributed magnetic circuit. The number of independent magnetic circuits is more than 2. Its
core construction is like spokes of a wheel. Otherwise it is symmetrical to that of shell type.
Diagrammatically it can be shown as in the Fug. 3.
Principle of working
2
The principle of mutual induction states that when two coils are inductively coupled and if current in
one coil is changed uniformly then an e.m.f. gets induced in the other coil. This e.m.f can drive a current,
when a closed path is provided to it. The transformer works on the same principle. In its elementary form,
it consists of tow inductive coils which are electrically separated but linked through a common magnetic
circuit. The two coils have high mutual inductance. The basic transformer is shown in the Fig 1.2.
One of the two coils is connected to source of alternating voltage. This coil in which electrical energy
is fed with the help of source called primary winding (P). The other winding is connected to load. The
electrical energy transformed to this winding is drawn out to the load.
Ratios of a Transformer
Consider a transformer shown in Fig.1 indicating various voltages and currents.
This ratio of secondary induced e.m.f. to primary induced e.m.f. is known as voltage transformation
ratio denoted as K,
Thus,
1. If N2 > N1 i.e. K > 1, E2 > E1 we get then the transformer is called step-up transformer.
2. If N2 < N1 i.e. K < 1, we get E2 < E1 then the transformer is called step-down transformer.
3. If = i.e. K= 1, we get E2 = E1 then the transformer is called isolation transformer or 1:1
transformer.
Concept of Ideal Transformer
Similarly the secondary induced e.m.f. E2 is also same as the terminal voltage V2 across the load.
Hence for an ideal transformer we can write,
No transformer is ideal in practice but the value of E1 is almost equal to V1 for properly designed
transformer.
Key point: Hence the currents are in the inverse ratio of the voltage transformation ratio.
Voltage ampere rating
When electrical power is transferred from primary winding to secondary there are few power losses in
between. These power losses appear in the form of heat which increases the temperature of the device.
Now this temperature must be maintained below certain limiting values as it is always harmful from
insulation point of view. As current is the main cause in producing heat, the output maximum rating is
generally specified as the product of output voltage and output current i.e.V 2 I2. This always indicates that
when transformer is operated under this specified rating, its temperature rise will not be excessive. The
copper loss (I2R) in the transformer depends on the current 'I' through the winding while the iron or core
loss depends on the voltage 'V' as frequency of operation is constant. None of these losses depend on the
power factor (cos ) of the load. Hence losses decide the temperature and hence the rating of the
transformer. As losses depend on V and I only, the rating of the transformer is specified as a product of
these two parameters VxI.
Key point: Thus the transformer rating is specified as the product of voltage and current called VA rating.
On both sides, primary and secondary VA rating remains same. This rating is generally expresses in
KVA (kilo volt amperes rating).
Now
V1 /V2 = I2 /I1 = K
...
V1 I1 = V2 I2
If V1 and V2 are the terminal voltages of primary and secondary then from specified KVA rating we
can decide full load currents of primary and secondary, I1 and I2. This is the safe maximum current limit
which may carry, keeping temperature rise below its limiting value.
Example 1: A single phase, 50 Hz transformer has 80 turns on the primary winding and 400 turns on the
secondary winding. The net cross-sectional area of the core is 200 cm 2. If the primary winding is connected
at a 240 V , 50 Hz supply, determine :
i) The e.m.f. induced in the secondary winding.
ii) The maximum value of the flux density in the core.
Solution
N1 = 80 , f = 50 Hz , N2 = 400 , a = 200 cm2 = 200 x 10-4 cm2
E1 = 240
K = N2 /N1 = 400/80 = 5/1
.
..
K =E2 /E1 = E2 /240= 5/1
E2 = 5 x 240 = 1200 V
Now
E1 = 4.44 f m N1
240 = 4.44 x 50 x m x 80
...
m = 240/(4.44 x 50 x 80) = 0.01351 Wb
...
Bm = m /a = 0.01351/(200 x 10-4) = 0.6756 Wb/m2
Example 2: For a single phase transformer having primary and secondary turns of 440 and 880
respectively, determine the transformer KVA rating if half load secondary current is 7.5 A and maximum
value of core flux is 2.25 Wb.
Solution
N1 = 440 ,
N2 = 880 ,
(I2)H.L. = 7.5 A,
fm = 2.25 mWb , E2 = 4.44 m f N2
Assuming
f = 50 Hz,
.
..
E2 = 4.44 x 2.25 x 10-3x 50x880 = 439.56 V
(I2)F.L. = KVA rating / E2
And
(I2)H.L. = 0.5 (I2)F.L.
...
(I2)H.L. = 0.5 x (KVA rating /E2 )
.
..
7.5 = 0.5 x (KVA rating / 439.56)
... KVA rating
= 2 x 7.5 x 439.56 x 10-3
= 6.5934 KVA
.....(10-3 for KVA)
Example 3: A single phase transformer has 350 primary and 1050 secondary turns. The primary is
connected to 400 V, 50 Hz a.c. supply. If the net cross-sectional area of the core is 50 cm 2, calculate i) The
maximum value of the flux density in the core ii) The induced e.m.f. in the secondary winding.
Solution
The given value are,
N1 = 350 turns,
N2 = 1050 turns
V1 = 400 V ,
A = 50 cm2= 50 x 10-4 m2
The e.m.f. of the transformer is,
E1 = 4.44 f m N1
E1 = 4.44 Bm A f N1
as m = Bm A
Flux density
Bm = E1 / (4.44 A f N1)
= 400 / (4.44 x 50 x 10-4 x50 x 350)
assume E1 = V1
2
= 1.0296 Wb/m
K = N2 /N1 = 1050/350 = 3
And
K = E2 /E1 = 3
...
E2 = 3 x E1 = 3 x 400 = 1200 V
In practical transformer, due to winding resistance, no load current I o is no longer at 90o with respect to V1.
But it lags V1 by angle o which is less than 90o. Thus cos o is called no load power factor of practical
transformer.
It may be denoted that the current is very small, about 3 to 5% of the full load rated current. Hence the
primary copper loss is negligibly small hence I c is called core loss or iron loss component. Hence power
input Wo on no load always represent the iron losses, as copper loss is negligibly small. The iron losses are
denoted as Pi and are constant for all load conditions.
Example 1 : The no load current of a transformer is 10 A at a power factor 0f 0.25 lagging, when
connected to 400 V, 50 Hz supply. Calculate,
a) Magnetising component of the no load current
b) Iron loss and c) Maximum value of flux in the core.
Assume primary winding turns as 500.
Solution : The given value are, = 10 A, cos = 0.25, = 400 V and f = 50 Hz
a)
Im = Io sin o = magnetising component
o = cos-1(0.25) = 75.522o
...
Im = 10 x sin (75.522o ) = 9.6824 A
b)
Pi = iron loss = power input on no load
= Wo = V1 Io cos o = 400 x 10 x 0.25
= 1000 W
c) On no load,
E1 = V1 = 400 V and N1 = 500
Now
E1 = 4.44 f m N1
...
400 = 4.44 x 50 x m x 500
...
m = 3.6036 mWb
I2' = I2/ K. Now I1 is the phasor addition of Io and I2'. This I1 causes the voltage drop across primary
resistance R1 and reactance X1.
Hence the equivalent circuit can be shown as in the Fig. 2.
Fig. 2
But in the equivalent circuit, windings are not shown and it is further simplified by transferring all the
values to the primary or secondary. This makes the transformer calculation much easy.
So transferring secondary parameters to primary we get,
R2'= R2/K2 ,
X2' = X2/K2' ,
Z2' = Z2/K2
While
E2' = E2/K'
I2' = K I2
Where
K = N2 /N1
While transferring the values remember the rule that
Low voltage winding High current Low impedance
High voltage winding Low current High impedance
Thus the exact equivalent circuit referred to primary can be shown as in the Fig. 3.
Now as long as no load branch i.e. exciting branch is in between Z 1 and Z2', the impedances cannot be
combined. So further simplification of the circuit can be done. Such circuit is called approximate
equivalent circuit.
Approximate Equivalent Circuit
To get approximate equivalent circuit, shift the no load branch containing Ro and Xo to the left of R1 and
X1. By doing this we are creating an error that the drop across R 1 and X1due to Io is neglected. Hence such
an equivalent circuit is called approximate equivalent circuit.
So approximate equivalent circuit referred to primary can be as shown in the Fig. 5.
Fig. 6
We know that, R1e = R1 + R2'= R1 + R2/K2
X1e = X1 + X2' = X1 + X2/K2
Z1e = R1e + j X1e
Ro = V1 /Ic and Xo = V1 /Im
Ic = Io coso and Im = Io sino
In the similar fashion, the approximate equivalent circuit referred to secondary also can be obtained.
Approximate Voltage Drop in Transformer
Consider the equivalent circuit referred to secondary as shown in the Fig. 1.
12
Fig. 1
From the Fig. 1 we can write,
As primary parameters are referred to secondary, there are no voltage drops in primary.
When there is no load, I2 = 0 and we get no load terminal voltage V20 as E2.
.
..
V20 = E2 = No load terminal voltage
while
V2 = Terminal voltage on load
Consider the phasor diagram for lagging p.f. load. The current I2 lags V2 by angle 2. Take V2 as
reference phasor. I2 R2e is in phase with I2 while I2 X2e leads I2 by 90o. The phasor diagram is shown in the
Fig.2.
Fig. 2
To derive the expression for approximate voltage drop, draw the circle with O as centre and OC as
redius, cutting extended OA at M. As OA = V2 and now OM = E2, the total voltage drop is AM = I2 Z2e.
But approximating this voltage drop is equal to AN instead of AM where N is intersection of
perpendicular drawn from C on AM. This is because angle is practically very very small and in practice M
and N are very close to each other.
Approximate voltage drop = AN
Draw perpendicular from B on AM intersecting it at D and draw parallel to DN from B to the point L
shown in the Fig. 2.
...
AD = AB cos 2= I2 R2e cos 2
and
DN = BL = BC sin 2 = I2 X2e sin 2
.
..
AN = AD + DN = I2 R2e cos 2 + I2 X2e sin 2
Assuming
2= 1=
... Approximate voltage drop = I2 R2e cos + I2 X2e sin
If all the parameters are referred to primary then we get,
Approximate voltage drop = I1 R1e cos + I1 X1e sin
13
If the load has leading p.f. then we get the phasor diagram as shown in the Fig. 3. The I 2 leads V2 by
angle 2 .
Fig. 3
In this case, the expression for approximate voltage drop remains same but the sign of I2 X2e sin
reverses.
Approximate voltage drop = I2 R2e cos - I2 X2e sin ....... Using referred to secondary values
= I1 R1e cos - I1 X1e sin ...........Using referred to primary values
It can be noticed that for leading power factor E2 < V2.
For the unity power factor, the phasor diagram is simple and is shown in the Fig. 4. For this case, as
cos = 1 and sin = 0, the approximate voltage drop is I2 R2e or I1R1e.
Fig. 4
Thus the general expression for the total approximate voltage drop is,
Approximate voltage drop = E2 - V2
= I2e R2e cos I2e X2e sin ........Using referred to secondary values
= I1e R1e cos I1e X1e sin ........Using referred to primary values
+ sing for lagging power factor while - sign for leading power factor loads.
Voltage Regulation of Transformer
The decrease in the secondary terminal voltage expressed as a fraction of the no load secondary
terminal voltage is called regulation of a transformer.
Let
14
The voltage drop should be as small as possible hence less the regulation better is the performance of a
transformer.
Expression for Voltage Regulation
Total voltage drop = I2 R2e cos I2 X2e sin
Hence the regulation can be expressed as,
'+' sing for lagging power factor while '-' sing for leading power factor loads.
The regulation van be further expressed in terms of I1 , V1, R1e and X1e.
Example 1 : 250/125 V, 5 KVA single phase transformer has primary resistance of 0.2 and reactance of
0.75. The secondary resistance is 0.05 and reactance of 0.2
i) Determine its regulation while supplying full load on 0.8 leading p.f.
ii) The secondary terminal voltage on full load 0.8 and leading p.f.
Solution : The given values are,
R1 = 0.2 , X1 = 0.75 , R2 = 0.05 , X2 = 0.2 , cos = 0.8 leading
K= E2 /E1 = 125/250 = 1/2 = 0.5
(I2) F.L.= KVA/V2 = 5x103 /125 = 40 A
...... full load
R2e = R2 + K2 R1 = 0.05 + (0.5)2 x 0.2 = 0.1
X2e = X2 + K2 X1 = 0.2 + (0.5)2 x 0.75 = 0.3875
i) Regulation on full load, cos = 0.8 leading
sin = 0.6
...
%R = ((I2 R2e cos - I2 X2e sin )/E2 ) x 100
where I2 = Full load current
...
% R = ((40 x 0.1 x 0.8 - 40 x 0.3875 x 0.6)/125) x 100 = -4.88%
ii) For secondary terminal voltage, use basic expression of regulation
% R = ((E2 - V2 )/E2 ) x 100
.
..
-4.88 = ((125- V2) /125) x 100
...
-6.1 = 125 - V2
.
..
V2 = 131.1 V
It can be seen that for leading p.f. E2 <V2.
Phasor Diagrams for Transformer on Load
Consider a transformer supplying the load as shown in the Fig. 1.
Fig. 1
The various transformer parameters are,
R1 = Primary winding resistance
X1 = Primary leakage reactance
R2 = Secondary winding resistance
X2 = Secondary leakage reactance
15
ZL = Load impedance
I1= Primary current
I2 = Secondary current = IL = Load current
now
1 = o + 2'
where
Io = No load current
I2'= Load component of current decided by the load
= K I2 where K is transformer component
The primary voltage V1 has now three components,
1. -E1, the induced e.m.f. which opposes V1
2. I1 R1, the drop across the resistance, in phase with I1
3. I1 X1, the drop across the reactance, leading I1 by 90o
The phasor diagram for the transformer on load depends on the nature of the load power factor. Let us
consider the various cases of the load power factor.
Unity power factor load, cos2 = 1
As load power factor is unity, the voltage V2 and I2 are in phase. Steps to draw the phasor diagram are,
1. Consider flux as reference
2. E1 lags by 90o. Reverse E1 to get -E1.
3. E1 and E2 are inphase
4. Assume V2 in a particular direction
5. I2 is in phase with V2.
6. Add I2 R2 and I2 X2 to to get E2.
7. Reverse I2 to get I2'.
8. Add Io and I2' to get I1.
9. Add I1 R1 and to -E1 to get V1.
Angle between V1 and I1 is 1 and cos1 is primary power factor. Remember that I 1X1 leads I1 direction
by 90o and I2 X2 leads I2 by 90o as current through inductance lags voltage across inductance by 90 o. The
phasor diagram is shown in the Fig.2
16
17
Losses in a Transformer
1. Losses in a Transformer
In a transformer, there exists two types of losses.
i) The core gets subjected to an alternating flux, causing core losses.
ii) The windings carry currents when transformer is loaded, causing copper losses.
1.1 Core or Iron Losses
Due to alternating flux set up in the magnetic core of the transformer, it undergoes a cycle of
magnetisation and demagnetisation. Due to hysteresis effect there is loss of energy in this process which is
called hysteresis loss.
It is given by,
hysteresis loss = Kh Bm1.67 f v watts
where
Kh = Hysteresis constant depends on material.
Bm = Maximum flux density.
f = Frequency.
v = Volume of the core.
The induced e.m.f. in the core tries to set up eddy currents in the core and hence responsible for the
eddy current losses. The eddy current loss is given by,
Eddy current loss = Ke Bm2 f2 t2 watts/ unit volume
where
Ke = Eddy current constant
t = Thickness of the core
As seen earlier, the flux in the core is almost constant as supply voltage V 1 at rated frequency f is
always constant. Hence the flux density Bm in the core and hence both hysteresis and eddy current losses
are constants at all the loads. Hence the core or iron losses are also called constant losses. The iron losses
are denoted as Pi.
The iron losses are minimized by using high grade core material like silicon steel having very low
hysteresis loop by manufacturing the core in the form of laminations.
1.2 Copper Losses
The copper losses are due to the power wasted in the form of I2 R loss due to the resistances of the
primary and secondary windings. The copper loss depends on the magnitude of the currents flowing
through the windings.
Total Cu loss = I12 R1 + I22 R2 = I12 ( R1 + R2' )= I22 ( R2 +R1' )
= I12 R1e = I22 R2e
The copper looses are denoted as. If the current through the windings is full load current, we get
copper losses at full load. If the load on transformer is half then we get copper losses at half load which are
18
less than full load copper losses. Thus copper losses are called variable losses. For transformer VA rating is
or. As is constant, we can say that copper losses are proportional to the square of the KVA rating.
So, Pcu I2 (KVA)2
Thus for a transformer,
Total losses = Iron losses + Copper losses
= Pi + Pcu
Efficiency of a Transformer
Due to the losses in a transformer, the output power of a transformer is less than the input power
supplied.
...
Power output = Power input - Total losses
...
Power input = Power output + Total losses
= Power output + Pi + Pcu
The efficiency of any device is defined as the ratio of the power output to power input. So for a
transformer the efficiency can be expresses as,
= Power output/power input
...
= Power output/(power output + Pi + Pcu )
Now power output = V2 I2 cos
where
cos = Load power factor
The transformer supplies full load of current I2 and with terminal voltage V2.
Pcu = Copper losses on full load = I22 R2e
...
= (V2 I2 cos 2 )/(V2 I2 cos 2 + Pi + I22 R2e)
But
V2 I2 = VA rating of a transformer
.
..
= (VA rating x cos ) / (VA rating x cos + Pi + I22 R2e)
where n = Fraction by which load power factor lagging, leading and unity the efficiency expression
does not change, and remains same.
Example : A 4 KVA, 200/400 V, 50 Hz, single phase transformer has equivalent resistance referred to
primary as 0.15 Calculate,
i) The total copper losses on full load.
ii) The efficiency while supplying full load at 0.9 p.f. lagging.
iii) The efficiency while supplying half load at 0.8 p.f. leading.
Assume total iron losses equal to 60 W.
19
Fig. 1
The load current at which the efficiency attains maximum value is denoted as I2m and maximum
efficiency is denoted as max.
Let us determine,
1. Condition for maximum efficiency.
2. Load current at which max occurs.
3. KVA supplied at maximum efficiency.
The efficiency is a function of load i.e. load current I 2 assuming cos constant. The secondary
terminal voltage V2 is also assumed constant. So for maximum efficiency,
d /d I2 = 0
Now
= (V2 I2 cos 2 )/(V2 I2 cos 2 + Pi + I22 R2e)
20
...
...
...
(V2 I2 cos 2 + Pi + I22 R2e)(V2 cos 2) - (V2 I2 cos 2)(V2 cos 2 + 2I2 R2e) = 0
Cancelling (V2 cos 2) from both the terms we get,
V2 I2 cos 2 + Pi +I22 R2e - V2 I2 2 - 2I22 R2e = 0
Pi - I22 R2e= 0
Pi = I22 R2e = Pcu
So condition to achieve maximum efficiency is that,
Copper losses = Iron losses
Example : A 250 KVA single phase transformer has iron loss of 1.8 KW. The full load copper loss is 2000
watts. Calculate
i) Efficiency at full load, 0.8 lagging p.f.
ii) KVA supplied at maximum eficiency
iii) Maximum efficiency at 0.8 lagging p.f.
Solution : The given values are,
Pi = 1800 W , (Pcu)F.L. = 2000 W
i)
= 98.135%
ii)
iii)
21
where
Pcu = Pi =1800W
= 98.137%
All Day Efficiency of a Transformer
For a transformer, the efficiency is defined as the ratio of output power to input power. This is its
efficiency. But power efficiency is not the true measure of the performance of some special types of
transformers such as distribution transformers.
Distribution transformer serve residential and commercial loads. The load on such transformers varies
considerably during the period of the day. For most period of the day these transformers are working at 30
to 40 % of full load only or even less than that. But the primary of such transformers is energized at its
rated voltage for 24 hours, to provide continuous supply to the consumer. The core loss which depends on
voltage, takes place continuously for all the loads. But copper loss depends on the load condition. For no
load, copper loss is negligibly small while on full load it is at its rated value. Hence power efficiency can
not give the measure of true efficiency of such transformers. in such transformers, the energy output is
calculated in kilo watt hour (kWh). Then ratio of total energy output to total energy input (output + losses)
is calculated. Such ratio is called energy efficiency or All Day Efficiency of a transformer. Based on this
efficiency, the performance of various distribution transformers is compared. All day efficiency is defined
as,
22
Vo = Rated voltage
Wo = Input power
Io = Input current = no load current
As transformer secondary is open, it is on no load. So current drawn by the primary is no load current
Io. The two components of this no load current are,
Im = Io sin o
Ic = Io cos o
where cos o = No load power factor
And hence power input can be written as,
Wo = Vo Io cos o
The phasor diagram is shown in the Fig. 2.
23
Fig. 2
As secondary is open, I2 = 0. Thus its reflected current on primary is also zero. So we have primary
current I1 =Io. The transformer no load current is always very small, hardly 2 to 4 % of its full load value.
As I2 = 0, secondary copper losses are zero. And I1 = Io is very low hence copper losses on primary are also
very very low. Thus the total copper losses in O.C. test are negligibly small. As against this the input
voltage is rated at rated frequency hence flux density in the core is at its maximum value. Hence iron losses
are at rated voltage. As output power is zero and copper losses are very low, the total input power is used to
supply iron losses. This power is measured by the wattmeter i.e. Wo. Hence the wattmeter in O.C. test gives
iron losses which remain constant for all the loads.
...
Wo = Pi = Iron losses
Calculations : We know that,
Wo = Vo Io cos
cos o = Wo /(Vo Io ) = no load power factor
Once cos o is known we can obtain,
Ic = Io cos o
and
Im = Io sin o
Once Ic and Im are known we can determine exciting circuit parameters as,
Ro = Vo /Ic
and
Xo = Vo /Im
Key Point : The no load power factor cos o is very low hence wattmeter used must be low power factor
type otherwise there might be error in the results. If the meters are connected on secondary and primary is
kept open then from O.C. test we get R o' and Xo' with which we can obtain Ro and Xo knowing the
transformation ratio K.
Short Circuit Test (S.C. Test)
In this test, primary is connected to a.c. supply through variac, ammeter and voltmeter as shown in the
Fig. 3.
24
Now the current flowing through the windings are rated current hence the total copper loss is full load
copper loss. Now the voltage supplied is low which is a small fraction of the rated voltage. The iron losses
are function of applied voltage. So the iron losses in reduced voltage test are very small. Hence the
wattmeter reading is the power loss which is equal to full load copper losses as iron losses are very low.
...
primary is high voltage itself to which supply is given in S.C. test. So in such case test results give us
parameters referred to primary i.e. R1e, Z1e and X1e.
Key point : In short, if meters are connected to primary of transformer in S.C. test, calculations give us R 1e
and Z1e if meters are connected to secondary of transformer in S.C. test calculations give us R2e and Z2e.
1.3 Calculation of Efficiency from O.C. and S.C. Tests
We know that,
From O.C. test, Wo = Pi
From S.C. test, Wsc = (Pcu) F.L.
Thus for any p.f. cos 2 the efficiency can be predetermined. Similarly at any load which is fraction of full
load then also efficiency can be predetermined as,
where
where
Calculation of Regulation
From S.C. test we get the equivalent circuit parameters referred to primary or secondary.
The rated voltages V1, V2 and rated currents (I1) F.L. and (I2) F.L. are known for the given transformer.
Hence the regulation can be determined as,
...
Key Point : Thus regulation at any load and any power factor can be predetermined, without actually
loading the transformer.
26
Example 1 : A 5 KVA, 500/250 V, 50 Hz, single phase transformer gave the following readings,
O.C. Test : 500 V, 1 A, 50 W (L.V. side open)
S.C. Test : 25 V, 10 A, 60 W (L.V. side shorted)
Determine : i) The efficiency on full load, 0.8 lagging p.f.
ii) The voltage regulation on full load, 0.8 leading p.f.
iii) The efficiency on 60% of full load, 0.8 leading p.f.
iv) Draw the equivalent circuit referred to primary and insert all the values in it.
Solution : In both the tests, meters are on H.V. side which is primary of the transformer. Hence the
parameters obtained from test results will be referred to primary.
From O.C. test,
Vo = 500 V, Io = 1 A, Wo= 50 W
..
cos o = Wo/Vo Io = 50/(500x1) = 0.1
...
Ic = Io cos = 1 x 0.1 = 0.1 A
and
Im = Io sin o = 1 x 0.9949 = 0.9949 A
...
Ro =Vo /Ic = 500/0.1 = 5000
and
Xo = Vo/Im = 500/0.9949 = 502.52
and
Wo = Pi= iron losses = 50 W
From S.C. test,
Vsc = 25 V, Isc = 10 A, Wsc = 60 W
.
..
R1e = Wsc /Isc2 = 60/(10)2 = 0.6
Z1e = Vsc /Isc = 25/10 = 2.5
.
..
X1e= (2.52 - 0.62) = 2.4269
(I1) F.L. = VA rating/V1
= (5 x 103 )/500 = 10 A
and
Isc = (I1) F.L.
.
..
Wsc = (Pcu) F.L. = 60 W
i) on full load, cos = 0.8 lagging
.
= - 1.95 %
iii) For 60% of full load, n = 0.6 and cos 2 = 0.8 leading]
...
Pcu = copper loss on new load = n2 x (Pcu) F.L.
= (0.6)2 x 60 = 21.6 W
= 97.103 %
iv) The equivalent circuit referred to primary is shown in the Fig. 4.
27
Fig. 4
Example 2 : The open circuit and short circuit tests on a 10 KVA, 125/250 V, 50 Hz, single phase
transformer gave the following results :
O.C. test : 125 V, 0.6 A, 50 W (on L.V. side)
S.C. test : 15 V, 30 A. 100 W (on H.V. side)
Calculate : i) copper loss on full load
ii) full load efficiency at 0.8 leading p.f.
iii) half load efficiency at 0.8 leading p.f.
iv) regulation at full load, 0.9 leading p.f.
Solution : From O.C. test we can weite,
Wo = Pi = 50 W = Iron loss
From S.C. test we can find the parameters of equivalent circuit. Now S.C. test is conducted on H.V.
side i.e. meters are on H.V. side which is transformer secondary. Hence parameters from S.C. test results
will be referred to secondary.
Vsc = 15 V, Isc = 30 A, Wsc = 100 W
R2e = Wsc/(Isc)2 =10/(30)2 = 0.111
Z1e = Vsc /Isc = 15/30 = 0.5
...
X2e = (Z2e2 - R2e2) = 0.4875
i) Copper loss on full load
(I2) F.L. = VA rating/V2 = (10 x 103)/250 = 40 A
In short circuit test, Isc = 30 A and not equal to full load value 40 A.
Hence Wsc does not give copper loss on full load
...
Wsc = Pcu at 30 A = 100 W
Now
Pcu I2
( Pcu at 30 A)/( Pcu at 40 A) = (30/40) 2
100/( Pcu at 40 A) = 900/1600
Pcu at 40 A = 177.78 W
...
(Pcu) F.L. = 177.78 W
ii) Full load , cos 2 = 0.8
...
28
= 97.69%
iv) Regulation at full load, cos = 0.9 leading
= -1.8015%
Methods of Cooling Transformers
When transformer supplies a load, two types of losses occur inside the transformer. The iron losses
occur in the core while copper losses occur in the windings. The power lost due to these losses appears in
the form of heat. This heat increases the temperature of the transformer.
Key Point : To keep the temperature rise of the transformer within limits, it is necessary to dissipate the
heat developed to the surroundings.
A suitable coolant and cooling method is necessary for each transformer to dissipate the heat,
effectively to the surroundings.
Basically there are two types of transformers, dry type transformers and oil immersed transformers. In
dry type, the heat is taken to the walls of tank and dissipate to the surrounding air through convection. In
oil immersed type, the oil is used as coolant. The entire assembly including core and windings is kept
immersed in a suitable oil. The heat developed is transferred to the walls of tank by convection through oil.
And finally heat is transferred to the surroundings from the tank walls by radiation.
The various cooling methods are designated using letter symbols which depend upon :
i) Cooling medium used and ii) Type of circulation employed
The various coolants used along with their symbols are,
1. Air - A,
2. Gas - G,
3. Synthetic oil - L,
4. Mineral oil - O,
5- Solid insulation - S and 6. Water - W
There are two types of circulations which are,
1. Neutral - N and 2. Forced - F
In natural cooling, the coolant circulating inside the transformer transfers entire heat to the tank walls
from where it is dissipated to the surroundings and transformers gets cooled by natural air circulating
surrounding the tank walls.
In forced cooling, the coolant circulating inside the transformer gets heated as it comes in contact with
windings and core. The coolant partly transfers heat to the tank walls but mainly coolant is taken to the
external heat exchanger where air or water is used in order to dissipate heat of the coolant.
1.1 Cooling Methods by Dry Type Transformers
The cooling methods of dry type transformers are classified as,
1. Air Natural (AN) :
29
This method uses atmospheric air as cooling medium. The natural air surrounding the tank walls is
used to carry away the heat generated, by natural convection. It is used for small voltage transformers. Due
to the available insulating materials like glass and silicon resins now a days, the method can be used for the
transformers upto ratings 1.5 MVA.
2. Air Blast (AB) :
In large transformers, cooling by natural air is inadequate. In such cases, the transformer is located
above the air chamber and a blast of compressed air is forced on core and windings with the help of
blowers or fans. This improves the heat dissipation and hence higher specific loadings are allowed in dry
type transformers. This reduced the size of transformers. The air supply must be property filtered to prevent
accumulation of dust particles.
1.2 Cooling Methods for Oil Immersed Transformers
The oil used as a coolant has following advantages,
1. It is good conductor of heat than air.
2. It has high coefficient of volume expansion. Due to this, adequate circulation is easily obtained.
3. The oil acts as an insulating medium, which increases the insulating strength.
The only limitation of oil immersed transformers is that these transformers can not be used at places
like mines where there are chances of fire hazard.
The various cooling methods used for such oil immersed transformers are classified as,
1. Oil natural (ON) :
The transformer is immersed in oil so heat generated in core and windings is passed on to oil by
conduction. The heated oil transfer heat to the tank wall from where it is taken away to the surrounding air.
The assembly of oil immersed transformer is shown in the Fig.1.
32