NX™ Ups: Ower Vailability
NX™ Ups: Ower Vailability
NX™ Ups: Ower Vailability
NX UPS
10-30kVA
208V, 60Hz
TABLE OF CONTENTS
1.0
GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1.1
1.1.2
Bypass Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Operating Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0
2.1
2.2
2.3
Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4
Alarm Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5
LCD Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6
Navigation Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.7
2.8
2.9
Language Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.10
2.11
2.12
2.13
Opening Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Default Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Help Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Screen Saver Window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
13
14
14
Pop-Up Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.13.1
2.13.2
2.13.3
2.13.4
15
15
15
15
3.0
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1
NX Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.1
3.2
Power Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
UPS Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2.1
3.2.2
Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Verify Switching Between Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3
3.4
3.5
3.6
3.7
Auto Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.8
Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions . . . . . . . . . . 23
i
4.0
OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.1
24
24
24
24
24
24
4.2
4.3
ii
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
Figure 16
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
iii
iv
General Description
1.0
GENERAL DESCRIPTION
1.1
Introduction
Lieberts NX Uninterruptible Power Supply system provides continuous, high-quality AC power to
your business-critical equipment, such as telecommunications and data processing equipment. The
NX UPS supplies power that is free of the disturbances and variations in voltage and frequency common to utility power, which is subject to brownouts, blackouts, surges and sags.
The NX utilizes the latest in high-frequency, double-conversion pulse width modulation (PWM) technology and fully digital controls to enhance its reliability and increase the ease of use.
The standard Liebert NX consists of the UPS and internal batteries in a compact, single cabinet.
As shown in Figure 1, the AC utility source is input at CB1 and the rectifier converts the AC utility
into DC power. The inverter converts that DC power from the utilityor DC power from the batteriesinto AC power for the load. The batteries power the load through the inverter in the event of a
power failure. The utility source can also power the load through the static bypass.
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in
service to the maintenance bypass.
Figure 1
Static Switch
Bypass Input
SW1/C
UPS Output
Contactor
Rectifier
AC Utility Input
CB1
Inverter
Neutral Wire
Discharge
Battery
Charger
Battery
Contactor
SW1/A
Neutral Wire
SW1/B
General Description
1.1.1
Bypass Supplies
The circuit block labeled Static Switch and Contactor in Figure 1 contains an electronically controlled switching circuit that enables the critical load to be connected to either the inverter output or
to a bypass power source via the static bypass line. During normal system operation the load is connected to the inverter and the inverter contactor is closed; but in the event of a UPS overload or
inverter failure, the load is automatically transferred to the static bypass line.
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the
static switch activates, connecting the load to bypass. To achieve this, the inverter output and bypass
supply must be fully synchronized during normal operating conditions. This is achieved through the
inverter control electronics, which make the inverter frequency track that of the static bypass supply,
provided that the bypass remains within an acceptable frequency window.
A manually controlled, maintenance bypass supply is incorporated into the UPS design. It enables the
critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine
maintenance.
NOTE
When the UPS is operating in bypass mode or on maintenance bypass, the connected
equipment is not protected from power failures or surges and sags.
1.1.2
Operating Modes
The UPS is designed to operate as an on-line, double-conversion, reverse-transfer system in the following modes:
Normal Mode
Operating in normal mode, the NX rectifier derives power from a utility AC source and supplies regulated DC power to the inverter, which regenerates precise AC power to supply the connected equipment. The rectifier also uses the utility source power to charge the batteries.
Battery Mode
When utility AC power fails, the NX protects the critical load by instantaneously channeling battery
power to the inverter which continues supporting the critical load without interruption. When utility
power returns and is within acceptable limits, the NX automatically shifts back to Normal mode, with
the rectifier powering the critical load.
Bypass Mode
When the NX is in bypass mode, the load is directly supported by utility power and is without battery
backup protection.
The NXs static transfer switch will shift the load from the inverter to bypass mode without an interruption in AC power if the inverter is synchronous with the bypass and any of the following occurs:
inverter fails
inverter overload capacity is exceeded
inverter is manually turned off by user
NOTE
If the inverter is asynchronous with the bypass, the static switch will transfer the load from the
inverter to the bypass WITH interruption in AC power to the critical load. This interruption
will be less than 15ms (in 50Hz), or less than 13.33ms (in 60Hz). This interruption time may be
altered by modifying the Output transfer interrupt time setting.
General Description
Maintenance Mode
For maintenance or repair, the NX may be operated in maintenance mode. To place the NX in maintenance mode, the load must be transferred to bypass and the inverter must be turned off. When those
conditions are met, the rotary switch may be turned to MAINT and the UPS may be shut down, permitting disconnecting the batteries for maintenance.
CAUTION
WARNING
The internal maintenance bypass must not be used when the UPS system is in 1+1 parallel.
The UPS input and output must be protected with external overcurrent protection devices. In
maintenance mode, the input and output busbars remain energized.
2.0
2.1
The main areas of the control panel are shown below in Figure 2 and detailed in Figure 3.
Mimic Display - view the status of the NX in single-line diagram formatindicators show status
by changing color when ON, flashing or OFF
Liquid Crystal Display (LCD) and Navigation keys - view status and operational data from
the NX in tabular format
Control buttons - turn the NX on or off, silence alarms
Figure 2
Liebert NXb
30KVA-3X3
Mimic display
Main
Bypass
Output
A(AB)
Vphase V
Iphase A
Freq. Hz
Vline V
Liquid Crystal
Display (LCD)
12:30:36
Norm al
B(BC)
120
20.5
50.1
208
0.99
120
20.5
50.1
208
0.99
P. F.
EPO
C(CA)
120
20.5
50.1
208
0.99
INVERTER ON
Control
buttons
INVERTER OFF
01-12 12:28:16
01-12 12:30:06
01-22 12:30:16
?
FAULT CLEAR
Navigation keys
2.1.1
F1
F2
F3
F4
SILENCE ON/OFF
HELP
Figure 3
5 6
8
2003-01-22
Unit #1
Liebert NXb
30KVA-3X3
Main
10
11
12
13
Output
B(BC)
120
20.5
50.1
208
0.99
120
20.5
50.1
208
0.99
P. F.
12:30:36
Norm al
Bypass
A(AB)
Vphase V
Iphase A
Freq. Hz
Vline V
C(CA)
120
20.5
50.1
208
0.99
EPO
INVERTER ON
INVERTER OFF
01-12 12:28:16
01-12 12:30:06
01-22 12:30:16
?
FAULT CLEAR
F1
14
15
16
17
F2
18
F3
F4
19
Mimic indicators
1. Rectifier indicator
2. Battery indicator
3. Bypass indicator
4. Inverter indicator
5. Load indicator
6. Alarm indicator
Control buttons
8. Button cover
9. EPO button
10. INVERTER ON button
11. INVERTER OFF button
12. FAULT CLEAR button
13. SILENCE ON/OFF button
-------------------------------------
---------------------------------------------------
7. Buzzer
SILENCE ON/OFF
HELP
14. LCD
Navigation keys
15. F1
16. F2
17. F3
18. F4
19. Help
2.2
Figure 4
Mimic indicators
1. Rectifier indicator
2. Battery indicator
3. Bypass indicator
4. Inverter indicator
5. Load indicator
6. Alarm indicator
2
1 3 4
5 6
2003-01-22
Unit #1
Liebert NXb
30KVA-3X3
Main
Bypass
A(AB)
Vphase V
Iphase A
Freq. Hz
Vline V
12:30:36
Norm al
120
20.5
50.1
208
Output
B(BC)
120
20.5
50.1
208
EPO
C(CA)
120
20.5
50.1
208
The current operational status of the NX is indicated by the color of the indicatorsgreen, amber or
redand whether they are ON (solid), flashing or OFF. Table 1 provides a guide to interpreting the
various states of the indicators.
Table 1
Indicator
(see Figure 4)
Green
Red
Off
Rectifier is normal, but utility is
abnormal
1. Rectifier
Load on rectifier
2. Battery
Battery or battery
Battery and converter are normal,
converter abnormal* and battery is not discharging
3. Bypass
Load on Bypass
power
Bypass out of
normal range
Bypass Normal
4. Inverter
Inverter fault
5. Load
UPS output on
UPS output
overloaded
UPS no output
6. Alarm
* Battery or battery converter abnormal events include these event messages (see Table 8 in Appendix A): No Battery, Battery Replaced,
Battery Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.
2.3
Control Buttons
The Control Buttons on the front panel may be used to shut down the UPS completely, turn the
inverter on or off, restart the UPS after a fault and silence the alarm, as shown in Figure 5. The
function of each button is described in Table 2.
NOTE
To activate a button properly, press and hold until you hear a short beepabout two seconds.
Figure 5
Liebert NXb
30KVA-3X3
Main
Bypass
A(AB)
Vphase V
Iphase A
Freq. Hz
Vline V
10
Output
B(BC)
120
20.5
50.1
208
0.99
120
20.5
50.1
208
0.99
P. F.
12:30:36
Norm al
EPO
C(CA)
120
20.5
50.1
208
0.99
Control buttons
8. Button cover
9. EPO button
10. INVERTER ON button
11. INVERTER OFF button
12. FAULT CLEAR button
13. SILENCE ON/OFF button
11
12
INVERTER ON
INVERTER OFF
13
01-12 12:28:16
01-12 12:30:06
01-22 12:30:16
?
FAULT CLEAR
F1
Table 2
F2
F3
F4
SILENCE ON/OFF
HELP
Control buttons
Button
(see Figure 5)
2.4
Function
14. EPO
15. INVERTER ON
Press this button to shut down the inverter during operation. The load will be transferred
to static bypass.
After the UPS shuts down due to a fault and the alarm condition has been resolved, press
this button to clear the fault and restart the UPS.
Press this button once to silence the alarm buzzer when an alarm is active. Any new fault
will sound the buzzer again.
If the alarm buzzer is not beeping, press this button to test the alarm sound.
Alarm Buzzer
The alarm buzzer produces three types of sounds:
Single beep - when any Control button is pressed
Single beep repeating every two seconds - the system has a general alarm
Continuous - the system has a serious fault
If the alarm buzzer makes no sound, the system may be operating properly or the alarm may have
been silenced manually.
Figure 6
2003-01-22
Unit #1
Bypass
Output
A(AB)
Alarm
Buzzer
Vphase V
Iphase A
Freq. Hz
Vline V
P. F.
B(BC)
120
20.5
50.1
208
0.99
120
20.5
50.1
208
0.99
12:30:36
Norm al
C(CA)
120
20.5
50.1
208
0.99
01-12 12:28:16
01-12 12:30:06
01 22 12 30 16
EPO
INVERTER ON
INVERTER OFF
2.5
LCD Overview
The LCD on the front panel has five main sections, as shown in Figure 7. Press the F1 key below the
LCD to scroll through these sections.
UPS system information - view UPS name and model, date and time, overall status (see
Table 4).
LCD Menu - choose a category of data items to appear below the menus (see Table 5).
Data and settings - view data items for the selected menu (see Table 5).
Current status messages - check the most recent UPS event and alarm messages (see Table 8
in Appendix A).
Navigation key icons - look at the icon above each navigation key to determine how the key
operates when pressed (see 2.6 - Navigation Keys).
The LCD displays alarm information in real time. After appearing in the current status section of the
LCD, status messages are stored in the history log512 records can be stored and retrieved.
Figure 7
LCD menu
Current status
messages
2004-01-22
Single
Mains
L-N voltage (V)
L-N current (A)
Frequency (Hz)
L-L voltage (A)
Power factor
12:30:36
Normal
Bypass
L1-N/L2
119.8
0.3
59.97
207.1
0.00
Fault reset
Manual turn on
Normal mode
Output
L2-N/L3
119.4
0.5
59.97
206.8
0.00
01-22
01-22
01-22
L3-N/L1
119.4
0.6
59.97
207.1
0.00
10:32
10:32
11:05
?
F1
F2
F3
UPS system
information
F4
HELP
Navigation
key icons
2.6
Navigation Keys
The navigation keys on the front panelF1 through F4 and Helpare used to access the LCD to view
the current status and other information about the NX.
Navigation key icons on the LCD appear above each key to indicate its operation (see Table 3). The
keys are soft keys that can change functions according to the icon.
Use F1 either to move to a different portion of the LCD (shift icon) or to escape to a previous view
(ESC icon).
Use F2 and F3 as cursor keys to move left and right or up and down, depending on the icons displayed above the keys.
Use F4 as an Enter key to confirm a choice.
Use HELP to access help information on the LCD.
Table 3
Key
Functions
Available
F1
F2
F3
Shift
Left
Right
ESC
Exit
2.7
F4
?
Enter
Up
Down
No.
Item Type
1
2
3
Liebert NXb
2002-10-12
12:30:36
030kVA-3x3
5
6
Unit #1
Single
Normal
Warning
Fault
Explanation
UPS name
Current date
Current time
030 means UPS model is 30kVA;
3x3 means 3 by 3 system (three phase input and output)
#1 of 6 Paralleled changed to Unit #1
UPS is configured as a single unit system running in Normal mode
UPS in normal condition, inverter feed load, no warning
UPS has a general alarm
UPS has a serious fault
HELP
Help
2.8
Mains - view utility power input data: voltage, current, frequency and power factor
Bypass - view bypass data: voltage and frequency
Output - view output data: voltage, current, frequency and power factor
Load - view load data: load percent, output current, output power and crest factor (CF)
System - view system data
Battery - view battery characteristicsvoltage, current, temperature, remaining time and capacityand messages when the battery is boost/float charging or disconnected
Records - access the history logdisplays all records in the log (newest records added at end)
Language - select a language for LCD text (choices appear in the native language)
Settings - configure UPS settings: adjust the display contrast, choose a format for date display,
set the date and time, set up the UPS for modem communications (baud rate, address, mode and
phone numbers to dial for alarm notifications) and change the password
Command - start or stop a battery maintenance test, battery capacity test or system test
Version - view firmware versions for the inverter, rectifier and software display board and the
model information for the UPS
Figure 8 shows a menu tree of the options available from the LCD menus.
Figure 8
Menu tree
Mains (input)
Bypass
Output
Load
System
Sout (kVA)
Pout (kW)
Qout (kVAR)
Loadlevel %
Crest factor
Sout (kVA)
Pout (kW)
Qout (kVAR)
Single unit, no
parallel data
Battery
Records
Language
Settings
(history log)
(Choices for
display)
Display contrast
Date format set
Date & time
Comm1 baud rate
Comm2 baud rate
Comm3 baud rate
Communication address
Communication mode
Callback times
Phone No.1
Phone No.2
Phone No.3
Command password
Command
Version
UPS version
UPS model
2.9
Language Selection
The LCD menus and data display is available in
12 languages. To select a different language:
From the main menu, press the F1 (shift) key
to move the cursor to the menu at the top of
the screen.
Press F2 and F3 (left and right arrows) as
needed to select the Language menu.
Press F1 (shift) to move the cursor to the data
and settings area of the LCD.
Use F2 and F3 (up and down) to select the
required language.
Press the F4 (enter) key to accept the language
selection.
Return to the main menu by repeatedly pressing F1 (ESC) as needed; all text on the LCD
will now be displayed in the selected language.
2.10
Liebert NXb
30kVA-3X3
2004-01-22
Single
Battery
Records
ENGLISH
FRANCAIS
NEDERLANDS
POLSKI
ESPAOL
Fault reset
Manual turn on
Normal mode
12:30:36
Normal
Language
DEUTSCH
ITALIANO
SVENSKA
PORTUGUS
01-22
01-22
01-22
10:32
10:32
11:05
?
F1
F2
F3
F4
HELP
10
Liebert NXb
30kVA-3X3
2004-01-22
Single
Records
Language
12:30:36
Normal
Settings
Display contrast
Date format set
D/M/Y
Date & time
01-22-2004
M/D/Y
Y/M/D
M/D/Y
12:30:36
Fault reset
Manual turn on
Normal mode
01-22
01-22
01-22
10:32
10:32
11:05
?
F1
F2
F3
F4
HELP
Table 5
Menu Type
Mains
(input)
Bypass
Output
Load
System
Battery
Records
Language
Settings
Explanation
Phase voltage
Phase current
Input frequency
Line-line voltage
Power factor
Phase voltage
Bypass frequency
Line-line voltage
Phase voltage
Phase current
Input frequency
Line-line voltage
Power factor
Sout: Apparent power
Pout: Active power
Qout: Reactive power
The percent of the UPS rating load
Output current Crest Factor
Sout: Apparent power
Pout: Active power
Qout: Reactive power
When configured as a single unit, UPS has only native load, no system load.
Battery bus voltage
Battery bus current
Internal battery temperature C
Battery run time remaining
Percentage of battery life remaining
Battery is boost charging
Battery is float charging
Battery is not connected
Displays all records in the history log
User may select any of 12 languages for LCD text.
Adjust the LCD display contrast
Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D
Set the date and time
Communication baud rate setting for Intellislot 1
Communication baud rate setting for Intellislot 2
Communication baud rate setting for Intellislot 3
This setting is applicable to RS485 communication mode
Communication Mode Setting
When Intellislot 1 Communication mode is Modem, this parameter sets the
number of times a number is redialed to send an alarm notification.
Callback times
Phone No.1
Phone No.2
Phone No.3
Command password
11
Table 5
Menu Type
Explanation
Stop testing
Version
UPS version
UPS model
2.11
This test performs a partial discharge of the battery to obtain a rough estimate
of the battery capacity. Load must be between 20% and 80%.
This test performs a full discharge of the battery to obtain a precise measure of
the battery capacity. Load must be between 20% and 80%.
This is a self-test of the UPS. When the user activates this function, a pop-up
window appears about 5 seconds later to show the results.
Figure 9
2004-01-22
Single
System
Battery
Bypass abnormal
Records
01-22-2004
01-22-2004
09:57:13
10:02:16
01-22-2004
01-22-2004
09:57:13
10:02:21
01-22-2004
01-22-2004
09:57:14
10:02:14
Inverter asynchronous
Mains freq. abnormal
Current status
messages
12:30:36
Normal
Fault reset
Manual turn on
Normal mode
01-22
01-22
01-22
History log
(records menu)
10:32
10:32
11:05
?
F1
F2
F3
F4
HELP
See Table 8 in Appendix A for a complete list of status messages, along with a description and any
recommended actions.
12
2.12
F1
F2
F3
HELP
F4
2004-01-22
Single
Mains
L-N voltage (V)
L-N current (A)
Frequency (Hz)
L-L voltage (A)
Power factor
12:30:36
Normal
Bypass
L1-N/L2
119.8
0.3
59.97
207.1
0.00
Fault reset
Manual turn on
Normal mode
Output
L2-N/L3
119.4
0.5
59.97
206.8
0.00
01-22
01-22
01-22
L3-N/L1
119.4
0.6
59.97
207.1
0.00
10:32
10:32
11:05
?
F1
F2
F3
13
F4
HELP
Help information
Select the current record window
Select the previous menu item
Q3
Q2
Q5
Q1
F1
F2
F3
F4
HELP
2004-01-22
Single
12:30:36
Normal
F2
F3
14
F4
HELP
2.13
Pop-Up Windows
Pop-up prompt windows appear when the user must confirm a choice or perform an operation. This
section describes the pop-up windows.
To confirm the choice and begin the battery capacity test, press
the F4 (Enter) key and the pop-up window disappears.
To cancel the test, press the F1 (ESC) key. The pop-up window disappears.
NOTE
For a battery capacity test to function properly, the load must be between 20% and 80%.
15
Operating Instructions
3.0
OPERATING INSTRUCTIONS
3.1
NX Operating Modes
The NX can operate in any of four modes, as shown in Table 6. This section provides instructions on
switching between modes, resetting the UPS, switching the inverter On and Off and performing other
operations.
Table 6
Operating
Mode
Rotary Switch
Position
Normal
Operation
NORMAL
MAINT
The UPS is shut down but the load is connected to utility power via the
Maintenance Bypass Supply line.
NOTE: The load is not protected against disturbances in AC input power in this
mode.
On Test
TEST
No load power is supplied by the UPS. The load is connected to utility power
via the Maintenance Bypass Supply line.
NOTE: The load is not protected against disturbances in AC input power in this
mode.
On Static
Bypass
BYPASS
or
NORMAL
The load power is supplied through the static bypass line. This may be
considered as a temporary mode during load transfers between inverter and
maintenance bypass or supply under abnormal operating conditions.
On Maintenance
Bypass
Description
NOTE
1. The user controls and indicators mentioned in these procedures are identified in 2.0 Operator Control and Display Panel.
2. The audible alarm may sound at various points during these procedures. It can be canceled
at any time by pressing the SILENCE ON/OFF push button.
NOTE
This unit refers to some modes and conditions that are set or adjusted using proprietary service
software. To take advantage of all the available features for the NX, the unit must be
commissioned by a Liebert factory-trained service engineer.
16
Operating Instructions
3.1.1
Power Switches
The UPS can be isolated by means of power switches, mounted inside the cabinet and accessible after
opening the front door.
The location of the UPS power switches is shown in Figure 14.
CB1 - Utility
Connection
Inside the door,
left side
SW1 - Rotary Switch
Inside the door, near
the center (above the
batteries)
Rotary
switch
position
OUTPUT
(SW1-A)
BYPASS
(SW1-C)
NORMAL
BYPASS
TEST
MAINT
MAINT
(SW1-D)
NEUTRAL
(SW1-B)
NOTE
Do NOT turn the rotary switch too fast. Allow the rotary switch to stay in each position at least
three seconds before turning it to the next position.
17
Operating Instructions
3.2
UPS Start-Up
The NX must be fully installed and commissioned before startup, and external power isolators must
be closed. Once those general conditions are met, the UPS may be started.
3.2.1
Start-Up Procedure
To start the UPS from a fully powered-down condition:
1. Open the UPS door to gain access to the main power switches.
WARNING
CAUTION
Do not operate the rotary switch too fast. Always wait at least three seconds when rotating
the switch from one position to another.
2. Close CB1.
3. Turn the rotary switch to TEST.
The bypass contactor (M2) closes automatically and the LCD begins to show start-up screens.
The Rectifier indicator flashes green while the rectifier is starting up. It stops flashing and
becomes solid green about 30 seconds after the rectifier enters the normal operation state.
After initialization, the bypass static switch closes.
Because output switch SW1-A is still open, the UPS
channels power through Maintenance Bypass Supply
line (SW1-D). The bypass indicator extinguishes, provided that the bypass is normal.
The opening display is shown in the figure at right.
The UPS Mimic display indicators will be:
Indicator
State
Rectifier indicator
Off
Battery indicator
Off
Bypass indicator
Off
Inverter indicator
Off
Load indicator
Off
Alarm indicator
Off
F1
WARNING
F2
F3
F4
Do NOT turn the rotary switch until the rectifier indicator stops flashing green.
18
HELP
Operating Instructions
Indicator
State
Rectifier indicator
Green
Battery indicator
Off
Bypass indicator
Green
Inverter indicator
Off
Load indicator
Green
Alarm indicator
Amber
The maintenance switch SW1-D opens and output switch SW1-A closes. The UPS powers from
static bypass instead of from maintenance bypass. The bypass and load indicators turn on. The
design of the rotary switch ensures uninterrupted output.
5. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds.
The inverter will start and the inverter indicator will flash green. After the inverter is ready, the
UPS transfers from bypass to inverter, the bypass indicator turns off and the inverter and load
indicators turn on.
The UPS is operating normally. The UPS Mimic display indicators will:
3.2.2
Indicator
State
Rectifier indicator
Green
Battery indicator
Off
Bypass indicator
Off
Inverter indicator
Green
Output indicator
Green
Alarm indicator
Green
19
Operating Instructions
3.3
CAUTION
Before performing this operation, read the messages on the LCD to be sure that bypass supply
is regular and the inverter is synchronous with it. If those conditions are not present, there is
a risk of a short interruption in powering the load.
3.4
WARNING
WARNING
CAUTION
Even with the UPS in maintenance bypass and Off, portions of the unit are still energized.
Service is to be performed by qualified personnel only.
The load equipment is not protected from normal supply aberrations when operating in the
maintenance bypass mode.
WARNING
20
Operating Instructions
3.5
WARNING
21
Operating Instructions
Figure 15 Typical configuration for single UPS with external Maintenance Bypass Cabinet
Input distribution
QinUPS
QINextBYP
Supplied by others
Bypass mains
supply
Input mains
supply
U3/V3/W3
U1/V1/W1
Battery
circuit
breaker 1
UPS
Q1
Rectifier
Battery 1
CB
X1
Inverter
J10
Q2
Static
switch
Y
Ext bypass
mains
EXT BYP
Q5
Q3BP
EXT SW OUT
U2/V2/W2/N2
UPS
output
QoutUPS
Maintenance
Bypass Cabinet
QextBYP
To load
22
Operating Instructions
3.6
3.7
Auto Restart
When main and bypass sources fail due to utility power failure, the system will operate on battery
continuously until shut down due to battery end of discharge (EOD).
When Auto Recovery after EOD Enabling is enabled, the UPS will enable output power after the
main or bypass source becomes normal, or after the user pushes the Fault Reset button. After the
time set in Auto Recovery after EOD delay time has expired and the rectifier is ready, the inverter
will be turned on automatically. The UPS will be in normal mode.
When Auto Recovery after EOD Enabling is disabled, the UPS will not turn back oneven if the
main or bypass source recoversuntil the user pushes the Fault Reset button.
The default setting for Auto Recovery after EOD Enabling is disabled, and the default setting for
Auto Recovery after EOD delay time is 10 minutes.
3.8
Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions
Once all appropriate measures have been taken to correct the problem indicated by the alarm message appearing on the operator control panel display, carry out this procedure to restore the UPS to
regular operation following an EPO action or for the following reasons: Inverter Over temperature,
Cut-off Overload, Battery Over voltage, excessive switching (BYP: XFER COUNT BLOCK), etc.
When the user confirms that the fault is cleared:
1. Press the FAULT CLEAR button to let the system exit the emergency off state.
NOTE
The rectifier will start again, the battery contactor will close and the bypass will begin to power
the load. The Rectifier indicator (1) flashes while the rectifier is starting up. When the rectifier
enters the normal operation state (about 30 seconds), the rectifier indicator turns green.
2. Press the INVERTER ON button (10) on the right side of the operator control panel for longer
than 2 seconds.
NOTE
The rectifier will be turned on automatically when the over temperature fault disappears at
5 minutes after the disappearance of overtemperature signals.
23
Options
4.0
OPTIONS
Several items of optional equipment are available for connection to the NX UPS.
4.1
4.1.1
4.1.2
4.1.3
Power Output
The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to
12V. The maximum current is 500mA.
4.1.4
RS232 Interface
There are two RS232 interface at the monitor board: BACKGROUND 232-1 and BACKGROUND
232-2.
BACKGROUND 232-1 can be connected to Modem for remote monitor. 232-1 and 485_1 share the
same one serial communication resource (SCI 1), they can not be connect to monitor device at the
same time.
BACKGROUND 232-2 can not be connected to Modem. It shares the same one serial communication
resource (SCI 2) with Intellislot 2. They can not be connected to monitor device at the same time.
4.1.5
CAUTION
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should
be segregated and run separate from all other power cables, by 25mm where applicable.
RS485 Interface
There are two RS485 interface at the X4 slot: 485_1 and 485_2. 485_1 can be used only when the UPS
is in Multipoint to point mode. The two parallel UPS modules 485_1 can be connected together to
background. 485_1 and 232-1 share the same one serial communication resource (SCI 1), they can not
be connected to monitor device at the same time. If not on parallel monitor mode, 485_1 is disabled.
485_2 shares the same one serial communication resource (SCI 3) with Intellislot 3. They can not be
connected to monitor device at the same time.
4.1.6
Intellislot
The NX UPS contains three Intellislot communication slots to allow the operator to field install
optional communication cards. Each bus can independently communicate via Liebert ESP2 protocol,
and cards that translate the information on the bus to the specific protocol needed: Modbus / Jbus,
SNMP, IGMnet and serial port card. But Intellislot 1 and RS232 use one common bus; only one of
them can be used at the same time. The Intellislot communication slots are designed to provide simple installation where all electrical connections are made via a 34 pin edge card connector. These
option cards allow the UPS to communicate via multiple communication methods to monitoring application interfaces.
24
Options
4.2
4.3
CAUTION
In LBS configuration, both units must be supplied from the same utility source.
CAUTION
Before attempting to start the UPS without utility power present, ensure that the batteries
are fully chargedover 2.1V per celland will supply adequate run time to the load.
SCI Channel 1#
RS232 Modem
Compatible Design
RS485/232
Converter
RS232/Modem
RS232
RS485 Bus-1/2
SCI Channel 3#
RS485/232
Converter
SCI Channel 2#
RS232
RS232
RS232
DB9
Intellislot-1
Phoenix
4 Pin
Intellislot-3
Intellislot-2
DB9
Dry Contactor
25
Options
26
The CAN communication between different UPSs within a parallel system fails.
Suggested Action
1. Check if there are some UPS not powered on in the parallel system. If so, power on
these UPSs and check if the alarm disappears.
2. Compare the actual number of UPS in the parallel system with the setting number of
any UPS via the configuration software. If they are different, change the setting number
via the configuration software.
3. If they are coincident,
a. Check the connection status of parallel cables.
b. Replace the parallel board and try again.
Battery Overtemp.
Ambient Overtemp.
Battery Fault
Battery Replaced
Before the end of discharging, battery under-voltage pre-warning should occur. After this
pre-warning, battery should have the capacity for 3 minutes discharging with full load. The
time is user configured from 3 to 60 minutes.
Suggested Action
Shut down the load in time
10
Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown.
Suggested Action
Check the input line-to-neutral voltage amplitude of rectifier.
11
Mains Undervoltage
12
13
14
Rectifier Fault
Rectifier Fault
15
The temperature of rectifier inductor is too high to keep the rectifier running.
Suggested Action
Check the ambient temperature and ventilation
27
Table 8
No.
16
Rectifier Overtemp.
The temperature of heat sink is too high to keep the rectifier running.
Suggested Action
The UPS can recover automatically. Check the environment and ventilation.
17
Balancer Fault
The difference voltage between the bus+ and bus- is above 50V.
Balancer: Balance Circuit
18
The IGBT current for balance circuit is over 3 times of rated current.
19
The difference between the output voltage of battery converter and the preset value is over
limit.
21
22
Batt. Converter
Overtemp.
23
Charger Fault
24
25
26
27
Rectifier Overcurrent
28
This alarm is triggered by an inverter software routine when the amplitude or frequency of
bypass voltage is beyond the normal range.
The amplitude threshold is fixed for positive and negative 10% rating. The frequency
threshold is set via the configuration software (2 Hz for default).
This alarm automatically resets once the bypass voltage goes normal.
Suggested Action
1. First verify that the bypass voltage and frequency displayed on the panel is within the
selected range. Note here the rated voltage and frequency are specified by Output
voltage level and Output frequency level respectively. And once this alarm occurs,
there is a hysteresis loop of 5V in phase voltage and 0.1Hz in frequency to recover.
2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and
frequency presented to the UPS. Check the external supply if it is found to be faulty. If
the utility is likely to trigger this alarm frequently, the alarm can be neglected through
the configuration software according to customers requirement. Or the bypass
frequency synchronization range can be changed a little larger through the
configuration software according to the customers agreement.
3. If Step 2 shows the displayed bypass voltage and frequency are quite different from the
actual bypass voltage and frequency, measure the signal to the U1 board. If this is
correct then replace the U1 Control Board; else check the wiring connections to M4
measure board, and if this is correct replace the M4 measure board.
20
29
28
Table 8
No.
30
31
32
Bypass Abnormal
This alarm is triggered by an inverter software routine when the amplitude or frequency of
bypass voltage exceeds the limit.
The amplitude and frequency limit of bypass voltage are set via the configuration software
(By default, +15% as maximum amplitude, -20% as minimum amplitude, 10% as
frequency range).
This alarm will also be activated by Bypass disconnect open, Bypass phase reverse or
Mains neutral lost alarms.
This alarm automatically resets once the bypass voltage goes normal.
Suggested Action
First check if there are some relevant alarms such as Bypass disconnect open, Bypass
phase reverse and Mains neutral lost. If they appear, solve them first.
1. Then verify that the bypass voltage and frequency displayed on the panel is within the
bypass limit. Note here the rated voltage and frequency are specified by Output
voltage level and Output frequency level respectively. And once this alarm occurs,
there is a hysteresis loop of 5V in phase voltage and 0.1Hz in frequency to recover.
2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and
frequency presented to the UPS. Check the external bypass supply if it is found to be
faulty. If the utility is likely to trigger this alarm frequently, the bypass limit can be
changed a little larger through the configuration software according to the customers
agreement.
3. If Step 2 shows the displayed bypass voltage and frequency are quite different from the
actual bypass voltage and frequency, measure the signal to the U1 control board. If this
is correct then replace the U1 control Board; else check the wiring connections to M4
measure board, and if this is correct replace the M4 measure board.
Inverter Asynchronous
This alarm is triggered by an inverter software routine when the inverter and bypass
waveforms are misaligned by more than 6 degrees in phase. This alarm resets
automatically once the condition is no longer true.
Suggested Action
1. First check if the alarm Bypass unable to trace or Bypass abnormal occurs. If so,
solve it first.
2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to
verify and seek any possible measurements.
3. Verify the stability of the bypass frequency. If the stability is not ideal, try to increase the
inverter slew-rate via the configuration software in single unit system. Or ask the
customer to verify and seek any possible measurements in a parallel system.
Inverter Fault
This alarm is triggered by an inverter software routine when the inverter voltage or the
output voltage satisfies one of the following conditions:
1. The output voltage comes with a DC waveform above 390V.
2. The inverter voltage goes above 112.5% rating or below 75% rating for 3 cycles when
the inverter current is less than 70% rating.
3. The inverter voltage goes above 112.5% rating or below 87.5% rating for 1 second.
Suggested Action
First verify whether this alarm is Inverter voltage fault or Inverter bridge short through
fault by pressing the RESET button on panel.
1. If the fault cannot be cleared, this alarm is brought by inverter bridge short through.
a. Power off the UPS, check the inverter IGBTs, also check the gate drivers. If there
are some errors, repair or replace them.
b. If the IGBTs are OK, then power on the UPS, and try to turn on the inverter without
load.
If the fault appears again, check the inverter voltage signals to the U1 control board from
the M4 measure board, and repair or replace as necessary.
If the fault disappears without load, check the loading conditions. Verify if there were great
impact or half-cycle loading conditions.
2. If the fault can be cleared, this alarm is brought by inverter voltage fault . Try to turn on
the inverter again without load, verify that the inverter voltage is at the normal value.
a. If the fault appears again, verify that the output voltage and regulation are set
appropriately via the configuration software. Reprogram them if necessary. Check
the inverter voltage signals to the U1 control board from the M4 measure board, and
repair or replace as necessary.
b. If the fault disappears without load, check the loading conditions. Verify if there were
great impact or half-cycle loading conditions.
29
Table 8
No.
33
34
35
36
The temperature of the output filter inductor is too high to keep inverter running.
This alarm is triggered by the signal from a thermostat mounted in the output filter inductor.
The UPS would recover automatically after a 5 minute delay from the disappearance of the
over temperature signal.
Suggested Action
1. If the over temperature condition is true then check for and verify:
a. high ambient air temperature.
b. blocked cooling airway.
c. any fan failure.
d. prolonged inverter overload.
2. If the over temperature condition is not true, then check the connection of thermostats
and wiring from M4 measure brd to U1 control board. Replace or repair it if any opencircuit error is found. If no open-circuit error is found, then replace the U1 board.
Inverter Overtemp.
The temperature of the inverter heat sink is too high to keep inverter running.
This alarm is triggered by the signal from a temperature monitoring thermostat on the
inverter bridge heat sink.
The UPS will recover automatically after a 5 minute delay from the disappearance of the
over temperature signal.
Suggested Action
1. If the over temperature condition is true then check for and verify:
a. high ambient air temperature.
b. blocked cooling airway.
c. any fan failure.
d. prolonged inverter overload.
2. If the over temperature condition is not true, then check the connection of thermostats
and wiring from M4 measure brd to U1 control brd. Replace or repair it if any opencircuit error is found. If no open-circuit error is found, then replace the U1 board.
Fan Fault
At least one of the cooling fans fails. This alarm is triggered when the fan fault signal is a
pulse whose duty is greater than 2/3 when bypass or inverter is in power supply.
It is just an alarm and nothing is activated. This alarm resets automatically once the
condition is no longer true.
Suggested Action
Confirm that the alarm is true by finding out which fan is not running correctly.
1. If the alarm is true, replace the abnormal fans.
2. If the alarm is false:
a. check the fan fault signal from M4 measure board and U1 control board.
b. replace the U1 board or M4 board as required.
At least one of the static switches of inverter side is open or short circuit. This fault is locked
until power off.
This fault is triggered when the inverter voltage or the output voltage satisfies one of the
following conditions:
1. The output voltage goes above 120V when the inverter is on with bypass and output
disconnect open, bypass SCR and inverter SCR drive invalid. This condition set an
inverter STS short-circuit fault.
2. The inverter voltage goes above 120V when the inverter is off. If the inverter current
goes above 10% rating at the same time, the confirm time would be shorten. This
condition set an inverter STS short-circuit fault.
3. The inverter voltage goes below 80V with inverter STS drive valid. This condition set an
inverter STS open-circuit fault.
Suggested Action
1. Power off the UPS (with maintenance bypass closed). Check the inverter SCRs for
open circuit and short circuit. Also check the gate drivers.
2. If the SCRs are OK then check the output voltage, inverter voltage and current signal
inputs to U1 control board via the M4 measure board, and repair or replace them as
necessary.
3. Sometimes this fault can be triggered by floating output voltage due to the absence of
output EMI board. Verify the displayed output voltage and the status of output EMI
board.
30
Table 8
No.
37
38
39
40
At least one of the static switches of bypass side is open or short circuit. This fault is locked
until power off.
This fault is triggered when the output voltage or the output current satisfies one of the
following conditions:
1. The output voltage goes above 120V with bypass disconnect closed, output disconnect
open, bypass SCR and inverter SCR drive invalid. This condition set a bypass STS
short-circuit fault.
2. The difference between output current and inverter current is greater than 20% rating
(or the bypass current transformers output a valid signal when the bypass is lost) and
the difference between output voltage and inverter voltage of the corresponding phase
is less than 5V when the bypass disconnect is closed, and the inverter STS drive is
valid. This condition set a bypass STS short-circuit fault.
3. The output voltage goes below 80V with bypass STS drive valid. This condition set a
bypass STS open-circuit fault.
Suggested Action
1. Power off the UPS (with maintenance bypass closed). Check the bypass SCR for open
circuit and short circuit. Also check the gate drivers.
2. If the SCRs are OK then check the output voltage and current, inverter voltage, inverter
and output current signals to U1 control board via the M4 measure board, and repair or
replace them as necessary. Check the signal from the bypass current transformers.
3. Sometimes this fault can be triggered by floating output voltage due to the absence of
output EMI board. Verify the displayed output voltage and the status of output EMI
board.
Operation Invalid
At least one of the output fuses is blown. This alarm is triggered by a detection circuit on
the M4 measure board, which monitors the status of the output fuses.
Suggested Action
Confirm that the alarm is true by checking the state of the mechanical pin on the fuse body
and then carry out a continuity check of the fuse itself using an ohmmeter.
1. If the fault is true
a. Replace the fuse by a new one with same rating.
b. Before restarting inverter, carry out a full check of the inverter components and
circuits, particularly short SCRs, pulse-by-pulse current limiting circuit on M4
measure board.
c. Investigate that if the user has added a impact load to the UPS.
2. If the fault is false:
a. Check the fuse error detection circuit on M4 board.
b. Check the wiring from the M4 measure board to the U1 control board.
c. Replace the U1 and/or M4 board as required.
31
Table 8
No.
41
42
43
44
Control Power 2 is abnormal or lost. This alarm is triggered by a detection circuit on the M4
measure board, which monitors the second control power board.
Suggested Action
Confirm that the alarm is true by checking the output voltage of the second control power
board.
1. If the alarm is true, check and verify the input voltage and input cables of the control
power board. If they are OK, replace the second control power board.
2. If the alarm is false:
a. Check the fault signal from the second control power board to the M4 board and
which from the M4 measure board to the U1 control board.
b. Check the wiring from the second control power board to the M4 board and which
from the M4 board to the U1 board.
c. Replace the control power board, U1 and/or M4 board as required.
The UPS is confirmed to be overload when the load arises above 105% nominal rating.
The alarm automatically resets once the overload condition is removed.
Suggested Action
Confirm that the alarm is true by checking the load percent indicated on the LCD panel to
determine which phase is being overloaded.
1. If the alarm is true, measure the actual output current to verify that the indications are
valid. Disconnect unnecessary load and ensure the safety. In a parallel system, a
severe load sharing error can also leads to the alarm.
2. If the alarm is not true:
a. Verify that the correct UPS kVA rating has been set via the configuration software.
b. Replace the U1 control board.
The UPS parallel system is confirmed to overload when the total load arises above 105%
nominal rating for the set basic number of UPSs. The alarm automatically resets once the
overload condition is removed.
Suggested Action
Confirm that the alarm is true by checking the system load percent indicated on the LCD
panel to determine which phase is being overloaded.
1. If the alarm is true, measure the actual output current to verify that the indications are
valid. Disconnect unnecessary load and ensure the safety. In a parallel system, a
severe load sharing error can also leads to the alarm.
2. If the alarm is not true:
a. Verify that the correct UPS kVA rating has been set via the configuration software.
b. Check the setting of basic number of UPS via the configuration software. If it is
different from the actual system, power up the rest of the UPSs, or change the
setting number via the configuration software.
c. Check the M5 auxiliary power board and the parallel cables for output current
detection.
d. Replace the M5 and/ or U1 control board as required.
32
Table 8
No.
45
1. When inverter overload times out and bypass is abnormal, the inverter will turn off and
the output will shutdown.
2. When bypass goes abnormal during the 5 minutes span just after an overload transfer
from inverter side.
3. When bypass goes abnormal when the bypass is feeding the load and an overload
alarm occurs.
Note: This alarm usually occurs with the accompany of Bypass abnormal.
Suggested Action
Confirm that the alarm is genuine by checking the amplitude and frequency of bypass
voltage.
Byp. Abnormal Shutdown
1. If the alarm is genuine
a. check the wiring of bypass circuit.
b. look over the current and history record to look for other relative alarm such as unit
over load, unit over load timeout, transfer time-out. Follow relevant procedure to
deal with the alarms.
2. If the alarm is not genuine
a. verify that the bypass up and down limits programmed via the configuration
software is appropriate and reprogram if necessary.
b. measure the signal to the U1 board. If this is correct then replace the U1 control
Board; else replace the M4 measure board.
46
Reserved
The current of inverter IGBT is over limit. This alarm is triggered by a hardware signal
emitted by the gate driving chip.
Suggested Action
1. Check for a reasonable cause for the fault by examining for shorts/burns, etc., in the:
a. output filter capacitors and associated wiring.
b. inverter IGBTs and associated cabling.
2. If no reasonable cause is found then:
a. if the fault signal is illuminated on the M4 board determine the cause of the
erroneous overload detection and repair/replace as necessary.
b. if the fault signal to the U1 board is OK, then replace the U1 control board.
Restart the inverter after RESET the fault.
48
49
Transfer Time-out
The load is on bypass because the output overload transfer and retransfer is clamped to
the set times during the current hour.
The system will transfer back to inverter side within an hour.
Suggested Action
1. Verify that the transfer times programmed via the configuration software is appropriate
and reprogram if necessary.
2. There should be other relative fault present in the history record such as unit over
load, unit over load timeout. Follow relevant procedure to deal with the alarms.
3. Suggest user do not apply frequent overload to make the UPS work in bypass mode
without protection.
UPS working within a parallel system are not sharing load current correctly.
Suggested Action
1. Verify the power connection of output during the parallel system.
2. Verify the connection status of parallel cables.
3. Verify the waveform or stability of bypass voltage.
4. Check if there are any errors on the parallel board, change it as necessary.
47
50
51
33
Table 8
No.
DC Bus Abnormal
System Transfer
The whole paralleled UPS system transferred to bypass at the same time. This message
will appear on the UPS which passive transfer to bypass.
Suggested Action
If the parallel operation system transfers to bypass mode, and the operation condition
enables, all the UPS modules can recover to normal mode synchronously.
Rectifier, inverter and battery converter were shutdown because DC bus voltage is too
high.
Suggested Action
Check whether there is a fault in rectifier side. If no, then check whether overload occurs.
Restart the inverter after RESET the fault.
57
58
Inverter DC Offset
59
LBS Active
60
61
Parallel ID Error
62
63
Balancer overtemp.
64
Protocol version between monitor unit and DSP unit is not compatible
Suggested Action
Please check monitor, rectifier and inverter firmware version.
65
66
Manual Turn On
67
68
EPO
69
Transfer Confirm
70
Transfer Cancel
52
53
54
55
56
34
Table 8
No.
71
72
73
Fault Reset
Fault Rest
74
Alarm Silence
Alarm Silence
75
Turn On Fail
Turn On Fail
76
Alarm Reset
77
Bypass Mode
78
Normal Mode
79
Battery Mode
80
Joint Mode
81
UPS Shutdown
82
Output Disabled
83
Generator Connected
84
85
86
87
88
Reserved
89
90
91
92
93
94
Bypass Disconnect
Closed
95
96
97
98
99
Battery Reverse
100
No Battery
101
Auto start
After UPS was shutdown at EOD, inverter auto starts when utility restore.
102
BCB closed
103
BCB open
104
105
106
Battery Discharging
Battery is discharging
107
108
109
110
111
Inverter in Setting
112
Rectifier in Setting
35
36
POWER AVAILABILITY
NX UPS
The Company Behind the Products
With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
developed a complete range of support and
protection systems for sensitive electronics:
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114